This document provides the design calculations for the earthing system of a 400kV switchyard. It includes inputs like system voltage, fault current, soil resistivity, equipment details. Preliminary calculations determine the area of switchyard, number of grids, total length of conductors and electrodes. The purpose is to design an earthmat that achieves tolerable touch and step potentials with earth grid resistance less than 1 ohm.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
222 views71 pages

Tower

This document provides the design calculations for the earthing system of a 400kV switchyard. It includes inputs like system voltage, fault current, soil resistivity, equipment details. Preliminary calculations determine the area of switchyard, number of grids, total length of conductors and electrodes. The purpose is to design an earthmat that achieves tolerable touch and step potentials with earth grid resistance less than 1 ohm.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 71

C 12/20/10 RAAJ SKW

B 12/06/10 RAAJ SKW

A 09/17/10 First Release RAAJ SKW

No. DATE REMARKS CHKD APPD

REVISION

LARSEN & TOUBRO LIMITED


ECC Division - EDRC

PROJECT : BULK POWER RECEIVING SUBSTATION FOR TATA STEEL LIMITED SIGN DATE

DSND AADI 16-Sep-10


PACKAGE : DRWN
CHKD RAAJ 17-Sep-10
TITLE : SCALE APPD SKW 17-Sep-10
DRG.No. REV.
400kV Switchyard - Earthing Design Calculation CODE
O10178-E-SY-AS-DC-0012 A
LARSEN & TOUBRO LIMITED Page 2 of 71
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!

CALCULATIONS ARE BASED ON IEEE Std 80-2000

PURPOSE AND SCOPE

The purpose of the document is to design the Earthmat for the 132 kV GIS-cum Control Room Building Layout at BPRS . The important aspect is
that the design should achieve "Tolerable Touch and Step potential " with the Earth grid resistance less than 1 ohm.

6.0.0 DESIGN INPUT

6.1.0 SYSTEM PARAMETERS

6.1.1 System Voltage = 400 kV

6.1.2 System Grounding = Solid

6.1.3 Maximum Fault Current If = #REF! (Spec Write up Cl. No:2.0)

6.1.4 Current Distribution Factor = #REF! (Refer Annexure- A & B)

(Current Distribution factor is considered as per Cl 15.6 of IEEE-80,2000 and Methodology is as per IEEE Transaction on Power
Apparatus and systems "Current for Design of Grounding System" ,Vol PAS .103,No.9,Sep 1984)

6.1.5 Maximum Fault Current considered Ig = #REF!

= #REF!

6.1.6 Duration of Fault Current ts = 1.00 s

6.1.7 Fault Clearing time ts = 1.00 s (specification Secion D4 Cl.


No:2.1.3)

6.6.0 ENVIRONMENTAL PARAMETERS

6.6.1 Soil Resistivity r = 333.55 ohm.m (Refer Soil Resistivity Report)

6.6.2 Top Layer resistivity (Crushed rock) rs = 5000 ohm.m (As per IEEE-80 cl. No:12.5)

6.6.3 Length of Switchyard L = 302 m (Drg .O10178-E-SY-AS-EL-0024)

6.6.4 Breadth of Switchyard B = 162.0 m (Drg .O10178-E-SY-AS-EL-0024)

6.3.0 OTHER DETAILS

6.3.1 Conductor diameter d = #REF! (Refer Conductor sizing calculation)

6.3.2 Conductor Area = #REF!

6.3.3 Depth of burial (minimum) h = 0.6 m


LARSEN & TOUBRO LIMITED Page 3 of 71
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!

6.3.4 Depth of Top Layer hs = 0.15 m (Assumed)


LARSEN & TOUBRO LIMITED Page 4 of 71
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!

6.3.5 No of electrodes
Reactor = 0 (1Nos x (2 Body +2 Neutral)
IC Transformer = 8 (2Nos x (2 Body +2 Neutral)
Lightning Arrester = 12 (12Nos x 1)
CVT = 12 (12Nos x 1)
Lightning Mast = 0 (0Nos x 1)
Tower with Peak = 30 (30Nos x 1)
Fence = 10 (10Nos X 1)

6.3.5 No of electrodes nr = 72

6.3.6 Length of electrode l = 3m

6.3.7 Diameter of electrode - GI Pipe dl = 50 mm

7.0.0 CALCULATIONS

7.1.0 CALCULATIONS - PRELIMINARY

7.1.1 Area of Switchyard Ag = LxB

= 302 x 162

= 48924 Sq.m

7.1.2 Spacing of Conductors Ds = 3.5 m

7.1.3 No: of grids in X direction Nx = (L/Ds)+1

= 302/3.5+1

= 88

7.1.4 No: of grids in Y direction Ny = (B/Ds)+1

= 162/3.5+1

= 48

7.1.5 Total length of conductors Lc = L.Ny + B.Nx

= 302 x 48 + 162 x 88

= 28752 m
LARSEN & TOUBRO LIMITED Page 5 of 71
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!

7.1.6 Total length of electrodes Lr = 72 x 3


LARSEN & TOUBRO LIMITED Page 6 of 71
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!
= 216 m

7.1.7 Peripheral length of Grid Lp = 2 x (L + B)

= 2 x ( 302 + 162 )

= 928 m

7.1.8 Maximum distance between two points on grid D m = √(L2 + B2)

= √ ( 302 ²+ 162 ²)

= 343 m
7.1.9 Geometric factor n
na = 2.Lc/Lp (IEEE-80 Eq. no. 85 page no 93)

= 2 x 28752 / 928

= 62.0

nb = √(Lp/(4 x √Ag)) (IEEE-80 Eq. no. 86 page no 93)

= √(928/( 4 x √48924))

= 1.0

nc = (L.B/Ag) 0.7 A/(L.B)


(IEEE-80 Eq. no. 87 page no 93)

= (302 x 162/48924)

= 1.0

nd = Dm/√(L2+B2) (IEEE-80 Eq. no. 88 page no 93)

= 343/√(302²+162²)

= 1.0

n = na . n b . n c . n d (IEEE-80 Eq. no. 84 page no 93)

= 62.0 x 1.0 x 1.0 x 1.0

= 63.5
LARSEN & TOUBRO LIMITED Page 7 of 71
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!

7.2.0 TOLERABLE TOUCH POTENTIAL

Etouch = ( 1000 + 1.5 Cs rs ) * 0.116 / √ts (IEEE-80 Eq. no. 32 page no 27)

Cs = 1 - 0.09 ( 1- r/rs) / ( 2 hs + 0.09) (IEEE-80 Eq. no. 27 page no 23)

= 1-0.09*(1-334/5000)/(2*0.15+0.09)

= 0.7846

Etouch = ( 1000 + 1.5 Cs rs ) * 0.116 / √ts

= (1000 + 1.5 * 0.7846 * 5000 ) * 0.116 / √ 1.0

= 798.62 V

7.3.0 TOLERABLE STEP POTENTIAL

Estep = ( 1000 + 6.0 *Cs * rs ) * 0.116 / √ts (IEEE-80 Eq. no. 29 page no 27)

= (1000 + 6.0 * 0.7846 * 5000 ) * 0.116 / √ 1.0

= 2846.50 V

7.4.0 TOUCH POTENTIAL ATTAINABLE

Emesh = r K m Ki I / L m (IEEE-80 Eq. no. 80 page no 91)

Lm = Lc + Lr (IEEE-80 Eq. no. 90 page no 94)

= 28752+216

= 28968 m

Km = 1 . ln Ds2 + (Ds + 2h ) 2
-h + Kii ln 8 (IEEE-80 Eq. no. 81 page no 93)
2p 16 hd 8 Ds d 4d Kh p (2n-1)

Kii = 1.00 for grids with ground rods in perimeter (IEEE-80 Eq. no. 82 page no 93)

1/(2n)2/n for grids with no ground round rods or grids with only a few ground rods

Here we consider grids with ground rods in perimeter

ho = 1.00 m ( reference depth of grid)


LARSEN & TOUBRO LIMITED Page 8 of 71
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!

Kh = √(1+h/ho) (IEEE-80 Eq. no. 83 page no 93)


LARSEN & TOUBRO LIMITED Page 9 of 71
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!

