Fire System
Fire System
Fire System
TYPES OF DETECTORS:
HEAT DETECTOR -
➔ Respond to the energy emission from the fire in the for of heat.
➔ They are placed at kitchen,smoking rooms,basements
➔ The sensing elements of the detector should be between 25mm-
150mm below ceiling.
➔ A clear space of 500mm is maintained below each detector.
➔ Max. height 7.5m
SMOKE DETECTOR -
RADIATION DETECTOR -
➔ Used to detect or identify high-energy particles, such as those produced
by nuclear decay, cosmic radiation, or reactions in a particle accelerator.
● The floor area of single zone shall not exceed 2000 sqmtr.
● If the total area of a building is less than 300 sqmtr, a zone can cover
more than one floor.
● If the total area of a building is more than 300 sqmtr, each zone shall
be restricted to a single floor.
● Voids above or below the floor area of a room, can be included in the
same zone. The voids and the room constitute a single compartment.
● The traveled distance by anyone responding to a fire alarm signal, shall
not exceed 30 mtrs.
● It is advisable to provide adequate fire separation between the zones.
● If the requirement of detectors or call points is less than 20 in any
area, division of the area into zones is not necessary. Similarly,
sectorization is not necessary if the number is not very large.
Spacing and sitting of detector :-
Under flat ceilings, the horizontal distance between any point in a protected
area and the detector nearest to that point shall not exceed
i) 7.5 mtrs. in case of smoke detector and ii) 5.3 mtrs. in case of heat
detector.
● Under sloping roof pitched ceiling (where the distance between the top of
apex and bottom of the roof exceeds 600mm), spacing of detectors at or in
the vicinity of apex may be spaced between 7.5 mtrs. to 8.5 mtrs. for
smoke detectors.
● Heat detectors should be installed that sensing element is not less than
25mm and more than 150mm below the ceiling/roof level. For smoke
detectors. Sensing element should not be less than 25 mm and not more
than 600mm below the ceiling/roof level except as necessary.
● Detectors shall not be mounted within 500mm of any walls, partitions or
obstructions to flow of smoke or hot gases, such as structural beams and
ductwork where the obstructions are greater than 250mm in depth.
● When structural beams or ductwork of any other ceiling attachments, not
greater than 250mm depth, create obstacles to the flow of smoke, detectors
shall not be mounted closer to the obstruction than twice the depth of the
obstruction.
● Where partitions or storage racks that reach within 300mm of the ceiling,
they shall be construed as walls that extend to the ceiling for the purpose of
sitting the detectors.
● Similarly, ceiling obstructions such as structural beams, deeper than 10% of
the overall ceiling height shall be construed as walls for the purpose of
sitting the detectors.
● Detectors shall not be mounted within 1000mm of any air inlet (supply air
Grills of HVAC system) or a forced ventilation system.
● A clear space of 500mm is maintained below each detector.
● Where detectors are constrained to be fixed to the wall, they shall be sited in
such away that the top of the detection element is between 150mm and
300mm below the ceiling.
● Additional detector shall be placed on the ceiling at a position 1500 mm
from any opening which might act like a flue.
● A detector shall be placed on the protected side of the premises on the
ceiling 1500mm from any door, window or any opening in the wall partitions
separating the protected premises from the other premises.
● All stairwells, lift shafts, other utility shafts, etc. shall have a detector at the
top.
● Lift machine rooms shall be provided with a detector.
● All enclosed staircase shall have one detector at each main landing within
the staircase.
TYPES OF MANUAL FIRE ALARMS:
A building fire emergency notification system consisting minimally of
audible and visual appliances that is horns and strobes installed within
all common use areas of a building and manual alarm stations that is
pull station installed at every exits from every level.
➔ They should not be placed more than 5 feet from the entrance of
each exit.
➔ If the occupant load is less than 50 then manual fire alarm system is
not required.
➔ If the occupant load is 51 to 100 a manual fire alarm system is required.
➔ When the occupant load is greater than 100 a manual fire alarm
system with emergency voice over alarm communications system
is required.
