DC4xS/C GENSET CONTROLLER USER MANUAL

DC4xS/C GENSET CONTROLLER


USER MANUAL

DC40S/C

DC42S/C

0
DC4xS/C GENSET CONTROLLER USER MANUAL

Software Version
No. Version Date Note
1 V1.0 2021-02-01 Original release.
Increase the charging coil signal detection
function;
2 V1.1 2022-01-24
Increase public open-circuit output, mains
phase loss setting

Chongqing Mebay Technology Co.,Ltd


Add: No6-2,Building 4, Gangan Rd, Jiangbei District, Chongqing.
Tel:+86-23-6869 3061
Fax:+86-23-6765 8207
Web:http://www.mebay.cn
http://www.cqmb.cn
E_mail:[email protected]

1
DC4xS/C GENSET CONTROLLER USER MANUAL

Symbol Description
Symbol Description

Remind operators to operate correctly, otherwise it may cause


Note the equipment not to work correctly.

It is indicated that potential hazards can damage equipment


Be care without proper precautions.

It is indicated if appropriate preventive measures are not taken,


potentially dangerous situations may result in death, serious
Warning personal injury or significant property losses.

2
DC4xS/C GENSET CONTROLLER USER MANUAL

Warning
1. The installation of this equipment must be carried out by professionals.
2. When installing and operating the controller, please read the entire instruction
manual first.
3. Any maintenance and commissioning of the equipment must be familiar with all the
equipment.
4. Safety standards and precautions in advance, otherwise it may cause personal
injury or damage to related equipment.
5. The engine must have an overspeed protection device independent of the
controller system to avoid casualties or other damage caused by engine out of
control.
6. After the installation of the controller is completed, please verify that all protection
functions are valid.

Be Care
1. Please keep the good connection of the power supply of the controller. Do not
share the connection lines of the positive and negative electrodes of the battery
with the floating charger.
2. During the operation of the engine, do not disconnect the battery, otherwise it may
cause damage to the controller.

3
DC4xS/C GENSET CONTROLLER USER MANUAL

CATALOGUE

1. Summary............................................................................................................................... 5

2. Main Features...................................................................................................................... 5

3. Parameters Display............................................................................................................. 6

4. Protection.............................................................................................................................. 7

5. Parameters........................................................................................................................... 7

6. Overall Dimension and Wiring Diagram........................................................................... 8

7. Installation instruction....................................................................................................... 17

8. Panel and display.............................................................................................................. 18

9. Control and operation instruction.................................................................................... 20

10. Warnings and Shutdown Alarms.................................................................................. 22

11. Parameters setting.......................................................................................................... 30

12. Fault finding......................................................................................................................46

Notes:
1. All rights reserved. No part of this duplication may be reproduced in any material
form (including photocopying or storing in any medium by electronic means or others)
without the written permission of the copyright holder.
2. MEBAY Technology reserves the rights to change the contents of this document
without prior notice.

4
DC4xS/C GENSET CONTROLLER USER MANUAL

1. Summary
This series controller is specialized for Diesel / Gasoline / Gas Genset Start,
Stop, Parameters monitoring, faults-checking as well as data setting.
2.8 inch LCD screen display with brand new UI design is adapted in this
controller that the relative failures can be displayed directly. All the parameters can
be displayed by simulated indicators and words. Besides, LCD screen can display
various faults in the same time that the genset will be stopped once it can’t work
smoothly.
There are Chinese/English interface options, more language can be set
according to user’s request. All the parameters can be configured through the front
face buttons or use programmable interface by RS485 or USB to adjust via PC. It can
be widely applied for all kinds of auto control system of gensets.
2. Main Features
There are eight Models under DC4xS/C series.
DC40S: Used for single machine automation. Start/Stop through remote start
signal.
DC40SR: Based on DC40S, it adds RS485 port.
DC42S: Based on DC40S, it adds Mains monitoring and AMF (Mains/Generator
automatic switching control), especially suitable for the automation system composed
by mains and genset.
DC42SR: Based on DC42S, it adds RS485 port.
DC40C: Used for single machine automation. Start/Stop through remote start
signal. it adds CAN port.
DC40CR:Based on DC40C, it adds RS485 port.
DC42C: Based on DC40C, it adds Mains monitoring and AMF (Mains/Generator
automatic switching control), especially suitable for the automation system composed
by mains and genset.
DC42CR: Based on DC42C, it adds RS485 port.
 Dual core 32bit high performance single chip microcomputer.
 2.8 inch 240 * 128 high-resolution LCD screen, Available in 6 languages, user’s
language set if necessary.
 Indicator and number display through UI surface.
 Acrylic material is adapted to protect the screen.
 Silicone panels;
 USB Port: parameters can be set even without power through USB port to monitor
in real time.
 With RS485 communication port, can achieve “Three Remote” functions via
MODBUS protocol.
 Standard CAN communication port, built-in J1939 protocol, has matched more
than 40 kinds of engines;
 Various kinds of parameters display.
 Input/output function, status can be shown directly.
 Real time clock inside: preset time operate and auto maintenance is available.
Genset working plan can be set as per week or month.

5
DC4xS/C GENSET CONTROLLER USER MANUAL

 Maintenance countdown function, can set maintenance time or date.


 The black box function can save the relevant parameters of the unit when the fault
alarm occurs in real time, and it is convenient to find the cause of the fault.
 Totally 6relay’s output, among which 4 relay output can be self-configurable, each
relay can be set as max 20 functions.
 With 4 switches input, up to 20 functions optional;
 3 sensor simulation input connectors, the oil pressure sensor is compatible with
voltage signal input, and various display units can be configured.
 Battery charging control function,which can protect the battery according to battery
voltage status.
 Sensor can be self-defined by front face button or PC software.
 Adapt to 3P4W,1P2W,2P3W(120V/240V,50/60HZ)
 Various of crank conditions (RPM, Frequency, Oil Pressure) can be chosen.
 Control Protection: Auto Start/Stop of genset, load transfer (ATS control) and
perfect failure display and protection.
 Standard water-proof rubber gasket. The waterproof can reach IP54
 Module design: All the connections are adapted with European connectors so that
installation, connection, repair and replacement can be more easily.
3. Parameters Display
 Engine RPM
 Engine oil pressure
 Engine temperature
 Engine fuel level
 Engine battery voltage
 Charging voltage
 CAN related parameters(C series only)
 Mains Frequency (only for DC42S/C)
 Mains phase voltage L-N (only for DC42S/C)
 Mains phase voltage L-L (only for DC42S/C)
 Generator 3 Phase voltage L-N
 Generator 3 Phase voltage L-L
 Generator 3 phase current A
 Generator Frequency Hz
 Generator Power Factor COS φ
 Generator active power KW
 Generator apparent power KVA
 Generator reactive power KVar
 Real-time load rate %
 Current load rate %
 Average loading rate %
 Current consumption KWH
 Total consumption KWH
 Total Crank times
 Cumulative power on time of controller

6
DC4xS/C GENSET CONTROLLER USER MANUAL

 Current running time


 Total running time
 Maintenance notice
 Switches input status display
 Output status display of relays
 Current date and time;
4. Protection
 Over speed
 Under speed
 Low oil pressure
 High temperature
 Low fuel level
 External emergency alarm
 D+ open
 RPM Lost
 Sensor Open
 Over Frequency
 Under Frequency
 Over voltage
 Under voltage
 Over current
 Non-balance of current
 Over power
 Maintenance expire
 Low water level alarm
 Emergency Stop
 Crank failure
 Battery over voltage
 Battery under voltage
 The charger fails to charge
 Charger charging failure
 Stop Failure
 ECU alarm failure
 ECU communication Failure
5. Parameters
Options Parameters
Working voltage DC8V----36V Continuous
Standby:24V:MAX 2W
Power consumption
Working:24V:MAX5W
1P2W 30VAC-276VAC (ph-N)
AC Voltage Input 2P3W 30VAC-276VAC (ph-N)
3P4W 30VAC-276VAC (ph-N)

7
DC4xS/C GENSET CONTROLLER USER MANUAL

Rotate speed sensor


50-10000Hz
Frequency
MAX Accumulating Time 99999.9Hours(Min Store time:6min)
Fuel Relay Output Max 5Amp DC+VE Supply voltage
Start Relay Output Max 5Amp DC+VE Supply voltage
AUX.OUTPUT 1 Max 1Amp DC+VE Supply voltage
AUX.OUTPUT 2 Max 1Amp DC+VE Supply voltage
AUX.OUTPUT 3 Max 1Amp DC+VE Supply voltage
AUX.OUTPUT 4 Max 1Amp DC+VE Supply voltage
Excitation output DC+VE supply voltage
AUX. Input Available if connecting with Battery -
Working condition -25-65℃
Storage condition -40-85℃
IP54:when waterproof rubber gasket is added
Protection Level
between controller and its panel
Apply AC2.2kV voltage between high voltage terminal
Insulation strength and low voltage terminal; The leakage current is not
more than 3mA within 1min.
Overall dimension 142mm*105mm*45mm
Panel cutout 116mm*90mm
Weight 0.6Kg
6. Overall Dimension and Wiring Diagram
 Overall Dimension:

8
DC4xS/C GENSET CONTROLLER USER MANUAL

 Descriptions of terminal connection

9
DC4xS/C GENSET CONTROLLER USER MANUAL

Cable cross
No. Function Description
sectional area
1 Battery Negative Input B- Controller power supply input B-. 2.5mm2
2 Battery Negative Input B+ Controller power supply input B+. 2.5mm2
3 Fuel Output +VE output, Max 5Amp 1.5mm2
4 Crank Output +VE output, Max 5Amp. 1.5mm2
5 Charging excitation output +VE output, Max 0.9Amp. 1.0mm2
6 Aux. Output 1 +VE output, Max 1Amp. 1.0mm2
7 Aux. Output 2 +VE output, Max 1Amp. 1.0mm2
8 Aux. Output 3 +VE output, Max 1Amp. 1.0mm2
9 Aux. Output 4 +VE output, Max 1Amp. 1.0mm2
10 Sensor common GND Connect the battery negative or outer. 1.0mm2
11 Oil pressure sensor Connect sensor input. 1.0mm2
12 Temperature Sensor Oil pressure sensor compatible with 1.0mm2
13 Fuel level sensor resistance/voltage sensors; 1.0mm2
Connect the power supply of the oil
14 +5V Output pressure sensor with the output voltage 1.0mm2
signal, with a maximum of 50mA.
15 Speed sensor + 1.0mm2
Use a shielded wire to connect the speed
16 Speed sensor - 1.0mm2
sensor.
17 Speed sensor SCR 1.0mm2
15 CAN _H 1.0mm2
A 120 Ω shielded wire and good grounding
16 CAN_ L 1.0mm2
are recommended.
17 CAN _SCR 1.0mm2
18 RS485_B 1.0mm2
A 120 Ω shielded wire and good grounding
19 RS485_A 1.0mm2
are recommended.
20 RS485_SCR 1.0mm2
21 Aux. Input 1 1.0mm2
22 Aux. Input 2 The grounding is valid according to the 1.0mm2
23 Aux. Input 3 function selection switch input. 1.0mm2
24 Aux. Input 4 1.0mm2
Connected to the power generation output R
25 Generator Voltage U 1.0mm2
phase.
Connected to the power generation output S
26 Generator Voltage V 1.0mm2
phase.
Connected to the power generation output T
27 Generator Voltage W 1.0mm2
phase.
Connected to the power generation output N
28 Generator Voltage N2 1.0mm2
phase.

