0970 - MAN - LCWM - 61070041 - y - EN - InstallationServiceManual
0970 - MAN - LCWM - 61070041 - y - EN - InstallationServiceManual
0970 - MAN - LCWM - 61070041 - y - EN - InstallationServiceManual
RingMount®
Weigh Modules
Installation and Service
Manual
61070041
(1/14).03
© 2000, 2001, 2004, 2006, 2010, 2011, 2014 Mettler-Toledo, LLC
No part of this manual may be reproduced or transmitted in any form or by any means, electronic or
mechanical, including photocopying and recording, for any purpose without the express written permission
of METTLER TOLEDO.
U.S. Government Restricted Rights: This documentation is furnished with Restricted Rights.
METTLER TOLEDO
Publication Name: 0970 Ring Weigh Modules Installation and Service Manual
Information about METTLER TOLEDO Technical Training can be obtained by writing, calling, or faxing:
METTLER TOLEDO
1900 Polaris Parkway
Columbus, Ohio 43240 USA
Phone: (614) 438-4511
Fax: (614) 438-4958
www.mt.com
WARNING!
This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used
properly, i.e., in accordance with the instructions manual, may cause harmful interference to radio
communications. It has been tested and found to comply with the limits for a Class A computing device,
pursuant to Subpart J of Part 15 of FCC Rules, which are designed to provide reasonable protection against
such interference when operated in a commercial environment. Operation of this equipment in a residential
area is likely to cause interference to radio communications, in which case the user at his own expense will
be required to take whatever measures may be required to correct the interference.
to which this declaration relates is in conformity with the following standard(s) or other normative document(s).
auf das sich diese Erklärung bezieht, mit der/den folgenden Norm(en) oder Richtlinie(n) übereinstimmt.
Auquel se réfère cette déclaration est conforme à la (aux) norme(s) ou au(x) document(s) normatif(s).
Al que se refiere esta declaración es conforme a la(s) norma(s) u otro(s) documento(s) normativo(s).
Waarnaar deze verklaring verwijst, aan de volende norm(en) of richtlijn(en) beantwoordt.
A cui si riferisce questa dichiarazione è conforme alla/e sequente/i norma/e o documento/i normativo/i.
in combination with an indicator terminal produced by Mettler-Toledo is in conformity with the following directives and standards.
Council directive on the harmonization of the laws of the Member Standards: Certificate number
states: (if applicable)
relating to non-automatic weighing instruments (90/384/EEC) amended EN 45501 D09-00.08
by directive (93/68/EEC), Article 1.2.a. and
OIML R60/1991
relating to electromagnetic compatibility (89/336/EEC) amended by EN 50081-1
directive (93/68/EEC; 92/31/EEC) EN 50082-2
relating to electrical apparatus for potentially explosive atmospheres EN 60079-0 : 2006 KEMA 03ATEX1372x1
(84/47/EEC) EN 60079-11 : 2007 II 2 G Ex ib IIC T4 or T6
EN 61241-0 : 2006 II 2 D Ex tD A21 IP 6X T70°C
EN 61241-1 : 2004
EN 60079-0 : 2006 KEMA 03ATEX1373x1
EN 60079-15 : 2005 II 3 G Ex nA II T4 or T6
EN 61241-0 : 2006 II 3 G Ex nL IIC T4 or T6
EN 61241-1 : 2004 II 3 D Ex tD A22 IP 6X T70°C
Directive 2011/65/EC related to the restrictions of Hazardous N/A N/A
Substances (RoHS) in electrical and electronic equipment.
Mettler-Toledo, LLC.
Worthington, Ohio USA
Darrell Flocken, Manager – Weights & Measures
Office of Weights and Measures
According to EN 45014
1
Certificate issued by DEKRA, Utrechtseweg 310, 6812 AR Arnhem, The Netherlands – NB Number 0344
PROPRIETARY NOTICE
The information contained in this publication is derived in part from proprietary and patented data of METTLER TOLEDO. This
publication shall not be copied in whole or in part without prior written approval of METTLER TOLEDO, nor shall it be used for
any purpose other than that intended. This document is subject to change without notice.
STANDARD WARRANTY
METTLER TOLEDO warrants that the equipment covered by this warranty will be free from defects in workmanship and material
for one year from date of installation or eighteen (18) months from date of shipment to the buyer, whichever comes first.
