Schedule of Loads

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

SCHEDULE OF LOADS

PANELBOARD : MAIN
QUANTITY VOLTS CURRENT
CKT NO. DESCRIPTION VOLTS AMPERE COPPER WIRE GROUNDING SIZE OF RIGID STEEL CONDUIT PIPE
L.O C.O ACU OTHER LOADS AMPERE PROTECTION
1 ROOM-1 9 6 1 230 2726 11.85 30 AT,2P 2-8.0mm2 THHN COPPER WIRE 1-5.5mm2 THHN COPPER WIRE 25mm DIA.ELECTRICAL PVC PIPE
2 ROOM-2 9 6 1 230 2726 11.85 30 AT,2P 2-8.5mm2 THHN COPPER WIRE 1-5.5mm2 THHN COPPER WIRE 25mm DIA.ELECTRICAL PVC PIPE
3 ROOM-3 9 6 1 230 2726 11.85 30 AT,2P 2-8.5mm2 THHN COPPER WIRE 1-5.5mm2 THHN COPPER WIRE 25mm DIA.ELECTRICAL PVC PIPE
10 SPARE 230 1800 7.83 20 AT,2P 2-5.5mm2 THHN COPPER WIRE 1-3.5mm2 THHN COPPER WIRE 20mm DIA.ELECTRICAL PVC PIPE
11 SPARE 230 1800 7.83 21 AT,2P 2-5.5mm2 THHN COPPER WIRE 1-3.5mm2 THHN COPPER WIRE 20mm DIA.ELECTRICAL PVC PIPE
TOTAL CONNECTED LOAD : 11778
Sub- Feeder
TOTAL CONNECTED LOAD : 8178 VA SERVICE FEEDER CONDUCTOR (COPPER WIRE)
IL = ((11778+25%(746))/230) = 52.02 Amps IF = 41.61 X 1.25 = 52.01 Amps
IL @ 80% DEMAND FACTOR USE : 2C- 14.0mm2 THW COPPER WIRE STRANDED
IL = 52.02 X .80 = 41.61 Amps + 1C-5.5mm2 STRANDED GROUND THW WIRE IN 32mm DIA. EMT PIPE.

SERVICE FEEDER EQUIPMENT : (CIRCUIT BREAKER)


ICB = {(11032+ 250%(746)}/230 = 56.07 Amps
USE :MAIN 70 AT,25kAIC ,2P,600 V,60 Hz.

ROOM-1
SCHEDULE OF LOADS
PANELBOARD : SUB-PANEL
CKT NO. DESCRIPTION QUANTITY VOLTS CURRENT COPPER WIRE GROUNDING SIZE OF RIGID STEEL CONDUIT PIPE
VOLTS AMPERE
L.O C.O ACU OTHER LOADS AMPERE PROTECTION
1 LIGHTING OUTLET 9 230 900 3.91 15 AT,2P 2-3.5mm2 THHN COPPER WIRE 15mm DIA.ELECTRICAL PVC PIPE
2 CONV.OUTLET 6 230 1080 4.70 20 AT,2P 2-3.5mm2 THHN COPPER WIRE 1-3.5mm2 THHN COPPER WIRE 15mm DIA.ELECTRICAL PVC PIPE
3 ACU- 1 1hp 1 230 746 3.24 30 AT,2P 2-5.5mm2 THHN COPPER WIRE 1-3.5mm2 THHN COPPER WIRE 20mm DIA.ELECTRICAL PVC PIPE
4 SPARE 230
5 SPARE 230
TOTAL CONNECTED LOAD : 2726
Sub- Feeder
TOTAL CONNECTED LOAD : 2726 VA SERVICE FEEDER CONDUCTOR (COPPER WIRE)
IL = ((2726+25%(746))/230) = 12.66 Amps IF = 10.13 X 1.25 = 12.66 Amps
IL @ 80% DEMAND FACTOR USE : 2C- 8.0mm2 THW COPPER WIRE STRANDED
IL = 12.66 X .80 = 10.13 Amps + 1C-5.5mm2 STRANDED GROUND THW WIRE IN 25mm DIA. EMT PIPE.

