Structure Data File in TXT Format 61478
Structure Data File in TXT Format 61478
Structure Data File in TXT Format 61478
1
TO WHOM IT MAY CONCERN
This report comprises the summary of the residential building of Nila Poudyal at
Lalitpur Municipality, Nepal. The reports consist of the design procedures
adopted, the assumptions made, the inputs made in the design and the design
output. During the design, it is assumed that the client will completely follow the
architectural as well as the structural design. It is also assumed that the
construction will be supervised by professional engineer.
The designer will not be responsible if any alterations to the structural system is
made by the client or the contractor without the prior written permission from
the designer, or the alterations to non-structural system is made such that the
weight of each individual floor or the weight of the whole building is altered by
more than 10% of design weight of each floor and the total weight.
The design calculations and derivations are limited to only a minimum to let the
concerned people know the methodology adopted. However, the calculations may
be provided to the client or concerned authorities when needed, upon request.
Hence the building is safe.
PART I: GENERAL DATA
Introduction
This report has been prepared as a part of the structural engineering analysis and
design of the residence building.
The massive data inputs, design analysis, calculations and outputs of the result are
computer aided by the Structural analysis and design software ETABS, which is a
special purpose computer program developed specifically for building structures by
CSI America. It provides the Structural Engineer with all the tools necessary to
create, modify, analyze, design, and optimize the structural elements in a building
model.
Based on the final results, the designs have been performed and drawings were
prepared using AutoCAD 2007.
Nepal is located in boundary between the Indian and Tibetan plates, along which a
relative shear strain of about 2 cm per year has been estimated. The Indian plate is
also sub-ducting at a rate of, thought to be, about 3 cm per year. The existence of the
Himalayan range with the world’s highest peaks is evidence of continued uplift. As a
result, Nepal is very active seismically.
Reinforced concrete buildings may fail due to the either columns are overstressed
and burst due to lack of enough strength to resist the shock of the earth tremor and
vibration or failure of reinforced concrete members like beams at the poor ductile
detailing. Columns also do fail due to short column effect and splicing failure. Beams
fail due to anchorage failure, shear failure and confinement failure.
For the design of the building, the Indian Standard criteria for earthquake resistant
design IS 1893:2002 have been referred. According to the IS Code, the seismic zone
for Kathmandu has been taken falling in Zone V with very severe seismic intensity
(zone factor z = 0.36) and accordingly all other parameters like spectral coefficient
(Sa/g) and tremor response period or fundamental natural period (T) were calculated.
After that all design requirements such as seismic weight of building, lateral forces at
different floor levels and different column heads, base shear, distribution of design
forces to different floor levels are considered.
The characteristic compressive strength for concrete of 20 N/mm 2 (M20) was used in
all structural members and characteristic strength of 500 N/mm 2 (Fe500) was used
for reinforcing steel.
PART II: PRELIMININARY DESIGN
The tentative size of structural elements are determined through the preliminary
design so that after analysis the pre assumed dimensions might not deviated
considerably , thus making the final design both safe and economical . Tentative size
of various elements has been determined as follows:
SLAB
For slab, preliminary design is done according to deflection criteria span /effective
depth = 40*modification factor. (IS 456-2000 Art 24.1)
BEAM
Thumb rule of (d=L/10 to L/12) basis is adopted to consider the preliminary design of
the beam section.
b 1
=
D 2
i) Depth of beam:
We have,
1 1
to
dbeam = 10 12 ofspan
ii) Width of beam:
1 2
to
We have, bbeam = 2 3 of d beam
COLUMN
Preliminary design of column is done consideration and interior column. For the load
acting in the column, live load is decreased according to IS 875-1978.
Cross-section of the column is adopted considering the economy. Square column
section is adopted in this building project as per the internal aesthetic requirements.
A percentage of steel is taken as 0.8 to 6 percentage of cross section area of
column, but as taking 6% area of steel is more at a laps section so generally % of
steel is taken up to 4% only..
We have,
pA pA
P= 0.4
f A +0 . 67 f A
ck c y sc =0 . 4 f ( A −100 )+0 .67 f 100
ck g
g
y
g
STAIRCASE
Stairs is designed as per drawing. Column for stairs boxes is not included in the grid
system but they are assumed to be simply tied with main frame with beam.