= √( 1 + 0.6 / 1.0 )

= 1.2649

Km = 1 . Ln 3.5² + (3.5 + 2*0.60 )² 0.6 +1 8


2π #REF! ### #REF! 1.26 334 (2*63.5-1)

= #REF!

Ki = 0.644 + 0.148 * n (IEEE-80 Eq. no. 89 page no 94)

= 0.644 + 0.148 *63.5

= 10.0364

Emesh = r K m Ki I / L m (IEEE-80 Eq. no. 80 page no 91)

= #REF!

= #REF! V

7.5.0 STEP POTENTIAL ATTAINABLE

Estep = r K s K i I / Ls (IEEE-80 Eq. no. 92 page no 94)

Ls = 0.75 Lc + 0.85 Lr (IEEE-80 Eq. no. 93 page no 94)

= 0.75 *28752.00+ 0.85* 216.00

= 21747.6 m

n = 63.5 (Higher of the no. of grids in X & Y direction)

Ks = 1* 1 + 1 + 1 (1- 0.5(n-2) ) (IEEE-80 Eq. no. 94 page no 94)


p 2h Ds + h Ds

= ( 1 / 22/7 ) * { 1 / (2 * 0.6 ) + 1 / ( 3.5 + 0.6 ) + 1 / 3.5 * ( 1 - 0.5^(63 - 2 ) }

= 0.4338

Estep = r K s K i I / Ls (IEEE-80 Eq. no. 92 page no 94)

= #REF!

= #REF! V
LARSEN & TOUBRO LIMITED Page 10 of 71
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!

8.0.0 CALCULATION OF GROUNDING RESISTANCE

8.1.0 RESISTANCE OF GROUND RODS

Re = r ln (8 l/dl ) - 1 + 2 K1 l (√nr-1)2 (IEEE-80 Eq. no. 55 page no 66)


2p nr l √Ag

K1 = 1.41-0.04x for H = 0

1.20-0.05x for H = 1/10 √Ag (IEEE-80 Fig no 25 (a) page no 67)

1.13-0.05x for H = 1/6 √Ag

H = 0.6 m

K1 = 1.41-0.04x

= 1.41-0.04(L/B)

= 1.41-0.04*302.00/162.00

= 1.3354

Re = #REF!
(3 / sqrt(48924)) * (sqrt (72)-1)^2 ]
= #REF! ohm

8.2.0 RESISTANCE OF GROUND GRID

Rs = r ln (2 Lc / h) + K1 Lc - K2 (IEEE-80 Eq. no. 54 page no 66)


p Lc √Ag

K2 = 5.50+0.15x for H = 0

4.68+0.10x for H = 1/10 √Ag (IEEE-80 Fig no 25 (b) page no 67)

4.40-0.05x for H = 1/6 √Ag

K2 = 4.68+0.10x

= 4.68+0.10(L/B)

= 4.68+0.10*302.00/162.00

= 4.87
LARSEN & TOUBRO LIMITED Page 11 of 71
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!
h' = √(d . h)
LARSEN & TOUBRO LIMITED Page 12 of 71
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!
= #REF!

= #REF!

Rs = #REF!
( 28752 / sqrt (48924.00 )) - 4.866 ]
= #REF! Ohms

8.3.0 MUTUAL RESISTANCE BETWEEN GROUND GRID AND GROUND RODS

Rse = r ln (2 Lc / l) + K1 Lc - K2 +1 (IEEE-80 Eq. no. 56 page no 66)


p Lc √Ag

= 333.55 / (22/7 * 28752) * [ln (2 * 28752 / 3.0 ) + 1.335 *


( 28752.00 / sqrt (48924.00 )) - 4.866 + 1]
= 0.6629 ohms

8.8.0 COMBINED RESISTANCE OF GROUND GRID AND GROUND RODS

Rg = Re . Rs - Rse2 (IEEE-80 Eq. no. 53 page no 66)


Re + Rs - 2Rse

= #REF!
#REF!

= #REF! Ohm

#REF!

9.0.0 RESULTS

9.1.1 Spacing of conductors Ds = 3.5 m

9.1.2 Total length of conductors Lc = 28752 m

9.1.3 Attainable step potential = #REF! V

9.1.4 Attainable touch potential = #REF! V

9.1.5 Tolerable step potential = 2846.50 V

9.1.6 Tolerable touch potential = 798.62 V

#REF!
#REF!

9.1.7 Combined resistance of Grid & ground rods = #REF! ohm #REF!
LARSEN & TOUBRO LIMITED Page 13 of 71
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!

CALCULATIONS ARE BASED ON IEEE Std 80-2000

PURPOSE AND SCOPE

The purpose of the document is to design the Earthmat for the 132 kV GIS-cum Control Room Building Layout at BPRS . The important aspect is
that the design should achieve "Tolerable Touch and Step potential " with the Earth grid resistance less than 1 ohm.

6.0.0 DESIGN INPUT

6.1.0 SYSTEM PARAMETERS

6.1.1 System Voltage = 400 kV

6.1.2 System Grounding = Solid

6.1.3 Maximum Fault Current If = #REF! (Spec Write up Cl. No:2.0)

6.1.4 Current Distribution Factor = #REF! (Refer Annexure- A & B)

(Current Distribution factor is considered as per Cl 15.6 of IEEE-80,2000 and Methodology is as per IEEE Transaction on Power
Apparatus and systems "Current for Design of Grounding System" ,Vol PAS .103,No.9,Sep 1984)

6.1.5 Maximum Fault Current considered Ig = #REF!

= #REF!

6.1.6 Duration of Fault Current ts = 1.00 s

6.1.7 Fault Clearing time ts = 1.00 s (specification Secion D4 Cl.


No:2.1.3)

6.6.0 ENVIRONMENTAL PARAMETERS

6.6.1 Soil Resistivity r = 333.55 ohm.m (Refer Soil Resistivity Report)

6.6.2 Top Layer resistivity (Crushed rock) rs = 3000 ohm.m (As per IEEE-80 cl. No:12.5)

6.6.3 Length of Switchyard L = 320 m (Drg .O10178-E-SY-AS-EL-0024)

6.6.4 Breadth of Switchyard B = 170.0 m (Drg .O10178-E-SY-AS-EL-0024)

6.3.0 OTHER DETAILS

6.3.1 Conductor diameter d = #REF! (Refer Conductor sizing calculation)

6.3.2 Conductor Area = #REF!

6.3.3 Depth of burial (minimum) h = 0.6 m


LARSEN & TOUBRO LIMITED Page 14 of 71
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!

6.3.4 Depth of Top Layer hs = 0.15 m (Assumed)


LARSEN & TOUBRO LIMITED Page 15 of 71
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!

6.3.5 No of electrodes
Reactor = 0 (1Nos x (2 Body +2 Neutral)
IC Transformer = 8 (2Nos x (2 Body +2 Neutral)
Lightning Arrester = 12 (12Nos x 1)
CVT = 12 (12Nos x 1)
Lightning Mast = 0 (0Nos x 1)
Tower with Peak = 30 (30Nos x 1)
Fence = 10 (10Nos X 1)

6.3.5 No of electrodes nr = 72

6.3.6 Length of electrode l = 3m

6.3.7 Diameter of electrode - GI Pipe dl = 32 mm

7.0.0 CALCULATIONS

7.1.0 CALCULATIONS - PRELIMINARY

7.1.1 Area of Switchyard Ag = LxB

= 320 x 170

= 54400 Sq.m

7.1.2 Spacing of Conductors Ds = 4.0 m

7.1.3 No: of grids in X direction Nx = (L/Ds)+1

= 320/4.0+1

= 81

7.1.4 No: of grids in Y direction Ny = (B/Ds)+1

= 170/4.0+1

= 44

7.1.5 Total length of conductors Lc = L.Ny + B.Nx

= 320 x 44 + 170 x 81

= 27850 m
LARSEN & TOUBRO LIMITED Page 16 of 71
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!

