1.) Unit shall be provided with additional components: two extra sets of belts and filters,
24" high roof curb, NEMA 3R rated disconnect switch.
2.) Unit shall have premium efficiency motors.
Submittal
Job Number:
Job Name:
Chappaqua CSD
Trane U.S. Inc. is pleased to provide the enclosed submittal for your review and approval.
Product Summary
Qty Product
1 3-10 Ton R-410A PKGD Unitary Cooling Rooftop
General
The units shall be convertible airflow. The operating range shall be between 115°F and 0°F in cooling as standard from
the factory for units with microprocessor controls. Operating range for units with electromechanical controls shall be
between 115°F and 40°F. Cooling performance shall be rated in accordance with ARI testing procedures. All units shall
be factory assembled, internally wired, fully charged with R-410A, and 100 percent run tested to check cooling
operation, fan and blower rotation, and control sequence before leaving the factory. Wiring internal to the unit shall be
colored and numbered for simplified identification. Units shall be cULus listed and labeled, classified in accordance for
Central Cooling Air Conditioners.
Casing
Unit casing shall be constructed of zinc coated, heavy gauge, galvanized steel. Exterior surfaces shall be cleaned,
phosphatized, and finished with a weather-resistant baked enamel finish. Units surface shall be tested 672 hours in a
salt spray test in compliance with ASTM B117. Cabinet construction shall allow for all maintenance on one side of the
unit. Service panels shall have lifting handles and be removed and reinstalled by removing two fasteners while providing
a water and air tight seal. All exposed vertical panels and top covers in the indoor air section shall be insulated with a
cleanable foil-faced, fire-retardant permanent, odorless glass fiber material. The base of the unit shall be insulated with
1/8", foil-faced, closed-cell insulation. All insulation edges shall be either captured or sealed. The units base pan shall
have no penetrations within the perimeter of the curb other than the raised 1 1/8" inch high downflow supply/return
openings to provide an added water integrity precaution, if the condensate drain backs up. The base of the unit shall
have provisions for forklift and crane lifting, with forklift capabilities on three sides of the unit.
Unit Top
The top cover shall be one piece construction or, where seams exist, it shall be double-hemmed and gasket-sealed.
The ribbed top adds extra strength and enhances water removal from unit top.
Filters
Throwaway filters shall be standard on all units. Optional 2-inch MERV 8 and MERV 13 filters shall also be available.
Compressors
All units shall have direct-drive, hermetic, scroll type compressors with centrifugal type oil pumps. Motor shall be suction
gas-cooled and shall have a voltage utilization range of plus or minus 10 percent of unit nameplate voltage. Internal
overloads shall be provided with the scroll compressors.
Dual compressors are outstanding for humidity control, light load cooling conditions and system back-up applications.
Dual compressors are available on 7½-10 ton models and allow for efficient cooling utilizing 3-stages of compressor
operation for all high efficiency models.
Outdoor Fans
The outdoor fan shall be direct-drive, statically and dynamically balanced, draw-through in the vertical discharge
position. The fan motor shall be permanently lubricated and shall have built-in thermal overload protection.
Indoor Fan
The following units shall be equipped with a direct drive plenum fan design (T/YSC120F,T/YHC074F,
T/YHC092F,T/YHC102F, 120F). Plenum fan design shall include a backward-curved fan wheel along with an external
rotor direct drive variable speed indoor motor. All plenum fan designs will have a variable speed adjustment
potentiometer located in the control box.
3 to 5 ton units (high efficiency 3-phase with optional motor) are belt driven, FC centrifugal fans with adjustable motor
sheaves. 3 to 5 ton units have multispeed, direct drive motors. All 6 to 8½ ton units (standard efficiency) shall have belt
drive motors with an adjustable idler-arm assembly for quick-adjustment to fan belts and motor sheaves. All motors shall
be thermally protected. All 10 tons, 6 ton (074), 7½ to 8½ (high efficiency) units have variable speed direct drive motors.
All indoor fan motors meet the U.S. Energy Policy Act of 1992 (EPACT).