PART III: METHODOLOGY
The methodology adopted in the Structural Analysis and Design of Three and half Storied RCC
framed Residential Building has been described below:
1. Data Collection
All the data required for this project work have been taken from different literatures.
Design parameters have been taken from Indian Standard Code of Practice. Soil test report
collect from site.
2. Load Calculation
Load calculations have been done using the IS 875-1987 (Part 1 & Part 2) as reference.
The exact value of unit weights of the material used in the building has been extracted from the
code for the calculation. Thickness of materials was taken as per design requirement.
2.1 Vertical Load
Loads on slabs may be divided into
i. Dead load - self-weight of slab.
ii. Live load - from relevant codes.
Load on beam are:
a. Self – weight of beam.
b. Load transfer from slab.
c. Load due to wall.
d. Load transfer from staircase.
Load on the columns were calculated by finding out the total dead load and live loads
acting on the columns according to their coverage and adding self – weight of it.
Lateral loads acting on building are earthquake load only. Earthquake or seismic load on
a building depends upon its geographic location, lateral stiffness and mass, and it’s reversible.
Thus its effect has been considered along both axes of the building taken one at the time. Due
to flat slab roof we have not considered wind load, also it is not practically used in our context.
Hence only seismic load analysis is carried out. For analysis and design earthquake action,
following methods can be applied.
1. Seismic Coefficient Method.
2. Response Spectrum Method.
Since the height of the building is less than 40m, equivalent static method is used.
On the basis of NBC 105:2020.
Seismic Load
Seismic design load for the building has been considered as per NBC 105:2020.
The building is in Soil Type D. All the buildings are fairly regular so Equivalent Static
Method was used.
Estimation of seismic force employing Equivalent Static Method (also known as
Seismic Coefficient Method): The method requires the calculation of base shear of the
building considering different factors. As per NBC 105:2020, the base shear, V is given
by,
V = Cd (T1) W
Where,
Cd (T1) = horizontal base shear coefficient as per 6.1
W = Seismic weight of the structure as per 5.2
Seismic Weight =DL+ p% of Live Load (30% or 60%)
C (T) = Ch(T) Z I
Where,
Ch(T) = Spectral Shape factor as per 4.1.2
Z = Seismic Zoning factor as per 4.1.4
I = Importance factor as per 4.1.5
The lateral seismic force (Fi) induced at each level ‘i’ shall be calculated as:
k
W i hi
F i= n
xV
∑ W i hki
i
Where,
Wi=seismic weight of the structure assigned to level ‘i’;
hi= height (m) from the base to level ‘i’;
n= total number of floors/levels
V= horizontal seismic base shear calculated as per 6.2
K= an exponent related to the structural period as follows:
for structure having time period T≤0.5sec, k=1
for structure having time period T≥2.5sec, k=2
for structure having period between 0.5 sec and 2.5 sec, k shall be
determined by linear interpolation between 1 and 2.
For Serviceability Limit State,
Cs ( T 1 )
C sd ( T 1 ) =
Ωs
Where,
Cs(T1) = Elastic Site Spectra as per 4.2
𝛀s = Over Strength Factor for SLS as per 5.4
The Elastic site spectra for SLS as per 4.2
Cs(T) = 0.20 C(T)
Where,
C(T) = Elastic site spectra for horizontal loading determined from clause
4.1.1
B. Live Load
IS: 875 (Part 2)-1987
Normal Residential building: 2kN/m2
Roof (Accessible)
LL = 1.5 kN/ m2
Roof ( Non-Accessible)
LL = 0.75 kN/ m2
Balcony and Lobby: 3 kN/ m2
C. Column assuming size, C1 =350mmx350mm
H. Parapet Wall
Load = 0.115(W)*1(H)*19.20
= 2.208kN/m
Load Combination
As per NBC105:2020 of Clause 3.6 for limit state method.
