DC42C Mebay
DC42C Mebay
DC40S/C
DC42S/C
0
DC4xS/C GENSET CONTROLLER USER MANUAL
Software Version
No. Version Date Note
1 V1.0 2021-02-01 Original release.
Increase the charging coil signal detection
function;
2 V1.1 2022-01-24
Increase public open-circuit output, mains
phase loss setting
1
DC4xS/C GENSET CONTROLLER USER MANUAL
Symbol Description
Symbol Description
2
DC4xS/C GENSET CONTROLLER USER MANUAL
Warning
1. The installation of this equipment must be carried out by professionals.
2. When installing and operating the controller, please read the entire instruction
manual first.
3. Any maintenance and commissioning of the equipment must be familiar with all the
equipment.
4. Safety standards and precautions in advance, otherwise it may cause personal
injury or damage to related equipment.
5. The engine must have an overspeed protection device independent of the
controller system to avoid casualties or other damage caused by engine out of
control.
6. After the installation of the controller is completed, please verify that all protection
functions are valid.
Be Care
1. Please keep the good connection of the power supply of the controller. Do not
share the connection lines of the positive and negative electrodes of the battery
with the floating charger.
2. During the operation of the engine, do not disconnect the battery, otherwise it may
cause damage to the controller.
3
DC4xS/C GENSET CONTROLLER USER MANUAL
CATALOGUE
1. Summary............................................................................................................................... 5
2. Main Features...................................................................................................................... 5
3. Parameters Display............................................................................................................. 6
4. Protection.............................................................................................................................. 7
5. Parameters........................................................................................................................... 7
7. Installation instruction....................................................................................................... 17
Notes:
1. All rights reserved. No part of this duplication may be reproduced in any material
form (including photocopying or storing in any medium by electronic means or others)
without the written permission of the copyright holder.
2. MEBAY Technology reserves the rights to change the contents of this document
without prior notice.
4
DC4xS/C GENSET CONTROLLER USER MANUAL
1. Summary
This series controller is specialized for Diesel / Gasoline / Gas Genset Start,
Stop, Parameters monitoring, faults-checking as well as data setting.
2.8 inch LCD screen display with brand new UI design is adapted in this
controller that the relative failures can be displayed directly. All the parameters can
be displayed by simulated indicators and words. Besides, LCD screen can display
various faults in the same time that the genset will be stopped once it can’t work
smoothly.
There are Chinese/English interface options, more language can be set
according to user’s request. All the parameters can be configured through the front
face buttons or use programmable interface by RS485 or USB to adjust via PC. It can
be widely applied for all kinds of auto control system of gensets.
2. Main Features
There are eight Models under DC4xS/C series.
DC40S: Used for single machine automation. Start/Stop through remote start
signal.
DC40SR: Based on DC40S, it adds RS485 port.
DC42S: Based on DC40S, it adds Mains monitoring and AMF (Mains/Generator
automatic switching control), especially suitable for the automation system composed
by mains and genset.
DC42SR: Based on DC42S, it adds RS485 port.
DC40C: Used for single machine automation. Start/Stop through remote start
signal. it adds CAN port.
DC40CR:Based on DC40C, it adds RS485 port.
DC42C: Based on DC40C, it adds Mains monitoring and AMF (Mains/Generator
automatic switching control), especially suitable for the automation system composed
by mains and genset.
DC42CR: Based on DC42C, it adds RS485 port.
Dual core 32bit high performance single chip microcomputer.
2.8 inch 240 * 128 high-resolution LCD screen, Available in 6 languages, user’s
language set if necessary.
Indicator and number display through UI surface.
Acrylic material is adapted to protect the screen.
Silicone panels;
USB Port: parameters can be set even without power through USB port to monitor
in real time.
With RS485 communication port, can achieve “Three Remote” functions via
MODBUS protocol.
Standard CAN communication port, built-in J1939 protocol, has matched more
than 40 kinds of engines;
Various kinds of parameters display.
Input/output function, status can be shown directly.
Real time clock inside: preset time operate and auto maintenance is available.
Genset working plan can be set as per week or month.
