PROTECTION& INTERLOCK
CLASSIFICATION OF BOILER
PROTECTIONS & INTERLOCKS
2
RC FEEDER INTERLOCK & PROTECTION
Furnace Safeguard Supervisory System(FSSS)
Introduction to FSSS
3
RC FEEDER INTERLOCK & PROTECTION
FSSS is designed to perform the following functions:
• Prevent any fuel firing unless a satisfactory furnace purge sequence has
first been completed.
• Prevent start-up of individual fuel firing equipment unless certain permissive
interlocks have first been satisfied.
• Monitor & control the proper sequence (Manual or Automatic) during start-
up and shutdown of fuel firing equipment.
• Make continued operation of fuel firing equipment subject to certain safety
interlocks remaining satisfied.
• Provide status feedback to the operator and in some cases, to the unit
control system.
• Provide flame supervision when fuel firing equipment is in service and affect
a fuel trip upon certain adverse operating conditions.
• Initiate a fuel trip when certain abnormal operating conditions exist. 4
RC FEEDER INTERLOCK & PROTECTION
FSSS’s Operational Function:
1) FURNACE PURGE SUPERVISION.
2) LIGHT OIL ON/OFF CONTROL & SUPERVISION.
3) HEAVY OIL ON/OFF CONTROL & SUPERVISION.
4) PULVERISER CONTROL & SUPERVISION.
a. Pulveriser discharge valve control.
b. Pulveriser ignition permissive.
c. Pulveriser ready permissive.
d. Pulveriser on/off control.
e. Hot air gate open/close control
f. Feeder start/stop control.
5) SADC - ON/OFF CONTROL & SUPERVISION.
6) FLAME SCANNER INTELLIGENCE & CHECKING.
a. Scanner air fan control.
b. Flame scan output indication.
c. Flame failure trip.
7) BOILER TRIP PROTECTION 5
RC FEEDER INTERLOCK & PROTECTION
FSSS’s Operational Function:
• Furnace Purge
Before any fuel firing can take place, (initially or after a boiler trip) a
successful furnace purge cycle must be completed. To start furnace purge
cycle
• Establish AC/DC supply to FSSS equipments.
• Bring normal water level in drum. A
N PURGE
• Take at least one ID&FD fans in service. D READY
• Establish airflow between 30% to 40% of MCR
START Press
PURGING
PURGE “START
PURGE”
button
5 minute count down
timer ON 6
RC FEEDER INTERLOCK & PROTECTION
FSSS’s Operational Function:
• Furnace Purge
If PURGE READY signal is not available, then check the following
conditions are satisfied
• Light oil trip valve is proven closed.
• Light oil nozzle valves are proven closed.
• Heavy oil trip valve is proven closed.
• Heavy oil nozzle valves are fully closed.
• All PA fans are off.
• All feeders are off.
• All hot air gates are fully closed.
• All the flame scanners show “NO FLAME”
• No boiler trip command is present.
• Airflow between 30% & 40% MCR.
• All auxiliary dampers are modulating.
