XIAL FLOW FAN - Direct Driven: Tda - L

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

02.

SF-B-01

AXIAL FLOW FAN - direct driven


TDA - L
LONG CASED
Construction
Double flanged casing is produced in mild steel or galvanised
Steel, the impeller having manually adjustable pitch blades is
made of PPG, PAG or Aluminium.

Finish
Painting or galvanised after manufacture is normal finish
on all parts.

Operating Temperature
-20°C to +55°C

Motors
Totally enclosed Class ‘F’ motor, to a min. IP54 protection
are fitted as standard. Standard motor up to 2.2kW are usually
supplied on DOL starting, motor 3.0kW and above are star/
delta starting.

Airflow Direction
Air flow from impeller to motor is fitted as standard. Air
flow from motor to impeller can be supplied upon request.

Option
Spark resistance construction in accordance with AMCA standard
99-0401-86-type C construction can be supplied upon request.

D
N° x Ø

Ø谺B
Ø谻C
Ø谹A

All Dimension in mm.


Weight Max.Motor* Weight Max.Motor*
MODEL A B C D N° ∅ ( kg ) FrameSize MODEL A B C D N° ∅ ( kg ) FrameSize

315 315 355 395 355 8 10 8 D71 900 900 945 1000 630 18 12 66 D160M

355 355 395 435 355 8 10 10 D80 1000 1000 1050 1100 630 24 12 73 D160M

400 400 440 480 355 12 10 11 D90S 1120 1120 1185 1250 900 24 12 135 D225M

450 450 490 530 400 12 10 14 D90L 1250 1250 1315 1380 1000 24 12 170 D250M

500 500 540 580 500 12 10 18 D90L 1400 1400 1465 1530 1100 32 14 220 D250M

560 560 605 660 500 12 10 22 D112M 1600 1600 1663 1730 1250 32 14 275 D250M

630 630 675 730 500 12 10 24 D112M 1800 1800 1856 1930 1400 32 14 335 D280M

710 710 755 810 500 18 12 40 D112M 2000 2000 2073 2130 1400 32 14 380 D315M

800 800 845 900 560 18 12 49 D132M 2250 2250 2330 2400 1535 36 18 430 D315M

* Please consult KRUGER if motor frame size is beyond the catalogue range.
• Note: Weight without motor and impeller.

The company is always improving and developing its products, therefore the company reserves the right of making changes to the illustrated products.
Certified dimension can be provided upon request.

LEA001.E2 March 2018


KRUGER VENTILATION INDUSTRIES ASIA CO LTD A member of
- 30/159 Moo 1, Sinsakorn Industrial Estate, Chetsadawithi road,
Edition 6 Khok Kham, Mueng, Samutsakorn 74000, Thailand
Printed in March 2018 - Tel +662 1054298 - Fax+662 0248256-9
- www.krugerfan.com
Date 30/11/2022 Kruger Ventilation Industries (Vietnam) Co. Ltd
Company Lot A7.2‑4 C2 Road
Customer Ref. Thanh Thanh Cong IZ
Trảng Bàng Dist
Project NITTO DENKO ‑ BÌNH DƯƠNG (PHASE 6)
Tay Ninh Province 
Reference KVN21‑AL‑188E_R05 Email: [email protected]
Line 102. SF-B-01 Tel: 84‑276 3585200/01/02 Fax: 84‑276 3585199
Website:  www.krugerfan.com

Tag: EF‑B‑01; SF‑B‑01
Fan Selection
Fan Type Axial
Unit TDA 710 /  12AA / 7‑7/24°
Operating Conditions Ducted
Required Volume 17900 m³/h
Required Pressure (Ps) 200 Pa
Air Volume 18214 m³/h (102%)
Static Pressure 207 Pa (104%)
Velocity Pressure 96 Pa
Total Pressure 303 Pa
Outlet Velocity 12.8 m/s
Fan Total Efficiency 67.8 %
Fan Static Efficiency 46.3 %
Fan Speed 1420 rpm
Air Temperature 20.0 °C
Altitude 0 m
Fan Absorbed Power 2.26 kW
Motor Selection
Recommended Motor 3.00kW(4P D100L)
Motor Speed 1420 rpm
Service Factor 33 %
Belt Selection
Fan Pulley / Bush
Motor Pulley / Bush
Belt Length
Number of Belts
Bearing Life (L10/L50) ‑ / ‑ hours
Starting Torque Hz 63 125 250 500 1k 2k 4k 8k Overall
Operating Limits Lwi(Lin) 86 92 88 87 85 82 79 76 96 dB
Max. Absorbed Power 20.00 kW Lwi(A) 59 76 80 84 85 83 80 75 90 dB(A)
Max. Fan Speed 1800 rpm Lpi(A) 39 56 59 64 65 63 60 55 70 dB(A)
*  Sound data is for the inlet side    * Sound Pressure Level 3.0 m, Free Field

ØA ØB ØC D KG* N°xØ
710 755 810 500 40 18x12
*weight excludes motor and drive All dimensions in mm.