Iriset Iriset: Telecom Cables (Copper) Telecom Cables (Copper)
Iriset Iriset: Telecom Cables (Copper) Telecom Cables (Copper)
TELECOM
TELECOMCABLES
CABLES(COPPER)
(COPPER)
इरिसेट IRISET
TC 1
June 2022
TC 1
TELECOM CABLES (COPPER)
INDEX
8 Testing of Cables
8.1 Types of tests 57
8.2 Acceptance tests for 6 Quad PIJF cables
8.3 Standard values of various tests
8.4 Mandatory Check & Tests to be done before commissioning of
BPAC/SSDAC/MSDAC applications on 4/6 Quad/PIJF cables
8.5 Causes for cable failures & precautions
8.6 Fault localisation tests
© IRISET
“This is the intellectual property for exclusive use of Indian Railways. No part of this publication
may be stored in a retrieval system, transmitted or reproduced in any way, including but not
limited to photo copy, photograph, magnetic, optical or other record without the prior agreement
and written permission of IRISET, Secunderabad, India”
http://www.iriset.indianrailways.gov.in
CHAPTER-1
For administrative purpose Telephone exchanges, Railnet (Intranet), UTS/PRS, FOIS (Freight
Operations Information System), MIS (Management Information System) MMIS (Material
management Information and IRPSM (Indian Railway Projects and Sanction Management) etc
are in use. Whereas for Train operation various safety circuits like Block, LC gate
communication, IB Phone (Intermediate Block), BPAC (Block Proving Axle Counter), EC
(Emergency Communication) and Train Traffic Control communication etc. are in use.
For all types of above Telecom networks, different types of Telecom links are established by
using Telecom trunk cables and tail cables.
Overhead lines may come in contact with trees, bushes, etc. and cause low insulation.
Due to natural calamities and ravages of human beings, overhead lines are Prone to a
higher fault incidence. Hence, less liable to damage as well as faults.
Due to headway considerations, the maximum number of pairs on a pole route in Over
Head Alignment is limited to 16.
Due to induced voltage effects from the 25 KV OHE system, Over Head lines are not fit for
Telecommunication circuits in RE area.
Low maintenance cost.
General appearance is better.
Unlike electrical noise, cross talk is the main criteria in telecom circuits. Cross talk arises mainly
from unbalanced electrostatic and electromagnetic couplings between the pairs of conductors
and sheath with respect to earth. These effects are respectively be measured in terms of
capacitance unbalance and mutual capacitance. At voice frequencies, capacitance unbalance is
the major source of cross talk. In order to reduce the cross talk in cables, insulated wires are
twisted together at regular intervals on their own axis helical throughout its length.
Different twist lengths are used to transpose the circuits continuously with respect to
one another pairs/quads. After laying the cable, if capacitance unbalance is persisting, it can
be reduced by introducing the external fixed capacitors. This process is called as “BALANCING
OF CABLES”.
In star quad cables diagonally opposite conductors are formed as one pair and two wires of the
pair are kept at an equal distance from the conductors of the remaining pair.
The four primary elements of cable should be taken into Consideration while designing
the circuits.
R = Series Resistance
L = Series self inductance
C = shunt capacitance
G = Shunt conductance [Leakage]
These four quantities per unit length of a pair of telephone lines are called primary elements of
the lines.
When alternating current flows through the lines, there will be voltage drop due to both
resistance and inductance and so they may be assumed to be present in series in the lines and
as capacitance and leakage are present between the lines, current is lost through them during
transmission.
Z0 = (L/C) are independent of frequency and as such all the frequency components are equally
attenuated during propagation through line. All the different types of distortions that are likely to
be introduced during transmission through long lines are thus eliminated when the condition GL
= RC is satisfied.
Telephone line is a balanced twisted pair transmission line and its characteristic impedance Z0
can be calculated from the data which was given by the manufacturer.
The impedance, which describes the combined effect of resistance (R), inductive reactance (XL)
and capacitive reactance (XC) in an AC circuit, whether it occurs in a single component, or in a
whole circuit.
Because impedance is affected by reactance (X), as well as resistance (R), it is also affected by
frequency (ƒ) and the value of impedance will change at different frequencies.
The component or circuit will not have the same impedance at all frequencies. It is common for
inputs and outputs on many types of equipment to have their impedances quoted in Ohms and
to assume a common frequency for that particular type of equipment. For example, audio
commonly uses a frequency of 1 kHz as the standard for measuring impedance. This is
because 1 kHz is approximately the centre of an audio amplifier s bandwidth, measured on a
logarithmic scale, as shown in the above figure.
The wiring to the subscriber in telephone networks is generally done in twisted pair cable. It is
possible to manufacture this kind of cable to have a 600 Ω characteristic impedance but it will
only be this value at one specific frequency. This might be quoted as a nominal 600 Ω
impedance at 800 Hz or 1 kHz. Below this frequency the characteristic impedance rapidly rises
and becomes more and more dominated by the ohmic resistance of the cable as the frequency
falls. At the bottom of the audio band the impedance can be several tens of kilo-ohms. On the
other hand, at high frequency in the MHz region, the characteristic impedance flattens out to
something almost constant.
When the diameter of the conductors is increased, the value of R is reduced. This is not
possible considering its size and cost. If the value of G is increased, the transmission loss will
be increased which is not acceptable to a long-distance transmission line. Therefore, there is
one way to increase the value of GL by increasing the value of L. This is achieved by using the
coils of suitable inductance value wound on dust cores are placed in series with the lines at
suitable intervals. This is called coil loading or lump loading.
IRISET 4 TC1 - Telecom Cables (Copper)
Introduction of Telecom Cables
The object of loading cables for voice frequencies is almost solely for the purpose of reducing
the attenuation constant per Km. For long distance cables and for trunk cables 118 mH coils are
used and spaced at regular intervalls of 2000 mtrs. Each (2000 mtrs) of such a cable then
appears as one section of a low pass filter in which L = 118 mH(59 mH in each limb of a pair)
and the shunt capacitance is C x S (C = Capacity per Km and S = spacing in Km)
Note: Unloaded cable has an attenuation of approx. 0.65 dB/ Km. This system of loading,
increases the Zo from 470 ohms to approximately 1,100 ohms and reduces attenuation to 1/3 of
its unloaded value i.e., 0.25dB/Km and this is the practice being followed in 6 Quad Cables.
(At present quad cables drum length of 1000 meters. are in use, hence number of Normal Joints
have been minimised)
The process of measuring the capacitance unbalances between various quads and earth, within
the quad and with adjacent quads and minimising the unbalances by connecting condensers is
called V.F. balancing.
Permissible limits of capacitance unbalance for full and half loading sections are 40 pF and 20
pF respectively.
IRISET 5 TC1 - Telecom Cables (Copper)
Introduction of Telecom Cables
e1, e2, e3, e4 - earth couplings & c1, c2, c3, c4 - capacitive couplings
14. Twisted Pair: A cable composed of two small-insulated conductors twisted together without
a common covering.
15. Cable: An assembly of one or more insulated conductors or optical fibers or combination
of both, within an enveloping jacket.
16. Underground Cable: A cable installed below the surface of the earth in conduit or ducts.
17. Unit-type Cable: A cable in which the pairs are first formed into bound units and then the
units are formed together to make the completed cable.
18. Moisture Barrier: In a cable, the material, usually in the form of an axially laid aluminium
foil/polyethylene laminated film, placed immediately inside the sheath. Generally called
Poly- Aluminium laminate moisture barrier.
19. Filling Compound (Jelly): It is a water resistance compound. The cable core shall be fully
filled with jelly and this will be used in joints also.
19. Sheath: A protective covering made of metals or plastics over the cable core.
20. Wire gauge: It is a measurement of wire diameter. This determines the amount of electric
current a wire can safely carry, as well as its electrical resistance. The following chart
gives above information on different copper wire gauges.
CHAPTER-2
Paired cables are balanced, by using two closely spaced conductors twisted together. The
purpose of twisting the wires is to reduce the electrical interference from neighbouring pairs.
A ground shield is used to prevent high frequency noise and balanced wires also reject noise
coming from ground loops.
The following representation shows potential difference between “Conductors without twist
(Fig.A) and Conductors with twist (Fig.B)”
Net induced voltages on L1 and L2 in twisted pair (figure B) are the same. Hence, no potential
difference, no current flow at destination then no cross-talk from adjacent pair or circuit.
2.4 Applications in Railways: These cables are used for indoor installation for the
interconnection of telephones & electronic equipment, Telephone switching exchanges, Switch
board & telephone wiring (MDF, SDH, DWDM, and DSLAM etc.) PDH/SDH systems, RS-232
Communication Systems and Digital Transmission networks.
2.5 Standard make of Switch Board Cables: Delton cables, Reliance cables, Finolex
cables, Havells cables etc.
2.6.1 Conductors
Each conductor shall consist of a solid wire of annealed high conductivity tinned copper circular
in cross section, uniform in physical, mechanical and electrical properties. The conductor is free
from spills, splits and defects of any other kind and shall conform to specification IS: 8130.The
conductor is uniformly coated with tin. Characteristic impedance of the conductor is 600 Ohms
2.6.2 Insulation
Each conductor is insulated with PVC. The PVC shall be applied by the extrusion process and
shall form a compact homogeneous uniform core. The PVC insulation shall have distinct single
colour for identification of each conductor.
For a hundred pairs cable, each unit consists of 20 pairs and there are all-together five units.
Mate colours of each unit is White, Red, Black and Yellow. The colour scheme of the 1st wire of
all other units is the same as shown above for the first unit.
2.6.3 Twining:
Two insulated conductors shall be uniformly twisted together with a right hand lay which shall
not exceed 100mm.Twisted pair shall be laid up to form a compact and symmetrical cable. The
lay of any two adjacent pairs shall be so chosen as to reduce the cross talk to the minimum
possible extent. The cable core consisting of the required number of twisted pairs shall be
stranded in concentric layers. The cable core shall be lapped with polythene tape.
2.6.4 Ripcord:
A non-metallic suitable ripcord shall be laid longitudinally under the PVC sheath. It shall
provide an effective means of ripping the PVC sheath longitudinally to facilitate the removal of
PVC sheath.
The cable shall be wound on suitable wooden drums/rolls /coils and shall be strong enough to
withstand the stress and strain of transportation and handling.
For data communication, two types of cable are used for LAN network:
i. UTP: Unshielded twisted pair
ii. STP: Shielded twisted pair
This cable is less expensive than a shielded twisted pair, less bulky and is also easier to work
with. It is, limited to segments no longer than 100 meters and generally does not transmit as fast
as its shielded relative. Unshielded twisted pair cabling comes in different grades that are
assigned to six standard categories created by the Electronic Industry Alliance and the
Telecommunications Industry Association (EIA/TIA).
