MV Instrument Transformers EN
MV Instrument Transformers EN
INSTRUMENT TRANSFORMERS
01
INDEX
02
03
GENERAL INFORMATION
Instrument Transformers: An instrument transformer is a piece of electrical equipment which converts primary
electrical values current or voltage-into comparable secondary values which are suitable for the devices to which it is
connected. They are defined in two kinds;
Current transformers convert primary rated current to a proper current level (1A…5A) which can be used by meter-
ing or protection devices. They can have several secondary windings with magnetically separated cores of the same
or different characteristics.
Voltage Transformers, isolate the primary - side rated voltage from the connected instruments and protection
circuits and convert the primary voltage into a measurable secondary voltage which is true in magnitude and phase.
It is the value that Current Transformer can withstand at defined current value while remaining in the limits of
current error. As described in IEC 61869-2, Standard values of rated primary current 120%, 150% and 200% of primary
current.
Limits of current error and phase displacement for measuring current transformers
As described IEC 61869-2;
For classes 0.1 – 0.2 – 0.5 and 1, the current error and phase displacement at rated frequency shall not exceed the
values given in table when the secondary burden is any value from 25 % to 100 % of the rated burden.
For classes 0,2 S and 0,5 S the current error and phase displacement at the rated frequency shall not exceed the
values given in table when the secondary burden is any value from 25 % and 100 % of the rated burden.
1. When the secondary terminals are connected to the measuring or protection devices, one of the terminals should
be earthed for safety as seen in FIGURE CT-1
2. The secondary circuit of a current transformer must not be operated open-circuited
3. The secondary winding of a current transformer which will not be used must always be short-circuited and
earthed as seen in FIGURE CT-2
4. For the transformer with reconnectable and/or tapped secondaries, unused terminals must be left open as seen
in FIGURE CT-3
5.The current transformers which have capacitive divider tap (Ck) must be connected to the indicator. If the tap
will not be used then it must be earthed as seen in FIGURE CT-4
6.The primary reconnection can only be used for primary currents up to 2 x 600A and for current transformers. The
ratio of the reconnection have to be always 1:2.
For primary reconnection, the primary winding consists of two winding parts (P1-C2 & C1-P2) which can either be
connected in series or parallel. FIGURE CT-5
05
OPERATION CONDITIONS
FOR VOLTAGE TRANSFORMERS
1. When the secondary terminals are connected to the measuring or protection devices, one of the terminals should
be earthed for safety as seen in FIGURE VT-1.
2. The base plate must be earthed.
3. The secondary circuits must not be short-circuited during operation. Otherwise the voltage transformers will be
thermally destroyed.
4. If any of the secondary windings of a voltage transformer, used for the purpose of measuring, will not be
used then it must be left open with one terminal connected to earth as seen in FIGURE VT-2. However, even if the
open-delta windings are not to be used for detection of earth faults, they must be connected in an open delta circuit
and an appropriate resistor (depending on the voltage and thermal power rating of the secondary) must be connected
and open-delta circuit must be earthed only at one point as seen on FIGURE VT-4. Please refer to the technical rec-
ommendations below.
5. For single phase transformers, the neutral terminal of the primary “ N ” must be earthed in the earthed (neutral)
systems as seen in FIGURE VT-3.
When using single pole insulated inductive voltage transformers, it is very important to be aware that, if a circuit
is being closed or during the decaying period of an earth fault,ferroresonance may occur.
Ferroresonance can lead to the overheating and thermal destruction of the voltage transformer or high levels of
voltages may be induced. In general, ferroresonance can be eliminated by the use of an appropriate resistor. The re-
sistor is placed as a burden in open-delta circuit formed by three voltage transformers delta windings. The open-delta
circuit must always be earthed only at one point as seen in FIGURE VT-4.The open-delta connection can also be used
for earth-fault monitoring with appropriate devices.
