Applied Product Solution
For Data Center
CLIVET SPA
Via Camp Lonc 25, Z.I. Villapaiera
32032 Feltre (BL) - Italy
Tel. +39 0439 3131 - Fax +39 0439 313300
[email protected]
Demand of Data Center Benefits of Clivet Applied Products
Process requirements
● Electronic components are sensitive to temperature,
humidity, and cleanliness, so these factors need to
be under strict control
● Considering the overall use of users, the working conditions with the largest proportion of use are in the highest efficiency
range to ensure good energy saving effect.
Airflow organization ● Two-stage compression, surge margin is larger. Low-pressure head can prevent surge by preventing the speed from being
● Large air flow, small enthalpy difference too low. Under the condition of high pressure head, the speed of the impeller is actively increased and adjusted with guide
vane to achieve stable operation and expand the operating range of compressor. Adopt new surge current identification
● CFD simulation to prevent too cold/hot locally
technology, real-time detection of current waveform, accurate identification of surge risk, to achieve equipment protection.
01 02
Benefits of Clivet Applied Products
Air
flow
Refrigerant system
Glycol soluton
03 04
Benefits of Clivet Applied Products
APPLICATION SCENARIOS The air conditioner is under the floor, even if there is water leakage, it does not affect the server and the equipment room will
never be affected by water.
IDC data center, sealed heat/cold channel.
FEATURES
In-Array series VS In-Row series
Installed under the electrostatic floor Installed above the electrostatic floor
p
Energy Saving Installed at the bottom of the server panel, the floor can provide
protection and isolation
Installed side by side with the server panel, without protection
Water leak can cause fatal damage to the server
The water leaks out from under the floor, so there is no water danger
All DC inverter In-Array series precision air conditioner pPUE is as low as 1.008. It saves 71.7% more electricity than In-Row
series.
pPUE
Factory Fabrication
1.04
1.035
1.035
Product modularization. Installation of water pipes, connectors and other engineering installation transferred to factory
1.03
1.025 prefabrication, the installation efficiency increased by 90%+
1.02
1.015
1.01 1.008 Factory fabrication Assembled on site
1.005
1
In-Array series In-Row series
Space Saving
The air conditioner is placed under the electrostatic floor, which saves equipment room space. APPLICATION
The loading rate of the equipment room is increased by 18.2% compared with In-Row series, and the economic income is
In-Array series + High efficiency centrifugal chiller + Free Cooling + Clivet-BMS, realizing the equipment room PUE≤1.25.
increased by 18%+.
Server panel
In-Row series
High efficiency In-Array series High efficiency centrifugal chiller + Free Cooling
precision air conditioner
Electrostatic floor Electrostatic floor
Extension box
Clivet-BMS
(Support customized development)
05 06
Benefits of Clivet Applied Products
IT equipment panel
IT equipment panel
IT equipment panel
IT equipment panel
Chilled
water
Frame type structure, modular design. Flexible combination and easy to expand cooling capacity.
1 Standard with G4 filter, reduce the pollution of dust particles
module
module
module
Master
Slave
Slave
2
Master module and Slave module (before assembly) Unit after assembly
(Utility model patent, patent number: CN201520281128.X)
5
5 PTC heater, small heating resistance, high heat transfer EASY INSTALLATION
efficiency, safe and reliable Key components are pre-integrated from the factory to reduce the amount of on-site installation work. Standardized design,
easy to transport.
6 New rotary electric control box, front design, easy 8
7
maintenance
Elevator
7 High efficiency humidifier, large humidification to meet Corridor corner
07 08
Benefits of Clivet Applied Products
Cold storage: conventional chiller + dual-working condition centrifugal chiller + cold storage tank
In-Row Series
Cold storage applies to areas with peak and valley electricity prices. At night with valley electricity price, the dual-working
condition centrifugal chiller is used for cooling; in the daytime with peak electricity price, the stored cold capacity is discharged
APPLICATION SCENARIOS for cooling in various working conditions.
IDC data center, medium and large switching equipment
room, local high heat room, high heat density room and
modular data
Cold water
center. pipe network
Chiller
Chilled
PRODUCT INTRODUCTION water
pump
In-Row series precision air conditioner is a row level chilled water temperature control product. It is a
terminal air supply unit installed in the equipment room. It usually forms a complete refrigeration 18°C
Chilled
12°C 18°C
water
system together with water chiller, water pump and chilled water pipe, etc. It adopts EC fan, usually Cold water pump Cold water Cold water
pipe network pipe network pipe network
installed in the row of equipment panel, close to the heat source, providing heat dissipation solu
tions for medium and high density data centers, helping to build the next generation of green data Chilled Data center
water
centers. pump
12°C 7°C
Fans are backup to each other Professional device selection and design
Can be maintained online, no interruption to cooling in the process
of fan replacement Dual-working Glycol pump Ice storage coil
condition unit
Intelligent control Dual power supplies (optional)
Balance running time of each unit, extending service life When the power is cut off in one circuit, it can automatically
switch to the other circuit
High efficiency component Dry coil design Efficient matching Dual-working condition unit and cold storage system can be used as emergency cold sources for a more reliable system.
