REB 33-11 KV Transformer
REB 33-11 KV Transformer
REB 33-11 KV Transformer
(BREB)
TENDER DOCUMENT
FOR THE
VOLUME 2 OF 3
1
Section 8
Particular Specifications
2
Contents of Particular Specifications
3
SCHEDULE A
4
SCHEDULE A
INTRODUCTION AND PREAMBLE TO THE PRICE & TECHNICAL
SCHEDULES
The work comprise of creating facilities for 06 (Six) nos. 33/11kV outgoing feeders
through extension of 1 nos. 33 kV Bay-Breaker of existing Gonggadhorpotti sub-station
and dismantling of existing 33kV Bus-bar and installation of new Bus-bar & related
works for Manikganj PBS at Gonggadhorpotti Grid Sub-Station.
Outdoor switchyard:
Civil works:
Complete design, supply materials and construction of all civil items required for
extension of 33 kV bay at switchyard for steel structure and Equipment foundation, RCC
Internal road, Power and control cable trenches, surface finishing with gravels,
switchyard earthings, switchyard lighting, lightning protection. The cable duct
constructed by PGCB in the control room building shall be used to run the control/
power cables to switching room for connecting control panel and Energy metering panel
to be installed. All control panel, separate energy metering panel, battery chargers and
AC/DC panels shall be installed in the existing control room building (if applicable).
5
dedicated for the energy meters to be installed in a separate energy metering panel and
core 3 shall have ratio 2400-1600/5-5-5A, 30VA, 5P20 for protection. Burden Shall be
Calculated as per Field Condition and Resistance of the Instrument Cables.
Earthing System:
Design, supply, delivery, installation of earthing system and lightning protection screen
including connections, connectors and clamps to suit the switching station overall
arrangement and provide supporting design calculations. However the design and
6
installation of earthing system done by PGCB/PDB should be followed for the 33kV
existing switching station also. Grounding resistance to be maintained less than 0.2 ohm.
Building Lighting, Small Power, Air Conditioning and Ventilation : (If Applicable)
Complete design and calculations supply, delivery, installation, testing & commissioning
of equipment to provide lighting ,LV power supply and air conditioning system and
emergency DC lighting at strategic location for equipment operations and inspections.
Approach rood, cable trench etc. to be constructed by the contractor.
Complete design and calculations supply, delivery, installation, testing & commissioning
of equipment to provide lighting (sodium light) for security, roadway and switchyard and
emergency DC lighting at strategic location for equipment operations and inspections.
Training:
The Contract Price shall include all costs for training of Employer’s representatives at
site. Four Engineers (Two from REB and two from PBS) nominated by the Employer
shall be given on job training at the time of installation as well as testing &
commissioning of the switching station.
Limitations:
The Contractor is to carry out the works taking full account of the limitations imposed by
the existing sites and the requirement to maintain all existing supplies during the
construction works. Any temporary works, structures, connections etc. necessary to
achieve this requirement are to be included in the tender price.
The Tenderer shall be deemed to have visited the site, inspected, gathered data and
verified details of the as built system in order to design, supply and interface their new
equipment. All necessary materials, adjustments dismantling, remedial and tiding-up
work in order to complete the work specified shall be included in the contract price. The
Contractor is responsible for ensuring that all and/or any item(s) of work required for the
7
safe, efficient and satisfactory completion and functioning of the works, are included in
the bid price whether they be described in the specification or not.
PLANT REQUIREMENTS:
i) Civil works:
ii) 33kV Incoming Feeder
iii) 33kV Outgoing Feeders
iv) 33kV Single Phase Voltage Transformers
v) 33kV Control Panels
vi) 11kV indoor Switchgear VCB (2000Amps) for incoming feeder with inbuilt
11 kV 2500Amps copper Bus-bar.
vii) 11kV indoor Switchgear VCB (2000Amps) for 11 kV Bus-coupler
viii) 11kV indoor Switchgear VCB (630Amps) for 11 kV outgoing feeders.
ix) Energy Metering Panel
x) 110V Battery and Battery Chargers
xi) LV AC / DC Panels
xii) Earthing System
xiii) Multi core Control and Power cables
xiv) Training
8
TECHNICAL SPECIFICATIONS FOR SWICHING STATION
9
Cable charging KA 50
Small inductive KA 02
25 Installation Outdoor
26 Creepage Distance mm/kv 25
27 Closing Coil Nos. 01
28 Tripping Coil Nos. 02
Standard IEC 62271-
29
100
10
3. 33KV CURRENT TRANSFORMER (CT)
11
4. 33KV VOLTAGE TRANSFORMER (VT FOR BUS & FEEDERS):
If Applicable
12
11 Power frequency withstand voltage (1.2/50 ms) kV 70
12 Lightning impulse residual voltage at 10kA kV PK 75
13 Duty Class Heavy Duty
Station Class
14 Earthing system Effectively
earthed
15 Discharge class 3
16 Pressure relief class Class A
17 Degree of Protection IP 55
18 Surge Counter & Current Monitor Yes
19 Standard IEC 60099-4
13
b) LT Yes
19 Neutral insulation Full insulation
and 100%
capacity
20 LT bushing Nos 4
21 Impedance voltage at 75 oC at normal ratio and 5%
rated capacity
22 Tapping range 1. 5 steps
off-load tap
changer, 2.5% per
step
23 Type of tap changer Manual
24 Maximum temperature rise over 40 oC ambient
when transformer is working at full load and tap
changer is at normal position
o
a) Winding by resistance C 65
o
b) Oil by temperature C 60
25 Type of base Ground
mounted
14
a) Power frequency dry (one min) kV 70
b) Power frequency wet(one min) kV 40
c) Impulse 1.2 / 50 micro sec kV 110
11 Flashover voltage (min)
a) Power frequency dry (one min) kV 80
b) Power frequency wet(one min) kV 50
c) 50% impulse 1.2 / 50 micro sec wave, positive kV 125
or impulse 1.2 / 50 micro sec wave positive
d) 50% impulse 1.2 / 50 micro sec wave, negative kV 130
12 Power frequency puncture voltage (min) kV 110
13 Radio influence voltage data (min)
a) Power frequency test voltage rms to ground kV 10
b) Maximum RIV at 1000Kc micro V 50
14 Minimum mechanical strength for suspension
a) Electro-mechanical breaking load kg 7260
b) Mechanical breaking load kg 6800
c) Tension proof test load kg 3400
d) Time load test value kg 4536
e) Mechanical impact strength mm kg 630
15 Minimum mechanical strength for strain stringing
a) Electro-mechanical breaking load kg 11340
b) Mechanical breaking load kg 11340
c) Tension proof test load kg 3400
d) Time load test value kg 4536
e) Mechanical impact strength mm kg 530
16 Insulator hardware Insulator
hardware for
insulator strings
or bus support
insulator shall
have UTS-120
KN and
galvanized as per
IEC-729
15
9 Class of Zinc coating Class-A
B Earth Grid
1 Material Copper
2 Maximum earth fault current for 3 sec kA 31.5
C Earth Electrodes
1 Material Copper
2 Diameter mm 16
3 Calculated resistance of combined earth grid Ohm Less than 0.5
16
minute
6 Output Current (continuous) A DC 50
7 Type of AVR DVR-Diode
Voltage
Regulator
8 Installation Indoor
9 Charging Mode: Both constant
current &
constant
Voltage
17
relay will reset
7 Reset time after removal of 10 times
CT rated current for:
a) Phase element (100%) Sec
b) E/F element (40%) Sec
A2. METERING AND INDICATION
A.2.1 KWH METER
1 Manufacturer’s Name & Country Siemens(Germany/Switzerl
and)/Alstom,(UK)/ABB(S
witzerland)/AEG(Germany
)/Schlumberger(USA)
2 Type of Meter Numerical
Programmable
multifunction(3 element
4-wire)
3 Number of KWH Meters Nos. 02 nos. with provision
for 04 meters in the
Metering panel
A.2.2 INDICATION METERS (VOLT,
AMPERE, KW, KVAR, PF)
1 Manufacturer Siemens(Germany/Switz
erland)/Alstom,(UK)/AB
B(Switzerland)/AEG(Ge
rmany)/Schlumberger
(USA)
2 Type of Meter Digital /Analog
3 Type of Meters in each Panel Volt, 3 nos. Amp, kW,
kVAR and Pf
Guaranteed Technical Data Schedule of 33KV, 1-Core × 500 Sq.mm U/G XLPE
Copper Cable
19
meter at 18000/30000 Volts , 50Hz
32 Maximum current carrying A Based on design calculation
capacity of conductor in ground
33 Maximum conductor temperature ̊C Based on design calculation
under continuous loading
34 Short circuit withstand capacity KA Min. 25
nof the cable for 1 sec. duration
35 conductor temperature at the end ̊C ≤250
of short circuit
36 Earth fault withstand capacity for 1 KA Min. 25
sec.
