Manual de Servicio ASV18PSBANED ASV18PSBAXED
Manual de Servicio ASV18PSBANED ASV18PSBAXED
Manual de Servicio ASV18PSBANED ASV18PSBAXED
ASV12PSBBNED ASV12PSBBXED
ASV18PSBANED ASV18PSBAXED
Model Code ASV09PSBANXLA ASV09PSBAXXLA
ASV12PSBBNXLA ASV12PSBBXXLA
ASV18PSBANXLA ASV18PSBAXXLA
Air Conditioner
Mode
Mode can help you sleep quickly and
soundly and wake up refreshed.
Silence Mod
When you use the "Silence Mode", you can
experience extremely quiet operation of your
air conditioner.
ASV09(12)PSBAXED ASV18PSBAXED
Operating Instructions and Installation
Contents
11. Precautions ........................................................................................................................................ 1-1
1-1 Installing the air conditioner .......................................................................................................... 1-1
1-2 Power supply and circuit breaker .................................................................................................. 1-1
1-3 During operation .............................................................................................................................. 1-1
1-4 Disposing of the unit ....................................................................................................................... 1-2
1-5 Others ................................................................................................................................................. 1-2
Samsung Electronics 1
Operating Instructions and Installation
Contents
9. Refigerating Cycle Diagram
...................................................................................................................... 9-1
2 Samsung Electronics
1SFDBVUJPOT
*OTUBMMJOHUIFBJSDPOEJUJPOFS
O 6TFSTTIPVMEOPUJOTUBMMUIFBJSDPOEJUJPOFSCZUIFNTFMWFT
"TLUIFEFBMFSPSBVUIPSJ[FEDPNQBOZUPJOTUBMMUIFBJSDPOEJUJPOFSFYDFQUUIFXJOEPXUZQFBJSDPOEJUJPOFSJO64"BOE$BOBEB
O *GZPVEPOUJOTUBMMUIFBJSDPOEJUJPOFSQSPQFSMZ
JUNBZDBVTFBGJSF
BXBUFSMFBLBHFPSBOFMFDUSJDTIPDL
O :PVNVTUJOTUBMMUIFBJSDPOEJUJPOFSBDDPSEJOHUPUIFOBUJPOBMXJSJOHSFHVMBUJPOTBOETBGFUZSFHVMBUJPOT
O *OTUBMMUIFJOEPPSVOJUIJHIFSUIBONGSPNUIFGMPPSUPBWPJEUIFJOKVSZDBVTFECZUIFPQFSBUJPOPGUIFGBO
FYDFQUUIFXJOEPXUZQFBJSDPOEJUJPOFS
O 5IFNBOVGBDUVSFSJTOPUSFTQPOTJCMFGPSBOZBDDJEFOUTPSJOKVSZDBVTFECZBOJODPSSFDUJOTUBMMBUJPO
O 8IFOJOTUBMMJOHUIFCVJMUJOUZQFBJSDPOEJUJPOFS
LFFQBMMFMFDUSJDDBCMFTTVDIBTUIFQPXFSDBCMFBOEUIFDPOOFDUJPODPSEJOQJQFT
EVDUT
PSDBCMFDIBOOFMTUPQSPUFDUUIFNGSPNUIFEBOHFSPGJNQBDUPSBOZPUIFSJODJEFOUT
1PXFSTVQQMZBOEDJSDVJUCSFBLFS
O *GUIFQPXFSDPSEPGUIFBJSDPOEJUJPOFSJTEBNBHFE
JUNVTUCFSFQMBDFECZUIFNBOVGBDUVSFSPSBRVBMJGJFEQFSTPOJOPSEFSUPBWPJE
BIB[BSE
O 5IFBJSDPOEJUJPOFSNVTUCFQMVHHFEJOUPBOJOEFQFOEFOUDJSDVJUJGBQQMJDBCMFPSDPOOFDUUIFQPXFSDBCMFUPUIFBVYJMJBSZDJSDVJU
CSFBLFS
"OBMMQPMFEJTDPOOFDUJPOGSPNUIFQPXFSTVQQMZNVTUCFJODPSQPSBUFEJOUIFGJYFEXJSJOHXJUIBDPOUBDUPQFOJOHPGNN
O %POPUFYUFOEBOFMFDUSJDDPSEUPUIFBJSDPOEJUJPOFS
O 5IFBJSDPOEJUJPOFSNVTUCFQMVHHFEJOBGUFSZPVDPNQMFUFUIFJOTUBMMBUJPO
%VSJOHPQFSBUJPO
O %POPUSFQBJSUIFBJSDPOEJUJPOFSBUZPVSEJTDSFUJPO
*UJTSFDPNNFOEFEUPDPOUBDUBTFSWJDFDFOUFSEJSFDUMZ
O /FWFSTQJMMBOZLJOEPGMJRVJEPOUIFBJSDPOEJUJPOFS
*GUIJTIBQQFOT
UVSOPGGUIFBJSDPOEJUJPOFSBOEDPOUBDUBOBVUIPSJ[FETFSWJDFDFOUFS
O %POPUJOTFSUBOZUIJOHCFUXFFOUIFBJSGMPXCMBEFTUPQSFWFOUEBNBHFPGUIFJOOFSGBOBOEDPOTFRVFOUJOKVSZ
,FFQDIJMESFOBXBZGSPNUIFBJSDPOEJUJPOFS
O %POPUQMBDFBOZPCTUBDMFTJOGSPOUPGUIFBJSDPOEJUJPOFS
O %POPUTQSBZBOZLJOEPGMJRVJEJOUPUIFJOEPPSVOJU*GUIJTIBQQFOT
UVSOPGGUIFBJSDPOEJUJPOFSBOEDPOUBDUBTFSWJDFDFOUFS
O .BLFTVSFUIBUUIFBJSDPOEJUJPOFSJTXFMMWFOUJMBUFEBUBMMUJNFT
%POPUQMBDFBDMPUIPSPUIFSNBUFSJBMTPWFSJU
O 3FNPWFUIFCBUUFSJFTJGZPVEPOUVTFUIFSFNPUFDPOUSPMGPSBMPOHUJNF *GBQQMJDBCMF
O 6TFUIFSFNPUFDPOUSPMXJUIJONFUFSTGSPNUIFJOEPPSVOJU *GBQQMJDBCMF
4BNTVOH&MFDUSPOJDT
%JTQPTJOHPGUIFVOJU
O #FGPSFUISPXJOHPVUUIFBJSDPOEJUJPOFS
SFNPWFUIFCBUUFSJFTGSPNUIFSFNPUFDPOUSPM
O 8IFOZPVEJTQPTFPGUIFBJSDPOEJUJPOFS
DPOTVMUZPVSEFBMFS*GQJQFTBSFSFNPWFEJODPSSFDUMZ
SFGSJHFSBOUNBZCMPXPVUBOEDBVTF
BJSQPMMVUJPO8IFOJUDPOUBDUTXJUIZPVSTLJO
JUDBODBVTFTLJOJOKVSZ
O 5IFQBDLBHFPGUIFBJSDPOEJUJPOFSTIPVMECFSFDZDMFEPSEJTQPTFEPGQSPQFSMZGPSFOWJSPONFOUBMSFBTPOT
0UIFST
O /FWFSTUPSFPSMPBEUIFBJSDPOEJUJPOFSVQTJEFEPXOPSTJEFXBZTUPQSFWFOUUIFEBNBHFUPUIFDPNQSFTTPS
O :PVOHDIJMESFOPSJOGJSNQFSTPOTTIPVMECFBMXBZTTVQFSWJTFEXIFOUIFZVTFUIFBJSDPOEJUJPOFS
O .BYDVSSFOUJTNFBTVSFEBDDPSEJOHUP*&$TUBOEBSEGPSTBGFUZ
O $VSSFOUJTNFBTVSFEBDDPSEJOHUP*40TUBOEBSEGPSFOFSHZFGGJDJFODZ