Should any such defects be found and reported during the first thirty (30) days after installation (if installation occurs during the
warranty period), METTLER TOLEDO (herein referred to as the “Company”) will, at its option, refund the purchase price or
correct such defects, furnishing replacement parts and service free of charge to the buyer. For the remainder of the first 12
months of the warranty term, the Company will furnish necessary replacement parts and on-site technician’s service free of
charge, provided the Buyer agrees to pay reasonable technician’s travel time, vehicle mileage, and associated travel expenses
to and from the nearest authorized Company service location. If the equipment is covered by a two-year warranty, for the last
12 months or remaining balance of the warranty period, whichever comes first, the Company will furnish the necessary
replacement parts to the Buyer free of charge, provided that the Buyer agrees to pay reasonable technician’s on-site labor
services, travel time, mileage, and expenses to and from the nearest authorized Company service location. The following are
NOT covered under any of these warranties:
1. Initial installation and ongoing scale calibration.
2. Damage to scale components by gross abuse, fire, flooding, explosion, water, voltage surges, or civil disturbance.
3. Normal maintenance or consumable items.
This warranty covers only the 0970 RingMount weigh module. Refer to METTLER TOLEDO Standard Product Warranty for
coverage of other scale system components, including scale instrument, printer, and/or other accessories.
THE COMPANY EXPRESSLY WARRANTS THE EQUIPMENT MANUFACTURED BY IT AS SET FORTH HEREIN. THE COMPANY
MAKES NO OTHER WARRANTIES EITHER EXPRESSED OR IMPLIED (INCLUDING WITHOUT LIMITATION WARRANTIES AS TO
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE). IN ADDITION, THIS DOCUMENT SHALL CONSTITUTE THE SOLE
AND EXCLUSIVE REMEDIES OF THE BUYER FOR ANY BREACH BY THE COMPANY OF ITS WARRANTIES HEREIN.
COMPANY LIABILITY UNDER THIS WARRANTY OR ANOTHER WARRANTY, WHETHER EXPRESSED OR IMPLIED IN LAW OR FACT,
SHALL BE LIMITED TO THE REPAIR OR REPLACEMENT OF DEFECTIVE MATERIAL AND WORKMANSHIP, AND IN NO EVENT
SHALL IT BE LIABLE FOR CONSEQUENTIAL OR INDIRECT DAMAGES.
This warranty coverage is applicable only to the United States of America.
Export Products: The Company warrants equipment destined for export or sold for export to be free from defects in
workmanship and material for a period of one year from date of installation or 18 months from date of shipment to the Buyer,
whichever occurs first. Should any such defect be found within that period, parts will be furnished free of charge (ex works)
point of origin or final distribution center. If the Buyer requests the performance of warranty work provided for under the
foregoing warranty outside of the contiguous United States, the Buyer shall be required to pay for labor, travel time, living, and
travel expenses of any personnel required to perform such warranty work.
APPLICATION GUIDES
The only warranty of METTLER TOLEDO is for the product it supplies under the Product Warranty Statement listed above.
Weighing application guidelines pertain to METTLER TOLEDO products.
Precautions
WARNING
READ this manual BEFORE PERMIT ONLY QUALIFIED PERSONNEL TO SERVICE THIS
operating or servicing this EQUIPMENT. EXERCISE CARE WHEN MAKING CHECKS,
equipment. TESTS, AND ADJUSTMENTS THAT MUST BE MADE WITH
POWER ON. FAILING TO OBSERVE THESE PRECAUTIONS CAN
RESULT IN BODILY HARM.
WARNING
DO NOT allow untrained DISCONNECT ALL POWER TO THIS UNIT BEFORE INSTALLING,
SERVICING, CLEANING, OR REMOVING THE FUSE. FAILURE TO
personnel to operate, clean,
DO SO COULD RESULT IN BODILY HARM AND/OR PROPERTY
inspect, maintain, service, or
DAMAGE.
tamper with this equipment.
CAUTION
ALWAYS DISCONNECT this BEFORE CONNECTING/DISCONNECTING ANY INTERNAL ELECTRONIC COMPONENTS OR
equipment from the power INTERCONNECTING WIRING BETWEEN ELECTRONIC EQUIPMENT, ALWAYS REMOVE
source before cleaning or POWER AND WAIT AT LEAST 30 SECONDS. FAILURE TO OBSERVE THESE PRECAUTIONS
performing maintenance. COULD RESULT IN BODILY HARM OR DAMAGE TO OR DESTRUCTION OF THE EQUIPMENT.
CAUTION
CALL METTLER TOLEDO for parts,
OBSERVE PRECAUTIONS FOR HANDLING ELECTROSTATIC
information, and service.
SENSITIVE DEVICES.
CAUTION
DO NOT PASS WELDING CURRENT THROUGH THE LOAD CELLS! WHEN WELDING ON A
SCALE, ALWAYS GROUND THE WELDING DEVICE AS CLOSE TO THE WORK AS POSSIBLE.