7.1.6 Total length of electrodes Lr = 72 x 3


LARSEN & TOUBRO LIMITED Page 17 of 71
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!
= 216 m

7.1.7 Peripheral length of Grid Lp = 2 x (L + B)

= 2 x ( 320 + 170 )

= 980 m

7.1.8 Maximum distance between two points on grid D m = √(L2 + B2)

= √ ( 320 ²+ 170 ²)

= 362 m
7.1.9 Geometric factor n
na = 2.Lc/Lp (IEEE-80 Eq. no. 85 page no 93)

= 2 x 27850 / 980

= 56.8

nb = √(Lp/(4 x √Ag)) (IEEE-80 Eq. no. 86 page no 93)

= √(980/( 4 x √54400))

= 1.0

nc = (L.B/Ag) 0.7 A/(L.B)


(IEEE-80 Eq. no. 87 page no 93)

= (320 x 170/54400)

= 1.0

nd = Dm/√(L2+B2) (IEEE-80 Eq. no. 88 page no 93)

= 362/√(320²+170²)

= 1.0

n = na . n b . n c . n d (IEEE-80 Eq. no. 84 page no 93)

= 56.8 x 1.0 x 1.0 x 1.0

= 58.3
LARSEN & TOUBRO LIMITED Page 18 of 71
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!

7.2.0 TOLERABLE TOUCH POTENTIAL

Etouch = ( 1000 + 1.5 Cs rs ) * 0.116 / √ts (IEEE-80 Eq. no. 32 page no 27)

Cs = 1 - 0.09 ( 1- r/rs) / ( 2 hs + 0.09) (IEEE-80 Eq. no. 27 page no 23)

= 1-0.09*(1-334/3000)/(2*0.15+0.09)

= 0.7949

Etouch = ( 1000 + 1.5 Cs rs ) * 0.116 / √ts

= (1000 + 1.5 * 0.7949 * 3000 ) * 0.116 / √ 1.0

= 530.93 V

7.3.0 TOLERABLE STEP POTENTIAL

Estep = ( 1000 + 6.0 *Cs * rs ) * 0.116 / √ts (IEEE-80 Eq. no. 29 page no 27)

= (1000 + 6.0 * 0.7949 * 3000 ) * 0.116 / √ 1.0

= 1775.73 V

7.4.0 TOUCH POTENTIAL ATTAINABLE

Emesh = r K m Ki I / L m (IEEE-80 Eq. no. 80 page no 91)

Lm = Lc + Lr (IEEE-80 Eq. no. 90 page no 94)

= 27850+216

= 28066 m

Km = 1 . ln Ds2 + (Ds + 2h ) 2
-h + Kii ln 8 (IEEE-80 Eq. no. 81 page no 93)
2p 16 hd 8 Ds d 4d Kh p (2n-1)

Kii = 1.00 for grids with ground rods in perimeter (IEEE-80 Eq. no. 82 page no 93)

1/(2n)2/n for grids with no ground round rods or grids with only a few ground rods

Here we consider grids with ground rods in perimeter

ho = 1.00 m ( reference depth of grid)


LARSEN & TOUBRO LIMITED Page 19 of 71
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!

Kh = √(1+h/ho) (IEEE-80 Eq. no. 83 page no 93)


LARSEN & TOUBRO LIMITED Page 20 of 71
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!

= √( 1 + 0.6 / 1.0 )

= 1.2649

Km = 1 . Ln 4.0² + (4.0 + 2*0.60 )² 0.6 +1 8


2π #REF! ### #REF! 1.26 334 (2*58.3-1)

= #REF!

Ki = 0.644 + 0.148 * n (IEEE-80 Eq. no. 89 page no 94)

= 0.644 + 0.148 *58.3

= 9.2653

Emesh = r K m Ki I / L m (IEEE-80 Eq. no. 80 page no 91)

= #REF!

= #REF! V

7.5.0 STEP POTENTIAL ATTAINABLE

Estep = r K s K i I / Ls (IEEE-80 Eq. no. 92 page no 94)

Ls = 0.75 Lc + 0.85 Lr (IEEE-80 Eq. no. 93 page no 94)

= 0.75 *27850.00+ 0.85* 216.00

= 21071.1 m

n = 58.3 (Higher of the no. of grids in X & Y direction)

Ks = 1* 1 + 1 + 1 (1- 0.5(n-2) ) (IEEE-80 Eq. no. 94 page no 94)


p 2h Ds + h Ds

= ( 1 / 22/7 ) * { 1 / (2 * 0.6 ) + 1 / ( 4.0 + 0.6 ) + 1 / 4.0 * ( 1 - 0.5^(58 - 2 ) }

= 0.4140

Estep = r K s K i I / Ls (IEEE-80 Eq. no. 92 page no 94)

= #REF!

= #REF! V
LARSEN & TOUBRO LIMITED Page 21 of 71
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!

8.0.0 CALCULATION OF GROUNDING RESISTANCE

8.1.0 RESISTANCE OF GROUND RODS

Re = r ln (8 l/dl ) - 1 + 2 K1 l (√nr-1)2 (IEEE-80 Eq. no. 55 page no 66)


2p nr l √Ag

K1 = 1.41-0.04x for H = 0

1.20-0.05x for H = 1/10 √Ag (IEEE-80 Fig no 25 (a) page no 67)

1.13-0.05x for H = 1/6 √Ag

H = 0.6 m

K1 = 1.41-0.04x

= 1.41-0.04(L/B)

= 1.41-0.04*320.00/170.00

= 1.3347

Re = #REF!
(3 / sqrt(54400)) * (sqrt (72)-1)^2 ]
= #REF! ohm

8.2.0 RESISTANCE OF GROUND GRID

Rs = r ln (2 Lc / h) + K1 Lc - K2 (IEEE-80 Eq. no. 54 page no 66)


p Lc √Ag

K2 = 5.50+0.15x for H = 0

4.68+0.10x for H = 1/10 √Ag (IEEE-80 Fig no 25 (b) page no 67)

4.40-0.05x for H = 1/6 √Ag

K2 = 4.68+0.10x

= 4.68+0.10(L/B)

= 4.68+0.10*320.00/170.00

= 4.87
LARSEN & TOUBRO LIMITED Page 22 of 71
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!
h' = √(d . h)
LARSEN & TOUBRO LIMITED Page 23 of 71
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!
= #REF!

= #REF!

Rs = #REF!
( 27850 / sqrt (54400.00 )) - 4.868 ]
= #REF! Ohms

8.3.0 MUTUAL RESISTANCE BETWEEN GROUND GRID AND GROUND RODS

Rse = r ln (2 Lc / l) + K1 Lc - K2 +1 (IEEE-80 Eq. no. 56 page no 66)


p Lc √Ag

= 333.55 / (22/7 * 27850) * [ln (2 * 27850 / 3.0 ) + 1.335 *


( 27850.00 / sqrt (54400.00 )) - 4.868 + 1]
= 0.6300 ohms

8.8.0 COMBINED RESISTANCE OF GROUND GRID AND GROUND RODS

Rg = Re . Rs - Rse2 (IEEE-80 Eq. no. 53 page no 66)


Re + Rs - 2Rse

= #REF!
#REF!

= #REF! Ohm

#REF!

9.0.0 RESULTS

9.1.1 Spacing of conductors Ds = 4 m

9.1.2 Total length of conductors Lc = 27850 m

9.1.3 Attainable step potential = #REF! V

9.1.4 Attainable touch potential = #REF! V

9.1.5 Tolerable step potential = 1775.73 V

9.1.6 Tolerable touch potential = 530.93 V

#REF!
#REF!

9.1.7 Combined resistance of Grid & ground rods = #REF! ohm #REF!
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!

CALCULATIONS ARE BASED ON IEEE Std 80-2000

PURPOSE AND SCOPE

The purpose of the document is to design the Earthmat for the 132 kV GIS-cum Control Room Building Layout at BPRS . The important aspect is
that the design should achieve "Tolerable Touch and Step potential " with the Earth grid resistance less than 1 ohm.

6.0.0 DESIGN INPUT

6.1.0 SYSTEM PARAMETERS

6.1.1 System Voltage = 400 kV

6.1.2 System Grounding = Solid

6.1.3 Maximum Fault Current If = #REF! (Spec Write up Cl. No:2.0)

6.1.4 Current Distribution Factor = 100.00% (Refer Annexure- A & B)

(Current Distribution factor is considered as per Cl 15.6 of IEEE-80,2000 and Methodology is as per IEEE Transaction on Power
Apparatus and systems "Current for Design of Grounding System" ,Vol PAS .103,No.9,Sep 1984)

6.1.5 Maximum Fault Current considered Ig = #REF!

= #REF!

