DEPARTMENT OF ENERGY
(Kagawaran ng Enerhiya)
DOE DC2016-04-0005
PPR 01: AC
Edition 2016
Annex B.1
Particular Product Requirements:
Air Conditioners
Table of Contents
Foreword .................................................................................................. 3
B.1.1 Scope .............................................................................................. 3
B.1.2 Definition of Terms ......................................................................... 3-4
B.1.3 Normative Reference.......................................................................... 4
B.1.4 Validation of Energy Labels ................................................................. 4
B.1.5 Sampling Method ............................................................................... 4
B.1.6 Specific Guidelines for the Conduct of Verification Testing .................... 4-5
B.1.7 Declaration of Generic Models ............................................................. 5
B.1.8 Monitoring ........................................................................................ 6
B.1.9 Performance Requirements .............................................................. 6-7
B.1.10 Presentation of Energy Labels....................................................... 8-10
B.1.11 Specification and Dimension of Energy Guide .................................... 10
B.1.12 Correction of Performance Ratings ................................................... 11
This PPR shall be an integral part of the Department Circular No. DC2016-04-
0005 entitled “Declaring the Compliance of Importers, Manufacturers,
Distributors and Dealers of electrical Appliances and Other Energy-Consuming
Products with the Philippine Energy Standards and Labeling Program (PESLP) as
a Policy of the Government” and its Implementing Guidelines.
This PPR provide the detailed technical requirements for air conditioners covered
by PESLP particularly requiring the attachment of an energy label as prescribed
in clause B.1.10
This PPR was developed by the Technical Working Group 01: Heating, Ventilating
and Air Conditioning Equipment and approved by the Policy Advisory Committee.
Any clause in this PPR not affected by amendments made in the General
Administrative Requirements and General Technical Requirements provided in
the Implementing Guidelines shall remain effective.
B.1.1 Scope
This PPR covers air conditioners with cooling capacity up to 50,000 kJ/hr or 14
kW for domestic and similar use, but not limited to, the following categories:
For the purpose of this PPR, the following definitions shall apply:
1. Make/Brand name - refers to the proprietary name use by the
manufacturer and importer.
2. Non-Ducted Air Conditioner - as defined in PNS ISO 5151:2014,
encased assembly or assemblies, designed primarily to provide free
delivery of conditioned air to an enclosed space, room or zone.
3. Cooling Seasonal Performance Factor (CSPF) - quotient of the
Cooling Seasonal Total Load (CSTL) in (kWh) divided by the Cooling
Seasonal Energy Consumption (CSEC) in (kWh).
4. Fixed speed air conditioner - refers to the fixed capacity unit
defined in PNS ISO 16358-1:2014.
5. Variable speed air conditioner - refers to the variable capacity
unit defined in PNS ISO 16358-1:2014.
6. Energy efficiency - refers to the quotient of capacity over power
input or capacity over power consumption.
The air conditioners covered under this PPR shall be tested, as applicable,
according to but not limited to the following standards and their future
amendments.
B.1.6.1 Testing
All general technical provisions in the Guidelines apply, including
the following:
B.1.6.1.1 Test methods to verify conformity to the claimed
information in the label shall be as specified in PNS
ISO 5151:2014 and PNS ISO 16358-1:2014.
B.1.8 Monitoring
B.1.8.2 The monitoring schedule for each showroom shall be done at least
once a year.
B.1.9.1.1 Fixed speed Air conditioners shall have rated CSPF not
lower than:
Note:
1. Measured CSPF shall be rounded-off to the nearest 0.01 Wh/Wh. The
rules of rounding-off shall be followed.
2. Verdict shall be based on the rounded-off value.
3. MEPS shall be subjected for review and upgrading every three (3)
years or earlier as necessary.
4. The MEPS for Variable-Speed, Multi-Split and Single-Ducted mobile is
under consideration until sufficient data will be available.
B.1.9.2 Tolerances
Note:
1. Measured percentage value shall be rounded-off to the nearest tenth.
The rules of rounding- off shall be followed.
2. Verdict shall be based on the rounded-off value.
Note: The method used on the above table is normalization of distribution rated
EER of air conditioner based on the latest list of certified air conditioner (April
2016)
1- Star
2- Star
4 -Star
B.1.11.1 The color of the label shall be yellow and blue. Letters and
numerals in blue background are in yellow, while letters and
numerals in yellow background are in blue.
B.1.11.2 The label shall have a dimension of 110 mm width and 150
mm height.
B.1.11.3 All required parameters shall be clear and conspicuous.
B.1.11.4 The paper thickness, pantone color, font face and size shall
be as follows:
Paper Thickness:
Paper thickness: 120 gsm
Pantone Color:
Pantone color yellow 100
Pantone color blue 100
Font Face and Size base on Energy label design artwork:
a. “Energy Guide”: Arial bold, 22 pts.
b. “Air Conditioner”: Arial bold, 11 pts.
c. “Cooling Seasonal Performance Factor”: Arial narrow bold, 9
pts.
d. “Rated CSPF”: Arial bold, 36 pts.
Table B.1.1 Energy Efficiency Classification (Window Type & Split Type)
Cooling Seasonal Performance Factor (CSPF)
Fixed Speed Variable Speed
EEC
Below 3.33 3.33 kW and Below 3.33 3.33 kW and
kW above kW above
One Star 2.90 to 2.93 2.81 to 2.83 - -
Two Star 2.94 to 3.03 2.84 to 2.94 - -
Three Star 3.04 to 3.24 2.95 to 3.12 - -
Four Star 3.25 to 3.99 3.13 to 3.76 3.25 to 3.99 3.13 to 3.76
Five Star 4.00 and 3.77 and 4.00 and 3.77 and
above above above above
Note 1: By 2020, in line with the ASEAN harmonization, the MEPS shall be the four (4) star
EEC.
Note 2: New set of values on table B.1.1 will be based on the available data where the
minimum CSPF will be 3.25 for units with capacity below 3.33 kW; and 3.13 for
units with capacity above 3.33 kW.