I N S T A L L A T I O N I N S T R U C T I O N S

EZ-Path® Multi-Gang Wall Bracket System


(Part Numbers: EZP544W, EZP544WD, EZP644W, & EZP644WD)

EZP544W Parts Included EZP544WD Parts Included EZP644W Parts Included EZP644WD Parts Included

x4
x8 x12
x4 x8
x4 x4
x4 x4 x4 x4

x4 x4
x4 x4 x4

Parts Included (not to scale) *Refer to page 2 for assembled configurations

1 2 3

Cut hole in the wall. Refer to table A for opening Connect one to six pathways together dependent Align intumescent tape/gasket (provided) with
requirements. upon project requirements. Align pathways, insert bottom edge of flat, solid surface of each wall
hook into eye window, press down firmly to connect bracket. Peel back paper to expose pressure
pathways. sensitive adhesive and adhere gasketing to each
bracket prior to installation

4 5 TABLE A: OPENING REQUIREMENTS


Bracket Pathways Height Length

EZP544W 1 4-5/8" (118 mm) 4-1/8" (105 mm)

EZP544W 2 4-5/8" (118 mm) 8-1/8" (206 mm)

Single Row
EZP544W 3 4-5/8" (118 mm) 12-1/8" (308 mm)

EZP544W 4 4-5/8" (118 mm) 16-1/8" (410 mm)

EZP544W 5 4-5/8" (118 mm) 20-1/8" (511 mm)

EZP644W 6 4-5/8" (118 mm) 24-1/8" (613 mm)

Loosely fasten brackets using screws and nuts Fasten brackets to the wall by inserting EZP544WD 2 9-1/4" (236 mm) 4-1/8" (105 mm)
provided. Slide brackets over pathways until appropriate fasteners (not provided) into EZP544WD 4 9-1/4" (236 mm) 8-1/8" (206 mm)
Double Row

gasketed flat surfaces of brackets rests firmly predrilled holes, For gypsum board/stud
EZP544WD 6 9-1/4" (236 mm) 12-1/8" (308 mm)
against wall surface. Tighten the screws and wall assemblies, use minimum 1/8” (3.2
nuts connecting brackets and set screws in short mm) diameter Type G steel screws (NOTE: EZP544WD 8 9-1/4" (236 mm) 16-1/8" (410 mm)
brackets to secure pathways in place. Brackets must be secured to wall framing
EZP544WD 10 9-1/4" (236 mm) 20-1/8" (511 mm)
members). For concrete or concrete block
walls, use minimum 3/16” (4.8 mm) diameter EZP644WD 12 9-1/4" (236 mm) 24-1/8" (613 mm)
steel concrete screws.

Note: For more information on firestop installation, refer to ASTM E3157.


Specified Technologies Inc.
Page 1 of 2
Somerville, NJ 08876 USA
Warranty: www.stifirestop.com/legal/warranty
T: (800) 992-1180
Made in USA • Printed in USA
F: (908) 526-9623 ZIS1051 3579
www.stifirestop.com
I N S T A L L A T I O N I N S T R U C T I O N S

EZ-Path® Multi-Gang Wall Bracket System


(Part Numbers: EZP544W, EZP544WD, EZP644W, & EZP644WD)

Option 2 – Installing Devices Prior to Wallboard (New Wall Construction)

1 2 3

Fasten plates to studs with tabs projecting into Insert devices into plates so that they project Gap between devices and finished gypsum board
wall ensuring that the plates are aligned. equally from both sides and tighten corresponding shall be filled with joint compound or SpecSeal®
set screws to hold devices in place. brand firestop sealant.

Configurations
1 2

EZP544W Configuration EZP544WD Configuration

3 4

EZP644W Configuration EZP644WD Configuration

Note: For more information on firestop installation, refer to ASTM E3157.


Specified Technologies Inc.
Page 2 of 2
Somerville, NJ 08876 USA
Warranty: www.stifirestop.com/legal/warranty
T: (800) 992-1180
Made in USA • Printed in USA
F: (908) 526-9623 ZIS1051 3579
www.stifirestop.com

You might also like