6.1.6 Duration of Fault Current ts = 1.00 s

6.1.7 Fault Clearing time ts = 1.00 s (specification Secion D4 Cl.


No:2.1.3)

6.6.0 ENVIRONMENTAL PARAMETERS

6.6.1 Soil Resistivity r = 333.55 ohm.m (Refer Soil Resistivity Report)

6.6.2 Top Layer resistivity (Crushed rock) rs = 5000 ohm.m (As per IEEE-80 cl. No:12.5)

6.6.3 Length of Switchyard L = 302 m (Drg .O10178-E-SY-AS-EL-0024)

6.6.4 Breadth of Switchyard B = 162.0 m (Drg .O10178-E-SY-AS-EL-0024)

6.3.0 OTHER DETAILS

6.3.1 Conductor diameter d = #REF! (Refer Conductor sizing calculation)

6.3.2 Conductor Area = #REF!

6.3.3 Depth of burial (minimum) h = 0.6 m

6.3.4 Depth of Top Layer hs = 0.15 m (Assumed)


LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!

6.3.5 No of electrodes
Reactor = 0 (1Nos x (2 Body +2 Neutral)
IC Transformer = 8 (2Nos x (2 Body +2 Neutral)
Lightning Arrester = 12 (12Nos x 1)
CVT = 12 (12Nos x 1)
Lightning Mast = 0 (0Nos x 1)
Tower with Peak = 30 (30Nos x 1)
Fence = 10 (10Nos X 1)

6.3.5 No of electrodes nr = 72

6.3.6 Length of electrode l = 3m

6.3.7 Diameter of electrode - GI Pipe dl = 50 mm

7.0.0 CALCULATIONS

7.1.0 CALCULATIONS - PRELIMINARY

7.1.1 Area of Switchyard Ag = LxB

= 302 x 162

= 48924 Sq.m

7.1.2 Spacing of Conductors Ds = 3.5 m

7.1.3 No: of grids in X direction Nx = (L/Ds)+1

= 302/3.5+1

= 88

7.1.4 No: of grids in Y direction Ny = (B/Ds)+1

= 162/3.5+1

= 48

7.1.5 Total length of conductors Lc = L.Ny + B.Nx

= 302 x 48 + 162 x 88

= 28752 m

7.1.6 Total length of electrodes Lr = 72 x 3


LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!
= 216 m

7.1.7 Peripheral length of Grid Lp = 2 x (L + B)

= 2 x ( 302 + 162 )

= 928 m

7.1.8 Maximum distance between two points on grid D m = √(L2 + B2)

= √ ( 302 ²+ 162 ²)

= 343 m
7.1.9 Geometric factor n
na = 2.Lc/Lp (IEEE-80 Eq. no. 85 page no 93)

= 2 x 28752 / 928

= 62.0

nb = √(Lp/(4 x √Ag)) (IEEE-80 Eq. no. 86 page no 93)

= √(928/( 4 x √48924))

= 1.0

nc = (L.B/Ag) 0.7 A/(L.B)


(IEEE-80 Eq. no. 87 page no 93)

= (302 x 162/48924)

= 1.0

nd = Dm/√(L2+B2) (IEEE-80 Eq. no. 88 page no 93)

= 343/√(302²+162²)

= 1.0

n = na . n b . n c . n d (IEEE-80 Eq. no. 84 page no 93)

= 62.0 x 1.0 x 1.0 x 1.0

= 63.5
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!

7.2.0 TOLERABLE TOUCH POTENTIAL

Etouch = ( 1000 + 1.5 Cs rs ) * 0.116 / √ts (IEEE-80 Eq. no. 32 page no 27)

Cs = 1 - 0.09 ( 1- r/rs) / ( 2 hs + 0.09) (IEEE-80 Eq. no. 27 page no 23)

= 1-0.09*(1-334/5000)/(2*0.15+0.09)

= 0.7846

Etouch = ( 1000 + 1.5 Cs rs ) * 0.116 / √ts

= (1000 + 1.5 * 0.7846 * 5000 ) * 0.116 / √ 1.0

= 798.62 V

7.3.0 TOLERABLE STEP POTENTIAL

Estep = ( 1000 + 6.0 *Cs * rs ) * 0.116 / √ts (IEEE-80 Eq. no. 29 page no 27)

= (1000 + 6.0 * 0.7846 * 5000 ) * 0.116 / √ 1.0

= 2846.50 V

7.4.0 TOUCH POTENTIAL ATTAINABLE

Emesh = r K m Ki I / L m (IEEE-80 Eq. no. 80 page no 91)

Lm = Lc + Lr (IEEE-80 Eq. no. 90 page no 94)

= 28752+216

= 28968 m

Km = 1 . ln Ds2 + (Ds + 2h ) 2
-h + Kii ln 8 (IEEE-80 Eq. no. 81 page no 93)
2p 16 hd 8 Ds d 4d Kh p (2n-1)

Kii = 1.00 for grids with ground rods in perimeter (IEEE-80 Eq. no. 82 page no 93)

1/(2n)2/n for grids with no ground round rods or grids with only a few ground rods

Here we consider grids with ground rods in perimeter

ho = 1.00 m ( reference depth of grid)

Kh = √(1+h/ho) (IEEE-80 Eq. no. 83 page no 93)


LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!

= √( 1 + 0.6 / 1.0 )

= 1.2649

Km = 1 . Ln 3.5² + (3.5 + 2*0.60 )² 0.6 +1 8


2π #REF! ### #REF! 1.26 334 (2*63.5-1)

= #REF!

Ki = 0.644 + 0.148 * n (IEEE-80 Eq. no. 89 page no 94)

= 0.644 + 0.148 *63.5

= 10.0364

Emesh = r K m Ki I / L m (IEEE-80 Eq. no. 80 page no 91)

= #REF!

= #REF! V

7.5.0 STEP POTENTIAL ATTAINABLE

Estep = r K s K i I / Ls (IEEE-80 Eq. no. 92 page no 94)

Ls = 0.75 Lc + 0.85 Lr (IEEE-80 Eq. no. 93 page no 94)

= 0.75 *28752.00+ 0.85* 216.00

= 21747.6 m

n = 63.5 (Higher of the no. of grids in X & Y direction)

Ks = 1* 1 + 1 + 1 (1- 0.5(n-2) ) (IEEE-80 Eq. no. 94 page no 94)


p 2h Ds + h Ds

= ( 1 / 22/7 ) * { 1 / (2 * 0.6 ) + 1 / ( 3.5 + 0.6 ) + 1 / 3.5 * ( 1 - 0.5^(63 - 2 ) }

= 0.4338

Estep = r K s K i I / Ls (IEEE-80 Eq. no. 92 page no 94)

= #REF!

= #REF! V
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!

8.0.0 CALCULATION OF GROUNDING RESISTANCE

8.1.0 RESISTANCE OF GROUND RODS

Re = r ln (8 l/dl ) - 1 + 2 K1 l (√nr-1)2 (IEEE-80 Eq. no. 55 page no 66)


2p nr l √Ag

K1 = 1.41-0.04x for H = 0

1.20-0.05x for H = 1/10 √Ag (IEEE-80 Fig no 25 (a) page no 67)

1.13-0.05x for H = 1/6 √Ag

H = 0.6 m

K1 = 1.41-0.04x

= 1.41-0.04(L/B)

= 1.41-0.04*302.00/162.00

= 1.3354

Re = #REF!
(3 / sqrt(48924)) * (sqrt (72)-1)^2 ]
= #REF! ohm

8.2.0 RESISTANCE OF GROUND GRID

Rs = r ln (2 Lc / h) + K1 Lc - K2 (IEEE-80 Eq. no. 54 page no 66)


p Lc √Ag

K2 = 5.50+0.15x for H = 0

4.68+0.10x for H = 1/10 √Ag (IEEE-80 Fig no 25 (b) page no 67)

4.40-0.05x for H = 1/6 √Ag

K2 = 4.68+0.10x

= 4.68+0.10(L/B)

= 4.68+0.10*302.00/162.00

= 4.87

h' = √(d . h)
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!
= #REF!

= #REF!