4BNTVOH&MFDUSPOJDT
1SPEVDU4QFDJGJDBUJPOT
5IF'FBUVSFPG1SPEVDU
QCatechin Filter
QDeodorizing Filter
4BNTVOH&MFDUSPOJDT
MODEL ASV09PSBA/ED ASV12PSBB/ED ASV18PSBA/ED
ITEM Indoor Unit Outoor Unit Indoor Unit Outoor Unit Indoor Unit Outoor Unit
Type Wall-mounted Wall-mounted Wall-mounted Wall-mounted Wall-mounted Wall-mounted
Cooling KW 0.75/2.65/3.2 0.75/3.05/3.65 1.2/5.29/6.2
Capacity
Heating (Low/Std/Max) - - -
Samsung Electronics
2-2
2-3 The Comparative Specificati ons of Product
Develop Model
MODEL AR12HSFSAWK/ET AR18HSFSAWK/EU AR24HSFSAWK/EU
Indoor Unit
Design
Outdoor Unit
Samsung Electronics
2-2
DB97-02851C(09K/12K)
DB90-02738A(18K)
DB93-11489C
4301-000121
DB98-32440A(09K/18K)
DB68-03248A(12K)
2-5
2-6
"MJHONFOUBOE"EKVTUNFOUT
5FTU.PEF
Q)PXUP"QQSPBDI5FTU.PEF
:PVDBOBQQSPBDIUIF5FTU.PEFCZQSFTTJOHUIFPOPGGTXJUDIPG
JOEPPSVOJUGPSTFDPOET
POPGGTXJUDI
QZ5FTU.PEF0QFSBUJPO0QUJPO
"GUFSJOTUBMMJOHUIFBJSDPOEJUJPOFS
DIFDLXIFUIFSFBDITVCPSEJOBUFJTOPSNBMMZPQFSBUFEPSOPUCZPQFSBUJOHUIF5FTU.PEF
t8IFOBOFSSPSPDDVST
EJTQMBZUIF&SSPS.PEF
t0QFSBUJPO.PEF$PPMNPEF0QFSBUFUIFDPPMNPEFCZPQFSBUJOHUIFDPNQSFTTPSCZGPSDFXJUIPVUUIFDPNQSFTTPS0/0''
BDDPSEJOHUPUIFTFUUFNQFSBUVSFJOEPPSUFNQFSBUVSF %POPUGPMMPXUIFBOUJGSFF[FDPOUSPM
t6QEPXOMPVWFS6QEPXOTXJOHNPEF
t*OEPPS'BO)JHI
t#FDBVTFUIF5FTU.PEFPQFSBUFUIFDPPMNPEFCZGPSDFOPUSFMBUFEUPUIFTFUUFNQFSBUVSFJOEPPSUFNQFSBUVSF
DIFDL
XIFUIFSFBDITVCPSEJOBUFJTPQFSBUFEOPSNBMMZPSOPUBGUFSDPNQMFUJOHJOTUBMMBUJPOBOENVTUUVSOPGGUIFQPXFSPGUIF
BJSDPOEJUJPOFS
4BNTVOH&MFDUSPOJDT
■ ASV09PSBANED,ASV12PSBBNED
OPERA GOOD
TION
TIMER
SLEEP DESCRIPTION
○ ◎ ○ Indoor Room Temp Sensor Error
◎ ◎ ○ Evap In Temp Sensor Error
○ ○ ◎ Fan Error (Indoor)
◎ ◎ ◎ EEPROM Error
◎ ◎ ◎ Option Error
● LED ON
◎ LED BLINKING
○ LED OFF
■ ASV18PSBANED
DESCRIPTION
■ ASV09PSBAXED,ASV12PSBBNED
YEL GRN RED DESCRIPTION
○ ○ ○ Power Off
◎ ◎ ◎
Reset
● ● ●
○ ◎ ● Normal Operation
○ ○ ●
Abnormal Communication
○ ● ●
○ ○ ◎ IPM Over Current(O.C)
○ ◎ ○ Comp Starting Error
Heatsink Sensor Error
○ ◎ ◎
Heatsink Over Heat
DC-Link Voltage Under/Over Error
○ ● ◎
Over Voltage Protection Error
◎ ○ ● OLP Over Heat
◎ ◎ ○ OLP Sensor Error
◎ Current Sensor Error
◎ ●
Input Current Sensor Error
◎ Comp Vlimit Error
● ○
Comp Current Limit Error
◎ ● ● 1min. Time Out Comm.
● ○ ◎ OTP Error
● ○ ● Comp Wire Missing Error
● ◎ ◎ DC-Link Voltage Sensor Error
● ◎ ● I-Trip Error
● ● ◎ AC Line Zero Cross Signal Out
■ ASV18PSBAXED
4. Troubleshooting
4-1 Setting Option Setup Method
SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 SEG19 SEG20 SEG21 SEG22 SEG23 SEG24
NOTE:
SEG1,SEG7,SEG13,SEG19 need not to be pressed in,so in fact the Option No.we should press in is as below.
Caution:
The terminal is locking type.
So, when you separate terminals,
pull pressing the button.
Button
Caution:
When you separate the connector,
pull pressing the locking button.
Caution:
When you separate the connector,
pull pressing the locking button.
Caution:
When you separate the connector,
pull pressing the locking button.
Caution:
When you separate the connector,
pull pressing the locking button.
4-8
4-9
4-10
4-11
4-2 Outdoor Unit(ASV18PSBAXED)
4-12
5) Loosen 2 screw(CCW) on the right side of
Cabinet Front. (Use +Screw Driver)
4-13
8 3
4-15
1) Release Nut at Fan Boss
2) Release 3 screws st Motor Bracket.
3) Detach Motor Wire from the Assy Control Out.
4-16
3.EEPROM DOWNLOAD
1 Maldives High
EER (only) 1) Power off
4-17
1
F1,F2
(2pin)
F1,F2
(2pin)
4-18
1 8) Click the Start button
and reset the power
D ownload
6 ) CLICK
7 ) CLICK
8 ) CLICK
4-19
2 Maldives
1) Power off
Normal
EER (only)
3) Connect PC-Download
Jig-PBA
4-20
Download connector (10pin)
3) Connect PC-Download
Jig-PBA
5) CLICK
7) CLICK
8) CLICK
4-21
Operating Instructions and Installation
1-5
Parts List
Qty
No. Code No. Description Specification SA/SNA
ASV12(09)PSBAN* AQV12PSANXAX ASV12(09)PSBANXAZ
1 DB94-02534A ASSY BACK BODY ASSY 1 1 - SA
DB94-02534B ASSY BACK BODY ASSY - - 1 SA
1-1 DB61-03656A BODY BACK HIPS 1 1 1 SA
1-2 DB61-03651B SUPPORT-EVAP RH HIPS 1 1 1 SA
1-3 DB62-05888A SEAL-INSUL BODY REAR EPS(30) 1 1 1 SA
1-4 DB61-03666A HOLDER-PIPE HIPS 1 1 1 SA
1-5 DB93-08656A ASSY-SPI SLIM COMPACT ASSY 1 1 1 SA
2 DB97-02851C ASSY-PLATE HANGER SGCC-M, T0.7 1 1 1 SA
DB92-02280C ASSY PANEL FRONT ASSY 1 1 - SA
3
DB92-02280P ASSY PANEL FRONT ASSY - - 1 SA
3-1 DB64-02561A PANEL FRONT HIPS 1 1 1 SA
3-2 DB63-02760D FILTER-PRE PP 2 2 2 SA