7
RC FEEDER INTERLOCK & PROTECTION
FSSS’s Operational Function:
LIGHT OIL TRIP VALVE CONTROL(LOTV)
• Conditions to be fulfilled to open LOTV after successful purging
A
Light oil supply pressure is adequate “LOTV OPEN”
N
All LO nozzle valve proven closed in AB elev D Permissive ok
FM To AB elevation
LDO LOFCV burners
RC FEEDER INTERLOCK & PROTECTION 8
LOTV
FSSS’s Operational Function:
HEAVY OIL TRIP VALVE CONTROL(HOTV)
• HOTV opening conditions
HORTV is fully open and
HOTV close command is not present
FM
To AB,CD,EF
HFO HOFCV
elevation burners
HOTV
Return line to
tanks
HORTV
Steam RC FEEDER INTERLOCK & PROTECTION 9
FSSS’s Operational Function:
HEAVY OIL TRIP VALVE CONTROL
• HOTV closing conditions
Master fuel trip
and
HO Recirculation valve is not closed
If any of the conditions exist for more than 5 sec
CLOSE
Atomizing steam pressure very low or command to
HOTV
No HO start or stop in any elevation and
•The valve can be manually closed by the push-button on the console insert only when the
pulveriser is off. The corresponding indications are available on the console insert as Red and
Green lamps for open and close positions respectively
11
RC FEEDER INTERLOCK & PROTECTION
FSSS’s Operational Function:
PULVERISER CONTROL
PULVERISER IGNITION PERMIT:
Prior to starting any feeder, the feeder ignition energy must be adequate to support coal firing. This is
accomplished all 6 elevations as follows:
PULVERISER "A“
A minimum of 3 of the 4-elevation “AB“ oil nozzle valves proven open Permit signal to
Boiler loading is greater than 30% or start PULVERISER A
PULVERISER "B“
A minimum of 3 of the 4-elevation “AB“oil nozzle valves proven open
Permit signal to
Boiler loading is greater than 30% or start PULVERISER B
and
PULVERISER "C"
A minimum of 3 of the 4-elevation “CD“oil nozzle valves proven open
Boiler loading is greater than 30% Permit signal to
Feeder “B” is in service at greater than 50% loading and or start PULVERISER
or C
Feeder “D” is in service at greater than 50% loading
A minimum of 3 of the 4-elevation “AB“oil nozzle valves proven open and
Feeder “B” is in service at greater than 50% loading.
12
RC FEEDER INTERLOCK & PROTECTION
FSSS’s Operational Function:
PULVERISER CONTROL
PULVERISER IGNITION PERMIT:
PULVERISER "D"
A minimum of 3 of the 4-elevation “CD“ oil nozzle valves proven open.
Permit signal to
Boiler loading is greater than 30% or
start
and PULVERISER D
Feeder “C” is in service at greater than 50% loading.
or
Feeder “E” is in service at greater than 50% loading.
PULVERISER "E“
A minimum of 3 of the 4-elevation “EF“oil nozzle valves proven open
Boiler loading is greater than 30% Permit signal to
Feeder “D” is in service at greater than 50% loading. and or start
Feeder “F” is in service at greater than 50% loading. or PULVERISER E
A minimum of 3 of the 4-elevation “CD“ oil nozzle valves proven open and
Feeder “D” is in service at greater than 50% loading.
PULVERISER "F“
A minimum of 3 of the 4-elevation “EF“oil nozzle valves proven open.
Permit signal to
or start
Boiler loading is greater than 30% PULVERISER F
and
Feeder “C” is in service at greater than 50% loading
13
RC FEEDER INTERLOCK & PROTECTION
FSSS’s Operational Function:
PULVERISER CONTROL
HOT AIR GATE(HAG) CONTROL:
14
RC FEEDER INTERLOCK & PROTECTION
FSSS’s Operational Function:
MASTER FUEL TRIP
• If some abnormal condition occurs(like less than 30% air ), Master Fuel Trip
Relay acts and ensures the closure of Heavy Oil Trip valve (HOTV) and all
light Oil Nozzle Valves (LONV), thus cutting off total oil supply.
• Thus MFT ensures a safe shut down of the boiler in case of any abnormal
conditions in boiler/ furnace.
• It also ensures the stopping of all pulverizer systems and Primary Air (PA)
fans, cutting off total coal supply to boiler. The various abnormal operating
conditions under which Master Fuel Trip occurs are as follows:-
15
RC FEEDER INTERLOCK & PROTECTION
FSSS’s Operational Function:
MASTER FUEL TRIP CONDITIONS
17
RC FEEDER INTERLOCK & PROTECTION
FSSS’s Operational Function:
FLAME SCANNER INTELLIGENCE AND CHECKING
SCANNER AIR FLOW CONTROL
FLAME SCANNER OUTPUT INDICATION
FLAME FAILURE PROTECTION
• During light up and until any main fuel (coal) is in service at a fire condition,
the flame scanners do not take part in the overall flame failure protection
system.
• A fire ball condition is established for coal firing when either or both the
adjacent feeders are proven
.AND.
2 out of 4 fireball scanners show flame.
18
RC FEEDER INTERLOCK & PROTECTION
FSSS’s Operational Function:
FLAME SCANNER INTELLIGENCE AND CHECKING
SCANNER AIR FAN CONTROL
Two scanner air fans (1 AC main + 1 DC stand-by) are provided for the unit.