Rs = #REF!
( 28752 / sqrt (48924.00 )) - 4.866 ]
= #REF! Ohms

8.3.0 MUTUAL RESISTANCE BETWEEN GROUND GRID AND GROUND RODS

Rse = r ln (2 Lc / l) + K1 Lc - K2 +1 (IEEE-80 Eq. no. 56 page no 66)


p Lc √Ag

= 333.55 / (22/7 * 28752) * [ln (2 * 28752 / 3.0 ) + 1.335 *


( 28752.00 / sqrt (48924.00 )) - 4.866 + 1]
= 0.6629 ohms

8.8.0 COMBINED RESISTANCE OF GROUND GRID AND GROUND RODS

Rg = Re . Rs - Rse2 (IEEE-80 Eq. no. 53 page no 66)


Re + Rs - 2Rse

= #REF!
#REF!

= #REF! Ohm

#REF!

9.0.0 RESULTS

9.1.1 Spacing of conductors Ds = 3.5 m

9.1.2 Total length of conductors Lc = 28752 m

9.1.3 Attainable step potential = #REF! V

9.1.4 Attainable touch potential = #REF! V

9.1.5 Tolerable step potential = 2846.50 V

9.1.6 Tolerable touch potential = 798.62 V

#REF!
#REF!

9.1.7 Combined resistance of Grid & ground rods = #REF! ohm #REF!
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!

CALCULATIONS ARE BASED ON IEEE Std 80-2000

PURPOSE AND SCOPE

The purpose of the document is to design the Earthmat for the 132 kV GIS-cum Control Room Building Layout at BPRS . The important aspect is
that the design should achieve "Tolerable Touch and Step potential " with the Earth grid resistance less than 1 ohm.

6.0.0 DESIGN INPUT

6.1.0 SYSTEM PARAMETERS

6.1.1 System Voltage = 400 kV

6.1.2 System Grounding = Solid

6.1.3 Maximum Fault Current If = 50000 A (Spec Write up Cl. No:2.0)

6.1.4 Current Distribution Factor = 100.00% (Refer Annexure- A & B)

(Current Distribution factor is considered as per Cl 15.6 of IEEE-80,2000 and Methodology is as per IEEE Transaction on Power
Apparatus and systems "Current for Design of Grounding System" ,Vol PAS .103,No.9,Sep 1984)

6.1.5 Maximum Fault Current considered Ig = 50000 x 1.0000

= 50000 A

6.1.6 Duration of Fault Current ts = 1.00 s

6.1.7 Fault Clearing time ts = 1.00 s (specification Secion D4 Cl.


No:2.1.3)

6.6.0 ENVIRONMENTAL PARAMETERS

6.6.1 Soil Resistivity r = 333.55 ohm.m (Refer Soil Resistivity Report)

6.6.2 Top Layer resistivity (Crushed rock) rs = 5000 ohm.m (As per IEEE-80 cl. No:12.5)

6.6.3 Length of Switchyard L = 302 m (Drg .O10178-E-SY-AS-EL-0024)

6.6.4 Breadth of Switchyard B = 162.0 m (Drg .O10178-E-SY-AS-EL-0024)

6.3.0 OTHER DETAILS

6.3.1 Conductor diameter d = #REF! (Refer Conductor sizing calculation)

6.3.2 Conductor Area = #REF!

6.3.3 Depth of burial (minimum) h = 0.6 m

6.3.4 Depth of Top Layer hs = 0.15 m (Assumed)


LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!

6.3.5 No of electrodes
Reactor = 0 (1Nos x (2 Body +2 Neutral)
IC Transformer = 8 (2Nos x (2 Body +2 Neutral)
Lightning Arrester = 12 (12Nos x 1)
CVT = 12 (12Nos x 1)
Lightning Mast = 0 (0Nos x 1)
Tower with Peak = 30 (30Nos x 1)
Fence = 10 (10Nos X 1)

6.3.5 No of electrodes nr = 72

6.3.6 Length of electrode l = 3m

6.3.7 Diameter of electrode - GI Pipe dl = 50 mm

7.0.0 CALCULATIONS

7.1.0 CALCULATIONS - PRELIMINARY

7.1.1 Area of Switchyard Ag = LxB

= 302 x 162

= 48924 Sq.m

7.1.2 Spacing of Conductors Ds = 4.0 m

7.1.3 No: of grids in X direction Nx = (L/Ds)+1

= 302/4.0+1

= 77

7.1.4 No: of grids in Y direction Ny = (B/Ds)+1

= 162/4.0+1

= 42

7.1.5 Total length of conductors Lc = L.Ny + B.Nx

= 302 x 42 + 162 x 77

= 25158 m

7.1.6 Total length of electrodes Lr = 72 x 3


LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!
= 216 m

7.1.7 Peripheral length of Grid Lp = 2 x (L + B)

= 2 x ( 302 + 162 )

= 928 m

7.1.8 Maximum distance between two points on grid D m = √(L2 + B2)

= √ ( 302 ²+ 162 ²)

= 343 m
7.1.9 Geometric factor n
na = 2.Lc/Lp (IEEE-80 Eq. no. 85 page no 93)

= 2 x 25158 / 928

= 54.2

nb = √(Lp/(4 x √Ag)) (IEEE-80 Eq. no. 86 page no 93)

= √(928/( 4 x √48924))

= 1.0

nc = (L.B/Ag) 0.7 A/(L.B)


(IEEE-80 Eq. no. 87 page no 93)

= (302 x 162/48924)

= 1.0

nd = Dm/√(L2+B2) (IEEE-80 Eq. no. 88 page no 93)

= 343/√(302²+162²)

= 1.0

n = na . n b . n c . n d (IEEE-80 Eq. no. 84 page no 93)

= 54.2 x 1.0 x 1.0 x 1.0

= 55.5
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!

7.2.0 TOLERABLE TOUCH POTENTIAL

Etouch = ( 1000 + 1.5 Cs rs ) * 0.116 / √ts (IEEE-80 Eq. no. 32 page no 27)

Cs = 1 - 0.09 ( 1- r/rs) / ( 2 hs + 0.09) (IEEE-80 Eq. no. 27 page no 23)

= 1-0.09*(1-334/5000)/(2*0.15+0.09)

= 0.7846

Etouch = ( 1000 + 1.5 Cs rs ) * 0.116 / √ts

= (1000 + 1.5 * 0.7846 * 5000 ) * 0.116 / √ 1.0

= 798.62 V

7.3.0 TOLERABLE STEP POTENTIAL

Estep = ( 1000 + 6.0 *Cs * rs ) * 0.116 / √ts (IEEE-80 Eq. no. 29 page no 27)

= (1000 + 6.0 * 0.7846 * 5000 ) * 0.116 / √ 1.0

= 2846.50 V

7.4.0 TOUCH POTENTIAL ATTAINABLE

Emesh = r K m Ki I / L m (IEEE-80 Eq. no. 80 page no 91)

Lm = Lc + Lr (IEEE-80 Eq. no. 90 page no 94)

= 25158+216

= 25374 m

Km = 1 . ln Ds2 + (Ds + 2h ) 2
-h + Kii ln 8 (IEEE-80 Eq. no. 81 page no 93)
2p 16 hd 8 Ds d 4d Kh p (2n-1)

Kii = 1.00 for grids with ground rods in perimeter (IEEE-80 Eq. no. 82 page no 93)

1/(2n)2/n for grids with no ground round rods or grids with only a few ground rods

Here we consider grids with ground rods in perimeter

ho = 1.00 m ( reference depth of grid)

Kh = √(1+h/ho) (IEEE-80 Eq. no. 83 page no 93)


LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!

= √( 1 + 0.6 / 1.0 )

= 1.2649

Km = 1 . Ln 4.0² + (4.0 + 2*0.60 )² 0.6 +1 8


2π #REF! ### #REF! 1.26 334 (2*55.5-1)

= #REF!

Ki = 0.644 + 0.148 * n (IEEE-80 Eq. no. 89 page no 94)

= 0.644 + 0.148 *55.5

= 8.8623

Emesh = r K m Ki I / L m (IEEE-80 Eq. no. 80 page no 91)

= #REF!

