Oil Burner Controls LOA2...


LOA3...
Oil burner controls for the supervision, startup and control of single- or 2-stage
forced draft oil burners in intermittent operation. Oil throughput up to 30 kg/h.

The LOA2... / LOA3... and this Data Sheet are intended for use by OEMs which
integrate the oil burner controls in their products.

Use, features

Use The LOA... are used for the startup, supervision and control of single- or 2-stage forced
draft oil burners in intermittent operation.
Yellow-burning flames are supervised with photoresistive detectors QRB..., blue-
burning flames with blue-flame detectors QRC...

- Forced draft oil burners conforming to EN 267


- Oil atomization burners as monoblocks conforming to EN 230

General features - Undervoltage detection


- Bridging contact for oil preheater (not with LOA28.173A27)

Specific features - Special versions including models for incinerator plant and flash-steam generators
- LOA36... with color LED for indicating flame strength and operation

CC1N7118en
Siemens Building Technologies
09.10.2002 HVAC Products
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒั นา กทม. 10170.
website: https://www.add-furnace.com/ โทร: 02-888-3472
Line ID: @add11 Wechat ID: add0883001122

Warning notes

To avoid injury to persons, damage to property or the environment, the following


warning notes should be observed!

Do not open, interfere with or modify the unit!

Before performing any wiring changes in the connection area of the LOA..., com-
pletely isolate the unit from the mains supply (all-polar disconnection)
Ensure protection against electric shock hazard by providing adequate protection
for the burner control’s connection terminals
Check to ensure that wiring is in an orderly state and that the wires are firmly con-
nected
Press the lockout reset button / operating button only manually (applying a force of
no more than 60 N), without using any tools or pointed objects
Fall or shock can adversely affect the safety functions. Such units may not be put
into operation, even if they do not exhibit any damage

Mounting notes

Ensure that the relevant national safety regulations are complied with

Installation notes

Installation and commissioning work must be carried out by qualified


staff Do not mix up live and neutral conductors
Always run high-voltage ignition cables separately while observing the greatest
possible distance to the unit and to other cables

Electrical connection of flame detectors

It is important to achieve practically disturbance- and loss-free signal transmission:


Never run the detector cable together with other cables
– Line capacitance reduces the magnitude of the flame signal
– Use a separate cable
Observe the permissible lengths of the flame detector cables (refer to Data Sheets
7714 (QRB...) and 7716 (QRC...))

Commissioning notes

Commissioning work must be carried out by qualified staff


When commissioning the plant, when carrying out maintenance work, or after
longer off periods, make the following safety checks:

Safety check Anticipated response


a) Burner startup with flame detector Lockout at the end of «TSA»
darkened
b) Burner startup with flame detector Lockout after approx. 40 seconds
exposed to extraneous light
c) Simulation of flame failure during Repetition followed by lockout at the
operation. For that purpose, darken end of «TSA»
the flame detector during operation
and maintain this state

2/10

Siemens Building Technologies CC1N7118en


HVAC Products 09.10.2002
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒั นา กทม. 10170.
website: https://www.add-furnace.com/ โทร: 02-888-3472
Line ID: @add11 Wechat ID: add0883001122

Standards

Conformity to EEC directives


Electromagnetic compatibility EMC (immunity) 89 / 336 EEC
Low-voltage directive 73 / 23 EEC

Service notes

Maintenance work must be carried out by qualified staff


Each time a unit has been replaced, check wiring to ensure it is in an orderly state
and that the wires are firmly connected; make the safety checks as indicated in
«Commissioning notes» above
Use the KF... test adapters for short periods of time only

Disposal notes

The unit contains electrical and electronic components and may not be disposed of
together with household waste.
Local and currently valid legislation must be observed.
Mechanical design
The housing is made of impact-proof, heat-resistant and flame-retarding plastic.
The oil burner control is of plug-in design and engages audibly in its base.