1)AC scanner fan will automatically start if following condition are fulfilled:
20
RC FEEDER INTERLOCK & PROTECTION
FSSS’s Operational Function:
FLAME SCANNER INTELLIGENCE AND CHECKING
FLAME FAILURE PROTECTION:
• An elevation voting for "No Flame" condition is as described below for the
respective coal and oil elevations.
ELEVATION “A”
Feeder “A” is not proven
ELEVATION A
Elevation AB- 3/4 Fireball scanners shows no flame and or VOTED NO
Elevation AB HO/LO- 2/4 nozzle valves not open FLAME
Elevation AB started and loss of 110V AC power
ELEVATION “B”
Feeder “B” is not proven.
Elevation AB- 3/4 Fireball scanners shows no flame
and
Elevation AB HO/LO- 2/4 nozzle valves not open ELEVATION B
or VOTED NO
FLAME
Elevation AB started and loss of 110V AC power
and
Elevation “BC” 3/4 fire ball scanners show no Flame
ELEVATION “C”
Feeder “C” is not proven.
Elevation CD- 3/4 Fireball scanners shows no flame
and ELEVATION C
Elevation CD HO- 2/4 nozzle valves not open. or VOTED NO
Elevation CD started and loss of 110V AC power. FLAME
Elevation “BC”- 3/4 fire ball scanners show no Flame and
RC FEEDER INTERLOCK
FSSS& PROTECTION 21
FSSS’s Operational Function:
FLAME SCANNER INTELLIGENCE AND CHECKING
FLAME FAILURE PROTECTION(cont):
ELEVATION “D”
Feeder “D” is not proven
Elevation CD 3 out of 4 Fireball scanners shows no flame and
ELEVATION D
Elevation CD HO 2 out of 4 nozzle valves not open or VOTED NO
Elevation CD started and loss of 110V AC power FLAME
and
Elevation “DE” 3 out of 4 fire ball scanners show no Flame
ELEVATION “E”
Feeder “E” is not proven
Elevation EF 3 out of 4 Fireball scanners shows no flame
and ELEVATION E
Elevation EF HO 2 out of 4 nozzle valves not open or
VOTED NO
Elevation EF started and loss of 110V AC power FLAME
and
Elevation “DE” 3 out of 4 fire ball scanners show no Flame
ELEVATION “F”
Feeder “F” is not proven.
ELEVATION F
Elevation EF 3 out of 4 Fireball scanners shows no flame and or
VOTED NO
Elevation EF HO 2 out of 4 nozzle valves not open FLAME
Elevation EF started and loss of 110V AC power
All elevation voting for “No Flame" as described above will cause a unit trip on Flame
Failure trip, provided the flame failure circuit is armed. (Unit Flame failure Trip circuit
is armed 2 seconds after any coal elevation is put into service. i.e. any feeder proven
RC FEEDER INTERLOCK & PROTECTION 23
FSSS’s Operational Function:
SADC CONTROL
Secondary Air Damper Control includes both auxiliary & fuel air Damper control
24
RC FEEDER INTERLOCK & PROTECTION
FSSS’s Operational Function:
SADC CONTROL
A) Auxiliary Air Damper Control:
Auxiliary air damper position at above & below 30% boiler load.
Note:
During furnace purge, all auxiliary air dampers are in
100% open condition 25
RC FEEDER INTERLOCK & PROTECTION
FSSS’s Operational Function:
SADC CONTROL
A) Auxiliary Air Damper Control:
1)Conditions leading to Manual control & automatically open of Auxiliary Air Damper
All ID fans OFF OR
Commanded to
All FD fans OFF 100% open
Logic
MFT +
Manual control
Loss of 24V DC
1)Conditions leading to Manual control & automatically open of Fuel Air Damper:
All ID fans OFF OR Commanded to
100% open
All FD fans OFF
Logic +
MFT Manual control
Loss of 24V DC
2) Conditions leading to Manual control :
Feeder rate signal failed OR
Thrown to
open cmd from FSSS
Logic Manual control
close cmd from FSSS
28
RC FEEDER INTERLOCK & PROTECTION
FSSS’s Operational Function:
SADC CONTROL
C) Over fire Air Damper Control:
Over fire air dampers are used to control SOx & NOX
1. Lower Over fire air damper will open when boiler load >50% MCR
2. Upper Over fire air damper will open when boiler load>75%MCR
29
RC FEEDER INTERLOCK & PROTECTION
BOILER AUXILIARIES INTERLOCK & PROTECTION
Conditions existing when the unit is shutdown and prior to starting of ID Fans:
1) ID fan A & B are OFF.