As the number of cable systems is increasing in the energy distribution systems, the protection of voltage trans-
formers have become very important for the uninterrupted operation of the system without any failure and/or down
time. For that reason, ALCE is always recommending the use of open-delta windings in single phase inductive voltage
transformers.
The use of open-delta windings may not be sufficient for the protection of voltagetransformers by itself in some
cases. An energy systems design engineer shall always use proper surge arresters, avalanche diodes, limiters and/or
their combinations for the survivability of the distribution system after a fault or disturbance.
FIGURE VT-4
06
INDOOR SUPPORT TYPE
CURRENT TRANSFORMERS
AB12 / AB12-3
AB12
AB12-3
TECHNICAL DATA
TYPE AB12 AB12-3
Rated Data
Operating Voltage (maximum) kV Up to 17,5
Test Voltages (maximum) kV 38/95
Rated Freguency Hz 50 or 60
Max. Rated Primary Current A 2500
Secondary Rated Current A 1 or 5
Rated Short-Time Thermal Current Ith (1s) kA max. 60 (1000 x In)
Rated Dynamic Current Idyn kA max. 120 (2,5 x Ith)
Weight (approx.) kg 20 - 22 30 - 35
07
INDOOR SUPPORT TYPE
CURRENT TRANSFORMERS
AB24 / AB24-3
AB24
AB24-3
TECHNICAL DATA
TYPE AB24 AB24-3
Rated Data
Operating Voltage (maximum) kV Up to 24
Test Voltages (maximum) kV 50/125
Rated Freguency Hz 50 or 60
Max. Rated Primary Current A 4000 (Icont 1 x In)
Secondary Rated Current A 1 or 5
Rated Short-Time Thermal Current Ith (1s) kA max. 60 (1000 x In)
Rated Dynamic Current Idyn kA max. 120 (2,5 x Ith)
08
Weight (approx.) kg 33 - 35 45 - 50
INDOOR SUPPORT TYPE
CURRENT TRANSFORMERS
AK24
AK24
TECHNICAL DATA
TYPE AK24
Rated Data
Operating Voltage (maximum) kV Up to 24
Test Voltages (maximum) kV 50/125
Rated Freguency Hz 50 or 60
Max. Rated Primary Current A 1500
Secondary Rated Current A 1 or 5
Rated Short-Time Thermal Current Ith (1s) kA max. 60 (1000 x In)
Rated Dynamic Current Idyn kA max. 120 (2,5 x Ith)
Weight (approx.) kg 20 09
INDOOR SUPPORT TYPE
CURRENT TRANSFORMERS
AB36
AB36
TECHNICAL DATA
TYPE AB36 AB36-T
Rated Data
Operating Voltage (maximum) kV Up to 36
Test Voltages (maximum) kV 70/170
Rated Freguency Hz 50 or 60
Max. Rated Primary Current A 4000 Icont 1* In
Secondary Rated Current A 1 or 5
Rated Short-Time Thermal Current Ith (1s) kA max. 60 (1000 x In)
Rated Dynamic Current Idyn kA max. 120 (2,5 x Ith)
10
Weight (approx.) kg 40 - 55 45 - 60
INDOOR SUPPORT TYPE
CURRENT TRANSFORMERS
AK36
TECHNICAL DATA
TYPE AK36
Rated Data
Operating Voltage (maximum) kV Up to 36
Test Voltages (maximum) kV 70/170
Rated Freguency Hz 50 or 60
Max. Rated Primary Current A 1500
Secondary Rated Current A 1 or 5
Rated Short-Time Thermal Current Ith (1s) kA max. 60 (1000 x In)
Rated Dynamic Current Idyn kA max. 120 (2,5 x Ith)
Weight (approx.) kg 28 - 36 11
INDOOR BUSBAR TYPE
CURRENT TRANSFORMERS
AD12 AD17
AD24 AD24-L
TECHNICAL DATA
TYPE AD12 - AD17 AD24 - AD24-L
Rated Data
Operating Voltage (maximum) kV Up to 17,5 Up to 24
Test Voltages (maximum) kV 38/95 50/125
Rated Freguency Hz 50 or 60
Max. Rated Primary Current A 800 - 3000 800 - 7500
Secondary Rated Current A 1 or 5
Rated Short-Time Thermal Current Ith (1s) kA max. 100
Rated Dynamic Current Idyn kA (2,5 x Ith)
Weight (approx.) kg 20 - 25 55 - 60
12
INDOOR SINGLE POLE
VOLTAGE TRANSFORMERS
VB12
VB12
TECHNICAL DATA
TYPE VB12
Rated Data
Highest Voltage For Equipment, Um(r.m.s.) kV Up to 17,5
Test Voltages (maximum) kV 38/95
Rated Freguency Hz 50 or 60
Rated Primary Voltage, Un (max.) kV 15/√3
Secondary Voltage V 100/ √3 or 110/ √3 or 120/ √3
Rated Burden in Class 0.2-0.5-1.0 VA 5 - 10 - 15 - 20 - 30 - 40...
