REB 33-11 KV Transformer

Download as pdf or txt
Download as pdf or txt
You are on page 1of 104

BANGLADESH RURAL ELECTRIFICATION BOARD

(BREB)
TENDER DOCUMENT
FOR THE

TURNKEY CONTRACT FOR DESIGN, SUPPLY, CONSTRUCTION,


INSTALLATION, TESTING & COMMISSIONING WORK FOR RENOVATION
AND UP-GRADATION OF EXISTING 10 MVA GANGGADHORPOTTI SUB-
STATION UNDER MANIKGANJ PBS

PACKAGE NO: D(N)-MNK-SSU-2017-18-01

VOLUME 2 OF 3

Particular Specification and Drawings

ISSUED TO: M/S………………………………………………………………

ON BEHALF OF THE OFFICE OF


Superintending Engineer
DHAKA ZONE (North), BREB, NOBINAGAR, SAVAR, DHAKA
Bangladesh Rural Electrification Board
Telephone No: 02-7792148
Fax :

SEAL & SIGNATURE

1
Section 8

Particular Specifications

2
Contents of Particular Specifications

Schedule A Introduction & Preamble to the Price & Technical Schedule


Schedule B Tender Prices
Schedule C Bar chart Programme of key activities
Schedule D Manufacturer’s, Places of Manufacture and Testing
Schedule E Technical Particulars and Guarantees
Schedule F Departures from Specifications
Schedule G Proposed Alternative Standards to which Equipment shall be provided
Schedule H proposed Contract and site Organization
Schedule I Drawings and Documents to be submitted with Tender
Schedule J Manufacturer’s Authorization Letter

3
SCHEDULE A

INTRODUCTION AND PREAMBLE TO THE PRICE & TECHNICAL SCHEDULES

4
SCHEDULE A
INTRODUCTION AND PREAMBLE TO THE PRICE & TECHNICAL
SCHEDULES

A1: BRIEF DESCRIPTION OF THE WORKS.

The work comprise of creating facilities for 06 (Six) nos. 33/11kV outgoing feeders
through extension of 1 nos. 33 kV Bay-Breaker of existing Gonggadhorpotti sub-station
and dismantling of existing 33kV Bus-bar and installation of new Bus-bar & related
works for Manikganj PBS at Gonggadhorpotti Grid Sub-Station.

Outdoor switchyard:

The extension of Switchyard shall Comprise of Steel Structures for 04 nos. 33 kV


outgoing feeders and space remaining for 01 no. outgoing feeder for future use. The Bus-
conductor shall be 2×Martin (2500A). The steel structure columns and electrical
equipment shall be installed on steel supports with RCC Foundation.

Civil works:

Complete design, supply materials and construction of all civil items required for
extension of 33 kV bay at switchyard for steel structure and Equipment foundation, RCC
Internal road, Power and control cable trenches, surface finishing with gravels,
switchyard earthings, switchyard lighting, lightning protection. The cable duct
constructed by PGCB in the control room building shall be used to run the control/
power cables to switching room for connecting control panel and Energy metering panel
to be installed. All control panel, separate energy metering panel, battery chargers and
AC/DC panels shall be installed in the existing control room building (if applicable).

33kV Bus- Isolator:


Design, supply, delivery, installation, testing & commissioning of 02 no. 33kV 2500A
capacity Bus-isolator without earthling switch for connecting existing and extended 33
kV Bus-bar.

33kV Outgoing Feeders:


Design, supply, delivery, installation, testing & commissioning of 04 nos. of 33kV
1250A capacity vacuum circuit breakers for 04 nos. out going feeders each with one set
of CT with ratio 800-400/5-5-5A, one set of isolator of capacity of 1250A without
earthing switch for bus side connection, one set of isolator of capacity of 1250A with
earthing switch for line side connection and one set of lightning arresters.
33kV Single Phase Current Transformers (Incoming): If Applicable
Design, supply, delivery, installation, testing & commissioning of 2 sets (6 nos) of single
phase current transformers will be required for the proposed 2 feeders. The feeder CTs
shall have 3 cores, core 1 shall have ratio 2400-1600/5-5-5A, 30VA, M0.2 for indicating
meters on control panels, core 2 shall have ratio 2400-1600/5-5-5A, 30VA M0.2

5
dedicated for the energy meters to be installed in a separate energy metering panel and
core 3 shall have ratio 2400-1600/5-5-5A, 30VA, 5P20 for protection. Burden Shall be
Calculated as per Field Condition and Resistance of the Instrument Cables.

33kV Single Phase Current Transformers (Outgoing):


Design, supply, delivery, installation, testing & commissioning of 04 sets (12 nos.) of
single phase current transformers will be required for the proposed 04 feeders. The
feeder CTs shall have 3 cores, core 1 shall have ratio 800-400/5-5-5A, 30VA, M0.2 for
indicating meters on control panels, core 2 shall have ratio 800-400/5-5-5A, 30VA M0.2
dedicated for the energy meters to be installed in a separate energy metering panel and
core 3 shall have ratio 800-400/5-5-5A, 30VA, 5P20 for protection. Burden shall be
Calculated as per Field Condition and Resistance of the Instrument Cables.
33kV Single Phase Voltage Transformers:
Design, supply, delivery, installation, testing & commissioning of one sets (3 nos.) of
33kV single phase voltage transformers to be installed at the two ends of structures in the
switchyard for bus VT. For all VTs core 1 of secondary winding of accuracy class 0.2
and capacity 50 VA will be dedicated for energy meters only and core 2 of accuracy
class 3P and capacity 50 VA will be used for indicating meters on the control panels.

33kV Control Panels:


Design, supply, delivery, installation, testing & commissioning of control panels for
33kV vacuum circuit breakers for 04 nos. out going feeders including all control cables
and AC/DC supplies (if applicable) .
Energy Metering Panel:
Design, supply, delivery, installation, testing & commissioning of one no. energy meter
panel having space provision for installation of 06(Six) nos. energy meters (if applicable
otherwise not) and 04 nos. energy meters for 04 nos. outgoing feeders. Dedicated supply
from both CTs and VTs will be drawn directly to the metering panel.

110V Battery and Battery Chargers:


Existing Battery and Battery charger in control room building shall be replaced by
supplying and installation of one set of new batteries and battery charger in the control
room including all power and control cables.
LV AC / DC Panels: (If Required)
Design, supply, delivery, installation, testing & commissioning of one set of low voltage
AC distribution panel in the control room to provide 415/230V supplies to all equipment
being supplied with necessary 3-phase MCCBs and one set of DC distribution panel in
the control room to provide 110V DC supplies as required and including all power and
control cables .

Earthing System:
Design, supply, delivery, installation of earthing system and lightning protection screen
including connections, connectors and clamps to suit the switching station overall
arrangement and provide supporting design calculations. However the design and

6
installation of earthing system done by PGCB/PDB should be followed for the 33kV
existing switching station also. Grounding resistance to be maintained less than 0.2 ohm.

Multi core Control / Power cables:


Complete set of multi core low voltage auxiliary power and control cables between all
items of equipment required under this contract shall be supplied, installed, landed,
terminated and have individual cores identified. The production of the overall switching
station cable routing and core schedules shall also be provided. The multi core control
cables shall be installed in such a way that those shall enter into the existing control
room building through the newly constructed and existing duct and laid on a suitable
cable tray as per direction of Engineer-in-charge. All control cable size should be 4/6 rm
and above if required.

Building Lighting, Small Power, Air Conditioning and Ventilation : (If Applicable)
Complete design and calculations supply, delivery, installation, testing & commissioning
of equipment to provide lighting ,LV power supply and air conditioning system and
emergency DC lighting at strategic location for equipment operations and inspections.
Approach rood, cable trench etc. to be constructed by the contractor.

Switchyard Lighting: (If Applicable)

Complete design and calculations supply, delivery, installation, testing & commissioning
of equipment to provide lighting (sodium light) for security, roadway and switchyard and
emergency DC lighting at strategic location for equipment operations and inspections.

Training:

The Contract Price shall include all costs for training of Employer’s representatives at
site. Four Engineers (Two from REB and two from PBS) nominated by the Employer
shall be given on job training at the time of installation as well as testing &
commissioning of the switching station.

Limitations:

The Contractor is to carry out the works taking full account of the limitations imposed by
the existing sites and the requirement to maintain all existing supplies during the
construction works. Any temporary works, structures, connections etc. necessary to
achieve this requirement are to be included in the tender price.

The Tenderer shall be deemed to have visited the site, inspected, gathered data and
verified details of the as built system in order to design, supply and interface their new
equipment. All necessary materials, adjustments dismantling, remedial and tiding-up
work in order to complete the work specified shall be included in the contract price. The
Contractor is responsible for ensuring that all and/or any item(s) of work required for the

7
safe, efficient and satisfactory completion and functioning of the works, are included in
the bid price whether they be described in the specification or not.

PLANT REQUIREMENTS:

i) Civil works:
ii) 33kV Incoming Feeder
iii) 33kV Outgoing Feeders
iv) 33kV Single Phase Voltage Transformers
v) 33kV Control Panels
vi) 11kV indoor Switchgear VCB (2000Amps) for incoming feeder with inbuilt
11 kV 2500Amps copper Bus-bar.
vii) 11kV indoor Switchgear VCB (2000Amps) for 11 kV Bus-coupler
viii) 11kV indoor Switchgear VCB (630Amps) for 11 kV outgoing feeders.
ix) Energy Metering Panel
x) 110V Battery and Battery Chargers
xi) LV AC / DC Panels
xii) Earthing System
xiii) Multi core Control and Power cables
xiv) Training

8
TECHNICAL SPECIFICATIONS FOR SWICHING STATION

1. 33KV OUTDOOR TYPE VACUUM CIRCUIT BREAKER (VCB)

Sl. Description Unit Requirements


No.
1 System voltage kV 33
2 Rated voltage KV 36
3 Rated frequency HZ 50
4 Rated normal current
a) Incoming Feeder A N/A
b) Outgoing Feeder A 1250
5 Interrupting medium Vacuum
6 Number of phases 3
7 Rated short-circuit breaking current KA 31.5
8 Rated short-circuit making current KA 78.75
9 First pole to clear factor 1.3
10 Rated operating sequence O-0.3s-CO-
3min-CO
11 Rated duration of short circuit Sec 3
12 Impulse withstand on 1.2/50 s wave KV 170
13 Power frequency test voltage (dry) at 50Hz,1 min KV 70
14 Circuit breaker operating mechanism type Gang operated
spring charged
& manual
15 Operating particulars
a) Opening time: without current at 100% rated ms 0.05
breaking current (max)
b) Breaking time ms <45ms
c) Closing time ms 70±10
16 Is the circuit breaker trip free? Yes/No Yes
17 Trip coil voltage VDC 110
18 Rated supply voltage of shunt opening release VDC 110
19 Spring charging motor voltage VAC 415/230
20 Minimum clearance in air
a) Between phases mm 430
b) Phases to earth mm 380
21 Degree of protection IP 55
22 Auxiliary switch:
NO 9
NC 9
23 Is lockout facility fitted Yes

24 Rated breaking current :


Line charging KA 25

9
Cable charging KA 50
Small inductive KA 02
25 Installation Outdoor
26 Creepage Distance mm/kv 25
27 Closing Coil Nos. 01
28 Tripping Coil Nos. 02
Standard IEC 62271-
29
100

2. 33KV DISCONNECTING SWITCH AND EARTHING SWITCH (DS/ES)

Sl. Description unit Requirements


No.
1 Installation Outdoor
2 Mounting position Vertical/Horizo
ntal
3 Method of operation Gang operated
4 Type of operating mechanism Manual
5 System voltage kV 33
6 Rated voltage kV 36
7 Frequency Hz 50
8 Number of pole Nos. 3
9 Rated normal current-
a) Bus Sectionalizer A 2000
b) Incoming Feeder A N/A
c) Outgoing Feeder A 1250
10 Rated short time withstand current kA rms 31.5
11 Rated duration of short circuit sec 3
12 Rated peak withstand current kA pk 110
13 Basic insulation level kV 170
14 Power frequency withstand voltage (1min) Kv 70
15 Creep age distance mm 900
16 Material contact Copper with
silver / Nickel
coating
17 Number of Auxiliary switch:
NO 9
NC 9
18 Earthing blade 6
19 Degree of protection IP 55
20 Type of breaks per pole Single
21 Standard IEC 62271-102

10
3. 33KV CURRENT TRANSFORMER (CT)

Sl. Description Unit Requirements


No.
1 Type Electromagneti
c induction,
single phase,
outdoor
2 Rated primary current
(a) Incoming Feeder (N/A) Ams 2400-1600/5-
5-5A
(b) Outgoing Feeder Ams 800-400/5-5-
5A
3 Rated secondary current Ams 5-5-5A
4 Rated secondary accuracy and burden
a) Metering (core 1- for indicating meters) 0.2, 30VA
b) Metering (core 2- dedicated for energy 0.2, 30VA
metering)
c) Protection (core 3) 5P20, 30VA
5 Rated frequency Hz 50
6 System voltage kV 33
7 Rated voltage for equipment kV 36
8 Short time current rating for 3 sec. kA 31.5
9 Extended current rating (% of rated current) % 120
10 Over current rating A 10
11 Basic insulation level on 1.2 / 50 micro-sec wave kV 170
12 Power frequency withstand voltage (1 min, 50 Hz) kV 70
13 Creepage distance mm/kv 25
14 Bushing Porcelain
outdoor type
15 System earthing Effectively
earthed
16 Insulation class A
17 Standard IEC 60044-1
18 Knee point voltage(at max ratio) <150v for
metering
<600v for
protection
* Remarks CT ratio to be reviewed
with PGCB / REB (if
required)

11
4. 33KV VOLTAGE TRANSFORMER (VT FOR BUS & FEEDERS):
If Applicable

Sl. Description Unit Requirements


No.
1 Type Electromagnetic
induction,
single phase,
outdoor
2 Rated primary voltage kV 33/ 3
3 Rated voltage for secondary windings kV 0.11 / 3 and
0.11 / 3
4 Rated secondary burden and accuracy
Secondary winding VA 60
Core 1 (Dedicated for energy metering) Class 0.2
Secondary winding VA 50
Core 2 Class 3P
5 Frequency Hz 50
6 Impulse withstand voltage (1.2/50 micro sec wave) kV 170
7 Cree page distance mm/kV 25
8 System earthing Effectively
earthed
9 Power frequency withstand voltage (1min) KV 70
10 Partial discharge PC ≤5
11 Short circuit withstand voltage KA 63
12 Rated voltage factor 1.2 continuous
1.9 30 second
13 Standard IEC 60044-2

5. 33KV LIGHTNING ARRESTER (LA)

Sl. Description Unit Requirement


No.
1 Type Metal Oxide,
(ZnO)
Gapless type,
single phase
2 System voltage kV 33
3 Rated voltage kV 36
4 System frequency Hz 50
5 Continuous operating voltage kV 25 kV (rms)
6 Rated arrester voltage kV 30
7 Standard nominal discharge current kA 10
8 Reference current at ambient temperature mA 2
9 Steep current impulse residual voltage kV PK 84
10 Basic insulation level on 1.2 / 50 micro-sec wave kV 170

12
11 Power frequency withstand voltage (1.2/50 ms) kV 70
12 Lightning impulse residual voltage at 10kA kV PK 75
13 Duty Class Heavy Duty
Station Class
14 Earthing system Effectively
earthed
15 Discharge class 3
16 Pressure relief class Class A
17 Degree of Protection IP 55
18 Surge Counter & Current Monitor Yes
19 Standard IEC 60099-4

