PROJECT : HEXAWARE

SUBJECT : BMS POINTS for PHE and Fire Service.

SL No Description Location No. of Pumps


Working Standby PROVISION AVAILABLE IN THE PHE PANEL FUNCTION REQUIRED

1 Water Treatment Plant


NO/NC contactors available in the motor control
a Filter Feed Pumps Pump room 1 1 On/Off , Trip Status Monitoring
panel. Further connectivity shall be by BMS
NO/NC contactors available in the motor control
Chlorine dosing 1 On/Off , Trip Status Monitoring
panel. Further connectivity shall be by BMS
NO/NC contactors available in the motor control
UV sterilizer dosing 1 On/Off , Trip Status Monitoring
panel. Further connectivity shall be by BMS
pH Meter 1 0-10 VDC / 4-20 mA Output pH Monitoring
Conductivity Meter 1 0-10 VDC / 4-20 mA Output Conductivity levels
On line chlorine measurement 1 0-10 VDC / 4-20 mA Output Chlorine levels

NO/NC contactors available in the motor control


b RO Option TERRACE On/Off , Trip Status Monitoring
panel. Further connectivity shall be by BMS
NO/NC contactors available in the motor control
Circulation pump 1 1 On/Off , Trip Status Monitoring
panel. Further connectivity shall be by BMS
NO/NC contactors available in the motor control
Hydro Pneumatic pump – RO supply 1 1 On/Off , Trip Status Monitoring
panel. Further connectivity shall be by BMS

a Treated (Hydro Pneumatic) Pump room 4 1 Modbus RS485 Communication Provision

NO/NC contactors available in the motor control


3 HVAC Plant room/Phe Plant sump pumps Pump room 1 1 On/Off , Trip Status Monitoring
panel. Further connectivity shall be by BMS

NO/NC contactors available in the motor control


6 External Terrace rain water Pumps Ground 2 2 On/Off , Trip Status Monitoring
panel. Further connectivity shall be by BMS

NO/NC contactors available in the motor control


7 Organic waste convertor External 1 On/Off , Trip Status Monitoring
panel. Further connectivity shall be by BMS

8 Hot Water System


NO/NC contactors available in the motor control
Return Pump Terrace 1 1 On/Off , Trip Status Monitoring
panel. Further connectivity shall be by BMS
NO/NC contactors available in the motor control
Circulation pump Terrace 2 2 On/Off , Trip Status Monitoring
panel. Further connectivity shall be by BMS

Water Consumption Monitoring ,


9 Water meter for domestic Pump room 1 Backnet Output
Data Logging

Water Consumption Monitoring ,


Water meter for Flushing STP plant room 1 Backnet Output
Data Logging

Water Consumption Monitoring ,


Water meter for Terrace Rain water Pump room 1 Backnet Output
Data Logging

Water Consumption Monitoring ,


Water meter for HVAC STP plant room 1 Backnet Output
Data Logging

Fire pumps load


PROJECT : HEXAWARE
Panel 1
PROJECT : HEXAWARE
NO/NC contactors available in the motor control
1 Sprinkler Pump 1 On/Off , Trip Status Monitoring
panel. Further connectivity shall be by BMS.
NO/NC contactors available in the motor control
2 Hydrant pump 1 On/Off , Trip Status Monitoring
panel. Further connectivity shall be by BMS.
NO/NC contactors available in the motor control
3 Diesel Pump Pump room 1 On/Off , Trip Status Monitoring
panel. Further connectivity shall be by BMS.
NO/NC contactors available in the motor control
4 Jockey pump 1 On/Off , Trip Status Monitoring
panel. Further connectivity shall be by BMS.
NO/NC contactors available in the motor control
4 Water Curtain pump 1 On/Off , Trip Status Monitoring
panel. Further connectivity shall be by BMS.

STP- Separate Panel


a Flushing (Hydro Pneumatic) STP plant room 2 1 Modbus RS485 Communication Provision

NO/NC contactors available in the motor control


b Cooling Tower Pumps STP plant room 1 1 On/Off , Trip Status Monitoring
panel. Further connectivity shall be by BMS.

NO/NC contactors available in the motor control


c Irrigation pumps STP plant room 1 1 On/Off , Trip Status Monitoring
panel. Further connectivity shall be by BMS.

Water Level Indicator


1 Fire Tank B1 2 0-10 VDC / 4-20 mA Output

2 Raw Water Tank B1 2 0-10 VDC / 4-20 mA Output

3 Treated Water Tank B1 2 0-10 VDC / 4-20 mA Output

4 Over Head tank


Fire Water 4 0-10 VDC / 4-20 mA Output
Domestic Water 4 0-10 VDC / 4-20 mA Output
5 HVAC Makeup water tank Terrace – NE 1 0-10 VDC / 4-20 mA Output