RAG3080
RAG3080
New options have been included in the RAG series of relays. Its design, durability and quality guarantee its application in high dependency applications such as power
stations, substations, railway, and continuous process industries (petrochemical, rolling mills, cement and chemical industries). Relays in the RAG series of relays have
been designed and manufactured in accordance with the most demanding test standards (IEC, EN, IEEE) and bear the CE mark. Their making/breaking capacities, high
permanent current and overvoltage capacity allow direct action on HV and MV switchgear.
Options
No 0
High breaking capacity (magnetic arc blow out)
Yes 1
No 0
Front LED
Yes 1
No 0
Contact position mechanical indicator
Yes 1
No 0
Relay trip flag
Yes 1
No 0
Push-to-test button To push the contacts 1
Fix the contacts 2
Characteristics
• Mechanical life: 107 operations • Contacts:
• Pick-up time: <20 ms Permanent current: 10 A
• Drop-out time: <15 ms/Vdc, <50 ms/Vac, Instant. current: 80A/200ms; 150A/10ms
<40 ms (DI and all relays with a front LED) Making capacity: 40A/0.5s/110Vdc
• Operating temperature: -10°C to +55°C Breaking capacity: see curves.
• Storage temperature: -30°C to +70°C Umax, opened contact: 250Vdc/400Vac
• Operating humidity: 93%/40°C • Standard voltages (UN):
24,48,72,96,110,125,220Vdc/Vac;50/60Hz
Construction Standards
• Electrical test IEC60255-5 • Inflammability tests UL94: V0
Dielectric test 2kV/50Hz/1 min Plastic materials
Surge withstand 5 kV/1.2/50µs • Protection degree relay IEC60529, EN60529: IP40
Insulation >2,000MΩ/500Vdc • Climatic tests IEC60068-2
Thermal shock -25°C +70°C
EMC Tests
EN 60255-22-1 •High frequency burst disturbance test: EN 61000-4-6 •Conducted disturbances induced by radio
1MHz, 400 imp/s, 2 s frequency fields.
Common mode: 2.5 kV • Dif. mode:1kV 0.15-80MHz, 10V, 80% AM (1kHz)
EN 61000-4-4 •Electrical Fast transient burst: EN 61000-4-2 •Electrostatic discharges:
4kV, 2.5kHz, 1min•2kV, 5kHz, 1min Contact: ±15kV • Air mode: ±15kV
EN 61000-4-5 •Surge: 1.2/50µs.(voltage) EN 61000-4-8 •Power frequency magnetic field:
8/20µs.(current) 100A/m 1min•1000 A/m 1s.
Common mode: 2kV • Differential mode: 1kV EN 55011 •Radio disturbance. Cover:
EN 61000-4-3 •Radiated electromagnetic field: Test level: Class A 30-230MHz, 40dB(µV/m) (quasi peak)-10m
80-1000MHz, 10V/m, 80% AM (1kHz) 230-1000MHz, 47dB(µV/m) (quasi peak)-10m
EN 61000-4-3 •Digital telephones radiated Power supply:
electromagnetic field: 0.15-0.5 MHz, 79dB(µV)(peak)/66dB med. value
900 ±5MHz, 10V/m, 50% (200Hz) 0.5-5 MHz, 73dB(µV) (peak)/60dB med. value
1.89GHz ±10MHz, 10V/m, 50% (200Hz) 5-30 MHz, 73dB(µV) (peak)/60dB med. value
Sockets
Screw Double Faston
Front connection PAV3 IP10 PAV3-2C IP10
Rear connection PAR3 OP N/A
Weights
RAG3080 – 500g
PAV3 IP10 and PAV3-2C IP10 – 225g
PAR3 OP – 180g.
Accessories
• Retaining clips.
• Function signs on the extraction ring.
• Security pins.