CAT1 is typically used for telephone wire. This type of wire is not capable of supporting
computer network traffic and is not twisted. CAT1 is also used by telco companies providing
ISDN and PSTN services. In such cases the wiring between the customer's site and the telco‟s
network is performed using CAT 1 type cable.
CAT2, CAT3, CAT4, CAT5/5e, CAT6 & CAT 7 are network wire specifications. This type of wire
can support computer network and telephone traffic. CAT2 is used mostly for token ring
networks, supporting speeds up to 4 Mbps. For higher network speeds (100 Mbps or higher)
CAT5e must be used, but for the almost extinct 10 Mbps speed requirements, CAT3 will suffice.
CAT3, CAT4 and CAT5 cables are actually 4 pairs of twisted copper wires and CAT5 has more
twists per inch than CAT3 therefore can run at higher speeds and greater lengths. The "twist"
effect of each pair in the cables ensures any interference presented/picked up on one cable is
cancelled out by the cable's partner which twists around the initial cable. CAT3 and CAT4 are
both used for Token Ring networks -- where CAT 3 can provide support of a maximum 10Mbps,
while CAT4 pushed the limit up to 16Mbps. Both categories have a limit of 100 meters.
The more popular CAT5 wire was later on replaced by the CAT5e specification which provides
improved crosstalk specification, allowing it to support speeds of up to 1Gbps. CAT5e is the
most widely used cabling specification world-wide and unlike the category cables that follow, is
very forgiving when the cable termination and deployment guidelines are not met.
CAT6 wire was originally designed to support gigabit Ethernet, although there are standards
that will allow gigabit transmission over CAT5e wire. It is similar to CAT5e wire, but contains a
physical separator between the four pairs to further reduce electromagnetic interference. CAT6
is able to support speeds of 1Gbps for lengths of up to 100 meters, and 10Gbps is also
supported for lengths of up to 55 meters.
Today, most new cabling installations use CAT6 as a standard, however it is important to note
that all cabling components (jacks, patch panels, patch cords etc) must be CAT6 certified and
extra caution must be given to the proper termination of the cable ends.
In 2009, CAT6A was introduced as a higher specification cable, offering better immunization to
crosstalk and electromagnetic interference.
Organizations performing installations using CAT6 cabling should request a thorough test report
using a certified cable analyzer, to ensure the installation has been performed according to
CAT6 guidelines & standards.
CAT7 is a newer copper cable specification designed to support speeds of 10Gbps at lengths of
up to 100 meters. To achieve this, the cable features four individually shielded pairs plus an
additional cable shield to protect the signals from crosstalk and electromagnetic interference
(EMI).
Due to the extremely high data rates, all components used throughout the installation of a CAT7
cabling infrastructure must be CAT7 certified. This includes patch panels, patch cords, jacks
and RJ-45 connectors. Failing to use CAT7 certified components will result in the overall
performance degradation and failure of any CAT7 certification tests (e.g using a Cable
Analyzer) since CAT7 performance standards are most likely not to be met. Today, CAT7 is
usually used in Data Centres for backbone connections between servers, network switches and
storage devices.
Conductor: Each conductor is made up of annealed copper of dia. 0.5mm.and PVC insulated.
USE: UTP cable is connected with the connector known as RJ-45 and IO box. Eight no. of wires
are connected to these RJ 45 connector or IO box. Thick Ethernet cable is also used to connect
a 15-pin connector known as DB-15 or DIX.
Coaxial cable often called coax is the round and flexible cable. Four separate elements are
identified, by the cross-sectional view. In the center there is a copper wire, carrying the signal.
Encasing this wire is a layer of non-conducting insulation made up of PVC or Teflon. Outside
the insulation, forming a protective sleeve around the conducting wire and its insulation, another
layer made up of a braided mesh of copper or Aluminium. This layer protects the transmitted
signal from the electromagnetic interference known as noise that can distort the transmitted
signal. Finally, outside the braided sleeve is an outer shield or jacket, made of either PVC or a
fire-resistant material such as Teflon. The coaxial cable comes in various forms for networking
a. Thin Ethernet or thin wire: Ethernet is based on the 3/8-inch coaxial cabling known as RG-
58. This Thinned cabling can carry a signal for about 185 meters. Above this the signal
begins to degrade.
Thin Ethernet LANs Coaxial cable is connected with the BNC (Bayonet Neill Concelman)
connector to make connection with the equipment.
b. Thick Ethernet: is based on less flexible coaxial cabling about ½ inch thick. Also known as
RG-8. Thick net cabling can carry signals farther than Thinned cabling about 500meters
and thus is often used as the backbone connecting.
A single compromise ratio is also desirable for certain fields of use because it simplifies
manufacturing and merchandising problems. These considerations have led to standardization,
in effect, of a single coaxial conductor diameter ratio for high frequency and microwave
application. This ratio (2.3) results in a nominal characteristic impedance of about 50 ohms. The
medium between conductors is assumed to be a gas.
CHAPTER-3
3.1 Introduction
PIJF telephone cables are widely used in Railways for local loop and other networks due to
improved technology and simplicity in installation and maintenance.
Indian Railway Standard specification for Polythene insulated polythene sheathed jelly filled
telephone. cable with Poly-Al Moisture Barrier is IRS-TC: 41/97 (RDSO spec)
B C D E F
A
A
Jelly filled cable is an underground cable having polythene as insulation on conductors and the
inter-spaces between the conductors is fully filled with petroleum jelly. Petroleum jelly prevents
ingress of moisture and water inside the core in the event of any damages to the cable. The
Cable is circular throughout its length and is free from any physical defects.
Jelly filled cable is wound on strong wooden drums. The length of cable on any drum is 500 /
1000 meter + 10% unless single longer lengths are specified by purchaser for specific
application. The diameter of the yoke of the drums is not less than 20 times of the overall
diameter of the cable. Both ends of the cable are kept inside the drum to get access to the cable
ends battens are painted by red colour arrow.
Number of pairs: The cable shall be of different sizes varying from 10 to 200 pairs and above
with nominal conductor diameter 0.5mm or 0.63mm or 0.9mm. The Standard cable sizes shall
be 10,20 50 100 and 200 pairs armoured / un-armoured.
Conductor: Each conductor shall consist of a solid round wire of annealed high conductivity
copper, smoothly drawn, normally circular in section, uniform in quality and free from defects.
Insulation: Conductor insulation shall be polythene insulating grade and 100% virgin material
as per ASTM (American Society for Testing and Materials) -D883.
Twining/Pairing: Two insulated conductors shall be twisted together with uniform lay to form a
pair. The length of the lay of any pair shall be different from the adjacent pairs. The lay of
various pairs shall be so chosen as to satisfy the capacitance unbalance.
Filling compound: (Petroleum Jelly): A cable core shall be fully filled with suitable water-
resistant compound like jelly, which is fully compatible with the polyethylene insulation, binders,
and tapes used in the cable.
Poly-Al Laminate moisture Barrier/Screen: Polythene coated aluminium tape shall be applied
longitudinally on the core with a minimum overlap of 6mm. Thickness of the aluminium tape
shall be 0.2mm + or –10% and that of polythene/ co-polymer coating on each side 0.05mm
nominal. Thickness of composite tape shall be 0.3mm + or - 15%.
Sheath: Cable shall be sheathed with polythene and containing a suitable anti oxidant system.
The material shall be virgin and meet required specification. The sheath shall be reasonably
circular and free from pin holes joints and other defects. The thickness depends on the size of
the cable.
Armour: The sheathed cable shall then be armoured with two applications of galvanized steel
tape conforming to IS: 3975 each applied helically in the same direction with gap in the first tape
of 25% + or – of the width of the tape, the second tape evenly covering the gap of the first tape.
Thickness of the galvanized steel tapes used in two applications including zinc coating on each
tape shall not be less than 0.5mm.
Jacket: The armoured cable shall be tightly jacketed with polythene conforming to the
requirements as specified for sheath.
In 5 pair,10 pair, 20 pair cable, colour code specified as below in para 3.4
Blue 1 6 11 16
Orange 2 7 12 17
Green 3 8 13 18
Brown 4 9 14 19
Grey 5 10 15 20
Pair 1st wire 2nd wire Pair 1st wire 2nd wire
no. Main colour Mate colour no. Main colour Mate colour
1 Blue White 11 Blue Black
2 Orange White 12 Orange Black
3 Green White 13 Green Black
4 Brown White 14 Brown Black
5 Grey White 15 Grey Black
6 Blue Red 16 Blue Yellow
7 Orange Red 17 Orange Yellow
8 Green Red 18 Green Yellow
9 Brown Red 19 Brown Yellow
10 Grey Red 20 Grey Yellow
Blue, Orange, Green, Brown & Grey are called the main colours. White, Red, Black and Yellow
are called mate colour. The five pairs make one unit. In this way there are four units in twenty
pair‟s cable. A cable of 50 pairs and 100 pairs, the twisted pairs shall be arranged in units of 10
pairs and 20 pairs respectively. 4 No of 50 pairs super unit shall be assembled to form a 200
pair cable.
Colour of binding tape: The different colours of the binding tape shall be used for identifying
each unit as given in Table 3.4
Unit number 1 2 3 4 5
Colour binder Blue Orange Green Brown Grey
3.5 Application: These cables are used for in transmission and distribution of networks
designed to be used underground, not inside the water. Cables having 0.5 mm conductor
diameter are used for short distance distribution networks, cables having 0.6 mm. conductor
diameter are used for long distance networks.
In Railways Polythene Sheathed Jelly Filled Cable with Ploy-Al moisture barrier is used for
providing telephone connections to the subscribers and local lead / last mile connectivity of
various circuits of both voice and data. These PIJF cables will be used in both RE and non RE
areas depending upon application.
Whereas in the RE area the usage of PIJF telephone cable may be limited to a maximum of 2
Km length due to induced voltage effects.
To enable proper identification of the cable, the following information is embossed, engraved or
printed on the polythene jacket in case of armoured cable, and on the sheath in case of un-
armoured cable. All the markings are white or yellow.
CHAPTER-4
In the system of electric traction adopted by the Indian Railways, the catenary wire is fed at
25,000 V, 50 c/s, and single phase. The rails are being employed as the return conductor. Such
an arrangement while resulting in several advantages in respect of power transmission and
traction engineering, the power feed being inherently unbalanced, produces certain undesirable
effects on communication circuits in the neighbourhood of the tracks, rendering them unsafe
and unworkable.
The mechanism of induction from the 25 KV AC traction system is due to electrostatic coupling
and electromagnetic coupling.
Electrostatic induction:- cable conductor insulated from earth and situated in this field will get
charged to certain potential with reference to the earth due to capacitance coupling. The
magnitude of this potential depends on the catenary current and distance between track and
conductor.
● With the catenaries maintained at 25,000 V an electric field is created in the vicinity of the
tracks.
● An electric conductor, such as a communication wire insulated from earth and situated
within this field will get „charged‟ to a certain potential with reference to earth due to
capacitance coupling.