10
DC4xS/C GENSET CONTROLLER USER MANUAL

29 Mains Voltage R Connected to the mains U phase. 1.0mm2


30 Mains Voltage S Connected to the mains V phase. 1.0mm2
31 Mains Voltage T Connected to the mains W phase. 1.0mm2
32 Mains Voltage N1 Connected to the mains N phase. 1.0mm2
33 Load CT Secondary L1 1.5mm2
Current Transformer Secondary Rated
34 Load CT Secondary L2 1.5mm2
5A.
35 Load CT Secondary L3 1.5mm2
36 Load CT Secondary ICOM Connect to the common. 1.5mm2
 DC40S 3-phase 4-wire Typical Wiring Diagram

CTs MUST BE 5AMP SECONDARY


FROM GENERATOR

U P1 P2

TO LOAD SWITCHING
S1 S2

V P1 P2
S1 S2

DEVICE
W P1 P2
S1 S2

N2

RS485_SCR
RS485_B
RS485_A
33 34 35 36 25 26 27 28 8 9 29 30 31 32 18 19 20
IA IB IC ICOM U V W N2 R S T N1 A B SCR
GEN CURRENT GEN VOLTS
DC40S SERIES MAIN VOLTS RS485
(AC 0~5A) (AC0-300V) (AC0-300V)
SENSOR
MAX 5A MAX 1A INPUTS (0-1000R) MPU USB

1 2 3 4 5 6 7 8 9 21 22 23 24 10 11 12 13 14 15 16 17
+5V_MAX 50mA

SCR
CRANK

+ -
FUEL

1. OIL PRESSURE(R/U)
SENSOR COM_GND

2. TEMPERATURE
AUX. OUTPUT 1
AUX. OUTPUT 2
AUX. OUTPUT 3
AUX. OUTPUT 4

3. FUEL LEVEL
AUX. INPUT 1
AUX. INPUT 2
AUX. INPUT 3
AUX. INPUT 4

AC
D+ WL

1-70VPP
+
0-10KHz
BATTERY
8-36V

ALT
-

BATTERY NEGATIVE MUST BE GROUNDED


REMARK: 1.No. 10 common sensor lines must be securely attached to the vicinity of the sensor body.
2.To ensure reliable operation of the module and the measuring accuracy, power lines as much as possible and do
not share power cable crude and other devices.

11
DC4xS/C GENSET CONTROLLER USER MANUAL

The charging coil can only be connected to pin 15 ,the speed sensor is
connected to pins 15, 16 or 15, 17.

Note: Please don’t move battery during running status or it may cause the
controller broken!

 DC42S 3-phase 4-wire Typical Wiring Diagram

MECHANICAL INTERLOCK

TO LOAD SWITCHING
DEVICE
CTs MUST BE 5AMP SECONDARY
L1 L2 L3 N
FROM GENERATOR

U P1 P2 R
S1 S2

FROM MAINS
V P1 P2 S
S1 S2

W P1 P2 T
S1 S2

N2 N1
ELECTRICAL
INTERLOCK
G M

RS485_SCR
RS485_B
RS485_A
33 34 35 36 25 26 27 28 8 9 29 30 31 32 18 19 20
IA IB IC ICOM U V W N2 R S T N1 A B SCR
GEN CURRENT GEN VOLTS
DC42S SERIES MAIN VOLTS RS485
(AC 0~5A) (AC0-300V) (AC0-300V)
SENSOR
MAX 5A MAX 1A INPUTS (0-1000R) MPU USB

1 2 3 4 5 6 7 8 9 21 22 23 24 10 11 12 13 14 15 16 17
+5V_MAX 50mA

SCR
CRANK

+ -
FUEL

1. OIL PRESSURE(R/U)
SENSOR COM_GND

2. TEMPERATURE
AUX. OUTPUT 1
AUX. OUTPUT 2
AUX. OUTPUT 3
AUX. OUTPUT 4

3. FUEL LEVEL
AUX. INPUT 1
AUX. INPUT 2
AUX. INPUT 3
AUX. INPUT 4

AC
D+ WL

1-70VPP
+
0-10KHz
BATTERY
8-36V

ALT
-

BATTERY NEGATIVE MUST BE GROUNDED


REMARK: 1.No. 10 common sensor lines must be securely attached to the vicinity of the sensor body.
2.To ensure reliable operation of the module and the measuring accuracy, power lines as much as possible and do
not share power cable crude and other devices.

12
DC4xS/C GENSET CONTROLLER USER MANUAL

The charging coil can only be connected to pin 15 ,the speed sensor is
connected to pins 15, 16 or 15, 17.

Note: Please don’t move battery during running status or it may cause the
controller broken!

 DC40C 3-phase 4-wire Typical Wiring Diagram


CTs MUST BE 5AMP SECONDARY
FROM GENERATOR

U P1 P2

TO LOAD SWITCHING
S1 S2

V P1 P2
S1 S2

DEVICE
W P1 P2
S1 S2

N2

RS485_SCR
RS485_B
RS485_A
33 34 35 36 25 26 27 28 8 9 29 30 31 32 18 19 20
IA IB IC ICOM U V W N2 R S T N1 A B SCR
GEN CURRENT GEN VOLTS
DC40C SERIES MAIN VOLTS RS485
(AC 0~5A) (AC0-300V) (AC0-300V)
SENSOR
MAX 5A MAX 1A INPUTS (0-1000R) CAN USB

1 2 3 4 5 6 7 8 9 21 22 23 24 10 11 12 13 14 15 16 17
CAN_SCR
+5V 50mA
CRANK

CAN_H
CAN_L
FUEL

1. OIL PRESSURE(R/U)
SENSOR COM_GND

2. TEMPERATURE
AUX. OUTPUT 1
AUX. OUTPUT 2
AUX. OUTPUT 3
AUX. OUTPUT 4

REMARK: 1.No. 10 common sensor


3. FUEL LEVEL
INPUT 1
INPUT 2
INPUT 3
INPUT 4

lines must be securely attached to


the vicinity of the sensor body.
D+ WL

2.To ensure reliable operation of the


+
BATTERY

module and the measuring accuracy,


8-36V

AUX.
AUX.
AUX.
AUX.

ALT power lines as much as possible and


- do not share power cable crude and
other devices.
BATTERY NEGATIVE MUST BE GROUNDED

Note: Please don’t move battery during running status or it may cause the
controller broken!

WARNING: When generator is on-load, C. T. secondary must not be open


circuit, Otherwise, the high voltage generated will pose a danger to personal safety.
13
DC4xS/C GENSET CONTROLLER USER MANUAL

 DC42C 3-phase 4-wire Typical Wiring Diagram


MECHANICAL INTERLOCK

TO LOAD SWITCHING
DEVICE
CTs MUST BE 5AMP SECONDARY
L1 L2 L3 N
FROM GENERATOR

U P1 P2 R
S1 S2

FROM MAINS
V P1 P2 S
S1 S2

W P1 P2 T
S1 S2

N2 N1
ELECTRICAL
INTERLOCK
G M

RS485_SCR
RS485_B
RS485_A
33 34 35 36 25 26 27 28 8 9 29 30 31 32 18 19 20
IA IB IC ICOM U V W N2 R S T N1 A B SCR
GEN CURRENT GEN VOLTS
DC42C SERIES MAIN VOLTS RS485
(AC 0~5A) (AC0-300V) (AC0-300V)
SENSOR
MAX 5A MAX 1A INPUTS (0-1000R) CAN USB

1 2 3 4 5 6 7 8 9 21 22 23 24 10 11 12 13 14 15 16 17
CAN_SCR
+5V 50mA
CRANK

CAN_H
CAN_L
FUEL

1. OIL PRESSURE(R/U)
SENSOR COM_GND

2. TEMPERATURE
AUX. OUTPUT 1
AUX. OUTPUT 2
AUX. OUTPUT 3
AUX. OUTPUT 4

REMARK: 1.No. 10 common sensor


3. FUEL LEVEL
AUX. INPUT 1
AUX. INPUT 2
AUX. INPUT 3
AUX. INPUT 4

lines must be securely attached to


the vicinity of the sensor body.
D+ WL

2.To ensure reliable operation of the


+
BATTERY

module and the measuring accuracy,


8-36V

ALT power lines as much as possible and


- do not share power cable crude and
other devices.
BATTERY NEGATIVE MUST BE GROUNDED

Note: Please don’t move battery during running status or it may cause the
controller broken!

WARNING: When generator is on-load, C. T. secondary must not be open


circuit, Otherwise, the high voltage generated will pose a danger to personal safety.