37 Screen short circuit withstand KA Min. 25
capacity
20
SCHEDULE B
TENDER PRICES
21
SCHEDULE B
TENDER PRICES
The Tenderer is to complete in full the following Price Schedule in accordance with
BOQ described in section-6 of this Tender Document.
Each item is to be priced separately for switching station & 33KV Line Augmentation
work and is to be fully inclusive of all costs associated with completing the Works. The
prices are to include for surveying, design, fabrication, manufacture, assembly, quality
control, testing, packing, insurance, delivery to site. The estimated cost of elements are
to be shown in the appropriate column in the schedule shall include landing, haulage,
transport to site, civil works, erection, construction, assembly, connecting, testing
finishing of, setting to work and maintenance during the defect liability period including
all supervision, project management costs, overheads, on-costs and profits etc.
The Works shall be valued and paid exclusively at the unit prices and total prices quoted
in the schedule, which are to remain fixed for the duration of the Contract.
The prices quoted are to be firm for the completed Works in full working order in
accordance with the requirements of the Contract.
Prices for the equipment at site, erection/ supervision elements are to be quoted in
Bangladesh Taka inclusive of all duties and taxes paid or payable on components and
material incorporated or to be incorporated in the plant.
Prices shall also include for all necessary local materials, inland transportation, insurance
etc.
22
SCHEDULE C
23
SCHEDULE C
The times given under column C are the commissioning target dates at present planned
to be achieved and may be the subject of mutual adjustment.
The times entered under column A are to be the dates guaranteed for arrival at site of the
equipment before plant erection to the extent necessary to enable him to proceed with
work to meet the dates under column B guaranteed for complete delivery, erection and
commissioning.
The time include all necessary control, relay, metering, auxiliary power, ancillary
equipment to enable the respective item of plant to be completely commissioned and put
into commercial operation together with such other associated equipment, e.g. bus-bars
etc. as will ensure that subsequent shutdown are unnecessary for at least only of a
temporary or short time nature.
A* B* C*
List of Guaranteed Arrival Guaranteed Target Completion
Equipment at site Completion
24
SCHEDULE D
25
SCHEDULE D
Operating Mechanism
Busbar
Connector
Insulator Disc
DO Fuse
Relays
Indicating Instrument
Energy Meters
Battery Charger
Battery
LVAC Panel
26
DC Panel
3. STEEL STRUCTURES
4. EARTHING
Copper Conductor
6. CIVIL WORKS
Construction by:
27
7. All materials for
Augmentation of 33 KV
existing line.
28
SCHEDULE E
29
SCHEDULE E
30
Sl. Description Unit Requirement Manufacturer’s
No. Guaranteed Data
b) Voltage AC V AC 415/230
38 Number of auxiliary switch contacts
a) normally open NO 9
b) normally closed NC 9
c) adjustable As required
39 Maximum creepage
a) to earth mm To be mentioned
b) across interrupter terminals mm To be mentioned
40 Number of interrupters per pole Nos 1
41 Material of interrupter chamber To be mentioned
42 Wall thickness of interrupter chamber mm To be mentioned
a) Material of contact surface primary arcing To be mentioned
b) Contact resistance To be mentioned
43 Length of each break mm To be mentioned
44 Length of stroke mm To be mentioned
45 Operating rod for moving contact(s) material To be mentioned
46 Dimensions etc. To be mentioned
47 Weight of circuit breaker unit complete kg To be mentioned
48 Maximum shock load imposed on floor or N To be mentioned
foundations when opening under fault
conditions (state whether tension or
compression)
49 Period of time equipment has been in To be mentioned
commercial operation
50 Opening time
a) Without current at 100% of rated breaking sec 0.5 max
current
b) Breaking time cycle 5 (0.1 second)
c) Closing time ms 70±10
51 Maximum arc duration at any duty cycle of ms To be mentioned
IEC 56-2 at........%
52 Current at which maximum arc duration A To be mentioned
occurs (critical current)
53 Make time ms To be mentioned
54 Time from closing of control switch to ms To be mentioned
completion of closing stroke during fault
making
55 Is an external series break incorporated in the Yes/no To be mentioned
breaker?
56 Is any device used to limit transient recovery Yes/no To be mentioned
voltage?