● The magnitude of this potential depends on the voltage of the catenary and distance.
● The currents flowing in the catenary returns to the feeding point via the rails.
● The rails are not specifically insulated from the earth, therefore, provides an alternate path
for the currents.
● Some portion of this current penetrates deeply into the earth, to find a path in other rails,
cable sheaths, metal pipes and similar conductors parallel to the track.
● Near the feeder points the whole of the current must return to the secondary windings of
supply transformer.
● The current in the catenary is the source of an alternating magnetic field.
● This field cuts any conductors parallel to the track and induces e.m.f.‟s in them.
● The catenary system acts like a primary winding and each other parallel conductor acts like
the secondary winding of a transformer.
Therefore, from the above, it should be evident that the inductive interference constitutes a
hazard to personnel using or working on the lines as also to the connected equipment. The
induced voltages also seriously interfere with the signalling arrangements on the
telecommunication circuits causing them to be unworkable. Apart from the induction at the
fundamental frequency 50 c/s another source of trouble is on account of the harmonic
components of the catenary currents.
The reduction in induced voltages that is affected by the various conductors parallel to the
catenary system is expressed by saying that each such conductor has a screening factor. This
is defined as follows: -
Screening factor, K is the ratio of Voltage induced into the conductors of the cable core in the
presence of the metallic sheath of the cable to which the screening factor refers to voltage that
would be induced to the conductor of the cable core if the metallic sheath of the cable to which
the screening factor refers, is absent.
● It follows from this definition that the screening factor is normally less than unity.
● Generally this value is as low as possible.
● The screening effect of current is the consequence of the magnetic field produced by
current in that conductor (sheath).
● This conductor (sheath) can only provide a screening factor when it is carrying current. To
achieve, it must be a part of a complete circuit.
● By considering the screening effect of a cable sheath, clear distinction should be made
between "the voltage of the core to the sheath," and “the voltage of the core to earth".
● If the sheath is insulated from earth, identical voltages are induced in sheath and core, the
voltage between them is zero.
● At the same time the sheath does nothing to reduce the voltage between core and earth.
● To do this the sheath must carry a return current, the field of which opposes the field
induced by the current in the catenary.
● To carry such a current the both ends of the sheath have to be earthed.
● According to the above mentioned phenomenon, it is very clear that an induced voltage
developed due to the difference of primary & secondary magnetic fluxes in the cable
conductors as shown in figure shown below.
• When cable is in close proximity to strong electromagnetic fields, unwanted current and
voltage may be induced on it. If the power level is high enough, the electrical "noise" can
interfere with voice and data applications running on the cabling. In data communication,
excessive electromagnetic interference (EMI) hinders the ability of remote receivers to
successfully detect data packets. The end result is increased errors, network traffic due to
packet retransmissions, and network congestion. For analog voice communication, EMI can
create psophometric noise, which degrades transmission quality. This will be measured
with a psophometric meter.
2. Special protective measures (viz. provision of G.D tubes, fuses and earthing etc) are
required to be taken for telecommunication lines entering equipment rooms/OFC huts.
3. For the human safety considerations, the safe working voltages should be 60 V under
normal conditions and 150 V with special precautions and 430 V under fault conditions as
discussed earlier.
CHAPTER-5
“STAR QUAD” is four conductors balanced cable, two pairs form a tighter, more consistent pack
will resist even more noise.
The 4/6 quads Jelly filled cable of IRS-Specification No- 30/2005 version-1 (0.9mm dia
conductor) affected from 1/1/2006 has been introduced (latest is amendment no. 5 for this
specification). In addition to this, 1.4 mm dia copper conductor underground Railway jelly filled 6
or 4 quad cables for Signalling & Telecom installations have been introduced by RDSO under
specification no: RDSO/SPN/TC/72/07 for long (more than 25 Km) distance Block sections.
(Latest specification is with amendment 2)
5.2.2 Jelly
The cable core is fully filled with a water resistant compound of jelly which is fully compatible
with the polythene insulation of the conductors.
5.2.6 Screen
The cores with inner sheath are surrounded by a reasonably close fitted screen of aluminium in
the form of wires/strips.
The aluminium screen is wrapped with a single layer of woven tape impregnated with barium
chromate to protect the screen from oxidation.
Further protection for the screening is provided by extruded PVC circular sheath over screening.
The colour of this intermediate sheath is grey.
5.2.9 Armouring
The galvanised steel tape armouring is applied tightly over the intermediate sheath with two
layers. The direction of the lay of the armour is opposite to that of the outermost layer of
screening.
The outer sheath is applied over the armouring. The colour of this outer sheath shall be black.
Wire A and B shall form a pair and similarly Wire C and D shall form another pair. Conductors
are diagonally opposite forming one pair and the remaining two diagonally opposite conductors
forming the second pair of the quad. The quad shall be held together firmly by means of an
open helical whipping of nylon yarn or coloured tape of suitable material of appropriate
thickness.
1.4 mm dia
Sl.No. General Specifications 0.9 mm dia conductor
conductor
Characteristic impedance 470 Ohms (Unloaded) 310 Ohms (Unloaded)
1
at 800 Hz 1120 Ohms (Loaded)
2 Max. Loop Resistance 56 Ohms / Km 23.2 Ohms / Km
Insulation resistance of the >100 M Ohms / Km >100 M Ohms / Km
3 PET Quad measured with
100V DC. Megger
Transmission loss at 1 Kz 0.63dB/Km. (Unloaded) 0.3 dB/Km. (Unloaded)
4
0.25 dB/Km. (Loaded)
5 RDSO spec. IRS:TC: 30/2005 ver.2 RDSO/SPN/TC/72-07
Note: The value of attenuation shall not exceed 2 dB/km for any frequency in the frequency
range 300 Hz – 3400 Hz at 20C.
Where the section is non-RE area only 6 quad cables was used for Train operational
communication arrangements. However, additional Signalling sub-systems like BPAC, TAWS,
IB Phone to improve safety and reliability are gradually being integrated into the Signalling
systems. Railway board have considered this emerging need and decided that 6 quad cables
shall be provided along with OFC in all future works on sections where communication based
Signalling schemes are being planned.
IRISET 30 TC1 - Telecom Cables (Copper)
Telecom Quad Cables
5.8 Guidelines for use of Optical Fiber System and 6 quad cable on various routes in
Indian Railways.
(b) Replacement of existing overhead /RE quad cable for control communication.
(i) Existing RE Telecom Cable, whenever it is due for replacement on age cum condition
basis, it should be replaced by Optical Fiber System with 6 quad cable
(ii) Existing Overhead alignment on A, B, C & D-special should be replaced with Optical
Fiber System with 6 quad cable.
Tentative Quad allocation of a 6 Quad Cable, when laid along with OFC or without OFC is as
under:
a) 6 quad cable with OFC b) 6 quad cable without OFC
Quad No Name of the circuit Quad No Name of the circuit
1 Block Circuit 1 Block Circuit
2 Spare 2 Section Control
3 Emergency Control 3 Emergency Control
4/1 LC gate telephone 4/1 BPAC
4/2 BPAC 4/2 LC gate telephone
5 BPAC 5 BPAC
6 TAWS 6 TAWS
Quad allocation of 6 quad cables
**Quad allocation will be done as per the section requirement duly following the latest Rly
Board letters if any and local circulars in the zone.
5.9 Difference between PIJF underground Paired and Quad Cables:
CHAPTER-6
After allocation of work, foot inspection has to be carried out to arrive at the approximate and
exact route plan of the alignment of cable route. While carrying out the survey, Railway
boundaries, availability of other Signal, Electrical cables, water pipes etc. are shall be identified
and certified by the P. Way, Signal & Electrical authorities of Railways. In case of obstruction or
availability of other cables, alternative routes have to be selected. On approval of the same, the
detailed survey of the section has to be started.
6.3.2 Soil strata report: After getting the clearance, carry out the soil strata analysis. To
identify soil condition, at every 500mtrs the pits have to be excavated and soil condition has to
be analysed. The analysis readings are to be recorded and incorporated in the report as well as
in the drawings.
6.3.3 Submission of cable route plan: Based on the above survey the cable route plan
should be prepared.
13. With engineering drawing already in hand, verify pathways/pedestrian crossing and other
lateral clearances.
14. Scale out the special work required if any and the manner of the cable route in approach of
the existing bridge‟s locations.
15. Identify, if any special lengths of cable is required to avoid joints on bridges/culverts etc.,
16. For the straight runs as far as possible a separation of 10 Meter should be kept from the
nearest track.
17. No OFC or Quad Cables shall be laid close to the existing track. It shall be laid
close to the Railway boundary on one side of the Railway track to the extent
possible to avoid any interference with the future works.
18. As a rule, a minimum distance of 5.75 M should be maintained between the OHE masts
and the cable. In Yards etc., where observance of this rule may be difficult, a minimum
distance of 3 Meter should be maintained. In exceptional cases where the cable trench
depth is less than 0.5 Meter the lateral distance may be reduced to 1Meter. In such
trenches, which are in close proximity to OHE masts, the cable should be laid in
PVC/RCC Pipe.
19. Location of traction substations / feeding posts and other OHE switching posts.
The Quad cable length is to be worked out on the following basis to arrive at the location of the
straight joints.
6.8 A typical cable requirement calculation for a block section having length of 10 km
with 3 LC gates, one major bridge and two minor bridges/culverts
7 Cable loop at joints (joints in the section are 10):10x 20 mtrs 00.20
a. The cable drums shall be stored on a well drained, hard surface, so that the drums do not
sink in the ground causing rot and damage to the cable drums. Paved surface is preferred,
particularly for long term storage.
b. The drums shall always be stored on their flanges, and not on their flat sides.
c. Both ends of the cables should be properly sealed to prevent ingress/ absorption of
moisture by the insulation during storage.
d. Protection from rain and sun is preferable for long term storage for all types of cables.
There should also be ventilation between cable drums.
e. Damaged battens of drums etc. should be replaced as may be necessary
a. Metalled, macadamised, concrete and stone paved roads shall also be cut to a depth of 1
metre. The cable shall be laid through RCC or DWC or GI pipes as applicable as per
Drawing No. RDSO/TCDO/COP/20. The road surface shall be restored to original.
b. When crossing Roadways, it is necessary to lay the cable in such a manner as to avoid the
necessity of handling the cable sharply and minimize the excavation of road surface as far
as possible. Where cable is laid on the surface, trunking, trunking aligning should be curved
down to the pipes and proper brick or concrete joint should be made between trunking and
pipe.
c. The crossing of main roads often involves difficulties especially if traffic is heavy.
Precautions to avoid accidents to workmen, pedestrians and the vehicles should be taken.
On minor roads, which can be temporarily closed to traffic, it is possible to open up and
cross the entire width of the road. Pipes should be installed quickly in the cutting, which is
then filled in thereby reducing to a minimum time for which the road is closed.
d. Some roadways, which are broad, may be opened for half the width first allowing the other
half for use by Road traffic. Pipes are laid in the opened half. After the backfilling the
opened portion, the other half is opened and the first half will be used by the road traffic.