3-3 DB97-11240C ASSY COVER TERMINAL ASSY 1 1 1 SA
3-4 DB90-06134A ASSY COVER DISPLAY ASSY 1 1 1 SA
3-5
DB64-02553C GRILLE-AIR INLET HIPS 1 1 - SA
DB64-02553E GRILLE-AIR INLET HIPS - - 1 SA
3-6 DB64-02550B DECO-GRILLE HIPS 1 1 1 SA
DB93-10953A ASSY CONTROL IN ASSY 1 1 - SA
4
DB93-10953B ASSY CONTROL IN ASSY - - 1 SA
4-1 DB93-10859G ASSY PCB MAIN IN PCB 1 1 1 SA
4-2 DB95-04570B ASSY THERMISTOR IN SENSOR 1 1 1 SA
5 DB90-04385A ASSY COVER CONTROL IN T0.5 1 1 1 SA
6 DB94-02960A ASSY TRAY DRAIN ASSY 1 1 - SA
DB94-02960B ASSY TRAY DRAIN ASSY - - 1 SA
6-1 DB63-02118A TRAY DRAIN ABS 1 1 1 SNA
6-2 DB61-03672A BLADE-V PP 2 2 2 SNA
6-3 DB66-01559A H
BLADE-H ABS 1 1 1 SA
6-4 DB62-05892A INSULATION-TRAY FR FR EPS(30) 1 1 1 SA
6-5 DB31-00371A MOTOR STEP DC12V,600gf.cm 1 1 1 SA
6-6 DB69-00839A CUSHION-TRAY RH EPS(30) 1 1 1 SA
6-7 DB63-02121A TRAY-STABILIZER HIPS 1 1 1 SA
DB94-00458D ASSY DRAIN-HOSE ASSY 1 1 - SA
6-8 DB94-00458E ASSY DRAIN-HOSE ASSY - - 1 SA
DB96-11359B ASSY EVAP TOTAL ASSY 1 1 - SA
7
DB96-12152G ASSY EVAP TOTAL ASSY - - 1 SA
7-1 DB61-03650A HOLDER-EVAP HIPS 1 1 1 SA
8 DB94-01874A ASSY-CROSS FAN ASSY AS +GF 30% 1 1 1 SA
8-1 DB94-00455B ASSY RUBBER BEARING ASSY 1 1 1 SA
DB31-00531D MOTOR FAN ASSY 1 1 SA
9 -
DB31-00531C MOTOR FAN ASSY - - 1 SA
28
12
29
31
3
Exploded Views and Parts List
Parts List
Q yt
No. Code No. Description Specification SA/SNA
AQ(S)V12(09)PSBA*
DB90-05752A ASSY CABI FRONT ASSY 1 SA
1
DB90-06424A ASSY CABI FRONT ASSY - SA
2 DB63-02588A GUARD FAN PP 1 SA
DB63-02004A GUARD FAN PP - SA
3 DB90-06226A ASSY BASE OUT ASSY 1 SA
4 DB90-05738A BRACKET-VALVE SGCC-M(PAINTED) 1 SA
5 DB31-00564A MOTOR FAN ASSY 1 SA
6 DB67-01042A FAN-PROPELLER PP-(GF+PD)40, Φ410 1 SA
7 6009-001369 SCREW-HEX M4, L12 3 SA
8 DB60-30004A SCREW-MACHINE M6,ZPC(WHT) 1 SA
9 DB90-06219B BRACKET MOTOR SGCC-M 1 SA
10 DB90-05736A ASSY CABINET-UPPER ASSY 1 SA
11 DB94-02998A ASSY-PARTITION ASSY 1 SA
12 DB27-00042B COIL CHOKE-REACTOR 5mH,15A 1 SA
13 DB96-15014A ASSY COND ASSY 1 SA
14 DB64-02444A SCREEN-COND BAR ASSY 1 SA
15 DB90-05751A ASSY CABINET-SIDE RH ASSY 1 SA
16 DB90-05740A ASSY COVER VALVE ASSY 1 SA
17 DB90-05749A ASSY CABINET-SIDE LF ASSY 1 SA
18 UG9A090FUBJPSS COMPRESSOR ROTARY 1 SA
19 6021-001142 NUT-HEXAGON FLANGE M5,ZPC(YEL) 1 SA
20 DB60-30028A SCREW-HEX M8,ZPC(WHT) 3 SA
21 DB99-01063A GROMMET ISOLATOR ASSY 3 SA
22 DB63-02310A COVER TERMINAL NORYL 1 SA
23 DB63-00817B GASKET EPDM RUBBER 1 SA
24 DB63-02863A FELT-COMP UPPER OUT FELT+PVC 1 SA
25 DB63-02861A FELT-COMP SIDE FELT 1 SA
26 DB63-02860A FELT-COMP SIDE OUT FELT+PVC 1 SA
27 DB63-02864A FELT-COMP BASE FELT 1 SA
28 DB93-10960A ASSY CONTROL OUT ASSY 1 SNA
29 DB96-15985A ASSY TUBE DISCHARGE ASSY 1 SA
30 DB96-14952B ASSY-VALVE CHECK ASSY 1 SA
31 DB96-15980A ASSY-TUBE SUCTION ASSY 1 SA
5-7
1
ASV12PSBBNED
5-1
Model
ASV18PSBANED
5-4 Ass'y ControlO ut
Model ASV18PSBAXED
6.Electric a l P ar ts List(18K)
INDOOR MAIN PCB DB93-10956C
18
Electrical Part List
SMPS
MODULE
CONTROL
MODULE
ZEROCROSS
MODULE
ASV12PSBBNED
n g l
u
s nt i a
a m de
S nf i
C o
ASV18PSBANED
SMPS
MODULE
ZERO CROSS
n g l
u
s nt i a
a m d e
S nf i
COMMUNICATION
C o
ASV09PSBAXED/ASV12PSBBXED
SENSOR/OLP
MODULE
COMP DRIVE
MODULE
ZEROCROSS
MODULE CURRENT SENSOR
MODULE
CONTROL
MODULE
SMPS
MODULE
EMI,SURGE,INRUSH
MODULE PFC
MODULE
ASV18PSBAXED
ASV09PSBANED
ASV12PSBBNED
ASV18PSBANED
CN81
CN43
CN32
CN72
CN31
CN21
1.CN21-COMMUNICATION
2.CN31-DOWNLOAD
3.CN32-FJM
4.CN43-TEMPRATURE SENSOR
5.CN91-DISPLAY
6.CN81-MPI
7.CN61-STEP MOTOR
8.CN71-POWER IN
9.CN72-FAN MOTOR
ASV09PSBAXED/ASV12PSBBXED
10-2
ASV18PSBAXED
Main parts
Room
temperature
sensor
Air intake
indicator
Operation indicator
Power button
ASV18PSBAXED
Remote controller display Power
Smart Saver
Mode
Less energy usage makes your space
Set one of the 5 operating modes
cool between the temperature range
(see pages 10-11 for instructions).
of 24°C~30°C.
Auto Clean
Turbo Auto clean function – Dry inside of the indoor
Operate in auto fan speed to unit to get rid of odor.
cool quickly.
Quiet Air swing
Reduce noise generated from an indoor
unit during operation. automatically up and down.
Temp + - Fan
Increase/Decrease the temperature by 1˚C.
such as Auto/Low/Medium/High.
Set the mode on.
Set
On Timer
Set the timer/ mode.
Set the On Timer on.
Cancel
Cancel the timer/ mode.
Time Up/Time Down
Adjust the time for timer/
mode.
This button doesn't have any function.