14
DC4xS/C GENSET CONTROLLER USER MANUAL

 DC40 Series 1-phase 2-wire Typical Wiring Diagram


CTs MUST BE 5AMP SECONDARY
FROM GENERATOR

U P1 P2

TO LOAD SWITCHING
S1 S2

DEVICE
N2

RS485_SCR
RS485_B
RS485_A
33 34 35 36 25 26 27 28 8 9 29 30 31 32 18 19 20
IA IB IC ICOM U V W N2 R S T N1 A B SCR
GEN CURRENT
DC40 SERIES RS485
GEN VOLTS MAIN VOLTS
(AC 0~5A) (AC0-300V) (AC0-300V)
USB
1 PHASE 2 WIRE

 DC42 Series 1-phase 2-wire Typical Wiring Diagram


MECHANICAL INTERLOCK

TO LOAD SWITCHING
DEVICE
CTs MUST BE 5AMP SECONDARY
L1 N
FROM GENERATOR

U P1 P2 R
S1 S2
FROM MAINS

N2 N1
ELECTRICAL
INTERLOCK
G M
RS485_SCR
RS485_B
RS485_A

33 34 35 36 25 26 27 28 8 9 29 30 31 32 18 19 20
IA IB IC ICOM U V W N2 R S T N1 A B SCR
GEN CURRENT GEN VOLTS
DC42 SERIES MAIN VOLTS RS485
(AC 0~5A) (AC0-300V) (AC0-300V)
USB
1 PHASE 2 WIRE

15
DC4xS/C GENSET CONTROLLER USER MANUAL

 DC40 Series 2-phase 3-wire Typical Wiring Diagram


CTs MUST BE 5AMP SECONDARY
FROM GENERATOR

U P1 P2

TO LOAD SWITCHING
S1 S2

V P1 P2
S1 S2

DEVICE
N2

RS485_SCR
RS485_B
RS485_A
33 34 35 36 25 26 27 28 8 9 29 30 31 32 18 19 20
IA IB IC ICOM U V W N2 R S T N1 A B SCR
GEN CURRENT GEN VOLTS
DC40 SERIES MAIN VOLTS RS485
(AC 0~5A) (AC0-300V) (AC0-300V)
USB
2 PHASE 3 WIRE

 DC42 Series 2-phase 3-wire Typical Wiring Diagram


MECHANICAL INTERLOCK

TO LOAD SWITCHING
DEVICE
CTs MUST BE 5AMP SECONDARY
L1 L2 N
FROM GENERATOR

U P1 P2 R
S1 S2
FROM MAINS

V P1 P2 S
S1 S2

W T

N2 N1
ELECTRICAL
INTERLOCK
G M
RS485_SCR
RS485_B
RS485_A

33 34 35 36 25 26 27 28 8 9 29 30 31 32 18 19 20
IA IB IC ICOM U V W N2 R S T N1 A B SCR
GEN CURRENT GEN VOLTS
DC42 SERIES MAIN VOLTS RS485
(AC 0~5A) (AC0-300V) (AC0-300V)
USB
2 PHASE 3 WIRE

16
DC4xS/C GENSET CONTROLLER USER MANUAL

7. Installation instruction
 The controller is fixed by two special fixing members and screws, and the screws
of the metal fasteners cannot be too tight.
 Panel Cutout: W1160mm*H90mm.

Note: If the controller is installed directly in the genset shell or other fluctuated
equipment, the rubber pad must be installed.
Battery Voltage Input
DC4xS/C controller is suitable for 8-36V DC battery voltage. Battery negative must
be reliably connected to the enclosure of the engine. The controller power supply B+
and B- must be connected to battery positive and negative, and the wire size must
not be less than 2.5mm2.

NOTE:
In case of floating charger connect charger output to battery positive and negative
directly, then, connect battery positive and negative poles to controller positive and
negative power supply.
Output and relay expansion

Note: All outputs of the controller are relay contacts. The maximum current
capacity is described in the "Parameters" in this manual. Please use it in the relay
current capacity. If an extended relay is needed, add a continuous current diode
(when the extended relay coil is DC) or a resistance-capacitance loop (when the
extended relay coil is AC) to both ends of the coil to prevent interference with the
controller or other equipment.
 AC current input
Current transformer with rated secondary current 5A must be externally connected
to the controller current input.
17
DC4xS/C GENSET CONTROLLER USER MANUAL

WARNING: When generator is on-load, C. T. secondary must not be open


circuit, Otherwise, the high voltage generated will pose a danger to personal safety.
Withstanding voltage test

If withstanding voltage test is conducted after the controller has already been
installed onto the control panel, please unplug all controller terminal connections in
order to prevent high voltage from damaging it.

8. Panel and display


LCD
 DC40S/C

Alarm Up

Warning OK/HOME

Running Down

Stop Manual Start

Auto Gens Close/on Manual

LCD
 DC42S/C

Alarm Up

Warning OK/HOME

Running Down

Stop Manual Start

Auto Gens/Mains Close Manual 18


DC4xS/C GENSET CONTROLLER USER MANUAL

 Key Function Description


KEYS NAME Main Function
 Can stop generator under manual/auto mode;
 Can reset shutdown alarm
 During stop procession, pressing this key again can
stop generator immediately.
Stop
 Pressing this key can cancel the setting and back to
Reset
upper class under edition.
Revert
 Under the setting mode with checking data, the data
can be saved and system will exit after pressing.
 In the standby state of the stop gear without any alarm,
press this key for 3 seconds to view the alarm record.
 Start the genset under manual mode.
Start  Pressing this key can start the genset under manual
testing mode.

Manual  Pressing this key will set the module into manual mode.

Auto  Pressing this key will set the module into auto mode.

 Under manual mode, pressing this key can transfer


Gens/ Mains load to genset/mains.
Close/On  Press this key for 3 seconds,public unload of Gens and
Mains.
 Under display mode, parts of the page can move up.
 Under edition mode, pressing this key to move the digit
Up or increase the numbers.
 Under records mode, pressing this key to move the
digit.
 Under display mode, parts of the page can move down.
 Under edition mode, pressing this key to move the digit
Down or decrease the numbers.
 Under records mode, pressing this key to move the
digit.
 Confirm the change under edition mode.
 Shift right under edition mode.
OK  Page exited under records checking mode.
UI Change  Black UI and white UI can be switched when Pressing.
 In standby state, press for 3 seconds to enter the
parameter setting mode.
 Test if all LED lights are OK, pressing this key to test if
LED Test
all lighted, all off when loosen it.
+
 Pressing OK and STOP simultaneously to come into
Setting mode
setting mode
+

19
DC4xS/C GENSET CONTROLLER USER MANUAL

 Engine flywheel teeth automatic adjustment


1) Crank disconnect must be set to include both "speed" and "frequency" options.
2) When the generator frequency and engine speed are not zero, press
and for more than 0.5 seconds, the controller will automatically calculate and
save the number of flywheel teeth according to the generation frequency and
generator poles.
3) After calculating and saving the number of flywheel teeth successfully, the
controller shows: " Flywheel xxx teeth, saved successfully!"
 Alarm records checking
DC4xS/C controller can save 14 groups of alarm records which contains time, gens
parameter, engine parameter and so on.How to check the alarm records:
1) Enter alarm record page:
a) Under stop mode, press this key for 3 seconds come into alarm
records page;
b) Enter the setting mode: Select the alarm record and press key to alarm
records page;
2) Press to turn upper digit and press to turn lower digit in order to choose
the record you need. Press to confirm the record and come into history
records checking page.
3) Press to turn lower records under records checking page. Press to turn
upper records and press to revert back to alarm history records page.
4) Exit from records page: In the history records page and checking page, press
to exit;

9. Control and operation instruction


Manual Start Mode
press and make sure it is in the stop position before starting.
Press “ ” and the test file indicator is on. At this time, it is detected whether the
connection of each sensor is normal. If the sensor is open, the sensor opens an
alarm. If it is normal, the unit start process is executed in the following sequence after
pressing the " ". automatically switch to Generator provide the power when the
unit is running normally. Press “ ” The controller performs the parking process at
the following timing:
Manual start and stop process:

20
DC4xS/C GENSET CONTROLLER USER MANUAL

Longest
Longest Longest
voltage
speed temperature
built/
rated
increasing increasing warming Cooling
increasing up time runn-
time time running time
time ing

Start Stop
Rated speed idle
Safe idle
Crank time time time
test
time ETS
Long- solen-
est oid
Idle hold
Pre- pre-oil Start
heat supply Crank
Wait
delay delay delay Stop

0RPM 2S 8S 5S 120S 10S 120S 10S 30S 5S


5S 0S 8S 10S 30S

After the manual start is successful, pressing the "automatic key" can be
converted into an automatic file. The specific working time is as follows:
Longest
Longest Longest
voltage
speed temperature
built/
rated Transfer
increasing increasing warming Cooling
increasing up time runn- back to
time time running time
time ing mains delay

Start Stop
Rated speed idle
Safe idle
Crank time time time
test
time ETS
Long- solen-
est oid
Idle hold
Pre- pre-oil Start
heat supply Crank
Wait
delay delay delay Stop

0RPM 2S 8S 5S 120S 10S 120S 10S 10S 30S 5S


5S 0S 8S 10S 30S

Automatic starting mode:


press and make sure it is in the stop position before starting.
Press “ ” and the test file indicator is on. At this time, it is detected whether the
connection of each sensor is normal. If the sensor is open, the sensor opens an
alarm. If it is normal, wait for the remote start signal to be valid (DC42 series detected
the remote starting signal is valid or the mains provide the power is invalid). The unit
will perform the starting process in the following sequence. When the unit enters the
normal rated operation, it will automatically switch to the generator provide the power.
The controller will detect the remote start signal and the mains status in real time
(DC42 series is available). When the remote start signal fails and the mains provide
the power returns to normal, the shutdown process after the "loop time delay" is
performed (DC42 series is available).
Auto start and stop process:
Longest
Longest Longest
voltage
speed temperature
built/ rated Transfer
increasing increasing warming Cooling
increasing up time runn- back to
time time
time ing mains delay running time

Start Stop
Rated speed idle
Safe idle
Crank time time time
test
time ETS
Long- solen-
Crank oid
Idle est
Auto Pre- pre-oil Start test Crank hold
Start heat supply Crank time rest Wait
delay delay delay delay time Stop

0RPM 2S 8S 10S 8S 5S 120S 10S 120S 10S 10S 30S 5S


5S 5S 0S 8S 10S 30S

21
DC4xS/C GENSET CONTROLLER USER MANUAL

 Notices in Starting Process

Note 1: During the Cranking time, the controller automatically detects the speed
signal, frequency signal and oil pressure value or the charging voltage (according to
the parameter setting) to reach the judgment condition of successful start, then the
judgment is that the start is successful and the motor relay is closed.

Note 2: Within the safety delay, only respond to emergency stop, immediate
stop, over speed, over frequency, Over voltage, ECU communication Failure,shutter
open abnormal, other alarms are not responded to.

Note 3: No response to alarm and warning of under speed, low frequency,


under voltage, over current, over power,non-balance of current,external instant
unloading shutdown,during start idle time.

