1860-T-0001Common

1 2
1867-PIT-0001
3 4 1867-P-0001A/B
5 6 1867-P-0001C/D
7 8 9 0001 10 11 12 13 14 15 16
?
Sea Water Intake Baisn Sea Fire Water PIT
GENERAL NOTES
1867-P-01A/B/ HOLD 1 1867-P-01C/D HOLD 1 1867-T-01A/B
MAIN FIRE WATER PUMPS (MOTOR) MAIN FIRE WATER PUMPS (DIESEL ENGINE) DIESEL FUEL TANK DAILY TANK
1867-SG-0001 RATED FLOWRATE (m3/hr) 1136.0 RATED FLOWRATE (m3/hr) 1136.0 SIZE, ID x HEIGHT (mm) 1300 x 2000
A RATED DIFF. HEAD (m) 119.0 RATED DIFF. HEAD (m) 119.0 NOMINAL CAPACITY (m³) 2 A
Stop Gate RATED DRIVER POWER (kW) 541.0 RATED DRIVER POWER (kW) 541.0 DESIGN PRESSURE (kg/cm ²g) 0
INSULATION / TRACING NI INSULATION / TRACING NI DESIGN TEMPERTAURE (°C) 32
1867-SP-HC0101 BY. OTHER
INSULATION / TRACING NI
for Fire Water System
BY. CONT. MOC CS

NEAR ROAD ACCESS


CONNECTION AT 2" 2"
ON SHORE BASE
2"-P-760201-01LC2B01-NI
Note 13 439 1867-2560-7502
NOTES
(DIESEL TRUCK TANK) 2"x1-1/2" TO DIESEL FUEL DAILY TANK 1. THE REFENCES THAT USED FOR P&ID FOR FIRE WATER PUMP
3/4" SET @ 14.00 kg/cm^2g SYSTEM_U1867ARE
B TRV - NFPA 20 "STANDARD FOR THE INSTALLATION OF STATIONARY PUMPS FOR B
2"-P-760202-01LC2B01-NI +
2"-FO-760203-01LC2B01-NI FIRE PROTECTION" 2019 ED. :
0001
- API RP 2001 "FIRE PROTECTION IN REFINERIES" 2001 ED.
1"150# - BASIC ENGINEERING DESIGN DATA TPPI OLEFIN COMPLEX DEVELOPMENT
20"-FW-760205-01LC2B01-NI FF TO GRADE AG PROJECT DOC NO : 21071-S-000-2200-0001 REV. O.
1867 1867-2560-7502 - DESIGN BASIS PHILOSOPHY ACTIVE FIRE PROTECTION TPPI OLEFIN COMPLEX
H H TO HEADER DISCHARGE FIRE DEVELOPMENT PROJECT REV. A(i),DOC . NO. : 21071-S-0000-3E00-0001.
LS LS - PROCESS DESIGN BASIS_U1867 DOC. NO: 21071-S-1867-2300-7501.
WATER
14" LO LO 0001A 14" LO 0001B 14" LO 2. MINIMUM QUANTITY OF MAIN FIRE WATER PUMPS PROVIDED IS N+2 BASED
14" LI L LI L
ONE (1) PUMP CAN BE ON MAINTENANCE AND ONE (1) SHALL BE ON STANDBY
0001A 0001B 1867-P-01D CONSIDERING. ONE OF MAIN PUMP FAILS TO OPERATING WHEN NEEDED.
1867-2560-7502 440 3. FIRE PUMP DRIVEN SHOULD BE AT LEAST ONE ELECTRIC MOTOR DRIVEN AND AT
C FROM MAIN FIRE WATER PUMPS LEAST ONE PUMP SHOULD HAVE A DIESEL ENGINE DRIVEN. POWER SUPPLY TO C
400 400
1" 2"
MM 2"
2"2" 1" 2"
MM 2"
2"2"
pipa THE ELECTRIC MOTOR DRIVEN BY A RELIABLE SOURCE (CONNECTED TO
ESSENTIAL FEEDER).