The housing accommodates the


- thermal-electric sequence switch
- flame signal amplifier with the flame relay
- lockout reset button with its integrated fault indication lamp

Type summary

The type references given below apply to burner controls without base and without flame detector.

Version Type reference Voltage Under- CE t1 t3 TSAmax. t3n t3n´ t4 Replacement


(VAC) voltage for
detection
Standard version LOA24.171B27 ²) 220 X x 13 13 10 15 --- 15 LAI2.3
LOA24.171B17 ²) 110 X x 13 13 10 15 --- 15
LOA24.173A27 220 X x 13 13 10 20 2 20 LAI2.3
LOA24.174A27 220 X x 13 13 10 35 2 35 ---
With remote reset LOA26.171B27 ²) 220 X x 13 13 10 15 --- 15 ---
facility LOA36.171A27 220 X x 13 13 10 15 --- 15 ---
For flash-steam LOA24.571C27 220 X x 6 6 10 20 --- 20 LAI5
generators
For incinerator plant LOA25.173C27 ¹) 220 X --- 13 13 10 --- 2 15 LAB2
LOA25.173C17 ¹) 110 X --- 13 13 10 --- 2 15
LOA28.173A27 ¹) 220 X --- 13 13 10 --- 2 15 ---

Legend ¹) LOA25... and LOA28... are designed for use on incinerator plant where lockout by extraneous light is not desired. These
types of oil burner controls are not covered by EN 230
²) IRD1010 infrared flicker detectors can also be used

t1 Prepurge time
t3 Preignition time
t3n Long postignition time
t3n´ Short postignition time
t4 Interval from establishment of flame to the release of «BV2»
TSA Ignition safety time

3/10

Siemens Building Technologies CC1N7118en


HVAC Products 09.10.2002
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒั นา กทม. 10170.
website: https://www.add-furnace.com/ โทร: 02-888-3472
Line ID: @add11 Wechat ID: add0883001122

Ordering

Oil burner control without plug-in base refer to «Type summary»

Electrical connections refer to Data Sheet 7201


- Plug-in base AGK11...
- Cable holders AGK65..., AGK66, AGK67...
- Cable strain relief elements for AGK67...

Electrical connections refer to Data Sheet 7203


- Plug-in base AGK13
- Plug-in housing AGK56
- Cover AGK68

Flame detectors
- Photoresistive detectors QRB1... refer to Data Sheet 7714
- Blue-flame detectors QRC1... refer to Data Sheet 7716

Pedestal (empty housing) AGK21


- To increase the overall height of the LOA...to that of the LAI... / LAB...

Remote reset module ARK21A27


- For use with the LOA26... / LOA36... printed circuit board versions

Adapter KF8819
- For replacing LAB1... / LAI... by LOA...
- No rewiring of plug-in base required

Demo case KF8891


- For showing the functioning of burner controls
- Refer to Operating Instructions B7989

Test case, for making functional tests KF8843


- For testing burner controls
- Refer to Operating Instructions B7986

Test adapter KF8885


- For testing burner controls
- With switch for manual startup of burner
- With switch for simulating the oil preheater’s release contact
- With 2 pairs of jacks for measuring the flame detector current
- Refer to Mounting Instructions C7981

Test adapter KF8833


- For testing burner controls fitted to the burner
- With signal lamps for program indication
- With 2 jacks for measuring the flame detector current

Test adapter KF8840


- For testing burner controls fitted to the burner
- With signal lamps for program indication
- With switch for simulating the flame signal
- With holes for checking the control voltages at the tabs of the burner control
- With 2 jacks for measuring the flame detector’s resistance

4/10

Siemens Building Technologies CC1N7118en


HVAC Products 09.10.2002
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒั นา กทม. 10170.
website: https://www.add-furnace.com/ โทร: 02-888-3472
Line ID: @add11 Wechat ID: add0883001122