Note 4: No response to low frequency, under voltage, over current non-balance


of current,external instant unloading shutdown and over power is required when
entering the RPM-up time.

Note 5: No response to low frequency, under voltage, over current non-balance


of current,external instant unloading shutdown and over power is required when
entering the temperature-up time.

Note 6: No response to low frequency, under voltage, over current non-balance


of current,external instant unloading shutdown and over power is required when
entering the Voltage-up time.

Note 7: No response to low frequency, under voltage, over current non-balance


of current,external instant unloading shutdown and over power is required when
entering the Warming-up time.

Note 8: After entering rated operation, the Gens load relay output.

Note 9: In the process of shutdown, if the remote starting signal is restored to


be valid within the " Cooling time", the rated operation will be entered again.

Note 10: If the stop key is pressed again during idle time, the idle time will be
canceled and the stop operation will be executed directly.

10. Warnings and Shutdown Alarms


 Warnings

Notes: Warning is a non-serious failure state, which will not harm the gensets
system for the time being. It only reminds operators to pay attention to the situation
that does not meet the requirements and solve it in time to ensure the continuous
operation of the system. When the warning occurs, the gensets does not stop. Once
the fault is removed, the warning is automatically canceled.

22
DC4xS/C GENSET CONTROLLER USER MANUAL

Low Oil Pressure Sensor Warning


When the controller parameter "Action if low oil pressure" is set to "Warning" and
the AUX. input port "Low oil pressure shutdown disabled" switch is valid,and the
controller detects that the engine Oil Pressure is lower than “Low oil pressure
warning”, Then start warning delay and the duration (Normal alarm delay) have not
returned to normal, the warning of low Oil Pressure is reported. "WARNING" lights
will light up, Generators will not stop, displays "Low OP sensor " on the current fault
screen.

Low Oil switch Warning


When the controller parameter "Action if low oil pressure" is set to "Warning" and
the AUX. input port "Low oil pressure shutdown disabled" switch is valid,and the
controller detects that the engine Oil Pressure is lower than “Low oil pressure
warning”, Then start warning delay and the duration (Normal alarm delay) have not
returned to normal, the warning of low Oil Pressure is reported. "WARNING" lights
will light up, Generators will not stop, displays "Low OP Switch " on the current fault
screen.

High temperature sensor warning


When the controller parameter "Action if high temperature" is set to "Warning" and
the AUX. input port "High temperature disabled" switch is valid,and the controller
detects that the coolant temperature value is higher than the "High temperature
warning", Then start warning delay and the duration (Normal alarm delay) have not
returned to normal, the warning of High coolant temperature warning is reported.
"WARNING" lights will light up, Generators will not stop, displays "High WT sensor"
on the current fault screen.

High temperature switch warning


When the controller parameter "Action if high temperature" is set to "Warning" and
the AUX. input port "High temperature disabled" switch is valid,and the controller
detects that the coolant temperature value is higher than the "High temperature
warning", Then start warning delay and the duration (Normal alarm delay) have not
returned to normal, the warning of High coolant temperature warning is reported.
"WARNING" lights will light up, Generators will not stop, displays "High WT sensor"
on the current fault screen.

Low fuel level sensor warning


When the controller detects that the fuel level value is lower than the "Low fuel level
warning", Then start warning delay and the duration (Normal alarm delay) have not
returned to normal, the warning of Low fuel level warning is reported. "WARNING"
lights will light up, Generators will not stop, displays "Low fuel level-A" on the current
fault screen.

Low fuel level switch warning


When the controller detects that the AUX. input "Low fuel level warning input"
switch is active, it starts warning delay and lasts for Normal alarm delay. When the
"Low fuel level warning input" switch is enabled, the engine low fuel level switch
warning is reported. "WARNING" lights will light up, Generators will not stop, displays
"Low fuel level-D" on the current fault screen.

23
DC4xS/C GENSET CONTROLLER USER MANUAL

External instant warning


When the controller detects that the AUX. input "External instant warning input"
switch is active, it starts warning delay and lasts for Normal alarm delay. When the
"External instant warning input" switch is enabled, the warning is reported.
"WARNING" lights will light up, Generators will not stop, displays "Instant warn" on
the current fault screen.

Speed signal lost warning


When the controller parameter "Action if RPM lost" is set to "warning", the detected
speed value is 0,Then start warning delay and the duration (Normal alarm delay)
have not returned to normal, the warning of speed signal lost warning is reported.
"WARNING" lights will light up, Generators will not stop, displays "Lose speed" on
the current fault screen.

Oil pressure sensor disconnected warning


When the controller parameter "Action if low oil pressure sensor disconnected" is
set to "warning", When the oil pressure sensor is detected to be disconnected,Then
start warning delay and the duration (Normal alarm delay) have not returned to
normal, the warning of Oil pressure sensor disconnected warning is reported.
"WARNING" lights will light up, Generators will not stop, displays "OP sensor open"
on the current fault screen.

Coolant temperature sensor disconnected warning


When the controller parameter "Action if water temperature sensor disconnected"
is set to "warning", When the coolant temperature sensor is detected to be
disconnected,Then start warning delay and the duration (Normal alarm delay) have
not returned to normal, the warning of coolant temperature sensor disconnected
warning is reported. "WARNING" lights will light up, Generators will not stop, displays
"WT sensor open" on the current fault screen.

Over battery voltage warning


When the controller detects that the battery voltage is higher than the "Over battery
voltage warning ", Then start warning delay and the duration (Normal alarm delay)
have not returned to normal, the warning of Over battery voltage warning is reported.
"WARNING" lights will light up, Generators will not stop, displays "Over voltage" on
the current fault screen.

External instant unloading switch warning


When the controller detects that the AUX. input "External instant unloading
shutdown disabled" switch is active, it starts warning delay and lasts for Normal
alarm delay. When the "External instant unloading shutdown disabled" switch is
enabled, the warning is reported. "WARNING" lights will light up, Generators will not
stop, displays "Unload switch" on the current fault screen.

Fuel Level sensor disconnected warning


When the controller parameter "Action if fuel Level sensor disconnected " is set to
"warning", When the fuel Level sensor is detected to be disconnected,Then start
warning delay and the duration (Normal alarm delay) have not returned to normal, the
warning of fuel Level sensor disconnected warning is reported. "WARNING" lights
will light up, Generators will not stop, displays "FL sensor open" on the current fault
24
DC4xS/C GENSET CONTROLLER USER MANUAL

screen.

Maintenance expiration warning


When the controller parameter "Maintenance expire" is set to "warning", when the
primary countdown to maintenance is detected as "0" or primary maintenance date
less than current date, then start warning delay and the duration (normal alarm delay),
the warning of maintenance expiration is reported. "WARNING" lights on, without
stopping the engine, and displays "Maintain end" on the LCD screen.

Low coolant level switch warning


When the controller detects that the AUX. input "Low water level warning" switch is
active, it starts warning delay and lasts for Normal alarm delay. When the "Low
water level warning" switch is enabled, the engine low coolant level switch warning
is reported. "WARNING" lights will light up, Generators will not stop, displays "Low
water level" on the current fault screen.

Over battery voltage warning


When the controller detects that the battery voltage is over than the "Over battery
voltage warning", Then start warning delay and the duration (Normal alarm delay)
have not returned to normal, the warning of over battery voltage warning is reported.
"WARNING" lights will light up, Generators will not stop, displays "Over BATT volt"
on the current fault screen.

Under battery voltage warning


When the controller detects that the battery voltage is lower than the "Under battery
voltage warning", Then start warning delay and the duration (Normal alarm delay)
have not returned to normal, the warning of Under battery voltage warning is reported.
"WARNING" lights will light up, Generators will not stop, displays "Under BATT volt"
on the current fault screen.

Charging failure warning


When the gap between D+ and B+ is over than this value, and there is charging
failure but still high(normal warning delay), then charge failure warns. "WARNING"
lights will light up, Generators will not stop, displays "Charger fault" on the current
fault screen.Once the gap is lower than the value, warns clear.

ECU faults warning


When the controller detects the warning information of ECU, Then start warning
delay and the duration (Normal alarm delay) have not returned to normal, the warning
of ECU faults warning is reported. "WARNING" lights will light up, Generators will not
stop, displays "ECU faults warn" on the current fault screen.

ECU Communication Failure Warning


When the controller parameter "CAN failure" is set to "warning", and controller
does not receive any message sent by ECU. It started to delay and lasted for some
time (Normal alarm delay) but still did not receive the message from ECU, the
warning of ECU faults warning is reported. "WARNING" lights will light up,
Generators will not stop, displays "ECU comm. fail" on the current fault screen.

25
DC4xS/C GENSET CONTROLLER USER MANUAL

 Starting fault
Fail to Start
If the number of cranks exceeds the predetermined number of cranks, the failure of
start-up will be reported if the start-up of the generating unit is still unsuccessful.
"ALARM" lights on, without stopping the engine, and displays " Crank failure " on
the current fault screen.

 Shutdown Alarms

Warning: After the Shutdown Alarm occurs, the system will be locked
immediately and the generator set will be stopped. Only after troubleshooting, press
key to clear the alarm, can it be re-operated.

Notes:When the shutdown alarm failure occurs, the "ALARM" lights will light
up and the generator unit automatically stops.

Over speed alarm


When the controller detects that the engine speed is higher than “Over speed alarm”,
Then start alarm delay and the duration (Emergency delay) have not returned to
normal, the alarm of over speed is reported. "ALARM" lights flicker, Generator stops
running, and displays " Over speed " on the current fault screen.

Under speed alarm


When the controller detects that the engine speed is under than “Under speed
alarm”, Then start alarm delay and the duration (Normal alarm delay) have not
returned to normal, the alarm of under speed is reported. "ALARM" lights flicker,
Generator stops running, and displays " Under speed " on the current fault screen.

Low oil pressure sensor alarm


When the controller detects that the engine Oil Pressure is lower than “Low oil
pressure alarm”, Then start alarm delay and the duration (Normal alarm delay) have
not returned to normal, the alarm of low Oil Pressure is reported. "ALARM" lights
flicker, Generator stops running, and displays "Low OP sensor " on the current fault
screen.

Low oil pressure switch alarm


When the controller detects that the AUX. input port "Low oil pressure alarm input"
switch is active. Start low oil pressure switch alarm delay, for a period of time
"general alarm delay" AUX. input port "low oil pressure alarm input" switch is valid.
Then the alarm, the public alarm light "ALARM" light is always on, stop the unit
operation, and display "Low OP switch" on the current fault screen.

