3.9 Load Calculation
3.9 Load Calculation
0 degree load
3 Wind load 90 degree load
Wind load on side cladding
Joint Weight
4 Seismic load SRSS Method
Expansion
5 Temperature load Contraction
LOAD CASES
Seismic X
Seismic Z
Applicable standard = EN1998-1 ( as per DBR Cl.5.1.6 )
Combination method = SRSS
Peak ground acceleration PGA = 0.20 g ( as per DBR Cl.5.1.6 )
Soil class = C ( as per DBR Cl.5.1.6 )
Damping = 0.05
Importance factor γ1 = 1.00
Design ground acceleration ag = 0.20 g
Joint weight considered = 1.0 DL + 0.3 LL
Operating platform
Folding Staircase
Staircase
Roof
Selfweight of Roof sheet = 0.10 kN/m2
Roof Sheeting fittings = 0.05 kN/m2
(50% of roof sheet weight)
Self weight of purlin = 0.18 kN/m (Channel - 150x75x18)
Hung load = 0.50 kN/m2
(For Electrical & other installations)
Tributary
Unfoirm UDL Load on Roof
S.No Length
Load
kN/m2 kN/m m kN/m
1 0.65 0.18 2.88 2.049
2 0.65 0.18 6.00 4.080
3 0.65 0.18 6.25 4.243
Unfoirm Tributary
UDL Load (Girts)
S.No Load Length
kN/m2 kN/m m kN/m
1 0.15 0.18 2.88 0.611
2 0.15 0.18 4.25 0.818
3 0.15 0.18 3.83 0.754
4 0.15 0.18 4.88 0.911
5 0.15 0.18 4.50 0.855
6 0.15 0.18 3.00 0.630
Live Load
Operating platform
Folding Staircase
Staircase
Unfoirm Tributary
S.No Load Length Load on Roof
kN/m2 m kN/m
1 0.6 2.88 1.725
2 0.6 6.00 3.600
3 0.6 6.25 3.750
Temperature load
Temperature load is considered with a temperature variation of ±14.7˚C.
ROTARY ENGINEERING LIMITED
Terrain parameters
Zo = 0.003 Table 4.1
ZoII = 0.050 Table 4.1
Zmin = 1.000 Table 4.1
Z (max Height) = 7.000 m
Basic wind velocity Vb = Vbo x Cdir x Cseason (As Per EN 1991-1-4:2005-Cl 4.2)
Mean wind velocity Vm(z) = Vbp x Cr(z) x Co(z) (As Per EN 1991-1-4:2005-Cl 4.3)
Roughness Factor Cr (Z) = Kr x In (Z / Z0) for Zmin ≤ Z ≤ Zmax (As Per EN 1991-1-4:2005-Cl 4.3.2)
qp (Z)
Building Station Height (Z) in m Cr(Z) Ce(Z) Vm(Z) p in kN/m2
kN/m2
Truck Loading Bay 7.000 1.22 1.91 47.057 2.60 5.20
Empty Free standing Canopy, refer figure 7.15 & 7.17 of EN1991:1-4
Roof angle α = 5 degree
CsCd = 1.000 Cls. 6.2
Blockage = 0.000 Fig. 7.15
Overall Pressure Coefficient Cf = -0.600 Table 7.7
For duopitch Canopies
Tributary length of Purlin L1 = 1.20
Tributary length of Purlin L2 = 0.84
Tributary length of Purlin L3 = 0.40
Tributary
Unfoirm Load Roof load
S.No Length
KN/m
kN/m 2
m
1 2.60 2.88 -4.49
2 2.60 6.00 -9.36
3 2.60 6.25 -9.75
Horizontal
Node L/C Fx kN
Max Fx 923 2029 1DL 1POL 0.3LL 1PAL 38.837
Min Fx 924 2079 1DL 1PDL 0.3LL -41.755
Max Fy 920 2088 1DL 1POL 1.3LL 1PAL 1PFL 1.3TL-C -20.029
Min Fy 917 2075 1DL 1PDL -6.005
Max Fz 923 2073 1DL 1PDL 11.429
Min Fz 923 2035 1DL 1POL 0.3LL 1PAL -14.227
Max Mx 917 2029 1DL 1POL 0.3LL 1PAL 33.373
Min Mx 917 2029 1DL 1POL 0.3LL 1PAL 33.373
Max My 923 2073 1DL 1PDL 11.429
Min My 923 2035 1DL 1POL 0.3LL 1PAL -14.227
Max Mz 917 2029 1DL 1POL 0.3LL 1PAL 33.373
Min Mz 917 2029 1DL 1POL 0.3LL 1PAL 33.373
Vertical Horizontal Moment
Fy kN Fz kN Mx kN-m My kN-m Mz kN-m
285.334 -0.357 0 0.082 0
6.774 0.31 0 -0.121 0
432.223 -0.653 0 0.028 0
-33.546 0.497 0 0.113 0
120.063 15.832 0 0.104 0
133.171 -15.904 0 0.11 0
202.792 -0.6 0 0.019 0
202.792 -0.6 0 0.019 0
121.745 0.425 0 0.143 0
115.504 0.403 0 -0.138 0
202.792 -0.6 0 0.019 0
202.792 -0.6 0 0.019 0