After the pipes have been laid in the second half, they must be linked with those laid in the
first half. DWC pipes shall be used for road crossings. In all cases, pipes shall be laid at a
depth of one meter below the formation level or lower as may be required.
e. Wherever a cable is laid across an important road particularly one with a special surface it
is good investment to provide for future expansion. The following methods may be adopted.
f. The size of the pipe shall be so chosen that other cables may be drawn subsequently. Two
lengths of G.I. wire 10 SWG shall be used as lead wire. Two such lengths of G.I. wire shall
be laid through the pipe. One wire shall be used for leading in the cable and the other shall
be kept with suitable overlay to enable cable pulled out at later stages if required. At road
crossings, RCC or DWC pipes of specified dia shall be used.
6.12.4 Laying of Cable in Solid & Rocky soils and Residential & Marshy areas
a. If the terrain is rocky normal dimensions of the trench cannot be ensured. In such cases
trenching to be done as per Railtel diagrams enclosed.
b. In marshy areas, where it is not possible to divert the cable route, the cable should be
suitably laid and protected as per the decision of the Railway
c. Representative depending on site condition, like laying cables in RCC pipes of suitable dia
concreted at every Meter.
d. The cable will have to be led inside any masonry buildings such as ASM‟s Room at a depth
of 0.75 m by cutting the Masonry structure of the wall. After the cable has been led inside
the masonry wall, the floor inside shall be duly repaired and plastered.
e. Laying of Cable near Power cable: When the contractor comes across any other cable
already laid, he shall first report the fact to the engineer. Should the cable be identified by
the Engineer as a Power cable (LT / HT), the trench shall be dug as far away from the route
of the power cable as practicable.
f. Crossing of Telecommunication cable with another cable shall be avoided wherever
possible. Where, however, this is not possible the telecommunication cable shall be laid in
RCC pipe. The length of the RCC Pipe to be provided on either side of the crossing shall be
at least one meter.
g. The cable shall be laid through GI pipes at the location marked on the tapping and route
plan and as required by SSE/JE.
h. Laying the cable through pipes, galvanized steel wires of a cross section not less than 10
SWG shall be used as a lead wire. Two such lengths of wires shall be laid through the
pipes so that after the cable is threaded through the pipe one led wire is permanently left in
the pipe with a suitable overlay at two ends to enable the cable to be pulled out at a later
stage if required to do so.
i. On arch bridges and culvert bridges, the cables will be threaded through the GI pipes etc.
j. Damages to cables is likely if care is not taken in laying cables where the bed changes from
solid support such as the foundation pipe or bridge to soft support such as soft soil. The
cable must not press against the edge of the solid support.
The soft soil near the edge must be tamped and the cable raised slightly.
k. Special Soil Condition: Cable should not be run through high acidic or alkaline soil or
through sewage. If this is unavoidable, special measures should be taken against
Corrosion.
l. Laying of 6 quad Cable near Feeding Posts/TSS: In the vicinity of feeding posts as far as
possible the cable shall laid be on the side of the track opposite to the feeding post. Further
the cable shall be at least one meter away from any metallic part of the OHE and other
equipments at the substation, which is fixed on the ground and at least one meter away
from substation earthing. In addition, the cable shall be laid in RCC pipes for a length of 300
meters on either side of the feeding point.
RCC cable markers shall normally be provided at a distance of every 50 meters on the cable
route, at derivations and also to be provided at all types of cable joints. They should be of
standard RCC with letters “IR / 6 QUAD CABLE “and logo engraved and painted. They shall be
painted with Green when placed at joint locations and painted with Red/ Orange for normal
indication.
Joint Inspection shall be carried out by SSE/JEs of Open Line and SSE/JEs of Concerned
Organisation (Ex: Projects/Con.) after completion of cable laying works.
Power and telecom cables should have the shortest length of parallelism. When high
voltage power cable 11 KV and above, has a parallelism exceeding 0.8 Km, appropriate
safety measures have to be taken.
Whenever laying of new telecom cables across or parallel to the existing 11KV and above
power crossing, PTTC (Power Telecom Co-ordination Committee) approval is mandatory to
protect Railway Telecom network from induced voltage effects from power lines and vice versa.
As per the PTTC guideline the protection devices such as surge protection devices shall be
provided.
As per PTTC, it is advisable to take the telecom cable with maximum horizontal clearance as far
as practicable but not less than 0.6 meters, so that the intensity of inductive interference can be
minimized. Absence of sheath continuity and armour continuity in Telecom cable and it‟s
improper earthing in the vicinity of power cable will result in AC induction and consequent
impairment of the telecom circuits. When the power parallelism is more than 0.8 kms the cable
route should be referred to PTCC for recommendation of protection measures. In case of
crossings, care should be taken to see that telecom cable crosses at right angles and at a
vertical clearance preferably of 0.6 meters but not less than 0.3 meters at any point. When the
specified clearances cannot be maintained, it is preferable to lay the telecom cable through
cement concrete pipes and seal the mouths at both ends.
In the vicinity of the switching stations, the cable shall be laid at least one meter away from any
metallic body of the station which is fixed in the ground and at least 5 meters away from the
station earthing. The distance of 5 meters can be reduced to one meter provided the cables are
laid in concrete pipes or ducts.
CHAPTER-7
Underground Telecommunication cables are manufactured in the lengths of 1000 Metres or 500
Metres. To increase the length of the communication media to the required length, the available
cable lengths are to be jointed compulsorily. Therefore, cable jointing is unavoidable to meet the
need. But cable jointing is a highly skilled job and should be done with all precautions. Any
defect in the joint may lead to the total failure of all the circuits. Joints are very vulnerable points
in a cable network, so efforts should be made to do the perfect joint strictly as per the
specifications.
The 6 Quad Telecommunication cable is received in lengths of 1000 metres. So, there will be a
cable joint at regular intervals. These joints are systematically arranged as
(i) Straight / Normal joints
(ii) Derivation Joints
(iii) Straight cum Derivation joints
i) Normal joints are straight through joints connecting two ends of a cable.
ii) Derivation Joints: These are transformer joints for tapping various railway control circuits,
to the various utilisation points. According to the requirements of the tapping points the
requisite number of transformers are kept inside of a joint. The derivation side of the
transformer windings are connected to the derivation cable and the main side of the
transformer windings are connected to the main cable.
iii) Straight cum Derivation joints: A normal joint for joining two ends of cable associated
with transformers for a derivation cable. In general, this type of joint will be carried out for
EC sockets, placed at regular intervals of 1 Km.
The type of transformer used will depend upon the type of circuit. The following table shows the
transformers of different ratios.
The cable drum length, of 10, 20, 50 and 100 pairs, is generally of 500/1000 mtrs. When two
cable lengths are joined together with the Thermo shrink filled closure type jointing kit, the
following sizes of jointing kits are selected. The jointing procedure of polythene insulated paired
cables is the same as the polythene insulated quad cables.
700 +/ –15
TSF-2 50P 50P 305/42 350
42/15
700+/-15
TSF-3 100P 100P 305/62 350
62/22
Thermo shrink joint closure for various types of joints in 6-quad Telecom cables is used as per
RDSO specification no. IRS.TC.77-2012 (rev.3). For EC sockets, L.C. gates, Pump Houses etc.,
the straight through joints with the 2T (for 1 quad) transformer assembly as per RDSO spec.
IRS TC-76/2021 (effective from 29-04-2021) shall be provided for deriving the circuits using 10
pair PIJF paired cable (as derivation cable).
Jointing Kit
Thermo Shrink Jointing kits, specification no: IRS-TC: 77/2012 (rev.3), for underground 4/6
Quad Jelly Filled Cables of conductor dia. 0.9 mm and 1.4 mm are in use. This Jointing Kit is
meant for straight through / normal, Y/derivation, transformer Joints.
a. For jointing of cables pit of 1Mx1Mx1.5M shall be made. The pit surface is to be levelled by
ramming the earth. In case of loose soil or mud, bricks or ballast may be used if necessary.
A tent may be placed over the pit to protect adverse weather/ dust.
b. Bend the two cables ends slowly into an „S‟ shape taking care that the cables are not
strained excessively and minimum overlap of 350 mm is available.
c. Prepare the cable ends as per the detailed installation instructions for making heat
shrinkable joints for 6 quad cables.
d. Preliminary checks may be carried out using Multimeter for continuity of conductors and
breaks/crosses etc., if any. The insulation is measured between all conductors bunched
together and screen/armour by 500 V megger. The equivalent average insulation
resistance/conductance/Km is obtained by multiplying the megger reading with the number
of conductors and the length of the cable in Kilometres.
e. Slip the quad rings on a PE insulated quad of the cable end. Similarly slip another quad ring
on the corresponding PE insulated quad of other cable ends. Select a conductor and slip a
PE sleeve over it. Take this corresponding conductor of the corresponding PE quad of the
other cable end. Peel off the PE insulation from these conductors for a length of 50mm.
f. Bring the two conductors together perpendicular to the cable. Twist the two conductors by
rotating, giving approximately 10 turns for a length of 25mm. Cut off the surplus wire. Solder
half the length of twisted conductors using solder resin core. Solder bit flat and blowlamp.
Fold the twisted conductors along the main cable conductors and allow it to cool. Draw a
PE sleeve over twisted joint in such a way that former projects equally on the two sides of
the latter and equally covers the polythene insulation of the two conductors. It should be
ensured that the PVC sleeve fits properly over the twisted joint and does not move easily
over it.
g. For tapping joint, select the quad from which the circuit is to be tapped. Cut the quad, slip
numbered group ring over both ends as also on the lead wire bunch of required
transformers. Select a conductor in one quad and slip a P.E. sleeve over it and its other
end. Select a conductor, a short lead wire and transformer lead wire and make twisted joint.
With the other end of the short lead and other cut end of same conductor, make another
twisted joint.
h. The conductors of the remaining PE quads should also be joined accordingly.
i. Complete the joint as per the detailed installation instructions given in the jointing kit for
making heat shrinkable joints for 6- Quad telecom Cable
Cable Preparation
A. Lay cables with overlap of 505mm for Straight through joint or Transformer joint
(Derivation).
B. Expose various sheaths/armour as per details given below:
- Outer Sheath : 505 mm
- GI double tape armour : 20 mm
- Intermediate sheath : 160 mm
- Aluminium Wine Screen : 50 mm
- Inner sheath + poly al : 275 mm
(Splice length)
C. Cut section of 40D/4QJ/6QJ cable for Thermoshrink joint.
1. Mark M1 on both the cables at a distance of 505mm from the end. Cut and remove the
outermost sheath up to M1.
3. Mark M2 at a distance of 180 mm from M1, towards the cable end, on the middle sheath.
Cut and remove the middle sheath up to M2.