NEVER WELD CLOSER THAN WITHIN 4 FEET (1.2 METERS) OF ANY LOAD CELL WITHOUT
REMOVING THE LOAD CELL.
WARNING
DO NOT USE THE RAAD JUNCTION BOX OR IDNet JUNCTION
BOX IN LOCATIONS CLASSIFIED AS HAZARDOUS BY THE
NATIONAL ELECTRICAL CODE (NEC) ARTICLE 500.
CAUTION
BE SURE TO BLOCK THE SCALE WHEN IT IS IN THE RAISED POSITION. OBSERVE ALL
APPROPRIATE SAFETY PROCEDURES WHEN INSTALLING AND SERVICING THE WEIGH
MODULES.
WARNING
IF USED IN A HAZARDOUS AREA, THE HAZARDOUS AREA MUST
BE MADE SAFE PRIOR TO INSTALLATION, REPLACEMENT, OR
TROUBLESHOOTING. FAILURE TO COMPLY COULD RESULT IN
PERSONAL INJURY, DEATH, AND/OR PROPERTY DAMAGE.
Disposal of Electrical
and Electronic Equipment
In conformance with the European Directive 2002/96 EC on Waste Electrical and
Electronic Equipment (WEEE) this device may not be disposed of in domestic waste.
This also applies to countries outside the EU, per their specific requirements.
Please dispose of this product in accordance with local regulations at the collecting
point specified for electrical and electronic equipment.
If you have any questions, please contact the responsible authority or the distributor
from which you purchased this device.
Should this device be passed on to other parties (for private or professional use), the
content of this regulation must also be related.
Thank you for your contribution to environmental protection.
Contents
1 Introduction ............................................................................................... 1-1
General .......................................................................................................................... 1-1
Model Number ................................................................................................................ 1-2
Accuracy ........................................................................................................................ 1-2
Power Supply Requirements ............................................................................................. 1-3
Load Cell Specifications .................................................................................................. 1-3
Approvals ....................................................................................................................... 1-4
Dimensions - Standard .................................................................................................... 1-5
Dimensions - Redundant .................................................................................................. 1-6
1 Introduction
General
Model 0970 RingMount® weigh modules are used to convert tanks, hoppers, and other
structures into scales. Each weigh module consists of a torsion-ring load cell and the
mounting plates needed to attach it to a structure. The weigh modules are available in
capacities of 250 kg to 10,000 kg.
We also offer redundant RingMount weigh modules, which produce two weight signals to
verify weighing accuracy and provide backup weighing. Each redundant weigh module is
equipped with two torsion-ring load cells. Redundant weigh modules are available in
capacities of 250 kg to 5,000 kg.
This manual explains how to install and service Model 0970 weigh modules. If any
information is incorrect or missing from the manual, please use the Publication
Suggestion Report at the back of the manual to tell us about it.
(1/14) 1-1
METTLER TOLEDO 0970 RingMount Weigh Modules Installation and Service Manual
Model Number
The weigh modules are listed in Table 1-1.
Accuracy
Scale accuracy depends on:
The design of the support steel on which the modules are mounted and the design of
the weigh structure (tank, hopper, conveyor, etc.) mounted to the modules
The design and number of dead-to-live connections attached to the scale
The total load cell capacity
Environmental factors: wind, vibration, temperature variations, etc.
Refer to the METTLER TOLEDO Weigh Module Systems Handbook
(Download from www.mt.com/ind-system-handbook).
1-2 (1/14)
Chapter 1: Introduction
Power Supply Requirements
Power Supply
Requirements
A METTLER TOLEDO digital scale terminal is used to power the analog load cells in
Model 0970 weigh modules. The type of terminal that is used determines which type of
junction box (Analog, RAAD, or IDNet) is required for the weigh modules.
Refer to the terminal’s service manual for the terminal’s power requirements.
(1/14) 1-3
METTLER TOLEDO 0970 RingMount Weigh Modules Installation and Service Manual
Approvals
NTEP Certification
Model RLC load cells (except 250-kg and 10,000-kg load cells) meet or exceed NIST
Handbook-44 requirements for Class III 5000 divisions/multiple cell (minimum). A
certificate of conformance was issued under the National Type Evaluation Program
(NTEP) of the National Conference of Weights and Measures (certificate number 00-
124).
OIML Certification
Model RLC load cells meet or exceed OIML requirements for R60 C3 3000 divisions. An
optional RLC load cell is available to meet C6 6000-division accuracy (1,000 kg to
5,000 kg). European Test Certificate: D09-00.08.
