AL-AIN MALL Work Method Statements

The document provides a method of work statement for fire and safety equipment testing and maintenance at the Al-Ain Mall project site. It will involve testing the fire alarm system, emergency lighting central battery system, and firefighting pumps. Testing the fire alarm system will include simulating alarms, inspecting devices, and confirming third party interfaces. Emergency lighting and the central battery system will be inspected and tested using proper tools. Firefighting pumps, including electrical and diesel pumps, will be tested by simulating pressure decreases that trigger the pumps to activate automatically. On-site supervisors will oversee the work and generate a report upon completion for approval.

Uploaded by

Abdul Raheem
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
100 views4 pages

AL-AIN MALL Work Method Statements

The document provides a method of work statement for fire and safety equipment testing and maintenance at the Al-Ain Mall project site. It will involve testing the fire alarm system, emergency lighting central battery system, and firefighting pumps. Testing the fire alarm system will include simulating alarms, inspecting devices, and confirming third party interfaces. Emergency lighting and the central battery system will be inspected and tested using proper tools. Firefighting pumps, including electrical and diesel pumps, will be tested by simulating pressure decreases that trigger the pumps to activate automatically. On-site supervisors will oversee the work and generate a report upon completion for approval.

Uploaded by

Abdul Raheem
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 4

AL BOSHIA FIRE & SAFETY EQUIPMENT EST.

Tel - 02 4458 528, e-mail- [email protected]

METHOD OF STATEMENT

PROJECT AL-AIN MALL

MAIN CONTRACTOR AL DEYAAR FACILITIES MANAGMENTS

TITLE METHOD OF WORK STATEMENT (FAS/EMLS/FFS)

LOCATION OF WORK
SPAR-KHALIFA CITY

START DATE DURATION

NAME OF SUPERVISOR
NUMBER OF PERSONS
IN-CHARGE

TOOLS USED
1) Electrical Tool Kit

2) Hand Tool Kit (Screw Drivers, Multimeter, Pipe Wrench, Wire Cutter, Brushes, Hammer)

3) Smoke testing kit / Heat testing kit

4) Scaffolding / ladders

EQUIPMENT TO BE USED

‘PERMIT TO WORK’ REQUIRED?


YES NO YES NO

HOT WORKS  WORK AT HEIGHT 

CRANE 

Page 1 of 4
EXCAVATION 

CONFINED SPACE 

RISER SHAFTS 

AL BOSHIA FIRE & SAFETY EQUIPMENT EST.


Tel - 02 4458 528, e-mail- [email protected]

DESCRIPTION OF WORK
Fire Alarm System
 Before Testing Fire Alarm Simulation Test Inform to the Facilities Team. To avoid panic situation
inside the mall area
 Visually inspect the Fire Alarm All Devices.
 Conduct the fire alarm test with authorized / approved person.
 Using proper smoke / heat kit for testing the fire alarm devices.
 Pull the manual call point to check the alarm system.
 Conform the interfacing third party connection from the fire alarm system.
 Testing the Existing third-party connection with fire alarm system
 After completion of testing clean properly testing devices to avoid false alarm system.
 Make a report for the fire alarm testing and get the signature form the authorized person from the
facilities management

Emergency lighting Central battery System


 Before Simulation Testing the Emergency, Central battery System Inform to the Facilities Team.
 Visually inspect the Emergency & Exit Central Battery All Devices.
 Using the proper tools Check the power supply Properly Voltages / Amperes from The Central
Battery Systems
 Testing the emergency & exit central battery system using the proper tools with authorized /
certified person can performed the Emergency & exit lighting testing
 After completion of testing make a report and get signature from the Authorized person from the

Page 2 of 4
facilities management

Fire Fighting Pumps

 Electrical fire fighting pump


 Check the water tank for the sufficient water
 Set the electrical pump in auto mode in the control panel
 Make sure that both the gate valves of suction line and discharge line always open position, check
the pressure gauge maximum
 Open the drain valve / hose reel when the pressure gauge reading decrease (6 to 5 bar) the electrical
pump starts automatically
 Stop the using fire hose reel, the pressure gauge reading will increase and reach the maximum level
and then electrical pump will automatically stop
Fire Fighting Diesel pump
 Check the water tank for the sufficient water
 Check the battery and Diesel tank and water coolant inside the radiator
 Set the Diesel pump in auto mode in the control panel
 Make sure that both the gate valves of suction line and discharge line always open position, check
the pressure gauge maximum
 Open the drain valve / hose reel when the pressure gauge reading decrease (6 to 5 bar) the electrical
pump starts automatically
 Stop the using fire hose reel, the pressure gauge reading will increase and reach the maximum level
and then Diesel pump will automatically stop

ON SITE IN-CHARGE OFF SITE INCHARGE

Page 3 of 4
Signature of supervisor DATE