Technical data

General unit data Mains voltage AC 220 V –15 %...AC 240 V +10 %
AC 100 V –15 %...AC 110 V +10 %
Mains frequency 50...60 Hz ±6 %
External primary fuse (Si) 10 A (fast)
Power consumption approx. 3 VA
Degree of protection IP 40, must be ensured through mounting
Safety class I
Perm. cable lengths max. 3 m with 100 pF/m line capacitance
- Detector cable laid separately max. 20 m
- Remote reset laid separately max. 20 m
Mounting position optional
Weight approx. 180 g
Input current to
- Terminal 1 5 A (short-time 15 A for max. 0.5 s)
- Terminal 3 5 A (excl. current draw of burner motor and
oil preheater)

Max. perm. current at Terminal Terminal Terminal Terminal Terminal Terminal


cos0.6 4 5 6 7 8 10
LOA24.171B27
LOA24.171B17
LOA24.571C27 1A 1A 2A 2A 5A 1A
LOA25.173C27
LOA25.173C17
LOA28.173A27
LOA24.173A27 1A 1A 2A 1.5 A 5A 1A
LOA24.174A27
LOA26.171B27 1A 1A 2A 0.1 A 5A 1A
LOA36.171A27

Environmental Transport DIN EN 60 721-3-2


conditions Climatic conditions class 2K2
Mechanical conditions class 2M2
Temperature range -50...+60 °C
Humidity < 95 % r.h.
Operation DIN EN 60 721-3-3
Climatic conditions class 3K5
Mechanical conditions class 3M2
Temperature range -20...+60 °C
Humidity < 95 % r.h.

Condensation, formation of ice and ingress of water are not permitted!

5/10

Siemens Building Technologies CC1N7118en


HVAC Products 09.10.2002
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒั นา กทม. 10170.
website: https://www.add-furnace.com/ โทร: 02-888-3472
Line ID: @add11 Wechat ID: add0883001122

Flame detectors For measuring circuits and detector cable lengths, refer to Data Sheets 7714 (QRB...)
and 7716 (QRC...).

QRB... Type of burner control QRB... (typically)


Min. detector current Max. perm. detector Max. detector current
required (with flame) current possible (with flame)
(without flame)
LOA24.171B27 / LOA24.171B17
LOA24.571C27
LOA25.173C27 / LOA25.173C17 70 µA 5.5 µA 210 µA
LOA26.171B27
LOA28.173A27
LOA24.173A27 45 µA 5.5 µA 45 µA
LOA24.174A27
LOA36.171A27 70 µA 5.5 µA 900 µA

QRC1... Type of burner control QRC... (typically)


Min. detector current Max. perm. detector Max. detector current
required (with flame) current possible (with flame)
(without flame)
LOA24.171B27
LOA24.571C27 70 µA 5.5 µA 110 µA
LOA26.171B27
LOA24.171B17 70 µA 5.5 µA 90 µA
LOA25.173C27 ¹) --- --- ---
LOA25.173C17 ¹)
LOA28.173A27 ¹)
LOA24.173A27 45 µA 5.5 µA 45 µA
LOA24.174A27
LOA36.171A27 70 µA 5.5 µA 110 µA

¹) These types of LOA... may not be used in connection with QRC...blue-flame detec-
tors

Data given in the above table only apply under the folllowing conditions:
- Mains voltage AC 230 V
- Ambient temperature 23 °C

Measuring curcuit for QRB... QRC...


detector current 11 12 LOA... 11 12 1 LOA... Legend
7118v01/0102 br 7118v02/0102
bl sw + bl sw +
µA DC DC microammeter
with an internal resistance of
µA DC µA DC Ri = max. 5 k
bl Blue
sw Black
br Brown

QRB... QRC1...