Max. Rated Burden For Protection Purpose in Class 3P/6P VA 100
Thermal Limiting Current For Earth Fault Detection Winding A 6
Rated Voltage Factor (8h) 1,9 Un
Weight (approx.) kg 25
13
INDOOR SINGLE POLE
VOLTAGE TRANSFORMERS
VK12
VK12
TECHNICAL DATA
TYPE VK12
Rated Data
Highest Voltage For Equipment, Um(r.m.s.) kV Up to 17,5
Test Voltages (maximum) kV 38/95
Rated Freguency Hz 50 or 60
Rated Primary Voltage, Un (max.) kV 15/√3
Secondary Voltage V 100/ √3 or 110/ √3 or 120/ √3
Rated Burden in Class 0.2-0.5-1.0 VA 5 - 10 - 15 - 20 - 30 - 40...
Max. Rated Burden For Protection Purpose in Class 3P/6P VA 100
Thermal Limiting Current For Earth Fault Detection Winding A 6
Rated Voltage Factor (8h) 1,9 Un
14
Weight (approx.) kg 23
INDOOR SINGLE POLE
VOLTAGE TRANSFORMERS
VB24
VB24
TECHNICAL DATA
TYPE VB24
Rated Data
Highest Voltage For Equipment, Um(r.m.s.) kV Up to 24
Test Voltages (maximum) kV 50/125
Rated Freguency Hz 50 or 60
Rated Primary Voltage, Un (max.) kV 24/ √3
Secondary Voltage V 100/ √3 or 110/ √3 or 120/ √3
Rated Burden in Class 0.2-0.5-1.0 VA 5 - 10 - 15 - 20 - 30 - 40...
Max. Rated Burden For Protection Purpose in Class 3P/6P VA 100
Thermal Limiting Current For Earth Fault Detection Winding A 6
Rated Voltage Factor (8h) 1,9 Un
Weight (approx.) kg 34 15
INDOOR SINGLE POLE
VOLTAGE TRANSFORMERS
VB36
VB36
TECHNICAL DATA
TYPE VB36
Rated Data
Highest Voltage For Equipment, Um(r.m.s.) kV Up to 36
Test Voltages (maximum) kV 70/170
Rated Freguency Hz 50 or 60
Rated Primary Voltage, Un (max.) kV 36/ √3
Secondary Voltage V 100/ √3 or 110/ √3 or 120/ √3
Rated Burden in Class 0.2-0.5-1.0 VA 5 - 10 - 15 - 20 - 30 - 40...