1-4 (1/14)
Chapter 1: Introduction
Dimensions - Standard
Dimensions - Standard
L
L1 L2
W2
D
W1 W
H2
H1
Load Cell
L L1 L2 W W1
Capacity
Load Cell
W2 H H1 H2 D
Capacity
(1/14) 1-5
METTLER TOLEDO 0970 RingMount Weigh Modules Installation and Service Manual
Dimensions -
Redundant
L
L1 L2
W2
D
W1 W
H2
H1
Load Cell
L L1 L2 W W1
Capacity
Load Cell
W2 H* H1 H2 D
Capacity
1-6 (1/14)
Chapter 2: Inspection and Site Selection
Inspection
Inspection
When you receive your weigh modules, inspect the packing containers and modules for
freight damage. Inspect:
1. Load cell and suspension assemblies
2. Load cell cables and junction box
3. Overall assembly
If you find damage, contact your freight carrier immediately. Fill out the enclosed
warranty card and return the weigh module to the address indicated.
Site Selection
Problems installing weigh modules are often caused by inappropriate site conditions.
Before installing the weigh modules, make sure the site meets the following criteria:
All support surfaces must be on the same plane and level.
At each weigh module location, the floor or structure must provide adequate support
and equal deflection for a given load throughout the scale’s weighing range.
Throughout the scale’s weighing range, the top plate should not deflect more than
0.5 degree with respect to the bottom plate.
Proper drainage away from each of the weigh modules.
No heavy vibrations or wind currents at or near the scale.
Access around each weigh module for installation and service.
Locations on the scale to add test weights for calibration.
Access to the scale for moving test weights to the scale’s loading locations.
A position near the scale to mount the junction box
(Do not mount the junction box on the live portion of the scale).
No excessive or unusual loading caused by the site or type of equipment mounted to
the weigh modules.
Shared foundation: Does the vessel to be weighed have an exclusive, isolated
support foundation? Does it share supports with other vessels? If the vessel shares a
foundation, the scale’s accuracy might be affected by the weight of other structures
on the foundation.
If the site meets the criteria listed here, proceed with the installation. Otherwise, make
necessary adjustments before installing the modules.
(1/14) 2-1
Chapter 3: Installation
General Guidelines
3 Installation
General Guidelines
WARNING
IF USED IN A HAZARDOUS AREA, THE HAZARDOUS AREA
MUST BE MADE SAFE PRIOR TO INSTALLATION,
REPLACEMENT, OR TROUBLESHOOTING. FAILURE TO
COMPLY COULD RESULT IN PERSONAL INJURY, DEATH,
AND/OR PROPERTY DAMAGE.
Each application has its own unique requirements and should be planned by a qualified
structural engineer. This manual is meant to serve only as a general guide for
installation.
(1/14) 3-1
METTLER TOLEDO 0970 RingMount Weigh Modules Installation and Service Manual
Weigh Module
Orientation
Before installing the weigh modules, decide how they will be arranged. Space the weigh
modules evenly so that each one supports approximately the same amount of weight.
In most applications, three or four weigh modules are used to support the weigh
structure. Figure 3-1 shows recommended mounting arrangements.
2L
3-2 (1/14)
Chapter 3: Installation
Installation
Installation
If the weigh modules are to be mounted to a concrete floor, locate and anchor the base
plates to the concrete before setting the weigh structure (tank, hopper, etc.) on the
modules. Make sure that you will be able to adjust the weigh structure to align it correctly
with the weigh modules. See Figure 3-4 for alternative installation methods.
Before you begin installation, make sure that the top plate of each weigh module is
locked into position so that it will not transfer any load to the load cell. During
installation, the shipping blocks should be in position (see Figure 3-2) and clamped to
the hold-down bolts.
Shipping
Block
Shipping
Block
WARNING
BE SURE TO BLOCK THE SCALE WHEN IT IS IN THE RAISED POSITION. IF THE
SCALE IS NOT SECURELY BLOCKED, IT COULD SHIFT POSITION, RESULTING IN
BODILY HARM OR PROPERTY DAMAGE.
CAUTION
DO NOT PASS WELDING CURRENT THROUGH THE LOAD CELLS! WHEN WELDING ON A
SCALE, ALWAYS GROUND THE WELDING DEVICE AS CLOSE TO THE WORK AS
POSSIBLE. NEVER WELD CLOSER THAN 4 FEET (1.2 METERS) TO ANY LOAD CELL
WITHOUT REMOVING THE LOAD CELL.
(1/14) 3-3
METTLER TOLEDO 0970 RingMount Weigh Modules Installation and Service Manual
Support
Bracket is
Not Level
1/2°
maximum
1/2°
maximum
Support
Structure is
Not Level
Figure 3-3: Maximum Amount that a Mounting Plate can be out of Level
IMPORTANT: When installing redundant RingMount weigh modules, bolt the top plates to
the weigh structure and the base plates to the support structure. Do not weld the plates.