5
DC4xS/C GENSET CONTROLLER USER MANUAL
6
DC4xS/C GENSET CONTROLLER USER MANUAL
7
DC4xS/C GENSET CONTROLLER USER MANUAL
8
DC4xS/C GENSET CONTROLLER USER MANUAL
9
DC4xS/C GENSET CONTROLLER USER MANUAL
Cable cross
No. Function Description
sectional area
1 Battery Negative Input B- Controller power supply input B-. 2.5mm2
2 Battery Negative Input B+ Controller power supply input B+. 2.5mm2
3 Fuel Output +VE output, Max 5Amp 1.5mm2
4 Crank Output +VE output, Max 5Amp. 1.5mm2
5 Charging excitation output +VE output, Max 0.9Amp. 1.0mm2
6 Aux. Output 1 +VE output, Max 1Amp. 1.0mm2
7 Aux. Output 2 +VE output, Max 1Amp. 1.0mm2
8 Aux. Output 3 +VE output, Max 1Amp. 1.0mm2
9 Aux. Output 4 +VE output, Max 1Amp. 1.0mm2
10 Sensor common GND Connect the battery negative or outer. 1.0mm2
11 Oil pressure sensor Connect sensor input. 1.0mm2
12 Temperature Sensor Oil pressure sensor compatible with 1.0mm2
13 Fuel level sensor resistance/voltage sensors; 1.0mm2
Connect the power supply of the oil
14 +5V Output pressure sensor with the output voltage 1.0mm2
signal, with a maximum of 50mA.
15 Speed sensor + 1.0mm2
Use a shielded wire to connect the speed
16 Speed sensor - 1.0mm2
sensor.
17 Speed sensor SCR 1.0mm2
15 CAN _H 1.0mm2
A 120 Ω shielded wire and good grounding
16 CAN_ L 1.0mm2
are recommended.
17 CAN _SCR 1.0mm2
18 RS485_B 1.0mm2
A 120 Ω shielded wire and good grounding
19 RS485_A 1.0mm2
are recommended.
20 RS485_SCR 1.0mm2
21 Aux. Input 1 1.0mm2
22 Aux. Input 2 The grounding is valid according to the 1.0mm2
23 Aux. Input 3 function selection switch input. 1.0mm2
24 Aux. Input 4 1.0mm2
Connected to the power generation output R
25 Generator Voltage U 1.0mm2
phase.
Connected to the power generation output S
26 Generator Voltage V 1.0mm2
phase.
Connected to the power generation output T
27 Generator Voltage W 1.0mm2
phase.
Connected to the power generation output N
28 Generator Voltage N2 1.0mm2
phase.
10
DC4xS/C GENSET CONTROLLER USER MANUAL
U P1 P2
TO LOAD SWITCHING
S1 S2
V P1 P2
S1 S2
DEVICE
W P1 P2
S1 S2
N2
RS485_SCR
RS485_B
RS485_A
33 34 35 36 25 26 27 28 8 9 29 30 31 32 18 19 20
IA IB IC ICOM U V W N2 R S T N1 A B SCR
GEN CURRENT GEN VOLTS
DC40S SERIES MAIN VOLTS RS485
(AC 0~5A) (AC0-300V) (AC0-300V)
SENSOR
MAX 5A MAX 1A INPUTS (0-1000R) MPU USB
1 2 3 4 5 6 7 8 9 21 22 23 24 10 11 12 13 14 15 16 17
+5V_MAX 50mA
SCR
CRANK
+ -
FUEL
1. OIL PRESSURE(R/U)
SENSOR COM_GND
2. TEMPERATURE
AUX. OUTPUT 1
AUX. OUTPUT 2
AUX. OUTPUT 3
AUX. OUTPUT 4
3. FUEL LEVEL
AUX. INPUT 1
AUX. INPUT 2
AUX. INPUT 3
AUX. INPUT 4
AC
D+ WL
1-70VPP
+
0-10KHz
BATTERY
8-36V
ALT
-
11
DC4xS/C GENSET CONTROLLER USER MANUAL
The charging coil can only be connected to pin 15 ,the speed sensor is
connected to pins 15, 16 or 15, 17.
Note: Please don’t move battery during running status or it may cause the
controller broken!
MECHANICAL INTERLOCK
TO LOAD SWITCHING
DEVICE
CTs MUST BE 5AMP SECONDARY
L1 L2 L3 N
FROM GENERATOR
U P1 P2 R
S1 S2
FROM MAINS
V P1 P2 S
S1 S2
W P1 P2 T
S1 S2
N2 N1
ELECTRICAL
INTERLOCK
G M
RS485_SCR
RS485_B
RS485_A
33 34 35 36 25 26 27 28 8 9 29 30 31 32 18 19 20
IA IB IC ICOM U V W N2 R S T N1 A B SCR
GEN CURRENT GEN VOLTS
DC42S SERIES MAIN VOLTS RS485
(AC 0~5A) (AC0-300V) (AC0-300V)
SENSOR
MAX 5A MAX 1A INPUTS (0-1000R) MPU USB
1 2 3 4 5 6 7 8 9 21 22 23 24 10 11 12 13 14 15 16 17
+5V_MAX 50mA
SCR
CRANK
+ -
FUEL
1. OIL PRESSURE(R/U)
SENSOR COM_GND
2. TEMPERATURE
AUX. OUTPUT 1
AUX. OUTPUT 2
AUX. OUTPUT 3
AUX. OUTPUT 4
3. FUEL LEVEL
AUX. INPUT 1
AUX. INPUT 2
AUX. INPUT 3
AUX. INPUT 4
AC
D+ WL
1-70VPP
+
0-10KHz
BATTERY
8-36V
ALT
-
12
DC4xS/C GENSET CONTROLLER USER MANUAL
The charging coil can only be connected to pin 15 ,the speed sensor is
connected to pins 15, 16 or 15, 17.