57 Number of close/trip operation possible on Nos. To be mentioned
one spring charge
58 Minimum clearance in air:
a) between phases mm 430
b) phase to earth mm 380
c) across interrupters mm To be mentioned
d) live parts to ground level mm To be mentioned
59 Period of time the equipment has been in Years To be mentioned
commercial operation
60 Cree page distance (min) kV/mm 25
61 Method of indicating VCB ON/OFF Mech/El To be mentioned
ect
62 Life of interrupter Years To be mentioned
63 Pressure in vacuum tube for VCB Bar To be mentioned
64 Guaranteed numbers of operation for
vacuum interrupter
a) at rated crrent switching Nos. To be mentioned
b) at short circuit current switching Nos. To be mentioned
65 All current carrying parts of VCB shall Copper
be made of
31
Sl. Description Unit Requirement Manufacturer’s
No. Guaranteed Data
66 Standard IEC 56
67 Degree of Protection IP 55
1.2 33KV OUTDOOR TYPE VACUUM CIRCUIT BREAKER (BUS COUPLER BREAKER)
(N/A)
32
Sl. Description Unit Requirement Manufacturer’s
No. Guaranteed Data
b) Closing coil current A DC To be mentioned
36 Rated supply voltage of shunt opening
release
a) Trip coil Volts V DC 110V
b) Trip coil current A DC To be mentioned
37 Spring charging motor
a) Current A AC To be mentioned
b) Voltage AC V AC 415/230
38 Number of auxiliary switch contacts
a) normally open NO 9
b) normally closed NC 9
c) adjustable As required
39 Maximum cree page
a) to earth mm To be mentioned
b) across interrupter terminals mm To be mentioned
40 Number of interrupters per pole Nos 1
41 Material of interrupter chamber To be mentioned
42 Wall thickness of interrupter chamber mm To be mentioned
a) Material of contact surface primary To be mentioned
arcing
b) Contact resistance To be mentioned
43 Length of each break mm To be mentioned
44 Length of stroke mm To be mentioned
45 Operating rod for moving contact(s) To be mentioned
material
46 Dimensions etc. To be mentioned
47 Weight of circuit breaker unit complete kg To be mentioned
48 Maximum shock load imposed on floor or N To be mentioned
foundations when opening under fault
conditions (state whether tension or
compression)
49 Period of time equipment has been in To be mentioned
commercial operation
50 Opening time
a) Without current at 100% of rated sec 0.5 max
breaking current
b) Breaking time cycle 5 (0.1 second)
c) Closing time ms 70±10
51 Maximum arc duration at any duty cycle of ms at......% To be mentioned
IEC 56-2
52 Current at which maximum arc duration A To be mentioned
occurs (critical current)
53 Make time ms To be mentioned
54 Time from closing of control switch to ms To be mentioned
completion of closing stroke during fault
making
55 Is an external series break incorporated Yes/no To be mentioned
in the breaker?
56 Is any device used to limit transient Yes/no To be mentioned
recovery voltage?
57 Number of close/trip operation possible Nos. To be mentioned
on one spring charge
58 Minimum clearance in air:
a) between phases mm 430
b) phase to earth mm 380
c) across interrupters mm To be mentioned
d) live parts to ground level mm To be mentioned
59 Period of time the equipment has been in Years To be mentioned
33
Sl. Description Unit Requirement Manufacturer’s
No. Guaranteed Data
commercial operation
Sl. Description Unit Requirement Manufacturer’s
No. Guaranteed Data
60 Cree page distance (min) kV/mm 25
61 Method of indicating VCB ON/OFF Mech/El To be mentioned
ect
62 Life of interrupter Years To be mentioned
63 Pressure in vacuum tube for VCB Bar To be mentioned
64 Guaranteed numbers of operation for
vacuum interrupter
a) at rated crrent switching Nos. To be mentioned
b) at short circuit current switching Nos. To be mentioned
65 All current carrying parts of VCB shall Copper
be made of
66 Standard IEC 56
67 Degree of Protection IP 55
34
2. 33KV DISCONNECTING SWITCH AND EARTHING SWITCH (DS/ES)
2.1. 33KV DISCONNECTING SWITCH (AT BUS SIDE FOR INCOMING) (If applicable)
35
2.2. 33KV DISCONNECTING SWITCH (BUS SECTION)
Sl. Description Unit Requirement Manufacturer’s
No. Guaranteed Data
1 Manufacturer To be mentioned
2 Model number To be mentioned
3 Operating system Vertical
4 System voltage kV 33
5 Rated voltage kV 36
6 Frequency Hz 50
7 Number of pole Nos. 3
8 Rated normal current A 2500
9 Rated short time withstand current for 3 kA rms 31.5
sec
10 Rated duration of short circuit Sec 3
11 Rated peak withstand current kA pk 78.75
12 Basic insulation level kV 170
13 Installation Outdoor
14 Type Air
15 Construction Open
16 Method of operation Gang operated,
17 Type of operating mechanism Manual
18 Mounting position Vertical
19 Type of contact To be mentioned
20 Materiall of contact service To be mentioned
21 Manual operating torque KNm To be mentioned
22 Load switching capability A To be mentioned
23 Mechanical Terminal Load N To be mentioned
24 Insulation Cree page mm To be mentioned
25 Number of auxiliary switches
a) normally open NO 9
b) normally closed NC 9
c) adjustable As required
26 Other auxiliary loads
a) voltage V DC 110
b) current A DC To be mentioned
27 Total weight of three pole dis- .Kg To be mentioned
connector complete
28 Period of time equipment has been in Yr To be mentioned
commercial operation
29 Line charging current breaking capacity A To be mentioned
30 Magnetizing current breaking capacity A To be mentioned
31 Standard IEC-129
32 Degree of Protection IP 55
33 Power frequency with stand voltage Kv 70
34 Creepage Distance 900
35 Material Contact Copper with Silver
Coating
36
2.3. 33KV DISCONNECTING SWITCH (FOR FEEDERS AT BUS SIDE)
37
2.4. 33KV DISCONNECTING SWITCH AND EARTHING SWITCH (FEEDER SIDE)
38
3. 33KV CURRENT TRANSFORMER (CT)
39
3.2 33KV CURRENT TRANSFORMER (FEEDER)
40
4. 33KV VOLTAGE TRANSFORMER (VT FOR BUS)
41
5. 33KV LIGHTNING ARRESTER (LA)
42
Sl. Description Unit Requirement Manufacturer’s
No. Guaranteed Data
34 Discharge Class 3
35 Pressure relief class Class A
36 Degree of protection IP 55
43
6. 33/0.415KV, 200KVA AUXILIARY TRANSFORMER
44
Sl. Description Unit Requirement Manufacturer’s
No. Guaranteed Data
o
b) Oil by temperature C 60
30 Type of base Ground mounted
31 Dimension of transformer
a) Width, mm To be mentioned
b) Length, mm To be mentioned
c) Height, mm To be mentioned
d) Tank Sheet thickness of top, bottom
& side, mm
32 Total weight of complete Transformer kg To be mentioned
including fittings & oil, Kg
33 Routine Test Report
a) Measurement of Voltage ratio test. To be mentioned
b) Vector group test. To be mentioned
c) Measurement of winding resistance. To be mentioned
d) Measurement of insulation To be mentioned
resistance.
e) Measurement of no load loss & no- To be mentioned
load current.
f) Measurement of impedance voltage To be mentioned
& load loss.
g) Power frequency (Separate source To be mentioned
voltage) withstands test.
h) Transformer oil test. To be mentioned
34 Type Test Report
a) Impulse Voltage Withstand Test. To be mentioned
b) Temperature Rise Test To be mentioned
c) Short Circuit Test or details To be mentioned
calculations on the basis of the design
data
45
7. 33KV BUSBARS AND CONNECTIONS
46
8. 33KV BUSBAR INSULATOR STRINGS
47
09. 11KV INDOOR TYPE VACUUM CIRCUIT BREAKER
09.1 11KV INDOOR TYPE VACUUM CIRCUIT BREAKER (BUS COUPLER BREAKER)
48
Sl. No. Description Unit Requirement Manufacturer’s
Guaranteed Data
current (Rated short circuit
breaking current) for 3 Sec.