= #REF! V

7.5.0 STEP POTENTIAL ATTAINABLE

Estep = r K s K i I / Ls (IEEE-80 Eq. no. 92 page no 94)

Ls = 0.75 Lc + 0.85 Lr (IEEE-80 Eq. no. 93 page no 94)

= 0.75 *25158.00+ 0.85* 216.00

= 19052.1 m

n = 55.5 (Higher of the no. of grids in X & Y direction)

Ks = 1* 1 + 1 + 1 (1- 0.5(n-2) ) (IEEE-80 Eq. no. 94 page no 94)


p 2h Ds + h Ds

= ( 1 / 22/7 ) * { 1 / (2 * 0.6 ) + 1 / ( 4.0 + 0.6 ) + 1 / 4.0 * ( 1 - 0.5^(56 - 2 ) }

= 0.4140

Estep = r K s K i I / Ls (IEEE-80 Eq. no. 92 page no 94)

= ( 333.55 * 0.4140 * 8.8623 * 50000 ) / 19052.1

= 3211.97 V
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!

8.0.0 CALCULATION OF GROUNDING RESISTANCE

8.1.0 RESISTANCE OF GROUND RODS

Re = r ln (8 l/dl ) - 1 + 2 K1 l (√nr-1)2 (IEEE-80 Eq. no. 55 page no 66)


2p nr l √Ag

K1 = 1.41-0.04x for H = 0

1.20-0.05x for H = 1/10 √Ag (IEEE-80 Fig no 25 (a) page no 67)

1.13-0.05x for H = 1/6 √Ag

H = 0.6 m

K1 = 1.41-0.04x

= 1.41-0.04(L/B)

= 1.41-0.04*302.00/162.00

= 1.3354

Re = #REF!
(3 / sqrt(48924)) * (sqrt (72)-1)^2 ]
= #REF! ohm

8.2.0 RESISTANCE OF GROUND GRID

Rs = r ln (2 Lc / h) + K1 Lc - K2 (IEEE-80 Eq. no. 54 page no 66)


p Lc √Ag

K2 = 5.50+0.15x for H = 0

4.68+0.10x for H = 1/10 √Ag (IEEE-80 Fig no 25 (b) page no 67)

4.40-0.05x for H = 1/6 √Ag

K2 = 4.68+0.10x

= 4.68+0.10(L/B)

= 4.68+0.10*302.00/162.00

= 4.87

h' = √(d . h)
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!
= #REF!

= #REF!

Rs = #REF!
( 25158 / sqrt (48924.00 )) - 4.866 ]
= #REF! Ohms

8.3.0 MUTUAL RESISTANCE BETWEEN GROUND GRID AND GROUND RODS

Rse = r ln (2 Lc / l) + K1 Lc - K2 +1 (IEEE-80 Eq. no. 56 page no 66)


p Lc √Ag

= 333.55 / (22/7 * 25158) * [ln (2 * 25158 / 3.0 ) + 1.335 *


( 25158.00 / sqrt (48924.00 )) - 4.866 + 1]
= 0.6655 ohms

8.8.0 COMBINED RESISTANCE OF GROUND GRID AND GROUND RODS

Rg = Re . Rs - Rse2 (IEEE-80 Eq. no. 53 page no 66)


Re + Rs - 2Rse

= #REF!
#REF!

= #REF! Ohm

#REF!

9.0.0 RESULTS

9.1.1 Spacing of conductors Ds = 4 m

9.1.2 Total length of conductors Lc = 25158 m

9.1.3 Attainable step potential = 3211.97 V

9.1.4 Attainable touch potential = #REF! V

9.1.5 Tolerable step potential = 2846.50 V

9.1.6 Tolerable touch potential = 798.62 V

#REF!
Attainable Estep is greater than Tolerable Estep

9.1.7 Combined resistance of Grid & ground rods = #REF! ohm #REF!
4

Page 38
5

Page 39
6

Page 40
7

Page 41
8

Page 42
9

Page 43
10

10

Page 44
11

11

Page 45
12

12

Page 46
13

13

Page 47
14

14

Page 48
15

15

Page 49
16

16

Page 50
17

17

Page 51
18

18

Page 52
19

19

Page 53
20

20

Page 54
21

21

Page 55
22

22

Page 56
LARSEN & TOUBRO LIMITED 57 of 71
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!
Annexure-A

A.1 Input Data Dgg' - 8.0m


V (Nominal Voltage) = 400 KV g g'

Max. Voltage = 420 kV

A = 9 m a a'

A - 9m
B = 9 m Daa' - 13.24m
b b'
G = 24.86 m

H - 50.9m
B - 9m Dbb' - 14.36m
H = 50.9 m

c c'
Dgg' = 7.95 m 0
Dcc' - 16.9m 8.45
G - 24.86m

Daa' = 13.24 m

Dbb' = 14.36 m

Dcc' = 16.9 m FGL


TYPICAL D/C 400kV TOWER
Design Temperature = 50 deg.C

No. of sub conductors N = 2 (TWIN)

Radius of conductor r = 0.015885 m (ACSR MOOSE)

Subconductor Spacing S = 0.45 m

Resistivity of earth r = 100 ohm-m (Typical Value for Transmission Line)

System frequency f = 50 Hz

Length of Line = 150 kM

A.2 METHODOLOGY
IEEE Transactions on Power Apparatus and Systems, Vol. PAS-103, No.9 September 1984.
The mutual and self impedance of a system can be calculated as follows.

Mutual impedance Zgm = 0.000988 * f + j 0.0028938 * f * log10(De/GMD) ohms/ km -------1

Self impedance Zg = Rc + 0.000988 * f + j 0.0028938 * f * log10(De/GMR) ohms/ km -------2

Where Rc : Resistance of ground wire


GMD : Geometric Mean Distance = (Dab * Dbc *Dca )1/3
GMR : Geometric Mean Radius = (Dsa * Dsb *Dsc )1/3
De : Equivalent depth of earth return 658.4 *√ (r / f)
LARSEN & TOUBRO LIMITED 58 of 71
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!

A.3 Calculation of Equivalent Depth of Earth Return (De)


De = 658.4 √ (r / f)

= 658.4 * √(100 / 50)

= 931.12 m

A.4 Calculation of Geometric Mean Radius (GMR)

Bundle radius A = S/2 / sin ( p / N)

= 0.000225 m

GMR of bundled conductor GMRb = (N r AN-1) 1/N

= (2 * (0.01589) * 0.0002^(2-1))^ 1/2

= 0.0027 m

Dsa = √( GMRb * Daa')

= 0.1881 m

Dsb = √(GMRb * Dbb')

= 0.1959 m

Dsc = √(GMRb * Dcc')

= 0.2126 m

Geometrical Mean Radius = ³√(Dsa . Dsb . Dsc)

= ³√(0.1881 *0.1959 * 0.2126)

= 0.1986 m

A.5 Calculation of Geometric mean Distance (GMD)

From the above GA of tower ,

Dab = Da'b' = 9.02 m Da'b =Dab' = 16.48 m


Dbc = Db'c'= 9.09 m Dbc' =Dcb' = 18.04 m (From Tower Geometry)
Dca = Dc'a'= 18.09 m Dca' =Dac' = 23.48 m

Dab = ( Dab . Da'b . Dab' . Da'b' ) 1/4

= (9.02 *16.48 * 16.48 * 9.02)^ 1/ 4

= 12.19 m

Dbc = ( Dbc . Db'c . Dbc' . Db'c' ) 1/4


LARSEN & TOUBRO LIMITED 59 of 71
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!

= (9.09 *18.04 * 18.04 * 9.09)^ 1/ 4

= 12.80 m

Dca = ( Dca . Dc'a . Dca' . Dc'a' ) 1/4

= (18.09 *23.48 * 23.48 * 18.09)^ 1/ 4

= 20.61 m

Geometrical Mean Distance = ³√(Dab . Dbc . Dca)

= ³√(12.19 *12.80 * 20.61)

= 14.76 m

A.6 Calculation of Ground Conductor resistance (Rc)

DC resistance at 20 Deg. C Rdc50 = 2.50 ohms/km (Typical Data)

M constant for Steel = 153.85

DC resistance at Design Temperature = Rdc20 (M+t2) ohms/km


(M+t1)

Rdc50 = 2.9314 ohms / km

AC resistance by considering Skin effect


Rac50 = k * Rdc50

Where k is a function of X = 0.063598 x √(mrf/Rdc32) (if Rdc is in ohm/mile)

= 0.080680 x √(mrf/Rdc32)

= 10.5369

k = 1.64051

Rac50 = 4.8090 ohms / km


(Typical Value)
No. of earth conductors in a TL Path = 2

Hence equivalent resistance Rc = 2.4045 ohms/ km i.e. Rac50 / 2

A.7 Calculation of Mutual & Self Impedance of Ground Wire

Zgm = 0.000988 * 50 + j 0.0028938 * 50 * Log10( 931.12 / 14.761)

= 0.0494+0.26043i ohm/ km

Zg = 2.4045 + 0.000988 * 50 + j 0.0028938 * 50 * Log10( 931.12 / 0.199)


LARSEN & TOUBRO LIMITED 60 of 71
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!