Note: Please don’t move battery during running status or it may cause the
controller broken!
U P1 P2
TO LOAD SWITCHING
S1 S2
V P1 P2
S1 S2
DEVICE
W P1 P2
S1 S2
N2
RS485_SCR
RS485_B
RS485_A
33 34 35 36 25 26 27 28 8 9 29 30 31 32 18 19 20
IA IB IC ICOM U V W N2 R S T N1 A B SCR
GEN CURRENT GEN VOLTS
DC40C SERIES MAIN VOLTS RS485
(AC 0~5A) (AC0-300V) (AC0-300V)
SENSOR
MAX 5A MAX 1A INPUTS (0-1000R) CAN USB
1 2 3 4 5 6 7 8 9 21 22 23 24 10 11 12 13 14 15 16 17
CAN_SCR
+5V 50mA
CRANK
CAN_H
CAN_L
FUEL
1. OIL PRESSURE(R/U)
SENSOR COM_GND
2. TEMPERATURE
AUX. OUTPUT 1
AUX. OUTPUT 2
AUX. OUTPUT 3
AUX. OUTPUT 4
AUX.
AUX.
AUX.
AUX.
Note: Please don’t move battery during running status or it may cause the
controller broken!
TO LOAD SWITCHING
DEVICE
CTs MUST BE 5AMP SECONDARY
L1 L2 L3 N
FROM GENERATOR
U P1 P2 R
S1 S2
FROM MAINS
V P1 P2 S
S1 S2
W P1 P2 T
S1 S2
N2 N1
ELECTRICAL
INTERLOCK
G M
RS485_SCR
RS485_B
RS485_A
33 34 35 36 25 26 27 28 8 9 29 30 31 32 18 19 20
IA IB IC ICOM U V W N2 R S T N1 A B SCR
GEN CURRENT GEN VOLTS
DC42C SERIES MAIN VOLTS RS485
(AC 0~5A) (AC0-300V) (AC0-300V)
SENSOR
MAX 5A MAX 1A INPUTS (0-1000R) CAN USB
1 2 3 4 5 6 7 8 9 21 22 23 24 10 11 12 13 14 15 16 17
CAN_SCR
+5V 50mA
CRANK
CAN_H
CAN_L
FUEL
1. OIL PRESSURE(R/U)
SENSOR COM_GND
2. TEMPERATURE
AUX. OUTPUT 1
AUX. OUTPUT 2
AUX. OUTPUT 3
AUX. OUTPUT 4
Note: Please don’t move battery during running status or it may cause the
controller broken!
14
DC4xS/C GENSET CONTROLLER USER MANUAL
U P1 P2
TO LOAD SWITCHING
S1 S2
DEVICE
N2
RS485_SCR
RS485_B
RS485_A
33 34 35 36 25 26 27 28 8 9 29 30 31 32 18 19 20
IA IB IC ICOM U V W N2 R S T N1 A B SCR
GEN CURRENT
DC40 SERIES RS485
GEN VOLTS MAIN VOLTS
(AC 0~5A) (AC0-300V) (AC0-300V)
USB
1 PHASE 2 WIRE
TO LOAD SWITCHING
DEVICE
CTs MUST BE 5AMP SECONDARY
L1 N
FROM GENERATOR
U P1 P2 R
S1 S2
FROM MAINS
N2 N1
ELECTRICAL
INTERLOCK
G M
RS485_SCR
RS485_B
RS485_A
33 34 35 36 25 26 27 28 8 9 29 30 31 32 18 19 20
IA IB IC ICOM U V W N2 R S T N1 A B SCR
GEN CURRENT GEN VOLTS
DC42 SERIES MAIN VOLTS RS485
(AC 0~5A) (AC0-300V) (AC0-300V)
USB
1 PHASE 2 WIRE
15
DC4xS/C GENSET CONTROLLER USER MANUAL
U P1 P2
TO LOAD SWITCHING
S1 S2
V P1 P2
S1 S2
DEVICE
N2
RS485_SCR
RS485_B
RS485_A
33 34 35 36 25 26 27 28 8 9 29 30 31 32 18 19 20
IA IB IC ICOM U V W N2 R S T N1 A B SCR
GEN CURRENT GEN VOLTS
DC40 SERIES MAIN VOLTS RS485
(AC 0~5A) (AC0-300V) (AC0-300V)
USB
2 PHASE 3 WIRE
TO LOAD SWITCHING
DEVICE
CTs MUST BE 5AMP SECONDARY
L1 L2 N
FROM GENERATOR
U P1 P2 R
S1 S2
FROM MAINS
V P1 P2 S
S1 S2
W T
N2 N1
ELECTRICAL
INTERLOCK
G M
RS485_SCR
RS485_B
RS485_A
33 34 35 36 25 26 27 28 8 9 29 30 31 32 18 19 20
IA IB IC ICOM U V W N2 R S T N1 A B SCR
GEN CURRENT GEN VOLTS
DC42 SERIES MAIN VOLTS RS485
(AC 0~5A) (AC0-300V) (AC0-300V)
USB
2 PHASE 3 WIRE
16
DC4xS/C GENSET CONTROLLER USER MANUAL
7. Installation instruction
The controller is fixed by two special fixing members and screws, and the screws
of the metal fasteners cannot be too tight.