4. Mark 50 mm from M2 towards the cable end, on the Aluminium shield wires. Cut and
remove Aluminium shield wires up to this mark.
5. Slide the split Al. ring over the A1. Shield wires and bend back the wires over the ring.
Repeat steps 2 to 5 on the other cable also.
6. Lay cables with an overlap equal to exposed inner sheath (275mm). This will be the splice
length.
7. Mark 275mm on the inner sheath from the cable end. Cut and remove inner sheath up to
this mark. In case of Jelly filled cable, clean the jelly using the cleaning liquid. This will
expose 25mm of inner sheath of the cable. By making two 10mm wide parallel cuts on the
inner sheath, lift this portion by 45º (inner sheath together with polyAl sheath) for crimping
sheath connector assembly.
the PVC sleeves over the soldered conductors. The conductor joints should be staggered to
ensure even splice bundle.
(i) In case of Transformer Joints, the lead wires of transformer and derivation cable also
need to be twisted along with the quad cable conductors and soldered.
(ii) For derivation joints, the wires of derivation cable should be twisted along with the
required wires of quad cables.
9. Slip the heat shrink tube centrally over the tinned copper braid and shrink the tube on the
braid. Ends will be exposed. Fix the bare end of copper braid to shield wire and apply one
turn of spring roll, bend the copper braid end towards inner sheath and complete full turns
of spring roll.
10. Affix Transparent PE Sheet on to the sealant tape and secure the ends of the pouch
after filling the splice filling compound. Filling Compound should be used in all quad
cables including dry core cables.
11. Wrap the PVC tape over the splice bundle with a 50% overlap. Start from one end and
proceed to the other.
12. Remove the insulation of the armour continuity wire to the required length and wrap three
rounds of the bare wire over the armour. Solder the wire to the armour and cover the
soldered area with sealant tape followed by PVC tape. The excess length of the wire can
be secured to the middle of the splice bundle, with PVC tape.
13. Install the Aluminium Cannister centrally over the splice bundle. Apply one round of PVC
tape in the center to hold the half-shells. Cover the parting lines with PVC tape. Wrap two
layers of PVC tape tightly, with 50% overlap, on the canister fingers to form the transition.
Start from the crown end and proceed to the finger end.
14. Place the reinforced H.S. Sleeve centrally on the splice and mark the sleeve ends on the
cable. The area between this mark and the end of the canister is the Bonding Surface.
Clean the bonding surface of grease and dirt with the cleaning tissue and abrade the
surface circumferentially with emery strip. DO NOT TOUCH THE BONDING SURFACE
AFTER CLEANING OR ABRADING.
15. Wrap the Adhesive Aluminium Foil around the Outer Cable Sheath by keeping 25mm of
foil inside the bonding surface.
16. Flame brush the bonding surface TILL IT BECOMES GLOSSY. DO NOT OVERHEAT AS
IT COULD DAMAGE THE CABLE SHEATH.
17. Remove the protective film from the Heat shrink Sleeve.
18. Wrap around the reinforced H.S. Sleeve and position the under clip on the rails at the
center. Slide the S.S. Channels over the rails in such a way that they meet at the center of
the sleeve and are held by the under clip. The S.S. Channel and the canister parting lines
should not come over one another.
19. Insert branch off clip between the cables on to the thermo shrink sleeve. The thermo shrink
sleeve shall be evenly distributed over all the cables. Use cable tie provided in the kit for
securing derivation cable and main cable together.
20. Preheat the channel for about 30 seconds to a minute and then start shrinking the sleeve.
Begin from the center and proceed circumferentially to either end. Tap the channel portion
gently at the transition points adjacent to the canister crown. The shrinking is complete
when the Thermo chromic paint changes colour and white lines appear below the
channels.
21. Concentrate the flame on the metal part of the BOC till the adhesive on the clip melts and
oozes out. Post heat the channels with a moving flame for 15 seconds. Press the channel
with a blunt tool to follow the form of the canister at the transition area and post heat the
transition area.
22. After shrinking, allow the joint to cool for at least 30 minutes, before handling.
The material (Kit Contents) for Universal Jointing Kit to be used for straight through joint, Y-
(Derivation) joint, Transformer Joint.
Length–450mm Length–470mm
Thickness 0.7mm & Thickness 0.7mm &
Stainless Steel
2 Under clip (Length = Under clip Length = 1
Channels x 2
35mm) & Thickness 1 35mm) & Thickness
0.2mm 0.2mm
Aluminium Canister Size = 75mm x Size = 92mm x
3 1 1
Finger Coated length 507mm length 507mm
Width (25mm ±1mm) x Width (25mm±1mm) x
Adhesive P.V.C. length (10 meter/roll length (10meter/roll
4 2 2
Tape Minimum) x Thickness Minimum) x Thickness
(0.1 to 0.13mm) (0.1 to 0.13mm)
Length(400mm±4mm) x Length(400mm±4mm) x
Adhesive width (100mm±2mm) x width (100mm±2mm) x
5 1 1
Aluminium Foil thickness (0.06 thickness (0.06
±0.01mm) ±0.01mm)
Cleaning Tissue
Tissue paper size- Tissue paper size-Length
( Soaked with 5ml
6 Length (190mm min.) 3 (190mm min.) Width- 3
min Iso Propyl
Width- (140mm min.) (140mm min.)
Alcohol )
Length (600mm±5mm) x Length (600mm± 5mm) x
7 Emery Strip width (25mm± 1mm) x 2 width (25mm± 1mm) x 2
60 mesh) 60 mesh)
length (500mm±5mm) x
length (500mm±5mm) x
width (7mm±1mm) with
Tinned Copper width (7mm±1mm) with
8 heat shrink tubing size 1 1
braid heat shrink tubing size
12/4mm (length
12/4mm (length 450mm).
450mm).
Note: - Supply of either item at SN.12 or items under SN 25, 26 and 27 shall be specific to
purchaser‟s requirement as per clause 12 of the specification. Item No. 25, 26 and 27 shall only
be supplied if IDC type discrete wire connectors are required by purchaser and in that case item
number 12 shall not be supplied.
Certain important points are highlighted in Annexure -1 which if taken care shall ensure correct
joint in the field.
The 6 Quad cable terminated in 20 pair cast iron termination box is 20 pair CTB. The CT box
after termination of quads shall be sealed by pouring paraffin wax. These 20 pair CTB will be
used at ASM rooms, LC gate lodges, IBS huts etc.
IRISET 54 TC1 - Telecom Cables (Copper)
Jointing of Underground Telecom Cables
The 6 quad cables will have to be led inside the masonry building in the ASM‟s room / SSP/IB
Hut at a depth of 0.75 meter by cutting the masonry structure of the wall. After the cable has
been lead inside the masonry wall, the floor inside shall be duly repaired and plastered. The 6
Quad cables shall be taken through GI pipe and dressed upon wood plank mounted at one-
meter height from the floor level and terminal box duly fixed on the wall with suitable bolts and
nuts.
The Six quad cables shall be terminated in the following order in a CTB
20 pair CTB
The case front cover and back plate shall be made from alloy aluminium casting. Brass used for
terminals. The terminals block shall form one face of the C.T. Box. It shall have requisite pairs of
brass terminals so that the connections of the underground cable can be soldered on the inner
side of the block and external wires can be connected with nuts on the outer side. For outdoor
cable termination the Cast Iron C.T. Box or Alloy aluminium casting C.T. Box is used for R.E or
non-R. E area.
Termination Box with Krone / Wago type modules are in use for terminating PIJF telephone
cables. Cable terminal boxes are supplied in different variants viz., 20 pairs, 50 pairs and 100
pairs. They are used for terminating the switchboard cables or jelly filled cables entering the
CTB.
KRONE LSA-PLUS® Connection Module, for 10 pairs with parallel test facility or provision for
over voltage protection using 10 pair protection magazine. Conductor diameters of connectable
wires are 0.40 to 0.63 mm
a b a b a b a b - - - - a1
1 2 3 4
1 1 2 2 3 3 4 4 a10 0
a b a b a b a b - - - -
1 2 3 4 a1
1 1 2 2 3 3 4 4 a10
At present the pairs of polythene-insulated jelly filled cables are terminated in Krone. Generally
one block of Krone can be used for termination of 10 pairs of cable. Such type of crone can be
used in CTB / Location Box for termination of primary, secondary or distribution cable. Each
block of Krone is assembled in a frame, which may hold 10 such blocks (100 pairs termination).
A 0.2mm square conductor (left) and nominal diameter 16mm square (right) in one 16mm
square terminal block. CAGE CLAMPR and CAGE CLAMPRS connections clamp Copper
conductors from 0.08mm square to 35mm square (95mm square), or from 0.25mm square to
25mm square, respectively. Splice protection is not required–but can be used. The conductor is
pressed against the current bar in the predefined contact area, without damaging it. The
clamping force automatically adjusts to the wire size. Possible conductor deformation is
balanced and an accidental loosening is safely prevented.
IRISET 56 TC1 - Telecom Cables (Copper)
Testing of Cables
CHAPTER-8
TESTING OF CABLES
The instrument used is Cross Talk measuring sets. The cross talk is of two types:
1. Near end crosstalk (NEXT) 2. Far end crosstalk (FEXT)
Meter Characteristic
DISTURBING PAIR
Output Impedance
N Far
Near end
end of
of the the
pairs Pairs
Meter Characteristic
DISTURBED PAIR
Input Impedance
Characteristic
Meter
DISTURBING PAIR Impedance
Output
Characteristic
DISTURBED Meter
Impedance
PAIR Input
S. No Description Value
1 Loop Resistance in Ω
Cable conductor of dia 0.51 mm 184 Ω / L.Km
Cable conductor of dia 0.63 mm 128 Ω / L.Km
Cable conductor of dia 0.9 mm 56 Ω / L.Km
• Using a Quad cable without jelly – Water enters into the joint along with cable core when
there is any cable damage (crowbar hit) in between two joints. Use the PIJF 6 quad cable
as per RDSO spec no. IRS: TC30-2005.
• Exposing of cables on Bridges/ Culverts/Rocky areas- Regular Cable route inspection shall
be done by section Technician (TCM)/JE and strengthening of cable route shall be carried
out as per Railway Board Telecom Action plan.
• Cable cuts and thefts- Ensure the cable laid within Railway boundary, avoid the exposing of
cable implement the Railway Board JPO for Earth digging works by Engg. Dept., update the
cable route diagrams and upload to the web page for easy access to concerned dept.
• Codal life of Cable- Plan for replacement of cable within its codal life (20 / 25 years).
Foot inspect the entire cable path in the section. If there is any sign indicating any recent
digging the same can be suspected to contain the fault. Excavate the trench and expose the
cable. Extend the trench for about 10 ft. length or up to the length covered by the recent digging.