6. 33/0.415KV, 100KVA AUXILIARY TRANSFORMER (N/A)

Sl. Description Unit Requirement


No.
1 Rated power KVA 100
2 Type of cooling ONAN
3 Coolant Mineral Oil
4 Number of phase 3
5 Frequency Hz 50
6 Normal transformation ratio KV 33/0.4
7 Rated primary voltage KV 33
8 Rated secondary voltage kV 0.415
9 Nominal LT voltage KV 0.415 /0.240
10 Highest system voltage of
a) Primary winding kV 36
b) Secondary winding V 457
11 Basic insulation level kV 170
12 Power frequency withstand voltage (1min)
a) HT side kV 70
b) LT side kV 2.5
13 Type Core
14 Insulation Outdoor,
tropical and
high humidity
15 Earthing Neutral earth at
LT,
3-phase 4-wire
16 Windings Double wound
and of high
conductivity
copper

17 Vector Group DYN ll


18 Neutral to be Brought out
a) HT Nil

13
b) LT Yes
19 Neutral insulation Full insulation
and 100%
capacity
20 LT bushing Nos 4
21 Impedance voltage at 75 oC at normal ratio and 5%
rated capacity
22 Tapping range 1. 5 steps
off-load tap
changer, 2.5% per
step
23 Type of tap changer Manual
24 Maximum temperature rise over 40 oC ambient
when transformer is working at full load and tap
changer is at normal position
o
a) Winding by resistance C 65
o
b) Oil by temperature C 60
25 Type of base Ground
mounted

7. 33KV BUSBARS AND CONNECTORS

Sl. Description Unit Requirement


No.
A. FLEXIBLE CONDUCTORS
1 Conductor/connector material ACSR/
2×Martin
2 Rated current (site rating) A 2500
o
3 Temperature rise at rated current C 35

8. 33KV BUSBAR INSULATOR STRING

Sl. Description Unit Requirement


No.
1 Insulator material Porcelain
2 Number of units per string nos. 4
3 Insulator voltage class
4 Type of insulator Ball and socket
type disc,
security clip
made of rod
brass alloy
5 Cree page/leakage distance (min) mm 298
6 Total Cree page distance of string mm 900
7 Unit spacing mm 146
8 Dry arcing distance (min) mm 1968
9 Diameter of insulator mm 256
10 Withstand voltage (min)

14
a) Power frequency dry (one min) kV 70
b) Power frequency wet(one min) kV 40
c) Impulse 1.2 / 50 micro sec kV 110
11 Flashover voltage (min)
a) Power frequency dry (one min) kV 80
b) Power frequency wet(one min) kV 50
c) 50% impulse 1.2 / 50 micro sec wave, positive kV 125
or impulse 1.2 / 50 micro sec wave positive
d) 50% impulse 1.2 / 50 micro sec wave, negative kV 130
12 Power frequency puncture voltage (min) kV 110
13 Radio influence voltage data (min)
a) Power frequency test voltage rms to ground kV 10
b) Maximum RIV at 1000Kc micro V 50
14 Minimum mechanical strength for suspension
a) Electro-mechanical breaking load kg 7260
b) Mechanical breaking load kg 6800
c) Tension proof test load kg 3400
d) Time load test value kg 4536
e) Mechanical impact strength mm kg 630
15 Minimum mechanical strength for strain stringing
a) Electro-mechanical breaking load kg 11340
b) Mechanical breaking load kg 11340
c) Tension proof test load kg 3400
d) Time load test value kg 4536
e) Mechanical impact strength mm kg 530
16 Insulator hardware Insulator
hardware for
insulator strings
or bus support
insulator shall
have UTS-120
KN and
galvanized as per
IEC-729

9. SHIELD WIRE, EARTHING GRID AND EARTHING ELECTRODE

Sl. Description Unit Requirement


No.
A. Shield Wires
1 Material High strength
steel
2 Grade of steel kg. 4
3 Number of strands nos. 7
4 Diameter of each strand mm 3.25
5 Overall diameter mm 9.8
6 Nominal cross section mm2 35
7 Weight per km length kg 460
8 Rated ultimate tensile strength kg 4900

15
9 Class of Zinc coating Class-A
B Earth Grid
1 Material Copper
2 Maximum earth fault current for 3 sec kA 31.5
C Earth Electrodes
1 Material Copper
2 Diameter mm 16
3 Calculated resistance of combined earth grid Ohm Less than 0.5

10. BATTERIES AND CHARGER (N/A)

Sl. Description Unit Requirements


N0.
A. BATTERY
1 Electrolyte type Nickel
Cadmium /
Alkaline
2 Nominal voltage V/per 1.2
cell
3 Capacity at 5 hour rate Ah 250
4 Number of cells nos. 92
5 Operating voltage VDC 110
6 Continuous discharge current at the rate of 10 hour Amp 10
and final cell voltage 1.1 volt
7 Short time discharge current at the rate of 2 hour and Amp 50
final cell voltage 1.1 volt
8 Discharge voltage V 1.0 – 1.4 per
cell
9 Charging voltage (normal) V 1.4-1.5Volt
per cell
10 Charging voltage (Maximum) V 1.54-1.69 per
cell
11 Battery voltage at end of the duty cycle V 1.1Volt per
cell
B. CHARGER
1 Rectifier Type (Thyristor
Controlled)
Silicon or
Selenium
2 AC input voltage V 415V±15%, 3
phase
3 Input a.c frequency HZ 50±5%
4 DC output voltage range V DC 110±10%
a) normal charge V DC 110±10%
b) Float charge V DC 1.42 volt per
cell 110±5%
c) Boast charge V DC 1.55 volt per
cell
5 Installation breakdown voltage kV 2kV for 1

16
minute
6 Output Current (continuous) A DC 50
7 Type of AVR DVR-Diode
Voltage
Regulator
8 Installation Indoor
9 Charging Mode: Both constant
current &
constant
Voltage

11. LV AC DC DISTRIBUTION BOARD (N/A)


Sl. Description Unit Requirement
No.
A. AC DISTRIBUTION BOARD
1 Bus bar rating (R, Y, B, N, G) Amps 600
2 Voltage Volts 415
3 Incoming breaker rating (MCCB) Amps 400
B. 2. D.C. DISTRIBUTION BOARD
1 Bus bars:- (+VE,-VE, G)
a) Maximum current rating A DC 200
b) Voltage rating V DC 110
C. Two distribution bus shall be maintained in each pannel (AC & DC
Distribution) and both shall be electricity interlocked.

12. 33KV CONTROL, METERING AND RELAY PANEL


Sl.No. Description Unit Requirement
A. 33KV CONTROL PANEL
1 Number of control panelsKVRH Meter Nos 1
Panel
2 Number of KWH Metering Panel No. 1
A1. PROTECTION
A.1.1 IDMT OVER CURRENT & EARTH
FAULT RELAYS
1 Manufacturer’s Name & Country Siemens (Germany)/
Alstom (UK/France)/
ABB
(Switzerland/Sweden)/
Schneider (France)
2 Type of relay Numerical
Programmable
3 Range of current setting
a) Phase element % of CT rating
b) Earth fault element % of CT rating
4 Range of timing settings at 10 time CT Sec
rating
5 Burden of relay at 10 time CT rating VA
6 Percentage of current setting at which %

17
relay will reset
7 Reset time after removal of 10 times
CT rated current for:
a) Phase element (100%) Sec
b) E/F element (40%) Sec
A2. METERING AND INDICATION
A.2.1 KWH METER
1 Manufacturer’s Name & Country Siemens(Germany/Switzerl
and)/Alstom,(UK)/ABB(S
witzerland)/AEG(Germany
)/Schlumberger(USA)
2 Type of Meter Numerical
Programmable
multifunction(3 element
4-wire)
3 Number of KWH Meters Nos. 02 nos. with provision
for 04 meters in the
Metering panel
A.2.2 INDICATION METERS (VOLT,
AMPERE, KW, KVAR, PF)
1 Manufacturer Siemens(Germany/Switz
erland)/Alstom,(UK)/AB
B(Switzerland)/AEG(Ge
rmany)/Schlumberger
(USA)
2 Type of Meter Digital /Analog
3 Type of Meters in each Panel Volt, 3 nos. Amp, kW,
kVAR and Pf

13. STEEL STRUCTURE DESIGN

Sl. Description Unit Requirements


N0.
1 Maximum ratio slenderness
a) Main members mm 120
b) Bracings mm 180
c) Redundant mm. 250
2 Minimum size of member mm 45455
3 Min member thickness
Main member mm 6
Other bracing member mm 5
Plate mm 5
Bolt diameter mm 16
4 Galvanizing thickness mm 85

14. Control cable


XLPE insulated multi core control cable Laid up beded with PVC or tap. Flat/round wire
armoring with helical steel taping and PVC sheathed, rated voltage 600/1000, continuous
permissible voltage 720/1200 volts (VDE 027/3.69 BDS 901:85) (NYRGby) suitable for
use in indoors, outdoors, underground and in water for continuous permissible service
voltage of 720/1200 volts. Maximum resistance 4.73 ohm/km at 35°C.
18
15. POWER CABLES

15.1. 33 KV POWER CABLES (U/G)

Guaranteed Technical Data Schedule of 33KV, 1-Core × 500 Sq.mm U/G XLPE
Copper Cable

SL Description Unit Required Specification


No.
1 Name and address of the To be mentioned
Manufacturer
2 Type/Model of the offered cable To be mentioned
3 Nominal system voltage KV 33
4 Rated voltage of cable KV 18/30(36)

5 Process of manufacturing VCV/CCV


6 Number of core and cross sectional Sq.mm 1×500
area of conductor cores
7 Conductor material Copper
8 Minimum no of strand No. 53
9 Diameter of each strand mm To be mentioned
10 Shape of conductor Compacted Circular
11 Type of conductor screen Semi-conducting
12 Thickness of semi conducting mm 0.6
screen
13 Avg. thickness of insulation mm 8.0
14 Process of curing Dry process
15 Material of insulation Cross Linked Polyethylene (XLPE)
16 Type of non metallic insulating Semi-conducting
screen
17 Thickness of semi conducting mm 1.0
insulation screen
18 Number and diameter of copper No./mm Based on design calculation
screen strands
19 Composition of filler PVC
20 Composition of bedding Extruded PVC
21 Thickness of bedding mm Based on design calculation
22 Number and diameter of armour No./mm As per IEC 60502
wire
23 Avg. thickness of MDPE over mm Based on design calculation
sheath
24 Nominal diameter of complete mm Based on design calculation
cable
25 Nominal weight per meter of Kg/m Based on design calculation
complete cable
26 Minimum radius of bend round mm Based on design calculation
which cable can be laid
27 Max. D.C resistance of conductor Ohm/m Based on design calculation
per meter at 20̊ C
28 Max. A.C resistance of conductor Ohm/m Based on design calculation
per meter at MAXIMUM
CONDUCTOR TEMPARATURE
29 Star resistance per meter of cable Ohm/m Based on design calculation
at 50Hz
30 Star capacitance per per meter of pF/m Based on design calculation
cable at 50Hz
31 Charging current per conductor per mA Based on design calculation

19
meter at 18000/30000 Volts , 50Hz
32 Maximum current carrying A Based on design calculation
capacity of conductor in ground
33 Maximum conductor temperature ̊C Based on design calculation
under continuous loading
34 Short circuit withstand capacity KA Min. 25
nof the cable for 1 sec. duration
35 conductor temperature at the end ̊C ≤250
of short circuit
36 Earth fault withstand capacity for 1 KA Min. 25
sec.
37 Screen short circuit withstand KA Min. 25
capacity

38 Armour short circuit capacity KA Based on design calculation


39 Cable resistance, reactance

a) for positive sequence Ohm/m Based on design calculation


b) negative sequence Ohm/m Based on design calculation
c) Zero sequence Ohm/m Based on design calculation

20
SCHEDULE B

TENDER PRICES

21
SCHEDULE B

TENDER PRICES

The Tenderer is to complete in full the following Price Schedule in accordance with
BOQ described in section-6 of this Tender Document.

Each item is to be priced separately for switching station & 33KV Line Augmentation
work and is to be fully inclusive of all costs associated with completing the Works. The
prices are to include for surveying, design, fabrication, manufacture, assembly, quality
control, testing, packing, insurance, delivery to site. The estimated cost of elements are
to be shown in the appropriate column in the schedule shall include landing, haulage,
transport to site, civil works, erection, construction, assembly, connecting, testing
finishing of, setting to work and maintenance during the defect liability period including
all supervision, project management costs, overheads, on-costs and profits etc.

The Works shall be valued and paid exclusively at the unit prices and total prices quoted
in the schedule, which are to remain fixed for the duration of the Contract.

The prices quoted are to be firm for the completed Works in full working order in
accordance with the requirements of the Contract.

Prices for the equipment at site, erection/ supervision elements are to be quoted in
Bangladesh Taka inclusive of all duties and taxes paid or payable on components and
material incorporated or to be incorporated in the plant.

Prices shall also include for all necessary local materials, inland transportation, insurance
etc.

22
SCHEDULE C

BAR CHART PROGRAMME OF KEY ACTIVITIES

23
SCHEDULE C

BAR CHART PROGRAMME OF KEY ACTIVITIES


The individual dates are all contractually bindings.

The times given under column C are the commissioning target dates at present planned
to be achieved and may be the subject of mutual adjustment.

The times entered under column A are to be the dates guaranteed for arrival at site of the
equipment before plant erection to the extent necessary to enable him to proceed with
work to meet the dates under column B guaranteed for complete delivery, erection and
commissioning.

The time include all necessary control, relay, metering, auxiliary power, ancillary
equipment to enable the respective item of plant to be completely commissioned and put
into commercial operation together with such other associated equipment, e.g. bus-bars
etc. as will ensure that subsequent shutdown are unnecessary for at least only of a
temporary or short time nature.

A* B* C*
List of Guaranteed Arrival Guaranteed Target Completion
Equipment at site Completion

* Time in months, after signing of Contract.

Preliminary foundation drawings as called for in the Technical Specification shall be


provided within 1.0 month of the contract commencing

24
SCHEDULE D

MANUFACTURERS, PLACES OF MANUFACTURE AND TESTING

25
SCHEDULE D

MANUFACTURERS, PLACES OF MANUFACTURE AND TESTING

Item Description Manufacturer Place of Place of Testing


Manufacture and Inspection
1. 33KV SWITCHGEAR

Circuit Breakers (VCB)

Operating Mechanism

Disconnecting Switch (DS)

Earthing Switch (ES)

Busbar

Connector

Lightning Arrester (LA)

Voltage Transformer (VT)

Current Transformer (CT)

Insulator Disc

Insulator Post Type

DO Fuse

Remote Control Panel

Relays

Indicating Instrument

Energy Meters

Battery Charger

Battery

LVAC Panel

26
DC Panel

LV Power & Control Cables

2. 11kV indoor Switchgear


VCB (2000Amps) for
incoming feeder with inbuilt
11 kV 2500Amps copper
Bus-bar.

11kV indoor Switchgear


VCB (2000Amps) for 11 kV
Bus-coupler

11kV indoor Switchgear


VCB (630Amps) for 11 kV
outgoing feeders.

3. STEEL STRUCTURES

4. EARTHING
Copper Conductor

5. SITE ERECTION AND


COMMISSIONING BY

6. CIVIL WORKS

Design to be performed by:

Construction by:

27
7. All materials for
Augmentation of 33 KV
existing line.