DC EC fan No dehumidification and Match with high efficiency Clivet chiller Tailored for peak and valley electricity prices to save costs.
Proportional integral water valve flow control humidification power consumption Clivet-BMS AI linkage control
The adoption of cold storage unit can reduce the unit capacity and the initial investment in chiller equipment.
0 power consumption wet film humidification
(optional)
APPLICATION
09 10
Benefits of Clivet Applied Products
Condensation heat recovery: heat pump centrifugal chiller/screw chiller + precision air conditioner Clivet-BMS
The HVAC systems of IDCs are complex. With the help of the Clivet-BMS, the systems can achieve efficient, stable, and energy
saving operations.
Hot water Heating, domestic hot water
pipe network
Hot water
pump
40°C 50°C 40°C
Management layer
Cloud Energy Air Air side
Mobile
Clivet-BMS DTU energy AI large screen display collection detection billing
O&M
efficiency system system system
Hot water Hot water
pipe network pipe
network
Hot water boiler
Cooling
tower Cold/heat
complementary
Control layer
Multi-agent Multi-agent
Cooling energy-saving energy-saving
water 32°C 37°C
control panel control panel AI core controller
pump (strong and weak (M2 power
current integrated) distribution panel) Clivet cloud gateway
Cold water
pipe network
Chiller
Equipment layer
Control switch, sensor, professional valve
(proportional-integral valve, electric valve, dynamic balance adjusting valve, smart valve)
Cold water pipe network
On-site self-control device
ADVANTAGES
Cold/Heat Transmission and Cooling
distribution MAHU FCU FAPU Lighting
source equipment
A large amount of condensation heat is generated during the long-term operation of data center. With the condensation and equipment
heat recovery system, the cooling requirements in summer, heating requirements in winter, and domestic hot water supply all Electromechanical equipment under control Ammeter Air quality Networked
Heat meter detector thermostat
year round in administrative and office areas of the data center can be met. It is energy efficient, improves the comprehensive
energy efficiency of the data center and brings about more economic benefits.
APPLICATION ADVANTAGES
Medium and large data centers The intelligent control of equipment room devices and air side air-conditioning devices is achieved. Based on the running
trend, the system can implement self diagnosis, adjust the operation status, maintain efficient operation of the entire
air-conditioning system, reduce the data center PUE, and save management and operation costs.
11 12
Clivet Application Solutions
The platform aims to provide visualized, integrated and Intelligent control of chiller plant system and wind
economical energy management services with large data system, cooperate with software application
processing capabilities and provide users with energy
information storage, display, calculation and analysis in the
form of cloud-hosted ser vices, thus maximizing
energy-saving potential and reducing energy consumption.
350-1,700RT 6.5kW
80-450RT 30-180kW
13 14
Reference Projects
1. Auto switch to power supply by generator when the mains is cut, auto start of unit within three minutes.
PERFORMANCE PARAMETERS
2. Low water temperature and low flow operation of cooling water; cooling water pipeline bypass control.
● Cooling capacity: 1800/2000RT
3. Hot gas bypass design to guarantee stable water temperature under low load; load of chiller can be as low as 10%.
● Working conditions: 19/14°C (chilled water), 32/37°C (cooling water)
● Special requirement: high temperature chiller 4. Energy saving design; cooling for equipment room by cooling tower plate heat exchanger in seasons with low temperature.
UNIT SELECTION: 6. Large capacity cold storage tank that can ensure cooling supply for four hours in emergencies.
High voltage centrifugal chiller 1800RT 2
15 16
Reference Projects
1. Project overview
Pengcheng Cloud Brain directly connects to the innovation base platform of the national new-generation AI development strat-
egy and major scientific engineering, and focuses on areas such as new-generation AI basic research and major scientific and
theoretic issues for information processing breakthrough. The construction of Pengcheng Cloud Brain also represents the
important development of diversified computing methods, and is of great reference value to the further application and prac- China Mobile (2020-2021) China Mobile (2018-2019) China Telecom Guangdong
tice of heterogeneous computing.
2. Design overview
The equipment room building of Pengcheng Data Center has three floors. Floor 1 is for distribution substations, battery rooms,
and operator equipment rooms. Floor 2 and Floor 3 are for data equipment rooms, control rooms, test equipment rooms, and
offices. Steel structure is adopted. The cold source module and chilled/cooling hydraulic module are configured on Floor 1.
3. System overview
The total cooling capacity of the data center is about 4428kW. Three 700RT centrifugal chillers in 2+1 mode are adopted. The
cooling capacity of each chiller is 2461kW (700RT).
Each refrigeration station has three cold source hydraulic modules, one chilled hydraulic module, and one cooling hydraulic
module. Floor 2 is for the liquid cooled cooling system, including one liquid cooled module. Two cold storage tanks are set out-
Shenzhen Sunway Huawei data center
doors. Shenyang Railway Bureau
Communication in Yantai