Only with LOA36... Detector current LED lit


Indication of flame - With QRB... min. 60 µA ±15 %
strength - With QRC... min. 40 µA ±15 %

6/10

Siemens Building Technologies CC1N7118en


HVAC Products 09.10.2002
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒั นา กทม. 10170.
website: https://www.add-furnace.com/ โทร: 02-888-3472
Line ID: @add11 Wechat ID: add0883001122

Function

Preconditions Burner control is reset


for startup Contacts in the line are closed
No undervoltage
Flame detector is darkened, no extraneous light

Undervoltage detection An additional electronic circuit ensures that if mains voltage drops below approximately
AC 165 V, burner startup will be prevented, or – without release of oil – lockout will be
triggered.

Control sequence in the Whenever lockout occurs, the outputs for the fuel valves, the burner motor, oil prehea-
event of fault ter and ignition equipment will immediately be deactivated (< 1 second).
The lockout indication lamp changes to red and terminal 10 («AL») for remote lockout
indication receives voltage.
This state is also maintained in the event of mains voltage failure.

Cause Response
Mains voltage failure New start
Extraneous light on burner startup Lockout; with LOA25... / LOA28...: Preven-
tion of start
No flame at the end of «TSA» Lockout
Loss of flame during operation Repetition

Reset After lockout, the burner control can be reset after 60...90 seconds (also refer to
«Warning notes»).

Indications

Lockout position The lockout position is indicated with the lamp integrated in the lockout reset button.

Flame strength Only with LOA36...

Indication of the flame strength (green LED) is used for checking the flame signal.
To ensure reliable burner operation, this LED must be lit.
If the green LED flickers or extinguishes during burner operation, the light conditions at
the burner are poor, caused by dirt for instance.

Operation Only with LOA36...

When the contacts of the control thermostat are closed, the orange LED is lit, indicating
the start of the oil preheater’s heating up phase (if present).

7/10

Siemens Building Technologies CC1N7118en


HVAC Products 09.10.2002
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒั นา กทม. 10170.
website: https://www.add-furnace.com/ โทร: 02-888-3472
Line ID: @add11 Wechat ID: add0883001122

Connection diagram and internal diagram

7
1
1
8
a
0
6

0
4
0
2
/
Control sequence
LOA24.171B17 L1 y cd e f g
LOA24.171B27 R A´ A B C D
tz2 tz1 SB 1
EK1 fr W

LOA24.571C27 x z a b FR OH 8
K
V
OW 3
t3n
TZ M 3
1 2 10 8 3 7 6 4 5 9 11 12
tw t1 6
SB Z
7
OW t3 TSA
W
BV1 4
R OH QRB t4
AL Z BV2 5
N BV1
11

w
Si

s
QRC FS
L

bl
M BV2 7118d04/0402 12
N 1
br

7118a0
7/0402
LOA24.174A27 L1 x y z cd f g W
LOA24.173A27 R A´ A B C D
tz2 tz1 SB 1
EK1 fr
e
a b FR OH 8
K
V
OW 3

TZ M 3
1 2 10 8 3 7 6 4 5 9 11 12
t3n´
SB 7
OW Z tw t1 t3n
W
6
R OH QRB t3 TSA
AL Z BV1 4
N BV1 t4
w

Si
s

QRC BV2 5
L
bl

M BV2
N 1 11
br FS
7118d01/0402 12
a10/0
7118

402

LOA25.173C17 L1 x y z cd e f g

LOA25.173C27 R A´ A B C D
tz2 tz1 SB 1
EK1 fr** W
LOA28.173A27 a b FR OH 8
K
V OW 3 1

TZ OW 3 2
1 2 10 8 3 7 6 4 5 9 11 12

SB M 3
tw t1 t3n´
W OW 6
Z
7
R OH
t3 TSA
Z
AL BV1 4
Si BV1 BV2 QRB. t4
L M BV2 5
N
11
FS
7118d02/0402 12

Not provided with the LOA28.173A27 1) LOA25.173C27 / LOA25.173C17 2) LOA28.173A27