You must remove the entire weigh module in order to replace a load cell. Welding the
plates to the structures will complicate replacement and other service procedures.
4. Fasten the top plate to the weigh structure using suitable hardware (see Table 3-1)
or by welding (see step 5 for welding guidelines). Do not weld redundant weigh
modules.
0970 Weigh Module Base Plate Bearing Top Plate Bolts Base Plate Bolts
NOTE: Mounting plate
bolts are not supplied by psi (K Pascal) (Metric) (Metric)
METTLER TOLEDO. 250 kg 23 (158)
500 kg 46 (317)
1,000 kg 92 (634) 1/2-13 UNC 1/2-13 UNC
2,000 kg 184 (1,267) (M12 x 1.75) (M12 x 1.75)
3,500 kg 322 (2,217)
5,000 kg 459 (3,168)
10,000 kg 580 (4,001) 5/8-18 UNC 5/8-18 UNC
(M16 x 2) (M16 x 2)
5. Bolt or weld each base plate to the foundation, structural beam, or anchored grout
plate:
Bolts: Mark the positions of the base plate mounting holes on the foundation
(four holes per base plate). Drill appropriately sized holes in the foundation.
3-4 (1/14)
Chapter 3: Installation
Installation
Each base plate should be level within 0.5 degree, and there should be no
gaps between the base plate and the foundation (shim as required). Fasten the
base plates to the foundation using suitable hardware (see Table 3-1).
NOTE: For redundant weigh modules, do not embed bolts in a concrete
foundation. You must be able to remove all bolts so that the weigh module can
be removed for service.
Welding: Remove the load cell before welding a weigh module. Weld the base
plates to the structural beam or anchored grout plate on all four sides of each
base plate:
9-mm (3/8-inch) fillet
25 mm (1 inch) long
75-mm (3-inch) centers, 50 mm (2 inches) between welds
Each base plate should be level within 0.5 degree, and there should be no
gaps between the base plate and the foundation (shim as required).
IMPORTANT: Do not weld redundant weigh modules. You must remove the
entire weigh module in order to replace a load cell. Welding the plates to the
structures will complicate replacement and other service procedures.
6. If the load cells were removed to protect them during welding, replace the load cells
in the weigh modules (see Figure 6-1).
7. After securing all the top and base plates, remove the shipping blocks and clamps.
NOTE: Consider calibrating the scale 8. Mount the junction box in a location where the load cell cables can be properly
before connecting any piping to the terminated in the junction box. Do not mount the junction box on the scale.
scale. The scale can then be used as
a meter to determine if a proper live- NOTE: Each load cell is supplied with a standard length of cable. Do not lengthen or
to-dead connection was made. shorten load cell cables in the field! Changing the length of a load cell cable will
affect compensation and void the warranty. If a cable is too long, simply coil the
excess cable and place it in or near the junction box. Nonstandard lengths of cable
can be ordered for applications that require them.
9. Connect the load cell cables to the junction box and terminate wires according to the
wiring and color code decal on the underside of the junction box lid.
IMPORTANT: For redundant weigh modules, wire all upper load cells to one
junction-box network and wire all lower load cells to a second junction-box network.
Connect each junction-box network to a separate scale terminal, or connect both
networks to a scale terminal that is capable of handling two scales.
10. Connect the junction box to the scale terminal with an appropriate cable.
11. Confirm that all live-to-dead connections are flexible and securely anchored at both
the scale and dead connection point.
(1/14) 3-5
METTLER TOLEDO 0970 RingMount Weigh Modules Installation and Service Manual
Tapped
Holes
Through
Holes Concrete
Leveling
Nonshrink Adjustment
Epoxy Grout Nut
3-6 (1/14)
Chapter 3: Installation
Modes of Operation
Modes of Operation
IMPORTANT: For redundant weigh modules, wire all upper load cells to one junction-box
network and wire all lower load cells to a second junction-box network. Connect each
junction-box network to a separate scale terminal, or connect both networks to a scale
terminal that is capable of handling two scales.
Analog Mode
Model 0970 weigh modules can be used with an analog junction box for summing the
load cell outputs. Only analog-compatible scale terminals work with an analog junction
box. See Figure 3-5 and Table 3-2 for cable connections.