1867-T-0001B digambar
TO LOCAL CONTROL PANEL 4. MAIN FIRE WATER PUMP OPERATING PHILOSOPHY
1867-T-0001A NOTE 6 NOTE 6 441 1867-2560-7502 - 1867-P-01A SHALL RUN IF PRESSURE AT DISCHARGE PUMP DROPPED TO
14"-FW-4295-01LC2B01-NI

14"-FW-4289-01LC2B01-NI
10 Kg/Cm²g
sampai SIGNAL
- 1867-P-01B SHALL RUN IF PRESSURE AT DISCHARGE PUMP DROPPED TO

14"-FW-4290-01LC2B01-NI
CI 9.5 Kg/Cm²g
CURRENT
0001A INDICATION
ke dalam - 1867-P-01C SHALL RUN IF PRESSURE AT DISCHARGE PUMP DROPPED TO
9 Kg/Cm²g.

14"-FW-4292-01LC2B01-NI
XA CI CURRENT
CI CI
tangki, - 1867-P-01D SHALL RUN IF PRESSURE AT DISCHARGE PUMP DROPPED TO
8.5 Kg/Cm²g
D 0001A FAULT INDICATION 1867-P-01E RUN IF PRESSURE AT DISCHARGE PUMP DROPPED TO 8.0 Kg/Cm²g D
XI AVAILABLE
0001B
XA
TAHH COOLING WATER
TEMPERATURE START 0003 CURRENT INDICATION TAHH COOLING WATER
TEMPERATURE START 0001D CURRENT INDICATION seperti 5. LOCAL CONTROL PANEL BY VENDOR.
INDICATION
0002A 0001C HIGH-HIGH HS XA 0001D HIGH-HIGH HS XA
contoh. 6. DETAIL ENGINE PUMP BY VENDOR.

1"-P-760206-01LC2B01-NI
1"-P-760207-01LC2B01-NI
0001A FAULT

1"-P-760204-01LC2B01-NI
1"-P-760205-01LC2B01-NI
VAHH 0001C 0001C FAULT VAHH 0001D 0001D FAULT 7. DETAIL ENGINE FUEL TANKS (LOCATED HIGHER THAN THE DIESEL ENGINE
XI XI AVAILABLE VIBRATION VIBRATION
START 0001A
RUNNING
START 0002B
INDICATION 0001C HIGH-HIGH XI AVAILABLE INDICATION 0001D HIGH-HIGH XI Juga
AVAILABLE INDICATION
FUEL PUMP INLET) BY VENDOR.
8. PG-00001/00002/00003/00004, PSV-00001/00002/00003/00004 , FI-00001
HS L
LOW SW FEED HS XI
RUNNING
LAL
0001C
FUEL LEVEL
LOW
0002C
XI
LAL
0001D
FUEL LEVEL
LOW
0002D
XI
untuk PT-00001/00002/00003/00004, PSL-00001/00002/00003/00004, LI-00001/00002,
LSH-00001/00002, AND LSL-00001/00002, DETAIL PSV AND ITS ACCESSORIES
0001A 0001B 0001B FOR EACH PUMP DETAILED BY VENDOR.
XL 0001C
RUNNING
XL 0001D
RUNNING
tangki 9. MATERIAL FOR 1867-P-01A/B/C/D/E AND 1867-P02A/B.
BATTERY
0003C VOLT METER
BATTERY
0003D VOLT METER - IMPELLER : NI - AL-BRONZE. , Non-
E MIN MIN MIN
lainnya
MIN
1.5M - CASING : NI-AL-BRONZE.
E
1.5M
1"x1/2"
1.5M
1"x1/2"
XL
OVER
0002C SPEED
1.5M
1"x1/2"
XL
OVER
0002D SPEED 1"x1/2"
10. A/G : ABOVE GROUND. metallic
11. REFER SYMBOL & LEGEND PIPING COMPONENT DOCUMENT NO :
XL ENGINE
CONTROL
XL ENGINE
CONTROL
21071-D-0000-2560-0002 flexible
PSH 12. ANTI SURGE VALVE
PSH 0001B
0001C TROUBLE
PSH
0001D TROUBLE
PSH connection
1.5M
I
0001A
MIN I MIN I
0001C
MIN I
0001D
MIN 13. Line 2"-P-760201- s
1.5M 1"x1/2" 1.5M 1.5M