Max. Rated Burden For Protection Purpose in Class 3P/6P VA 100
Thermal Limiting Current For Earth Fault Detection Winding A 6
Rated Voltage Factor (8h) 1,9 Un
16
Weight (approx.) kg 42
INDOOR SINGLE POLE
VOLTAGE TRANSFORMERS
VK36
VK36
TECHNICAL DATA
TYPE VK36
Rated Data
Highest Voltage For Equipment, Um(r.m.s.) kV Up to 36
Test Voltages (maximum) kV 70/170
Rated Freguency Hz 50 or 60
Rated Primary Voltage, Un (max.) kV 36/ √3
Secondary Voltage V 100/ √3 or 110/ √3 or 120/ √3
Rated Burden in Class 0.2-0.5-1.0 VA 5 - 10 - 15 - 20 - 30 - 40...
Max. Rated Burden For Protection Purpose in Class 3P/6P VA 100
Thermal Limiting Current For Earth Fault Detection Winding A 6
Rated Voltage Factor (8h) 1,9 Un
Weight (approx.) kg 48 17
INDOOR DOUBLE POLE
VOLTAGE TRANSFORMERS
2VB12
2VB12
TECHNICAL DATA
TYPE 2VB12
Rated Data
Highest Voltage For Equipment, Um(r.m.s.) kV Up to 17,5
Test Voltages (maximum) kV 38/95
Rated Freguency Hz 50 or 60
Rated Primary Voltage, Un (max.) kV 12
Secondary Voltage V 100 or 110 or 120
Rated Burden in Class 0.2-0.5-1.0 VA 5 - 10 - 15 - 20 - 30 - 40...
Max. Rated Burden For Protection Purpose in Class 3P/6P VA 100
Rated Voltage Factor (8h) 1,2 Un
18
Weight (approx.) kg 24
INDOOR DOUBLE POLE
VOLTAGE TRANSFORMERS
2VB24
2VB24
280
360
TECHNICAL DATA
TYPE 2VB24
Rated Data
Highest Voltage For Equipment, Um(r.m.s.) kV Up to 24
Test Voltages (maximum) kV 50/125
Rated Freguency Hz 50 or 60
Rated Primary Voltage, Un (max.) kV 24
Secondary Voltage V 100 or 110 or 120
Rated Burden in Class 0.2-0.5-1.0 VA 5 - 10 - 15 - 20 - 30 - 40...
Max. Rated Burden For Protection Purpose in Class 3P/6P VA 100
Rated Voltage Factor (8h) 1,2 Un
Weight (approx.) kg 36 19
INDOOR DOUBLE POLE
VOLTAGE TRANSFORMERS
2VK36
2VB12
2VK36-1
2VK36-2
TECHNICAL DATA
TYPE 2VK36
Rated Data
Highest Voltage For Equipment, Um(r.m.s.) kV Up to 36
Test Voltages (maximum) kV 70/170
Rated Freguency Hz 50 or 60
Rated Primary Voltage, Un (max.) kV 36
Secondary Voltage V 100 or 110 or 120
Rated Burden in Class 0.2-0.5-1.0 VA 5 - 10 - 15 - 20 - 30 - 40...
Max. Rated Burden For Protection Purpose in Class 3P/6P VA 100
Rated Voltage Factor (8h) 1,2 Un
20
Weight (approx.) kg 55 - 60
INDOOR SINGLE POLE
VOLTAGE TRANSFORMERS WITH FUSE
VBF12-FE / VBF12-FS
• With fuse
• Single pole insulated
• Block type design
• Standard: IEC 61869-3, VDE, ANSI, GOST
VBF12-FE
VBF12-FS
TECHNICAL DATA
TYPE VBF12-FE VBF12-FS
Rated Data
Highest Voltage For Equipment, Um(r.m.s.) kV Up to 17,5
Test Voltages (maximum) kV 38/95
Rated Freguency Hz 50 or 60
Rated Primary Voltage, Un (max.) kV 15/ √3
Secondary Voltage V 100/ √3 or 110/ √3 or 120/ √3
Rated Burden in Class 0.2-0.5-1.0 VA 5 - 10 - 15 - 20 - 30 - 40...