PULL ALARM SYSTEM : The user activates the alarm by pulling the
handle down, which completes a circuit and locks the handle in the
activated position, sending an alarm to the fire alarm control panel.
➔ Present in all floors.
➔ Pull stations are placed within 60 inches of every individual exit.
➔ The alarms must be installed between 42 to 48 inches from the floor.
➔ The height of the manual fire alarm boxes shall be a minimum of
42 inches and a maximum of 54 inches measured vertically, from
the floor level to the activating handle or lever of the box. Manual fire
alarm boxes shall be red in color.
BREAK GLASS SYSTEM : The glass works to protect the fire alarm
from accidental activations. However, these alarms are activated by
a pressure switch, which is why glass is incorporated into the trigger.
When the glass fails or breaks, the switch will be triggered, the
signal will be sent to the alarm panel, and the sound will go off.
➔ Located in all floors.
➔ Located within a 20 foot radius of the windows.
➔ Also known as manual call point system (MCP)
COMPONENTS OF SECURITY ROOM
➔ An fire alarm control panel (FACP) which monitors the state of all
parts of the installation.It identifies the point of origin of an
alarm,displays this on the panel and communicates this to remote
control locations.
➔ Panel supplies electrical energy to operate any associated initiating
device.
➔ There are four types
● Coded panels
● Conventional panels
● Addressable panels( commonly used )
● Multiplex systems
JOCKEY PUMP : These pumps are initiated first in the case of an event of
fire.
DIESEL PUMP : These are driven by diesel and is used in the case of a
power shutdown.
PUMP CAPACITY-
● Pump near underground static water storage tank (fire pump) with
minimum pressure of 3.5 kg/sqcm at terrace level
*30m+ high buildings = two electric and one diesel pump of capacity
2280l/min and one electric pump of capacity 180l/min
WATER SUPPLY -
● Terrace tank
WET RISER:
➔ The riser pipe is full of water and is pressurised using gravity tanks
or dedicated fire pumps hence water is always available for fire
fighting.
➔ The pipe system is connected to a permanent water supply
normally a tank fed from the town mains
➔ The maximum number of sprinklers on one control valve is 1000.
➔ They are provided in high rise buildings with height more than
23m.
DRY RISER:
➔ The riser pipe is empty and does not have any water in them in
the event of fire incident water is pumped into the riser from the
fire tenders using the fire brigade inlets provided at the bottom of
the riser.
➔ Dry risers are normally installed in low rise buildings of height
less than 23 meters.
➔ Dry riser of minimum 100mm diameter pipe with hydrant outlet
on the floors constructed with a fire service inlet to boost the
water in the dry riser.(As per NBC)
➔ Water storage tank capacity 20,000 litres.(As per NBC)
➔ Drums of 2000 litre capacity filled with water with two fire
buckets on each floor.
FIRE HOSE CABINET
➔ A hose reel with axial supply. a water supply stop tap adjacent to the
hose reel.
➔ They should be located where users are least likely to be endangered
by the fire, i.e. the staircase landing.
➔ Fixed or swinging hose reels are located in wall recesses at a height of
about 1m above floor level.A basic length of semi-rigid hose 30m
maximum in length.
➔ Fire Hose Cabinet, Size: 750 x 600 x 250 mm
FIRE EXTINGUISHER-
● Powder extinguishers
● Wet chemical extinguishers
● Water extinguishers
● Foam extinguishers
● Carbon Dioxide CO2 extinguishers
Portable Fire Extinguishers can save lives and property by putting out
or containing fires within the capability of the extinguisher.
when the burring metals are reactive to water and water containing
agents and in certain cases carbon dioxide, halogenated hydrocarbons
and ordinary dry powders. These fires require special media and
techniques to extinguish.
EXIT
STAIRCASES
DOORWAYS
A horizontal exit shall be through a fire door of 120 min rating in a fire
resistant wall.Horizontal exit require separation with the refuge area or
adjoining compartment through 120 min fire barrier.
