Data sheet 3RV2041-4RA15

Circuit breaker size S3 for motor protection, CLASS 10 A-release 65...84 A


N-release 1170 A screw terminal Standard switching capacity with
transverse auxiliary switches 1 NO+1 NC

product brand name SIRIUS


product designation Circuit breaker
design of the product For motor protection
product type designation 3RV2
General technical data
size of the circuit-breaker S3
size of contactor can be combined company-specific S3
product extension auxiliary switch Yes
power loss [W] for rated value of the current
● at AC in hot operating state 34 W
● at AC in hot operating state per pole 11.3 W
insulation voltage with degree of pollution 3 at AC rated 1 000 V
value
surge voltage resistance rated value 8 kV
shock resistance according to IEC 60068-2-27 25g / 11 ms Sinus
mechanical service life (switching cycles)
● of the main contacts typical 25 000
● of auxiliary contacts typical 25 000
electrical endurance (switching cycles) typical 25 000
type of protection according to ATEX directive Ex II (2) GD
2014/34/EU
certificate of suitability according to ATEX directive DMT 02 ATEX F 001
2014/34/EU
reference code according to IEC 81346-2 Q
Substance Prohibitance (Date) 03/01/2017
Ambient conditions
installation altitude at height above sea level maximum 2 000 m
ambient temperature
● during operation -20 ... +60 °C
● during storage -50 ... +80 °C
● during transport -50 ... +80 °C
relative humidity during operation 10 ... 95 %
Main circuit
number of poles for main current circuit 3
adjustable current response value current of the 65 ... 84 A
current-dependent overload release
operating voltage
● rated value 20 ... 690 V
● at AC-3 rated value maximum 690 V
● at AC-3e rated value maximum 690 V
operating frequency rated value 50 ... 60 Hz
operational current rated value 84 A

3RV20414RA15 Subject to change without notice


11/4/2022
Page 1/6 © Copyright Siemens
operational current
● at AC-3 at 400 V rated value 84 A
● at AC-3e at 400 V rated value 84 A
operating power
● at AC-3
— at 230 V rated value 22 kW
— at 400 V rated value 45 kW
— at 500 V rated value 55 kW
— at 690 V rated value 75 kW
● at AC-3e
— at 230 V rated value 22 kW
— at 400 V rated value 45 kW
— at 500 V rated value 55 kW
— at 690 V rated value 75 kW
operating frequency
● at AC-3 maximum 15 1/h
● at AC-3e maximum 15 1/h
Auxiliary circuit
design of the auxiliary switch transverse
number of NC contacts for auxiliary contacts 1
● note 1
number of NO contacts for auxiliary contacts 1
● note 1
operational current of auxiliary contacts at AC-15
● at 24 V 2A
● at 230 V 0.5 A
operational current of auxiliary contacts at DC-13
● at 24 V 1A
● at 60 V 0.15 A
Protective and monitoring functions
product function
● ground fault detection No
● phase failure detection Yes
trip class CLASS 10
design of the overload release thermal
breaking capacity maximum short-circuit current (Icu)
● at AC at 240 V rated value 100 kA
● at AC at 400 V rated value 65 kA
● at AC at 500 V rated value 8 kA
● at AC at 690 V rated value 5 kA
breaking capacity operating short-circuit current (Ics)
at AC
● at 240 V rated value 100 kA
● at 400 V rated value 30 kA
● at 500 V rated value 4 kA
● at 690 V rated value 3 kA
response value current of instantaneous short-circuit trip 1 170 A
unit
UL/CSA ratings
full-load current (FLA) for 3-phase AC motor
● at 480 V rated value 84 A
● at 600 V rated value 84 A
yielded mechanical performance [hp]
● for single-phase AC motor
— at 110/120 V rated value 7.5 hp
— at 230 V rated value 15 hp
● for 3-phase AC motor
— at 200/208 V rated value 25 hp
— at 220/230 V rated value 30 hp
— at 460/480 V rated value 60 hp
— at 575/600 V rated value 75 hp
contact rating of auxiliary contacts according to UL C300 / R300
Short-circuit protection