5SPVCMFTIPPUJOH
*UFNTUPCFDIFDLFEGJSTU
5IFJOQVUWPMUBHFTIPVMECFSBUJOHWPMUBHFSBOHF
5IFBJSDPOEJUJPOFSNBZOPUPQFSBUFQSPQFSMZJGUIFWPMUBHFJTPVUPGUIJTSBOHF
*TUIFMJOLDBCMFMJOLJOHUIFJOEPPSVOJUBOEUIFPVUEPPSVOJUMJOLFEQSPQFSMZ
5IFJOEPPSVOJUBOEUIFPVUEPPSVOJUTIBMMCFMJOLFECZDBCMFT
$IFDLUIFUFSNJOBMTJGUIFJOEPPSVOJUBOEPVUEPPSVOJUBSFQSPQFSMZMJOLFECZUIFTBNFOVNCFSPGDBCMFT
0UIFSXJTFUIFBJSDPOEJUJPOFSNBZOPUPQFSBUFQSPQFSMZ
8IFOBQSPCMFNPDDVSTEVFUPUIFDPOUFOUTJMMVTUSBUFEJOUIFUBCMFCFMPXJUJTBTZNQUPNOPUSFMBUFEUPUIFNBMGVODUJPOPGUIF
BJSDPOEJUJPOFS
/P 0QFSBUJPOPGBJSDPOEJUJPOFS &YQMBOBUJPO
5IF01&3"5*0/JOEJDBUJPO-&% #-6&
CMJOLTXIFOBQPXFS *UJOEJDBUFTQPXFSJTPO5IF-&%TUPQTCMJOLJOHJGUIFPQFSBUJPO
QMVHPGUIFJOEPPSVOJUJTQMVHHFEJOGPSUIFGJSTUUJNF 0/0''CVUUPOPOUIFSFNPUFDPOUSPMVOJUJTQVTIFE
'BOTQFFETFUUJOHJTOPUBMMPXFEJO%3:
NPEF 5IFTQFFEPGUIFJOEPPSGBOJTTFUUP--JO%3:NPEF
'BOTQFFEJTTFMFDUFEBVUPNBUJDBMMZJO"650NPEF
$PNQSFTTPSTUPQTPQFSBUJPOJOUFSNJUUFOUMZJO%3:
$PNQSFTTPSPQFSBUJPOJTDPOUSPMMFEBVUPNBUJDBMMZJO%3:NPEF
NPEF EFQFOEJOHPOUIFSPPNUFNQFSBUVSFBOEIVNJEJUZ
5JNFS-&% 03"/(&
PGUIFJOEPPSVOJUMJHIUTVQBOEUIF 5JNFSJTCFJOHBDUJWBUFEBOEUIFVOJUJTJOSFBEZNPEF
BJSDPOEJUJPOFSEPFTOPUPQFSBUF 5IFVOJUPQFSBUFTOPSNBMMZJGUIFUJNFSPQFSBUJPOJTDBODFMMFE
5IFDPNQSFTTPSTUPQTJOUFSNJUUFOUMZJOB$00-NPEFPS 5IFDPNQSFTTPSTUPQTJOUFSNJUUFOUMZPSUIFGBOTQFFEPGUIF
%3:NPEF
BOEGBOTQFFEPGUIFJOEPPSVOJUEFDSFBTFT JOEPPSVOJUEFDSFBTFTUPQSFWFOUJOTJEFPVUTJEFBJSGSP[FO
EFQFOEJOHPOUIFJOTJEFPVUTJEFBJSUFNQFSBUVSF
<*ODBTFPGIFBUQVNQNPEFM> 5IFDPNQSFTTPSBOEJOEPPSGBOTUPQJOUFSNJUUFOUMZJGSPPN
5IFDPNQSFTTPSBOEJOEPPSGBOTUPQJOUFSNJUUFOUMZJO)&"5 UFNQFSBUVSFFYDFFETBTFUUJOHUFNQFSBUVSFJOPSEFSUPQSPUFDU
NPEF UIFDPNQSFTTPSGSPNPWFSIFBUFEBJSJOB)&"5NPEF
<*ODBTFPGIFBUQVNQNPEFM> 5IFDPNQSFTTPSPQFSBUFTJOBSFWFSTFDZDMFUPSFNPWF
*OEPPSGBOBOEPVUEPPSGBOTUPQPQFSBUJPOJOUFSNJUUFOUMZ FYUFSJPSJDFJOB)&"5NPEF
BOEJOEPPSGBOBOEPVUEPPS
JOB)&"5NPEF GBOEPOPUPQFSBUFJOUFSNJUUFOUMZGPSXJUIJOPGUIFUPUBM
IFBUFSPQFSBUJPO
4BNTVOH&MFDUSPOJDT
Communication error
1.Checklist :
1) Is the cable between the indoor unit and outdoor unit connected correctly?
2) Isn't the power cable and communication cable cross?
2. Troubleshooting procedure
Restart after power off.
YES
NO
Is the connection of power cable
Correct the wrong cable.
and communication cable normal?
YES
NO
Is the communication error Terminate the service.
occurred again?
YES
1.Checklist :
1) Is the indoor units temperature sensor connected correctly?
2) Is the sensor placed correctly?
3) Does the both terminal of sensor satisfy the resistance value in accordance with temperature?
Sensor Replace
Is the sensor resistance value #1-#2
NO Sensor resistance value : 20℃ - 12.09kohm
10kohm±3% at the room
30℃ - 8.31kohm
temperature
35℃ - 6.94kohm
of 25℃
40℃ - 5.83kohm
YES
YES
Below 0.5V or Over 4.5V? Exchange the indoor PBA
NO
YES
12-3
Indoor Eva-in temperature sensor error
1.Checklist :
1) Is the indoor units temperature sensor connected correctly?
2) Is the sensor placed correctly?
3) Does the both terminal of sensor satisfy the resistance value in accordance with temperature?
2. Troubleshooting procedure
Sensor Replace
Is the sensor resistance value #3-#4
NO Sensor resistance value : 20℃ - 12.09kohm
10kohm±3% at the room
30℃ - 8.31kohm
temperature
35℃ - 6.94kohm
of 25℃
40℃ - 5.83kohm
YES
YES
Below 0.5V or Over 4.5V? Exchange the indoor PBA
NO
YES
12-4
When the Up/Down louver motor does not operate (Initial Diagnosis) (Not displayed)
1.Checklist :
1) Is the input power voltage normal?
2) Is the Up/Down louver motor properly connected with the connector? (CN61)
2. Troubleshooting procedure
Unplug the power cord and plug it after 30seconds
later.
YES
NO
Is the connected louver wire? Connect the wire PBA to louver motor
YES
NO
YES
12-5
When the remote control is not receiving
1.Checklist :
1) Check if the connector was normally assembled.
2) Check the battery in remote control
3) All the lights out and check again : Change electronic typed to a fluorescent light
4) Put the set in operation and check the voltage of display PBA
5) Replace the display PBA
12-6
Indoor fan motor speed detecting error (AC fan)
1.Checklist :
1) Is the indoor units fan motor properly connected with the connector(CN72)?
2) Is the AC voltage correct?
3) Is the HALL IC(feedback sensing) in indoor fan motor properly connected with the connector(CN44)?
4) Is the running capacitor(CR71) properly connected with PBA?
2. Troubleshooting procedure
YES
YES
YES
NO
Is the supply voltage of the fan PBA should be
PBA is out of order
motor sufficient? replaced
Test location Normal
PBA CN72 Condition voltage
Fan About AC
pin #3~#5
operate 180V
Motor fan-capacitor is Motor fan capacitor
out of order should be replaced
YES
Fan motor
Fan motor is out of order
should be replaced
12-7
OLP sensor error/OLP over heat
1.Checklist :
1) Is the sensor connected correctly?
2) Is the sensor placed correctly?
3) Does the both terminal of sensor satisfy the resistance value in accordance with temperature?
4) Is the resistance value of sensor connection pull-up correct?
5) Check the compressor locking or gas leak
2. Troubleshooting procedure
YES
Sensor Replace
Is the sensor resistance value #3-#4
NO Sensor resistance value : 20℃ - 242kohm
200kohm±3% at the room
30℃ - 166ohm
temperature
35℃ - 138ohm
of 25℃
40℃ - 115kohm
YES
YES
Below 0.5V or Over 4.5V? Exchange the Outdoor PBA
NO
12-8
Compressor starting error
1.Checklist :
1) Is the connection of cable for the compressor?
2) Is the compressor wire is connected clockwise? U(RED)-V(BLU)-W(YEL)
3) Is the interphase resistance of compressor normal?
2. Troubleshooting procedure
NO
Is the restart error occurred again? Terminate the service
YES
NO
Is the connection of compressor
wire is normal? Connect the comp wire normally
YES
NO
Is the restart error occurred again? Terminate the service
YES
YES
Is the compressor body and
Exchange the Outdoor PBA
interphase resistance insulated?
NO
12-9
Compressor wire missing error/rotation error
1.Checklist :
1) Is the connection of cable for the compressor?
2) Is the compressor wire is connected clockwise? U(RED)-V(BLU)-W(YEL)
3) Is the interphase resistance of compressor normal?
2. Troubleshooting procedure
Restart after power off.
NO
Is the restart error occurred again? Terminate the service
YES
YES
NO
Is the restart error occurred again? Terminate the service
YES
YES
Is the compressor body and
Exchange the Outdoor PBA
interphase resistance insulated?
NO
12-10
O.C(Over Current) error
1.Checklist :
1) Is the IPM Shunt(R451,R452,R453) resistance value correct? Check the resistor is opened
2) Is the condition of surrounding temperature abnormal overload?
3) Is there any problem as like the temperature sensor separation or measurement value error?
4) Is the interphase resistance of compressor normal?
2. Troubleshooting procedure
Restart after power off.
NO
Is the O.C error occurred? Terminate the service
YES
NO
Is the connection of compressor
wire is normal? Connect the comp wire normally
YES
NO
Is the O.C error occurred again? Terminate the service
YES
YES
YES Is the O.C error NO Terminate the
occurred again? service
YES
NO
12-11
DC_link voltage sensor error
1.Checklist :
1) Is the input voltage of outdoor terminal block is normal?
2) Is the reactor wire connected?