Type of design load case considered:
Dead Load
Live Load
Seismic Load
From clause 3.6.1 load combination for parallel systems is adopted thus load combination is,
The number of modes taken is 12. After 12 modes, the modal Participation Mass Ratio comes
out to be 100%. As per IS 1893-2002, the sum total of Modal mass of all modes considered
should be 90% of the Total Seismic Mass. Taking into consideration, the irregularities in Plan
configuration of the building, the modal Participation Mass Ratio comes out to 100% after 12
modes which is greater than 90% of Total Seismic Mass. So, the number of modes taken for
Modal Analysis is adequate.
As per Cl. no. 5.6.3 of NBC 105:2020, the ratio of the inter-story deflection to the corresponding
story height shall not exceed:
0.025 at ultimate limit state
0.006 at serviceability limit state
The deflections shall be obtained by using the effective stiffness properties of the components as
given in 3.4. The design horizontal deflections shall be determined by multiplying the horizontal
deflection found from Equivalent Static Method or Modal Response Spectrum Method by the
Ductility factor (Rμ).
The storey drift obtained from ETABS shown in tabulated from below
TABLE: Story Drifts by Ultimate Limit State Method
Case Directio
Story Output Case Type n Drift Label X Y Z
Top EQX LinStatic X 0.002244675 32 9.7536 8.5852 11.3792
Top EQY LinStatic Y 0.002287017 11 11.43 0 11.3792
Third EQX LinStatic X 0.003585539 32 9.7536 8.5852 8.5344
Third EQY LinStatic Y 0.003973427 11 11.43 0 8.5344
Secon
d EQX LinStatic X 0.004749587 32 9.7536 8.5852 5.6896
Secon
d EQY LinStatic Y 0.005025511 11 11.43 0 5.6896
First EQX LinStatic X 0.003318102 7 8.382 8.5852 2.8448
First EQY LinStatic Y 0.00338903 11 11.43 0 2.8448
Max= 0.005025511
Note: The maximum story drift for ultimate limit state was found to be 0.00502 which when
multiplied by ductility factor Rµ (4 in this case) is 0.02 and is within the limit i.e. 0.025.
Note: The maximum story drift for service limit state was found to be 0.0029 and is within the
limit i.e. 0.006.
Irregularity Check
Weak Storey Check
A story is considered as weak story if the strength of the lateral force resisting
system in that story is less than 80% of the strength of the story above.
TABLE: Story Forces
Locatio
Story Output Case Case Type n P VX VY
Top EQX LinStatic Top 1.78E-13 -83.5498107 1.40E-10
Top EQX LinStatic Bottom 1.78E-13 -83.5498107 1.40E-10
Top EQY LinStatic Top -1.31E-13 7.17E-11 -83.5498107
Top EQY LinStatic Bottom -1.31E-13 7.17E-11 -83.5498107
-
252.684617
Third EQX LinStatic Top 7.07E-12 4 3.41E-10
-
252.684617
Third EQX LinStatic Bottom 7.07E-12 4 3.41E-10
Third EQY LinStatic Top -4.63E-12 -5.74E-10 -
252.684617
4
-
252.684617
Third EQY LinStatic Bottom -4.63E-12 -5.74E-10 4
-
Secon 385.274117
d EQX LinStatic Top 8.41E-12 2 4.60E-10
-
Secon 385.274117
d EQX LinStatic Bottom 8.41E-12 2 4.60E-10
-
Secon 385.274117
d EQY LinStatic Top -4.72E-12 -1.14E-09 2
-
Secon 385.274117
d EQY LinStatic Bottom -4.72E-12 -1.14E-09 2
-
450.182098
First EQX LinStatic Top 9.47E-12 5 5.18E-10
-
450.182098
First EQX LinStatic Bottom 9.47E-12 5 5.18E-10
-
450.182098
First EQY LinStatic Top -9.39E-12 -1.20E-09 4
-
450.182098
First EQY LinStatic Bottom -9.39E-12 -1.20E-09 4
From Table we can see that there is no weak story in this building.
Plan Irregularity
Torsion irregularity is considered to exist where the maximum horizontal
displacement of any floor in the direction of the lateral force (applied at the center of
mass) at one end of the story is more than 1.5 times its minimum horizontal
displacement at the far end of the same story in that direction.
