AS2011-00

Photoelectric Smoke Sensor

Standard Features Operation


• Low Profile - Only 2.0” high, including The detection chamber consists of a light-
base emitting diode (LED) and photodiode
arrangement. The chamber is designed such
• Simple and reliable device addressing
that light emitted by the LED cannot
• Automatic compensation for sensor normally reach the photodiode. In the event
contamination of fire, particles of smoke enter the chamber
and scatter the light. As the smoke level
• Built-in fire test feature increases, the scattering effect increases,
• Uses the noise-immune Digital causing more light to hit the photodiode.
Communication Protocol (DCP), which The chamber contains a unique baffle design
utilizes interrupts for fast response to which allows smoke to enter the chamber
fires while preventing external light from
affecting the photodiode. The photodiode
• Two built-in power/alarm LEDs input level is sampled to sense smoke
density.
• Programmable non-polling LEDs
When the smoke density exceeds a preset
• Non-directional smoke chamber
threshold the sensor transmits an interrupt
• Vandal resistant security locking feature to the fire control panel indicating a fire
condition. The fire alarm control panel can
• Removable smoke labyrinth for cleaning adjust the sensor threshold to compensate
or replacement for contamination.
Note: Up to 127 devices are permitted on each SLC
loop. A sensor address is set by a hand-held
Bases are not included Application programming unit. The sensor mounts to an
electronics-free base and incorporates a
with detectors, please The AS2011 Photoelectric Smoke Sensor is locking mechanism for secure installation.
particularly suited to detecting optically dense The base provides mounting slots, terminals
order separately. smoke typical of fires involving materials such for field wiring and a third contact for a
as soft furnishings, plastic, foam or other remote indicator / LED. The sensor
similar materials which tend to smolder and incorporates dual LEDs for easy viewing of
produce large visible smoke particles. sensor status
Avenger’s unique design allows fast response
to flaming fires as well as smoldering fires
while preventing false alarms.

Fire Detection System by Avenger, Las Vegas, Nevada 89141 U.S.A. I Phone: 1-702-513-4654
[email protected] I www.avengersystems.com
VERSION 3.01 - 2017/09
Engineering Specification
The contractor shall furnish and install where indicated on
Technical Specifications
the plans, photoelectric sensors AS2011 The combination Operating Voltage: 17-41 VDC
sensor head and twist lock base shall be UL listed compatible Standby Current: 450μA
with a UL listed fire alarm control panel. Alarm Current: 540μA
The Sensor and Base shall be UL listed as compatible with the Transmission Method: DCP—Digital Communication Protocol
fire alarm control panel (FACP). The base shall permit direct
Maximum Humidity: 95% RH Non-Condensing
interchange with the Avenger AS2011 photoelectric smoke
sensor, AS2010 heat sensor, and the AS2012 Multi-Criteria UL Temperature Range: 32º F to 115º F
sensor. Operating Temperature Range: 14º F to 122º F
The sensitivity of the sensor shall be capable of being Sensitivity Range: 0.7 - 4.0%/ FT @ 300 FPM
measured by the control panel. 0.7 - 3.86%/ FT @ 2000 FPM 0.7
2.65%/ FT @ 4000 FPM
The vandal-resistant, security locking feature shall be used in
Air Velocity Range: 0-4000 fpm
those areas as indicated on the drawing. The locking feature
shall be optional and can be implemented when required. Color & Case Material: Bone/ White - ABS Blend
Weight: 3.4 oz, (5.1 oz with 4” base)

Bases
The AS7001 and the AS7002 mounting bases are electronics
free and are a simple rugged design with screw terminals for
Ordering Codes
wiring connections. A common mounting base allows sensor Part Number Description
interchange and maintains loop continuity when sensors are AS2011-00 Photoelectric Smoke Detector
removed. A simple anti-tamper head locking system is
provided which is enabled by removing a small plastic tab on AS7001-00 4” Mounting Base
the back of the sensor. Once locked, the head can be AS7002-00 6” Mounting Base
removed using a small diameter screw driver. AS7008-00 6” Sounder Base

Fire Detection System by Avenger, Las Vegas, Nevada 89141 U.S.A. I Phone: 1-702-513-4654
[email protected] I www.avengersystems.com