Panel Cutout: W1160mm*H90mm.
Note: If the controller is installed directly in the genset shell or other fluctuated
equipment, the rubber pad must be installed.
Battery Voltage Input
DC4xS/C controller is suitable for 8-36V DC battery voltage. Battery negative must
be reliably connected to the enclosure of the engine. The controller power supply B+
and B- must be connected to battery positive and negative, and the wire size must
not be less than 2.5mm2.
NOTE:
In case of floating charger connect charger output to battery positive and negative
directly, then, connect battery positive and negative poles to controller positive and
negative power supply.
Output and relay expansion
Note: All outputs of the controller are relay contacts. The maximum current
capacity is described in the "Parameters" in this manual. Please use it in the relay
current capacity. If an extended relay is needed, add a continuous current diode
(when the extended relay coil is DC) or a resistance-capacitance loop (when the
extended relay coil is AC) to both ends of the coil to prevent interference with the
controller or other equipment.
AC current input
Current transformer with rated secondary current 5A must be externally connected
to the controller current input.
17
DC4xS/C GENSET CONTROLLER USER MANUAL
If withstanding voltage test is conducted after the controller has already been
installed onto the control panel, please unplug all controller terminal connections in
order to prevent high voltage from damaging it.
Alarm Up
Warning OK/HOME
Running Down
LCD
DC42S/C
Alarm Up
Warning OK/HOME
Running Down
Manual Pressing this key will set the module into manual mode.
Auto Pressing this key will set the module into auto mode.
19
DC4xS/C GENSET CONTROLLER USER MANUAL
20
DC4xS/C GENSET CONTROLLER USER MANUAL
Longest
Longest Longest
voltage
speed temperature
built/
rated
increasing increasing warming Cooling
increasing up time runn-
time time running time
time ing
Start Stop
Rated speed idle
Safe idle
Crank time time time
test
time ETS
Long- solen-
est oid
Idle hold
Pre- pre-oil Start
heat supply Crank
Wait
delay delay delay Stop
After the manual start is successful, pressing the "automatic key" can be
converted into an automatic file. The specific working time is as follows:
Longest
Longest Longest
voltage
speed temperature
built/
rated Transfer
increasing increasing warming Cooling
increasing up time runn- back to
time time running time
time ing mains delay
Start Stop
Rated speed idle
Safe idle
Crank time time time
test
time ETS
Long- solen-
est oid
Idle hold
Pre- pre-oil Start
heat supply Crank
Wait
delay delay delay Stop
Start Stop
Rated speed idle
Safe idle
Crank time time time
test
time ETS
Long- solen-
Crank oid
Idle est
Auto Pre- pre-oil Start test Crank hold
Start heat supply Crank time rest Wait
delay delay delay delay time Stop
21
DC4xS/C GENSET CONTROLLER USER MANUAL
Note 1: During the Cranking time, the controller automatically detects the speed
signal, frequency signal and oil pressure value or the charging voltage (according to
the parameter setting) to reach the judgment condition of successful start, then the
judgment is that the start is successful and the motor relay is closed.
Note 2: Within the safety delay, only respond to emergency stop, immediate
stop, over speed, over frequency, Over voltage, ECU communication Failure,shutter
open abnormal, other alarms are not responded to.
Note 8: After entering rated operation, the Gens load relay output.
Note 10: If the stop key is pressed again during idle time, the idle time will be
canceled and the stop operation will be executed directly.
Notes: Warning is a non-serious failure state, which will not harm the gensets
system for the time being. It only reminds operators to pay attention to the situation
that does not meet the requirements and solve it in time to ensure the continuous
operation of the system. When the warning occurs, the gensets does not stop. Once
the fault is removed, the warning is automatically canceled.
22
DC4xS/C GENSET CONTROLLER USER MANUAL
23
DC4xS/C GENSET CONTROLLER USER MANUAL
screen.