High temperature sensor alarm


When the controller detects that the temperature value is higher than the "High
temperature alarm", Then start alarm delay and the duration (Normal alarm delay)
have not returned to normal, the alarm of High temperature alarm is reported.
26
DC4xS/C GENSET CONTROLLER USER MANUAL

"ALARM" lights will light up, Generator stops running,and displays "High Temp
sensor" on the current fault screen.

High Temperature Switch Alarm


When the controller detects that the High temperature alarm switch input is valid to
the ground, then start alarm delay and the duration (Normal alarm delay) have not
returned to normal, the alarm of High Temperature Switch is reported. "ALARM"
lights flicker, Generator stops running, and displays "High Temp switch" on the
current fault screen.

Low fuel level sensor alarm


When the controller detects that the fuel level value is lower than the "Low fuel level
alarm", Then start alarm delay and the duration (Normal alarm delay) have not
returned to normal, the alarm of Low fuel level alarm is reported. "ALARM" lights will
light up, Generator stops running,and displays "Low fuel level-A" on the current fault
screen.

Low fuel level switch alarm


When the controller detects that the AUX. input "Low fuel level alarm input" switch
is active, it starts alarm delay and lasts for Normal alarm delay. When the "Low fuel
level alarm input" switch is enabled, the engine low fuel level switch alarm is
reported. "ALARM" lights will light up, Generator stops running,and displays "Low
fuel level-D" on the current fault screen.

External instant alarm


When the controller detects that the “External instant alarm input” switch of the
AUX. input port is valid, the external instant trip is started and the shutdown alarm
delay is delayed for a period of time “Normal alarm delay” AUX. input port
“External instant alarm input” switch When it is valid, it will alarm, the public alarm
light "ALARM" lights will light up,Generator stops running, and display "Instant
parking" on the current fault screen.

Speed signal lost alarm


When the controller parameter "Action if RPM lost" is set to "alarm", the detected
speed value is 0,Then start alarm delay and the duration (Normal alarm delay) have
not returned to normal, the alarm of speed signal lost warning is reported. "ALARM"
lights will light up, Generator stops running, displays "Lose speed" on the current
fault screen.

Oil pressure sensor disconnected alarm


When the controller parameter "Action if low oil pressure sensor disconnected" is
set to "alarm", When the oil pressure sensor is detected to be disconnected,Then
start alarm delay and the duration (Normal alarm delay) have not returned to normal,
the alarm of Oil pressure sensor disconnected alarm is reported. "ALARM" lights will
light up, Generator stops running, displays "OP sensor open" on the current fault
screen.

Temperature sensor disconnected alarm


When the controller parameter "Action if temperature sensor disconnected" is set
to "alarm", When the temperature sensor is detected to be disconnected,Then start
27
DC4xS/C GENSET CONTROLLER USER MANUAL

alarm delay and the duration (Normal alarm delay) have not returned to normal, the
alarm of temperature sensor disconnected alarm is reported. "ALARM" lights will light
up, Generator stops running, displays "Temp sensor open" on the current fault
screen.

Fuel Level sensor disconnected alarm


When the controller parameter "Action if fuel Level sensor disconnected " is set to
"alarm", When the fuel Level sensor is detected to be disconnected,Then start alarm
delay and the duration (Normal alarm delay) have not returned to normal, the alarm
of fuel Level sensor disconnected alarm is reported. "ALARM" lights will light up,
Generator stops running, displays "FL sensor open" on the current fault screen.

Over frequency alarm


When the controller detects that the generator frequency is higher than “Over
frequency alarm”, Then start alarm delay and the duration (Emergency delay) have
not returned to normal, the alarm of over frequency is reported. "ALARM" lights will
light up, Generator stops running, displays " Over frequency " on the current fault
screen.

Under frequency alarm


When the controller detects that the generator frequency is lower than “Under
frequency alarm”, Then start alarm delay and the duration (Normal alarm delay)
have not returned to normal, the alarm of under frequency is reported. "ALARM"
lights will light up, Generator stops running, displays " Under frequency " on the
current fault screen.

Over voltage alarm


When the controller detects that the generator voltage is higher than “Over voltage
alarm”, Then start alarm delay and the duration (Normal alarm delay) have not
returned to normal, the alarm of over voltage is reported. "ALARM" lights will light up,
Generator stops running, displays " Over voltage " on the current fault screen.

Under voltage alarm


When the controller detects that the generator voltage is lower than “Under voltage
alarm”, Then start alarm delay and the duration (Normal alarm delay) have not
returned to normal, the alarm of under voltage is reported. "ALARM" lights will light
up, Generator stops running, displays " Under voltage " on the current fault screen.

Over current alarm


When the controller detects that the generator phase current is higher than “Phase
current over-load alarm”, Then start alarm delay and the duration (Normal alarm
delay) have not returned to normal, the alarm of over current is reported. "ALARM"
lights will light up, Generator stops running, displays " Over current " on the current
fault screen.
Over power alarm
When the controller detects that the generator power is higher than “Over total

28
DC4xS/C GENSET CONTROLLER USER MANUAL

power alarm”, Then start alarm delay and the duration (Normal alarm delay) have
not returned to normal, the alarm of over power is reported. "ALARM" lights will light
up, Generator stops running, displays " Over power " on the current fault screen.

Non-balance current ratio alarm


When the controller is 2 phase 3 wire or 3 phase 4 wire, the controller detects that
the unbalance degree of the three-phase or two-phase current of the generator is
higher than the "Non-balance current ratio alarm".Then start alarm delay and the
duration (Normal alarm delay) have not returned to normal, the alarm of Non-balance
current ratio is reported. "ALARM" lights will light up, Generator stops running,
displays " Unbalance of AMP " on the current fault screen.

Maintenance Expiration Alarm


When the action after the primary maintenance expired set as “alarm”, When the
countdown to maintenance is detected as "0", Then start warning delay and the
duration (Normal alarm delay) have not returned to normal, the warning of
Maintenance expiration is reported. "ALARM" lights on, Generator stops running, and
displays "Maintain end" on the current fault screen.

ECU faults alarm


When the controller detects the alarm information of ECU, Then start alarm delay and
the duration (Normal alarm delay) have not returned to normal, the alarm of ECU
faults alarm is reported. "ALARM" lights will light up, Generator stops running,
displays "ECU faults warn" on the current fault screen.

ECU communication failure alarm


When the controller parameter "CAN failure" is set to "alarm", and controller does
not receive any message sent by ECU. It started to delay and lasted for some time
(Normal alarm delay) but still did not receive the message from ECU, the alarm of
ECU faults alarm is reported. "ALARM" lights will light up, Generator stops running,
displays "ECU comm. fail" on the current fault screen.

Low coolant level switch alarm


When the controller detects that the AUX. input "Low water level alarm" switch is
active, it starts alarm delay and lasts for Normal alarm delay. When the "Low water
level alarm" switch is enabled, the engine low coolant level switch alarm is reported.
"ALARM" lights will light up, Generator stops running, displays "Low water level" on
the current fault screen.

Louver opening exception alarm


When the controller detects that the AUX. input "Louver status input" switch is
active, it starts alarm delay and lasts for Normal alarm delay. When the "Louver
status input" switch is enabled, the Louver status input alarm is reported. "ALARM"
lights will light up, Generator stops running, displays "Louver abnormal" on the
current fault screen.

Emergency stop alarm


When the controller detects that the input voltage of PIN 3 is less than 2V, then start
alarm delay and the duration (Emergency delay) have not returned to normal, the

29
DC4xS/C GENSET CONTROLLER USER MANUAL

alarm of Emergency Stop is reported. "ALARM" lights will light up, Generator stops
running, and displays "Emergency stop" on the current fault screen.

Stop failure with frequency alarm


When the controller detects that the frequency is not "0" after the execution of the
shutdown, the alarm of stop failure is reported. "ALARM" lights will light up and
displays "Stop fail-Hz" on the current fault screen.

Stop failure with pressure alarm


When the controller detects that the Oil Pressure is not "0" after the execution of the
shutdown, the alarm of stop failure is reported. "ALARM" lights will light up and
displays " Stop fail-OP-A " on the current fault screen.

Stop failure with oil pressure switch


When the controller detects that the oil pressure switch has not returned after the
stop, it will alarm, the public alarm light “ALARM” lights will light up, and the current
fault screen displays “ Stop fail-OP-D”.

11. Parameters setting


 Enter the edition page
Please set the parameters according to below steps:
1) The setting mode can be actived after pressing and simultaneously,
under the status of standby without any alarm. The default password is “07623”.
2) Press and add number 1, press to reduce number 1, press to turn
the digit into right, press once done. Then system comes into menu after
confirmation of password setting. The screen will display error if password is
wrong. The correct password should be put after pressing any button.
3) Press to turn the digit into upper position, press to turn the digit into
lower position, press to get into parameters setting page.
4) Press to shift up the parameters, press to shift down the parameters,
press to get into parameter changing page.
5) Press to add number 1, press to reduce number 1, press to turn the
digit into right, press once done. If the parameters setting is in the valid setting
range,then it can be saved, if not, it can not be saved.
6) Press and to save the parameters and exit from edition page.
7) Press to revert back to last class if in any setting position.

Revert back to default: put password “97011” when coming into parameters
setting, then all the parameters can be set as defaults.