SHLD
+EXE
+EXE
+SIG
+SIG
-EXE
-EXE
-SIG
-SIG
LC2 LC4
+EXE +EXE
+SEN +SEN
INPUT
+SIG ANALOG JBOX +SIG
AUX
LC1 LC3
SHLD
SHLD
+EXE
+EXE
+SIG
+SIG
-EXE
-EXE
-SIG
-SIG
(1/14) 3-7
METTLER TOLEDO 0970 RingMount Weigh Modules Installation and Service Manual
RAAD Mode
Model 0970 weigh modules can be used with a RAAD junction box for summing load
cell outputs. An IND780 terminal must be used with the RAAD junction box. The terminal
serves as the host for the RAAD junction box, allowing you to use the terminal’s keypad
to adjust scale parameters. See Figure 3-6 and Table 3-3 for cable connections. Load
cell wiring for RAAD mode is the same as for analog mode.
NOTE: The RAAD box is a Remote
Addressable Analog-to-Digital junction
box. It converts a standard analog
signal to a DigiTOL signal and allows WARNING!
monitoring of individual load cell
channels. DO NOT USE THE RAAD JUNCTION BOX IN LOCATIONS
CLASSIFIED AS HAZARDOUS BY THE NATIONAL
NOTE: A DigiTOL POWERCELL card ELECTRICAL CODE (NEC) ARTICLE 500.
must be installed in the IND780
terminal.
COM B
COM A
COM A
SW4: On if Load Cell 4 is used
SHLD
SHLD
SHLD
SHLD
+EXC
+EXC
+EXC
+EXC
+SIG
+SIG
+SIG
+SIG
-EXC
-EXC
-EXC
-EXC
GND
GND
GND
GND
GND
GND
-SIG
-SIG
-SIG
-SIG
+VC
+VB
+VC
+VB
+VA
+VA
SW5: On if last J-box in series
3-8 (1/14)
Chapter 3: Installation
Modes of Operation
IDNet Mode
The IDNet junction box can output an IDNet data format compatible with METTLER
TOLEDO IDNet weight displays. See Figure 3-7 and Table 3-4 for cable connections. For
detailed information about the terminal’s capabilities and operating instructions, refer to
the appropriate service manual.
WARNING!
DO NOT USE THE IDNet JUNCTION BOX IN LOCATIONS
CLASSIFIED AS HAZARDOUS BY THE NATIONAL
ELECTRICAL CODE (NEC) ARTICLE 500.
ST2 ST3
W1
+EXC
LC4
P7 P8
Terminal
-SIG +SIG
1
-EXC
SA1
P1 P2
5
W3 W2 W5
(1/14) 3-9
METTLER TOLEDO 0970 RingMount Weigh Modules Installation and Service Manual
Junction Box
Home Run Cable Spherical Washer Enclosure
Connect the home run cable from the scale terminal to the junction box (refer to Figure 3-
8):
1. Wire the home run cable to the PCB according to Figure 3-5 for Analog, Figure 3-6
for RAAD, or Figure 3-7 for IDNet.
2. Place the desiccant bag inside the junction box.
3. Reinstall the junction box lid. Make sure that the rubber gasket is clean and correctly
positioned. Tighten all screws and make sure all cord grip caps are secure.
3-10 (1/14)
Chapter 4: Calibration
Shift Adjust
4 Calibration
Shift Adjust
Before making calibration adjustments, check all mechanical parts and make sure that
the scale provides repeatable weight readings. To check repeatability, repeatedly place a
test weight in the same position on the scale and confirm that you get the same weight
reading each time.
Then perform a shift adjust so that the weight reading at or near each weigh module is
the same for the same test weight.
The test weight used for the shift test should equal at least 10 percent of the rated scale
capacity. Test weights should be concentrated directly (or as close as possible) over the
weigh modules.
Perform a shift adjustment, using the load cell trim potentiometers mounted on the PCB
inside the analog junction box.
1. Turn all potentiometers fully clockwise before applying test weights.
2. Successively place the test weight at each of the designated locations (at or near the
weigh modules). Record each of the displayed weight readings.
3. Determine the location with the lowest weight reading and note the reading.
4. Start at the location of the lowest weight reading, and proceed clockwise, placing the
test weight at each designated location. If necessary, adjust the trim potentiometer
corresponding to that location to obtain the weight reading noted in Step 3.
5. Repeat this procedure until all weight readings at the designated locations are the
same or within the tolerances specified by the local weights and measures authority.
6. Make sure all cable connectors and cord grip caps are tight, place the desiccant bag
in the box, and reinstall the junction box lid.