25
DC4xS/C GENSET CONTROLLER USER MANUAL
Starting fault
Fail to Start
If the number of cranks exceeds the predetermined number of cranks, the failure of
start-up will be reported if the start-up of the generating unit is still unsuccessful.
"ALARM" lights on, without stopping the engine, and displays " Crank failure " on
the current fault screen.
Shutdown Alarms
Warning: After the Shutdown Alarm occurs, the system will be locked
immediately and the generator set will be stopped. Only after troubleshooting, press
key to clear the alarm, can it be re-operated.
Notes:When the shutdown alarm failure occurs, the "ALARM" lights will light
up and the generator unit automatically stops.
"ALARM" lights will light up, Generator stops running,and displays "High Temp
sensor" on the current fault screen.
alarm delay and the duration (Normal alarm delay) have not returned to normal, the
alarm of temperature sensor disconnected alarm is reported. "ALARM" lights will light
up, Generator stops running, displays "Temp sensor open" on the current fault
screen.
28
DC4xS/C GENSET CONTROLLER USER MANUAL
power alarm”, Then start alarm delay and the duration (Normal alarm delay) have
not returned to normal, the alarm of over power is reported. "ALARM" lights will light
up, Generator stops running, displays " Over power " on the current fault screen.
29
DC4xS/C GENSET CONTROLLER USER MANUAL
alarm of Emergency Stop is reported. "ALARM" lights will light up, Generator stops
running, and displays "Emergency stop" on the current fault screen.
Revert back to default: put password “97011” when coming into parameters
setting, then all the parameters can be set as defaults.
Note: the data can’t be saved if the user didn’t press and to confirm the
setting.
30
DC4xS/C GENSET CONTROLLER USER MANUAL
Parameter setting
1)Delay time setting
No Parameter Range(default) Notes
The time during the genset starts after the
1 Start delay 0-65000s(5.0s)
remote signal is valid.
The time needed to be preheated before
2 Preheat time 0-6500.0s (0.0s)
the starter on power.
Under pre-oil supply, if the oil pressure is
Longest pre-oil
3 0-180.0s(0.0s) higher than setting value, then pre-oil
supply
supply stopped.
Fuel output The time the fuel valve relay outputs before
4 1.0-60.0s (2.0s)
delay the motor operates.
5 Cranking time 3.0-60.0s (8.0s) The time when the starter is on power.
If crank failure, the waiting time before the
6 Crank rest time 3.0-60.0s (10.0s)
second test time.
Low oil pressure, high water temperature,
under speed, under frequency, under
7 Safety delay 1.0-60.0s (8.0s) voltage, charge failure are all invalid during
this time except for emergency stop and
over speed.
8 Start idle time 0-3600.0s (5.0s) Idle running time when crank successfully.
The longest speed-up time,during which
Longest RPM-up 0-3600.0s
9 time the system will exit once speed
time (120.0s)
increased successfully .
The longest warming-up time,during which
Longest Temp.-
10 0-3600.0s(0.0s) time the system will exit once temperature
up time
increased successfully .
The longest voltage-up time,during which
Longest Volt.-up 0-3600.0s
11 time the system will exit once voltage
time (120.0s)
increased successfully .
12 Warming-up time 0-3600.0s(10.0s) The time needed for loading.
After unloading, the time of cooling down
by radiator before stop. during the delay, if
13 Cooling time 0-3600.0s(30.0s)
the remote start signal is valid, then genset
will come into rated running.
14 Stop idle time 0-3600.0s (5.0s) Idle-speed running time.
15 E.T.S. hold time 0-600.0s (10.0s) Stop solenoid on power time.
If the RPM is 0 during the stop failure time,
16 Fail to stop 5-180.0s (30.0s)
then the stop failure time is no needed.
Emergency Emergency and over frequency alarm
17 0-10.0s (1.5s)
delay delay.
Normal alarm The alarm delay except for emergency
18 2.0-20.0s (5.0s)
delay stop and over frequency
Normal warning
19 1.0-20.0s (2.0s) The warning delay.
delay
Pulse speed up The interval time of the pulse speed up
20 0.1-60.0s(0.2s)
delay relay change.
Pulse speed The interval time of the pulse speed down
21 0.1-60.0s(0.2s)
down delay relay change.
22 Load 1.0-10.0s (5.0s) Gens loading and unloading pulse width,
31
DC4xS/C GENSET CONTROLLER USER MANUAL
2)Engine setting
No Parameter Range (defaults) Notes
1 CAN Protocol 0- Disabled CAN protocol Option: the Engine paramet
1: J1939 ers like RPM, oil pressure, water temperat
2: Cummins ISB ure are all from ECU data after choosing t
3: Cummins-CM850 he relative protocol.