➔ Doorways shall not be less than 2000mm in height.
➔ Width shall not be less than 1000mm .
➔ Doors shall not be located within 3m of the foot or top of stairs
or escalators.
➔ Doors shall have fire rating as per the requirements at the point of
Installation.
➔ Each door shall be capable of exiting 50 people.
➔ A manual release device shall be provided in the readily accessible
vicinity of the egress door with a signage PUSH TO EXIT.
PANIC BARS
➔ Adequate passage way and clearances required for fire fighting vehicles
to enter the premises shall be provided at the main entrance; the width
of such entrance shall be not less than 5 metres or as stipulated
elsewhere in these rules, whichever is higher.
➔ If an arch or covered gate is constructed, it shall have a clear headroom
of not less than 5 meter.
TURNING RADIUS
➔ Minimum turning radius of 9 metres to be provided for fire tenders.
1) The refuge area shall be provided on the periphery of the floor and open
to air at least on one side protected with suitable railings.
2) Refuge area(s) shall be provided at/or immediately above 24 m and
thereafter at every 15 m or so.
Each refuge area shall be ventilated and provided with first aid box, fire
extinguishers, public address speaker, fireman talk back, and adequate
emergency lighting as well as drinking water facility.
Refuge areas shall be approachable from the space they serve by an
accessible means of egress.
Refuge areas shall connect to firefighting shaft (comprising fireman's lift,
lobby and staircase) without having the occupants requiring to return to
the building spaces through which travel to the area of refuge occurred.
➔ The refuge area shall always be kept clear. No storage of combustible
products and materials, electrical and mechanical equipment, etc shall
be allowed in such areas. k) Refuge area shall be provided with
adequate drainage facility to maintain efficient storm water disposal.
➔ m) Entire refuge area shall be provided with sprinklers.
➔ n) Where there is a difference in level between connected areas for
horizontal exits, ramps of slope not steeper than 1 in 12 shall be
provided (and steps should be avoided).
➔ NOTE
➔ Refuge area provided in excess of the requirements shall be counted
towards FAR.
➔ High rise apartment buildings with apartments having balcony, need not
be provided with refuge area; however apartment buildings without
balcony shall provide refuge area as given above. Refuge areas for
apartment buildings of height above 60 m while having balconies shall
be provided at 60 m and thereafter at every 30 m. The refuge area shall
be an area equivalent to 0.3 m2 per person for accommodating
occupants of two consecutive floors, where occupant load shall be
derived on basis of 12.5 m2 of gross floor area and additionally 0.9 m2
for accommodating wheelchair requirement or shall be 15 m2,
whichever is higher.
TYPES OF FIRE PROTECTION REQUIREMENTS
(ACTIVE DEFENSE)
First aid fire extinguishers Minimum First aid fire extinguishers bearing ISI
mark shall be installed in the each floor as per
the scale laid down in IS 2190:1992.
First aid hose reel To provide on each floor in the staircase landing
and shall be connected directly to the wet/dry
riser main and diameter of the hose reel shall be
not less than 19 mm with set off nozzle.
External Hydrant system At all around the building as ring man and having
main not less than 200/150/100 mm internal dia
meter G.I. ‘C’ class pipe. Single/Double hose box
with a delivery hose & standard branch pipe 19
mm diameter
Side Set Back area Total height of the building divided by 03 (h/3= m
all around the building)
➔ A horizontal exit shall be through a fire door of 120 min rating in a fire
resistant wall. Horizontal exit require separation with the refuge area or
adjoining compartment through 120 min fire barrier. The adjoining
compartment of the horizontal exit should allow unlocked and ease of
egress and exits for the occupants using defend in place strategy.
➔
➔ Requirements of horizontal exits are as under:
➔ a) Width of horizontal exit doorway shall be suitable to meet the
occupant load factor foregress.
➔ b) Doors in horizontal exits shall be openable at all times from both
sides.
➔ c) All doors shall swing in the direction of exit
➔ travel. For horizontal exits, if a double leaf door is used, the right hand
door leaf shall swing in the direction of exit travel.