2) Regulating dampers of fans A & B are fully open.
3) Inlet gates of ID fans A & B open.
4) Outlet gates of ID fans A & B open.
5) The regulating dampers and hydraulic coupling will be on manual control
during shutdown and impulse from furnace draft control to regulating
dampers of ID fans disconnected.
31
RC FEEDER INTERLOCK & PROTECTION
BOILER AUXILIARIES INTERLOCK & PROTECTION
ID FAN’S INTERLOCKS & PROTECTION
Starting of ID Fan A (ID Fan B is OFF):
A) ID fan A shall be prohibited from starting till the following conditions are satisfied:
1) Regulating dampers of ID FAN - A in minimum position.
2) Hydraulic coupling scoop tube for ID FAN - A in minimum position & manual.
3) Outlet gate of ID FAN – A closed.
4) Intel gate of ID FAN – A closed.
5) ID FAN - A’s fan & motor bearing temperature not very high.
6) Motor winding temperature not very high.
7) One of APH is running with its inlet & Outlet dampers in open position.
8) Lube oil permissive satisfied(any LOP on & pressure >0.8 ata).
9) Hydraulic coupling of ID Fan-A’s oil level O.K and cooler ready for operation.
10)Flue gas path available(dampers across APH,ESP & FD fan o/l damper open).
32
RC FEEDER INTERLOCK & PROTECTION
BOILER AUXILIARIES INTERLOCK & PROTECTION
ID FAN’S INTERLOCKS & PROTECTION
Starting of ID Fan A (ID Fan B is OFF):
B) When ID fan A is started , impulses shall be given for :-
1) Opening the inlet gate of ID Fan- A after the motor reaches rated speed.
2) Connecting the regulating dampers/scoop tube control of ID Fan – A to
auto control
3) Closing the inlet gate and the outlet gate of ID Fan – B and bring the
regulating dampers/scoop tube control to minimum position
4) Permission to start either FD Fan – A or B
33
RC FEEDER INTERLOCK & PROTECTION
BOILER AUXILIARIES INTERLOCK & PROTECTION
ID FAN’S INTERLOCKS & PROTECTION
Tripping of ID Fan A (ID Fan B is OFF):
A) ID fan A will trip automatically under following conditions:-
34
RC FEEDER INTERLOCK & PROTECTION
BOILER AUXILIARIES INTERLOCK & PROTECTION
ID FAN’S INTERLOCKS & PROTECTION
Tripping of ID Fan A (ID Fan B is OFF):
B) When ID fan A trips simultaneous impulse will be give for :-
1) Tripping signal to working FD fan.
2) Tripping signal to Boiler through FSSS.
3) Disconnecting the impulse from auto control to regulating damper and
Hydraulic coupling control.
4) Opening of inlet & outlet gate of ID fan B.
5) Commanded to wide open of regulating damper of ID A & B.
35
RC FEEDER INTERLOCK & PROTECTION
BOILER AUXILIARIES INTERLOCK & PROTECTION
ID FAN’S INTERLOCKS & PROTECTION
Starting of ID Fan B (ID Fan A is ON):
A) ID fan B shall be prohibited from starting till the following conditions are satisfied:
1) Regulating dampers of ID FAN - B in minimum position.
2) Hydraulic coupling scoop tube for ID FAN - B in minimum position & manual.
3) Outlet gate of ID FAN – B closed.
4) Intel gate of ID FAN – B closed.
5) ID FAN - B’s fan & motor bearing temperature not very high.
6) ID FAN - B’s Motor winding temperature not very high.
7) Lube oil permissive satisfied(any LOP on & pressure >0.8 ata).
8) ID Fan-B’s Hydraulic coupling oil level O.K.