4: Cummins QSX15-
CM570
5: Cummins-CM850-
PCC13X
6: Cummins-DCEC-
QSZ13
7: Cummins-CCEC-QSN
8: Perkins
9: Perkins-1100
10: Volvo
11: Volvo-EMS2
12: Volvo-EMS2b
13: Volvo-EDC4
14: Scania
15: Scania-kw2000
16: Scania-kw2k-coo
17: John Deere
18: mtu-ADEC
19: mtu-ADEC-SAM
20: mtu-ADEC-303
21: mtu-ADEC-304
22: BOSCH
23: GTSC1
24: MTSC1
25: YUCHAI-YCECU
32
DC4xS/C GENSET CONTROLLER USER MANUAL
33
DC4xS/C GENSET CONTROLLER USER MANUAL
34
DC4xS/C GENSET CONTROLLER USER MANUAL
3)Generator parameters
No Parameter Range(defaults) Notes
When the flywheel teeth are set as 0, the RPM
will be resulted by frequency.
Pole 2: 50Hz---3000RPM.
1 Gens poles 2/4/6/8(4)
Pole 4: 50Hz---1500RPM.
Pole 6: 50Hz---1000RPM.
Pole 8: 50Hz---750RPM
Disable
Gens phases:
1 phase 2 wire
No gens parameters can be displayed if setting
2 Gens AC system 2 phase 3 wire
as disable, which is applied to water pump
3 phase 3 wire
genset.
3 phase 4 wire
40.0-80.0Hz Setting generator rated frequency to choose the
3 Rated frequency
(50.0Hz) meter range and calculate the alarm value.
Rated frequency multiplying by this value is
regarded as under over frequency alarm value.
4 Over freq alarm 0-200% (114%)
When the Freq is higher than the value and
comes into over freq delay but still higher
35
DC4xS/C GENSET CONTROLLER USER MANUAL
4)Loading setting
No Parameter Range (default) Notes
1 CT rate 5-6000A(500A) Used for setting genset CT primary current.
Rated phase Setting generator phase current to choose the
2 5-6000A (500A)
current meter range and calculate the alarm value.
5-2000Kw Set total power of generator to choose the meter
Rated total
3 range and calculate the average loading rate and
power (276Kw)
alarm value.
Rated current multiplying by this value is regarded
as over current alarm value. When the current is
Phase current higher than the value and comes into over current
4 0-200% (100%)
over-load alarm delay but still higher (over current faults delay),
then over current alarms, If the value is set as
200, then the alarm is disabled.
Over phase When this parameter is set to 0, the over current
5 current 0-3600.0s (30s) delay is the inverse time; if not, the over current
delay delay is the time set for this parameter.
Over current This option will not take effect until the [23-Over
6 0.1-36.0 (36.0)
【inverse time】 phase current delay] is set to 0. The over current
36
DC4xS/C GENSET CONTROLLER USER MANUAL
5)Mains protection
No Parameter Range(defaults) Notes
Disable Choose the input, there is no display if setting as
1 Phase 2 Wire disable.
1 Phase 2 Phase 3 Wire
3 Phase 3 Wire
3 Phase 4 Wire
2 Mains under volt 55-330V(184V) When the mains voltage is lower than the "low
3 Revert under volt 55-330V(207V) voltage crank threshold" and comes into mains
low voltage delay(normal failure delay) but still
lower, then mains becomes invalid. If the voltage
become higher than "low voltage revert threshold"
during normal failure delay time, then it will not
alarm.
4 Mains over volt 55-330V(276V) When the mains voltage is higher than the" high
5 Revert over volt 55-330V(253V) voltage crank threshold" and comes into mains
high voltage delay(normal failure delay) but still
higher, then mains becomes invalid. If the voltage
become lower than "low voltage revert threshold"
during normal failure delay time, then it will not
alarm.
Mains normal 0.0-3600.0S The time from abnormal to normal, which is used
6
delay (10.0S) for ATS transfer.
Mains abnormal 0.0-3600.0S
7
delay (5.0S)
37
DC4xS/C GENSET CONTROLLER USER MANUAL
Loss of Phase 1 Set the phase loss condition to judge whether the
Loss of Phase
8 Loss of Phase 2 mains is abnormal.
judgment
Loss of Phase 3
6)Input setting
No Parameters Range(defaults) Notes
℃/KPA
℃/BAR
Pressure/Tem ℃/PSI
1 Unit display.
perature unit ℉/KPA
℉/BAR
℉/PSI
Coolant 0: Disable Choose the usual water temperature
temperature 1.Self-define resistance sensor, If the sensor used by the user is
sensor curve not the commonly used type, it can be
2.VDO 40-120℃ User-defined.