Calculation,
TABLE: Joint Displacements by Ultimate State Method
Stor Labe
y l Unique Name Output Case Case Type Ux Uy Uz
-
0.002
Top 6 189 EQX LinStatic 39.5368 2.2386 4
-
34.252 0.152
Top 6 189 EQY LinStatic -4.9452 8 7
Top 7 190 EQX LinStatic 39.5368 -3.4711 -
0.139
3
-
38.688 0.126
Top 7 190 EQY LinStatic -4.9452 4 2
0.096
Top 9 191 EQX LinStatic 32.9739 -3.4711 4
-
38.688 0.090
Top 9 191 EQY LinStatic 0.1532 4 8
-
0.194
Top 10 192 EQX LinStatic 32.9739 -7.4088 4
-
41.747 0.230
Top 10 192 EQY LinStatic 0.1532 4 4
-
0.226
Top 11 193 EQX LinStatic 28.4455 -7.4088 3
41.747 0.203
Top 11 193 EQY LinStatic 3.6710 4 0
0.092
Top 12 194 EQX LinStatic 28.4455 -3.4711 5
38.688 0.257
Top 12 194 EQY LinStatic 3.6710 4 4
-
0.005
Top 18 198 EQX LinStatic 33.8271 2.2386 7
34.252 0.009
Top 18 198 EQY LinStatic -0.5096 8 4
-
0.047
Top 21 200 EQX LinStatic 32.9739 -5.2430 5
-
40.064 0.214
Top 21 200 EQY LinStatic 0.1532 9 5
-
0.215
Top 22 201 EQX LinStatic 33.8271 -5.2430 0
-
40.064 0.443
Top 22 201 EQY LinStatic -0.5096 9 5
-
1.675
Top 32 202 EQX LinStatic 39.5368 -5.2430 6
40.064 0.061
Top 32 202 EQY LinStatic -4.9452 9 0
Top 1 1 EQX LinStatic 34.2349 -2.9298 0.000
0
38.267 0.000
Top 1 1 EQY LinStatic -0.8265 9 0
41.747
Max= 39.5368 4
34.252
Min= 28.4455 8
Max/Min= 1.390 1.219
Stirrup
S.N Column ID Size ALL FLOOR
At End Ties At Mid Ties
1 A4,B4 350*350 4-20φ +4-16Ф 8mmφ @100mm c/c 8mmφ @150mm c/c
3 C1,A2,C2, 350*350 4-16φ +4-12Ф 8mmφ @100mm c/c 8mmφ @150mm c/c
Section Properties
b (mm) h (mm) dc (mm) Cover (Torsion) (mm)
350 350 56 30
Material Properties
Ec (MPa) fck (MPa) Lt.Wt Factor (Unitless) fy (MPa) fys (MPa)
25000 25 1 500 500
Notes:
N/A: Not Applicable
N/C: Not Calculated
N/N: Not Needed
BEAMDESIGN RESULT
BEAM SIZE Top Bar Area Required Bottom Bar Area Required
FLOOR
(mm) At Support At End At Support At End
2-16φ (Regular)+ 2-12φ (Regular)+
First 230*350 2-16φ (Regular) 2-12φ (Regular)
(1-12φ) (Extra) (1-12φ) (Extra)
2-16φ (Regular)+ 2-12φ (Regular)+
Second 230*350 2-16φ (Regular) 2-12φ (Regular)
(1-12φ) (Extra) (1-12φ) (Extra)
2-12φ (Regular)+ 2-12φ (Regular)+
Third 230*350 2-12φ (Regular) 2-12φ (Regular)
(1-12φ) (Extra) (1-12φ) (Extra)
2-12φ (Regular)+ 2-12φ (Regular)+
TOP 230*350 2-12φ (Regular) 2-12φ (Regular)
(1-12φ) (Extra) (1-12φ) (Extra)
ETABS Concrete Frame Design
IS 456:2000 + IS 13920:2016 Beam Section Design
Section Properties
b (mm) h (mm) bf (mm) ds (mm) dct (mm) dcb (mm)
230 350 230 0 25 25
Material Properties
Ec (MPa) fck (MPa) Lt.Wt Factor (Unitless) fy (MPa) fys (MPa)
25000 25 1 500 500
N/
Grade of the concrete fck= 20 mm2
N/
Grade of the steel fy= 500 mm3
KN/
Density of the concrete ɼ= 25 m3