= 2.4539+0.53115i ohm/ km

A.8 Calculation of Inductance of Line (H/m/ph)

L = ###

A.9 Calculation of Capacitance of Line (F/m/ph)

C = ###

A.9 Calculation of Impedance (SIL) & Maximum Allowable Power that can be transmitted through the Line

Z = ### OHM

P = ### MW

A.9 Calculation of Inductive Reactance of Line (XL)

XL = ### OHM
LARSEN & TOUBRO LIMITED 61 of 71
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!
Annexure-A

A.1 Input Data Dgg' - 0.0m


V (Nominal Voltage) = 220 KV g g'

Max. Voltage = 245 kV

A = 5.28 m a a'

A - 5.28m
B = 5.34 m Daa' - 9m
b b'
G = 19.95 m

H - 35.78m
B - 5.34m Dbb' - 9.36m
H = 35.78 m

c c'
Dgg' = 0 m 0
Dcc' - 9.9m 4.95
G - 19.95m

Daa' = 9.00 m

Dbb' = 9.36 m

Dcc' = 9.90 m FGL


TYPICAL D/C 220kV TOWER
Design Temperature = 50 deg.C

No. of sub conductors N = 1 (SINGLE)

Radius of conductor r = 0.01431 m (ACSR ZEBRA)-SINGLE CIRCUIT

Subconductor Spacing S = 0 m

Resistivity of earth r = 100 ohm-m (Typical Value for Transmission Line)

System frequency f = 50 Hz

Length of Line = 150 kM

A.2 METHODOLOGY
IEEE Transactions on Power Apparatus and Systems, Vol. PAS-103, No.9 September 1984.
The mutual and self impedance of a system can be calculated as follows.

Mutual impedance Zgm = 0.000988 * f + j 0.0028938 * f * log10(De/GMD) ohms/ km -------1

Self impedance Zg = Rc + 0.000988 * f + j 0.0028938 * f * log10(De/GMR) ohms/ km -------2

Where Rc : Resistance of ground wire


GMD : Geometric Mean Distance = (Dab * Dbc *Dca )1/3
GMR : Geometric Mean Radius = (Dsa * Dsb *Dsc )1/3
De : Equivalent depth of earth return 658.4 *√ (r / f)
LARSEN & TOUBRO LIMITED 62 of 71
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!

A.3 Calculation of Equivalent Depth of Earth Return (De)


De = 658.4 √ (r / f)

= 658.4 * √(100 / 50)

= 931.12 m

A.4 Calculation of Geometric Mean Radius (GMRL)

GMRL = 0.0111 m

A.4 Calculation of Geometric Mean Radius (GMRC)

GMRL = 0.0143 m

A.5 Calculation of Geometric mean Distance (GMD)


Geometrical Mean Distance = ³√(Dab . Dbc . Dca)

= 6.69 m

A.6 Calculation of Ground Conductor resistance (Rc)

DC resistance at 20 Deg. C Rdc50 = 2.50 ohms/km (Typical Data)

M constant for Steel = 153.85

DC resistance at Design Temperature = Rdc20 (M+t2) ohms/km


(M+t1)

Rdc50 = 2.9314 ohms / km

AC resistance by considering Skin effect


Rac50 = k * Rdc50

Where k is a function of X = 0.063598 x √(mrf/Rdc32) (if Rdc is in ohm/mile)

= 0.080680 x √(mrf/Rdc32)

= 10.5369

k = 1.64051

Rac50 = 4.8090 ohms / km


(Typical Value)
No. of earth conductors in a TL Path = 2

Hence equivalent resistance Rc = 2.4045 ohms/ km i.e. Rac50 / 2

A.7 Calculation of Mutual & Self Impedance of Ground Wire

Zgm = 0.000988 * 50 + j 0.0028938 * 50 * Log10( 931.12 / 6.690)


LARSEN & TOUBRO LIMITED 63 of 71
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!
= 0.0494+0.31015i ohm/ km

Zg = 2.4045 + 0.000988 * 50 + j 0.0028938 * 50 * Log10( 931.12 / 0.011)

= 2.4539+0.71216i ohm/ km

A.8 Calculation of Inductance of Line (H/m/ph)

L = ###

A.9 Calculation of Capacitance of Line (F/m/ph)

C = ###

A.9 Calculation of Impedance (SIL) & Maximum Allowable Power that can be transmitted through the Line

Z = ### OHM

P = ### MW

A.9 Calculation of Inductive Reactance of Line (XL)

XL = ### OHM
LARSEN & TOUBRO LIMITED 64 of 71
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!
Annexure-A

A.1 Input Data Dgg' - 0.0m


V (Nominal Voltage) = 220 KV g g'

Max. Voltage = 245 kV

A = 5.28 m a a'

A - 5.28m
B = 5.34 m Daa' - 9m
b b'
G = 19.95 m

H - 35.78m
B - 5.34m Dbb' - 9.36m
H = 35.78 m

c c'
Dgg' = 0 m 0
Dcc' - 9.9m 4.95
G - 19.95m

Daa' = 9.00 m

Dbb' = 9.36 m

Dcc' = 9.90 m FGL


TYPICAL D/C 220kV TOWER
Design Temperature = 50 deg.C

No. of sub conductors N = 1 (SINGLE)

Radius of conductor r = 0.01431 m (ACSR ZEBRA)-DOUBLE CIRCUIT

Subconductor Spacing S = 0 m

Resistivity of earth r = 100 ohm-m (Typical Value for Transmission Line)

System frequency f = 50 Hz

Length of Line = 150 kM

A.2 METHODOLOGY
IEEE Transactions on Power Apparatus and Systems, Vol. PAS-103, No.9 September 1984.
The mutual and self impedance of a system can be calculated as follows.

Mutual impedance Zgm = 0.000988 * f + j 0.0028938 * f * log10(De/GMD) ohms/ km -------1

Self impedance Zg = Rc + 0.000988 * f + j 0.0028938 * f * log10(De/GMR) ohms/ km -------2

Where Rc : Resistance of ground wire


GMD : Geometric Mean Distance = (Dab * Dbc *Dca )1/3
GMR : Geometric Mean Radius = (Dsa * Dsb *Dsc )1/3
De : Equivalent depth of earth return 658.4 *√ (r / f)
LARSEN & TOUBRO LIMITED 65 of 71
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!

A.3 Calculation of Equivalent Depth of Earth Return (De)


De = 658.4 √ (r / f)

= 658.4 * √(100 / 50)

= 931.12 m

A.4 Calculation of Geometric Mean Radius (GMRL)


Geometrical Mean Radius = 3
√(GMRa*GMRb*GMRc)

GMRa = √(0.7788*r* Daa')

= 0.317 m

GMRa = √(0.7788*r* Dbb')

= 0.323 m

GMRa = √(0.7788*r* Dcc')

= 0.332 m

GMRL = 0.3239 m

A.4 Calculation of Geometric Mean Radius (GMRC)


Geometrical Mean Radius = 3
√(GMRa*GMRb*GMRc)

GMRa = √(r* Daa')

= 0.359 m

GMRa = √(r* Dbb')

= 0.366 m

GMRa = √(r* Dcc')

= 0.376 m

GMRL = 0.3670 m

A.5 Calculation of Geometric mean Distance (GMD)

From the above GA of tower ,

Dab = Da'b' = 5.28 m Da'b =Dab' = 10.59 m


Dbc = Db'c'= 5.35 m Dbc' =Dcb' = 11.01 m (From Tower Geometry)
Dca = Dc'a'= 10.63 m Dca' =Dac' = 14.22 m

Dab = ( Dab . Da'b . Dab' . Da'b' ) 1/4

= (5.28 *10.59 * 10.59 * 5.28)^ 1/ 4


LARSEN & TOUBRO LIMITED 66 of 71
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!