Max. Rated Burden For Protection Purpose in Class 3P/6P VA 100
Thermal Limiting Current For Earth Fault Detection Winding A 6
Rated Voltage Factor (8h) 1,9 Un
Weight (approx.) kg 26 21
INDOOR SINGLE POLE
VOLTAGE TRANSFORMERS WITH FUSE
VBF24-FE / VBF24-FS
• With fuse
• Single pole insulated
• Block type design
• Standard: IEC 61869-3, VDE, ANSI, GOST
VBF24-FE
VBF24-FS
TECHNICAL DATA
TYPE VBF24-FE VBF24-FS
Rated Data
Highest Voltage For Equipment, Um(r.m.s.) kV Up to 24
Test Voltages (maximum) kV 50/125
Rated Freguency Hz 50 or 60
Rated Primary Voltage, Un (max.) kV 24/ √3
Secondary Voltage V 100/ √3 or 110/ √3 or 120/ √3
Rated Burden in Class 0.2-0.5-1.0 VA 5 - 10 - 15 - 20 - 30 - 40...
Max. Rated Burden For Protection Purpose in Class 3P/6P VA 100
Thermal Limiting Current For Earth Fault Detection Winding A 6
Rated Voltage Factor (8h) 1,9 Un
22
Weight (approx.) kg 35
INDOOR SINGLE POLE
VOLTAGE TRANSFORMERS WITH FUSE
VBF36-FE / VBF36-FS
• With fuse
• Single pole insulated
• Block type design
• Standard: IEC 61869-3, VDE, ANSI, GOST
VBF36-FE
VBF36-FS
TECHNICAL DATA
TYPE VBF36-FE VBF36-FS
Rated Data
Highest Voltage For Equipment, Um(r.m.s.) kV Up to 36
Test Voltages (maximum) kV 70/170
Rated Freguency Hz 50 or 60
Rated Primary Voltage, Un (max.) kV 36/ √3
Secondary Voltage V 100/ √3 or 110/ √3 or 120/ √3
Rated Burden in Class 0.2-0.5-1.0 VA 5 - 10 - 15 - 20 - 30 - 40...
Max. Rated Burden For Protection Purpose in Class 3P/6P VA 100
Thermal Limiting Current For Earth Fault Detection Winding A 6
Rated Voltage Factor (8h) 1,9 Un
Weight (approx.) kg 48 23
OUTDOOR TYPE
INSTRUMENT TRANSFORMERS
24
OUTDOOR SUPPORT TYPE
CURRENT TRANSFORMERS
AH17
• Outdoor application
• Cyloaliphatic epoxy resin insulated
• Ambient air temperature: -40ºC to +55ºC
• Altitude: Up to 1000 meters above sea level (>1000m on request)
• Exposure to solar radiation: More than 2.800 hours annually
peaking at 1000W/m² for horizontal surfaces.
• Max. relative humidity: 100% Max. wind. velocity: 100km/h
• Standard: IEC 61869-2, ANSI, GOST, VDE
AH17
TECHNICAL DATA
TYPE AH17
Rated Data
Operating Voltage (maximum) kV Up to 17,5
Test Voltages (maximum) kV 38/95
Rated Freguency Hz 50 or 60
Maximum Rated Primary Current A 2500
Secondary Rated Current A 1 or 5
Rated Short-Time Thermal Current lth (1s) kA max. 60 (1000 x In)
Rated Dynamic Current ldyn A max.120 (2,5 x Ith)
Weight (approx.) kg 38 25
OUTDOOR SUPPORT TYPE
CURRENT TRANSFORMERS
AH24
• Outdoor application
• Cyloaliphatic epoxy resin insulated
• Ambient air temperature: -40ºC to +55ºC
• Altitude: Up to 1000 meters above sea level (>1000m on request)
• Exposure to solar radiation: More than 2.800 hours annually
peaking at 1000W/m² for horizontal surfaces.