Note: the data can’t be saved if the user didn’t press and to confirm the
setting.
30
DC4xS/C GENSET CONTROLLER USER MANUAL

 Parameter setting
1)Delay time setting
No Parameter Range(default) Notes
The time during the genset starts after the
1 Start delay 0-65000s(5.0s)
remote signal is valid.
The time needed to be preheated before
2 Preheat time 0-6500.0s (0.0s)
the starter on power.
Under pre-oil supply, if the oil pressure is
Longest pre-oil
3 0-180.0s(0.0s) higher than setting value, then pre-oil
supply
supply stopped.
Fuel output The time the fuel valve relay outputs before
4 1.0-60.0s (2.0s)
delay the motor operates.
5 Cranking time 3.0-60.0s (8.0s) The time when the starter is on power.
If crank failure, the waiting time before the
6 Crank rest time 3.0-60.0s (10.0s)
second test time.
Low oil pressure, high water temperature,
under speed, under frequency, under
7 Safety delay 1.0-60.0s (8.0s) voltage, charge failure are all invalid during
this time except for emergency stop and
over speed.
8 Start idle time 0-3600.0s (5.0s) Idle running time when crank successfully.
The longest speed-up time,during which
Longest RPM-up 0-3600.0s
9 time the system will exit once speed
time (120.0s)
increased successfully .
The longest warming-up time,during which
Longest Temp.-
10 0-3600.0s(0.0s) time the system will exit once temperature
up time
increased successfully .
The longest voltage-up time,during which
Longest Volt.-up 0-3600.0s
11 time the system will exit once voltage
time (120.0s)
increased successfully .
12 Warming-up time 0-3600.0s(10.0s) The time needed for loading.
After unloading, the time of cooling down
by radiator before stop. during the delay, if
13 Cooling time 0-3600.0s(30.0s)
the remote start signal is valid, then genset
will come into rated running.
14 Stop idle time 0-3600.0s (5.0s) Idle-speed running time.
15 E.T.S. hold time 0-600.0s (10.0s) Stop solenoid on power time.
If the RPM is 0 during the stop failure time,
16 Fail to stop 5-180.0s (30.0s)
then the stop failure time is no needed.
Emergency Emergency and over frequency alarm
17 0-10.0s (1.5s)
delay delay.
Normal alarm The alarm delay except for emergency
18 2.0-20.0s (5.0s)
delay stop and over frequency
Normal warning
19 1.0-20.0s (2.0s) The warning delay.
delay
Pulse speed up The interval time of the pulse speed up
20 0.1-60.0s(0.2s)
delay relay change.
Pulse speed The interval time of the pulse speed down
21 0.1-60.0s(0.2s)
down delay relay change.
22 Load 1.0-10.0s (5.0s) Gens loading and unloading pulse width,
31
DC4xS/C GENSET CONTROLLER USER MANUAL

pulse width when it is 10s, it is regarded as continuous


Unload output.
23 1.0-10.0s (3.0s)
pulse width
Transfer switch
24 0-3600.0s(1.0s) The time from Mains to Gens.
delay
AC Voltage
25 2.0-20.0s(10.0s) Over / under voltage delay.
abnormal delay
To avoid the switch actions if the mains
unstable.If the remote start signal is invalid
(DC42 series will check if the mains
Back to Mains normal), genset will not switch immediately,
26 0-3600.0s(10.0s)
time after the delay time, it will transfer to
mains. during the delay, if the remote start
signal is valid, then genset will come into
rated running.
There shall be loading delay from Mains to
Back to Gens 0-3600.0s
27 Gens if the remote start signal valid or
time (5.0s)
Mains abnormal under Cooling time.

2)Engine setting
No Parameter Range (defaults) Notes
1 CAN Protocol 0- Disabled CAN protocol Option: the Engine paramet
1: J1939 ers like RPM, oil pressure, water temperat
2: Cummins ISB ure are all from ECU data after choosing t
3: Cummins-CM850 he relative protocol.
4: Cummins QSX15-
CM570
5: Cummins-CM850-
PCC13X
6: Cummins-DCEC-
QSZ13
7: Cummins-CCEC-QSN
8: Perkins
9: Perkins-1100
10: Volvo
11: Volvo-EMS2
12: Volvo-EMS2b
13: Volvo-EDC4
14: Scania
15: Scania-kw2000
16: Scania-kw2k-coo
17: John Deere
18: mtu-ADEC
19: mtu-ADEC-SAM
20: mtu-ADEC-303
21: mtu-ADEC-304
22: BOSCH
23: GTSC1
24: MTSC1
25: YUCHAI-YCECU

32
DC4xS/C GENSET CONTROLLER USER MANUAL

26: Y&C ENGINE-YC6K


27: WEICHAI-WISE15
28: CHANGCHAI-ECU15
29: YUCHAI-LMB
30: MAN
31: J1939-C
32: SDEC-H/D
33: SDEC-E
34: YTO
35: DEUTZ EMR2-2001
36: DEUTZ EMR2-2012
37: DEUTZ EMR3
38: DEUTZ EMR4
39:NEWND ECU13
40:Cummins-CM2150
If the setting is 0, (RPM sensor Disabled),
2 Flywheel teeth 0-300 (0)
then RPM is resulted by Hz.
Choose the meter range and calculate the
3 Rated RPM 500-4500RPM (1500)
alarm value.
This fault can be checked only if there is
Action if RPM Warning
4 gens frequency checked as one condition
lost Alarm and stop
of crank successfully.
Rated RPM multiplying by this value is
regarded as speed-up stop value. When
5 RPM-up stop 0-200%(90%)
the RPM is over this value, then the RPM-
Up procession is stopped in time.
Rated RPM multiplying by this value is
regarded as over speed alarm value.
When the RPM is higher than the alarm
value and comes into over speed delay
6 Overspeed alarm 0-200% (114%)
but still higher (emergency faults delay),
then over speed alarms. if the value is set
as 200, then the over speed alarm is
disabled.
Rated RPM multiplying by this value is
regarded as under speed alarm value.
When the RPM is lower than the alarm
Under speed
7 0-200% (80%) value and comes into under speed delay
alarm
but still lower (normal faults delay), then
under speed alarms. if the value is set as
0, then the under speed alarm is disabled.
Battery Rated Standard for detecting of over/under
8 8.0-36.0V (24.0V)
Voltage voltage of battery.
Rated battery voltage multiplying by this
value is regarded as over battery voltage
warning value. When the battery input is
Over battery
9 0-200% (135%) higher than the warning value and comes
voltage warning
into over battery voltage delay but still
higher (normal faults delay), then over
battery voltage warns. if the value is set as

33
DC4xS/C GENSET CONTROLLER USER MANUAL

200, then the over battery voltage is


disabled.
Rated battery voltage multiplying by this
value is regarded as under battery voltage
warn value. When the battery input is
lower than the warning value and comes
Under battery
10 0-200% (67%) into under battery voltage delay but still
voltage warning
lower (normal faults delay), then under
battery voltage warns. if the value is set as
0, then the under battery voltage is
disabled.
When the gap between D+ and B+ is over
than this value, and there is charging
failure but still high (normal warning
11 Charger warning 1.0-30.0V (30.0V) delay), then charge failure warns. Once
the gap is lower than the value, warns
clear. If the value is set as 300, then the
charge failure is disabled.
Manual crank
12 1-30 (1 time) Crank times under mode and test mode.
times
Auto start crank
13 1-30 (3 times) Crank times under auto mode.
times
The max E.T.S. hold on power shall be
canceled once stop success under auto
14 E.T.S. hold times 1-10 (2 times)
mode. the output interval time is " Fail to
stop ".
RPM 1.If there is no oil pressure sensor, please
Frequency don’t choose the type.
Oil pressure 2.Oil pressure switch input is not the crank
RPM/Frequency condition
RPM/Oil Pressure 3.Please check if the running status, stop
Crank
15 Frequency/Oil Pressure condition are according with crank
disconnect
RPM/Frequency/Oil condition.
press. 4.Means either of the conditions can be
acceptable as crank condition. But all of
them should be meet together to regard
as stop condition.
Rated frequency multiplying by this value
is regarded as crank success condition.
Frequency
16 0-200% (28%) When the gens frequency is over the
disconnect
condition value, then system regards it as
crank success.
Rated RPM multiplying by this value is
regarded as crank success condition.
17 RPM disconnect 0-200% (24%) When the RPM is over the condition
value, then system regards it as crank
success, motor escaped.
When the engine oil pressure is over the
Oil pressure
18 0-400kpa (200kpa) condition value, then system regards it as
disconnect
crank success, motor escaped.

34
DC4xS/C GENSET CONTROLLER USER MANUAL

When the crank condition contains oil


pressure, if the oil pressure is higher than
Oil pressure
19 0-20.0s (0.0s) the presets value and continue for few
delay
seconds, then it is regarded as crank
success.
When the oil pressure is over the
OP pre-supply
20 50-600kpa(200kpa) condition value, then pre-oil supply is
stop
stopped.
When the fuel level is lower than preset
21 Fuel pump open 0-100% (25%) value and remains 10S, fuel pump opened
signal output
When the fuel level is higher than preset
22 Fuel pump close 0-100% (80%) value and remains 1S, fuel pump closed
signal output.
Maximum fuel The maximum output time of the fuel
23 0-65000s (65000s)
pump on time pump.
Used for controlling radiator: when the
Temperature
24 20-200℃(75℃) water temperature reaches the set
for Fan open
temperature, then the radiator is opened.
Used for controlling radiator: when the
Temperature
25 20-200℃(60℃) water temperature is lower than the set
for Fan close
temperature, then the radiator is closed.
Battery charging When the battery voltage is lower than
26 8.0-30.0 (25.6V)
start start value and remains 10s under non-
running status, then the relay is opened.
Battery charging When it is higher than the close value and
27 10.0-36.0 (27.8V)
stop remains 10s, relay is closed. Once coming
into running mode, there is no output.
0-Speed sensor Select the speed signal of different engine
28 Speed type
1-Charging coil types.

3)Generator parameters
No Parameter Range(defaults) Notes
When the flywheel teeth are set as 0, the RPM
will be resulted by frequency.
Pole 2: 50Hz---3000RPM.
1 Gens poles 2/4/6/8(4)
Pole 4: 50Hz---1500RPM.
Pole 6: 50Hz---1000RPM.
Pole 8: 50Hz---750RPM
Disable
Gens phases:
1 phase 2 wire
No gens parameters can be displayed if setting
2 Gens AC system 2 phase 3 wire
as disable, which is applied to water pump
3 phase 3 wire
genset.
3 phase 4 wire
40.0-80.0Hz Setting generator rated frequency to choose the
3 Rated frequency
(50.0Hz) meter range and calculate the alarm value.
Rated frequency multiplying by this value is
regarded as under over frequency alarm value.
4 Over freq alarm 0-200% (114%)
When the Freq is higher than the value and
comes into over freq delay but still higher
35
DC4xS/C GENSET CONTROLLER USER MANUAL

(emergency faults delay), then over frequency


alarms, If the value is set as 200, then the alarm
is disabled.
Rated frequency multiplying by this value is
regarded as under frequency alarm value. When
the Freq is lower than the value and comes into
5 Under freq alarm 0-200% (80%)
under freq delay but still lower (normal faults
delay), then under frequency alarms, If the value
is set as 0, then the alarm is disabled.
Rated phase Setting generator phase voltage to choose the
6 80-420V(230V)
voltage meter range and calculate the alarm value.
Rated voltage multiplying by this value is
regarded as voltage-up stop value. When the
7 Voltage-up stop 0-200%(85%)
voltage is over this value, then the voltage-Up
procession is stopped in time.
Rated voltage multiplying by this value is
regarded as over voltage alarm value. When the
Over voltage voltage is higher than the value and comes into
8 0-200% (120%)
alarm over voltage delay but still higher (normal faults
delay), then over voltage alarms, If the value is
set as 200, then the alarm is disabled.
Rated voltage multiplying by this value is
regarded as under voltage alarm value. When the
Under voltage voltage is lower than the value and comes into
9 0-200% (80%)
alarm under voltage delay but still lower (normal faults
delay), then under voltage alarms, If the value is
set as 0, then the alarm is disabled.
When it is set to enabled, when the generator set
ATS in
10 Disable/Enable meets the closing conditions, it will be loaded
manual mode
automatically.