Note:
Building system modeling in energy simulation software like TRACE is recommended to evaluate performance
improvements for your application.
SZ VAV is fully integrated into the ReliaTel Control system and is available today. It provides the simplest and fastest
commissioning in the industry through proven factory-installed, wired, and tested system controllers. All control
modules, logic and sensors are factory installed, and tested to assure the highest quality and most reliable system
available. This means no special programming of algorithms, or hunting at the jobsite for sensors, boards, etc. that need
to be installed in the field. Single zone VAV is a quick and simple solution for many applications and is available from
your most trusted rooftop VAV system solution provider- Trane.
Plenum Fan
The following unit shall be equipped with a direct drive plenum fan design (all 10 tons and 7.5-8.5 ton high efficiency
units). Plenum fan design shall include a backward-curved fan wheel along with an external rotor direct drive variable
speed indoor motor. All plenum fan designs will have a variable speed adjustment potentiometer located in the control
box.
Controls
Unit shall be completely factory-wired with necessary controls and contactor pressure lugs or terminal block for power
wiring. Unit shall provide an external location for mounting a fused disconnect device. A choice of microprocessor or
electromechanical controls shall be available. Microprocessor controls provide for volt control functions. The resident
control algorithms shall make all heating, cooling, and/or ventilating decisions in response to electronic signals from
sensors measuring indoor and outdoor temperatures. The control algorithm maintains accurate temperature control,
minimizes drift from set point, and provides better building comfort. A centralized Microprocessor shall provide anti-short
cycle timing and time delay between compressors to provide a higher level of machine protection.
Refrigerant Circuits
Each refrigerant circuit offer thermal expansion valve as standard. Service pressure ports, and refrigerant line filter
driers are factory-installed as standard. An area shall be provided for replacement suction line driers.
Phase monitor
Phase monitor shall provide 100% protection for motors and compressors against problems caused by phase loss,
phase imbalance, and phase reversal. Phase monitor is equipped with an LED that provides an ON or FAULT indicator.
FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 7 of 17
Others
Chappaqua CSD June 28, 2018
There are no field adjustments. The module will automatically reset from a fault condition.
Note: The disconnect switch will be sized per NEC and UL guidelines but will not be used in place of unit overcurrent
protection.
Trane Single Zone Variable Air Volume Control Sequence of Operation (Precedent 17 Plus)
General Standby Mode
During normal occupied periods, when there is no space cooling or heating demands, the user will be able to choose
Continuous or Cycling supply fan operation. During this period, if the supply fan is operating due to a Continuous Fan
Mode selection or due to a ventilation request, the supply fan will operate at 50% of the user selected, application
specific, maximum airflow. The unit controls will be compatible with BACnet and LonTalk Building Automation System
communication interfaces.
Cooling Operation
Default Operation:
During Cooling operation, the control will monitor the Space Temperature and Space Cooling setpoint and with a PI
control algorithm determine if active cooling capacity is required. As the Space Temperature deviates from the Space
Cooling Setpoint, the unit controller will calculate an active Discharge Air Cooling setpoint that the economizer (if
installed) and compressor outputs will be controlled to meet. This active Discharge Air Cooling setpoint will be
calculated between the Space Cooling setpoint and a user adjustable minimum (65F Default for Single Zone Variable
Air Volume Control). Once the control determines that a discharge air temperature equal to the user selected minimum
(65F Default) is required to meet the space cooling demand, if the space demand continues to increase, the supply fan
speed will be allowed to increase above its minimum speed proportionally to meet the additional demand.