3) Is the DC_link capacitor(CE101,CE102,CE103) assembled in accordance the specification? (Outdoor PBA)
4) Is the DC_link resistor(R104,R106,R107,R108) value is normal?
2. Troubleshooting procedure
Is the connected of reactor wire? NO
Connect the reactor wire
(PBA-Reactor)
YES
YES
YES
NO
Is the reactor insulation damaged? Exchange the Outdoor PBA
YES
12-12
DC_link voltage under/over error, Over voltage protection error/PFC over load
1.Checklist :
1) Is the input voltage of outdoor terminal block is normal?
2) Is the input voltage is higher than 300Vac?
3) Is the reactor wire connected?
4) Is the DC_link capacitor(CE101,CE102,CE103) assembled in accroance the specification? (Outdoor PBA)
5) Is the DC_link resistor(R104,R106,R107,R108) value is normal?
2. Troubleshooting procedure
YES
YES
YES
YES
NO
Is the reactor insulation damaged? Exchange the Outdoor PBA
YES
12-13
I_trip error, PFC over current
1.Checklist :
1) Is the PFC Shunt(R062,R063) resistance value correct? Check the resistor is opened
2) Is the condition of surrounding temperature abnormal overload?
3) Is there any problem as like the temperature sensor separation or measurement value error?
4) Is the interphase resistance of compressor normal?
2. Troubleshooting procedure
Restart after power off.
YES
Is the I_trip error NO Terminate the
YES occurred again? service
YES
YES
12-14
Current sensor error/Input current sensor error
1.Checklist :
1) Is the PFC Shunt(R062,R063) resistance value correct? Check the resistor is opened
2) Is the IPM Shunt(R451,R452,R453) resistance value correct? Check the resistor is opened
3) Is there no short or open around IC451?
2. Troubleshooting procedure
Restart after power off.
Is the PFC shunt and IPM shunt NO Exchange the Outdoor PBA
resistance value correct?
YES
YES
12-15
Heatsink sensor error/Heatsink over heat
1.Checklist :
1) Are there screws assembly in PBA-heatsink?
2) Is the gap PBA-heatsink
3) Is the fan operation normal?
4) Is the cover assembly in conrol-box normal?
2. Troubleshooting procedure
YES
YES
12-16
Comp Vlimit error/Comp current limit error
1.Checklist :
1) Is the IPM Shunt(R451,R452,R453) resistance value correct? Check the resistor is opened
2) Is the condition of surrounding temperature abnormal overload?
3) Is there any problem as like the temperature sensor separation or measurement value error?
4) Is the interphase resistance of compressor normal?
2. Troubleshooting procedure
Restart after power off.
NO
Is the O.C error occurred? Terminate the service
YES
NO
Is the connection of compressor
wire is normal? Connect the comp wire normally
YES
NO
Is the O.C error occurred again? Terminate the service
YES
YES
YES Is the O.C error NO Terminate the
occurred again? service
YES
NO
12-17
EEPROM error/OTP error
1.Checklist :
1) Is there a short around micom?
2) Is there a short around IC502?
3) Did you download or insert EEPROM IC, after changing outdoor PBA?
2. Troubleshooting procedure
power off and download EEPROM data
(or. Insert the service EEPROM IC)
YES
1.Checklist :
1) Check the power condition at customer's house (Is there any power noise?)
2) Have been there power failure?
2. Troubleshooting procedure
Restart after power off
YES
12-19
No power indoor (Initial Diagnosis) (Not displayed)
1.Checklist :
1) Is input power normal?
2) Is AC power linked correctly?
3) Is input voltage of DC_link capacitor normal?
4) Is the voltage of DC regulator normal?
2. Troubleshooting procedure
Unplug the power cord
YES
YES
YES
YES
12-20
No power outdoor (Initial Diagnosis) (Not displayed)
1.Checklist :
1) Is input power normal?
2) Is AC power linked correctly?
3) Is the cable connected correctly between indoor and outdoor unit?
4) Is there AC power in indoor terminal block?
5) Is the cable connected correctly between Terminal block and PBA?
6) Is input voltage of SMPS DC_link capacitor normal?
7) Is the voltage of SMPS normal?
2. Troubleshooting procedure
YES
Is the voltage of indoor unit NO Check the wiring from indoor terminal block to
terminal block correctly? N(1)-1 : indoor PBA
230Vac Exchange the indoor PBA
YES
Check the cable connection from indoor unit to
Is the voltage of outdoor unit NO outdoor unit
terminal block correctly? N(1)-1 : The remote control signal receiver on the display
230Vac PBA is wrong . Check the display board
YES
Is the input voltage of outdoor NO Check the wiring from outdoor terminal block to
PBA correctly? CN001-CN002:
outdoor PBA
230Vac
YES
YES
12-22
Heatsink sensor error/Heatsink over heat
1.Checklist :
1) Are there screws assembly in PBA-heatsink?
2) Is the gap PBA-heatsink
3) Is the fan operation normal?
4) Is the cover assembly in conrol-box normal?
YES
YES
12-23
12-3-1 Pre-inspection Notices
1. Check if you pulled out the AC power plug when you eliminate the PCB or front panel
2. Don't hold the PCB side not impose excessive force on it to eliminate the PCB
3. Don’t pull the lead wire but hold the whole housing to connect or disconnect a connector to the PCB
4. In case of outdoor PCB disassembly, check first the complete discharge of condenser after 1 minute power off
12-33
12-3-4 Outdoor detailed inspection procedure
No procedure Inspection Method Cause
. Over current
Plug out and pull the PCB out of
. AC part and pattern short of Indoor
the control box 1) Is 1st fuse disconnected?
1 PBA
Check the PCB fuse 2) Is indoor PBA faulty?
. AC part and pattern short of Outdoor
(Wait 3 minutes after power off)
PBA
1) Is the Compressor wire connected
clockwise?
2) Is the Reactor wire connected
. Wrong assembly
2 Check the Wiring normal?
. Installation(service) condition is bad
3) Is the Fan wire connected normal?
4) Is the 4way wire connected normal?
5) Is the sensor wire connected
Check the power voltage
1) Is the voltage between Terminal . Power cord is faulty, Indoor PBA
block N(1)-1 200Vac~240Vac? fault, Wrong Power cable Wiring
. L,N,E wire wrong wiring (Terminal
Block-PBA)
2) Is the PFC050(#26-#27) input . Fuse open
voltage 200Vac~240Vac? . PTC020 open
. RY021, RY022 is faulty
. Outdoor Micom(IC151) error
Supply power and operate the set . Power circuit is faulty
3 (Use Remote-control, button in 3) Is the CE151 voltage 280Vdc~320dc?
. Load short
indoor set) . PFC050 is faulty
3) Is the CE101 voltage 280Vdc~320dc?
. Reactor wire is wrong connection
. Switching Trans of Power circuit is
4) Is the voltage CE157 voltage 15Vdc? faulty
. Load short
. Switching Trans of Power circuit is
5) Is the voltage CE155 voltage 12Vdc? faulty
. Load short
. Switching Trans of Power circuit is
6) Is the voltage CE153 voltage
faulty
3.3Vdc?