3RV20414RA15 Subject to change without notice


11/4/2022
Page 2/6 © Copyright Siemens
product function short circuit protection Yes
design of the short-circuit trip magnetic
Installation/ mounting/ dimensions
mounting position any
fastening method screw and snap-on mounting onto 35 mm standard mounting rail
according to DIN EN 60715
height 165 mm
width 70 mm
depth 176 mm
required spacing
● with side-by-side mounting at the side 0 mm
● for grounded parts at 400 V
— downwards 70 mm
— upwards 70 mm
— at the side 10 mm
● for live parts at 400 V
— downwards 70 mm
— upwards 70 mm
— at the side 10 mm
● for grounded parts at 500 V
— downwards 110 mm
— upwards 110 mm
— at the side 10 mm
● for live parts at 500 V
— downwards 110 mm
— upwards 110 mm
— at the side 10 mm
● for grounded parts at 690 V
— downwards 150 mm
— upwards 150 mm
— at the side 30 mm
● for live parts at 690 V
— downwards 150 mm
— upwards 150 mm
— at the side 30 mm
Connections/ Terminals
type of electrical connection
● for main current circuit screw-type terminals
● for auxiliary and control circuit screw-type terminals
arrangement of electrical connectors for main current Top and bottom
circuit
type of connectable conductor cross-sections
● for main contacts
— solid 2x (2.5 ... 16 mm²)
— solid or stranded 2x (2,5 ... 50 mm²), 1x (10 ... 70 mm²)
— finely stranded with core end processing 2x (2.5 ... 35 mm²), 1x (2.5 ... 50 mm²)
— finely stranded without core end processing 2x (10 ... 35 mm²), 1x (10 ... 50 mm²)
type of connectable conductor cross-sections
● for auxiliary contacts
— finely stranded with core end processing 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
● at AWG cables for auxiliary contacts 2x (20 ... 16), 2x (18 ... 14)
tightening torque
● for main contacts for ring cable lug 4.5 ... 6 N·m
outer diameter of the usable ring cable lug maximum 19 mm
tightening torque
● for main contacts with screw-type terminals 4.5 ... 6 N·m
● for auxiliary contacts with screw-type terminals 0.8 ... 1.2 N·m
design of the thread of the connection screw
● of the auxiliary and control contacts M3
Safety related data
B10 value
● with high demand rate according to SN 31920 5 000
proportion of dangerous failures
● with low demand rate according to SN 31920 50 %

3RV20414RA15 Subject to change without notice


11/4/2022
Page 3/6 © Copyright Siemens
● with high demand rate according to SN 31920 50 %
T1 value for proof test interval or service life according to 10 y
IEC 61508
protection class IP on the front according to IEC IP20
60529
touch protection on the front according to IEC 60529 finger-safe, for vertical contact from the front
display version for switching status Handle
Certificates/ approvals
General Product Approval

Confirmation KC

For use in hazardous locations Declaration of Conformity Test Certificates

Type Test Certific- Special Test Certific-


ates/Test Report ate

Marine / Shipping

Marine / Shipping other Railway

Confirmation Confirmation Vibration and Shock

Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RV2041-4RA15
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RV2041-4RA15
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RV2041-4RA15
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RV2041-4RA15&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RV2041-4RA15/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RV2041-4RA15&objecttype=14&gridview=view1

3RV20414RA15 Subject to change without notice


11/4/2022
Page 4/6 © Copyright Siemens
1/L1

3/L2

5/L3

13

21

-F

I> I> I>


2/T1

4/T2

6/T3

14

22

last modified: 6/25/2022

3RV20414RA15 Subject to change without notice


11/4/2022
Page 5/6 © Copyright Siemens
3RV20414RA15 Subject to change without notice
11/4/2022
Page 6/6 © Copyright Siemens