28
SCHEDULE E

TECHNICAL PARTICULARS AND GUARRANTEES

29
SCHEDULE E

TECHNICAL PARTICULARS AND GUARRANTEES

1.0 33KV OUTDOOR TYPE VACUUM CIRCUIT BREAKER (VCB)

1.1 33KV OUTDOOR TYPE VACUUM CIRCUIT BREAKER (FEEDER BREAKER)

Sl. Description Unit Requirement Manufacturer’s


No. Guaranteed Data
1 Manufacturer To be mentioned
2 Model number To be mentioned
3 Number of phases 3
4 No. of break per phase To be mentioned
5 Interrupting medium Vacuum
6 Vacuum interrupter’s manufacturer To be mentioned
7 Rated voltage KV 33
8 Maximum voltage KV 36
9 Rated frequency HZ 50
10 Rated normal current for outgoing feeder A 1250
11 Rated breaking currents: Arms
a) Line charging A 25
b) Cable charging A 50
c) Small inductive A 02
12 Rated short-circuit breaking current KA rms 31.5
13 First pole to clear factor To be mentioned
14 Rated transient recovery voltage at 100% KV To be mentioned
rated short circuit breaking current
15 Rated short-circuit making current KA 78.75
16 Rated operating sequence O-0.3s-CO-3min-C
17 Rated duration of short-circuit S 3
18 Rated out of phase breaking current KA To be mentioned
19 Rated opening time ms To be mentioned
20 Rated break time ms To be mentioned
21 Rated closing time ms To be mentioned
22 Is circuit breaker re-strike free Yes/no Yes
23 Rated short time withstand current, 3 sec rms KA 31.5
24 Impulse withstand on 1.2/50s wave kV 170
25 Power frequency test voltage (dry) at 50Hz 1 kV 70
min
26 Type of arc contacts or arc control device To be mentioned
27 Main contact
a) Type of contact To be mentioned
b) Material of contact surfaces To be mentioned
c) Contact resistance µΩ Less than 40
28 Length of break mm To be mentioned

29 Length of stroke mm To be mentioned


30 Operating mechanism manufacturer To be mentioned
31 Operating mechanism type Spring
32 Trip free/or fixed trip Trip free
33 Is lockout facility fitted? Yes
35 Closing supply
a) Closing coil Volts V DC 110V
b) Closing coil current A DC To be mentioned
36 Rated supply voltage of shunt opening release
a) Trip coil Volts V DC 110V
b) Trip coil current A DC To be mentioned
37 Spring charging motor
a) Current A AC To be mentioned

30
Sl. Description Unit Requirement Manufacturer’s
No. Guaranteed Data
b) Voltage AC V AC 415/230
38 Number of auxiliary switch contacts
a) normally open NO 9
b) normally closed NC 9
c) adjustable As required
39 Maximum creepage
a) to earth mm To be mentioned
b) across interrupter terminals mm To be mentioned
40 Number of interrupters per pole Nos 1
41 Material of interrupter chamber To be mentioned
42 Wall thickness of interrupter chamber mm To be mentioned
a) Material of contact surface primary arcing To be mentioned
b) Contact resistance To be mentioned
43 Length of each break mm To be mentioned
44 Length of stroke mm To be mentioned
45 Operating rod for moving contact(s) material To be mentioned
46 Dimensions etc. To be mentioned
47 Weight of circuit breaker unit complete kg To be mentioned
48 Maximum shock load imposed on floor or N To be mentioned
foundations when opening under fault
conditions (state whether tension or
compression)
49 Period of time equipment has been in To be mentioned
commercial operation
50 Opening time
a) Without current at 100% of rated breaking sec 0.5 max
current
b) Breaking time cycle 5 (0.1 second)
c) Closing time ms 70±10
51 Maximum arc duration at any duty cycle of ms To be mentioned
IEC 56-2 at........%
52 Current at which maximum arc duration A To be mentioned
occurs (critical current)
53 Make time ms To be mentioned
54 Time from closing of control switch to ms To be mentioned
completion of closing stroke during fault
making
55 Is an external series break incorporated in the Yes/no To be mentioned
breaker?
56 Is any device used to limit transient recovery Yes/no To be mentioned
voltage?
57 Number of close/trip operation possible on Nos. To be mentioned
one spring charge
58 Minimum clearance in air:
a) between phases mm 430
b) phase to earth mm 380
c) across interrupters mm To be mentioned
d) live parts to ground level mm To be mentioned
59 Period of time the equipment has been in Years To be mentioned
commercial operation
60 Cree page distance (min) kV/mm 25
61 Method of indicating VCB ON/OFF Mech/El To be mentioned
ect
62 Life of interrupter Years To be mentioned
63 Pressure in vacuum tube for VCB Bar To be mentioned
64 Guaranteed numbers of operation for
vacuum interrupter
a) at rated crrent switching Nos. To be mentioned
b) at short circuit current switching Nos. To be mentioned
65 All current carrying parts of VCB shall Copper
be made of

31
Sl. Description Unit Requirement Manufacturer’s
No. Guaranteed Data
66 Standard IEC 56
67 Degree of Protection IP 55

1.2 33KV OUTDOOR TYPE VACUUM CIRCUIT BREAKER (BUS COUPLER BREAKER)
(N/A)

Sl. Description Unit Requirement Manufacturer’s


No. Guaranteed Data
1 Manufacturer To be mentioned
2 Model number To be mentioned
3 Number of phases 3
4 No. of break per phase To be mentioned
5 Interrupting medium Vacuum
6 Vacuum interrupter’s manufacturer To be mentioned
7 Rated voltage KV 33
8 Maximum voltage KV 36
9 Rated frequency HZ 50
10 Rated normal current-feeder A 1250
11 Rated breaking currents: Arms
a) Line charging A 25
b) Cable charging A 50
c) Small inductive A 02
12 Rated short-circuit breaking current KA rms 31.5
13 First pole to clear factor To be mentioned
14 Rated transient recovery voltage at 100% KV To be mentioned
rated short circuit breaking current
15 Rated short-circuit making current KA 78.75
16 Rated operating sequence O-0.3s-CO-3min-C
17 Rated duration of short-circuit S 3
18 Rated out of phase breaking current KA To be mentioned
19 Rated opening time ms To be mentioned
20 Rated break time ms To be mentioned
21 Rated closing time ms To be mentioned
22 Is circuit breaker re-strike free Yes/no Yes
23 Rated short time withstand current, 3 sec KA 31.5
rms
24 Impulse withstand on 1.2/50s wave kV 170
25 Power frequency test voltage (dry) at 50Hz kV 70
1 min
Sl. Description Unit Requirement Manufacturer’s
No. Guaranteed Data
26 Type of arc contacts or arc control device To be mentioned
27 Main contact
a) Type of contact To be mentioned
b) Material of contact surfaces To be mentioned
c) Contact resistance µΩ Less than 40
28 Length of break mm To be mentioned

Sl. Description Unit Requirement Manufacturer’s


No. Guaranteed Data
29 Length of stroke mm To be mentioned
30 Operating mechanism manufacturer To be mentioned
31 Operating mechanism type Spring
32 Trip free/or fixed trip Trip free
33 Is lockout facility fitted? Yes
35 Closing supply
a) Closing coil Volts V DC 110V

32
Sl. Description Unit Requirement Manufacturer’s
No. Guaranteed Data
b) Closing coil current A DC To be mentioned
36 Rated supply voltage of shunt opening
release
a) Trip coil Volts V DC 110V
b) Trip coil current A DC To be mentioned
37 Spring charging motor
a) Current A AC To be mentioned
b) Voltage AC V AC 415/230
38 Number of auxiliary switch contacts
a) normally open NO 9
b) normally closed NC 9
c) adjustable As required
39 Maximum cree page
a) to earth mm To be mentioned
b) across interrupter terminals mm To be mentioned
40 Number of interrupters per pole Nos 1
41 Material of interrupter chamber To be mentioned
42 Wall thickness of interrupter chamber mm To be mentioned
a) Material of contact surface primary To be mentioned
arcing
b) Contact resistance To be mentioned
43 Length of each break mm To be mentioned
44 Length of stroke mm To be mentioned
45 Operating rod for moving contact(s) To be mentioned
material
46 Dimensions etc. To be mentioned
47 Weight of circuit breaker unit complete kg To be mentioned
48 Maximum shock load imposed on floor or N To be mentioned
foundations when opening under fault
conditions (state whether tension or
compression)
49 Period of time equipment has been in To be mentioned
commercial operation
50 Opening time
a) Without current at 100% of rated sec 0.5 max
breaking current
b) Breaking time cycle 5 (0.1 second)
c) Closing time ms 70±10
51 Maximum arc duration at any duty cycle of ms at......% To be mentioned
IEC 56-2
52 Current at which maximum arc duration A To be mentioned
occurs (critical current)
53 Make time ms To be mentioned
54 Time from closing of control switch to ms To be mentioned
completion of closing stroke during fault
making
55 Is an external series break incorporated Yes/no To be mentioned
in the breaker?
56 Is any device used to limit transient Yes/no To be mentioned
recovery voltage?
57 Number of close/trip operation possible Nos. To be mentioned
on one spring charge
58 Minimum clearance in air:
a) between phases mm 430
b) phase to earth mm 380
c) across interrupters mm To be mentioned
d) live parts to ground level mm To be mentioned
59 Period of time the equipment has been in Years To be mentioned

33
Sl. Description Unit Requirement Manufacturer’s
No. Guaranteed Data
commercial operation
Sl. Description Unit Requirement Manufacturer’s
No. Guaranteed Data
60 Cree page distance (min) kV/mm 25
61 Method of indicating VCB ON/OFF Mech/El To be mentioned
ect
62 Life of interrupter Years To be mentioned
63 Pressure in vacuum tube for VCB Bar To be mentioned
64 Guaranteed numbers of operation for
vacuum interrupter
a) at rated crrent switching Nos. To be mentioned
b) at short circuit current switching Nos. To be mentioned
65 All current carrying parts of VCB shall Copper
be made of
66 Standard IEC 56
67 Degree of Protection IP 55

34
2. 33KV DISCONNECTING SWITCH AND EARTHING SWITCH (DS/ES)

2.1. 33KV DISCONNECTING SWITCH (AT BUS SIDE FOR INCOMING) (If applicable)

Sl. Description Unit Requirement Manufacturer’s


No. Guaranteed Data
1 Manufacturer To be mentioned
2 Model number To be mentioned
3 Operating system Vertical
4 System voltage kV 33
5 Rated voltage kV 36
6 Frequency Hz 50
7 Number of pole Nos. 3
8 Rated normal current A 2000
9 Rated short time withstand current for 3 kA rms 31.5
sec
10 Rated duration of short circuit Sec 3
11 Rated peak withstand current kA pk 78.75
12 Basic insulation level kV 170
13 Installation Outdoor
14 Type Air
15 Construction Open
16 Method of operation Gang operated,
17 Type of operating mechanism Manual
18 Mounting position Vertical
19 Type of contact To be mentioned
20 Materiall of contact service To be mentioned
21 Manual operating torque KNm To be mentioned
22 Load switching capability A To be mentioned
23 Mechanical Terminal Load N To be mentioned
24 Insulation Cree page mm To be mentioned
25 Number of auxiliary switches
a) normally open NO 9
b) normally closed NC 9
c) adjustable As required
26 Other auxiliary loads
a) voltage V DC 110
b) current A DC To be mentioned
27 Total weight of three pole dis- .Kg To be mentioned
connector complete
28 Period of time equipment has been in Yr To be mentioned
commercial operation
29 Line charging current breaking capacity A To be mentioned
30 Magnetizing current breaking capacity A To be mentioned
31 Standard IEC-129
32 Degree of Protection IP 55
33 Power frequency with stand voltage Kv 70
34 Creepage Distance mm 900
35 Material Contact Copper with Silver
Coating

35
2.2. 33KV DISCONNECTING SWITCH (BUS SECTION)
Sl. Description Unit Requirement Manufacturer’s
No. Guaranteed Data
1 Manufacturer To be mentioned
2 Model number To be mentioned
3 Operating system Vertical
4 System voltage kV 33
5 Rated voltage kV 36
6 Frequency Hz 50
7 Number of pole Nos. 3
8 Rated normal current A 2500
9 Rated short time withstand current for 3 kA rms 31.5
sec
10 Rated duration of short circuit Sec 3
11 Rated peak withstand current kA pk 78.75
12 Basic insulation level kV 170
13 Installation Outdoor
14 Type Air
15 Construction Open
16 Method of operation Gang operated,
17 Type of operating mechanism Manual
18 Mounting position Vertical
19 Type of contact To be mentioned
20 Materiall of contact service To be mentioned
21 Manual operating torque KNm To be mentioned
22 Load switching capability A To be mentioned
23 Mechanical Terminal Load N To be mentioned
24 Insulation Cree page mm To be mentioned
25 Number of auxiliary switches
a) normally open NO 9
b) normally closed NC 9
c) adjustable As required
26 Other auxiliary loads
a) voltage V DC 110
b) current A DC To be mentioned
27 Total weight of three pole dis- .Kg To be mentioned
connector complete
28 Period of time equipment has been in Yr To be mentioned
commercial operation
29 Line charging current breaking capacity A To be mentioned
30 Magnetizing current breaking capacity A To be mentioned
31 Standard IEC-129
32 Degree of Protection IP 55
33 Power frequency with stand voltage Kv 70
34 Creepage Distance 900
35 Material Contact Copper with Silver
Coating

36
2.3. 33KV DISCONNECTING SWITCH (FOR FEEDERS AT BUS SIDE)

Sl. Description Unit Requirement Manufacturer’s


No. Guaranteed Data
1 Manufacturer To be mentioned
2 Model number To be mentioned
3 Operating system Vertical
4 System voltage kV 33
5 Rated voltage kV 36
6 Frequency Hz 50
7 Number of pole Nos. 3
8 Rated normal current A 1250
9 Rated short time withstand current for 3 kA rms 31.5
sec
10 Rated duration of short circuit Sec 3
11 Rated peak withstand current kA pk 78.75
12 Basic insulation level kV 170
13 Installation Outdoor
14 Type Air
15 Construction Open
16 Method of operation Gang operated,
17 Type of operating mechanism Manual
18 Mounting position Vertical
19 Type of contact To be mentioned
20 Materiall of contact service To be mentioned
21 Manual operating torque KNm To be mentioned
22 Load switching capability A To be mentioned
23 Mechanical Terminal Load N To be mentioned
24 Insulation Cree page mm To be mentioned
25 Number of auxiliary switches
a) normally open NO 9
b) normally closed NC 9
c) adjustable As required
d) Earting blade 6
26 Other auxiliary loads
a) voltage V DC 110
b) current A DC To be mentioned
27 Total weight of three pole dis- .Kg To be mentioned
connector complete
28 Period of time equipment has been in Yr To be mentioned
commercial operation
29 Line charging current breaking capacity A To be mentioned
30 Magnetizing current breaking capacity A To be mentioned
31 Standard IEC-129
32 Degree of Protection IP 55
33 Power frequency with stand voltage Kv 70
34 Creepage Distance 900
35 Material Contact Copper with Silver
Coating

37
2.4. 33KV DISCONNECTING SWITCH AND EARTHING SWITCH (FEEDER SIDE)