. Load short
1) Normal : RED on, GRN blink, YEL off
2) Abnormal
. L,N,C wire wrong wiring
4 Check the LED lamp display - All off : check no power
. Outdoor PBA is faulty
- abnormal display : check error
mode
12-33
4
01230
#MPDL%JBHSBN
*OEPPS6OJU
015*0/
$0/530--&3
*$.$6
)&"5&9$)"/(&34&/403
t#-"%&$0/530-
300.5&.1&3"563&4&/403 t*/%003'"/.0503$0/530-
t065%003$0..6/*$"5*0/
%*41-":1"35
*/'3"3&%4*(/"- t108&33&-":$0/530-
t5&.1&3"563&$0/530- 5&.1&3"563&
t5*.&3 01&3"5*0/
t#6;;&3.&-0%:$0/530- "650$-&"/
t"/*0/$0/530- 563#0
&/&3(:4"7*/(
5*.&3
04$*--"5*0/
$*3$6*5 "/*0/
;&30 '"/41&&%
3&.05&$0/530- 70-5"(&
%&5&$5
108&30/0''
53*((&3
t$0.13&4403$0/530- 4*(/"-
.0%& 4*(/"-
"650
$00-
%3:
'"/
t45&11*/(.0503
)&"5
$0/530-4*(/"- 443 */%003'"/.0503
t#6;;&3.&-0%:$0/530-
563#001&3"5*0/ 4*(/"-
$0..6/*$"5*0/
t"/*0/$0/530-4*(/"- 065%0036/*5
4*(/"-
'"/41&&%4&-&$5 ).-
"650
$0.13&4403
065%003'"/.0503
#-"%&) 8":7"-7&
.07*/(4&-&$5 #6;;&3
t45&11*/(.0503%3*7&
t#6;;&3%3*7&
0/
0''5*.&3 "/*0/
4&-&$5$"/$&- t"/*0/%3*7&
45&11*/(.0503
5&.1&3"563& #-"%&$0/530-
4&-&$5 61%08/
4-&&101&3"5*0/ .&-0%:$0/530-1"35
%$7
"/*0/4&-&$5 70-5"(&3&(6-"503
41&",&3
"650$-&"/4&-&$5
015*0/
&/&3(:4"7*/(4&-&$5
%$7
4.14108&3#-0$,
406/%0/0''4&-&$5
%*(*5"- 0/0''
%$7
%$7
"$7
"$*/165
%$7
4BNTVOH&MFDUSPOJDT
1 3 -2
ASV09PSBAXED/ASV12PSBBXED
13-2
ASV18PSBAXED
A S V 1 8 H B A X
Ex.) Maldives (Grille – White) Heat Pump12k Btu/h Model Indoor Unit
A Q V 1 2 P W A N
(1), (2) Product Division (6) Project (7) Grille Color (8) Version
A Mont Blanc (Premium) B Black A-K SSEC
AS Cooling Only B Cry stal - Temporary
S Silver L-S TSE
AQ Heat Pump Max(including Smart)
C W White
- Temporary
D Mont Blanc (Deluxe) F La Fleur (9) Unit
(3) Inverter E Cry stal (V ivaldi Deluxe) U Blue N Indoor Unit
V Inverter F Forte
G Grey X Outdoor unit
G GP
None Non Inverter H HB
J W W Premium
(4), (5) Capacity K Jungfrau-PRM
L Forte Deluxe
09 9,000 Btu
M Moderato
12 12,000 Btu N Neo Forte
18 18,000 Btu P Maldives
R Max Smart (V ivaldi Std)
24 24,000 Btu
S Forte Smart (SSEC)
T Boracay
U Max (V ivaldi Standard)
V V ivace
W WW
X Forte Smart (TSE)
Y Jungfrau-DLX
14-2 Low Refrigerant Pressure Distribution
Note : Please measure the refrigerant pressure after the air conditioner operates on testing cooling mode during more than
10 minutes.
* *
* *
Outdoor Temperature[ ]
Q1PXFS)FBU
8 DBMT LDBMI #UVI )1 LH NT *C NT
4BNTVOH&MFDUSPOJDT
2"GPS/POUSPVCMF
2 5IFDPPMJOHJTXFBL
" 8
IFOJUJTIPUPVUTJEF
JUTDPPMJOHDBQBDJUZEFDSFBTFTEVFUPUIFJODSFBTFPGUIFBNCJFOUUFNQFSBUVSF8IFO
UIFEVTUGJMUFSHFUTCMPDLFEPSXBSNPVUTJEFBJSHFUTJO
UIFDPPMJOHDBQBDJUZXJMMEFDSFBTF4P
NBLFTVSFUP
DMFBOUIFEVTUGJMUFSGSFRVFOUMZ
QSFWFOUIFBUMPTTCZDMPTJOHUIFEPPSTBOEJOTVMBUFUIFDPPMJOHBSFBCZVTJOH
DVSUBJOT
CMJOET
TIBEFTPSXJOEPXUJOUJOH
2 5IFDPPMJOHJTHPPEHFOFSBMMZ#VU JUHFUTXFBLXIFOJUJTDPOTJEFSBCMZIPU
2 *UGBJMTUPEPDPPMJOH
" 8
IFOUIFBJSDPOEJUJPOFSJTTFUUP7FOUJMBUJPOPSUIFEFTJSFEUFNQFSBUVSFJTTFUIJHIFSUIBOUIF
DVSSFOUUFNQFSBUVSF
JUGBJMTUPEPDPPMJOH*OUIJTDBTF
TFMFDU$PPMJOHPSTFUUIFEFTJSFEUFNQFSBUVSFMPXFS
2 *UGMPPETUIFGMPPS
2 8BUFSESJQTBUUIFESBJODPOOFDUJPO TFSWJDFWBMWF
PGUIFPVUEPPSVOJU
" 8
IFOBHMBTTCPUUMFJTUBLFOPVUPGUIFSFGSJHFSBUPS
NPJTUVSFHFUTDPOEFOTFEPOJUTTVSGBDFEVFUPUIF
UFNQFSBUVSFEJGGFSFODFT5IFTBNFQSJODJQMFBQQMJFTUPUIFBJSDPOEJUJPOFS8IFODPMESFGSJHFSBOUHPFT
UISPVHIUIFDPQQFSUVCF
NPJTUVSFHFUTDPOEFOTFEPOUIFTVSGBDFPGUIFUVCFBOEUIFDPOOFDUJPOBSFBT
-FBLBHF 5PQSFWFOUUIFXBUFSDPOEFOTBUJPO
UIFQJQFTBSFJOTVMBUFE#VU
UIFDPOOFDUJPOBSFBTPGUIFPVUEPPSVOJUBSF
OPUJOTVMBUFEGPSUIFQVSQPTFPGNBJOUFOBODFPSSFQBJS
BOEXBUFSHFUTDPOEFOTFEEVFUPUIFUFNQFSBUVSF
EJGGFSFODFTBOEESJQTEPXO(FOFSBMMZ
JUFWBQPSBUFTSJHIUBXBZ#VU
XIFOJUESJQTNVDIEVSJOHNVHHZEBZT
QVUBXBUFSQBOPOUIFGMPPS
2 *UMFBLTFWFOUIPVHIBESBJOQVNQJTVTFE
" * UPDDVSTXIFOUIFESBJOQVNQJTQMVHHFEPVUPSJUJTPVUPGPSEFS$IFDLUIFQPXFSPGUIFESBJOQVNQBOE
UIFQPTJUJPOPGUIFESBJOIPTF
BOEXIFOUIFQVNQJTGBVMUZ
DPOUBDUUIFESBJOQVNQNBOVGBDUVSFS4BNTVOH
&MFDUSPOJDTEPOPUNBOVGBDUVSFESBJOQVNQT4P
XFBSFOPUBCMFUPDPSSFDUUIFESBJOQVNQQSPCMFNT
2 8IFOFWFSUIFBJSDPOEJUJPOFSJTUVSOFEPO JUJSSJUBUFTNZFZFTBOEHJWFTNFBIFBEBDIF