27 Rated Peak withstand current kA 62.5
(Rated short circuit making
current)
28 Breaking Capacity:
Symmetrical rms kA 25
Asymmetrical mis kA 25
29 Rated duration of short circuit Sec. To be mentioned
30 Degrees of protection by IP To be mentioned
enclose
31 First pole to clear factor - To be mentioned
32 Rated transient recovery kVp To be mentioned
voltage at 100% rated short
circuit breaking current
33 Rated line charging breaking A To be mentioned
current
34 Rated cable charging breaking A To be mentioned
current
35 Rated out of phase breaking A To be mentioned
current
36 Is circuit breaker re-strike - Yes
free?
37 No. of tripping coil Nos. 2
38 Trip coil current A To be mentioned
39 Trip coil voltage VDC 110
40 Is circuit breaker trip free? - Yes
41 Type of main contact - To be mentioned
42 Material of contact surface - To be mentioned
43 Contact resistance µ To be mentioned
44 Does magnetic effect of load - To be mentioned
current increase contract?
45 Length of each break/phase mm To be mentioned
46 Length of stroke mm To be mentioned
47 Weight of circuit breaker Kg To be mentioned
complete without operating
mechanism and cubicles
48 Weight of circuit breaker Kg To be mentioned
complete with PCM Cubicles
as in service
49 Maximum shock load imposed N To be mentioned
on floor or foundation when
opening under fault condition
(State compression or tension)
OPERATING:
50 Operating Sequence To be mentioned
51 Opening time without ms To be mentioned
current at 100% of rated
breaking current
Braking time Cycle To be mentioned
Closing time ms To be mentioned
52 Maximum arc duration of any ms at To be mentioned
duty cycle as per latest …..%
49
Sl. No. Description Unit Requirement Manufacturer’s
Guaranteed Data
revision of relevant IEC
53 Current at which maximum arc A To be mentioned
duration occurs (critical
current)
54 Make time ms To be mentioned
55 Minimum time for arc ms To be mentioned
extinction remake when
adapted for auto closing
56 Time form closing of control of ms To be mentioned
switch to completion of closing
stroke during fault making
57 Manufacturer’s Name & - To be mentioned
Country of Origin of vacuum
interrupter
58 Manufacturer’s Model No. of - To be mentioned
vacuum interrupter
59 Pressure in vacuum tube bar To be mentioned
60 Guaranteed no. of vacuum Nos. To be mentioned
interrupter
61 In normal condition at rated Nos. To be mentioned
current switching
62 In short circuit condition i.e. at Nos. ≥100
the short circuit current
switching
CONSTRUCTION FEATURE:
63 Is an external series break - To be mentioned
incorporated in the breaker?
64 Is any device used to limit - To be mentioned
transient recovery voltage?
65 Method of closing - To be mentioned
66 Method of tripping To be mentioned
67 Minimum clearance in air:
Between phase mm To be mentioned
Phase to earth mm To be mentioned
68 Material of tank or chamber - To be mentioned
69 Material of moving contact - To be mentioned
tension rod
70 Period of time equipment has Years To be mentioned
been in commercial operation
71 Is removable draw-out VCB - To be mentioned
mounted on the lower part of
the panel i.e. on floor?
72 All meters, protective relays, - To be mentioned
signaling etc. mounted on the
upper part of the panel
73 Rated voltage of spring Vac To be mentioned
winding motor for closing
74 Materials of all current carrying - To be mentioned
parts of VCB
75 Name of relevant IEC - To be mentioned
standard to be followed in
Design, Manufacture, Testing
and Performance
PROTECTION
A. 33/11kV, 10/13.33MVA, 11kV Transformer Incoming Cubicles
76.0 Over current and earth fault protection with IDMT & instantaneous features
76.1 Manufacture's name & country - Siemens(Germany/
50
Sl. No. Description Unit Requirement Manufacturer’s
Guaranteed Data
of relay Switzerland)/ABB
(Switzerland/Swede
n/Finland) Schneider
(UK/France), Alstom
(UK/France)
76.2 Manufacture's model no. - To be mentioned
76.3 Type of relay - Numerical
programmable with
all necessary
features
76.4 Range of timing settings at 10 Sec. To be mentioned
time CT rating
76.5 Burden of relay at 10 time CT VA To be mentioned
rating
76.6 Percentage of current setting % To be mentioned
at which relay will reset
76.7 Reset time after removal of 10
time CT rated current for :
a) Phase element (100%) Sec To be mentioned
b) E/F element (40%) Sec To be mentioned
77.0 Standard Earth Fault Protection
77.1 Manufacture's name & country - Siemens(Germany/
Switzerland)/ABB
(Switzerland/Swede
n/Finland) Schneider
(UK/France), Alstom
(UK/France)
77.2 Manufacture's model no. - To be mentioned
77.3 Type of relay - Numerical
programmable with
all necessary
features
77.4 Range of current setting:
a) Phase element (% of CT Sec To be mentioned
Rating)
b) earth fault element (%of Sec To be mentioned
CT Rating)
77.5 Range of timing settings at 10 Sec To be mentioned
time CT rating
77.6 Burden of relay at 10 time CT VA To be mentioned
rating
77.7 Percentage of current setting % To be mentioned
at which relay will reset
77.8 Reset time after removal of 10
time CT rated current for :
a) Phase element (100%) Sec To be mentioned
b) E/F element (40%) Sec To be mentioned
B. 11kV Bus Coupler Cubicles:
78.0 Over Current and Earth Fault Protection with IDMT & instantaneous features
78.1 Manufacture's name & country - Siemens(Germany/
of relay Switzerland)/ABB
(Switzerland/Swede
n/Finland) Schneider
(UK/France), Alstom
(UK/France)
78.2 Manufacture's model no. - To be mentioned
78.3 Type of relay - Numerical
51
Sl. No. Description Unit Requirement Manufacturer’s
Guaranteed Data
programmable with
all necessary
features
78.4 Range of current setting:
a) Phase element (% of CT Sec To be mentioned
Rating)
b) earth fault element (%of Sec To be mentioned
CT Rating)
78.5 Range of timing settings at 10 Sec To be mentioned
time CT rating
78.6 Burden of relay at 10 time CT VA To be mentioned
rating
78.7 Percentage of current setting % To be mentioned
at which relay will reset
78.8 Reset time after removal of
10 time CT rated current for
:
a) Phase element (100%) Sec To be mentioned
b) E/F element (40%) Sec To be mentioned
C. 11kV Outgoing Feeder Cubicles
79.0 Over Current and Earth Fault Protection with IDMT & instantaneous features
79.1 Manufacture's name & country - Siemens(Germany/
of relay Switzerland)/ABB
(Switzerland/Swede
n/Finland) Schneider
(UK/France), Alstom
(UK/France)
79.2 Manufacture's model no. - To be mentioned
79.3 Type of relay - Numerical
programmable with
all necessary
features
79.4 Range of current setting:
a) Phase element (% of CT Sec To be mentioned
Rating)
b) earth fault element (%of Sec To be mentioned
CT Rating)
79.5 Range of timing settings at 10 Sec To be mentioned
time CT rating
79.6 Burden of relay at 10 time CT VA To be mentioned
rating
79.7 Percentage of current setting % To be mentioned
at which relay will reset
79.8 Reset time after removal of 10 time CT rated current for :
a) Phase element (100%) Sec To be mentioned
b) E/F element (40%) Sec To be mentioned
Metering and indication for 33/11kV, 10/13.33MVA Transformer 11kV Incoming and 11kV
outgoing Feeder
80.0 kWh Meter
80.1 Manufacture's name & country - Siemens(Germany/
Switzerland)/ABB
(Switzerland)/AEG
(Germany)/Schlumb
erger
(USA)/Elster(Roman
ia)
80.2 Manufacture's model no. - To be mentioned
52
Sl. No. Description Unit Requirement Manufacturer’s
Guaranteed Data
80.3 Type of Meter - Numerical
programmable
Multifunction
80.4 Class of Accuracy - 0.2
81.0 Indication Volt Meters &
Ammeters
81.1 Manufacture's name & country - To be mentioned
81.2 Manufacture's model no. - To be mentioned
81.3 Type of Meter - Analogue
81.4 Class of Accuracy - To be mentioned
53
09.2 11KV INDOOR TYPE VACUUM CIRCUIT BREAKER (INCOMING BREAKER)
54
Sl. No. Description Unit Requirement Manufacturer’s
Guaranteed Data
breaking current) for 3 Sec.