Sl. Description Unit Requirement Manufacturer’s


No. Guaranteed Data
1 Manufacturer To be mentioned
2 Model number To be mentioned
3 Operating system Vertical
4 System voltage kV 33
5 Rated voltage kV 36
6 Frequency Hz 50
7 Number of pole Nos. 3
8 Rated normal current A 1250
9 Rated short time withstand current for 3 kA rms 31.5
sec
10 Rated duration of short circuit Sec 3
11 Rated peak withstand current kA pk 78.75
12 Basic insulation level kV 170
13 Installation Outdoor
14 Type Air
15 Construction Open
16 Method of operation Gang operated,
17 Type of operating mechanism Manual
18 Mounting position Vertical
19 Type of contact To be mentioned
20 Materiall of contact service To be mentioned
21 Manual operating torque KNm To be mentioned
22 Load switching capability A To be mentioned
23 Mechanical Terminal Load N To be mentioned
24 Insulation Cree page mm To be mentioned
25 Number of auxiliary switches
a) normally open NO 9
b) normally closed NC 9
c) adjustable As required
d) Earthing blade 6
26 Other auxiliary loads
a) voltage V DC 110
b) current A DC To be mentioned
27 Total weight of three pole dis- .Kg To be mentioned
connector complete
28 Period of time equipment has been in Yr To be mentioned
commercial operation
29 Line charging current breaking capacity A To be mentioned
30 Magnetizing current breaking capacity A To be mentioned
31 Standard IEC-129
32 Degree of Protection IP 55
33 Power frequency with stand voltage Kv 70
34 Creepage Distance 900
35 Material Contact Copper with Silver
Coating

38
3. 33KV CURRENT TRANSFORMER (CT)

3.1 33KV CURRENT TRANSFORMER (BUS COUPLER) (If applicable)

Sl. Description Unit Requirement Manufacturer’s


No. Guaranteed Data
1 Manufacturer To be mentioned
2 Model number To be mentioned
3 Standard IEC 185 or equivalent
4 Installation Outdoor type mounted
on galvanized steel
structure
5 Type Electromagnetic
induction, single
phase, outdoor, oil/
Synthetic
6 Bushing Porcelain
7 Major insulation Low oil content
outdoor type
8 Application Protection/ metering
9 Rated secondary accuracy and burden
a) Metering (core 1- for indicating 0.2, 50VA
metering)
b) Metering (core 2- for energy 0.2, 50VA
metering)
c) Protection (core 3) 5P20, 50VA
10 Rated primary current Arms 2400-1600/5-5-5A
11 Rated secondary current Arms 5-5-5A
12 Extended current rating % 120
13 Over current rating A 10
13 Short time current rating kA 25 for 3 sec
14 No of core 3
15 System voltage kV 33
16 Rated voltage kV 36
17 Rated frequency Hz 50
18 Basic insulation level on 1.2 / 50 micro kV 170
sec wave
19 Power frequency withstand voltage (1 kV 70
min, 50Hz)
20 Insulator cree page (phase to earth) mm/kV 25
21 Rated dynamic current kA pk 100
22 Insulation class A
23 Is earth screen fitted between primary Yes
and secondary windings
24 Extended Current Rating (% of rated % 120
current)
25 Over Current Rating A 10
26 Knee point voltage V To be mentioned
27 System earthing Effectively earthed
28 Standard - As per relevant IEC-
185

39
3.2 33KV CURRENT TRANSFORMER (FEEDER)

Sl. Description Unit Requirement Manufacturer’s


No. Guaranteed Data
1 Manufacturer To be mentioned
2 Model number To be mentioned
3 Standard IEC 185 or equivalent
4 Installation Outdoor type mounted
on galvanized steel
structure
5 Type Electromagnetic
induction, single
phase, outdoor, oil/
Synthetic
6 Bushing Porcelain
7 Major insulation Low oil content
outdoor type
8 Application Protection/ metering
9 Rated secondary accuracy and burden
a) Metering (core 1) 0.2, 30VA
b) Protection (core 2) 5P20, 30VA
10 Rated primary current Amps 800-400/5-5-5A
11 Rated secondary current Amps 5-5-5A
12 Extended current rating % 120
13 Over current rating A 10
13 Short time current rating kA 31.5 for 3 sec
14 No of core 3
15 System voltage kV 33
16 Rated voltage kV 36
17 Rated frequency Hz 50
18 Basic insulation level on 1.2 / 50 micro kV 170
sec wave
19 Power frequency withstand voltage (1 kV 70
min, 50Hz)
20 Insulator cree page (phase to earth) mm/kV 25
21 Rated dynamic current kA pk 100
22 Insulation class A
23 Is earth screen fitted between primary Yes
and secondary windings
24 Extended Current Rating (% of rated % 120
current)
25 Over Current Rating A 10
26 Knee point voltage V To be mentioned
27 System earthing Effectively earthed
28 Standard - As per relevant IEC-
185

40
4. 33KV VOLTAGE TRANSFORMER (VT FOR BUS)

Sl. Description Unit Requirement Manufacturer’s


No. Guaranteed Data
1 Manufacture To be mentioned
2 Model number To be mentioned
3 Installation Outdoor type mounted
on galvanized steel
structure
4 Type Electromagnetic
induction, single
phase, outdoor, Oil
5 Bushing Porcelain
6 Application Protection and
metering
7 Major insulation Low oil content
8 System voltage kV 33
9 Rated voltage kV 36
10 Frequency Hz 50
11 Transformation ratio kV 33/3: 0.11/3:
0.11 /3
12 Type of secondary Double winding
13 Rated secondary burden and accuracy
a) Secondary winding VA 60
Core 1 (Dedicated for energy metering) Class 0.2
(a) Secondary winding VA 50
Core 2 Class 3P
14 Total capacitance at 100 Hz PF To be mentioned
15 50 Hz 1(one) minute withstand voltage kV To be mentioned
wet
16 Impulse withstand voltage (1.2 / 50 kV (min) 170
micro sec wave)
17 Temperature co-efficient of ratio per ºC To be mentioned
18 Total external cree page distance mm/kV 25
19 Maximum errors with 5% primary
voltage
a) Ratio % To be mentioned
b) Phase angle minutes To be mentioned
20 Total install weight kg To be mentioned
21 System earthing Effectively earthed
22 Standard IEC 186 or equivalent
23 Power frequency with stand voltage Kv 70
24 Partial Discharge PC ≤5
25 Short circuit withstand voltage KA 63
26 Rated voltage factor 1.2contin
uous
1.9 30
second

41
5. 33KV LIGHTNING ARRESTER (LA)

Sl. Description Unit Requirement Manufacturer’s


No. Guaranteed Data
1 Manufacturer To be mentioned
2 Model Number To be mentioned
3 Type Metal Oxide (Zno)
single phase, Gapless
type,
4 System voltage kV 33
5 Rated voltage kV 36
6 Frequency Hz 50
7 Continuous operating voltage kV 24
8 Rated arrester voltage kV 30
9 Standard nominal discharge current kA 10
10 Reference current at ambient temperature mA 2
11 Steep current impulse residual voltage kV pk 84
12 Basic insulation level on 1.2 / 50 micro kV 170
sec wave
13 Power frequency withstand voltage of
housing KVrms 70
Dry : KVrms 70
Wet : KV 170
Impulse :
14 Power frequency withstand voltage kV 70
(1.2/50 ms)
15 Lightning impulse residual voltage (8/20 kVpk 100
micro sec front time)
16 Step current impulse residual voltage at kV pk 110
10kA of 1 micro sec front time
17 High current impulse withstand value kA 100
(4/10 micro sec)
18 Duty Class Heavy
19 Nominal diameter of resistor blocks mm
20 Pressure relief device fitted? Yes/no
21 Temporary over voltage capability
a) 0.1 sec To be mentioned
b) 1.0 sec To be mentioned
c) 10.0 sec To be mentioned
d) 100.0 sec To be mentioned
22 Leakage current at rated voltage To be mentioned
23 Minimum reset voltage To be mentioned
24 Overall height of arrester (without m To be mentioned
supporting structure)
25 Clearances:
Phase to earth (from centre line) mm To be mentioned
Phase to phase (centre line to centre line) mm To be mentioned
26 Overall weight of arrester (without kg To be mentioned
supporting structure)
27 Minimum creepage distance over mm/kV To be mentioned
insulator housing
28 Type & Description of surge monitoring
device
29 Over all dimension
i) Height mm To be mentioned
ii) Diameter mm To be mentioned
30 Connecting lead from LA terminal to 16 mm2 insulated cu
surge monitor cable
31 Neutral connection - Effectively Earthed
32 Surge monitor Shall be provided
33 Standard IEC 99-4

42
Sl. Description Unit Requirement Manufacturer’s
No. Guaranteed Data
34 Discharge Class 3
35 Pressure relief class Class A
36 Degree of protection IP 55

43
6. 33/0.415KV, 200KVA AUXILIARY TRANSFORMER

Sl. Description Unit Requirement Manufacturer’s


No. Guaranteed Data
1 Manufacturer To be mentioned
2 Model Number To be mentioned
3 Standard IEC-76
4 Rated power KVA 200
5 Type of cooling ONAN
6 Coolant Mineral Oil
7 Number of phase 3
8 Frequency Hz 50
9 Normal transformation ratio KV 33/0.4
10 Nominal HT voltage KV 33
11 Maximum HT voltage KV 36
12 Nominal LT voltage KV 0.415 /0.240
13 Maximum LT voltage KV 0.457
14 Type Core
15 Insulation Outdoor, tropical and
high humidity
16 Earthing Neutral earth at LT,
3-phase 4-wire
17 Windings Double wound and of
high conductivity
copper
18 No-load loss, Watts W To be mentioned
19 Load losses at rated full load at 750C, W To be mentioned
Watts
20 Magnetising current at normal voltage, A To be mentioned
Amps
21 Test Voltage:
a) Impulse Test voltage 1.2/50 s
i) H.T KV 170
ii) L.T KV 10
b) Power frequency withstand voltage
for 1 minute
i) HT KV 70
ii) L.T KV 2.5
22 Vector Group Dynll
23 Neutral to be Brought out
a) HT Nil
b) LT Yes
24 Neutral insulation Full insulation and
100% capacity
25 LT bushing Nos 4
26 Impedance voltage at 75 oC at normal About 5%
ratio and rated capacity
27 Tapping range 5 steps off-load tap
changer, 2.5% in each
step
28 Type of tap changer Manual
Sl. Description Unit Requirement Manufacturer’s
No. Guaranteed Data
29 Maximum temperature rise over 40 oC
ambient when transformer is working at
full load and tap changer is at normal
position
o
a) Winding by resistance C 65

44
Sl. Description Unit Requirement Manufacturer’s
No. Guaranteed Data
o
b) Oil by temperature C 60
30 Type of base Ground mounted
31 Dimension of transformer
a) Width, mm To be mentioned
b) Length, mm To be mentioned
c) Height, mm To be mentioned
d) Tank Sheet thickness of top, bottom
& side, mm
32 Total weight of complete Transformer kg To be mentioned
including fittings & oil, Kg
33 Routine Test Report
a) Measurement of Voltage ratio test. To be mentioned
b) Vector group test. To be mentioned
c) Measurement of winding resistance. To be mentioned
d) Measurement of insulation To be mentioned
resistance.
e) Measurement of no load loss & no- To be mentioned
load current.
f) Measurement of impedance voltage To be mentioned
& load loss.
g) Power frequency (Separate source To be mentioned
voltage) withstands test.
h) Transformer oil test. To be mentioned
34 Type Test Report
a) Impulse Voltage Withstand Test. To be mentioned
b) Temperature Rise Test To be mentioned
c) Short Circuit Test or details To be mentioned
calculations on the basis of the design
data

45
7. 33KV BUSBARS AND CONNECTIONS

Sl. Description Unit Requirement Manufacturer’s


No. Guaranteed Data
A. CONDUCTORS AND
CONNECTIONS
1. Manufacturer To be mentioned
2. Material of conductor To be mentioned
a) Bus-bar ACSR/2xMartin
b) Jumper/connections To be mentioned
3. Overall diameter mm To be mentioned
4. Nominal cross section mm2 To be mentioned
5. Maximum rated current A 2500
Maximum working tension of main
6. kg/m2 To be mentioned
connections
DC resistance of conductors per 1000
7. Ohms To be mentioned
meters at 20ºC
2
8. Tensile breaking stress of material N/mm To be mentioned
9. Maximum permissible span length m To be mentioned
Maximum sag under own weight of
10. mm To be mentioned
maximum span
11. Temperature rise at rated current ºC 35

46
8. 33KV BUSBAR INSULATOR STRINGS

Sl. Description Unit Requirement Manufacturer’s


No. Guaranteed Data
B. INSULATORS
1 Manufacturer - To be mentioned
2 Model no. - To be mentioned
3 Insulator material - Porcelain
4 Number of units per string Nos. 4
5 Insulator Voltage Class KV
6. Weight of insulator complete kg
7 Type of Insulator - Ball and socket type
disc, security clip
made of rod brass
alloy.
8 Creepage/ leakage distance (min.) mm To be mentioned
9 Total creepage distance of string mm 900
10 Unit Spacing mm To be mentioned
11 Dry Arcing distance (minimum) mm To be mentioned
12 Diameter of Insulator mm To be mentioned
13 Withstand Voltage, Minimum :
a) Power Frequency, dry (one min.) KV 70
b) Power Frequency, wet (one min.) KV 40
c) Impulse 1.2/50  sec KV 110
14 Flashover Voltage, Minimum :
a) Power Frequency, dry KV 80
b) Power Frequency, wet KV 50
c) 50% Impulse 1.2/50  sec wave, KV 125
positive or impulse 1.2/50  sec
wave positive.
d) 50% Impulse 1.2/50  sec wave KV 130
Negative
15 Power Frequency Puncture Voltage, KV 110
minimum
16 Minimum Mechanical Strength for
Suspension :
a) Electro-mechanical Breaking Load Kg 7260
b) Mechanical Breaking load Kg 6800
c) Tension Proof Test Load Kg 3400
d) Time Load Test Value Kg 4536
e) Mechanical Impact Strength mm Kg 630
17 Minimum Mechanical Strength for
Strain Stringing :
a) Electro-mechanical Breaking Load Kg 11340
b) Mechanical Breaking load Kg 11340
c) Tension Proof Test Load Kg 3400
d) Time Load Test Value Kg 4536
e) Mechanical Impact Strength mm Kg 530
18 Insulator Hardware Insulator hardware for
insulator strings or
bus-support such shall
have UTS-120 KN and
galvanized as per BS-
729.
19 Standard AS per latest editions
of IEC-383.

