INSPECTION CHECKLIST
INSPECTION REQUEST NO: DATE:
Item(s) to be Inspected:
OTDR Test on Fiber Optic cables
Comments
Item
ITEM FOR INSPECTION SUBCON. CSO PERTAMINA Remarks
No.
Check that a long launch lead cable is used. This will allow the OTDR to settle Note. 1
2 down after the initial pulse and provides a reference cable for testing the first
connector on the cable.
Check that the each end face of connector of the test cables is clean and free
3
from dirt prior to plug- in.
5 Ensure to use correct mating adapter and fiber connector (where applicable).
Ensure that the set-up of OTDR is not set to auto- configuration options enabled;
7
else OTDR will struggle with the configuration of the FFT sensor.
Ensure that all testing on the Micro strain systems is performed at 1550 nm with
8
fiber refractive index of 1.4682.
Ensure the distance setting at the OTDR is set to a distance longer than the total
9
expected length of the cable.
Ensure to set the pulse width setting as necessary to slightly increase the pulse
10
width to allow for the excess losses from the start and end sensors.
Ensure to test the Fiber Optic cable in both directions, first from the lead-in, then
11
from the lead- out.
Check that the fiber loss result meets the recommended typical reading of
12
0.25dB/km and an increase margin of 0.02dB/Km is acceptable.
13 Check that the fusion splices losses must be less than 0.05dB at a maximum.
14 Check that the connector loss must be less than 0.5dB at maximum.
NOTE:
1. Always start with the OTDR set for the shortest pulse width for best resolution and a range at least twice (2) times the length of the cable you are testing.