3: MEBAY-001B
4: SGH
5: SGD
6: SGX
2 7: CURTIS
8: DATCON
9: VOLVO-EC
10: 3015238
11:PT100
12: MEBAY-Mier
13: 13: WEICHAI 40-120℃
14: GENCON 40-120℃
15: From ECU
Action if
Disable
temperature Action if Water temperature sensor
3 Warning
sensor disconnected.
Alarm and stop
disconnected
When the temperature is over the preset
Temperature-
4 20-200℃(68℃) value, then temperature-up procession is
up stop
stopped in time.
When the water temperature is higher than
the alarm value and comes into high
High water
20-200℃ temperature delay but still higher (normal
5 temperature
(98℃) faults delay), then high temperature
alarm
alarms. if the value is set as 200, then the
high temperature alarm is disabled.
Alarm and stop: when the temperature is
higher than preset value or high
Warning temperature signal is valid, then controller
Action if high Alarm and stop will alarm and stop after normal faults
6
temperature Alarm and stop after delay.
unloading If setting as warning:the AUX. input should
be set as high temperature stop disabled
and input is valid. When the temperature
38
DC4xS/C GENSET CONTROLLER USER MANUAL
39
DC4xS/C GENSET CONTROLLER USER MANUAL
2. 0-100Ω
3. 100-0Ω
4. 0-107Ω
5. 107-0Ω
6. 0-180Ω
7. 180-0Ω
8. 180-10Ω
9. 10-180Ω
10. 120-10Ω
11.10-120Ω
12. 90-0Ω
13. 0-90Ω
14. 0-30Ω
15. 73-10Ω
16. 240-33Ω
17. 33-100Ω
18. 0-200Ω
19. 200-0Ω
20. 100-33Ω
Action if fuel Disable
12 Level sensor Warning Action if Fuel level sensor disconnected.
disconnected Alarm and stop
When the fuel level is lower than the value
and comes into low fuel level warning
delay but still lower (normal warning delay),
Low fuel level 0-100%
13 then low fuel level warns. If it is higher than
warning (20%)
the value then warning clears. If the value
is set as 0, then the low fuel level warning
is disabled.
When the fuel level is lower than the alarm
value and comes into low fuel level delay
Low fuel level 0-100%
14 but still lower (normal faults delay), then
alarm (0%)
low fuel level alarms. if the value is set as
0, then the low fuel level alarm is disabled.
15 AUX.INPUT 1 0-40 (18. Remote start) 0. Disable.
AUX.INPUT 2 0-40 (12. Gens un/loading 1. Low oil pressure alarm switch.
17
input) 2. High temperature alarm switch.
0-40 (1. Low oil pressure 3. Low water level warning switch.
19 AUX.INPUT 3 4. Low water level alarm switch.
alarm switch)
AUX.INPUT 4 5. Low fuel level warning input.
6. Low fuel level alarm input.
7. Charging failure warning: output when
charging failure.
8. Low oil pressure shutdown disabled:
0-40(2. High water valid if there is signal input.
21
temperature alarm switch) 9. High temperature shutdown disabled:
valid if there is signal input.
10. External instant warning input.
11.External instant alarm input.
12. Gens un/loading input: connect to the
40
DC4xS/C GENSET CONTROLLER USER MANUAL
41
DC4xS/C GENSET CONTROLLER USER MANUAL
7) Output setting
AUX.OUTPUT 0-50(1. Public warning 0. Disable.
1
1 output) 1. Public warning output: when there is any
AUX.OUTPUT 0-50(2. Public alarm warning output.
2
2 output) 2. Public alarm output: when there is any
AUX.OUTPUT alarm output, alarm locks till revert back.
3 0-50(17.E.S.T. hold) 3. Audio alarm: when there is any alarm
3
output, the Audio controls.
4. Shades control: there is output once
genset starts and stop till stable.
5. Preheat mode 1: preheat before start.
6. Pre-oil supply control: Under pre-oil
supply,if the oil pressure is higher than
setting value or pre-oil supply time ends,
then pre-oil supply stopped.
7. Fuel output: output once gens starts and
off till stable.
8. Crank output: output once cranking, no
output in other mode.
9. Genset running: output under running,off
once RPM is lower than cranking RPM.
The crank success condition can be set.
10. Idle speed control 1: used for speed
controller, there is output under idle but no
output under high speed.
11.Speed-up control: during the procession
of speed increasing, the output time is the
Longest RPM-up time.
AUX.OUTPUT 0-50 (10. Idle speed 12. High speed control: The output is valid
4 after idle delay is completed, and the
4 control)
output is closed after high-speed heat
dissipation.
13. Excitation output: there is output during
cranking procession and there is 2s output
if there is no frequency under high speed
status.
14. Gens load: continuous or pulse type
according to time setting.
15. Gens unload: continuous or pulse type
according to time setting.