47
09. 11KV INDOOR TYPE VACUUM CIRCUIT BREAKER
09.1 11KV INDOOR TYPE VACUUM CIRCUIT BREAKER (BUS COUPLER BREAKER)

Sl. No. Description Unit Requirement Manufacturer’s


Guaranteed Data
1 Manufacturer’s Name & - To be mentioned
Country of Origin
2 Manufacturer’s Model No. - To be mentioned
3 System nominal voltage kV 11
4 Maximum system voltage kV 12
5 Rated frequency Hz 50
6 Rated normal current:
 Incoming for 10/13.33 A 2000
MVA Transformer
 Outgoing Feeder A 630
7 No. of Phase Nos. 3
8 No. of breaks per phase Nos To be mentioned
9 Interrupting medium - Vacuum
10 Manufacturer’s name and - To be mentioned
country of origin of Vacuum
Interrupter
11 Manufacturer’s model no. of - To be mentioned
vacuum interrupter
12 Power frequency withstand kV 28
voltage
13 Lightning impulse withstand kV 75
voltage on 1.2/50 µs wave
14 Emergency overload rating of - To be mentioned
normal at 20C ambient
15 Duration in any 24 hrs. period - To be mentioned
16 Busbar scheme No. Single
17 Number of busbar Nos. 3
18 Temperature rise of busbar at C To be mentioned
rated current
19 Material of busbar - Copper
2
20 Cross-section of busbar mm To be mentioned
21 Rated normal current of A 2000
busbar for 10/13.33 MVA S/S
22 Busbar insulation material - To be mentioned
23 Are floor plates or rails - To be mentioned
included?
24 Overall dimension of each circuit breaker unit:
 Incomer:
-Height mm To be mentioned
-Width mm To be mentioned
-Depth mm To be mentioned
 Feeder:
-Height mm To be mentioned
-Width mm To be mentioned
-Depth mm To be mentioned
 Bus coupler:
-Height mm To be mentioned
-Width mm To be mentioned
-Depth mm To be mentioned
25 Width necessary for breaker
withdrawal
26 Rated short time withstand kA 25

48
Sl. No. Description Unit Requirement Manufacturer’s
Guaranteed Data
current (Rated short circuit
breaking current) for 3 Sec.
27 Rated Peak withstand current kA 62.5
(Rated short circuit making
current)
28 Breaking Capacity:
 Symmetrical rms kA 25
 Asymmetrical mis kA 25
29 Rated duration of short circuit Sec. To be mentioned
30 Degrees of protection by IP To be mentioned
enclose
31 First pole to clear factor - To be mentioned
32 Rated transient recovery kVp To be mentioned
voltage at 100% rated short
circuit breaking current
33 Rated line charging breaking A To be mentioned
current
34 Rated cable charging breaking A To be mentioned
current
35 Rated out of phase breaking A To be mentioned
current
36 Is circuit breaker re-strike - Yes
free?
37 No. of tripping coil Nos. 2
38 Trip coil current A To be mentioned
39 Trip coil voltage VDC 110
40 Is circuit breaker trip free? - Yes
41 Type of main contact - To be mentioned
42 Material of contact surface - To be mentioned
43 Contact resistance µ To be mentioned
44 Does magnetic effect of load - To be mentioned
current increase contract?
45 Length of each break/phase mm To be mentioned
46 Length of stroke mm To be mentioned
47 Weight of circuit breaker Kg To be mentioned
complete without operating
mechanism and cubicles
48 Weight of circuit breaker Kg To be mentioned
complete with PCM Cubicles
as in service
49 Maximum shock load imposed N To be mentioned
on floor or foundation when
opening under fault condition
(State compression or tension)

OPERATING:
50 Operating Sequence To be mentioned
51  Opening time without ms To be mentioned
current at 100% of rated
breaking current
 Braking time Cycle To be mentioned
 Closing time ms To be mentioned
52 Maximum arc duration of any ms at To be mentioned
duty cycle as per latest …..%

49
Sl. No. Description Unit Requirement Manufacturer’s
Guaranteed Data
revision of relevant IEC
53 Current at which maximum arc A To be mentioned
duration occurs (critical
current)
54 Make time ms To be mentioned
55 Minimum time for arc ms To be mentioned
extinction remake when
adapted for auto closing
56 Time form closing of control of ms To be mentioned
switch to completion of closing
stroke during fault making
57 Manufacturer’s Name & - To be mentioned
Country of Origin of vacuum
interrupter
58 Manufacturer’s Model No. of - To be mentioned
vacuum interrupter
59 Pressure in vacuum tube bar To be mentioned
60 Guaranteed no. of vacuum Nos. To be mentioned
interrupter
61 In normal condition at rated Nos. To be mentioned
current switching
62 In short circuit condition i.e. at Nos. ≥100
the short circuit current
switching
CONSTRUCTION FEATURE:
63 Is an external series break - To be mentioned
incorporated in the breaker?
64 Is any device used to limit - To be mentioned
transient recovery voltage?
65 Method of closing - To be mentioned
66 Method of tripping To be mentioned
67 Minimum clearance in air:
 Between phase mm To be mentioned
 Phase to earth mm To be mentioned
68 Material of tank or chamber - To be mentioned
69 Material of moving contact - To be mentioned
tension rod
70 Period of time equipment has Years To be mentioned
been in commercial operation
71 Is removable draw-out VCB - To be mentioned
mounted on the lower part of
the panel i.e. on floor?
72 All meters, protective relays, - To be mentioned
signaling etc. mounted on the
upper part of the panel
73 Rated voltage of spring Vac To be mentioned
winding motor for closing
74 Materials of all current carrying - To be mentioned
parts of VCB
75 Name of relevant IEC - To be mentioned
standard to be followed in
Design, Manufacture, Testing
and Performance
PROTECTION
A. 33/11kV, 10/13.33MVA, 11kV Transformer Incoming Cubicles
76.0 Over current and earth fault protection with IDMT & instantaneous features
76.1 Manufacture's name & country - Siemens(Germany/

50
Sl. No. Description Unit Requirement Manufacturer’s
Guaranteed Data
of relay Switzerland)/ABB
(Switzerland/Swede
n/Finland) Schneider
(UK/France), Alstom
(UK/France)
76.2 Manufacture's model no. - To be mentioned
76.3 Type of relay - Numerical
programmable with
all necessary
features
76.4 Range of timing settings at 10 Sec. To be mentioned
time CT rating
76.5 Burden of relay at 10 time CT VA To be mentioned
rating
76.6 Percentage of current setting % To be mentioned
at which relay will reset
76.7 Reset time after removal of 10
time CT rated current for :
a) Phase element (100%) Sec To be mentioned
b) E/F element (40%) Sec To be mentioned
77.0 Standard Earth Fault Protection
77.1 Manufacture's name & country - Siemens(Germany/
Switzerland)/ABB
(Switzerland/Swede
n/Finland) Schneider
(UK/France), Alstom
(UK/France)
77.2 Manufacture's model no. - To be mentioned
77.3 Type of relay - Numerical
programmable with
all necessary
features
77.4 Range of current setting:
a) Phase element (% of CT Sec To be mentioned
Rating)
b) earth fault element (%of Sec To be mentioned
CT Rating)
77.5 Range of timing settings at 10 Sec To be mentioned
time CT rating
77.6 Burden of relay at 10 time CT VA To be mentioned
rating
77.7 Percentage of current setting % To be mentioned
at which relay will reset
77.8 Reset time after removal of 10
time CT rated current for :
a) Phase element (100%) Sec To be mentioned
b) E/F element (40%) Sec To be mentioned
B. 11kV Bus Coupler Cubicles:
78.0 Over Current and Earth Fault Protection with IDMT & instantaneous features
78.1 Manufacture's name & country - Siemens(Germany/
of relay Switzerland)/ABB
(Switzerland/Swede
n/Finland) Schneider
(UK/France), Alstom
(UK/France)
78.2 Manufacture's model no. - To be mentioned
78.3 Type of relay - Numerical

51
Sl. No. Description Unit Requirement Manufacturer’s
Guaranteed Data
programmable with
all necessary
features
78.4 Range of current setting:
a) Phase element (% of CT Sec To be mentioned
Rating)
b) earth fault element (%of Sec To be mentioned
CT Rating)
78.5 Range of timing settings at 10 Sec To be mentioned
time CT rating
78.6 Burden of relay at 10 time CT VA To be mentioned
rating
78.7 Percentage of current setting % To be mentioned
at which relay will reset
78.8 Reset time after removal of
10 time CT rated current for
:
a) Phase element (100%) Sec To be mentioned
b) E/F element (40%) Sec To be mentioned
C. 11kV Outgoing Feeder Cubicles
79.0 Over Current and Earth Fault Protection with IDMT & instantaneous features
79.1 Manufacture's name & country - Siemens(Germany/
of relay Switzerland)/ABB
(Switzerland/Swede
n/Finland) Schneider
(UK/France), Alstom
(UK/France)
79.2 Manufacture's model no. - To be mentioned
79.3 Type of relay - Numerical
programmable with
all necessary
features
79.4 Range of current setting:
a) Phase element (% of CT Sec To be mentioned
Rating)
b) earth fault element (%of Sec To be mentioned
CT Rating)
79.5 Range of timing settings at 10 Sec To be mentioned
time CT rating
79.6 Burden of relay at 10 time CT VA To be mentioned
rating
79.7 Percentage of current setting % To be mentioned
at which relay will reset
79.8 Reset time after removal of 10 time CT rated current for :
a) Phase element (100%) Sec To be mentioned
b) E/F element (40%) Sec To be mentioned
Metering and indication for 33/11kV, 10/13.33MVA Transformer 11kV Incoming and 11kV
outgoing Feeder
80.0 kWh Meter
80.1 Manufacture's name & country - Siemens(Germany/
Switzerland)/ABB
(Switzerland)/AEG
(Germany)/Schlumb
erger
(USA)/Elster(Roman
ia)
80.2 Manufacture's model no. - To be mentioned

52
Sl. No. Description Unit Requirement Manufacturer’s
Guaranteed Data
80.3 Type of Meter - Numerical
programmable
Multifunction
80.4 Class of Accuracy - 0.2
81.0 Indication Volt Meters &
Ammeters
81.1 Manufacture's name & country - To be mentioned
81.2 Manufacture's model no. - To be mentioned
81.3 Type of Meter - Analogue
81.4 Class of Accuracy - To be mentioned

53
09.2 11KV INDOOR TYPE VACUUM CIRCUIT BREAKER (INCOMING BREAKER)

Sl. No. Description Unit Requirement Manufacturer’s


Guaranteed Data
1 Manufacturer’s Name & - To be mentioned
Country of Origin
2 Manufacturer’s Model No. - To be mentioned
3 System nominal voltage kV 11
4 Maximum system voltage kV 12
5 Rated frequency Hz 50
6 Rated normal current:
 Incoming for 10/13.33 A 2000
MVA Transformer
 Outgoing Feeder A 630
7 No. of Phase Nos. 3
8 No. of breaks per phase Nos To be mentioned
9 Interrupting medium - Vacuum
10 Manufacturer’s name and - To be mentioned
country of origin of Vacuum
Interrupter
11 Manufacturer’s model no. of - To be mentioned
vacuum interrupter
12 Power frequency withstand kV 28
voltage
13 Lightning impulse withstand kV 75
voltage on 1.2/50 µs wave
14 Emergency overload rating of - To be mentioned
normal at 20C ambient
15 Duration in any 24 hrs. period - To be mentioned
16 Busbar scheme No. Single
17 Number of busbar Nos. 3
18 Temperature rise of busbar at C To be mentioned
rated current
19 Material of busbar - Copper
2
20 Cross-section of busbar mm To be mentioned
21 Rated normal current of A 2000
busbar for 10/13.33 MVA S/S
22 Busbar insulation material - To be mentioned
23 Are floor plates or rails - To be mentioned
included?
24 Overall dimension of each circuit breaker unit:
 Incomer:
-Height mm To be mentioned
-Width mm To be mentioned
-Depth mm To be mentioned
 Feeder:
-Height mm To be mentioned
-Width mm To be mentioned
-Depth mm To be mentioned
 Bus coupler:
-Height mm To be mentioned
-Width mm To be mentioned
-Depth mm To be mentioned
25 Width necessary for breaker
withdrawal
26 Rated short time withstand kA 25
current (Rated short circuit

54
Sl. No. Description Unit Requirement Manufacturer’s
Guaranteed Data
breaking current) for 3 Sec.
27 Rated Peak withstand current kA 62.5
(Rated short circuit making
current)
28 Breaking Capacity:
 Symmetrical rms kA 25
 Asymmetrical mis kA 25
29 Rated duration of short circuit Sec. To be mentioned
30 Degrees of protection by IP To be mentioned
enclose
31 First pole to clear factor - To be mentioned
32 Rated transient recovery kVp To be mentioned
voltage at 100% rated short
circuit breaking current
33 Rated line charging breaking A To be mentioned
current
34 Rated cable charging breaking A To be mentioned
current
35 Rated out of phase breaking A To be mentioned
current
36 Is circuit breaker re-strike - Yes
free?
37 No. of tripping coil Nos. 2
38 Trip coil current A To be mentioned
39 Trip coil voltage VDC 110
40 Is circuit breaker trip free? - Yes
41 Type of main contact - To be mentioned
42 Material of contact surface - To be mentioned
43 Contact resistance µ To be mentioned
44 Does magnetic effect of load - To be mentioned
current increase contract?
45 Length of each break/phase mm To be mentioned
46 Length of stroke mm To be mentioned
47 Weight of circuit breaker Kg To be mentioned
complete without operating
mechanism and cubicles
48 Weight of circuit breaker Kg To be mentioned
complete with PCM Cubicles
as in service
49 Maximum shock load imposed N To be mentioned
on floor or foundation when
opening under fault condition
(State compression or tension)
OPERATING:
50 Operating Sequence To be mentioned
51  Opening time without ms To be mentioned
current at 100% of rated
breaking current
 Braking time Cycle To be mentioned
 Closing time ms To be mentioned
52 Maximum arc duration of any ms at To be mentioned
duty cycle as per latest …..%
revision of relevant IEC
53 Current at which maximum arc A To be mentioned
duration occurs (critical
current)

55
Sl. No. Description Unit Requirement Manufacturer’s
Guaranteed Data
54 Make time ms To be mentioned
55 Minimum time for arc ms To be mentioned
extinction remake when
adapted for auto closing
56 Time form closing of control of ms To be mentioned
switch to completion of closing
stroke during fault making
57 Manufacturer’s Name & - To be mentioned
Country of Origin of vacuum
interrupter
58 Manufacturer’s Model No. of - To be mentioned
vacuum interrupter
59 Pressure in vacuum tube bar To be mentioned
60 Guaranteed no. of vacuum Nos. To be mentioned
interrupter
61 In normal condition at rated Nos. To be mentioned
current switching
62 In short circuit condition i.e. at Nos. ≥100
the short circuit current
switching

CONSTRUCTION FEATURE:
63 Is an external series break - To be mentioned
incorporated in the breaker?
64 Is any device used to limit - To be mentioned
transient recovery voltage?
65 Method of closing - To be mentioned
66 Method of tripping To be mentioned
67 Minimum clearance in air:
 Between phase mm To be mentioned
 Phase to earth mm To be mentioned
68 Material of tank or chamber - To be mentioned
69 Material of moving contact - To be mentioned
tension rod
70 Period of time equipment has Years To be mentioned
been in commercial operation
71 Is removable draw-out VCB - To be mentioned
mounted on the lower part of
the panel i.e. on floor?
72 All meters, protective relays, - To be mentioned
signaling etc. mounted on the
upper part of the panel
73 Rated voltage of spring Vac To be mentioned
winding motor for closing
74 Materials of all current carrying - To be mentioned
parts of VCB
75 Name of relevant IEC - To be mentioned
standard to be followed in
Design, Manufacture, Testing
and Performance
PROTECTION
A. 33/11kV, 10/13.33MVA, 11kV Transformer Incoming Cubicles
76.0 Over current and earth fault protection with IDMT & instantaneous features
76.1 Manufacture's name & country - Siemens(Germany/
of relay Switzerland)/ABB
(Switzerland/Swede
n/Finland) Schneider

56
Sl. No. Description Unit Requirement Manufacturer’s
Guaranteed Data
(UK/France), Alstom
(UK/France)
76.2 Manufacture's model no. - To be mentioned
76.3 Type of relay - Numerical
programmable with
all necessary
features
76.4 Range of timing settings at 10 Sec. To be mentioned
time CT rating
76.5 Burden of relay at 10 time CT VA To be mentioned
rating
76.6 Percentage of current setting % To be mentioned
at which relay will reset