Expose the cable. Inspect for any damage on the cable. If there is any damage, operate the
cable.
a) Find out from the cable diagram the joint nearest to the point of localisation. Locate it (Joint
J1 in figure). Expose the joint. Inspect for any damage. If the joint is damaged, verify if this
was the fault. If so, repair and close the case.
b) If the fault is not found in this joint, expose the joint on the other side of point of localisation.
Call it joint J2 and repeat the above operation of testing.
Spot localizations
1. Test from joint J1 to determine if the fault is towards the point of localisation or on the other
side i.e., towards joint J3.
All the types of faults in the cable as mentioned below can be identified
1. Break/Open Circuit and Short Circuit fault.
2. Low Insulation faults.
3. Induced Voltage
For accurate and speedy fault localisation, the techniques using pulse reflection method is
found to be quite useful. It is essentially a high frequency AC test signal generator and useful for
localizing those faults that do not upset any DC condition but affect the propagation of the A.C.
high frequency energy. The nature of faults that include open circuits, open sheaths, high
resistance joints, and water logged cable section etc.
Testing Procedure
There is no need for a good pair or limb for conducting the tests of break, open, insulation and
induced voltage. However, if a good pair is required as a reference pair to identify low insulation
faults. It is advisable that the cable pair to be tested is free from voltage. The reflection of pulse
will depend on the impedance irregularity of the pair under test.
In the case of open or break fault the reflection pulse will be indicated by upward kink or positive
reflection. For short or low resistance faults the reflection pulse will be indicated by downward
kink or negative reflection. Whatever energy reaches the dead short is totally reflected back
because the dead short appears as a mere impedance irregularity and we can see a big
reflected pulse corresponding to the dead short. Poorer the insulation at the fault greater is the
magnitude of the impedance irregularity and bigger the reflected pulse. The presence of
moisture in a particular section alters transmission characteristics of that section. It is essential
to connect the instrument to one end of the circuit under test and shift it to the other end and
carryout the same test so as to find out the length of overlap.
The accuracy of distance to fault depends upon the accuracy of V/2 values.
D = V/2 X T
Where T is the time taken for the reflected pulse energy to arrive back at the instrument, V is the
velocity of propagation in a circuit and D is the distance to fault.
For Knowing V/2 value, connect the cable pair to the instrument the reflected pulse should be
aligned accurately with the incident pulse and the switch should be set such that the display on
the digital readout corresponds to the V/2 value for that pair.
It should be remembered that alignment of incident and reflected pulses should be done with
reference to the commencement of their leading edges (align the foot of the reflected pulse with
the foot of incident pulse).
1. Conductor break fault (one limb or both): A positive reflection will be shown at the point of
break.
2. Contact Fault (Limb to Limb). A negative reflection will be shown at the point of contact.
3. Earth Fault (Limb to Sheath). It is a very low resistance fault. When pulse is applied
between the conductor (limb) and sheath a negative reflection similar in the above case is
observed.
CHAPTER-9
1. Cable burnt at joint due to lightning and all circuits failed- armour connectivity in joint was
given up.
2. Cable is noisy while train passing in the section and BPAC circuit is frequently failing-
improper earthing of cable armour.
3. Abnormal delay (48 hrs) in restoring of 6 quad cable fault: Cable was not traceable
because cable was laid outside Railway Boundary one year back and the colony people
constructed culvert on the cable route at about 10mts. The drainage water was overflowing
and spread over the area and got covered with thick bushes. Staff were not able to walk on
the cable route with cable route locator and missed the fault. Cable was found damaged in
the culvert.
Integrated Cable path diagram showing all S&T Cable path positions shall be prepared
and made available with all S&T staff to protect the underground S&T Cables.
General Instructions
Do's
Quad cable testing of Block, BPAC and IB applications should be done with
1.
disconnection and jointly with ESM/ JE-Sig.
To avoid train detention, ensure proper planning before work and test the circuit
2.
after the work is completed in consultation with signal staff.
3. Before testing the cable, ensure suitable staff availability at both ends
4. Before testing, check your meters for correct calibration.
5. Isolate the working circuit from the end point and test the cable end to end.
Before insulation testing check earth resistance at test point. Test results will be
6.
misleading in absence of proper earth.
7. Ensure the watering of the earth pit on every visit.
After testing and reconnecting the cable, ensure functioning of all circuits with SMR
8.
/ Test room.
Don’ts
Don‟t disconnect Block, BPAC and IB circuits without issuing disconnection memo
1
for testing of Quad cable
Inspections
Quad 1
Quad 2
Quad 3
Quad 4 / 1
Quad 4 / 2
Quad 5
Quad 6 / 1
Quad 6 / 2
INDEX SHEET
SSE / JE Section: ________________________________________
Page Sl. Page
Sl. No. Name of the Block Section Name of the Block Section
No. No. No.
1 21
2 22
3 23
4 24
5 25
6 26
7 27
8 28
9 29
10 30
11 31
12 32
13 33
14 34
15 35
16 36
17 37
18 38
19 39
20 40
Pair Pair
Pair-1 Pair-2 Pair-1 Pair-2 Pair-2 Pair-1 Pair-2 Pair-2 Pair-1 Pair-2
-1 -1
6
1) Earth Resistance
at cable Armour
( To ensure integrity of
________ Ω. ________ Ω. ________ Ω.
Earth)
2) Armour continuity
with respect to Earth
( To ensure Armour
________ Ω. ________ Ω. ________ Ω.
continuity)
Remarks:
Signature
Name
Designation
Pai Pair
Pair-1 Pair-2 Pair-1 Pair-2 Pair-2 Pair-1 Pair-2 Pair-2 Pair-1 Pair-2
r-1 -1
6
1) Earth Resistance
at cable Armour
( To ensure integrity of
________ Ω. ________ Ω. ________ Ω.
Earth)
2) Armour continuity
with respect to Earth
( To ensure Armour
________ Ω. ________ Ω. ________ Ω.
continuity)
Remarks:
Signature
Name
Designation
Pai Pair
Pair-1 Pair-2 Pair-1 Pair-2 Pair-2 Pair-1 Pair-2 Pair-2 Pair-1 Pair-2
r-1 -1
6
1) Earth Resistance
at cable Armour
( To ensure integrity of
________ Ω. ________ Ω. ________ Ω.
Earth)
2) Armour continuity
with respect to Earth
( To ensure Armour
________ Ω. ________ Ω. ________ Ω.
continuity)
Remarks:
Signature
Name
Designation
Transmission
Transmission Transmission
Loss @
Quad Loss @ 800HZ Conduction Loss @ 800HZ
Conduction 800HZ (0.28 Conduction
No (0.28 db/KM for Test (0.28 db/KM
Test db/KM for Test
loaded (56 Ω for loaded
(56 Ω /KM) loaded (56 Ω /KM)
0.8db/Km /KM) 0.8db/Km
0.8db/Km
unloaded) unloaded)
unloaded)
Pai
Pair-1 Pair-2 Pair-1 Pair-2 Pair-2 Pair-1 Pair-2 Pair-1 Pair-2 Pair-1 Pair-2
r-1
6
1) Earth Resistance
at cable Armour
( To ensure integrity of
________ Ω. ________ Ω. ________ Ω.
Earth)
2) Armour continuity
with respect to Earth
( To ensure Armour
________ Ω. ________ Ω. ________ Ω.
continuity)
Remarks:
Signature
Name
Designation
Remarks:
Signature
Name
Designation
CHAPTER -10
10.4.1 Searching
1. Mode Switch to the appropriate mode is to be selected first
2. Holding the On/Off trigger. The Locator should emit the audible battery test
tone and the digital display should come on. Battery level indicator to be checked
for confirming the batteries are usable.
3. Sensitivity Control to be rotated clockwise for the required maximum setting
and it will be indicated by the arrow on the control.
4. Carrying out the search using a grid pattern. Walking slowly and keeping the
Locator upright at all times and stationary to get the better result.
5. On approaching the area in which there is a signal, the Locator will respond
and shows a visual response on the display. Walk to be continued till the visual
responses disappear in the display to pinpoint the cable.
10.4.2 Pinpointing
After getting a signal the next step is to pinpoint the source. The closer the
Locator is to the signal source, the stronger the response. This can be done by:
1. By keeping the Locator vertical, to be moved through the area of the
signal response for any changes in the signal. If the visual response is observed
moving out of the scale, then walking to be stopped and the sensitivity of the
Locator to be reduced slightly before continuing.
2. The width of the signal response will shrink as the sensitivity is
reduced. Once it is reduced enough then a clear peak response will be seen on
the display, as the Locator traverses the service. The Locator is to be positioned
directly above the buried service. When the display is at its highest (peak)
reading, then the Locator to be rotated over the peak reading until the visual
response falls to a minimum. The Locator is now roughly IN LINE with the
direction of the buried service (cable). Now the position can be marked.
10.4.3 Tracing
After pinpointing a service (cable/ pipe) it will be possible to trace its route.
1. The direction of the signal holding the Locator at right angles to the line of the
signal is to be followed carefully. It is necessary to constantly „slice‟ the Locator
from side to side in order to be sure of still being over the peak signal response.
2. The position of the signal at regular intervals is to be marked. If more marks
are recorded, the precise direction of the service will become more apparent.
4. Earth Stake to be placed in the ground. The ideal position for the Earth Stake
is at right angles to the assumed line of the cable.
5. Black Earth Lead will be connected to the Earth Stake. If the earth point is too
far away from the pipe access point for the black Earth Lead to reach then 10
metre yellow Auxiliary Earth Lead can be used
6. As the Earth Lead is connected to the Earth Stake, the audible signal from
the Signal Generator should change in pitch. Lower the pitch, the better the
signal. If there is no change in the pitch, it indicates there may be some dirt,
rust or paint on the pipe.
7. Output Power Level to be adjusted to suit the system.
13. POWER ON/OFF Switch turns power on when depressed. Release or alternate
action of switch turns power off.
14. RANGE SELECTOR 50m, 100m & 300m position provides a short duration
transmitted pulse for ranges 50m, 100m & 300m. The 1KM, 3KM, 10KM
positions provides progressively wide pulses required for 0 - 1 KM, 0 - 3 KM, 0 -
10 KM ranges respectively
15. ALTERNATE TRACE SELECTOR when pressed, the CRT shows the complete
trace of the cable under test and allows the reflection to be shifted towards the
transmitted pulse as controlled by Trace Shift Control 18. When not pressed,
only one trace is displayed.
16. SHIFT / MEASURE SELECTOR In the SET position, the Trace Shift Control 18
can be used to pinpoint a reflection. When READ is pressed, it allows digital
readout of the distance to the selected pulse reflection.
17. SWITHC L1-L1/L2 in pressed position it will be used to compare two traces of the
cable pairs
18. ALIGNMENT CONTROL is used to pinpoint a reflection
19. EXTPWR is used to connect external 12 V- 15 V DC power supply
20. GROUND is used to connect the earth to L1 and L2 jacks
21. Chg. ON LED used to indicate the unit is in charging condition
22. SELFTEST is used to self-test the fault locator
23. HVON LED Red LED indication shows when HV is available on the cable lead
10.9.5.3 Sheath
A short or low resistance between one or both conductors shows a negative reflection,
which is smaller as resistances increases. A small reflection is seen at the far end.