= 5.28 m

Dbc = ( Dbc . Db'c . Dbc' . Db'c' ) 1/4

= (5.35 *11.01 * 11.01 * 5.35)^ 1/ 4

= 5.34 m

Dca = ( Dca . Dc'a . Dca' . Dc'a' ) 1/4

= (10.63 *14.22 * 14.22 * 10.63)^ 1/ 4

= 10.62 m

Geometrical Mean Distance = ³√(Dab . Dbc . Dca)

= ³√(5.28 *5.34 * 10.62)

= 6.69 m

A.6 Calculation of Ground Conductor resistance (Rc)

DC resistance at 20 Deg. C Rdc50 = 2.50 ohms/km (Typical Data)

M constant for Steel = 153.85

DC resistance at Design Temperature = Rdc20 (M+t2) ohms/km


(M+t1)

Rdc50 = 2.9314 ohms / km

AC resistance by considering Skin effect


Rac50 = k * Rdc50

Where k is a function of X = 0.063598 x √(mrf/Rdc32) (if Rdc is in ohm/mile)

= 0.080680 x √(mrf/Rdc32)

= 10.5369

k = 1.64051

Rac50 = 4.8090 ohms / km


(Typical Value)
No. of earth conductors in a TL Path = 2

Hence equivalent resistance Rc = 2.4045 ohms/ km i.e. Rac50 / 2

A.7 Calculation of Mutual & Self Impedance of Ground Wire

Zgm = 0.000988 * 50 + j 0.0028938 * 50 * Log10( 931.12 / 6.690)


LARSEN & TOUBRO LIMITED 67 of 71
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!

= 0.0494+0.31015i ohm/ km

Zg = 2.4045 + 0.000988 * 50 + j 0.0028938 * 50 * Log10( 931.12 / 0.324)

= 2.4539+0.50043i ohm/ km

A.8 Calculation of Inductance of Line (H/m/ph)

L = ###

A.9 Calculation of Capacitance of Line (F/m/ph)

C = ###

A.9 Calculation of Impedance (SIL) & Maximum Allowable Power that can be transmitted through the Line

Z = ### OHM

P = ### MW

A.9 Calculation of Inductive Reactance of Line (XL)

XL = ### OHM
LARSEN & TOUBRO LIMITED 68 of 71
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!
Annexure-A

A.1 Input Data Dgg' - 0.0m


V (Nominal Voltage) = 220 KV g g'

Max. Voltage = 245 kV

A = 5.28 m a a'

A - 5.28m
B = 5.34 m Daa' - 9m
b b'
G = 19.95 m

H - 35.78m
B - 5.34m Dbb' - 9.36m
H = 35.78 m

c c'
Dgg' = 0 m 0
Dcc' - 9.9m 4.95
G - 19.95m

Daa' = 9.00 m

Dbb' = 9.36 m

Dcc' = 9.90 m FGL


TYPICAL D/C 220kV TOWER
Design Temperature = 50 deg.C

No. of sub conductors N = 1 (SINGLE)

Radius of conductor r = 0.015885 m (ACSR MOOSE)-DOUBLE CIRCUIT

Subconductor Spacing S = 0 m

Resistivity of earth r = 100 ohm-m (Typical Value for Transmission Line)

System frequency f = 50 Hz

Length of Line = 150 kM

A.2 METHODOLOGY
IEEE Transactions on Power Apparatus and Systems, Vol. PAS-103, No.9 September 1984.
The mutual and self impedance of a system can be calculated as follows.

Mutual impedance Zgm = 0.000988 * f + j 0.0028938 * f * log10(De/GMD) ohms/ km -------1

Self impedance Zg = Rc + 0.000988 * f + j 0.0028938 * f * log10(De/GMR) ohms/ km -------2

Where Rc : Resistance of ground wire


GMD : Geometric Mean Distance = (Dab * Dbc *Dca )1/3
GMR : Geometric Mean Radius = (Dsa * Dsb *Dsc )1/3
De : Equivalent depth of earth return 658.4 *√ (r / f)
LARSEN & TOUBRO LIMITED 69 of 71
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!

A.3 Calculation of Equivalent Depth of Earth Return (De)


De = 658.4 √ (r / f)

= 658.4 * √(100 / 50)

= 931.12 m

A.4 Calculation of Geometric Mean Radius (GMRL)


Geometrical Mean Radius = 3
√(GMRa*GMRb*GMRc)

GMRa = √(0.7788*r* Daa')

= 0.334 m

GMRa = √(0.7788*r* Dbb')

= 0.340 m

GMRa = √(0.7788*r* Dcc')

= 0.350 m

GMRL = 0.3412 m

A.4 Calculation of Geometric Mean Radius (GMRC)


Geometrical Mean Radius = 3
√(GMRa*GMRb*GMRc)

GMRa = √(r* Daa')

= 0.378 m

GMRa = √(r* Dbb')

= 0.386 m

GMRa = √(r* Dcc')

= 0.397 m

GMRL = 0.3867 m

A.5 Calculation of Geometric mean Distance (GMD)

From the above GA of tower ,

Dab = Da'b' = 5.28 m Da'b =Dab' = 10.59 m


Dbc = Db'c'= 5.35 m Dbc' =Dcb' = 11.01 m (From Tower Geometry)
Dca = Dc'a'= 10.63 m Dca' =Dac' = 14.22 m

Dab = ( Dab . Da'b . Dab' . Da'b' ) 1/4

= (5.28 *10.59 * 10.59 * 5.28)^ 1/ 4


LARSEN & TOUBRO LIMITED 70 of 71
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!

= 5.28 m

Dbc = ( Dbc . Db'c . Dbc' . Db'c' ) 1/4

= (5.35 *11.01 * 11.01 * 5.35)^ 1/ 4

= 5.34 m

Dca = ( Dca . Dc'a . Dca' . Dc'a' ) 1/4

= (10.63 *14.22 * 14.22 * 10.63)^ 1/ 4

= 10.62 m

Geometrical Mean Distance = ³√(Dab . Dbc . Dca)

= ³√(5.28 *5.34 * 10.62)

= 6.69 m

A.6 Calculation of Ground Conductor resistance (Rc)

DC resistance at 20 Deg. C Rdc50 = 2.50 ohms/km (Typical Data)

M constant for Steel = 153.85

DC resistance at Design Temperature = Rdc20 (M+t2) ohms/km


(M+t1)

Rdc50 = 2.9314 ohms / km

AC resistance by considering Skin effect


Rac50 = k * Rdc50

Where k is a function of X = 0.063598 x √(mrf/Rdc32) (if Rdc is in ohm/mile)

= 0.080680 x √(mrf/Rdc32)

= 10.5369

k = 1.64051

Rac50 = 4.8090 ohms / km


(Typical Value)
No. of earth conductors in a TL Path = 2

Hence equivalent resistance Rc = 2.4045 ohms/ km i.e. Rac50 / 2

A.7 Calculation of Mutual & Self Impedance of Ground Wire

Zgm = 0.000988 * 50 + j 0.0028938 * 50 * Log10( 931.12 / 6.690)


LARSEN & TOUBRO LIMITED 71 of 71
ECC Division - EDRC (Electrical)

DOCUMENT NO DATE
PROJECT #REF!
#REF! #REF!
PREPARED CHECKED SHEET
TITLE #REF!
#REF! #REF!

= 0.0494+0.31015i ohm/ km

Zg = 2.4045 + 0.000988 * 50 + j 0.0028938 * 50 * Log10( 931.12 / 0.341)

= 2.4539+0.49715i ohm/ km

A.8 Calculation of Inductance of Line (H/m/ph)

L = ###

A.9 Calculation of Capacitance of Line (F/m/ph)

C = ###

A.9 Calculation of Impedance (SIL) & Maximum Allowable Power that can be transmitted through the Line

Z = ### OHM

P = ### MW

A.9 Calculation of Inductive Reactance of Line (XL)

XL = ### OHM