27 Rated Peak withstand current kA 62.5
(Rated short circuit making
current)
28 Breaking Capacity:
Symmetrical rms kA 25
Asymmetrical mis kA 25
29 Rated duration of short circuit Sec. To be mentioned
30 Degrees of protection by IP To be mentioned
enclose
31 First pole to clear factor - To be mentioned
32 Rated transient recovery kVp To be mentioned
voltage at 100% rated short
circuit breaking current
33 Rated line charging breaking A To be mentioned
current
34 Rated cable charging breaking A To be mentioned
current
35 Rated out of phase breaking A To be mentioned
current
36 Is circuit breaker re-strike - Yes
free?
37 No. of tripping coil Nos. 2
38 Trip coil current A To be mentioned
39 Trip coil voltage VDC 110
40 Is circuit breaker trip free? - Yes
41 Type of main contact - To be mentioned
42 Material of contact surface - To be mentioned
43 Contact resistance µ To be mentioned
44 Does magnetic effect of load - To be mentioned
current increase contract?
45 Length of each break/phase mm To be mentioned
46 Length of stroke mm To be mentioned
47 Weight of circuit breaker Kg To be mentioned
complete without operating
mechanism and cubicles
48 Weight of circuit breaker Kg To be mentioned
complete with PCM Cubicles
as in service
49 Maximum shock load imposed N To be mentioned
on floor or foundation when
opening under fault condition
(State compression or tension)
OPERATING:
50 Operating Sequence To be mentioned
51 Opening time without ms To be mentioned
current at 100% of rated
breaking current
Braking time Cycle To be mentioned
Closing time ms To be mentioned
52 Maximum arc duration of any ms at To be mentioned
duty cycle as per latest …..%
revision of relevant IEC
53 Current at which maximum arc A To be mentioned
duration occurs (critical
current)
55
Sl. No. Description Unit Requirement Manufacturer’s
Guaranteed Data
54 Make time ms To be mentioned
55 Minimum time for arc ms To be mentioned
extinction remake when
adapted for auto closing
56 Time form closing of control of ms To be mentioned
switch to completion of closing
stroke during fault making
57 Manufacturer’s Name & - To be mentioned
Country of Origin of vacuum
interrupter
58 Manufacturer’s Model No. of - To be mentioned
vacuum interrupter
59 Pressure in vacuum tube bar To be mentioned
60 Guaranteed no. of vacuum Nos. To be mentioned
interrupter
61 In normal condition at rated Nos. To be mentioned
current switching
62 In short circuit condition i.e. at Nos. ≥100
the short circuit current
switching
CONSTRUCTION FEATURE:
63 Is an external series break - To be mentioned
incorporated in the breaker?
64 Is any device used to limit - To be mentioned
transient recovery voltage?
65 Method of closing - To be mentioned
66 Method of tripping To be mentioned
67 Minimum clearance in air:
Between phase mm To be mentioned
Phase to earth mm To be mentioned
68 Material of tank or chamber - To be mentioned
69 Material of moving contact - To be mentioned
tension rod
70 Period of time equipment has Years To be mentioned
been in commercial operation
71 Is removable draw-out VCB - To be mentioned
mounted on the lower part of
the panel i.e. on floor?
72 All meters, protective relays, - To be mentioned
signaling etc. mounted on the
upper part of the panel
73 Rated voltage of spring Vac To be mentioned
winding motor for closing
74 Materials of all current carrying - To be mentioned
parts of VCB
75 Name of relevant IEC - To be mentioned
standard to be followed in
Design, Manufacture, Testing
and Performance
PROTECTION
A. 33/11kV, 10/13.33MVA, 11kV Transformer Incoming Cubicles
76.0 Over current and earth fault protection with IDMT & instantaneous features
76.1 Manufacture's name & country - Siemens(Germany/
of relay Switzerland)/ABB
(Switzerland/Swede
n/Finland) Schneider
56
Sl. No. Description Unit Requirement Manufacturer’s
Guaranteed Data
(UK/France), Alstom
(UK/France)
76.2 Manufacture's model no. - To be mentioned
76.3 Type of relay - Numerical
programmable with
all necessary
features
76.4 Range of timing settings at 10 Sec. To be mentioned
time CT rating
76.5 Burden of relay at 10 time CT VA To be mentioned
rating
76.6 Percentage of current setting % To be mentioned
at which relay will reset
57
Sl. No. Description Unit Requirement Manufacturer’s
Guaranteed Data
features
78.4 Range of current setting:
a) Phase element (% of CT Sec To be mentioned
Rating)
b) earth fault element (%of Sec To be mentioned
CT Rating)
78.5 Range of timing settings at 10 Sec To be mentioned
time CT rating
78.6 Burden of relay at 10 time CT VA To be mentioned
rating
78.7 Percentage of current setting % To be mentioned
at which relay will reset
78.8 Reset time after removal of
10 time CT rated current for
:
a) Phase element (100%) Sec To be mentioned
b) E/F element (40%) Sec To be mentioned
C. 11kV Outgoing Feeder Cubicles
79.0 Over Current and Earth Fault Protection with IDMT & instantaneous features
79.1 Manufacture's name & country - Siemens(Germany/
of relay Switzerland)/ABB
(Switzerland/Swede
n/Finland) Schneider
(UK/France), Alstom
(UK/France)
79.2 Manufacture's model no. - To be mentioned
79.3 Type of relay - Numerical
programmable with
all necessary
features
79.4 Range of current setting:
a) Phase element (% of CT Sec To be mentioned
Rating)
b) earth fault element (%of Sec To be mentioned
CT Rating)
79.5 Range of timing settings at 10 Sec To be mentioned
time CT rating
79.6 Burden of relay at 10 time CT VA To be mentioned
rating
79.7 Percentage of current setting % To be mentioned
at which relay will reset
79.8 Reset time after removal of 10 time CT rated current for :
a) Phase element (100%) Sec To be mentioned
b) E/F element (40%) Sec To be mentioned
Metering and indication for 33/11kV, 10/13.33MVA Transformer 11kV Incoming and 11kV
outgoing Feeder
80.0 kWh Meter
80.1 Manufacture's name & country - Siemens(Germany/
Switzerland)/ABB
(Switzerland)/AEG
(Germany)/Schlumb
erger
(USA)/Elster(Roman
ia)
80.2 Manufacture's model no. - To be mentioned
80.3 Type of Meter - Numerical
programmable
58
Sl. No. Description Unit Requirement Manufacturer’s
Guaranteed Data
Multifunction
80.4 Class of Accuracy - 0.2
81.0 Indication Volt Meters &
Ammeters
81.1 Manufacture's name & country - To be mentioned
81.2 Manufacture's model no. - To be mentioned
81.3 Type of Meter - Analogue
81.4 Class of Accuracy - To be mentioned
59
09.3 11KV INDOOR TYPE VACUUM CIRCUIT BREAKER (FEEDER BREAKER)
60
Sl. No. Description Unit Requirement Manufacturer’s
Guaranteed Data
breaking current) for 3 Sec.