16. Speed-down control: the output time is
shutdown idle delay during shutdown idle
or shutdown on power procession.
17. E.S.T. hold: shutdown output, it is used for
gens with stop solenoid. when the setting
value of shutdown delay is over, then it is
off.
18. System in stop: there is output under
stop mode.
19. System in manual: there is output under
manual mode.
42
DC4xS/C GENSET CONTROLLER USER MANUAL
8)CAN communication
NO Parameter Range(default) Notes
1 CAN failure Disable ECU communication failure.
Warn
Alarm and Stop
2 ECU warning Disable/Enable ECU warnings enable.
3 ECU alarm Disable/Enable ECU alarms enable.
4 Mask SPN 0-12 Up to 12 sets of alarm codes can be input,
and the controller will not respond to the
input alarm codes.
5 Rated idle speed 500-4500rpm ECU idle speed value.
(750rpm)
6 Slow rise time 0-120.0S(5.0S) The time of ECU from idling to high speed.
9)Module settings
NO Parameter Range(default) Notes
0-English
1-简体中文
2-繁体中文
1 Language Language option.
3-español
4-русский
5-Türk dili
Select the instrument communication
0: Slave mode mode, the host can read and display the
2 Host and slave mode
1: Host mode parameters of the slave through the RS485
port.
00000-65535
3 User password Change the password.
(07623)
4 Controller ID 1-255(16) The IP built by controller and PC.
0-4800
1-9600
2-19200
5 RS485 baud rate RS485 communication baud rate.
3-38400
4-57600
5-115200
STOP The primary modes on power, easy for
Manual user operation.
6 Primary Modes
Auto Note: auto record function can’t record the
Auto save mode with load.
Start screen display
7 0-20.0s (5.0s) Start screen display time,0: No-display.
time
8 LCD contrast 50-127(106) Set the LCD display contrast.
5.0-6000.0s LCD light will be closed automatically
9 Saving mode
(600.0s) without any button pressed after delay. If
44
DC4xS/C GENSET CONTROLLER USER MANUAL
b) working plan
No Parameter Range(default) Notes
Disable
Enable 1: remote start
1 Working plan Enable 2: running always Working plan start condition.
Enable 3: the above 1 or 2
Enable 4:running always
2 Start time 00:00-23:59 (08:00) The start time allowed.
The end time allowed (the next day is
3 End time 00:00-23:59 (17:00)
valid).
Multiple choices according to the reality.
4 Dates 1-31
The longest running time is 24 hours.
c) Maintenance plan
No Parameter Range(defaults) Notes
1 Maintenance 0-5000h(5000h) When it is set as 5000, then this function
45
DC4xS/C GENSET CONTROLLER USER MANUAL
countdown is disabled.
Maintenance When it is set as 2000/01/01, this function
2 2000/01/01-2099/12/31
date is disabled.
Maintenance Warning The action after the primary maintenance
3
expire Alarm and stop expired.
d) Data/time setting
No Parameter Range(defaults) Notes
1 Date/Time 2016/01/01-2099/12/31
Internal calendar, please calibrate
2 Current time 00:00:00-23:59:59
regularly.
3 Current week Monday to Sunday
e) Self-define curve
NO Parameter Notes
1 Self-define oil pressure resistance curve Sensor curve can be User-defined by
2 Self-define oil pressure voltage curve panel buttons, resistance and
3 Self-define water temperature curve according value should be input, MAX
15 groups, MIN 2 groups.
4 Self-define fuel level curve Rule: resistance should be input
from small to large.
12. Fault finding
Symptoms Possible Solutions
Controller no response Check DC voltage. Check DC fuse.
with power Check if the terminal 1 and 2 is with battery voltage.
Check the water/cylinder temperature is too high or not.
Genset shutdown Check the genset AC voltage.
Check DC fuse.
Check whether the emergency stop button is normal;
Genset Emergency
Check whether the AUX.IPUT is configured correctly;
Stop
Check whether the controller cable is normal.
Check oil pressure sensor and its wiring.
Check the oil pressure sensor type and controller settings must
Low oil pressure alarm
be consistent.
Check whether the low oil pressure sensor is normal.
Check temperature sensor and its wiring.
High temperature Check the temperature sensor type and controller settings must
alarm be consistent.
Check whether the temperature sensor is normal.
Check related switch and its connections according to the
Shutdown Alarm in
information on LCD.
running
Check AUX.INPUT.
Check fuel return circuit and wiring.
Fail to start Check start battery.
Consult engine manual.
Starter motor does not Check the wiring to the starter.
respond Check start battery.
Unit operation but ATS Check the ATS.
does not switch Check the cable between the controller and the ATS.
USB communication is Check the USB connection.
abnormal Check whether the USB port of the computer is normal.
46
DC4xS/C GENSET CONTROLLER USER MANUAL
47