36
RC FEEDER INTERLOCK & PROTECTION
BOILER AUXILIARIES INTERLOCK & PROTECTION
ID FAN’S INTERLOCKS & PROTECTION
Starting of ID Fan B (ID Fan A is ON):
B) When ID fan B is started (ID fan A is ON), impulses shall be given for :-
1) Opening the inlet gate of ID Fan- B after the motor reaches rated speed.
2) Connecting the regulating dampers/scoop tube control of ID Fan – B to auto
control
3) Permission to start another FD Fan.
37
RC FEEDER INTERLOCK & PROTECTION
BOILER AUXILIARIES INTERLOCK & PROTECTION
ID FAN’S INTERLOCKS & PROTECTION
Tripping of ID Fan B (ID Fan A is ON):
A) ID fan B will trip automatically under following conditions:-
ID fan B’s fan bearing temp too high> 90’c >10sec
ID fan B’s hydraulic coupling working oil temp very high>110’c for 2sec
39
RC FEEDER INTERLOCK & PROTECTION
BOILER AUXILIARIES INTERLOCK & PROTECTION
ID FAN’S LUBRICATION OIL PUMPS:
• There are 2x100% LOPs(1W, 1S) are provided for each ID fans
LOP A or B will automatically stop under following condition(when both LOPs are ON):
LOP A ON
AND
LOP B ON >5secs TRIP CMD TO ANY ONE LOP A or B
Lub Oil pressure>0.8ATA LOGIC
Conditions existing when the unit is shutdown and prior to starting of FD Fans:
1) FD fan A & B are OFF
2) FD fan A & B blade pitch in maximum position.
3) FD fan blade pitch control disconnected.
4) Lub Oil pumps of FD fans off.
5) Outlet dampers are fully open.
41
RC FEEDER INTERLOCK & PROTECTION
BOILER AUXILIARIES INTERLOCK & PROTECTION
FD FAN’S INTERLOCKS & PROTECTION
Starting of FD Fan A (FD Fan B is OFF):
A)FD fan A shall be prohibited from starting till the following conditions are satisfied:
1) ID fan either A or B is ON.
2) FD FAN – A blade pitch control in minimum position.
3) Outlet damper of FD FAN – A closed
4) Intel gate of FD FAN – A open
5) FD FAN - A’s fan & motor bearing temperature not very high
6) Motor winding temperature not very high
7) FD fan’s Lube oil permissive satisfied(any LOP on & pressure >13bar)
42
RC FEEDER INTERLOCK & PROTECTION
BOILER AUXILIARIES INTERLOCK & PROTECTION
FD FAN’S INTERLOCKS & PROTECTION
Starting of FD Fan A (FD Fan B is OFF):
B) When FD fan A is started (FD fan B is off), impulses shall be given for :-
1) Opening the outlet gate of FD Fan- A after the motor reaches rated speed.
2) Outlet damper of FD Fan – B to close & impeller blades of FAN-B to be
driven to minimum position.
3) Connecting the blade pitch control of Fan – A to auto control.
43
RC FEEDER INTERLOCK & PROTECTION
BOILER AUXILIARIES INTERLOCK & PROTECTION
FD FAN’S INTERLOCKS & PROTECTION
Tripping of FD Fan A (FD Fan B is OFF):
A) FD fan A will trip automatically under following conditions:-
44
RC FEEDER INTERLOCK & PROTECTION
BOILER AUXILIARIES INTERLOCK & PROTECTION
FD FAN’S INTERLOCKS & PROTECTION
Tripping of FD Fan A (FD Fan B is OFF):
B) When FD fan A trips simultaneous impulse will be give for :-
1) Disconnecting the blade pitch of FD fan A & B to the maximum.
2) Opening the outlet damper of fan B.
3) To open the scanner air emergency suction damper.
4) Tripping signal to Boiler through FSSS
5) The outlet damper of FD fan A shall remain open.
*Same similar interlocks for FD Fan B(FD Fan A is OFF)
45
RC FEEDER INTERLOCK & PROTECTION
BOILER AUXILIARIES INTERLOCK & PROTECTION
FD FAN’S INTERLOCKS & PROTECTION
Starting of FD Fan B (FD Fan A is ON):
A)FD fan B shall be prohibited from starting till the following conditions are satisfied:
1) Two ID fans should be ON.
2) FD FAN – B blade pitch control in minimum position.
