1. The document provides guidance on communication settings for various PLC models including the EH-150, Micro-EH, and CPU104/208/308/316. It describes dip switch and toggle switch settings for configuring communication port parameters such as baud rate, protocol, and port type. 2. Wiring diagrams are provided for connecting the PLCs to devices like PCs, HMIs, and modems via RS-232, RS-422, and RS-485 interfaces. 3. The settings tables explain how to configure the port number, protocol, baud rate, and other parameters through register values for proprietary "H-protocol" communication.

Uploaded by

Eta Courses
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
51 views3 pages

Hitach Programming Cable

1. The document provides guidance on communication settings for various PLC models including the EH-150, Micro-EH, and CPU104/208/308/316. It describes dip switch and toggle switch settings for configuring communication port parameters such as baud rate, protocol, and port type. 2. Wiring diagrams are provided for connecting the PLCs to devices like PCs, HMIs, and modems via RS-232, RS-422, and RS-485 interfaces. 3. The settings tables explain how to configure the port number, protocol, baud rate, and other parameters through register values for proprietary "H-protocol" communication.

Uploaded by

Eta Courses
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

V1, Mar.

2002

Communication Setting Guidance


1. EH-150
Dip and toggle switch configuration
1 2 3 4 5 6 T
RUN/STOP Remote ON - - - - - -
mode RUN Switch off - - - - - -
Port 1 Dedicated port 4,800 bps - - ON ON ON - -
(Programming / HMI) 9,600 bps - - off ON ON - -
19,200 bps - - ON off ON - -
38,400 bps - - off off ON - -
General purpose port Modem mode - ON - - off - -
Normal mode - off - - off - -
Port 2 Dedicated port 4,800 bps - - - - - off off
(Programming / HMI) 9,600 bps - - - - - ON off
19,200 bps - - - - - off ON
38,400 bps - - - - - ON ON

Port configuration ON
Toggle switch
Ø CPU104 / 208 / 308 / 316 [ WRF036 ] (SW T)
OFF
Port type Setting value 8
RS-232C (Default) H0003 (à H0002) Dip switch 7
RS-422 H0005 (à H0004) 6
RS-485 H0009 (à H0008) 5
OFF 4 ON
Note : When the baud rate is set properly, CPU changes
3
it into the value in ( ) automatically. 2
1

Ø CPU104A / 208A / 308A / 316A / 448 [ WRF037 ]


Port type Setting value CPU changes to Next power ON
RS-232C (Default) H8000 H0?00 H0000
RS-422 H8100 H0?00 H0500
RS-485 H8200 H0?00 H0A00
RS-485 St. No. HA2xx H2?xx H2Axx
Note : This setting is valid after the next power ON. The above “?” depends on the last setting.
Note : xx : station number (BCD)

Please see the below table for further information.

15 14 13 12 11 10 9 8 7 0
WRF037 a b c d e f g h i

bit Value Set by


a 1 : Request to set 1 : User, 0 : CPU
b 0 : Procedure 1 (Std.), 1 : Procedure 2 User
c 0 : Standard, 1 : With station No. User
d Not used -
e, f 00 : RS-232C, 01 : RS-422, 10 : RS-485 CPU
g, h 00 : RS-232C, 01 : RS-422, 10 : RS-485 User
i Station number (BCD h’00 – h’31) User
Note : Procedure 2 is another different H-protocol for peer-to-peer communication without LUMP
address, ACK/NAK and ENQ.
Modem setting [ WRF01A ]

Baud rate [bps] Setting value


2400 H0000 or H0001
4800 H0002
9600 H0004
19.2k H0008
38.4k H0010
57.6k H0020

Cable connection

EH-150 to PC (D-sub 9 pole) EH-150 to EH-HMI (D-sub 15 pole)

EH-150 PC EH-150 EH-HMI


RS-232C RS-232C
1 : SG 5 : GND 1 : SG 5 : GND
5 : SD 2 : RX 5 : SD 2 : RX
6 : RD 3 : TX 6 : RD 3 : TX
7 : DR 4 : DTR 7 : DR 4 : 5V
8 : RS 8 : CTS 8 : RS 11 : CTS
1 : DCD
6 : DSR

EH-150 to EH-HMI (D-sub 15 pole) EH-150 to EH-HMI (D-sub 15 pole)

EH-150 EH-HMI EH-150 EH-HMI


RS-422 RS-485
6: RXN 6 : CHA- 6: RXN 6 : CHA-
5 : TXN 7 : CHB- 5 : TXN 7 : CHB-
7 : RX 14 : CHA+ 7 : RX 14 : CHA+
4 : TX 15 : CHB+ 4 : TX 15 : CHB+
10 : CTS 10 : CTS
11 : RTS 11 : RTS

EH-150 to Modem (D-sub 25/15/9 pole)


Connector on CPU (Socket side)
Modem D-sub
EH-150 25 / 15 / 9 pin Pin 1
RS-232C
1: SG 7 9 5 SG
2 : CD 8 1 1 DCD
3 : ER1 20 8 4 DTR
5 : SD 2 2 3 TXD Pin 8
6 : RD 3 6 2 RXD
7 : DR 6 7 6 DSR
8 : RS 4 12 7 RTS
2. MICRO-EH

Port 1 : RS-232C
Dip Switch Setting
Baud rate [bps] SW 1 SW 2 SW 3 SW 4
38.4k ON off ON off
19.2k ON off off off
9600 off off ON off
4800 off off off off
Modem off ON off off

Cable connection
MICRO-EH to PC (D-sub 9 pole) MICRO-EH to EH-HMI (D-sub 15 pole)

MICRO-EH PC MICRO-EH EH-HMI


1 : SG 5 : GND 1 : SG 5 : GND
5 : SD 2 : RX 5 : SD 2 : RX
6 : RD 3 : TX 6 : RD 3 : TX
7 : DR 4 : DTR 7 : DR 4 : 5V
8 : RS 8 : CTS 8 : RS 11 : CTS
1 : DCD
6 : DSR
Connector on CPU (Socket side)

Pin 1
Port 1

Pin 8
Port 2 : RS-422/485

Port configuration [ WRF03D ]


Baud rate [bps] Standard H-protocol Station number H-protocol
38.4k H8300 (à H0300) HA3xx (à H23xx)
19.2k H8200 (à H0200) HA2xx (à H22xx)
9600 H8100 (à H0100) HA1xx (à H21xx)
4800 H8000 (à H0000) HA0xx (à H20xx)
Note : xx : station number (BCD)
Note : When the baud rate is set properly, CPU changes it into the value in ( ) automatically.

Cable connection
MICRO-EH to EH-HMI (RS-422) MICRO-EH to EH-HMI (RS-485)

MICRO-EH EH-HMI MICRO-EH EH-HMI


RS-422 RS-485
10: RDN 6 : CHA- 10: RDN 6 : CHA-
12 : SDN 7 : CHB- 12 : SDN 7 : CHB-
11 : RDP 14 : CHA+ 11 : RDP 14 : CHA+
13 : SDP 15 : CHB+ 13 : SDP 15 : CHB+
10 : CTS 10 : CTS
11 : RTS 11 : RTS