27 Rated Peak withstand current kA 62.5
(Rated short circuit making
current)
28 Breaking Capacity:
Symmetrical rms kA 25
Asymmetrical mis kA 25
29 Rated duration of short circuit Sec. To be mentioned
30 Degrees of protection by IP To be mentioned
enclose
31 First pole to clear factor - To be mentioned
32 Rated transient recovery kVp To be mentioned
voltage at 100% rated short
circuit breaking current
33 Rated line charging breaking A To be mentioned
current
34 Rated cable charging breaking A To be mentioned
current
35 Rated out of phase breaking A To be mentioned
current
36 Is circuit breaker re-strike - Yes
free?
37 No. of tripping coil Nos. 2
38 Trip coil current A To be mentioned
39 Trip coil voltage VDC 110
40 Is circuit breaker trip free? - Yes
41 Type of main contact - To be mentioned
42 Material of contact surface - To be mentioned
43 Contact resistance µ To be mentioned
44 Does magnetic effect of load - To be mentioned
current increase contract?
45 Length of each break/phase mm To be mentioned
46 Length of stroke mm To be mentioned
47 Weight of circuit breaker Kg To be mentioned
complete without operating
mechanism and cubicles
48 Weight of circuit breaker Kg To be mentioned
complete with PCM Cubicles
as in service
49 Maximum shock load imposed N To be mentioned
on floor or foundation when
opening under fault condition
(State compression or tension)
OPERATING:
50 Operating Sequence To be mentioned
51 Opening time without ms To be mentioned
current at 100% of rated
breaking current
Braking time Cycle To be mentioned
Closing time ms To be mentioned
52 Maximum arc duration of any ms at To be mentioned
duty cycle as per latest …..%
revision of relevant IEC
53 Current at which maximum arc A To be mentioned
duration occurs (critical
current)
61
Sl. No. Description Unit Requirement Manufacturer’s
Guaranteed Data
54 Make time ms To be mentioned
55 Minimum time for arc ms To be mentioned
extinction remake when
adapted for auto closing
56 Time form closing of control of ms To be mentioned
switch to completion of closing
stroke during fault making
57 Manufacturer’s Name & - To be mentioned
Country of Origin of vacuum
interrupter
58 Manufacturer’s Model No. of - To be mentioned
vacuum interrupter
59 Pressure in vacuum tube bar To be mentioned
60 Guaranteed no. of vacuum Nos. To be mentioned
interrupter
61 In normal condition at rated Nos. To be mentioned
current switching
62 In short circuit condition i.e. at Nos. ≥100
the short circuit current
switching
CONSTRUCTION FEATURE:
63 Is an external series break - To be mentioned
incorporated in the breaker?
64 Is any device used to limit - To be mentioned
transient recovery voltage?
65 Method of closing - To be mentioned
66 Method of tripping To be mentioned
67 Minimum clearance in air:
Between phase mm To be mentioned
Phase to earth mm To be mentioned
68 Material of tank or chamber - To be mentioned
69 Material of moving contact - To be mentioned
tension rod
70 Period of time equipment has Years To be mentioned
been in commercial operation
71 Is removable draw-out VCB - To be mentioned
mounted on the lower part of
the panel i.e. on floor?
72 All meters, protective relays, - To be mentioned
signaling etc. mounted on the
upper part of the panel
73 Rated voltage of spring Vac To be mentioned
winding motor for closing
74 Materials of all current carrying - To be mentioned
parts of VCB
75 Name of relevant IEC - To be mentioned
standard to be followed in
Design, Manufacture, Testing
and Performance
PROTECTION
A. 33/11kV, 10/13.33MVA, 11kV Transformer Incoming Cubicles
76.0 Over current and earth fault protection with IDMT & instantaneous features
76.1 Manufacture's name & country - Siemens(Germany/
of relay Switzerland)/ABB
(Switzerland/Swede
n/Finland) Schneider
(UK/France), Alstom
62
Sl. No. Description Unit Requirement Manufacturer’s
Guaranteed Data
(UK/France)
76.2 Manufacture's model no. - To be mentioned
76.3 Type of relay - Numerical
programmable with
all necessary
features
76.4 Range of timing settings at 10 Sec. To be mentioned
time CT rating
76.5 Burden of relay at 10 time CT VA To be mentioned
rating
63
Sl. No. Description Unit Requirement Manufacturer’s
Guaranteed Data
programmable with
all necessary
features
78.4 Range of current setting:
64
Sl. No. Description Unit Requirement Manufacturer’s
Guaranteed Data
(USA)/Elster(USA)
80.2 Manufacture's model no. - To be mentioned
80.3 Type of Meter - Numerical
programmable
Multifunction
80.4 Class of Accuracy - 0.2
81.0 Indication Volt Meters &
Ammeters
81.1 Manufacture's name & country - To be mentioned
81.2 Manufacture's model no. - To be mentioned
81.3 Type of Meter - Analogue
81.4 Class of Accuracy - To be mentioned
65
10. SHIELD WIRES, EARTHING GRID AND EARTHING ELECTRODE
A SHIELD WIRES
Sl. Description Unit Requirement Manufacturer’s
No. Guaranteed Data
1 Manufacturer To be mentioned
2 Conductor material High strength steel
3 Grade of steel PSI 60000
4 Nos. of strand Nos 7
5 Diameter of each strand mm 3.25
6 Overall diameter mm 9.80
7 Nominal cross section mm2 35
8 Weight per 1000 meter length kg 460
9 Maximum rated current (3 sec) A To be mentioned
10 Maximum working tension of main kg/m2 To be mentioned
connection
11 Resistance of conductors per 1000 Ohms To be mentioned
meters at 20ºC
12 Rated ultimate tensile strength kg/m2 4900
13 Maximum permissible span length m To be mentioned
14 Maximum sag under own weight of mm To be mentioned
maximum span
15 Co-efficient of linear expansion cm/ºC To be mentioned
16 Class of zinc coating class – A
17 Galvanization As per BS-729
B EARTHING GRID
1 Manufacturer To be mentioned
2 Material Copper
3 Overall diameter mm To be mentioned
4 Nominal cross section
A) interconnecting the earth electrodes mm2 To be mentioned
B) Connecting equipment to mesh mm2 To be mentioned
5 Area of each earthing grid mxm To be mentioned
6 Depth of bedding of conductor mm To be mentioned
7 Maximum earth fault current for 3 sec kA 31.5
8 Resistance of conductors per 1000 Ohms To be mentioned
meters at 20ºC
C. EARTHING ELECTRODES
1 Manufacturer To be mentioned
2 Material Copper
3 Dimentions
a) Diameter To be mentioned
b) Length To be mentioned
4 Number of electrodes per group To be mentioned
5 Number of earthing points To be mentioned
6 Caculated resistance of combined earth Ohm Less than 0.5
grid and points
66
11. BATTERIY AND CHARGER CUBICLE
67
12. LV AC / DC DISTRIBUTION PANEL
68
13. 33KV CONTROL AND ENERGY METERING PANEL
69
Sl. Description Unit Requirement Manufacturer’s
No. Guaranteed Data
berger(USA)
2 Model number To be mentioned
3 Type of Meter Digital/Analog
4 Class of accuracy To be mentioned
70
14. STEEL STRUCTURE
71
15. Control cable
PVC insulated multi core control cable Laid up beded with PVC or tap. Flat /
round wire armoring with helical steel taping and PVC sheathed, rated voltage
600/1000, continuous permissible voltage 720/1200 volts (VDE 0271/3.69 BDS 901:
85) (NYRGby) suitable for use in indoors, outdoors, underground and in water for
continuous permissible service voltage of 720/1200 volts. Maximum resistance 4.73
ohm/km at 35°C.