76.7 Reset time after removal of 10


time CT rated current for :
a) Phase element (100%) Sec To be mentioned
b) E/F element (40%) Sec To be mentioned
77.0 Standard Earth Fault Protection
77.1 Manufacture's name & country - Siemens(Germany/
Switzerland)/ABB
(Switzerland/Swede
n/Finland) Schneider
(UK/France), Alstom
(UK/France)
77.2 Manufacture's model no. - To be mentioned
77.3 Type of relay - Numerical
programmable with
all necessary
features
77.4 Range of current setting:
a) Phase element (% of CT Sec To be mentioned
Rating)
b) earth fault element (%of Sec To be mentioned
CT Rating)
77.5 Range of timing settings at 10 Sec To be mentioned
time CT rating
77.6 Burden of relay at 10 time CT VA To be mentioned
rating
77.7 Percentage of current setting % To be mentioned
at which relay will reset
77.8 Reset time after removal of 10
time CT rated current for :
a) Phase element (100%) Sec To be mentioned
b) E/F element (40%) Sec To be mentioned
B. 11kV Bus Coupler Cubicles:
78.0 Over Current and Earth Fault Protection with IDMT & instantaneous features
78.1 Manufacture's name & country - Siemens(Germany/
of relay Switzerland)/ABB
(Switzerland/Swede
n/Finland) Schneider
(UK/France), Alstom
(UK/France)
78.2 Manufacture's model no. - To be mentioned
78.3 Type of relay - Numerical
programmable with
all necessary

57
Sl. No. Description Unit Requirement Manufacturer’s
Guaranteed Data
features
78.4 Range of current setting:
a) Phase element (% of CT Sec To be mentioned
Rating)
b) earth fault element (%of Sec To be mentioned
CT Rating)
78.5 Range of timing settings at 10 Sec To be mentioned
time CT rating
78.6 Burden of relay at 10 time CT VA To be mentioned
rating
78.7 Percentage of current setting % To be mentioned
at which relay will reset
78.8 Reset time after removal of
10 time CT rated current for
:
a) Phase element (100%) Sec To be mentioned
b) E/F element (40%) Sec To be mentioned
C. 11kV Outgoing Feeder Cubicles
79.0 Over Current and Earth Fault Protection with IDMT & instantaneous features
79.1 Manufacture's name & country - Siemens(Germany/
of relay Switzerland)/ABB
(Switzerland/Swede
n/Finland) Schneider
(UK/France), Alstom
(UK/France)
79.2 Manufacture's model no. - To be mentioned
79.3 Type of relay - Numerical
programmable with
all necessary
features
79.4 Range of current setting:
a) Phase element (% of CT Sec To be mentioned
Rating)
b) earth fault element (%of Sec To be mentioned
CT Rating)
79.5 Range of timing settings at 10 Sec To be mentioned
time CT rating
79.6 Burden of relay at 10 time CT VA To be mentioned
rating
79.7 Percentage of current setting % To be mentioned
at which relay will reset
79.8 Reset time after removal of 10 time CT rated current for :
a) Phase element (100%) Sec To be mentioned
b) E/F element (40%) Sec To be mentioned
Metering and indication for 33/11kV, 10/13.33MVA Transformer 11kV Incoming and 11kV
outgoing Feeder
80.0 kWh Meter
80.1 Manufacture's name & country - Siemens(Germany/
Switzerland)/ABB
(Switzerland)/AEG
(Germany)/Schlumb
erger
(USA)/Elster(Roman
ia)
80.2 Manufacture's model no. - To be mentioned
80.3 Type of Meter - Numerical
programmable

58
Sl. No. Description Unit Requirement Manufacturer’s
Guaranteed Data
Multifunction
80.4 Class of Accuracy - 0.2
81.0 Indication Volt Meters &
Ammeters
81.1 Manufacture's name & country - To be mentioned
81.2 Manufacture's model no. - To be mentioned
81.3 Type of Meter - Analogue
81.4 Class of Accuracy - To be mentioned

59
09.3 11KV INDOOR TYPE VACUUM CIRCUIT BREAKER (FEEDER BREAKER)

Sl. No. Description Unit Requirement Manufacturer’s


Guaranteed Data
1 Manufacturer’s Name & - To be mentioned
Country of Origin
2 Manufacturer’s Model No. - To be mentioned
3 System nominal voltage kV 11
4 Maximum system voltage kV 12
5 Rated frequency Hz 50
6 Rated normal current:
 Incoming for 10/13.33 A 1250
MVA Transformer
 Outgoing Feeder A 630
7 No. of Phase Nos. 3
8 No. of breaks per phase Nos To be mentioned
9 Interrupting medium - Vacuum
10 Manufacturer’s name and - To be mentioned
country of origin of Vacuum
Interrupter
11 Manufacturer’s model no. of - To be mentioned
vacuum interrupter
12 Power frequency withstand kV 28
voltage
13 Lightning impulse withstand kV 75
voltage on 1.2/50 µs wave
14 Emergency overload rating of - To be mentioned
normal at 20C ambient
15 Duration in any 24 hrs. period - To be mentioned
16 Busbar scheme No. Single
17 Number of busbar Nos. 3
18 Temperature rise of busbar at C To be mentioned
rated current
19 Material of busbar - Copper
2
20 Cross-section of busbar mm To be mentioned
21 Rated normal current of A 1250
busbar for 10/13.33 MVA S/S
22 Busbar insulation material - To be mentioned
23 Are floor plates or rails - To be mentioned
included?
24 Overall dimension of each circuit breaker unit:
 Incomer:
-Height mm To be mentioned
-Width mm To be mentioned
-Depth mm To be mentioned
 Feeder:
-Height mm To be mentioned
-Width mm To be mentioned
-Depth mm To be mentioned
 Bus coupler:
-Height mm To be mentioned
-Width mm To be mentioned
-Depth mm To be mentioned
25 Width necessary for breaker
withdrawal
26 Rated short time withstand kA 25
current (Rated short circuit

60
Sl. No. Description Unit Requirement Manufacturer’s
Guaranteed Data
breaking current) for 3 Sec.
27 Rated Peak withstand current kA 62.5
(Rated short circuit making
current)
28 Breaking Capacity:
 Symmetrical rms kA 25
 Asymmetrical mis kA 25
29 Rated duration of short circuit Sec. To be mentioned
30 Degrees of protection by IP To be mentioned
enclose
31 First pole to clear factor - To be mentioned
32 Rated transient recovery kVp To be mentioned
voltage at 100% rated short
circuit breaking current
33 Rated line charging breaking A To be mentioned
current
34 Rated cable charging breaking A To be mentioned
current
35 Rated out of phase breaking A To be mentioned
current
36 Is circuit breaker re-strike - Yes
free?
37 No. of tripping coil Nos. 2
38 Trip coil current A To be mentioned
39 Trip coil voltage VDC 110
40 Is circuit breaker trip free? - Yes
41 Type of main contact - To be mentioned
42 Material of contact surface - To be mentioned
43 Contact resistance µ To be mentioned
44 Does magnetic effect of load - To be mentioned
current increase contract?
45 Length of each break/phase mm To be mentioned
46 Length of stroke mm To be mentioned
47 Weight of circuit breaker Kg To be mentioned
complete without operating
mechanism and cubicles
48 Weight of circuit breaker Kg To be mentioned
complete with PCM Cubicles
as in service
49 Maximum shock load imposed N To be mentioned
on floor or foundation when
opening under fault condition
(State compression or tension)
OPERATING:
50 Operating Sequence To be mentioned
51  Opening time without ms To be mentioned
current at 100% of rated
breaking current
 Braking time Cycle To be mentioned
 Closing time ms To be mentioned
52 Maximum arc duration of any ms at To be mentioned
duty cycle as per latest …..%
revision of relevant IEC
53 Current at which maximum arc A To be mentioned
duration occurs (critical
current)

61
Sl. No. Description Unit Requirement Manufacturer’s
Guaranteed Data
54 Make time ms To be mentioned
55 Minimum time for arc ms To be mentioned
extinction remake when
adapted for auto closing
56 Time form closing of control of ms To be mentioned
switch to completion of closing
stroke during fault making
57 Manufacturer’s Name & - To be mentioned
Country of Origin of vacuum
interrupter
58 Manufacturer’s Model No. of - To be mentioned
vacuum interrupter
59 Pressure in vacuum tube bar To be mentioned
60 Guaranteed no. of vacuum Nos. To be mentioned
interrupter
61 In normal condition at rated Nos. To be mentioned
current switching
62 In short circuit condition i.e. at Nos. ≥100
the short circuit current
switching
CONSTRUCTION FEATURE:
63 Is an external series break - To be mentioned
incorporated in the breaker?
64 Is any device used to limit - To be mentioned
transient recovery voltage?
65 Method of closing - To be mentioned
66 Method of tripping To be mentioned
67 Minimum clearance in air:
 Between phase mm To be mentioned
 Phase to earth mm To be mentioned
68 Material of tank or chamber - To be mentioned
69 Material of moving contact - To be mentioned
tension rod
70 Period of time equipment has Years To be mentioned
been in commercial operation
71 Is removable draw-out VCB - To be mentioned
mounted on the lower part of
the panel i.e. on floor?
72 All meters, protective relays, - To be mentioned
signaling etc. mounted on the
upper part of the panel
73 Rated voltage of spring Vac To be mentioned
winding motor for closing
74 Materials of all current carrying - To be mentioned
parts of VCB
75 Name of relevant IEC - To be mentioned
standard to be followed in
Design, Manufacture, Testing
and Performance
PROTECTION
A. 33/11kV, 10/13.33MVA, 11kV Transformer Incoming Cubicles
76.0 Over current and earth fault protection with IDMT & instantaneous features
76.1 Manufacture's name & country - Siemens(Germany/
of relay Switzerland)/ABB
(Switzerland/Swede
n/Finland) Schneider
(UK/France), Alstom

62
Sl. No. Description Unit Requirement Manufacturer’s
Guaranteed Data
(UK/France)
76.2 Manufacture's model no. - To be mentioned
76.3 Type of relay - Numerical
programmable with
all necessary
features
76.4 Range of timing settings at 10 Sec. To be mentioned
time CT rating
76.5 Burden of relay at 10 time CT VA To be mentioned
rating

76.6 Percentage of current setting % To be mentioned


at which relay will reset

76.7 Reset time after removal of 10


time CT rated current for :
a) Phase element (100%) Sec To be mentioned
b) E/F element (40%) Sec To be mentioned
77.0 Standard Earth Fault Protection
77.1 Manufacture's name & country - Siemens(Germany/
Switzerland)/ABB
(Switzerland/Swede
n/Finland) Schneider
(UK/France), Alstom
(UK/France)
77.2 Manufacture's model no. - To be mentioned
77.3 Type of relay - Numerical
programmable with
all necessary
features
77.4 Range of current setting:
a) Phase element (% of CT Sec To be mentioned
Rating)
b) earth fault element (%of Sec To be mentioned
CT Rating)
77.5 Range of timing settings at 10 Sec To be mentioned
time CT rating
77.6 Burden of relay at 10 time CT VA To be mentioned
rating
77.7 Percentage of current setting % To be mentioned
at which relay will reset
77.8 Reset time after removal of 10
time CT rated current for :
a) Phase element (100%) Sec To be mentioned
b) E/F element (40%) Sec To be mentioned
B. 11kV Bus Coupler Cubicles:
78.0 Over Current and Earth Fault Protection with IDMT & instantaneous features

78.1 Manufacture's name & country - Siemens(Germany/


of relay Switzerland)/ABB
(Switzerland/Swede
n/Finland) Schneider
(UK/France), Alstom
(UK/France)
78.2 Manufacture's model no. - To be mentioned

78.3 Type of relay - Numerical

63
Sl. No. Description Unit Requirement Manufacturer’s
Guaranteed Data
programmable with
all necessary
features
78.4 Range of current setting:

a) Phase element (% of CT Sec To be mentioned


Rating)
b) earth fault element (%of Sec To be mentioned
CT Rating)
78.5 Range of timing settings at 10 Sec To be mentioned
time CT rating
78.6 Burden of relay at 10 time CT VA To be mentioned
rating

78.7 Percentage of current setting % To be mentioned


at which relay will reset

78.8 Reset time after removal of


10 time CT rated current for
:
a) Phase element (100%) Sec To be mentioned
b) E/F element (40%) Sec To be mentioned
C. 11kV Outgoing Feeder Cubicles
79.0 Over Current and Earth Fault Protection with IDMT & instantaneous features
79.1 Manufacture's name & country - Siemens(Germany/
of relay Switzerland)/ABB
(Switzerland/Swede
n/Finland) Schneider
(UK/France), Alstom
(UK/France)
79.2 Manufacture's model no. - To be mentioned
79.3 Type of relay - Numerical
programmable with
all necessary
features
79.4 Range of current setting:
a) Phase element (% of CT Sec To be mentioned
Rating)
b) earth fault element (%of Sec To be mentioned
CT Rating)
79.5 Range of timing settings at 10 Sec To be mentioned
time CT rating
79.6 Burden of relay at 10 time CT VA To be mentioned
rating
79.7 Percentage of current setting % To be mentioned
at which relay will reset
79.8 Reset time after removal of 10 time CT rated current for :
a) Phase element (100%) Sec To be mentioned
b) E/F element (40%) Sec To be mentioned
Metering and indication for 33/11kV, 10/13.33MVA Transformer 11kV Incoming and 11kV
outgoing Feeder
80.0 kWh Meter
80.1 Manufacture's name & country - Siemens(Germany/
Switzerland)/ABB
(Switzerland)/AEG
(Germany)/Schlumb
erger

64
Sl. No. Description Unit Requirement Manufacturer’s
Guaranteed Data
(USA)/Elster(USA)
80.2 Manufacture's model no. - To be mentioned
80.3 Type of Meter - Numerical
programmable
Multifunction
80.4 Class of Accuracy - 0.2
81.0 Indication Volt Meters &
Ammeters
81.1 Manufacture's name & country - To be mentioned
81.2 Manufacture's model no. - To be mentioned
81.3 Type of Meter - Analogue
81.4 Class of Accuracy - To be mentioned

65
10. SHIELD WIRES, EARTHING GRID AND EARTHING ELECTRODE

A SHIELD WIRES
Sl. Description Unit Requirement Manufacturer’s
No. Guaranteed Data
1 Manufacturer To be mentioned
2 Conductor material High strength steel
3 Grade of steel PSI 60000
4 Nos. of strand Nos 7
5 Diameter of each strand mm 3.25
6 Overall diameter mm 9.80
7 Nominal cross section mm2 35
8 Weight per 1000 meter length kg 460
9 Maximum rated current (3 sec) A To be mentioned
10 Maximum working tension of main kg/m2 To be mentioned
connection
11 Resistance of conductors per 1000 Ohms To be mentioned
meters at 20ºC
12 Rated ultimate tensile strength kg/m2 4900
13 Maximum permissible span length m To be mentioned
14 Maximum sag under own weight of mm To be mentioned
maximum span
15 Co-efficient of linear expansion cm/ºC To be mentioned
16 Class of zinc coating class – A
17 Galvanization As per BS-729
B EARTHING GRID
1 Manufacturer To be mentioned
2 Material Copper
3 Overall diameter mm To be mentioned
4 Nominal cross section
A) interconnecting the earth electrodes mm2 To be mentioned
B) Connecting equipment to mesh mm2 To be mentioned
5 Area of each earthing grid mxm To be mentioned
6 Depth of bedding of conductor mm To be mentioned
7 Maximum earth fault current for 3 sec kA 31.5
8 Resistance of conductors per 1000 Ohms To be mentioned
meters at 20ºC
C. EARTHING ELECTRODES
1 Manufacturer To be mentioned
2 Material Copper
3 Dimentions
a) Diameter To be mentioned
b) Length To be mentioned
4 Number of electrodes per group To be mentioned
5 Number of earthing points To be mentioned
6 Caculated resistance of combined earth Ohm Less than 0.5
grid and points

