VESDA-E Power Supplies
VESDA-E Power Supply Units are uniquely Features
designed to complement the style and
appearance of VESDA-E aspirating smoke •
detectors (ASD) and are technically matched
charging capacity to meet the requirement of •
EN 54-4. Black and Silver
The STX variants are VdS approved and CE • Temperature compensated charging to
for use in territories where these approvals
•
territories where ISO 7240-4 is required. detectors
• Knockouts designed to line up with
Style STX product range VESDA-E detectors
Designed with the same width, colour and • External LED indication
styling of the VESDA-E detectors, the power
• Relay outputs for connection to
the general-purpose input for fault
and also incoproate an internal channel which accommodates the exhaust of the VESDA-E
monitoring.
• 230 Vac only
(RAL 7047) Listings / Approvals
detectors. •
VPS-220-STX & VPS-220-STX-SLV: 0.5 A load / 14 Ah batteries (max)
•
This is the shallower unit within the range with a depth and width matching the VESDA-E 0786-CPR-20783 and
detectors. 0786-CPR-20890
Internally is an EN54-4 approved Power Supply rated to provide a 0.5 Amp continuous 24 •
upto fan speed 6 for similar periods.
VPS-250-STX & VPS-250-STX-SLV: 2 A load / 24 Ah batteries (max)
This is the deeper unit designed for installation with a VESDA-E VEU detector running at fan
Installation arrangements
25mm
min
which line up with the VESDA-E
enclosure allowing positioning of the
VESDA-E detector. The PSU may also
detector as illustrated opposite. 10mm Inverted
min detector
The front cover supports 2 LEDs giving
a quick visual indication of OK and fault 150mm
condition. A change over fault relay is VPS min
PCB
the General Purpose Input (GPI) of the
Batteries
relay input.
Inverted &
backvented
VESDA-E Power Supplies
Technical Highlights
VPS-220-STX VPS-220-STX-SLV VPS-250-STX VPS-250-STX-SLV
•
very useful for initial commissioning of
Nominal AC
Xtralis detectors as mains power is often
Supply Voltage
(simpler alternatives may require mains
Power Output
power to be detected before they will start
Load to power a detector – even if healthy
(3 Amps not EN54-4) batteries are connected)
Dimensions • Style STX power supplies perform full
(H x W x D)
Weight
condition.
Temperature (simpler alternatives may tolerate weaker
batteries which are unlikely to be capable
Humidity of providing the required hold up time in
IP Rating IP 30 the event of a mains failure)
Batteries (not • Style STX units disconnect the load (i.e.
supplied by power down the Xtralis detector) after a
Xtralis) prolonged period of mains failure (>24
Recommended Yuasa NP (or equivalent) hours) to prevent permanent damage to
Battery
Indications (simpler alternatives may successfully
disconnect the load when the battery
Fault Relay
voltage fails but then reconnect it almost
immediately because the battery voltage
Fuse Rating tends to recover when the load is
removed. Such units then switch on and
off until the battery is permanently below
Cable Entries the minimum voltage putting undue stress
Various positions on the load and draining the batteries
Detector Exhaust Internal channel to route detector exhaust with 2 x 27 mm knockouts unnecessarily)
Color / Finish Matt Black or Grey (RAL 7047) • Style STX units use a tiny current
(< 3 mA) to monitor for restoration of
Mounting 4 x 5 mm holes on 286 x 240 centers
mains power after disconnecting the
* Note: 4x7AH is allowed by EN 54-4 but may not be compliant with installation codes (e.g. BS5839-1).
are unlikely to suffer a damaging deep
discharge as long as the fault is attended
Battery monitoring link: to within a week.
(simpler alternatives draw larger currents
Charge current link: to monitor for restoration of mains and
drive indicators when in load-shed so are
more likely to damage batteries by a deep
Note: EN 54-4 requires that batteries are recharged to 80% within 24 hours of a full discharge discharge)
while simultaneously supplying the maximum load current.
VPS-220-STX
VPS-250-STX
VPS-220-STX-SLV
VPS-250-STX-SLV
Note: Batteries are NOT included
www.xtralis.com
UK and Europe D-A-CH The Americas
Middle East Asia Australia and New Zealand
and without further notice. Except as otherwise provided, all warranties, express or implied, including without limitation any implied warranties of
.
Doc. no. 29635_02 Part. no. 30730