Connect the model 3039-I between the sheath and one or both conductors. Sheath
should not be grounded when making this test.
Good Splices: Even good splices show a reflection because of capacitance change. This
shows as a small positive reflection followed by a negative one
ANNEXURE-1
ANNEXURE-2
ANNEXURE-3
Telecom Cables
PIJF Telephone Cable (Polythene Insulated
1 polythene sheathed Jelly Filled Telephone IRS TC 41/97(Amd.3)
Cable with poly –Al moisture barrier)
Underground Railway Jelly Filled Quad Cables
2 for Signalling and Telecom Installations (0.9 mm IRS TC 30/2005 (Ver.-1) Amd.5
dia conductor)
RDSO/SPN/TC/72/2007, Rev.0,
3 1.4 mm dia copper conductor 4/6 quad cable
Amd.2
Composite Underground Armoured Cable
4 **RDSO/SPN/TC/50/2007 (Rev 5)
Consisting of 6 Copper Quads And 8/24 Fibers
TECSpecification:
5 Telecommunication Switch Board Cables
GIR/WIR – 06/03 March 02
Jointing Kits
Thermo Shrink Jointing Kit for Jointing RDSO/SPN/TC/57/2015
1
Underground PIJF Cable (TSF: 1-5) (Rev.1) Amd-1
Thermo Shrink Jointing Kit for Jointing
Underground Quad Cable (RTSF for
0.9mm/1.4mm conductor dia 4/6 quad cable IRS TC 77/2012(Rev.3)
2
Derivation Joint/transformer Joint/Straight amendment 3
through Joint/Condenser Joint/Loading Coil
Joint)
Joint Closure for Composite (Optical & Quad) **RDSO/SPN/TC/56/2007(Rev.-2)
3
Underground Armoured Cable. (Amdt-1)
RDSO/SPN/TC/101/2012
4 Silicone Gel based cable jointing kit
amendment1
Termination boxes
1 Cable Termination Boxes (indoor) IRS TC 18/75
Telecom Cable Termination Box (non-metallic)
2 RDSO/SPN/TC/97-2012 Rev.1
for indoor use
TEC: CT Block spec. GR/CTN-
4 KRONE LSA-PLUS Connection Module
03/03 March 04
TEC spec. GR/CTN-01/04 May
5 KRONE LSA-PLUS Insertion Tool
2005
Passive Devices
V.F. Tapping Transformer; 1120: 1120, 1120:
1 IRS TC: 22/2021 ver 1.1
600 & 470: 1120
V.F. Transformers (2T/3T) Suitable for
2 IRS TC: 76/2021 ver 1.0
underground telecom. Cable circuits.
3 Balancing Condensers. IRS TC 11/73
Polystyrene Condenser for Balancing and
4 **IRS TC 49/93
Building out Network.
5 Loading Coil joints. IRS TC 29/81
Earthing System
1 Conventional Earthing arrangement RDSO drg no: TCA 565(ADV)
Code of practice for earthing and bonding
2 system for signalling equipment (The acceptable RDSO/SPN/197/2014 ver.1
Earth Resistance shall not be more than 1 ohm).
Control Communication
4 Wire / 2 Wire Train Traffic Control Equipment
IRS TC: 60/2007 amendment 1
1 with Dual Tone Multi Frequency (DTMF)
Signalling
2 Repeater Station Equipment IRS TC 50/90
Voice Frequency Communication System for RDSO/SPN/TC/34/2002 (Ver. 4)
3
Underground Quad cable amendment1
Junction Equipment and speech Conversion
4 IRS TC 46-88
Equipment used in AC Electrified Area.
5 Desk Type 2 Wire, 12 Way DTMF Telephone IRS TC 80/2000 (Amd. 3)
6 Universal Wayside DTMF Control Telephone IRS TC 82/ 2005 (Amd.3)
Integrated Way Station Control Communication **RDSO/SPN/TC/70/2007
7
Equipment With Amendment- 1
8 Emergency Control Room Equipment IRS TC:61/93 (Amd.2)
9 Light Weight Portable Control Telephone IRS TC: 78/20 version 1
10 4-Wire Way Station Control Telephone IRS TC: 38/97 (Amd.2)
11 2 –Wire Way Station Control Telephone IRS TC 37/97 (Amd.2)
4-Wire/2 Wire Combined Portable Control
12 IRS TC: 75/99 (Amd.4)
Telephone
13 Magneto Telephone Desk Type IRS TC: 36/97 (Amd.2)
14 Desk Type Electronic Magneto Telephone IRS TC: 79/2000(Amd.4)
LC Gate Control Equipment Using Wired &
15 RDSO/SPN/TC/49/202- Ver. 1
Wireless Data Communication.
16 Electronic L.C Gate Telephone System RDSO/SPN/TC/51/2021 rev 1.0
Auto Dialling System from Emergency Socket in
17 IRS: S-83/2007 Amd-1
RE Area
18 Six Pin Emergency Plug and Socket IRS TC: 42/20 ver1.0
19 Emergency Socket Box of FRP Material RDSO/SPN/TC/44/2002 Ver.3.0
Power Supply Unit for Telecom Installations at
20 IRS TC: 72/97 (Amd.1)
Way Side Stations In 25 KV Electrified Area
Measuring Instruments
1 Digital Capacitance Unbalance Measuring set. IRS TC 48/90
2 Transmission Measuring Sets. IRS TC 43/87
3 Cross Talk Measuring Sets. IRS TC 45-88
TEC Spec: GR/TIE-05/03 July
4 Digital Cable Fault Locator
2006
OFC Cable
1 24 Fiber Armoured Optic Fiber Cable IRS TC: 55/2006 Rev-1 Amd.3
2 Fiber Distribution Management System RDSO/SPN/TC/037/2020 Rev.4.0
Fiber Distribution Management System for
**RDSO/SPN/TC/071/2008
3 Composite (Optical and Quad) Underground
(Rev. 1.0) Amdt. -1
Armoured Cable
** RDSO site presently not showing the reference for these specifications.
QUESTION BANK
OBJECTIVE
Chapter 1
1. The maximum number of pairs on a pole route in Over Head Alignment is limited to ____.
a) 8 b) 12 c) 16 d) 20
2. Distortion less condition in a cable can be achieved by satisfying the condition of______.
a) LR=CG b) GL=CR c) RG=CL d) CG=LR
3. Length of Loading section in the 4/6 quad cable system is _______________________.
a) 500 meters b) 1000 meters c) 1500 meters d) 2000 meters
4. Commonly used frequency for standard audio measurements is__________________.
a) 10 KHz b) 3.4 KHz c) 1 KHz d) 0.3 KHz
5. Loading of cable in underground cable is done to reduce cross-talk. (T/F)
6. Overhead lines are not fit for Telecom circuits in the RE area because of induced voltage.
(T/F)
7. Phantom circuit is a super imposed circuit derived from side circuits. (T/F)
8. Cross-talk couplings causes‟ noise and Earth couplings cause side tone in VF circuits.
(T/F)
9. The purpose of twisted pairs in telecom cables is to reduce cross talk. (T/F)
10. Capacitance unbalance can be reduced by adding118 mH external capacitors. (T/F)
Chapter 2
Chapter 3
1. Expand PIJF: ___________________________________________________________
2. RDSO spec. for PIJF telephone Cable is ____________________________________
3. In 20 pair PIJF cable, colour code of pair number 18 is __________________________.
a) Green-Black b) Green-Yellow c) Brown-Black d) Brown-Yellow
4. In 20 pair PIJF cable, number of main conductor insulation colours are ___________ and
mate colours are ________.
a) 5 and 5 b) 4 and 5 c) 5 and 4 d) 4 and 4
5. The number of conductors in 20 pair cable are ______________________.
a) 10 b) 20 c) 30 d) 40
6. The number of units in 50 pair cable are ___________________________.
a) 2 b) 3 c) 5 d) 10
7. The number of pairs in each unit in 100 pair cable are ___________________.
a) 5 b) 10 c) 20 d) 50
8. The number of units in 20 pair cable are ______________________.
a) 1 b) 2 c) 4 d) 5
9. The colour of the binding tape used for identifying 4 th unit in 50 pair cable is__________.
a) White b) Blue c) Red d) Brown
10. 0.51 mm dia conductor pair may be used upto _____ mtrs for subscriber loop application.
a) 100 b) 500 c) 1000 d) 5000
11. Entry of moisture / water is prevented by __________________in the core of PIJF cable.
a) Sheath b) PVC Jacket c) Jelly d) Armour
12. Loop Resistance of a pair of 0.63 mm dia conductor is ____________Ohms.
a) 184 b) 128 c) 86 d) 56
13. Min. bending radius of underground PIJF Telecom cable is _____time of cable diameter
a) 3 b) 5 c) 10 d) 15
14. How many number of super units shall be assembled to form a 200 pair cable?
a) 2 b) 4 c) 5 d) 10
15. The basic purpose of Amour in UG cable is to reduce induced voltage. (T/F)
16. Loop Resistance of pair of 0-51 mm dia conductor is 184 Ohms. (T/F)
17. PVC Jacket is the sheathing arrangement made over armoured cable to protect the
armour against oxidation. (T/F)
18. Information of the cable exists throughout the length of cable at regular intervals of ten
meters. (T/F)
19. 0 .63 mm dia conductor pair may be used upto 10 Km for subscriber loop application (T/F)
20. A 50 pair cable consists of 10 numbers of 5 pair units (T/F)
Chapter 4
7. Electrostatic induction occurs due to capacitance coupling between conductor and earth.
(T/F)
8. Before cutting the armour or sheath/screen of cables an electrical connectivity is to be
established between two ends of the cable through an external wire. (T/F)
9. Screening factor is the ratio of voltage induced in the conductor in absence of metallic
sheath and voltage induced in the presence of metallic sheath. (T/F)
10. In RE area normal field strength of 87.5 V/Km exists in telecom cable (T/F)
11. The 25KV AC catenary system acts like a primary winding and each other parallel
conductor acts like the secondary winding of a transformer. (T/F)
12. Usage of “Insulated Tools and Rubber Gloves” are mandatory precautions for protection
of staff who are working in 25 KV 50 Hz AC traction territory. (T/F)
13. The induction by A.C traction system in Telecom circuits is due to electrostatic coupling
and electromagnetic coupling. (T/F)
14. Sectionalisation of the Telecom circuits prevents cumulative build-up of induced voltage
(T/F)
15. The magnitude of potential due to electrostatic induction depends on the voltage of the
catenary and distance. (T/F)
Chapter 5
1. The Transmission loss in 4.5 mm dia ACSR line is 0.038 dB and 0.9 mm dia copper pair
in quad cable is 0.63 dB. (T/F)
2. 4 Wire system in U/G cable is because of usage of amplifiers. (T/F)