ATRIUM REQUIREMENTS
➔ Smoke detectors shall be provided on the underside of each floor
protruding into the atrium, at the atrium roof and adjacent to each
return air intake from the atrium. Within atrium space, beam type or
aspirating type smoke detectors shall be used to ensure detection of
smoke, considering factors such as stratification of smoke.
➔ Where the ceiling of the atrium is more than 17 m above the floor,
water based protection (automatic sprinklers) at the ceiling of atrium is
not required.
➔ Hydrants shall be available at the floor of the atrium and also at the
adjoining upper spaces/floors of the atrium.
➔ Sprinklers are required to be installed for coverage of glass areas of
retail, tenant and other areas adjoining the exit access corridor and
atrium.
➔ Sprinklers shall be at a distance of 450 mm to 600 mm enabling
cooling of such glass and limiting the extent of fire and smoke to the
atrium.
➔ Atrium in business occupancy shall be planned with 6 air changes per
hour (ACPH) while atrium in hotels and assembly occupancy shall be
planned with 8 ACPH smoke extraction system.
➔ Such air changes shall be planned in atrium for a height of 15 m from
the top. Smoke exhaust fans shall be capable of operating effectively
at 250°C for 120 min
COMMERCIAL KITCHEN
➔ Where both parking and repair operations are conducted in the same
building, the entire building shall comply with the requirements for
Group G occupancies, unless the parking and repair sections are
effectively separated by separation walls of 120 min.
RATING
The time that a material or construction will withstand the standard fire
exposure as determined by fire test done in accordance with the standard
methods of fire tests of materials/structures.
● Walls of lift enclosures shall have a fire rating of two hours. Lift shafts
shall have a vent at the top of area not less than 0.2 sq m.
● Landing doors in lift enclosures shall have a fire resistance of not less
than one hour.
● The number of lifts in one lift bank shall not exceed four. A wall of two
hours fire rating shall separate individual shafts in a bank
● Lift car doors shall have a fire resistance rating of 1 hour.
RATING
● Wherever the air conditioning ducts pass through fire walls or floor, the
opening around the ducts should be sealed with fire resisting material
of the same rating as of walls/floors.
● Composite roofs may be used over as addition to the roofs of buildings
as a weatherproofing, but should not be considered as a roof in itself
that is, without the support of a non-combustible construction beneath,
unless it is of not less than half an hour fire resistance.
● Service ducts should be enclosed by walls and doors (if any) of 2 hours
fire rating; if ducts are larger than Im3 the floor should seal them, but
provide suitable openings for the pipes to pass through, with the gaps
sealed.
● Linings or false ceilings should not be permissible in buildings and in
situations, where permitted, such additions should not detract in
anyway from minimum fire rating of half an hour.
In some cases, requiring provision of skylights, monitor lights or north
lights in the roofs and where these are necessary, the glazings should
be of glass in metal frames for tire rating of half an hour minimum.
● The enclosure for staircases and hoists should be constructed entirely
of brick, concrete or of reinforced concrete or similar material of
construction having 2 hours rating. Every opening from the enclosure
on to a roof used as floor or to any other part of the building should be
fitted with a fire resistant door of rating not less than 1 hour.
● Every opening in the wall should be protected by fire resisting doors
having the fire rating of not less than 1 hour. Similar protection should
also be done in other openings like rope races, motor alley ways,
staircases, etc, of rating not less than 2 hours.
● Openings provided to allow plumbing/gas/steam pipes and similar
services should be sealed with filler material of fire rating not less than
that of the walls in which these are situated.
● If there is an opening on both sides of the separating wall within 3 m of
the wall, those on one side should be bricked up to full thickness of
wall, or an alternative should be provided with fire resisting doors of fire
rating not less than of 2 hours for walls of 4 hours rating and 1 hour for
other rating.
RATING
Rs 5300/-
Swinging Hose Reel
CP
Hose Pipe @Rs.4200/-