SERVICE FEEDER EQUIPMENT : (CIRCUIT BREAKER)


ICB = {(1980+ 250%(746)}/230 = 16.71 Amps
USE :MAIN 40 AT,25kAIC ,2P,600 V,60 Hz.

ROOM-2
SCHEDULE OF LOADS
PANELBOARD : SUB-PANEL
CKT NO. DESCRIPTION QUANTITY VOLTS CURRENT COPPER WIRE GROUNDING SIZE OF RIGID STEEL CONDUIT PIPE
VOLTS AMPERE
L.O C.O ACU OTHER LOADS AMPERE PROTECTION
1 LIGHTING OUTLET 9 230 900 3.91 15 AT,2P 2-3.5mm2 THHN COPPER WIRE 15mm DIA.ELECTRICAL PVC PIPE
2 CONV.OUTLET 6 230 1080 4.70 20 AT,2P 2-3.5mm2 THHN COPPER WIRE 1-3.5mm2 THHN COPPER WIRE 15mm DIA.ELECTRICAL PVC PIPE
3 ACU- 1 1hp 1 230 746 3.24 30 AT,2P 2-5.5mm2 THHN COPPER WIRE 1-3.5mm2 THHN COPPER WIRE 20mm DIA.ELECTRICAL PVC PIPE
4 SPARE 230
5 SPARE 230
TOTAL CONNECTED LOAD : 2726
Sub- Feeder
TOTAL CONNECTED LOAD : 2726 VA SERVICE FEEDER CONDUCTOR (COPPER WIRE)
IL = ((2726+25%(746))/230) = 12.66 Amps IF = 10.13 X 1.25 = 12.66 Amps
IL @ 80% DEMAND FACTOR USE : 2C- 8.0mm2 THW COPPER WIRE STRANDED
IL = 12.66 X .80 = 10.13 Amps + 1C-5.5mm2 STRANDED GROUND THW WIRE IN 25mm DIA. EMT PIPE.

SERVICE FEEDER EQUIPMENT : (CIRCUIT BREAKER)


ICB = {(1980+ 250%(746)}/230 = 16.71 Amps
USE :MAIN 40 AT,25kAIC ,2P,600 V,60 Hz.

ROOM-3
SCHEDULE OF LOADS
PANELBOARD : SUB-PANEL
CKT NO. DESCRIPTION QUANTITY VOLTS CURRENT COPPER WIRE GROUNDING SIZE OF RIGID STEEL CONDUIT PIPE
VOLTS AMPERE
L.O C.O ACU OTHER LOADS AMPERE PROTECTION
1 LIGHTING OUTLET 9 230 900 3.91 15 AT,2P 2-3.5mm2 THHN COPPER WIRE 15mm DIA.ELECTRICAL PVC PIPE
2 CONV.OUTLET 6 230 1080 4.70 20 AT,2P 2-3.5mm2 THHN COPPER WIRE 1-3.5mm2 THHN COPPER WIRE 15mm DIA.ELECTRICAL PVC PIPE
3 ACU- 1 1hp 1 230 746 3.24 30 AT,2P 2-5.5mm2 THHN COPPER WIRE 1-3.5mm2 THHN COPPER WIRE 20mm DIA.ELECTRICAL PVC PIPE
4 SPARE 230
5 SPARE 230
TOTAL CONNECTED LOAD : 2726
Sub- Feeder
TOTAL CONNECTED LOAD : 2726 VA SERVICE FEEDER CONDUCTOR (COPPER WIRE)
IL = ((2726+25%(746))/230) = 12.66 Amps IF = 10.13 X 1.25 = 12.66 Amps
IL @ 80% DEMAND FACTOR USE : 2C- 8.0mm2 THW COPPER WIRE STRANDED
IL = 12.66 X .80 = 10.13 Amps + 1C-5.5mm2 STRANDED GROUND THW WIRE IN 25mm DIA. EMT PIPE.

SERVICE FEEDER EQUIPMENT : (CIRCUIT BREAKER)


ICB = {(1980+ 250%(746)}/230 = 16.71 Amps
USE :MAIN 40 AT,25kAIC ,2P,600 V,60 Hz.

You might also like