The LOA2... / LOA3... and this Data Sheet are intended for use by OEMs which
integrate the oil burner controls in their products.
Use, features
Use The LOA... are used for the startup, supervision and control of single- or 2-stage forced
draft oil burners in intermittent operation.
Yellow-burning flames are supervised with photoresistive detectors QRB..., blue-
burning flames with blue-flame detectors QRC...
Specific features - Special versions including models for incinerator plant and flash-steam generators
- LOA36... with color LED for indicating flame strength and operation
CC1N7118en
Siemens Building Technologies
09.10.2002 HVAC Products
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒั นา กทม. 10170.
website: https://www.add-furnace.com/ โทร: 02-888-3472
Line ID: @add11 Wechat ID: add0883001122
Warning notes
Before performing any wiring changes in the connection area of the LOA..., com-
pletely isolate the unit from the mains supply (all-polar disconnection)
Ensure protection against electric shock hazard by providing adequate protection
for the burner control’s connection terminals
Check to ensure that wiring is in an orderly state and that the wires are firmly con-
nected
Press the lockout reset button / operating button only manually (applying a force of
no more than 60 N), without using any tools or pointed objects
Fall or shock can adversely affect the safety functions. Such units may not be put
into operation, even if they do not exhibit any damage
Mounting notes
Ensure that the relevant national safety regulations are complied with
Installation notes
Commissioning notes
2/10
Standards
Service notes
Disposal notes
The unit contains electrical and electronic components and may not be disposed of
together with household waste.
Local and currently valid legislation must be observed.
Mechanical design
The housing is made of impact-proof, heat-resistant and flame-retarding plastic.
The oil burner control is of plug-in design and engages audibly in its base.
Type summary
The type references given below apply to burner controls without base and without flame detector.
Legend ¹) LOA25... and LOA28... are designed for use on incinerator plant where lockout by extraneous light is not desired. These
types of oil burner controls are not covered by EN 230
²) IRD1010 infrared flicker detectors can also be used
t1 Prepurge time
t3 Preignition time
t3n Long postignition time
t3n´ Short postignition time
t4 Interval from establishment of flame to the release of «BV2»
TSA Ignition safety time
3/10
Ordering
Flame detectors
- Photoresistive detectors QRB1... refer to Data Sheet 7714
- Blue-flame detectors QRC1... refer to Data Sheet 7716
Adapter KF8819
- For replacing LAB1... / LAI... by LOA...
- No rewiring of plug-in base required
4/10
Technical data
General unit data Mains voltage AC 220 V –15 %...AC 240 V +10 %
AC 100 V –15 %...AC 110 V +10 %
Mains frequency 50...60 Hz ±6 %
External primary fuse (Si) 10 A (fast)
Power consumption approx. 3 VA
Degree of protection IP 40, must be ensured through mounting
Safety class I
Perm. cable lengths max. 3 m with 100 pF/m line capacitance
- Detector cable laid separately max. 20 m
- Remote reset laid separately max. 20 m
Mounting position optional
Weight approx. 180 g
Input current to
- Terminal 1 5 A (short-time 15 A for max. 0.5 s)
- Terminal 3 5 A (excl. current draw of burner motor and
oil preheater)
5/10
Flame detectors For measuring circuits and detector cable lengths, refer to Data Sheets 7714 (QRB...)
and 7716 (QRC...).
¹) These types of LOA... may not be used in connection with QRC...blue-flame detec-
tors
Data given in the above table only apply under the folllowing conditions:
- Mains voltage AC 230 V
- Ambient temperature 23 °C
QRB... QRC1...
6/10
Function
Undervoltage detection An additional electronic circuit ensures that if mains voltage drops below approximately
AC 165 V, burner startup will be prevented, or – without release of oil – lockout will be
triggered.
Control sequence in the Whenever lockout occurs, the outputs for the fuel valves, the burner motor, oil prehea-
event of fault ter and ignition equipment will immediately be deactivated (< 1 second).
The lockout indication lamp changes to red and terminal 10 («AL») for remote lockout
indication receives voltage.
This state is also maintained in the event of mains voltage failure.
Cause Response
Mains voltage failure New start
Extraneous light on burner startup Lockout; with LOA25... / LOA28...: Preven-
tion of start
No flame at the end of «TSA» Lockout
Loss of flame during operation Repetition
Reset After lockout, the burner control can be reset after 60...90 seconds (also refer to
«Warning notes»).
Indications
Lockout position The lockout position is indicated with the lamp integrated in the lockout reset button.
Indication of the flame strength (green LED) is used for checking the flame signal.