3) Outlet damper of FD FAN – B is in closed position.
4) FD FAN - B’s fan & motor bearing temperature not very high
5) Motor winding temperature not very high
6) FD fan’s Lube oil permissive satisfied(any LOP on & pressure >3BAR)
46
RC FEEDER INTERLOCK & PROTECTION
BOILER AUXILIARIES INTERLOCK & PROTECTION
FD FAN’S INTERLOCKS & PROTECTION
Starting of FD Fan B (FD Fan A is ON):
B) When FD fan B is started (FD fan A is on), impulses shall be given for :-
1) Opening of outlet damper of FD Fan- B after the motor reaches rated speed.
2) Connecting the blade pitch control of Fan – B to auto control.
48
RC FEEDER INTERLOCK & PROTECTION
BOILER AUXILIARIES INTERLOCK & PROTECTION
FD FAN’S INTERLOCKS & PROTECTION
Tripping of FD Fan B (FD Fan A is ON):
B) When FD fan B trips simultaneous impulse will be give for :-
1) Disconnecting FD fan B the blade pitch control from auto.
2) Bringing the FD fan B blade pitch control to minimum position.
3) Closing the outlet damper of Fan B.
4) Initiation of partial load relay for 60% MCR
49
RC FEEDER INTERLOCK & PROTECTION
BOILER AUXILIARIES INTERLOCK & PROTECTION
FD FAN’S LUBRICATION OIL PUMPS:
There are 2x100% LOPs(1W, 1S) are provided for each FD fans
LOP will automatically stop under following condition(when both LOPs are ON):
LOP A ON
AND
LOP B ON >5secs TRIP CMD TO ANY ONE LOP A or B
Lub Oil pressure>13BAR LOGIC
Conditions existing when the unit is shutdown and prior to starting of PA Fans:
1) PA fan A & B are OFF
2) PA fan A & B blade pitch in maximum position.
3) PA fans blade pitch control disconnected.
4) Lub Oil pumps of PA fans off.
5) Outlet dampers are fully open for PA Fan A & PA Fan B.
51
RC FEEDER INTERLOCK & PROTECTION
BOILER AUXILIARIES INTERLOCK & PROTECTION
PA FAN’S INTERLOCKS & PROTECTION
Starting of PA Fan A (PA Fan B is OFF):
A)PA fan A shall be prohibited from starting till the following conditions are satisfied:
1) Either FD fan A or B is ON.
2) PA FAN – A blade pitch control in minimum position.
3) Purge completed
4) PA FAN - A’s fan & motor bearing temperature not very high
5) Motor winding temperature not very high.
6) APH should be in service with one gas & air inlet and outlet damper opened.
7) PA fan’s Lube oil permissive satisfied(any LOP on & pressure >0.8 ata)
52
RC FEEDER INTERLOCK & PROTECTION
BOILER AUXILIARIES INTERLOCK & PROTECTION
PA FAN’S INTERLOCKS & PROTECTION
Starting of PA Fan A (PA Fan B is OFF):
B) When PA fan A is started , impulses shall be given for :-
1) Opening the outlet damper of PA Fan- A.
2) Connecting the blade pitch control of PA Fan – A to auto control
3) Bringing the blade pitch of PA fan B to minimum position.
4) Closing of outlet damper of PA fan B
5) Permission to start 3 lower coal elevations through FSSS
53
RC FEEDER INTERLOCK & PROTECTION
BOILER AUXILIARIES INTERLOCK & PROTECTION
PA FAN’S INTERLOCKS & PROTECTION
Tripping of PA Fan A (PA Fan B is OFF):
A) PA fan A will trip automatically under following conditions:-
54
RC FEEDER INTERLOCK & PROTECTION
BOILER AUXILIARIES INTERLOCK & PROTECTION
PA FAN’S INTERLOCKS & PROTECTION
Tripping of PA Fan A (PA Fan B is OFF):
B) When PA Fan B trips simultaneous impulse will be give for :-
1) Disconnecting the blade pitch control from auto.
2) Bringing the PA fan A blade pitch control to minimum position.
3) Closing the outlet damper of PA Fan A.
