1
1
1
The
distribution system may be particularly designed for flexibility in applying grounding by having only
three-wire loads connected directly to the generator or even having only a single transformer connected
to the generator (unit bank). Thus the design may employ high-resistance grounding to minimize
damage from internal ground faults, or low-resistance grounding if needed to operate selective ground
relays. In either case the ground-current level should be substantially less than the phase-current fault
levels. The generator may also be applied to a four-wire load without transformation. If the generator is
rated for solidly grounded service, the neutral may be connected directly to Figure 1-27—Zero-sequence
currents during a wye side fault IEEE SYSTEM GROUNDING Std 142-2007 Copyright © 2007 IEEE. All
rights reserved. 41 the grounded circuit conductor. If a standard generator is used, a reactor should be
connected between neutral and the grounded circuit conductor so as to limit the momentary ground-
fault current to no more than the momentary three-phase fault current (see Beeman; NEMA MG 1).
When 3i0 = i"d the value of this neutral reactor, XN, should be as shown in Equation (1.1): (1.1) where
3i0 = Ground-fault current = 3Vin/(X"d + X2 + X0 + 3Xn) i"d = Three-phase subtransient fault current =
Vin/X"d X"d = Generator subtransient reactance X2 = Generator negative-sequence reactance X0 =
Generator zero-sequence reactance Vin = Phase to neutral voltage Note that a resistor should not be
used for this purpose, since its impedance is in quadrature with the machine reactance and thus would
require a much larger value of resistance than reactance. This resistance would incur large losses from
the flow of either fault or load current. The zero-sequence load current would also produce an
objectionable voltage drop, since the load is primarily resistive. On the other hand, the neutral reactor
will cause little voltage drop to be produced by inphase zero-sequence load current. The total zero-
sequence current will be a small value because the generator has limited unbalanced current capacity.
The continuous negativesequence current capability of generators covered in ANSI C50 standards is 8%
or 10%. For salient-pole generators covered under NEMA MG 1, the limit is 10% at full load. The use of
the reactor between the generator neutral and the neutral circuit conductor does not affect the NEC
requirement that the neutral circuit conductor be solidly grounded. If generators are solidly grounded,
the system’s circuit breaker duty must be calculated at the higher ground-fault duty. If the wye side of a
delta-wye transformer is connected to a generator that is configured for four-wire service, the generator
should be designed with a two-thirds pitch winding. This transformer will act as a short circuit to third
harmonic currents, and without cancellation of third harmonic voltage, the resultant current may
adversely affect groundfault relaying and generator capacity.