Thickness of the slab and durability considerations
Center to center distance between column= Lx eff.= 4.420 m
Center to center distance between column= Ly eff.= 4.420 m
Cover for the mild exposure c 20 mm
Effective depth provided d 105 mm
Overall depth of the slab D 125 mm
width of slab b 1000 mm
3)design load
Dead load of the slab DL= 3.125 KN/m2
Floor finish FF= 1 KN/m2
Partition wall PP= 1 KN/m2
Live load LL= 2 KN/m2
Ceiling plaster CP= 0.5 KN/m2
Total load TL= 7.625 KN/m2
11.43
Factored load Pu= 8 KN/m2
Minimum depth
Mu=0.136*fck*b*d^2
d= 62.13 < 105 mm
Hence, OK
6) Reinforcement Calculation
A) Short direction (-ve Mx)
For -ve Mx
Mx=0.87*fy*Astx(d-(fy*Astx)/(fck*b))
1050013
A= 10.875 B= -45675 C= 5
Astx= 244.07 mm2
Spacing(m As(mm2
Let us Provide dia. (mm) m) ) %
0.2
Required reinforcement bars 8 205.84126 244.07 3
0.3
Provide Reinforcement bars 8 150 334.93 2
with Alternate Bent up bars
B) Long direction
For -ve My
My=0.87*fy*Asty(d-(fy*Asty)/(fck*b))
A= 10.875 B= -45675 C= 1050013
5
Asty= 244.07 mm2
Spacing(m As(mm2
Let us Provide dia. (mm) m) )
Required reinforcement bars 8 205.84126 244.07
Provide Reinforcement bars 8 150 334.93
Again,
B) Long direction
For +ve My
My=0.87*fy*Asty(d-(fy*Asty)/(fck*b))
A= 10.875 B= -45675 C= 7819250
Asty= 178.81 mm2
Spacing(m As(mm2
Let us Provide dia. (mm) m) )
Required reinforcement bars 8 280.98 178.81
Provide Reinforcement bars 8 150 334.93
with Alternate Bent up bars
Size of Footing
Area= 2.70 mm^2 1.643
Considering square Footing
Length of footing (L)= 1.95 m
Breadth of footing (B)= 1.95 m
Reaction of soil (qa')= 96.797 KN/m <100 KN/m
d= 212.261 mm
Adopting
Overall depth (D)= 500 mm
Effective depth (d)= 450 mm 0.45 m
Calculation of Reinforcement
Mmax=0.87*fy*Ast*d*(1-Ast*fy/(B*d*fck))
A= 5.5769230 B= - C= 6E+07
77 19575
0
Ast= 311.325 mm^2
At1= 113.097 mm^2 using 12 mmФ
providing 12mmФ @150mm c/c
1470.26 mm^2 311.32
Ast provided = 1 > 5 mm^2
Vmax=qa'*B*(L/2-l/2-d)
= 66.064 KN
Nominal shear stress
(τv)= Vmax/B*d
0.075 N/mm^2
100*Ast/B*d= 0.17
N/ N/
(τc)= 0.296 mm^2> 0.075 mm^2 ok
(τc)= ks*τc'
0.25*fck^1
τc'= /2
= 1.118 N/mm^2
N/
(τc)= 1.118 N/mm^2 > 0.213 mm^2 ok
= 679.6875 mm
KN (Exterior
Pc1= 318.7754 column)
KN (Interior
Pc2= 585.2905 Column)
service load on column1= 212.52 KN
service load on column2= 390.19 KN
Distance between two column from center to center
(L)= 4.420 m
(350*350
Size of Column 1 = ) mm^2
(350*350
Size of Column 2 = ) mm^2
Safe Bearing Capacity of soil(S.B.C)= 100 KN/m^2
a1= 0.35 m
Materials Used
M20 grade
Fe 500TMT
bars
Ultimate Stresses
N/
fck= 20 mm^2
N/
fy= 500 mm^2
Size Of Footing
Depth Of Footing
Mu= 0.134*fck*b*d^2
d= 85.318 mm
Check for
shear