(1/14) 4-1
METTLER TOLEDO 0970 RingMount Weigh Modules Installation and Service Manual
ST2 ST3
W1
Potentiometer Pair LC4
+EXC
LC4
P7 P8
1 Potentiometer Pair LC3
-SIG +SIG
-EXC
LC3 6
LC2
7
8 LC4
3 7 Potentiometer Pair LC1
6 LC3
8 5
LC1 4
3
LC2
4 2
9 1
LC1
-SEN +SEN
SA1
5 P1 P2
Hook Switches
W3 W2 W5
1. Successively place the test weight(s) at the designated locations and record each
weight reading. If the readings are within the desired tolerance, no shift adjustment is
needed. If the readings are not within the desired tolerance, perform Steps 2 to 6.
2. Activate the trim potentiometers by opening the eight hook switches (if they are not
already open) on the PCB (see Figure 4-1). Once activated, the switches remain
open. Do not close the latches, even after completing the shift adjustment.
3. Start the adjustment at the load cell having the highest positive reading. This process
trims the load cells to match the value of the lowest recorded value.
4. To make minor adjustments, turn the trim potentiometers (each load cell has two)
clockwise to increase the reading or counterclockwise to decrease the reading.
4-2 (1/14)
Chapter 4: Calibration
Scale Calibration (Span)
5. If the scale needs further adjustment, turn all potentiometers counterclockwise. Stop
turning the potentiometers when the indication on the instrument or meter stabilizes.
6. Reapply the test weight(s) to the location that has the highest recorded weight
reading. Then adjust the load cell potentiometers to match the reading of the location
that has the lowest recorded value. Repeat this step until the readings at all locations
are the same or within the specified scale tolerances. Repeat Step 1 to verify shift
tolerances.
7. Make sure all cable connectors and cord grip caps are tight. Then place a desiccant
bag in the box, leave all hook latches open, and reinstall the junction box lid.
Scale Calibration
(Span)
METTLER TOLEDO recommends calibrating the scale using test weights equal to the
scale’s capacity. With the proper test weight, continue calibrating the weighing system
according to the instructions provided in your digital terminal’s manual.
(1/14) 4-3
METTLER TOLEDO 0970 RingMount Weigh Modules Installation and Service Manual
Electronic Calibration
When using the electronic calibration method, replace the load cell cables with leads
from a load cell simulator. The simulator sends out a signal equal to the signal the load
cells should produce. Electronic calibration is noted for its speed and simplicity; however,
it calibrates only the electronics. It does not verify the scale performance because it
assumes that the tank and all mechanical connections are in perfect working order.
1. With the simulator adjusted to zero output, set the terminal to zero.
2. Adjust the simulator to full output, a signal equal to that which all the load cells
should produce at their rated capacity.
3. Adjust the terminal to show the total capacity of all load cells in the system.
4. Attach the load cell input to the terminal.
5. “Zero off” the empty weight of the tank.
4-4 (1/14)
Chapter 5: Routine Care and Maintenance
General
General
Once you have installed your scale, you should have an authorized METTLER TOLEDO
representative periodically inspect and calibrate it. If the scale is used for legal-for-trade
purposes, consult the local weights and measures authorities for minimum inspection
requirements. Contact your local authorized METTLER TOLEDO service representative for
information on periodic inspection and calibration services.
Site Inspection
Make sure that the scale site remains in good condition. Check for changes in the dead-
to-live connections, changes in support for the weigh modules, overloading and
excessive vibration conditions, and debris or material build-up under or around the scale
that could prevent the scale from moving freely.
(1/14) 5-1
Chapter 6: Troubleshooting
General
6 Troubleshooting
General
WARNING
IF USED IN A HAZARDOUS AREA, THE HAZARDOUS AREA
MUST BE MADE SAFE PRIOR TO INSTALLATION,
REPLACEMENT, OR TROUBLESHOOTING. FAILURE TO
COMPLY COULD RESULT IN PERSONAL INJURY, DEATH,
AND/OR PROPERTY DAMAGE.
WARNING
PERMIT ONLY QUALIFIED PERSONNEL TO SERVICE THIS
EQUIPMENT. EXERCISE CARE WHEN MAKING CHECKS,
TESTS, AND ADJUSTMENTS THAT MUST BE MADE WITH
POWER ON. FAILING TO OBSERVE THESE PRECAUTIONS
CAN RESULT IN BODILY HARM.
CAUTION
BEFORE CONNECTING/DISCONNECTING ANY INTERNAL ELECTRONIC COMPONENTS
OR INTERCONNECTING WIRING BETWEEN ELECTRONIC EQUIPMENT, ALWAYS
REMOVE POWER AND WAIT AT LEAST 30 SECONDS. FAILURE TO OBSERVE THESE
PRECAUTIONS COULD RESULT IN BODILY HARM OR DAMAGE TO OR DESTRUCTION
OF THE EQUIPMENT.