• Max. relative humidity: 100% Max. wind. velocity: 100km/h
• Standard: IEC 61869-2, ANSI, GOST, VDE
AH24
TECHNICAL DATA
TYPE AH24
Rated Data
Operating Voltage (maximum) kV Up to 24
Test Voltages (maximum) kV 50/125
Rated Freguency Hz 50 or 60
Maximum Rated Primary Current A 3000
Secondary Rated Current A 1 or 5
Rated Short-Time Thermal Current lth (1s) kA max. 60 (1000 x In)
Rated Dynamic Current ldyn A max.120 (2,5 x Ith)
26
Weight (approx.) kg 48-50
OUTDOOR SUPPORT TYPE
CURRENT TRANSFORMERS
A32H
A32-H
• Outdoor application
• Cyloaliphatic epoxy resin insulated
• Ambient air temperature: -40ºC to +55ºC
• Altitude: Up to 1000 meters above sea level (>1000m on request)
• Exposure to solar radiation: More than 2.800 hours annually
peaking at 1000W/m² for horizontal surfaces.
• Max. relative humidity: 100% Max. wind. velocity: 100km/h
• Standard: IEC 61869-2, ANSI, GOST, VDE
A32H-1 A32H-2
A32H-3 A32H-4
TECHNICAL DATA
TYPE A32H
Rated Data
Operating Voltage (max.) kV Up to 36
Test Voltages (maximum) kV 70/170
Rated Freguency Hz 50 or 60
Maximum Rated Primary Current A 3000
Secondary Rated Current A 1 or 5
Rated Short-Time Thermal Current lth (1s) kA max.60 (1000 x ln)
Rated Dynamic Current ldyn kA max.120 (2,5 x lth)
Weight (approx.) kg 60 - 65 27
OUTDOOR SINGLE POLE
VOLTAGE TRANSFORMERS
VH17
A32-H
• Outdoor application
• Cyloaliphatic epoxy resin insulated
• Ambient air temperature: -40ºC to +55ºC
• Altitude: Up to 1000 meters above sea level (>1000m on request)
• Exposure to solar radiation: More than 2.800 hours annually
peaking at 1000W/m² for horizontal surfaces.
• Max. relative humidity: 100% Max. wind. velocity: 100km/h
• Standard: IEC 61869-3, ANSI, GOST, VDE
VH17
TECHNICAL DATA
TYPE VH17
Rated Data
Highest Voltage For Equipment, Um(r.m.s.) kV Up to 17.5
Test Voltages (maximum) kV 38/95
Rated Freguency Hz 50 or 60
Rated Primary Voltage, Un (max.) kV 15/√3
Secondary Voltage V 100/√3 or 110/√3 or 120/√3
Rated Burden in Class 0.2-0.5-1.0 VA 5 - 10 - 15 - 20 - 30 - 40...
Max. Rated Burden For Protection Purpose in Class 3P/6P VA 100
Thermal Limiting Current For Earth Fault Detection Winding A 6
Rated Voltage Factor (8h) 1,9 Un
28 Weight (approx.) kg 38
OUTDOOR SINGLE POLE
VOLTAGE TRANSFORMERS
VH24
A32-H
• Outdoor application
• Cyloaliphatic epoxy resin insulated
• Ambient air temperature: -40ºC to +55ºC
• Altitude: Up to 1000 meters above sea level (>1000m on request)
• Exposure to solar radiation: More than 2.800 hours annually
peaking at 1000W/m² for horizontal surfaces.
• Max. relative humidity: 100% Max. wind. velocity: 100km/h
• Standard: IEC 61869-3, ANSI, GOST, VDE
VH24
TECHNICAL DATA
TYPE VH24
Rated Data
Highest Voltage For Equipment, Um(r.m.s.) kV Up to 24
Test Voltages (maximum) kV 50/125
Rated Freguency Hz 50 or 60
Rated Primary Voltage, Un (max.) kV 24/√3
Secondary Voltage V 100/√3 or 110/√3 or 120/√3
Rated Burden in Class 0.2-0.5-1.0 VA 5 - 10 - 15 - 20 - 30 - 40...