66
11. BATTERIY AND CHARGER CUBICLE

Sl. Description Unit Requirement Manufacturer’s


No. Guaranteed Data
A. BATTERY
1 Manufacturer To be mentioned
2 Model no To be mentioned
3 Electrolyte Nickel Cadmium
Alkaline
4 Installation Indoor
5 Operating voltage V DC 110
6 Continuous Discharge Current at rate of Amp 10
10 hour & Final Cell Voltage 1.1 Volt.
7 Short Time Discharge Current at rate of Amp 50
2 hour & Final Cell Voltage 1.1 Volt.
8 Charging Voltage (Maximum) Volt 1.54-1.69 Per Cell
9 Normal float charge rate A To be mentioned
10 Maximum boost charge rate A To be mentioned
11 Voltage per cell V/per 1.2
cell
12 Capacity at 5 hour rate Ah 250
13 Number of cells Nos 92
14 Float voltage per cell V per 1.4-1.42
cell
Discharge voltage v per cell 1.3-1.5
15 Battery voltage at end of the duty cycle V 1.1V per cell
16 Nominal charging rate A 40
17 Maximum charging rate A 40
18 Ampere-hour efficiency at ten hour rate % To be mentioned
19 Ampere-hour efficiency at one hour % To be mentioned
rate
20 Dimensions of cells mm To be mentioned
22 Weight of cell complete with kg To be mentioned
electrolyte
23 Internal resistance per cell when fully ohms To be mentioned
charged
24 Material of battery case To be mentioned
25 Standard IEC 623
B. CHARGER
1 Manufacturer To be mentioned
2 Model no To be mentioned
3 Rectifier Type Thyristor
4 AC input voltage V 415V15%
5 Input a.c frequency HZ 505%
6 DC output voltage
a) Normal Charge V DC 11010%
b) Float Charge V DC 1.42 for11015%
c) Boost Charge V DC 1.53 volt per cell
7 Output current (continuous) A 50
8 Rated Battery Current A To be mentioned
9 Efficiency % To be mentioned
10 Ripple Voltage % To be mentioned
11 Type of AVR Static
12 Standard % IEC-146
C CHARGER CUBCLE COMPLETE
1 Manufacturer To be mentioned
2 Overall dimensions To be mentioned
3 Total weight To be mentioned

67
12. LV AC / DC DISTRIBUTION PANEL

Sl. Description Unit Requirement Manufacturer’s


No. Guaranteed Data
A. AC DISTRIBUTION PANEL
1 Manufacturer To be mentioned
2 Model number To be mentioned
3 Bus bar rating Amps 400
4 Fault Rating for 1 sec. KA 15
5 Voltage Volts 400
6 Incoming breaker rating A 400
7 Thickness of sheet steel (encloser) mm To be mentioned
8 Number and rating of circuits Nos./A To be mentioned
9 Overall dimensions mmxmm To be mentioned
xmm
10 Total weight Kg To be mentioned
11 MCCB
a) Manufacturr To be mentioned
b) Model number To be mentioned
c) Rated voltage V To be mentioned
d) Rated current A To be mentioned
B. DC DISTRIBUTION PANEL
1 Manufacturer To be mentioned
2 Model number
3 Bus bar rating Amps 40
4 Fault Rating for 1 sec KA 6
5 Voltage Volts 400
6 Incoming breaker rating A 400
7 Thickness of sheet steel (encloser) mm To be mentioned
8 Number and rating of circuits Nos./A To be mentioned
9 Overall dimensions mmxmm To be mentioned
xmm
10 Total weight Kg To be mentioned
11 MCCB
a) Manufacturr To be mentioned
b) Model number To be mentioned
c) Rated voltage V To be mentioned
d) Rated current A To be mentioned

68
13. 33KV CONTROL AND ENERGY METERING PANEL

Sl. Description Unit Requirement Manufacturer’s


No. Guaranteed Data
A. 33KV CONTROL PANEL
1 Manufacturer To be mentioned
2 Model number To be mentioned
3 Overall dimensions mm To be mentioned
4 Weight of panel Kg To be mentioned
A1. PROTECTION
A.1.1 IDMT OVER CURRENT &
EARTH FAULT RELAY
1 Manufacturer Siemens (Germany)/
Alstom (UK/France)/
ABB (Switzerland/
Sweden
2 Model number To be mentioned
3 Type of relay Numerical
Programmable
4 Range of current setting

a) Phase element % of CT To be mentioned


rating
b) Earth fault element % of CT To be mentioned
rating
5 Range of timing settings at 10 time Sec To be mentioned
CT rating
6 Burden of relay at 10 time CT rating VA To be mentioned
7 Percentage of current setting at % To be mentioned
which relay will reset
8 Reset time after removal of 10 times
CT rated current for:
a) Phase element (100%) Sec To be mentioned
b) E/F element (40%) Sec To be mentioned
A2. METERING AND INDICATION
A.2.1 KWH METER Separate Panel for
Energy Metering
1 Manufacturer Siemens(Germany/Sw
itzerland)/Alstom,(UK
)/ABB(Switzerland)/A
EG(Germany)/Schlum
berger (USA)
2 Model number To be mentioned
3 Type of Meter Numerical
Programmable
multifunction
4 Number of KWH Meters 2 with provision of 4
meters in a separate
metering panel

5 Class of accuracy 0.2


A2.2 INDICATION METERS (VOLT,
AMPERE, KW, KVAR &
POWER FACTOR)
1 Manufacturer Siemens(Germany/Sw
itzerland)/Alstom,(UK
)/ABB(Switzerland)/A
EG(Germany)/Schlum

69
Sl. Description Unit Requirement Manufacturer’s
No. Guaranteed Data
berger(USA)
2 Model number To be mentioned
3 Type of Meter Digital/Analog
4 Class of accuracy To be mentioned

70
14. STEEL STRUCTURE

Sl. Description Unit Requirement Manufacturer’s


No. Guaranteed Data
1 Manufacturer - To be mentioned
2 Maximum ratio of unsupported length of steel
compression to their least redius of gyration:
a) Main members mm 120
b) Bracing's mm 200
c) Redundant mm 250
3 Steel Grade Mild Steel
a) Elastic limit stress in tension members Kg/ To be mentioned
mm2
b) Ultimate stress in compression members Kg/ To be mentioned
(expressed as function L/R) mm2
4 Steel Grade HTGH Tension Steel
a) Elastic limit stress in tension members Kg/ To be mentioned
mm2
b) Ultimate stress in compression members Kg/ To be mentioned
(expressed as function L/R) mm2
5 Minimum size of member mm 45 x 45 x 6
6 Weight of each Column Kg To be mentioned
7 Weight of each Girder Kg To be mentioned
8 Total weight Kg To be mentioned
9 Minimum member thickness mm 6
Main member mm 5
Other breching member mm 5
Bolt diameter mm 16
10 Galvanizing thickness mm 85

71
15. Control cable
PVC insulated multi core control cable Laid up beded with PVC or tap. Flat /
round wire armoring with helical steel taping and PVC sheathed, rated voltage
600/1000, continuous permissible voltage 720/1200 volts (VDE 0271/3.69 BDS 901:
85) (NYRGby) suitable for use in indoors, outdoors, underground and in water for
continuous permissible service voltage of 720/1200 volts. Maximum resistance 4.73
ohm/km at 35°C.

a) Guaranteed Technical Particulars for 4C4 mm2 XLPE Insulated and PE Sheathed
Copper Cable
(To be filled u by the Manufacturer in Manufacturer’s Letterhead Pad with
appropriated data)

Sl Description Unit Purchaser’s Manufacturer’s


No. Requirement Particulars
1 Name of the Item 4c4 mm2LPE
Insulated and PE
Sheathed Copper Cable
with Armouring
2 Name of the Manufacturer Shall be mentioned
3 Address of the Manufacturer Shall be mentioned
4 Standard Performance Design
and Testing shall be in
accordance to the BS,
IEC, BDS or equivalent
International Standards.
5 Cable Size mm2 4C4 rm
6 Material XLPE Insulated and PE
Sheathed Copper Cable
with Armouring
7 Numbers & Diameter of Copper Wires mm 7/0.85
8 Numbers & Diameter of Steel Wires mm 24/1.4
9 Nominal size of Steel Tape mm 80.3
10 Maximum resistance at 30 deg.c Ω/Km 4.56
11 Nominal thickness of insulation mm 0.8 (min)
12 Nominal thickness of sheath mm 1.8 (min)
13 Colour of sheath Black
14 Colour of Core Red, Yellow, Blue,
Black
15 Approximate outer diameter mm 19
16 Approximate weight Kg/Km 760
17 Drum wound length m 1000
18 Net Weight Kg Shall be mentioned
19 Gross weight Kg Shall be mentioned
20 Treated Wooden Drum Standard AWPA C1-82,
C2-83, c16-82,
P5-83.

72
b) Guaranteed Technical Particulars for 4C6 mm2 XLPE Insulated and PE Sheathed
Copper Cable
(To be filled u by the Manufacturer in Manufacturer’s Letterhead Pad with
appropriated data)
Sl Description Unit Purchaser’s Manufacturer’s
No. Requirement Particulars
1 Name of the Item To be mentioned
2 Name of the Manufacturer To be mentioned
3 Address of the Manufacturer To be mentioned
4 Standard To be mentioned
5 Cable Size mm2 4C6 rm
6 Material To be mentioned
7 Numbers & Diameter of Copper Wires mm To be mentioned
8 Numbers & Diameter of Steel Wires mm To be mentioned
9 Nominal size of Steel Tape mm To be mentioned
10 Maximum resistance at 30 deg.c Ω/Km To be mentioned
11 Nominal thickness of insulation mm To be mentioned
12 Nominal thickness of sheath mm To be mentioned
13 Colour of sheath To be mentioned
14 Colour of Core To be mentioned
15 Approximate outer diameter mm To be mentioned
16 Approximate weight Kg/Km To be mentioned
17 Drum wound length m To be mentioned
18 Net Weight Kg To be mentioned
19 Gross weight Kg To be mentioned
20 Treated Wooden Drum Standard To be mentioned

c) Guaranteed Technical Particulars for 2C4 mm2 XLPE Insulated and PE Sheathed
Copper Cable
(To be filled u by the Manufacturer in Manufacturer’s Letterhead Pad with
appropriated data)
Sl Description Unit Purchaser’s Manufacturer’s
No. Requirement Particulars
1 Name of the Item To be mentioned
2 Name of the Manufacturer To be mentioned
3 Address of the Manufacturer To be mentioned
4 Standard To be mentioned
5 Cable Size mm2 2C4 rm
6 Material To be mentioned
7 Numbers & Diameter of Copper Wires mm To be mentioned
8 Numbers & Diameter of Steel Wires mm To be mentioned
9 Nominal size of Steel Tape mm To be mentioned
10 Maximum resistance at 30 deg.c Ω/Km To be mentioned
11 Nominal thickness of insulation mm To be mentioned
12 Nominal thickness of sheath mm To be mentioned
13 Colour of sheath To be mentioned
14 Colour of Core To be mentioned
15 Approximate outer diameter mm To be mentioned
16 Approximate weight Kg/Km To be mentioned
17 Drum wound length m To be mentioned
18 Net Weight Kg To be mentioned
19 Gross weight Kg To be mentioned
20 Treated Wooden Drum Standard To be mentioned

73
d) Guaranteed Technical Particulars for 2C6 mm2 XLPE Insulated and PE Sheathed
Copper Cable
(To be filled u by the Manufacturer in Manufacturer’s Letterhead Pad with
appropriated data)
Sl Description Unit Purchaser’s Manufacturer’s
No. Requirement Particulars
1 Name of the Item To be mentioned
2 Name of the Manufacturer To be mentioned
3 Address of the Manufacturer To be mentioned
4 Standard To be mentioned
5 Cable Size mm2 2C6 rm
6 Material To be mentioned
7 Numbers & Diameter of Copper Wires mm To be mentioned
8 Numbers & Diameter of Steel Wires mm To be mentioned
9 Nominal size of Steel Tape mm To be mentioned
10 Maximum resistance at 30 deg.c Ω/Km To be mentioned
11 Nominal thickness of insulation mm To be mentioned
12 Nominal thickness of sheath mm To be mentioned
13 Colour of sheath To be mentioned
14 Colour of Core To be mentioned
15 Approximate outer diameter mm To be mentioned
16 Approximate weight Kg/Km To be mentioned
17 Drum wound length m To be mentioned
18 Net Weight Kg To be mentioned
19 Gross weight Kg To be mentioned
20 Treated Wooden Drum Standard To be mentioned

e) Guaranteed Technical Particulars for 19C4 mm2 XLPE Insulated and PE


Sheathed Copper Cable
(To be filled u by the Manufacturer in Manufacturer’s Letterhead Pad with
appropriated data)
Sl Description Unit Purchaser’s Manufacturer’s
No. Requirement Particulars
1 Name of the Item To be mentioned
2 Name of the Manufacturer To be mentioned
3 Address of the Manufacturer To be mentioned
4 Standard To be mentioned
5 Cable Size mm2 19C4 rm
6 Material To be mentioned
7 Numbers & Diameter of Copper Wires mm To be mentioned
8 Numbers & Diameter of Steel Wires mm To be mentioned
9 Nominal size of Steel Tape mm To be mentioned
10 Maximum resistance at 30 deg.c Ω/Km To be mentioned
11 Nominal thickness of insulation mm To be mentioned
12 Nominal thickness of sheath mm To be mentioned
13 Colour of sheath To be mentioned
14 Colour of Core To be mentioned
15 Approximate outer diameter mm To be mentioned
16 Approximate weight Kg/Km To be mentioned
17 Drum wound length m To be mentioned
18 Net Weight Kg To be mentioned
19 Gross weight Kg To be mentioned
20 Treated Wooden Drum Standard To be mentioned
16. POWER CABLES

74
16.1. 33 KV POWER CABLES (U/G)

Guaranteed Technical Data Schedule of 33KV, 1-Core × 500 Sq.mm U/G XLPE Copper
Cable

SL Description Unit Required Manufacturer’s


No. Specification Particulars
1 Name and address of the To be mentioned
Manufacturer
2 Type/Model of the offered cable To be mentioned
3 Nominal system voltage KV 33
4 Rated voltage of cable KV 18/30(36)

5 Process of manufacturing VCV/CCV


6 Number of core and cross sectional Sq.mm 1×500
area of conductor cores
7 Conductor material Copper
8 Minimum no of strand No. 53
9 Diameter of each strand mm To be mentioned
10 Shape of conductor Compacted Circular
11 Type of conductor screen Semi-conducting
12 Thickness of semi conducting mm 0.6
screen
13 Avg. thickness of insulation mm 8.0
14 Process of curing Dry process
15 Material of insulation Cross Linked
Polyethylene (XLPE)
16 Type of non metallic insulating Semi-conducting
screen
17 Thickness of semi conducting mm 1.0
insulation screen
18 Number and diameter of copper No./mm Based on design
screen strands calculation
19 Composition of filler PVC
20 Composition of bedding Extruded PVC
21 Thickness of bedding mm Based on design
calculation
22 Number and diameter of armour No./mm As per IEC 60502
wire
23 Avg. thickness of MDPE over mm Based on design
sheath calculation
24 Nominal diameter of complete mm Based on design
cable calculation
25 Nominal weight per meter of Kg/m Based on design
complete cable calculation
26 Minimum radius of bend round mm Based on design
which cable can be laid calculation
27 Max. D.C resistance of conductor Ohm/m Based on design
per meter at 20̊ C calculation
28 Max. A.C resistance of conductor Ohm/m Based on design
per meter at MAXIMUM calculation
CONDUCTOR TEMPARATURE
29 Star resistance per meter of cable at Ohm/m Based on design
50Hz calculation
30 Star capacitance per per meter of pF/m Based on design
cable at 50Hz calculation