4) Tripping all the operating mills (through FSSS)
55
RC FEEDER INTERLOCK & PROTECTION
BOILER AUXILIARIES INTERLOCK & PROTECTION
PA FAN’S INTERLOCKS & PROTECTION
Starting of PA Fan B (PA Fan A is ON):
A) PA fan B shall be prohibited from starting unless following condition are satisfied
1) Both FD fans ON.
2) Blade pitch control of PA fan B in min. condition.
3) PA fan B & Motor bearing temp not very high(<90oC)
4) Motor winding temp. not very high(<80oC).
5) Both APH are running with their gas and air inlet and outlet dampers opened
6) Lube oil permissives satisfied
*Same similar interlocks for Starting PA Fan B (PA Fan A is ON)
56
RC FEEDER INTERLOCK & PROTECTION
BOILER AUXILIARIES INTERLOCK & PROTECTION
PA FAN’S INTERLOCKS & PROTECTION
Starting of PA Fan B (PA Fan A is ON):
B) When PA fan B is started (PA fan A is ON), impulses shall be given for :-
1) Opening the outlet damper of PA fan B after the motor ON (TD = 30 sec.).
2) Connecting the damper control of PA fan B to auto control.
3) Permission to put in service remaining coal elevation through FSSS.
57
RC FEEDER INTERLOCK & PROTECTION
BOILER AUXILIARIES INTERLOCK & PROTECTION
PA FAN’S INTERLOCKS & PROTECTION
Tripping of PA Fan B (PA Fan A is ON):
A) PA fan B will trip automatically under following conditions:-
MFT acted
58
RC FEEDER INTERLOCK & PROTECTION
BOILER AUXILIARIES INTERLOCK & PROTECTION
PA FAN’S INTERLOCKS & PROTECTION
Tripping of PA Fan B (PA Fan A is ON):
B)When PA Fan B trips simultaneous impulse will be give for :-
1) Disconnecting the blade pitch control of PA fan B from auto.
2) Bringing the PA fan B blade pitch control to minimum position.
3) Closing the outlet damper of PA Fan B.
4) Initiation of partial load relay for 60% MCR
59
RC FEEDER INTERLOCK & PROTECTION
BOILER AUXILIARIES INTERLOCK & PROTECTION
PA FAN’S LUBRICATION OIL PUMPS:
• There are 2x100% LOPs(1W, 1S) are provided for each PA fans
LOP will automatically stop under following condition(when both LOPs are ON):
LOP A ON
AND
LOP B ON >5secs TRIP CMD TO ANY ONE LOP A or B
Lub Oil pressure>20BAR LOGIC
2) Impulse shall be given for closing of the inlet and outlet dampers for air &
gas side of Air Heater B which is off
61
RC FEEDER INTERLOCK & PROTECTION
BOILER AUXILIARIES INTERLOCK & PROTECTION
APH’s INTERLOCKS & PROTECTION
Tripping of APH-A (APH-B is OFF):
1) APH electric motor fault.
2) Whenever the sump oil temperature of support/guide bearing is greater than
70oC an alarm shall be initiated through RTD to the operator. The
operator shall check the circulation pump operation & the coolant flow
at local to bring down the sump oil temperature. In case if the
temperature of sump oil is unable to be brought down, APH electric
motor/air motor shall be tripped manually.
When APH’s electric motor trips simultaneous impulse will be give for :-
62
RC FEEDER INTERLOCK & PROTECTION
BOILER AUXILIARIES INTERLOCK & PROTECTION
APH’s INTERLOCKS & PROTECTION
Tripping of APH-A (APH-B is ON) or vise versa:
1) Gas I/L & O/T damper, Secondary air O/T damper, and PA I/L & O/T damper
of the tripped AH shall be automatically closed.
2) Boiler load reduced approx 60 %MCR
63
RC FEEDER INTERLOCK & PROTECTION
BOILER AUXILIARIES INTERLOCK & PROTECTION
APH’s INTERLOCKS & PROTECTION
Interlocks for Oil Circulation Pumps of support bearings(SB) of Air heaters:
2 x 100% oil circulation pump have been provided for the support bearing.
Anyone of the two oil circulation pumps can be pre selected as main pump and
the other as standby.
