Operating Range
Operating Range
Removing a device If a device shall be removed from an already running and commis‐
sioned network, proceed as follows:
Removing a device 1. Execute the system update order
n Check 1: The easYgen tries to close the GCB, but the gener‐
ator is not within its operating range (parame‐
ters 5800 Ä p. 322, 5801 Ä p. 322, 5802 Ä p. 322, or
5803 Ä p. 322).
n Check 2: The easYgen tries to synchronize the GCB, but the
busbar is not within the generator operating range (parame‐
ters 5800 Ä p. 322, 5801 Ä p. 322, 5802 Ä p. 322, or
5803 Ä p. 322).
n Check 3: The easYgen tries close the GCB in breaker transi‐
tion mode "Open transition" with GCB and MCB open status. In
this condition the busbar is expected as dead, but the busbar
voltage is NOT below the dead busbar detection limit (param‐
eter 5820 Ä p. 439).
n Check 4: The easYgen wants to close the GCB onto a dead
busbar, but the device cannot close the breaker because there
is at least one neighbor device recognized with a closed GCB.
n Check 5: The easYgen tries to synchronize the GCB, the MCB
is closed, but mains and/or bussbar are not within its operating
range (parameters 5810 Ä p. 368, 5811 Ä p. 368,
5812 Ä p. 368, or 5813 Ä p. 368).
n Check 6: The easYgen wants close the GGB, but the gener‐
ator minimum power is not reached.
n Check 7: The easYgen wants close the GGB in the Open
Transition Mode, but the generator minimum power is not
reached.
n Check 8: The easYgen wants synchronize the GGB , but the
generator minimum power is not reached.
n Check 9: (GGB control mode) The MCB or the GGB is closed
with min. one neighbor GCB is closed to the busbar. There is a
conflict, the external voltage monitoring of the Load Busbar sig‐
nals a "Dead load busbar", which cannot be the case.
n Check 10: The easYgen wants synchronize the GGB, the MCB
is closed, but the mains is not in operating range
n Check 11: The easYgen checks the plausibility of generator
and busbar, if GCB is closed and the engine runs without run-
up synchronization, but he operating range of generator OR
busbar is not matched.
n Check 12: The easYgen checks the phase rotation of gener‐
ator, busbar, and mains and a synchronisation shall be exe‐
cuted, but the phase rotation of all systems does not match.
(Synchronisation is blocked.)
NOTICE!
If load-dependent start/stop (refer to Ä Chapter
4.4.5.5 “Load Dependent Start/Stop (LDSS)”
on page 304) is enabled, this monitoring function
must be configured with a shutdown alarm class C,
D, E, or F) or disable load-dependent start/stop if
triggered to ensure that the next engine will be
started.
2660 Monitoring 2 [On] Monitoring of the operating range is carried out according to the following
parameters.
2663 Delay 2 1 to 999 s If one of the above mentioned conditions for an operating range failure is ful‐
filled, an alarm will be issued. If the respective condition is not fulfilled any‐
[30 s] more before the delay time expires, the delay time will be reset.