a) Guaranteed Technical Particulars for 4C4 mm2 XLPE Insulated and PE Sheathed
Copper Cable
(To be filled u by the Manufacturer in Manufacturer’s Letterhead Pad with
appropriated data)
72
b) Guaranteed Technical Particulars for 4C6 mm2 XLPE Insulated and PE Sheathed
Copper Cable
(To be filled u by the Manufacturer in Manufacturer’s Letterhead Pad with
appropriated data)
Sl Description Unit Purchaser’s Manufacturer’s
No. Requirement Particulars
1 Name of the Item To be mentioned
2 Name of the Manufacturer To be mentioned
3 Address of the Manufacturer To be mentioned
4 Standard To be mentioned
5 Cable Size mm2 4C6 rm
6 Material To be mentioned
7 Numbers & Diameter of Copper Wires mm To be mentioned
8 Numbers & Diameter of Steel Wires mm To be mentioned
9 Nominal size of Steel Tape mm To be mentioned
10 Maximum resistance at 30 deg.c Ω/Km To be mentioned
11 Nominal thickness of insulation mm To be mentioned
12 Nominal thickness of sheath mm To be mentioned
13 Colour of sheath To be mentioned
14 Colour of Core To be mentioned
15 Approximate outer diameter mm To be mentioned
16 Approximate weight Kg/Km To be mentioned
17 Drum wound length m To be mentioned
18 Net Weight Kg To be mentioned
19 Gross weight Kg To be mentioned
20 Treated Wooden Drum Standard To be mentioned
c) Guaranteed Technical Particulars for 2C4 mm2 XLPE Insulated and PE Sheathed
Copper Cable
(To be filled u by the Manufacturer in Manufacturer’s Letterhead Pad with
appropriated data)
Sl Description Unit Purchaser’s Manufacturer’s
No. Requirement Particulars
1 Name of the Item To be mentioned
2 Name of the Manufacturer To be mentioned
3 Address of the Manufacturer To be mentioned
4 Standard To be mentioned
5 Cable Size mm2 2C4 rm
6 Material To be mentioned
7 Numbers & Diameter of Copper Wires mm To be mentioned
8 Numbers & Diameter of Steel Wires mm To be mentioned
9 Nominal size of Steel Tape mm To be mentioned
10 Maximum resistance at 30 deg.c Ω/Km To be mentioned
11 Nominal thickness of insulation mm To be mentioned
12 Nominal thickness of sheath mm To be mentioned
13 Colour of sheath To be mentioned
14 Colour of Core To be mentioned
15 Approximate outer diameter mm To be mentioned
16 Approximate weight Kg/Km To be mentioned
17 Drum wound length m To be mentioned
18 Net Weight Kg To be mentioned
19 Gross weight Kg To be mentioned
20 Treated Wooden Drum Standard To be mentioned
73
d) Guaranteed Technical Particulars for 2C6 mm2 XLPE Insulated and PE Sheathed
Copper Cable
(To be filled u by the Manufacturer in Manufacturer’s Letterhead Pad with
appropriated data)
Sl Description Unit Purchaser’s Manufacturer’s
No. Requirement Particulars
1 Name of the Item To be mentioned
2 Name of the Manufacturer To be mentioned
3 Address of the Manufacturer To be mentioned
4 Standard To be mentioned
5 Cable Size mm2 2C6 rm
6 Material To be mentioned
7 Numbers & Diameter of Copper Wires mm To be mentioned
8 Numbers & Diameter of Steel Wires mm To be mentioned
9 Nominal size of Steel Tape mm To be mentioned
10 Maximum resistance at 30 deg.c Ω/Km To be mentioned
11 Nominal thickness of insulation mm To be mentioned
12 Nominal thickness of sheath mm To be mentioned
13 Colour of sheath To be mentioned
14 Colour of Core To be mentioned
15 Approximate outer diameter mm To be mentioned
16 Approximate weight Kg/Km To be mentioned
17 Drum wound length m To be mentioned
18 Net Weight Kg To be mentioned
19 Gross weight Kg To be mentioned
20 Treated Wooden Drum Standard To be mentioned
74
16.1. 33 KV POWER CABLES (U/G)
Guaranteed Technical Data Schedule of 33KV, 1-Core × 500 Sq.mm U/G XLPE Copper
Cable
75
SL Description Unit Required Manufacturer’s
No. Specification Particulars
31 Charging current per conductor per mA Based on design
meter at 18000/30000 Volts , 50Hz calculation
32 Maximum current carrying A Based on design
capacity of conductor in ground calculation
33 Maximum conductor temperature ̊C Based on design
under continuous loading calculation
34 Short circuit withstand capacity nof KA Min. 25
the cable for 1 sec. duration
35 conductor temperature at the end of ̊C ≤250
short circuit
36 Earth fault withstand capacity for 1 KA Min. 25
sec.
37 Screen short circuit withstand KA Min. 25
capacity
76
16.2. 11 KV POWER CABLES (U/G)
16.2.1: Guaranteed Technical Data Schedule of 11KV, 1-Core × 500 Sq.mm U/G
XLPE
Copper Cable
77
SL Description Unit Required Supplier’s/
No. Specification Manufacturer’s
Particulars
28 Star capacitance per per meter pF/m Based on design
of cable at 50Hz calculation
29 Charging current per mA Based on design
conductor per meter at calculation
18000/30000 Volts , 50Hz
30 Maximum current carrying A 775
capacity of conductor in
ground
31 Maximum conductor ̊C 90
temperature under continuous
loading
32 Short circuit withstand KA Min. 20
capacity nof the cable for 1
sec. duration
33 conductor temperature at the ̊C ≤250
end of short circuit
34 Earth fault withstand capacity KA Min.10
for 1 sec.