" 5 IFSFBSFOPDPNQPOFOUTJOUIFBJSDPOEJUJPOFSJSSJUBUJOHUIFFZFTBOETFOEJOHPVUDIFNJDBMTNFMMT
#VU
XIFOUIFBJSDPOEJUJPOFSJTUVSOFEPO
PUIFSTNFMMTPVSDFTBSFTVDLFEJOUPUIFBJSDPOEJUJPOFSBOE
4NFMMT HFUPVUPGJU4P
GJOEBOESPPUPVUUIFTNFMMTPVSDFT(FOFSBMMZ
JUPDDVSTBUBJOUFSJPSSFOPWBUFEQMBDF
B
QIBSNBDZ
BHBTPMJOFIBOEMJOHQMBDF
BUJSFTIPQ
BTFDPOEIBOECPPLTIPQPSBOFMFDUSPOJDDPNQPOFOU
IBOEMJOHQMBDFXIFOJUTDIFNJDBMPSNVTUZTNFMMTBSFTVDLFEJOBOETFOUPVU
JUDBOCFNJTMFEUIBUUIFBJS
DPOEJUJPOFSHFOFSBUFTUIFN4P
GJOEBOESPPUPVUUIFQSPCMFNPSSFGSFTIUIFSPPNGSFRVFOUMZ
4BNTVOH&MFDUSPOJDT
3FGFSFODF4IFFU
2 8IFOFWFSUIFBJSDPOEJUJPOFSJTUVSOFEPO JUTUJOLT
2 8IFOFWFSUIFBJSDPOEJUJPOFSJTUVSOFEPO JUTNFMMTTPVS
2 8IFOFWFSUIFBJSDPOEJUJPOFSJTUVSOFEPO JUTFOETPVUCBETNFMMTTVDIBTTUBMFTNFMMT
2 *UTFOETPVUCBETNFMMT
2 *UXPOhUTUBSU
2 *UHPFTPGGEVSJOHPQFSBUJPO
2 5IFSFNPUFDPOUSPMMFSXPOhUPQFSBUF
" 8IFOUIFCBUUFSJFTSVOPVUPSUIFUSBOTNJUUFSPSSFDFJWFSPGUIFSFNPUFDPOUSPMMFSJTCMPDLFECZPCTUBDMFT
DIBOHFUIFCBUUFSJFTPSLFFQUIFPCTUBDMFTBXBZGSPNUIFDPOUSPMMJOHBSFB"MTP
UIFSFNPUFDPOUSPMMFSNBZ
OPUXPSLVOEFSJOUFOTJWFMJHIUGSPNBXBWFMFOHUIMBNQPSBOFPOTJHOEVFUPUIF&.**OUIJTDBTF
UBLF
UIFSFNPUFDPOUSPMMFSDMPTFSUPUIFSFDFJWFS
4BNTVOH&MFDUSPOJDT
3FGFSFODF4IFFU
2 8IPJOTUBMMTUIFBJSDPOEJUJPOFS 3FMPDBUJPO3FJOTUBMMBUJPO
" 8
IFOSFMPDBUJOHPSSFJOTUBMMJOHUIFBJSDPOEJUJPOFS
NBLFTVSFUPDPOUBDU4BNTVOH&MFDUSPOJDT4FSWJDF
$FOUFSPS"VUIPSJ[FE4FSWJDF"HFOUBOEIBWFUIFNUPEPUIFKPC *GOPU
JUDPVMEDBVTFQFSTPOBMJOKVSZPS
QSPEVDUEBNBHF
5IFDPTUGPSUIFSFMPDBUJPOSFJOTUBMMBUJPOPGUIFBJSDPOEJUJPOFSJTTVCKFDUUPUIFDVTUPNFShTFYQFOTF
5IFSFJTBDPTUUBCMF#VU
PVSTFSWJDFFOHJOFFSOFFETUPWJTJUUPUPUBMVQUIFDPTUDPSSFDUMZ
8IFOZPVNPWFJO
NBLFTVSFUPDPOUBDU4BNTVOH&MFDUSPOJDT4FSWJDF$FOUFSPS"VUIPSJ[FE4FSWJDF"HFOUJO
BEWBODFUPTUSFBNMJOFUIFQSPDFTT
2 *TJUQPTTJCMFUPJOTUBMMUIFPVUEPPSVOJUPVUTJEF
" * UJTQPTTJCMFUPJOTUBMMJUBUBEFTJHOBUFEQMBDFJOUIFBQBSUNFOUPSPOUIFSPPGUPQOFBSCZ
#VU
JUhTJMMFHBMIBOHJOHBOBOHMFJSPODBTFXJUIUIFPVUEPPSVOJUJOJUPVUTJEFUIFBQBSUNFOU
*OTUBMMBUJPO "MTP
JUJTJMMFHBMPCTUSVDUJOHQBTTFSTCZXJUIUIFPVUEPPSVOJUJOTUBMMFEPVUTJEF
2 8IBUDBOCFEPOFUPJOTUBMMUIFPVUEPPSVOJUGBDJOHUIFSPBECFDBVTFJUJTBDPNNFSDJBMCVJMEJOH
" 5 IFGPMMPXJOHJTBOFYDFSQUGSPN#VJMEJOH$PEFHPJOHJOUPFGGFDUGSPN+6/&TU5IFFYIBVTUQJQFPGB
DPPMJOHPSWFOUJMBUJPOGBDJMJUZJOTUBMMFEJOBCVJMEJOHBEKBDFOUUPUIFTUSFFUTPGDPNNFSDJBMPSSFTJEFOUJBMBSFBT
TIBMMCFJOTUBMMFEIJHIFSUIBONUPQSFWFOUUIFFYIBVTUBJSGSPNCMPXJOHEJSFDUMZUPQBTTFSTCZBOEUIF
DVSSFOUGBDJMJUJFTTIBMMCFDPSSFDUFECZ.":TU4P
QMFBTFJOTUBMMJUIJHIFSUIBONPSOPUUPCMPXUIF
IPUFYIBVTUJOHBJSEJSFDUMZUPQBTTFSTCZ
2 8IBUBCPVUJOTUBMMJOHBXJOETDSFFOEVSJOHJOTUBMMBUJPOOPUUPCMPXIPUBJSEJSFDUMZUPQBTTFSTCZ
4BNTVOH&MFDUSPOJDT
Opening the panel
Tightly grab top of the front panel and pull it down to open.
Then slightly lift the panel up.
Open the panel and put the Air filter out. Clean the Air filter with a vacuum cleaner or soft brush.
If dust is too heavy, rinse it with running water.
Insert the Air filter back in its original position Dry the Air filter in a ventilated area.
and close the front panel.
on the usage and environmental conditions. In dusty area, clean it once a week.
Power
well-ventilated area.
3FGFSFODF4IFFU
$MFBOJOH%FPEPSJ[JOHBOE#JPGJMUFS 0QUJPO
5PSFNPWFNJOVUFEVTUQBSUJDMFTBOEPEPST
EFPEPSJ[JOHBOE#JPGJMUFSBSFJOTUBMMFEJOUIFBJSDPOEJUJPOFS
:PVTIPVMEDMFBOUIFGJMUFSTFWFSZNPOUIT
0QFOUIFVQQFSGSPOUHSJMMFCZQVMMJOHUIFMPXFSSJHIUBOEMFGUUBCTPGUIFHSJMMF
%FPEPSJ[JOH'JMUFS
1VMMPVUUIFEFPEPSJ[JOHBOE#JPGJMUFS
#JP'JMUFS
*OTFSUUIFGJMUFSTJOUPUIFPSJHJOBMQPTJUJPO
/PUFt:PVDBODIBOHFUIFQPTJUJPOPGGJMUFSTXJUIFBDIPUIFS
$MPTFUIFGSPOUHSJMMF
4BNTVOH&MFDUSPOJDT
*OTUBMMBUJPO
#FGPSF*OTUBMMBUJPO
,FFQUIFBJSDPOEJUJPOFSPVUMFUBOEJOMFUGSFFGSPNJUTTVSSPVOEJOHT
*ODBTFPGJOTUBMMBUJPO
LFFQUIFTZNNFUSZBOEGJYJUUPQSFWFOUWJCSBUJPO
5IFQJQFMFOHUITIBMMNFFUUIFTUBOEBSEBTGBSBTQPTTJCMF
*OTUBMMBUJPO1SPDFEVSF
Q -PDBUJPO
*OTUBMMUIFQSPEVDUJOBOBSFBUPHVBSBOUFFUIFCFTUDPPMJOHFGGFDU
DPOWFOJFODFPGQJQJOHBOEFMFDUSJDXPSL
BOEJOFYJTUFODFPG
WJCSBUJPOPSXJOE
Q 8BMM%SJMMJOH
%SJMMUIFXBMMEPXOXBSEJOBEJBNFUFSPGUPNN
Q 'JYJOH*OEPPS6OJU0VUEPPS6OJU
'JYUIFBJSDPOEJUJPOFSJOEPPSVOJUTFDVSFMZUPUIFXBMM4FDVSFUIFPVUEPPSVOJUJOBTVJUBCMFQPTJUJPO