8/10

Siemens Building Technologies CC1N7118en


HVAC Products 09.10.2002
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒั นา กทม. 10170.
website: https://www.add-furnace.com/ โทร: 02-888-3472
Line ID: @add11 Wechat ID: add0883001122

Connection diagram and internal diagram Control sequence

7
1
1
8
a
0
8

0
4
0
2
/
L1 x y z cd e f R A´ A B C D
LOA26.171B27 g

SB 1
tz2 tz1
EK1 fr
W
a b FR OH 8
With ARK21 K
V
remote lockout
OW 3
reset module TZ t3n
1 2 10 8 3 7 6 4 5 9 11 12
M 3
SB tw t1
OW Z 6
W

R OH QRB SA 7
Z
AL
t3 TSA
N SA BV1
Si BV1 4
N QRC

b
l
L

sw
M BV2 t4
N 1
10
br BV2 5

11
2 1013 FS
9 EK2 7118d05/0402 12
14
ARK21A27

7118a09/0402
L1 x y z cd ef LED1 R A´ A B C D
LOA36.171A27 g

SB 1
tz2 tz1
EK1 fr
W
a b FR
OH 8
With ARK21 K
V
remote lockout
L2
OW 3
reset module TZ t3n
1 2 10 8 3 7 6 4 5 9 11 12
M 3
SB
tw t1
OW Z 6
W

R OH QRB SA 7
Z
AL
t3 TSA
N SA BV1
Si BV1 4
N QRC
b
l

L
sw

M BV2 t4
N 1
br BV2 5
10

11
2 1013 FS
9 EK2 7118d05/0402 12
14
ARK21A27

Legend AL Alarm device OW Release contact of oil preheater


BV... Fuel valve OH Oil preheater
EK1 Lockout reset button QRB Photoresistive detector
EK2 Remote lockout reset button QRC Blue-flame detector
FR Flame relay with contacts «fr» bl = blue, br = brown, sw = black
fr Bridging contact for release contact of «OH» R Control thermostat or pressurestat
FS Flame signal SA Actuator with automatic setback
K Catch of flame relay for locking contact «tz1» SB Safety limit thermostat
in the event of premature flame signals or for locking Si External primary fuse
the contact when the flame signal is correct TZ Thermal-electric sequence switch
L1 Indication of faults (red) tz... Contacts of «TZ»
L2 Indication of operation (green) W Limit thermostat or pressure switch
LED1 Indication of flame strength (green) V Flame signal amplifier
M Burner motor Z Ignition transformer

TSA Ignition safety time A´ Beginning of the startup sequence with burners using an «OH»
tw Waiting time A Beginning of the startup sequence with burners using no «OH»
t1 Prepurge time B Time of flame establishment
t3 Preignition time C Running position
t3n Long postignition time D Controlled shutdown by «R»
t3n´ Short postignition time
t4 Interval between flame signal and release of «BV2» Control signals delivered by the LOA...
Required input signals
Permissible input signals

9/10

Siemens Building Technologies CC1N7118en


HVAC Products 09.10.2002
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวฒั นา กทม. 10170.
website: https://www.add-furnace.com/ โทร: 02-888-3472
Line ID: @add11 Wechat ID: add0883001122

Dimensions

Dimensions in mm

22
LOA...

5,5
62,5

7118m05/1002
88 41,5

91

LOA2... LOA3...

62,5
62,5

47
47

xxxxxxxxxx xxxxxxxxxx

36,5 7118m03/0300

Status indication, orange Indication

of flame strength, green

83,5
Remote lockout reset
23 12 67,5
module ARK21A27
66
50

+ +

7118m04/0300

Remote lockout reset module for use with the LOA26... / LOA36...
Printed circuit board with no housing.
Degree of protection IP 00, which means that protection against electric shock hazard
must be ensured through mounting.
Do not place any metal objects in the hatched area.
The module must be fitted with the help of spacers made of plastic.
Do not use spacers made of metal.

10/10