35 Screen short circuit withstand KA Min. 10
capacity
36 Armour short circuit capacity KA Based on design
calculation
37 Cable resistance, reactance
78
16.2.2: Guaranteed Technical Data Schedule of 11KV, 1-Core × 185 Sq.mm U/G
XLPE
Copper Cable
SL Description Unit Required Supplier’s/
No. Specification Manufacturer’s
Particulars
1 Name and address of the To be mentioned
Manufacturer
2 Type/Model of the offered To be mentioned
cable
3 Nominal system voltage KV To be mentioned
4 Rated voltage of cable KV To be mentioned
79
SL Description Unit Required Supplier’s/
No. Specification Manufacturer’s
Particulars
18000/30000 Volts , 50Hz
30 Maximum current carrying A To be mentioned
capacity of conductor in
ground
31 Maximum conductor ̊C To be mentioned
temperature under continuous
loading
32 Short circuit withstand KA To be mentioned
capacity nof the cable for 1
sec. duration
33 conductor temperature at the ̊C To be mentioned
end of short circuit
34 Earth fault withstand capacity KA To be mentioned
for 1 sec.
35 Screen short circuit withstand KA To be mentioned
capacity
36 Armour short circuit capacity KA Based on design
calculation
37 Cable resistance, reactance
Tenderer shall provide all necessary information which deem to be necessary to complete the work in all
respect
80
SCHEDULE F
81
SCHEDULE F
Tenderers are to list all departures from the requirements of the specification in this
schedule. All departures whether they be commercial, financial, technical or of a
contractual nature are to be included and submitted with the Technical Proposal.
Any item that does not have a departure listed in this schedule will be deemed to be in
full accordance with the requirements of the specification.
82
SCHEDULE G
83
SCHEDULE G
The Tenderer shall list below all the alternative engineering and design Standards, which
he proposes to use in his design, manufacture and testing of equipment to be supplied.
Should these standards differ from the specified standard in any respect, the Tenderer
shall detail the differences between the proposed and specified standard.
Compliance with any standard equal or superior to those specified will be considered
acceptable.
In the absence of any listed alternative standard, it is deemed that the standards specified
in the Tender Documents are fully complied with.
84
SCHEDULE H
85
SCHEDULE H
The Tenderer is required to provide full organization charts of his proposed head office
and site office arrangements. This should include how site subcontractors are to interface
with the contractor’s organization.
The Tenderer shall list in the form of Schedule attached, the key personnel (including
first nominee and the second choice alternate)he will employ at head office and site
office to direct and execute and work for the execution of the Contract together with their
qualifications, positions held and their nationalities. Should specialist sub-designers be
proposed (e.g civil designers) details of these are also to be provided with how this
interface with the contractor’s organization.
Should the Tenderer be proposing to put any restriction on his site managers authority to
carry out the instructions issued by the Employer Representative, full details of these, be
they financial/contractual/technical are to be provided in the tender.
The information provided in the Tender in accordance with the above, will not represent
any limitations on the staff required to perform the works in accordance with the
conditions of Contract. Should the Contractor require utilizing additional staff to those
proposed in order to meet his obligations these are to be provided at no additional cost.
The Contractor shall however have to employ all the expatriate staffs proposed in the
tender as to be employed at site. In case of failure to employ the expatriate staffs at site
as per tender proposal, the Employer may go for termination of the Contract.
In addition the Tenderer is required to provide a schedule of the site resources he intends
to provide, e.g. equipment for haulage, lifting, site power supplies, foundation, erection,
stringing, testing and commissioning. Major items of equipment for construction
purposes, which the Tenderer proposes to import, are to be submitted with the Tender.
The Tenderer shall have to bring the above proposed equipment during construction
otherwise they may be panelized, as per clause of the tender, for any delay due to non-
availability of such equipment at site. The successful Tenderer will be required to submit
detailed schedules of his proposed site testing and commissioning equipment and
experience of his commissioning engineers.
The Tenderer is also required to provide details of his site organization concerning office
locations, storage facilities proposed, both open and covered, site transportation, etc. The
successful Tenderer will be required to provide details of his proposed organizational
procedures for the receipt, inspection and transportation of plant, plus monthly progress
monitoring, invoice submission etc.
The Contractor shall ensure that the cash flow is maintained as forecasted in their price
proposal. In case there is any liquidity problem for which there is any delay in
implementing the project, the Contractor may be panelized as per tender.
86
SCHEDULE H OF KEY PERSONNEL
87
SCHEDULE H OF EQUIPMENT FOR CONSTRUCTION
88
SCHEDULE I
89
SCHEDULE I
1. Typical plan and section drawings of transformer incoming, bus coupler and
outgoing feeders for 33 kV switchyard.
2. Block diagram showing overall dimensions of 33kV switchyard at site.
3. Drawings of circuit breakers, disconnecting switches, current transformers,
voltage transformers, lightning arresters and disc Insulator units showing details
of construction and dimensions.
4. Typical arrangement drawing of control panel cubicles, energy meter panel
cubicle, battery charger cubicle, LVAC and DC distribution boards.
5. Typical block-schematic and logic diagrams of all protection and control
schemes.
6. Lay-out Plan of control panel to be installed in substation control room building.
7. Cross Section Drawing of the head design of the insulator unit.
8. Type test certificate of the following shall be submitted as per relevant IEC/BS
standards.
i) Circuit Breaker (VCB)
(a) Lightning impulse voltage withstand dry test
(b) Temperature rise test
(c) Power frequency withstand test
(d) Short time withstand & Peak withstand current test
(e) Mechanical operation tests
(f) Short Circuit Current making & breaking test
(g) Out of phase making & breaking test
90
(d) Temperature rise test
iv) Voltage Transformer (VT)
(a) Temperature rise test
(b) Impulse voltage withstand tests for voltage transformers for
service in exposed installation.
(c) Short circuit test
(d) Short time over voltage test
v) Lightning Arrester (LA)
(a) Lightning impulse voltage withstand test on Arrester Housing
(b) Lightning impulse residual voltage test
(c) Step current impulse residual voltage test
(d) Long duration current impulse withstand test
(e) High Current Impulse withstand test
(f) Pressure relief test
vi) Disc Insulator units
(a) Mechanical failing load test
(b) Impulse voltage puncture test
(c) Power are test
(d) Residual strength test
9. Type test certificates of the above equipment shall be from independent testing
laboratory.
10. Quality Assurance Certificate ISO9001/9002 Certification (or equivalent and
Quality Assurance Program & Typical Quality Plan for the work from the
manufacturers of the following equipment:
i) Circuit breaker
ii) Disconnecting switch
iii) Current transformer
iv) Voltage transformer
v) Lightning arrester
vi) Insulator
vii) Relays
91
DRAWINGS AND DOCUMENTS TO BE SUBMITTED WITH
TENDER
FOR 33 KV LINE AUGMENTATION WORK
92
SCHEDULE K
93
SCHEDULE J
Manufacturer’s Authorization Letter
[This letter of authorization should be on the letterhead of the manufacturer and should
be signed by the person with the proper authority to sign documents that are binding on
the manufacturer]
Invitation for Tender No: Date:
Tender Identification No:
To:
Therefore, we do hereby:
2. Extend our full guarantee and warranty in accordance with GCC Clause
10 with respect to the Goods offered in the Tender.
Signed
[ name of manufacturer]
Date:
94
Section 9
Drawings
95
96
97
98
99
100
101
102
103