Maximum shear occurs at a distance of d/2 mm from the face of the column A
Maximum shear force Vu = 185.484 KN
Maximum shear stress Tvc =Vu/bd 1.178 Mpa
1.17 o
Maximum shear strength of M20 concrete Tc max= 2.8 > 8 k
Percentage of tension reinforcement ( pt) = 0.64 %
(Clause 40.2.1.1 of IS 456-2000)
for D = 500 mm
K= 1
(Table 19 of IS 456-2000)
Permissible shear stress = k Tc = 0.525 < 1.178 Mpa
Provide shear reinforcement
Balance shear force = Vus = 102.796 KN
Also, Vus = 0.87 fy Asv d / Sv
Adopt 8 mm 2- legged stirrup
Therefore, spacing Sv= 192.558 mm
Provide 8mm 2- legged stirrups @ 150mm c/c
Details of strap beam
width =
350mm
depth 500mm
Reinforcement at top 5-16Ф(Reg)
Reinforcement at Bottom 4-16Ф(Reg)
8 mm stirrups @ 150 mm c/c
foundation size 1.95m*1.95m
Foundation depth = 1.524m from ground level
Reinforcement in foundation= 12mm Ф @ 150mm c/c Top & Bottom (Both ways)
σx = P/A±MY*x/Iy±MX*y/Ix
σi(KN/
Column Joint Pu (KN) X (m) Y(m) mm^2) Result
-
3.64
A2 136 321.566 -2.943 7 47.372
-
3.64 σi<100
A3 134 309.669 1.477 7 48.644
-
KN/
3.64
mm^2
A4 132 171.927 4.499 7 49.513
0.47
C2 142 585.693 -2.943 3 43.243
-
0.16
B3 128 565.712 1.477 4 45.152
-
0.16
B4 130 183.630 4.499 4 46.021
4.90
D2 124 453.696 -2.943 5 38.800
4.90
D3 126 498.956 1.477 5 40.071
Adopte spacin
Beam σi Length Wide B. M d Ast min Ast d g provided % Provided bar
KN/m^2 (L)m (B)m KN-m mm req req Bar mm Ast Ast in two direction
mm^2 (mm^2)
12mmφ @125mm
(A-A 48.510 4.42 2.235 142.16 450 758.1407 540 12 125 905.1429 0.2 c/c
12mmφ @125mm
(B-C) 44.805 4.42 4.002 131.3 450 697.8068 540 12 125 905.1429 0.2 c/c
12mmφ @125mm
(D-D) 39.435 4.42 2.671 115.56 450 611.113 540 12 125 905.1429 0.2 c/c
SUMMARY OF FOOTING
Grade of Concrete M20
Grade of steel Fe 500
S.N Grid Footing Size Overall Effective Reinforcement
m Depth mm Depth mm
12 mmФ@125 mm c/c (X-
dir)
1 B3,D3,C2,D2 RF1 9.507*8.22 500 450
12 mmФ@150 mm c/c (Y
dir)
2 A1,C1,D1 F1 1.95*1.95 500 450 12 mmФ@150 mm c/c
1. Indian Standards Code of Practice For Plain & Reinforced Concrete IS: 456-
2000; Bureau of Indian Standards (BIS), July 2000, New Delhi
2. Design Aids for Reinforced Concrete IS: 456-1978 Special Publication: 16
Bureau of Indian Standards (BIS), New Delhi
3. Nepal National Building Code, NBC 105: 2020, Department of Housing and
Physical Planning.
4. Handbook on Concrete reinforcement and Detailing, Special Publication: 34 [SP:
34 –1987].
5. Explanatory Handbook on Code for Earthquake Engineering IS: 1893 –2002,
Beau of Indian Standards (BIS), New Delhi.
6. Ductile Detailing of Reinforced Concrete Structures subjected to Seismic forces-
Indian Code of Practice IS 13920: 1993, Beau of Indian Standards (BIS), New
Delhi.