Max. Rated Burden For Protection Purpose in Class 3P/6P VA 100
Thermal Limiting Current For Earth Fault Detection Winding A 6
Rated Voltage Factor (8h) 1,9 Un
Weight (approx.) kg 45 29
OUTDOOR SINGLE POLE
VOLTAGE TRANSFORMERS
VH36
• Outdoor application
• Cyloaliphatic epoxy resin insulated
• Ambient air temperature: -40ºC to +55 ºC
• Altitude: Up to 1000 meters above sea level (>1000m on request)
• Exposure to solar radiation: More than 2.800 hours annually
peaking at 1000W/m² for horizontal surfaces.
• Max. relative humidity: 100% Max. wind. velocity: 100km/h
• Standard: IEC 61869-3, ANSI, GOST, VDE
VH36
TECHNICAL DATA
TYPE VH36
Rated Data
Highest Voltage For Equipment, Um(r.m.s.) kV Up to 36
Test Voltages (maximum) kV 70/170
Rated Freguency Hz 50 or 60
Rated Primary Voltage, Un (max.) kV 36/√3
Secondary Voltage V 100/√3 or 110/√3 or 120/√3
Rated Burden in Class 0.2-0.5-1.0 VA 5 - 10 - 15 - 20 - 30 - 40...
Max. Rated Burden For Protection Purpose in Class 3P/6P VA 100
Thermal Limiting Current For Earth Fault Detection Winding A 6
Rated Voltage Factor (8h) 1,9 Un
30
Weight (approx.) kg 60
OUTDOOR DOUBLE POLE
VOLTAGE TRANSFORMERS
2VH24
• Outdoor application
• Cyloaliphatic epoxy resin insulated
• Ambient air temperature: -40ºC to +55ºC
• Altitude: Up to 1000 meters above sea level (>1000m on request)
• Exposure to solar radiation: More than 2.800 hours annually
peaking at 1000W/m² for horizontal surfaces.
• Max. relative humidity: 100% Max. wind. velocity: 100km/h
• Standard: IEC 61869-3, ANSI, GOST, VDE
2VH24
TECHNICAL DATA
TYPE 2VH24
Rated Data
Highest Voltage For Equipment, Um(r.m.s.) kV Up to 24
Test Voltages (maximum) kV 50/125
Rated Freguency Hz 50 or 60
Rated Primary Voltage, Un (max.) kV 24
Secondary Voltage V 100 or 110 or 120
Rated Burden in Class 0.2-0.5-1.0 VA Max. 150
Rated Voltage Factor (8h) 1,2 Un
Weight (approx.) kg 48 31
OUTDOOR DOUBLE POLE
VOLTAGE TRANSFORMERS
2VH36
• Outdoor application
• Cyloaliphatic epoxy resin insulated
• Ambient air temperature: -40ºC to +55ºC
• Altitude: Up to 1000 meters above sea level (>1000m on request)
• Exposure to solar radiation: More than 2.800 hours annually
peaking at 1000W/m² for horizontal surfaces.
• Max. relative humidity: 100% Max. wind. velocity: 100km/h
• Standard: IEC 61869-3, ANSI, GOST, VDE
2VH36
TECHNICAL DATA
TYPE 2VH36
Rated Data
Highest Voltage For Equipment, Um(r.m.s.) kV Up to 36
Test Voltages (maximum) kV 70/170
Rated Freguency Hz 50 or 60
Rated Primary Voltage, Un (max.) kV 36
Secondary Voltage V 100 or 110 or 120
Rated Burden in Class 0.2-0.5-1.0 VA Max. 150
Rated Voltage Factor (8h) 1,2 Un
32
Weight (approx.) kg 65