4)Loading setting
No Parameter Range (default) Notes
1 CT rate 5-6000A(500A) Used for setting genset CT primary current.
Rated phase Setting generator phase current to choose the
2 5-6000A (500A)
current meter range and calculate the alarm value.
5-2000Kw Set total power of generator to choose the meter
Rated total
3 range and calculate the average loading rate and
power (276Kw)
alarm value.
Rated current multiplying by this value is regarded
as over current alarm value. When the current is
Phase current higher than the value and comes into over current
4 0-200% (100%)
over-load alarm delay but still higher (over current faults delay),
then over current alarms, If the value is set as
200, then the alarm is disabled.
Over phase When this parameter is set to 0, the over current
5 current 0-3600.0s (30s) delay is the inverse time; if not, the over current
delay delay is the time set for this parameter.
Over current This option will not take effect until the [23-Over
6 0.1-36.0 (36.0)
【inverse time】 phase current delay] is set to 0. The over current
36
DC4xS/C GENSET CONTROLLER USER MANUAL

delay is inverse time, and the formula is


T=t/((IA/IT) -1)^2.
Rated power multiplying by this value is regarded
as over power alarm value. When the loading
Over total power power is higher than the value and comes into
7 0-200% (100%)
alarm delay but still higher (power faults delay), then
over power alarms, If the value is set as 200, then
the alarm is disabled.
When this parameter is set to 0, the over power
Over total power
8 0-3600.0s (10s) delay is the inverse time; if not, the over current
delay
delay is the time set for this parameter.
This option will not take effect until the [24-Over
9 Over
2 power total power delay] is set to 0. The over power
0.1-36.0 (36.0)
4
【inverse time】 delay is inverse time, and the formula is
T=t/((IA/IT) -1)^2.
It is valid for 2P3W or 3P4W.When the non-
balance current ratio is higher than the value and
Non-balance
comes into delay but still higher(normal warn
10 current ratio 10-100%(100%)
delay), then non-balance current ratio warns.If the
warning
value is set as 100, then the warning is disabled.
IOOB =((I Max - I Ave)/Ave)*100%
0-5A
11 CT Sec.current 1-50mA Chose the secondary rated current.
2-62.5mA

5)Mains protection
No Parameter Range(defaults) Notes
Disable Choose the input, there is no display if setting as
1 Phase 2 Wire disable.
1 Phase 2 Phase 3 Wire
3 Phase 3 Wire
3 Phase 4 Wire
2 Mains under volt 55-330V(184V) When the mains voltage is lower than the "low
3 Revert under volt 55-330V(207V) voltage crank threshold" and comes into mains
low voltage delay(normal failure delay) but still
lower, then mains becomes invalid. If the voltage
become higher than "low voltage revert threshold"
during normal failure delay time, then it will not
alarm.
4 Mains over volt 55-330V(276V) When the mains voltage is higher than the" high
5 Revert over volt 55-330V(253V) voltage crank threshold" and comes into mains
high voltage delay(normal failure delay) but still
higher, then mains becomes invalid. If the voltage
become lower than "low voltage revert threshold"
during normal failure delay time, then it will not
alarm.
Mains normal 0.0-3600.0S The time from abnormal to normal, which is used
6
delay (10.0S) for ATS transfer.
Mains abnormal 0.0-3600.0S
7
delay (5.0S)
37
DC4xS/C GENSET CONTROLLER USER MANUAL

Loss of Phase 1 Set the phase loss condition to judge whether the
Loss of Phase
8 Loss of Phase 2 mains is abnormal.
judgment
Loss of Phase 3
6)Input setting
No Parameters Range(defaults) Notes
℃/KPA
℃/BAR
Pressure/Tem ℃/PSI
1 Unit display.
perature unit ℉/KPA
℉/BAR
℉/PSI
Coolant 0: Disable Choose the usual water temperature
temperature 1.Self-define resistance sensor, If the sensor used by the user is
sensor curve not the commonly used type, it can be
2.VDO 40-120℃ User-defined.
3: MEBAY-001B
4: SGH
5: SGD
6: SGX
2 7: CURTIS
8: DATCON
9: VOLVO-EC
10: 3015238
11:PT100
12: MEBAY-Mier
13: 13: WEICHAI 40-120℃
14: GENCON 40-120℃
15: From ECU
Action if
Disable
temperature Action if Water temperature sensor
3 Warning
sensor disconnected.
Alarm and stop
disconnected
When the temperature is over the preset
Temperature-
4 20-200℃(68℃) value, then temperature-up procession is
up stop
stopped in time.
When the water temperature is higher than
the alarm value and comes into high
High water
20-200℃ temperature delay but still higher (normal
5 temperature
(98℃) faults delay), then high temperature
alarm
alarms. if the value is set as 200, then the
high temperature alarm is disabled.
Alarm and stop: when the temperature is
higher than preset value or high
Warning temperature signal is valid, then controller
Action if high Alarm and stop will alarm and stop after normal faults
6
temperature Alarm and stop after delay.
unloading If setting as warning:the AUX. input should
be set as high temperature stop disabled
and input is valid. When the temperature
38
DC4xS/C GENSET CONTROLLER USER MANUAL

value is higher than the preset value or


high temperature alarm input signal is
valid, then controller only display warning
but not stop.
If setting as alarm and stop after
unloading:the AUX. input should be set as
high temperature stop and input is valid.
When the temperature value is higher than
the preset value or high temperature alarm
input signal is valid, then controller shall
start the unloading procession and stop
with alarm.
Oil pressure 0: Disable Choose the usual oil pressure sensor, If
sensor 1: Self-define resistance the sensor used by the user is not the
curve commonly used type, it can be User-
2: Self-define voltage curve defined.
3: Voltage type 1MPa-0-5V
4: Voltage type 1MPa-05-
4.5V
5: VDO 0-10Bar
6: MEBAY-003B
7 7: SGH
8: SGD
9: SGX
10: CURTIS
11: DATCON 10Bar
12: VOLVO-EC
13: 3015237
14: WEICHAI 0-0.6Mpa
15: GENCON 0-10BAR
16: From ECU
Action if oil
Disable
pressure
8 Warning Action if oil pressure sensor disconnected.
sensor
Alarm and stop
disconnected
When the oil pressure is lower than the
alarm value and comes into low oil
Low oil
0-999kpa pressure delay but still lower (normal faults
9 pressure
(103kpa) delay), then low oil pressure alarms. if the
alarm
value is set as 0, then the under speed
alarm is disabled.
If setting as warning,the AUX. input should
be set as Low oil pressure stop disabled
Action if low
Warning and input is valid. When the oil pressure
10 oil
Alarm and stop value is lower than the preset value or low
pressure
oil pressure alarm input signal is valid, then
controller only display warning but not stop.
Fuel level 0: Disable If the sensor used by the user is not the
11 sensor 1. Self-define resistance commonly used type, it can be User-
curve defined.

39
DC4xS/C GENSET CONTROLLER USER MANUAL

2. 0-100Ω
3. 100-0Ω
4. 0-107Ω
5. 107-0Ω
6. 0-180Ω
7. 180-0Ω
8. 180-10Ω
9. 10-180Ω
10. 120-10Ω
11.10-120Ω
12. 90-0Ω
13. 0-90Ω
14. 0-30Ω
15. 73-10Ω
16. 240-33Ω
17. 33-100Ω
18. 0-200Ω
19. 200-0Ω
20. 100-33Ω
Action if fuel Disable
12 Level sensor Warning Action if Fuel level sensor disconnected.
disconnected Alarm and stop
When the fuel level is lower than the value
and comes into low fuel level warning
delay but still lower (normal warning delay),
Low fuel level 0-100%
13 then low fuel level warns. If it is higher than
warning (20%)
the value then warning clears. If the value
is set as 0, then the low fuel level warning
is disabled.
When the fuel level is lower than the alarm
value and comes into low fuel level delay
Low fuel level 0-100%
14 but still lower (normal faults delay), then
alarm (0%)
low fuel level alarms. if the value is set as
0, then the low fuel level alarm is disabled.
15 AUX.INPUT 1 0-40 (18. Remote start) 0. Disable.
AUX.INPUT 2 0-40 (12. Gens un/loading 1. Low oil pressure alarm switch.
17
input) 2. High temperature alarm switch.
0-40 (1. Low oil pressure 3. Low water level warning switch.
19 AUX.INPUT 3 4. Low water level alarm switch.
alarm switch)
AUX.INPUT 4 5. Low fuel level warning input.
6. Low fuel level alarm input.
7. Charging failure warning: output when
charging failure.
8. Low oil pressure shutdown disabled:
0-40(2. High water valid if there is signal input.
21
temperature alarm switch) 9. High temperature shutdown disabled:
valid if there is signal input.
10. External instant warning input.
11.External instant alarm input.
12. Gens un/loading input: connect to the

40
DC4xS/C GENSET CONTROLLER USER MANUAL

gens loading switchs auxiliary point.