To ensure reliable burner operation, this LED must be lit.
If the green LED flickers or extinguishes during burner operation, the light conditions at
the burner are poor, caused by dirt for instance.
When the contacts of the control thermostat are closed, the orange LED is lit, indicating
the start of the oil preheater’s heating up phase (if present).
7/10
7
1
1
8
a
0
6
0
4
0
2
/
Control sequence
LOA24.171B17 L1 y cd e f g
LOA24.171B27 R A´ A B C D
tz2 tz1 SB 1
EK1 fr W
LOA24.571C27 x z a b FR OH 8
K
V
OW 3
t3n
TZ M 3
1 2 10 8 3 7 6 4 5 9 11 12
tw t1 6
SB Z
7
OW t3 TSA
W
BV1 4
R OH QRB t4
AL Z BV2 5
N BV1
11
w
Si
s
QRC FS
L
bl
M BV2 7118d04/0402 12
N 1
br
7118a0
7/0402
LOA24.174A27 L1 x y z cd f g W
LOA24.173A27 R A´ A B C D
tz2 tz1 SB 1
EK1 fr
e
a b FR OH 8
K
V
OW 3
TZ M 3
1 2 10 8 3 7 6 4 5 9 11 12
t3n´
SB 7
OW Z tw t1 t3n
W
6
R OH QRB t3 TSA
AL Z BV1 4
N BV1 t4
w
Si
s
QRC BV2 5
L
bl
M BV2
N 1 11
br FS
7118d01/0402 12
a10/0
7118
402
LOA25.173C17 L1 x y z cd e f g
LOA25.173C27 R A´ A B C D
tz2 tz1 SB 1
EK1 fr** W
LOA28.173A27 a b FR OH 8
K
V OW 3 1
TZ OW 3 2
1 2 10 8 3 7 6 4 5 9 11 12
SB M 3
tw t1 t3n´
W OW 6
Z
7
R OH
t3 TSA
Z
AL BV1 4
Si BV1 BV2 QRB. t4
L M BV2 5
N
11
FS
7118d02/0402 12
8/10
7
1
1
8
a
0
8
0
4
0
2
/
L1 x y z cd e f R A´ A B C D
LOA26.171B27 g
SB 1
tz2 tz1
EK1 fr
W
a b FR OH 8
With ARK21 K
V
remote lockout
OW 3
reset module TZ t3n
1 2 10 8 3 7 6 4 5 9 11 12
M 3
SB tw t1
OW Z 6
W
R OH QRB SA 7
Z
AL
t3 TSA
N SA BV1
Si BV1 4
N QRC
b
l
L
sw
M BV2 t4
N 1
10
br BV2 5
11
2 1013 FS
9 EK2 7118d05/0402 12
14
ARK21A27
7118a09/0402
L1 x y z cd ef LED1 R A´ A B C D
LOA36.171A27 g
SB 1
tz2 tz1
EK1 fr
W
a b FR
OH 8
With ARK21 K
V
remote lockout
L2
OW 3
reset module TZ t3n
1 2 10 8 3 7 6 4 5 9 11 12
M 3
SB
tw t1
OW Z 6
W
R OH QRB SA 7
Z
AL
t3 TSA
N SA BV1
Si BV1 4
N QRC
b
l
L
sw
M BV2 t4
N 1
br BV2 5
10
11
2 1013 FS
9 EK2 7118d05/0402 12
14
ARK21A27
TSA Ignition safety time A´ Beginning of the startup sequence with burners using an «OH»
tw Waiting time A Beginning of the startup sequence with burners using no «OH»
t1 Prepurge time B Time of flame establishment
t3 Preignition time C Running position
t3n Long postignition time D Controlled shutdown by «R»
t3n´ Short postignition time
t4 Interval between flame signal and release of «BV2» Control signals delivered by the LOA...
Required input signals
Permissible input signals
9/10
Dimensions
Dimensions in mm
22
LOA...
5,5
62,5
7118m05/1002
88 41,5
91
LOA2... LOA3...
62,5
62,5
47
47
xxxxxxxxxx xxxxxxxxxx
36,5 7118m03/0300
83,5
Remote lockout reset
23 12 67,5
module ARK21A27
66
50
+ +
7118m04/0300
Remote lockout reset module for use with the LOA26... / LOA36...
Printed circuit board with no housing.
Degree of protection IP 00, which means that protection against electric shock hazard
must be ensured through mounting.
Do not place any metal objects in the hatched area.
The module must be fitted with the help of spacers made of plastic.
Do not use spacers made of metal.
10/10