75
SL Description Unit Required Manufacturer’s
No. Specification Particulars
31 Charging current per conductor per mA Based on design
meter at 18000/30000 Volts , 50Hz calculation
32 Maximum current carrying A Based on design
capacity of conductor in ground calculation
33 Maximum conductor temperature ̊C Based on design
under continuous loading calculation
34 Short circuit withstand capacity nof KA Min. 25
the cable for 1 sec. duration
35 conductor temperature at the end of ̊C ≤250
short circuit
36 Earth fault withstand capacity for 1 KA Min. 25
sec.
37 Screen short circuit withstand KA Min. 25
capacity

38 Armour short circuit capacity KA Based on design


calculation
39 Cable resistance, reactance

a) for positive sequence Ohm/m Based on design


calculation
b) negative sequence Ohm/m Based on design
calculation
c) Zero sequence Ohm/m Based on design
calculation

76
16.2. 11 KV POWER CABLES (U/G)

16.2.1: Guaranteed Technical Data Schedule of 11KV, 1-Core × 500 Sq.mm U/G
XLPE
Copper Cable

SL Description Unit Required Supplier’s/


No. Specification Manufacturer’s
Particulars
1 Name and address of the To be mentioned
Manufacturer
2 Type/Model of the offered To be mentioned
cable
3 Nominal system voltage KV 11
4 Rated voltage of cable KV 6/10(12)

5 Process of manufacturing VCV/CCV


6 Number of core and cross Sq.mm 1×500
sectional area of conductor
cores
7 Conductor material Copper
8 Shape of conductor Round
9 Type of conductor screen Semi-conducting
10 Thickness of semi conducting mm 0.6
screen
11 Avg. thickness of insulation mm 3.4
12 Process of curing Dry process
13 Material of insulation Cross Linked
Polyethylene
(XLPE)
14 Type of non metallic Semi-conducting
insulating screen
15 Thickness of semi conducting mm 1.0
insulation screen
16 Number and diameter of No./mm Based on design
copper screen strands calculation
17 Composition of filler MDPE
18 Composition of bedding Extruded PVC
19 Thickness of bedding mm Based on design
calculation
20 Number and diameter of No./mm As per IEC 60502
armour wire
21 Avg. thickness of MDPE over mm Based on design
sheath calculation
22 Nominal diameter of complete mm Based on design
cable calculation
23 Nominal weight per meter of Kg/m Based on design
complete cable calculation
24 Minimum radius of bend mm 12×D
round which cable can be laid
25 Max. D.C resistance of Ohm/m Based on design
conductor per meter at 20̊ C calculation
26 Max. A.C resistance of Ohm/m Based on design
conductor per meter at calculation
MAXIMUM CONDUCTOR
TEMPARATURE
27 Star resistance per meter of Ohm/m Based on design
cable at 50Hz calculation

77
SL Description Unit Required Supplier’s/
No. Specification Manufacturer’s
Particulars
28 Star capacitance per per meter pF/m Based on design
of cable at 50Hz calculation
29 Charging current per mA Based on design
conductor per meter at calculation
18000/30000 Volts , 50Hz
30 Maximum current carrying A 775
capacity of conductor in
ground
31 Maximum conductor ̊C 90
temperature under continuous
loading
32 Short circuit withstand KA Min. 20
capacity nof the cable for 1
sec. duration
33 conductor temperature at the ̊C ≤250
end of short circuit
34 Earth fault withstand capacity KA Min.10
for 1 sec.
35 Screen short circuit withstand KA Min. 10
capacity
36 Armour short circuit capacity KA Based on design
calculation
37 Cable resistance, reactance

a) for positive sequence Ohm/m Based on design


calculation
b) negative sequence Ohm/m Based on design
calculation
c) Zero sequence Ohm/m Based on design
calculation

78
16.2.2: Guaranteed Technical Data Schedule of 11KV, 1-Core × 185 Sq.mm U/G
XLPE
Copper Cable
SL Description Unit Required Supplier’s/
No. Specification Manufacturer’s
Particulars
1 Name and address of the To be mentioned
Manufacturer
2 Type/Model of the offered To be mentioned
cable
3 Nominal system voltage KV To be mentioned
4 Rated voltage of cable KV To be mentioned

5 Process of manufacturing To be mentioned


6 Number of core and cross Sq.mm 1×185
sectional area of conductor
cores
7 Conductor material Copper
8 Shape of conductor Round
9 Type of conductor screen To be mentioned
10 Thickness of semi conducting mm To be mentioned
screen
11 Avg. thickness of insulation mm To be mentioned
12 Process of curing To be mentioned
13 Material of insulation To be mentioned
14 Type of non metallic To be mentioned
insulating screen
15 Thickness of semi conducting mm To be mentioned
insulation screen
16 Number and diameter of No./mm Based on design
copper screen strands calculation
17 Composition of filler To be mentioned
18 Composition of bedding To be mentioned
19 Thickness of bedding mm Based on design
calculation
20 Number and diameter of No./mm To be mentioned
armour wire
21 Avg. thickness of MDPE over mm Based on design
sheath calculation
22 Nominal diameter of complete mm Based on design
cable calculation
23 Nominal weight per meter of Kg/m Based on design
complete cable calculation
24 Minimum radius of bend mm To be mentioned
round which cable can be laid
25 Max. D.C resistance of Ohm/m Based on design
conductor per meter at 20̊ C calculation
26 Max. A.C resistance of Ohm/m Based on design
conductor per meter at calculation
MAXIMUM CONDUCTOR
TEMPARATURE
27 Star resistance per meter of Ohm/m Based on design
cable at 50Hz calculation
28 Star capacitance per per meter pF/m Based on design
of cable at 50Hz calculation
29 Charging current per mA Based on design
conductor per meter at calculation

79
SL Description Unit Required Supplier’s/
No. Specification Manufacturer’s
Particulars
18000/30000 Volts , 50Hz
30 Maximum current carrying A To be mentioned
capacity of conductor in
ground
31 Maximum conductor ̊C To be mentioned
temperature under continuous
loading
32 Short circuit withstand KA To be mentioned
capacity nof the cable for 1
sec. duration
33 conductor temperature at the ̊C To be mentioned
end of short circuit
34 Earth fault withstand capacity KA To be mentioned
for 1 sec.
35 Screen short circuit withstand KA To be mentioned
capacity
36 Armour short circuit capacity KA Based on design
calculation
37 Cable resistance, reactance

a) for positive sequence Ohm/m Based on design


calculation
b) negative sequence Ohm/m Based on design
calculation
c) Zero sequence Ohm/m Based on design
calculation

Tenderer shall provide all necessary information which deem to be necessary to complete the work in all
respect

Seal and Signature of


the Tenderer

80
SCHEDULE F

DEPARTURES FROM SPECIFICATIONS

81
SCHEDULE F

DEPARTURES FROM SPECIFICATIONS

Tenderers are to list all departures from the requirements of the specification in this
schedule. All departures whether they be commercial, financial, technical or of a
contractual nature are to be included and submitted with the Technical Proposal.

Any item that does not have a departure listed in this schedule will be deemed to be in
full accordance with the requirements of the specification.

No other document or detail accompanying the tender will be considered in evaluating


departures. Tenderers are not permitted to offer any alternative to this schedule.

Item Volume Clause Detail of Departure from Specification

82
SCHEDULE G

PROPOSED ALTERNATIVE STANDARDS TO WHICH


EQUIPMENT SHALL BE PROVIDED

83
SCHEDULE G

PROPOSED ALTERNATIVE STANDARDS TO WHICH EQUIPMENT SHALL BE


PROVIDED

The Tenderer shall list below all the alternative engineering and design Standards, which
he proposes to use in his design, manufacture and testing of equipment to be supplied.
Should these standards differ from the specified standard in any respect, the Tenderer
shall detail the differences between the proposed and specified standard.

Compliance with any standard equal or superior to those specified will be considered
acceptable.

In the absence of any listed alternative standard, it is deemed that the standards specified
in the Tender Documents are fully complied with.

84
SCHEDULE H

PROPOSED CONTRACT AND SITE ORGANISATION AND SITE


RESOURCES

85
SCHEDULE H

PROPOSED CONTRACT AND SITE ORGANISATION AND SITE RESOURCES

The Tenderer is required to provide full organization charts of his proposed head office
and site office arrangements. This should include how site subcontractors are to interface
with the contractor’s organization.

The Tenderer shall list in the form of Schedule attached, the key personnel (including
first nominee and the second choice alternate)he will employ at head office and site
office to direct and execute and work for the execution of the Contract together with their
qualifications, positions held and their nationalities. Should specialist sub-designers be
proposed (e.g civil designers) details of these are also to be provided with how this
interface with the contractor’s organization.

Should the Tenderer be proposing to put any restriction on his site managers authority to
carry out the instructions issued by the Employer Representative, full details of these, be
they financial/contractual/technical are to be provided in the tender.

The information provided in the Tender in accordance with the above, will not represent
any limitations on the staff required to perform the works in accordance with the
conditions of Contract. Should the Contractor require utilizing additional staff to those
proposed in order to meet his obligations these are to be provided at no additional cost.
The Contractor shall however have to employ all the expatriate staffs proposed in the
tender as to be employed at site. In case of failure to employ the expatriate staffs at site
as per tender proposal, the Employer may go for termination of the Contract.

In addition the Tenderer is required to provide a schedule of the site resources he intends
to provide, e.g. equipment for haulage, lifting, site power supplies, foundation, erection,
stringing, testing and commissioning. Major items of equipment for construction
purposes, which the Tenderer proposes to import, are to be submitted with the Tender.
The Tenderer shall have to bring the above proposed equipment during construction
otherwise they may be panelized, as per clause of the tender, for any delay due to non-
availability of such equipment at site. The successful Tenderer will be required to submit
detailed schedules of his proposed site testing and commissioning equipment and
experience of his commissioning engineers.

The Tenderer is also required to provide details of his site organization concerning office
locations, storage facilities proposed, both open and covered, site transportation, etc. The
successful Tenderer will be required to provide details of his proposed organizational
procedures for the receipt, inspection and transportation of plant, plus monthly progress
monitoring, invoice submission etc.

The Contractor shall ensure that the cash flow is maintained as forecasted in their price
proposal. In case there is any liquidity problem for which there is any delay in
implementing the project, the Contractor may be panelized as per tender.

86
SCHEDULE H OF KEY PERSONNEL

Position Name Nationality Summary of qualifications,


experience and present
occupation
Head Office Staff:

Site Office Staff:

Signature and Seal of the Tenderer

87
SCHEDULE H OF EQUIPMENT FOR CONSTRUCTION

Name of Equipment Ownership Present Location

Signature and Seal of the Tenderer

88
SCHEDULE I

DRAWINGS AND DOCUMENTS TO BE SUBMITTED


WITH TENDER

89
SCHEDULE I

DRAWINGS AND DOCUMENTS TO BE SUBMITTED WITH


TENDER
FOR 33 KV SWITCHING STATION WORK
The Tenderer shall submit the following drawings/documents with the tender:

1. Typical plan and section drawings of transformer incoming, bus coupler and
outgoing feeders for 33 kV switchyard.
2. Block diagram showing overall dimensions of 33kV switchyard at site.
3. Drawings of circuit breakers, disconnecting switches, current transformers,
voltage transformers, lightning arresters and disc Insulator units showing details
of construction and dimensions.
4. Typical arrangement drawing of control panel cubicles, energy meter panel
cubicle, battery charger cubicle, LVAC and DC distribution boards.
5. Typical block-schematic and logic diagrams of all protection and control
schemes.
6. Lay-out Plan of control panel to be installed in substation control room building.
7. Cross Section Drawing of the head design of the insulator unit.
8. Type test certificate of the following shall be submitted as per relevant IEC/BS
standards.
i) Circuit Breaker (VCB)
(a) Lightning impulse voltage withstand dry test
(b) Temperature rise test
(c) Power frequency withstand test
(d) Short time withstand & Peak withstand current test
(e) Mechanical operation tests
(f) Short Circuit Current making & breaking test
(g) Out of phase making & breaking test

ii) Disconnecting Switch DS/ES)


(a) Lightning Impulse voltage withstand dry test
(b) Power frequency voltage withstand dry test
(c) Short time withstand current test
iii) Current Transformer (CT)
(a) Short time current test
(b) Impulse voltage withstands tests for current transformers for
service in exposed installation.
(c) Power frequency voltage withstand test

90
(d) Temperature rise test
iv) Voltage Transformer (VT)
(a) Temperature rise test
(b) Impulse voltage withstand tests for voltage transformers for
service in exposed installation.
(c) Short circuit test
(d) Short time over voltage test
v) Lightning Arrester (LA)
(a) Lightning impulse voltage withstand test on Arrester Housing
(b) Lightning impulse residual voltage test
(c) Step current impulse residual voltage test
(d) Long duration current impulse withstand test
(e) High Current Impulse withstand test
(f) Pressure relief test
vi) Disc Insulator units
(a) Mechanical failing load test
(b) Impulse voltage puncture test
(c) Power are test
(d) Residual strength test
9. Type test certificates of the above equipment shall be from independent testing
laboratory.
10. Quality Assurance Certificate ISO9001/9002 Certification (or equivalent and
Quality Assurance Program & Typical Quality Plan for the work from the
manufacturers of the following equipment:
i) Circuit breaker
ii) Disconnecting switch
iii) Current transformer
iv) Voltage transformer
v) Lightning arrester
vi) Insulator
vii) Relays

91
DRAWINGS AND DOCUMENTS TO BE SUBMITTED WITH
TENDER
FOR 33 KV LINE AUGMENTATION WORK

1. According to design & drawing, Technical Specification and GTP of all


materials to be used for augmentation of 33 kV existing line.

2. Relevant all Test Report of all materials to be used for augmentation of 33 kV


existing line confirming the Technical Specification and GTP submitted by the
Tenderer.

3. Manufacturer’s Assurance Certificate for supplying line materials in favour of


the Tender.

4. Quality Assurance Certificate ISO9001/9002 Certification (or equivalent and


Quality Assurance Program & Typical Quality Plan for the work from the
manufacturers of the required materials for 33 kV line augmentation work.

5. Brochure/Catalog of manufacturer indicating manufacturing facilities and


available materials.

92
SCHEDULE K

MANUFACTURER’S AUTHORIZATION LETTER

93
SCHEDULE J
Manufacturer’s Authorization Letter
[This letter of authorization should be on the letterhead of the manufacturer and should
be signed by the person with the proper authority to sign documents that are binding on
the manufacturer]
Invitation for Tender No: Date:
Tender Identification No:

To:

(Name and address of The Employer)


WHEREAS, we [name and address of manufacturer] are reputable manufacturers having
factories at [list of places of factories].

Therefore, we do hereby:

1. Authorize [name of Tenderer] to submit a Tender in response to the


invitation for Tenders indicated above, the purpose of which is to
provide the [description of goods], manufactured by us, and to
subsequently sign the Contract for the supply of such Goods; and,

2. Extend our full guarantee and warranty in accordance with GCC Clause
10 with respect to the Goods offered in the Tender.
Signed

In the capacity of:

Duly authorized to sign the authorization for and on


behalf of

[ name of manufacturer]

Date:

94
Section 9

Drawings

95
96
97
98
99
100
101
102
103
104

You might also like