13. Mains un/loading input: connect to
auxiliary point of mains loading
switch.( Only for Dx42 series).
14. Shades status input.
15. Auto start disabled: gens will not start
if there is signal input whatever mains
normal or not.
16. Auto stop disabled: gens will not stop
if there is signal input whatever mains
normal or not.
17. Stop by radiator if high
temperature:The controller will
shutdown the gens after high speed
cooling down delay when temperature
is too high if this signal is valid and
gens under normal running . the
controller will shutdown the gens
directly if the signal is not valid.
18. Remote start(with load): the gens
comes into start procession if this signal
is valid and under auto mode.
19. Soundproof alarm: audio alarm output
is disabled if there is signal output.
20. Front face button disabled: any
button except for page button is
disabled if there is signal output.
21. Meter mode: all output are disabled,
alarm and warns are invalid. any button
except for page button is disabled.
22. Remote control mode: any button
except for page button is disabled if the
input is valid, LCD will display remote
mode.remote control module can
start/stop and monitor parameters
through front face buttons.
23. Idle speed input;
24. Emergency stop alarm input;
25. Speed up pulse input;
26. – 40. Reserved.
AUX.INPUT 1 0-Normal close
16
valid 1-Normal open
AUX.INPUT 2 0-Normal close
18
valid 1-Normal open
The status of switch value input valid.
AUX.INPUT 3 0-Normal close
20
valid 1-Normal open
AUX.INPUT 4 0-Normal close
22
valid 1-Normal open

41
DC4xS/C GENSET CONTROLLER USER MANUAL

7) Output setting
AUX.OUTPUT 0-50(1. Public warning 0. Disable.
1
1 output) 1. Public warning output: when there is any
AUX.OUTPUT 0-50(2. Public alarm warning output.
2
2 output) 2. Public alarm output: when there is any
AUX.OUTPUT alarm output, alarm locks till revert back.
3 0-50(17.E.S.T. hold) 3. Audio alarm: when there is any alarm
3
output, the Audio controls.
4. Shades control: there is output once
genset starts and stop till stable.
5. Preheat mode 1: preheat before start.
6. Pre-oil supply control: Under pre-oil
supply,if the oil pressure is higher than
setting value or pre-oil supply time ends,
then pre-oil supply stopped.
7. Fuel output: output once gens starts and
off till stable.
8. Crank output: output once cranking, no
output in other mode.
9. Genset running: output under running,off
once RPM is lower than cranking RPM.
The crank success condition can be set.
10. Idle speed control 1: used for speed
controller, there is output under idle but no
output under high speed.
11.Speed-up control: during the procession
of speed increasing, the output time is the
Longest RPM-up time.
AUX.OUTPUT 0-50 (10. Idle speed 12. High speed control: The output is valid
4 after idle delay is completed, and the
4 control)
output is closed after high-speed heat
dissipation.
13. Excitation output: there is output during
cranking procession and there is 2s output
if there is no frequency under high speed
status.
14. Gens load: continuous or pulse type
according to time setting.
15. Gens unload: continuous or pulse type
according to time setting.
16. Speed-down control: the output time is
shutdown idle delay during shutdown idle
or shutdown on power procession.
17. E.S.T. hold: shutdown output, it is used for
gens with stop solenoid. when the setting
value of shutdown delay is over, then it is
off.
18. System in stop: there is output under
stop mode.
19. System in manual: there is output under
manual mode.
42
DC4xS/C GENSET CONTROLLER USER MANUAL

20. System in auto: there is output under


auto mode.
21. Fuel pump output: there is output if the
oil capacity is lower than start condition for
10s and shutdown if it is higher than the
shutdown condition for 1s.
22. Battery charging control: there is output
if the voltage is lower than the preset value
under standby status and shutdown after
start and in running status.
23. Mains load: continuous or pulse type
according to time setting. Only for DC42
series.
24. Mains unload: continuous or pulse type
according to time setting. Only for DC42
series.
25. Idle speed control 2: used for speed
controller, there is output under idle but no
output under high speed.
26. Rated running: there is output under
rated running.
27. ECU power: apply to electrical ECU
engine, used for control ECU power.
28. ECU stop: apply to electrical ECU engine,
used for control ECU shutdown.
29. ECU warning: there is a warn signal from
ECU.
30. ECU alarm: there is an alarm signal from
ECU.
31. ECU communication failure: Cannot
communicate with ECU.
32. Fan control: When the engine
temperature is higher than the "open fan
temperature value", it will output, and it will
be disconnected when it is lower than the
"close fan temperature value".
33. Pulse speed up output: the pulse shall
be sent out in the interval of “Pulse speed
up delay” under speed –up.
34. Pulse speed down output:the pulse
shall be sent out in the interval of “Pulse
speed down delay” under stop idle speed.
35. Public unload: Public unload of Gens and
Mains.
36. Preheat mode 2: Preheat stops after
successful start.
37. Preheat mode 3: Preheat stops after
safety delay.
38. Preheat mode 4: Preheat stops after
Temp.-up time.
39. Preheat mode 5: Preheat stops after
43
DC4xS/C GENSET CONTROLLER USER MANUAL

Temp.-up time,no preheat start the motor;


40. -50: Reserved

8)CAN communication
NO Parameter Range(default) Notes
1 CAN failure Disable ECU communication failure.
Warn
Alarm and Stop
2 ECU warning Disable/Enable ECU warnings enable.
3 ECU alarm Disable/Enable ECU alarms enable.
4 Mask SPN 0-12 Up to 12 sets of alarm codes can be input,
and the controller will not respond to the
input alarm codes.
5 Rated idle speed 500-4500rpm ECU idle speed value.
(750rpm)
6 Slow rise time 0-120.0S(5.0S) The time of ECU from idling to high speed.

9)Module settings
NO Parameter Range(default) Notes
0-English
1-简体中文
2-繁体中文
1 Language Language option.
3-español
4-русский
5-Türk dili
Select the instrument communication
0: Slave mode mode, the host can read and display the
2 Host and slave mode
1: Host mode parameters of the slave through the RS485
port.
00000-65535
3 User password Change the password.
(07623)
4 Controller ID 1-255(16) The IP built by controller and PC.
0-4800
1-9600
2-19200
5 RS485 baud rate RS485 communication baud rate.
3-38400
4-57600
5-115200
STOP The primary modes on power, easy for
Manual user operation.
6 Primary Modes
Auto Note: auto record function can’t record the
Auto save mode with load.
Start screen display
7 0-20.0s (5.0s) Start screen display time,0: No-display.
time
8 LCD contrast 50-127(106) Set the LCD display contrast.
5.0-6000.0s LCD light will be closed automatically
9 Saving mode
(600.0s) without any button pressed after delay. If
44
DC4xS/C GENSET CONTROLLER USER MANUAL

setting as 6000.0s, back light always


lighted.
The time when the page reverts back to
5.0-600.0s
10 Homing display the home page. If setting as 600.0s:
(600.0s)
disabled.
Start screen will be opened without any
LOGO delay display 5.0-6000.0
11 button pressed after delay. If setting as
under standby (6000.0s)
6000.0s: disabled.

a) Working plan and maintenance setting


No Parameter Range(defaults) Notes
This mode must be under auto mode.
Working plan is disabled once setting as
disable.
Disable The working plan will be executed
1 Working plan format Every month according the chosen date when setting as
Every week every month.
The working plan will be executed
according the chosen date when setting as
every week.
From 1st to 31st
Maintenance date per
2 Default: the first The date chosen for every month.
month
day
Maintenance date per Monday to Sunday
3 The date chosen for every week.
week Default: Sunday
Maintenance with load To choose if the genset starts with load or
4 Disabled/with load
or not not.
5 Maintenance start time 00:00-23:59(00:00) Maintenance start time setting.
Maintenance running
6 1-120m(5min) Maintenance running time setting.
time

b) working plan
No Parameter Range(default) Notes
Disable
Enable 1: remote start
1 Working plan Enable 2: running always Working plan start condition.
Enable 3: the above 1 or 2
Enable 4:running always
2 Start time 00:00-23:59 (08:00) The start time allowed.
The end time allowed (the next day is
3 End time 00:00-23:59 (17:00)
valid).
Multiple choices according to the reality.
4 Dates 1-31
The longest running time is 24 hours.

c) Maintenance plan
No Parameter Range(defaults) Notes
1 Maintenance 0-5000h(5000h) When it is set as 5000, then this function
45
DC4xS/C GENSET CONTROLLER USER MANUAL

countdown is disabled.
Maintenance When it is set as 2000/01/01, this function
2 2000/01/01-2099/12/31
date is disabled.
Maintenance Warning The action after the primary maintenance
3
expire Alarm and stop expired.
d) Data/time setting
No Parameter Range(defaults) Notes
1 Date/Time 2016/01/01-2099/12/31
Internal calendar, please calibrate
2 Current time 00:00:00-23:59:59
regularly.
3 Current week Monday to Sunday
e) Self-define curve
NO Parameter Notes
1 Self-define oil pressure resistance curve Sensor curve can be User-defined by
2 Self-define oil pressure voltage curve panel buttons, resistance and
3 Self-define water temperature curve according value should be input, MAX
15 groups, MIN 2 groups.
4 Self-define fuel level curve Rule: resistance should be input
from small to large.
12. Fault finding
Symptoms Possible Solutions
Controller no response Check DC voltage. Check DC fuse.
with power Check if the terminal 1 and 2 is with battery voltage.
Check the water/cylinder temperature is too high or not.
Genset shutdown Check the genset AC voltage.
Check DC fuse.
Check whether the emergency stop button is normal;
Genset Emergency
Check whether the AUX.IPUT is configured correctly;
Stop
Check whether the controller cable is normal.
Check oil pressure sensor and its wiring.
Check the oil pressure sensor type and controller settings must
Low oil pressure alarm
be consistent.
Check whether the low oil pressure sensor is normal.
Check temperature sensor and its wiring.
High temperature Check the temperature sensor type and controller settings must
alarm be consistent.
Check whether the temperature sensor is normal.
Check related switch and its connections according to the
Shutdown Alarm in
information on LCD.
running
Check AUX.INPUT.
Check fuel return circuit and wiring.
Fail to start Check start battery.
Consult engine manual.
Starter motor does not Check the wiring to the starter.
respond Check start battery.
Unit operation but ATS Check the ATS.
does not switch Check the cable between the controller and the ATS.
USB communication is Check the USB connection.
abnormal Check whether the USB port of the computer is normal.

46
DC4xS/C GENSET CONTROLLER USER MANUAL

Check whether the USB driver is installed.


Check the connection.
Check if the communication ID number setting is correct.
RS485 cannot Check if the A and B lines of RS485 are reversed.
communicate normally Check if the RS485 communication line driver is installed or not.
Check if the communication port of the PC is damaged.
Add a 120 Ω resistor between the AB of the controller RS485.
Get information from LCD of alarm page; If there is detailed
ECU warning or stop alarm, check engine according to description. If not, please
refer to engine manual according to SPN alarm code.

47