Q 1JQF4QPPMJOH$POOFDUJOH
:PVTIBMMDVUUIFQJQFXJUIBQJQFDVUUFSBOEHSJOEBMMUIFCVSSTPGUIFDVUTVSGBDF
1JQFFYQBOTJPONBZDPOUJOVFVOUJMUIFQJQFTVSGBDFCFDPNFTVOFWFOPSUPSOBQBSU
#FTVSFUPVTFBUPSRVFXSFODIUPUJHIUFOQJQFTPSGMBSFOVUT
5PSRVF%FQUI
0VUFS%JBNFUFS %
5PSRVF LHGrDN
%FQUI "
NN
_ NN
NN
_ NN
NN
_ NN
NN
_ NN
NN
_
NN
Q -FBL5FTU
1 VUBOJOFSUHBTMJLFOJUSPHFOJOUIFPVUEPPSVOJUQJQFBOEQVUTPBQCVCCMFTPSPUIFSUFTUMJRVJETPOUIFQJQFTVSGBDFGPSUIF
MFBLUFTU
Q %SBJO)PTF$POOFDUJOH
*OTUBMMUIFESBJOIPTFEPXOXBSEUPESBJOXBUFSOBUVSBMMZ#FTVSFUPQPVSXBUFSJOUPUIFIPTFUPDIFDLJGJUESBJOTXFMM
Q &MFDUSJD&BSUI8PSL
& MFDUSJDBOEFBSUIXPSLTIBMMNFFUUIF&MFDUSJD'BDJMJUZ5FDIOPMPHZ4UBOEBSEBOEUIF*OUFSOBM8JSF3FHVMBUJPOPGUIF&MFDUSJD
#VTJOFTT-BXT
Q *OTQFDUJPO5SJBM3VO
6QPODPNQMFUJPOPGUIFUFTUT
ZPVTIBMMNBLFBUSJBMSVOXIJMFZPVFYQMBJOUIFNBJOGVODUJPOTPGUIFBJSDPOEJUJPOFSUPGJOJTIUIF
JOTUBMMBUJPO
4BNTVOH&MFDUSPOJDT
*OTUBMMBUJPO%JBHSBNPG*OEPPS6OJUBOE0VUEPPS6OJU
"JS1VSHF1SPDFEVSF
0VUEPPSVOJU *OEPPSVOJU
$POOFDUFBDIBTTFNCMZQJQFUPUIFBQQSPQSJBUFWBMWF
POUIFPVUEPPSVOJUBOEUJHIUFOUIFGMBSFOVU (BTQJQFTJEF
-JRVJEQJQFTJEF
$POOFDUUIFDIBSHJOHIPTFPGMPXQSFTTVSFTJEFPG
NBOJGPMEHBVHFUPUIFQBDLFEWBMWFIBWJOHBTFSWJDF
QPSUBTTIPXOBUUIFGJHVSF
0QFOUIFWBMWFPGUIFMPXQSFTTVSFTJEFPG
NBOJGPMEHBVHFDPVOUFSDMPDLXJTF
1VSHFUIFBJSGSPNUIFTZTUFNVTJOHWBDVVNQVNQ
GPSBCPVUNJOVUFT
o.BLFTVSFUIBUQSFTTVSFHBVHFTIPX
.1B DN)H
BGUFSBCPVUNJOVUFT
o5IJTQSPDFEVSFJTWFSZJNQPSUBOUJOPSEFSUPBWPJE
HBTMFBL
o5VSOPGGUIFWBDVVNQVNQ
o$MPTFUIFWBMWFPGUIFMPXQSFTTVSFTJEFPG
NBOJGPMEHBVHFDMPDLXJTF
o3FNPWFUIFIPTFPGUIFMPXQSFTTVSFTJEF
PGNBOJGPMEHBVHF
7BDVVN1VNQ
4FUWBMWFDPSLPGCPUIMJRVJETJEFBOEHBTTJEFPG
QBDLFEWBMWFUPUIFPQFOQPTJUJPO
7BMWFTUFN
.PVOUUIFWBMWFTUFNOVUTBOEUIFTFSWJDFQPSUDBQ
4UFNDBQ
UPUIFWBMWF
BOEUJHIUFOUIFNBUUIFUPSRVFPG
LHGtDNXJUIBUPSRVFXSFODI "
HBT
#
MJRVJE
$IFDLGPSHBTMFBLBHF
"UUIJTUJNF
FTQFDJBMMZDIFDLGPSHBTMFBLBHFGSPN
UIFXBZWBMWFTTUFNOVUT
BOEGSPNUIFTFSWJDF
QPSUDBQ
4BNTVOH&MFDUSPOJDT
3FGFSFODF4IFFU
i1VNQEPXOw1SPDFEVSF
1VNQEPXOXJMMCFDBSSJFEPVUXIFOBOFWBQPSBUPSJTSFQMBDFEPSXIFOUIFVOJUJTSFMPDBUFEJOBOPUIFSBSFB
3FNPWFUIFDBQTGSPNUIFXBZWBMWFBOEUIF
8BZWBMWF
5VSOUIF8BZWBMWFDMPDLXJTFUPDMPTFBOE
DPOOFDUBQSFTTVSFHBVHF MPXQSFTTVSFTJEF
XBZ7BMWF
UPUIFTFSWJDFWBMWF
BOEPQFOUIFXBZWBMWF
BHBJO
XBZ7BMWF
4FUUIFVOJUUPDPPMPQFSBUJPONPEF
$IFDLJGUIFDPNQSFTTPSJTPQFSBUJOH
5VSOUIF8BZWBMWFDMPDLXJTFUPDMPTF
8IFOUIFQSFTTVSFHBVHFJOEJDBUFTUVSOUIF
8BZWBMWFDMPDLXJTFUPDMPTF
4UPQPQFSBUJPOPGUIFBJSDPOEJUJPOFS
$MPTFUIFDBQPGFBDIWBMWF
3FMPDBUJPOPGUIFBJSDPOEJUJPOFS
t3FGFSUPUIJTQSPDFEVSFXIFOUIFVOJUJTSFMPDBUFE
t$BSSZPVUUIFQVNQEPXOQSPDFEVSF SFGFSUPUIFEFUBJMTPGhQVNQEPXOh
t3FNPWFUIFQPXFSDPSE
t%JTDPOOFDUUIFBTTFNCMZDBCMFGSPNUIFJOEPPSBOEPVUEPPSVOJUT
t3FNPWFUIFGMBSFOVUDPOOFDUJOHUIFJOEPPSVOJUBOEUIFQJQF
t"UUIJTUJNF
DPWFSUIFQJQFPGUIFJOEPPSVOJUBOEUIFPUIFSQJQFVTJOHBDBQPSWJOZMQMVHUPBWPJEGPSFJHO
NBUFSJBMFOUFSJOH
t%JTDPOOFDUUIFQJQFDPOOFDUFEUPUIFPVUEPPSVOJU
"UUIJTUJNF
DPWFSUIFWBMWFPGUIFPVUEPPSVOJUBOEUIFPUIFSQJQFVTJOHBDBQPSWJOZMQMVHUPBWPJEGPSFJHONBUFSJBM
FOUFSJOH
t.BLFTVSFZPVEPOPUCFOEUIFDPOOFDUJPOQJQFTJOUIFNJEEMFBOETUPSFUPHFUIFSXJUIUIFDBCMFT
t.PWFUIFJOEPPSBOEPVUEPPSVOJUTUPBOFXMPDBUJPO
t3FNPWFUIFNPVOUJOHQMBUFGPSUIFJOEPPSVOJUBOENPWFJUUPBOFXMPDBUJPO
4BNTVOH&MFDUSPOJDT
15-1. POWER SUPPLY
Working Voltage 176V ~ 264V
Within a 3% Deviation from Each Voltage at the Main Terminal of
Voltage Imbalance
Outdoor Unit
Starting Voltage Higher than 80% of the Rated Voltage
Cooling Heating
working range min (oC) max (oC) rated (oC) working range min (oC) max (oC) rated (oC)
outdoor -10 46 35 outdoor -10 24 7
indoor 16 32 27 indoor __ 27 20
30 30
20 20
10 10
0 0
-10 -10
-20 -20
-10 -5 0 5 10 15 20 25 30 35 40 -10 -5 0 5 10 15 20 25 30 35 40
Indoor temperature Indoor temperature
Applicable models:
ASV09PSBANXAP ASV09PSBAXXAP
ASV09PSBANXAP ASV09PSBAXXAP
ASV09PSBANXAX ASV09PSBAXXAX
ASV09PSBANXAX ASV09PSBAXXAX
ASV09PSBANXAZ ASV09PSBAXXAZ
ASV12PSBANXAZ ASV12PSBAXXAZ
Cooling
working range min (oC) max (oC) rated (oC)
outdoor 16 46 35
indoor 16 32 27
30
20
10
0
-10
-20
-10 -5 0 5 10 15 20 25 30 35 40
Indoor temperature