Following interlocks shall be provided for Oil Circulating Pumps
APH ON
AND
SB LOP1 OFF>2SEC
64
RC FEEDER INTERLOCK & PROTECTION
BOILER AUXILIARIES INTERLOCK & PROTECTION
APH’s INTERLOCKS & PROTECTION
Interlocks for Oil Circulation Pumps of guide bearings(GB) of Air heaters:
2 x 100% oil circulation pump have been provided for the guide bearing. Anyone
of the two oil circulation pumps can be pre selected as main pump and the other
as standby.
Following interlocks shall be provided for Oil Circulating Pumps
APH ON
AND
GB LOP OFF>2SEC
65
RC FEEDER INTERLOCK & PROTECTION
BOILER AUXILIARIES INTERLOCK & PROTECTION
PULVERISER INTERLOCKS & PROTECTION
Conditions existing when the unit is shutdown and prior to starting of MILL:
1) Mill Motor off
2) LOPs for Mills off
66
RC FEEDER INTERLOCK & PROTECTION
BOILER AUXILIARIES INTERLOCK & PROTECTION
PULVERISER INTERLOCKS & PROTECTION
Starting of Mill:
A)MILL shall be prohibited from starting till the following conditions are satisfied:
1) Bunker Outlet Gate open
2) Feeder Inlet Gate open
3) Mill Discharge valves open(4nos)
4) Seal air valve is open
5) Mill start permit from Pulveriser Lub Oil System
6) Mill outlet temp not high <94˚C
7) Cold air Gate open
8) Tramp Iron Hopper Valve open
9) Mill/Oil elevation start permit.
10) Nozzle tilts placed in the horizontal position(for 1st pulveriser only).
11) Primary air pressure is adequate(>650mmwc)
12) Pulveriser Bowl DP Adequate >200 mmwc
13) MILL status off & ignition permit available
67
RC FEEDER INTERLOCK & PROTECTION
BOILER AUXILIARIES INTERLOCK & PROTECTION
PULVERISER INTERLOCKS & PROTECTION
Starting of Mill:
B) When MILL is started, impulses shall be given for :-
1) Permission to open the hot air gate(HAG) & impulse to regulate HAG
2) Permission to start the Raw Coal Feeder.
69
RC FEEDER INTERLOCK & PROTECTION
BOILER AUXILIARIES INTERLOCK & PROTECTION
PULVERISER INTERLOCKS & PROTECTION
Tripping of MILL:
B) When MILL is tripped, simultaneous impulses shall be given for :-
1) Signal to trip the feeder’s motor
2) To close the hot air gate.
3) To bring cold air damper to minimum position
71
RC FEEDER INTERLOCK & PROTECTION
BOILER AUXILIARIES INTERLOCK & PROTECTION
RC FEEDER INTERLOCKS & PROTECTION
RC Feeder Starting:
B) RC Feeder motor is simultaneous impulse shall be give for :
1) To include feeder output in totalizing circuit after 15secs
2) To release feeder speed control to auto after 50secs
3) To modulate fuel air dampers according to feeder speed after 50secs
72
RC FEEDER INTERLOCK & PROTECTION
BOILER AUXILIARIES INTERLOCK & PROTECTION
RC FEEDER INTERLOCKS & PROTECTION
Tripping of RC feeder motor:
Boiler Trips
Elevation DC fails >2secs
Elevation AC fails
Trip
OR
Pulveriser trips
LOGIC signal to
RC motor’s electrical trip RC motor
Loss of coal flow & pulveriser amps low
73
RC FEEDER INTERLOCK & PROTECTION
BOILER AUXILIARIES INTERLOCK & PROTECTION
REHEATER PROTECTION
This protection is provided to protect the Reheater against starvation of steam flow
during abnormal conditions. To take care of Reheater protection, the Boiler shall be
tripped after 10 seconds, when any of the following conditions occur.
AND
ANY FEEDER ON REHEATER PROTECTION
OR ARMED
LOGIC
BOILER FIRING SIGNAL FROM
FSSS LOGIC
74
RC FEEDER INTERLOCK & PROTECTION
BOILER AUXILIARIES INTERLOCK & PROTECTION
REHEATER PROTECTION
Reheater protection will automatically enable under following conditions:
75
RC FEEDER INTERLOCK & PROTECTION