If a scale is not working properly, find out as much about the problem as possible. Try to
determine whether the problem is constant or intermittent. Mechanical and electrical
influences can cause malfunctions, so be patient and use sound logic when
troubleshooting.
Check the instrument cable for damage and check all connections for any loose/incorrect
wiring. Examine the physical location of the scale, checking for the following:
Water
Corrosive materials
Unlevel floors
High vibrations
Air currents
Physical damage to the scale platform or frame
(1/14) 6-1
METTLER TOLEDO 0970 RingMount Weigh Modules Installation and Service Manual
Check Wiring
1. Remove power from the system.
2. Remove the lid from the junction box and check the interior for moisture and foreign
material.
3. Make sure that all wiring connections are tight and that no insulation material is
touching the terminal contacts.
4. Check all cable connections for correct wiring. The wiring color codes are given in
Table 6-1.
5. Make sure that the trim resistor is still installed on the -Signal load cell wire.
*See Figure 3-6 and Table 3-3 for 6. Check all cable connectors and cord grip caps on the junction box. Tighten any
RAAD box instrument cable wiring. loose connectors.
6-2 (1/14)
Chapter 6: Troubleshooting
Check Load Cells
(1/14) 6-3
METTLER TOLEDO 0970 RingMount Weigh Modules Installation and Service Manual
Check Mechanical
Components
Because the 0970 weigh module design is so simple, only a few mechanical
components require troubleshooting. Make sure that the scale can move freely.
Check the following:
Is the scale rocking? Reshimming may be required.
Check the rocker pins for unusual wear. Replace unevenly worn pins or pins with
flattened bearing surfaces.
Check new or modified dead-to-live connections on the scale.
Does rigid piping or poor structural support result in mechanical binds?
CAUTION
BE SURE TO BLOCK THE SCALE WHEN IT IS IN THE RAISED POSITION. OBSERVE
ALL APPROPRIATE SAFETY PROCEDURES WHEN INSTALLING AND SERVICING THE
WEIGH MODULES.
9. Carefully pull the defective load cell cable through the conduit while feeding the string
through the junction box opening. Once the string is at the load cell location, detach
it from the load cell cable.
10. Remove the rocker pin and load cell receiver from the defective load cell.
6-4 (1/14)
Chapter 6: Troubleshooting
Load Cell Replacement - Redundant
CAUTION
BE SURE TO BLOCK THE SCALE WHEN IT IS IN THE RAISED POSITION. OBSERVE
ALL APPROPRIATE SAFETY PROCEDURES WHEN INSTALLING AND SERVICING THE
WEIGH MODULES.
8. Slide the weigh module out from under the weigh structure.
9. Remove the load cell retaining screws (three screws in the top plate and one screw
in the base plate) and keep them for reinstallation.
(1/14) 6-5
METTLER TOLEDO 0970 RingMount Weigh Modules Installation and Service Manual
10. Remove the load cells, receivers, and rocker pin from the weigh module.
11. Carefully pull the defective load cell cable through the conduit while feeding the string
through the junction box opening. Once the string is at the load cell location, detach
it from the load cell cable.
12. Remove the rocker pin and load cell receiver from the defective load cell.
Receiver
Rocker Pin
Receiver
6-6 (1/14)
Chapter 7: Service Parts
0970 Weigh Module
7 Service Parts
Refer to the following drawing and table when ordering parts for Model 0970 weigh
modules.
(1/14) 7-1
METTLER TOLEDO 0970 RingMount Weigh Modules Installation and Service Manual
9 4
10
3
11
8
12
7-2 (1/14)
Chapter 7: Service Parts
0970 Weigh Module
(1/14) 7-3
METTLER TOLEDO 0970 RingMount Weigh Modules Installation and Service Manual
Redundant Weigh
Module
5
8
2
10
11
4
7
6
9
1
6
3
8
7-4 (1/14)
Chapter 7: Service Parts
Redundant Weigh Module
(1/14) 7-5
Chapter 8: Reference Material
Reference Drawings
8 Reference Material
Reference Drawings
Weigh Module Systems Handbook
(Download from www.mt.com/ind-system-handbook)
Redundant:
TB601294
Recommended Spare
Parts
For part numbers, refer to Chapter 7.
Qty. Description
1 Load cell
1 Junction box circuit board (type of board is per model of scale)
1 Junction box desiccant bag
1 Rocker pin
(1/14) 8-1
METTLER TOLEDO
Publication Suggestion Report
841--7295
If you have suggestions concerning this publication, please complete this form and fax it to (614) 841
Clarity
What is not clear?
Sequence
What is not in the
the right order?
Other Comments
Use another sheet for
additional comments.
Phone Number: ( )
www.mt.com/support
P/N: 61070041
(1/14).03
61070041