F
MCC
PSL
1"x1/2" MCC
PSL
0001B
MCC
PSL
1"x1/2" MCC
PSL
1"x1/2" 01LC2D01-NI is for Diesel F
0001A 0001C 0001D Fuel REFERENCE DRAWINGS
LOCAL CONTROL PANEL LOCAL CONTROL PANEL 21071-D-0000-2550-0001 OVERALL SITE PLAN
HS XL XL NOTE 5
HS XL NOTE 5 PROCESS DESIGN BASIS_U1867
0001A 0001A 0002A HS HS 21071-S-1867-2300-7501
0001B 0001B UTILITY FLOW DIAGRAM_U1867
START/STOP RUNNING 0001 1300D 21071-S-1867-2570-7501
HAND/OFF/AUTO START/STOP RUNNING 21071-D-0000-2550-0001~ 0012 PID SYMBOL AND LEGEND
START/STOP START/STOP
FI HAND/OFF/AUTO
HAND/OFF/AUTO HAND/OFF/AUTO
LOCAL CONTROL PANEL 00001A LOCAL CONTROL PANEL
NOTE 5 NOTE 5
16" 16"x12" 16"x12" NNF 16"-FW-760206-01LC2B01-NI
G G
EXHAUST EXHAUST
LINE ATM LINE ATM

SILENCER SILENCER
1867-P-0001D HOLDS
S

S
14" COOLING
1867-P-0001C COOLING
1. CAPACITY AND NUMBER OF MAIN FIRE WATER PUMPS NOT YET FIXED DUE TO
NC NC 14" NC NC FIRE WATER DEMAND CALCULATION NOT YET ISSUED.
14" WATER WATER 14"
SET @ 16.00 kg/cm^2g SET @ 16.00 kg/cm^2g SET @ 16.00 kg/cm^2g 2. P&ID MAIN FIRE WATER RING NOT YET ISSUED.
VALVE ASSY VALVE ASSY
1867-P-0001A 3/4" 1867-P-0001B 3/4"
PSV 3/4" 3/4"
8"x6" PSV 8"x6" PSV
H PSV
+
+
H
PG SET @ 16.00 kg/cm^2g PG 00001B 00001C
+

0001D
D

D
+

0001A 0001A M
M 0001B
NOTE 12 NOTE 12 NOTE 12 NOTE 12
2"
14"x8"

14" 14"
14"x8"

2" 2" 2"


14" 14" PG PG
14" E
1026B
14"x8"
1026B 14"x8"
E
1867
NOTE 2
-SG- LSLL LSL 0 30 DES 22 1ST ISSUED (INTERNAL) WLD/NUR TS/SFI/CHR S.B.KIM

I 00001 0001 REV DATE DESCRIPTION DRAWN CHK'D APP'D I


0001 RADAR SEA WATER LEVEL. THIS DRAWING EMBODIES PROPRIETARY INFORMATION OF PT. KILANG PERTAMINA INTERNASIONAL THIS DRAWING OR THE

14"-FW-760222-01LR2B01-NI
MATERIAL DESCRIBED THEREON MAY NOT BE COPIED OR DISCLOSED IN ANY FORM OR MEDIUM TO THIRD PARTIES, OR USED
2"-FW-760208-01LR2B01-NI

14"-FW-760218-01LR2B01-NI

FOR OTHER THAN THE PURPOSE FOR IN ANY FORM OR MEDIUM TO THIRD PARTIES, OR USED FOR OTHER THAN THE

2"-FW-4282-01LR2B01-NI
2"-FW-4280-01LR2B01-NI
2"-FW-760212-01LR2B01-NI
14"-FW-750101-01LR2B01-NI

14"-FW-760214-01LR2B01-NI

PURPOSE FOR WHICH IT HAS BEEN PROVIDED, IN WHOLE OR IN PART IN ANY MANNER EXCEPT AS EXPRESSLY PERMITTED
BY PT. KILANG PERTAMINA INTERNASIONAL.

PROJECT

14"- TPPI OLEFIN COMPLEX DEVELOPMENT PROJECT

FW OWNER
J PT KILANG PERTAMINA J
INTERNASIONAL
1861-T-0001

CONTRACTOR

TITLE :
PIPING & INSTRUMENTATION DIAGRAM
FOR FIRE SYSTEM
K K
1867-PIT-0001 (UNIT 1867)
FILE NAME :

FIRE WATER PUMP 1/2


NONE SP-21071 21071-D-1867-3E10-7602 1/1 O
SCALE CONTRACT NO. DRAWING NO. SHT NO. REV.
A1 (841x594)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16