CONDENSER FAN
EVAPORATOR SECTION
ACCESS PANEL
27 5/8"
47 7/8" CONDENSER
COIL SIDE
53 3/4"
33" 32 1/8"
SUPPLY RETURN
3 5/8"
17 1/2" 17 1/2"
PLAN VIEW OF UNIT
DIMENSION DRAWING 62 1/4"
9 3/8"
COIL
SERVICE
HORIZONTAL
SIDE
AIR FLOW
99 11/16"
CONDENSATE DRAIN (SEE NOTE 4) 63 3/16" 162"
PACKAGED COOLING
DIMENSION DRAWING
(2)(4)(6)
GENERAL
Model: THC120
Unit Operating Voltage: 187-253
Unit Primary Voltage: 208
Unit Secondary Voltage 230
Unit Hertz: 60
Unit Phase: 3
EER 12.5
Standard Motor Oversized Motor Field Installed Oversized Motor
Minimum Circuit Ampacity: 46.1 Minimum Circuit Ampacity: N/A Minimum Circuit Ampacity: N/A
Maximum Fuse Size: 60.0 Maximum Fuse Size: N/A Maximum Fuse Size: N/A
Maximum (HACR) Circuit Breaker: 60.0 Maximum (HACR) Circuit Breaker: N/A Maximum (HACR) Circuit Breaker: N/A
INDOOR MOTOR
Standard Motor Outsized Motor Field Installed Oversized Motor
Number: 2 Number: 1
Horsepower: 5.1/2.7 Horsepower: 0.75
Phase: 3 Motor Speed (RPM): 1100
Rated Load Amps: 19.6/10.4 Phase: 3
Locked Rotor Amps: 136.0/73.0 Full Load Amps: 2.7
Locked Rotor Amps: 9.8
(3) (2)
POWER EXHAUST ACCESSORY FILTERS REFRIGERANT
(Field Installed Power Exhaust)
Type R-410
Phase: N/A Type:
Horsepower: N/A Factory Charge
Furnished: 7.1 lb
Motor Speed (RPM): N/A Circuit #1
Number
Full Load Amps: N/A Circuit #2 5.0 lb
Recommended
Locked Rotor Amps: N/A
NOTES:
1. Maximum (HACR) Circuit Breaker sizing is for installations in the United States only.
2. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
3. Value does not include Power Exhaust Accessory.
4. Value includes oversized motor.
5. Value does not include Power Exhaust Accessory.
6. EER is rated at AHRI conditions and in accordance with DOE test procedures.
ECONOMIZER 93.0 lb
BAROMETRIC RELIEF
OVERSIZED MOTOR
POWER EXHAUST
HEATER
REHEAT
NOVAR CONTROL
ROOF CURB
NOTE:
1. All weights are approximate.
2. Weights for options that are not list refer to Installation guide.
3. The actual weight are listed on the unit nameplate.
4. Refer to unit nameplate and installation guide for weights before scheduling transportation and installation
of unit.
5. The weight shown represents the typical unit operating weight for the configuration selected. Estimated
at +/- 10 % of the nameplate weight. .
6. Verify weight, connection, and all dimension with installer documents before installation.
7. Corner weights are given for information only.
8. Net/Shipping weight of optional accessories should be added to unit weight when ordering factory or field
installed accessories.
E F
PACKAGED COOLING
RIGGING AND CENTER OF GRAVITY
CLEARANCE 36"
CLEARANCE 48"
SUPPLY
RETURN
PACKAGED COOLING
CLEARANCE
ROOF OPENING
UNIT OUTLINE
46" 63 3/16"
46"
99 11/16"
PACKAGED COOLING
DOWNFLOW TYPICAL ROOF OPENING
RETURN OPENING
NOTES:
1. VERIFY WEIGHT, CONNECTION, AND ALL DIMENSION WITH
INSTALLER DOCUMENTS BEFORE INSTALLATION
SUPPLY OPENING
80 1/2"
1 11/16" 5 1/8"
34 7/16" 34 7/16"
56 7/16"
2" 2"
20 1/4"
83 7/8"
59 13/16"
14"
84 1/2" 60 7/16"
17 3/4"
33 3/4"
17 3/4"
33 3/4"
DUCT CONNECTIONS
ACCESSORY
L1 L2 L3
HTB1
22 GAUGE 1800"
20 GAUGE 3000"
18 GAUGE 4500"
16 GAUGE 7200"
14 GAUGE 11700"
NOTE:
1. All wiring and devices shown dashed to be supplied and installed by the customer in accordance with national and local electrical codes.
2. Low voltage control wiring must not be run in conduit with power wiring.