3 RDSO specification of 4/6 PIJF quad cable of 0.9 mm dia conductor is IRS:TC 30/2005.
(T/F)
4. RDSO specification of 4/6 PIJF quad cable of 1.4 mm dia conductor is RDSO SPN TC
RDSO/SPN/TC/72-07. (T/F)
5. A 1.4 mm dia conductor 4/6 quad cable is used in longer (more than 25 Km) distance
Block sections. (T/F)
6. The insulation resistance between each conductor of a quad shall not be less than 5000
Mega ohms per kilometre when measured with 500V megger under factory acceptance
test. (T/F)
7. Purpose of the Poly Aluminium Moisture Barrier in a quad cable is to prevent ingress of
moisture. (T/F)
8. The colour code of quad no 5 in 6 quad cable is Yellow-White & Red-Grey (T/F)
9. Present Status of 6 Quad Cable System used in various Railways is, 6 quad cable with
Equalizer Amplifier OFC and 6 quad cable with OFC (T/F)
10. The Colour of the 4th quad whipping is Green (T/F)
Chapter 6
1. The normal depth of the trench for Telecom Quad Cable is ______cm.
a) 150 b) 120 c) 100 d) 80
2. The standard drum length of 4/6 quad cable is ________ meters.
a) 500 b) 1000 c) 1500 d) 2000
3. OFC and 6 quad U/G cables are to be laid in same trench in a depth ___ & ____cm
a) 100 & 80 b) 100 & 100 c) 120 & 100 d) 120 &120
Chapter 7
1. The impedance ratio of the transformer used for EC socket in an unloaded quad cable
system is _____________Ohms.
a) 1120:1120 b) 470:470 c) 1120:470 d) 470:1120
2. Value of loading coil used for 6Q cable is ____________________ mH.
a) 88 b) 98 c) 118 d) 128
3. Length of loading section in 6Quad cable is ____________________ meters.
a) 500 b) 1000 c) 1500 d) 2000
4. Shelf life of U/G quad cable jointing kit is_______________________ months.
a) 12 b) 24 c) 36 d) 48
5. Minimum of ______ meter of cable of each end is coiled in the jointing pit while laying.
a) 3 b) 5 c) 8 d) 10
6. “Branch off clip” is used for derivation joint. (T/F)
7. RTSF is Reinforce Thermo Shrink Jointing Filled (T/F)
8. RDSO specification for RTSF jointing kit is RDSO / SPN / TC: 77 / 2012 (T/F)
9. The transformer used in unloaded quad cable for termination of 2 wire circuit is 470:1120
Ohms. (T/F)
10. Aluminium foil in TSF kit is to prevent the damaging of conductors during the shrinking
process. (T/F)
11. TSF 4 kit is used for jointing of 6 quad cable. (T/F)
12. In 6 quad cable the splice is to be filled with petroleum jelly. (T/F)
13. In a Quad cable jointing, the aluminium screen of the cable is made through by using
“Sheath Connector Assembly´. (T/F)
IRISET 102 TC1 - Telecom Cables (Copper)
Question Bank
14. The KRONE module can be used for termination of quad cable conductors. (T/F)
15. Wago terminals can be used for termination of different telecom cable conductors. (T/F)
Chapter 8
1. Insulation resistance of quad cable conductors shall be tested with 100 V Megger, at the
time of commissioning of quad cables. (T/F)
2. Transmission loss test shall be carried out with TMS kit. (T/F)
3. Cross Talk in quad cable has to be measured once in 6 months. (T/F)
4. Quad cable armour shall be connected to earth which is having resistance of 10 Ohms.
(T/F)
5. Working principle of Digital Cable Fault locator is reflection of pulses. (T/F)
6. Periodicity of Psophpmetric Noise test in a quad cable is once in a year. (T/F)
7. The insulation resistance of quad cable conductors shall not be less than
100 Mega Ohms/Km. (T/F)
8. Quad cable conductors can be paralleled for reducing the conductor resistance for BPAC
circuit. (T/F)
9. Transmission loss at 2 KHz will be 1.2 dB/Km. (T/F)
10. The instrument used for measuring all types of noise together is Psophometer. (T/F)
Chapter 9
1. Before disconnecting Block, BPAC and IB circuits in quad cable for testing, disconnection
memo has to be issued to Station Master. (T/F)
2. The Integrated Cable path diagram will show all S&T Cable path positions of particular
section in one sheet of paper. (T/F)
3. The important tools to protect S&T Cables from damages are Integrated Cable Path
diagram, Cable route tracer and Cable Fault Locator. (T/F)
4 BPAC circuit in quad cable shall be tested from Entry location to Exit locaton. (T/F)
5. Quad cable has to be tested periodically by JE/SSE/T once in three months.
(T/F)
6. Quad cable has to be inspected by officers once in a year. (T/F)
7. Insulation Resistance Test will be carried out one in three months under Schedule of
Testing. (T/F)
8. SSE / T/ Section In-charge has to test the quad cable one in six months. (T/F)
9. Induced Voltage in quad cable conductor with respect to earth shall be below 5V AC.
(T/F)
10. Near End Crosstalk @ 800 Hz in quad cable pairs shall be better than -65db. (T/F)
Key to Objective
Chapter 1: 1) c 2) b 3) d 4) c 5) False
6) True 7) True 8) False 9) True 10) False
Chapter 2: 1) b 2) c 3) b 4) a 5) c
6) True 7) False 8) True 9) False 10) True 11) False
Chapter 3:
1) Polythene Insulated Jelly Filled 2) IRS-TC: 41/97
3) b 4) c 5) d 6) c 7) c 8) c 9) d 10) d
11) c 12) b 13) d 14) b 15) False 16) True 17) True 18) False
19) True 20) False
Chapter 6: 1) c 2) b 3) c 4) b 5) c 6) c 7) b 8) c 9) c 10) b
11) True 12) False 13) True 14) True 15) False
SUBJECTIVE:
Chapter 1
1. What are the different types of transmission media used in Indian Railways
Telecommunication?
2. Compare Underground cables with O/H lines.
3. Give the Classification of Telecommunication cables.
4. What are the “Primary elements” in telecom cable? What is their effect? How are they taken
care while manufacturing the cable?
5. Explain the relation between Impedance and Frequency in Telecom transmission lines.
6. What is the importance of V.F Balancing and Loading in Telecom cable?
7. What are the different types of capacitive and Earth couplings in Telecom quad cable?
Chapter 2
1. What are different types of Switch Board Cables and its specifications?
2. What are the different types of schemes of colour codes of 20 pair SB cable?
3. Explain briefly about Twin Flat and FS cable.
4. Write short notes on UTP and STP cables.
5. Mention different types of cables and its applications in Railways.
Chapter 3
Chapter 4
Chapter 5
1. Explain the importance of Quad Cable over ACSR overhead lines in RE area.
2. What are different types of Quad Cables?
3. Explain about RE Main Cables.
4. Explain the construction of 6 quad cables with a neat figure.
5. Explain the importance of metallic protection systems available in quad cable.
6. What is the colour code scheme of 6 quad cable?
7. What are the general specifications of 4/6 quad cable of 0.9 mm & 1.4 mm dia conductor?
8. Write the Specifications of 6 quad cable.
9. Write the quad allocation of 6 quad cables with OFC and without OFC.
10. What is the difference between PIJF underground Paired and Quad Cables
Chapter 6
1. What are the important objectives to be considered in the preliminary cable route survey?
2. What are guidelines for finalizing the route and preparation of the cable route plans?
3. What are the methods of laying underground cable? Explain each in detail.
4. What is the procedure of laying U/G cable while crossing Roadways, Railway tracks?
5. How underground cables shall be protected on culverts and bridges?
6. What precautions to be taken while laying underground cables at TSS/FP locations?
7. How are underground telecom cables protected in the 11KV electric cables area?
Chapter 7
Chapter 8
1. What are the tests to be carried out before laying the cable and after laying the cable?
2. What are mandatory checks and tests to be carried out before commissioning of a BPAC
application in quad cable?
3. What are causes for cable failures and how to prevent them?
4. How to localize the cable faults and explain its procedure?
5. What cable faults can be identified by using a Digital Cable fault locator?
Chapter 9
Chapter 10
ABBREVIATIONS / ACRONYMS
ACSR- Aluminium conductor, steel reinforced. Aluminium wires stranded around a steel core.
AERIAL CABLE- A cable suspended in the air on poles or other overhead structures.
AWG: AMERICAN WIRE GAUGE
ANNEALED WIRE- Wire which has been softened by heating and gradually cooling.
ARMOUR - An outer braid of metal or spiral steel tapes, primarily for the purpose of mechanical
protection.
ATTENUATION - The loss of power or signal in a circuit, generally expressed in decibels (dB)
per unit length, usually one thousand (1,000) feet. In optical fiber cables, attenuation is the ratio
of input power vs. output power, measured in decibels per unit length, usually dB/km.
Abbreviated as attn.
AUDIO FREQUENCY - The range of frequencies audible to the human ear, approximately 20 to
20,000 Hz.
AWG - Abbreviation for American Wire Gauge. The system most commonly used in the United
States for describing the size of copper wire.
CABLE- A cable may be a small number of large conductors or a large number of small
conductors, cabled together, usually colour coded and with a pro-tective jacket overall.
CABLE ASSEMBLY - A cable assembly is a cable with plugs or connectors on each end for a
specific pur-pose. It may be formed in various configurations.
CABLE CORE- The portion of an insulated cable lying under the protective covering or jacket.
CAPACITANCE, MUTUAL- The capacitance be-tween two conductors with all other
conductors, including shield, short-circuited to ground.
CAPACITANCE, UNBALANCED - An inequality of capacitance between the wires of two or
more pairs which results in a transfer of unwanted signal from one pair to others.
CAPACITANCE, UNBALANCED to GROUND - An inequality of capacitance between the
ground ca-pacitance of the conductors of a pair which results in a pickup of external source
energy, usually from power transmission lines.
CAPACITIVE COUPLING - Electrical interaction between two conductors caused by the
capacitance between them.
CHARACTERISTIC IMPEDANCE- a) The imped-ance that when connected to the output
terminals of a transmission line of any length, makes the line appear infinitely long. b) The ratio
of voltage to cur-rent at every point along a transmission line on which there are no standing
waves.
COAXIALCABLE- A cable in which one conductor completely surrounds the other, the two
being coaxial and separated by a continuous solid dielectric or by dielectric spacers. When the
outside conductor is grounded, the inside conductor is not susceptible to external fields from
outside sources.
IRISET 107 TC1 - Telecom Cables (Copper)
Abbreviations/Acronyms
COIL- A coiled conductor, wound on a form or core which uses electromagnetic induction to
cause changes in a current.
COLOR CODE- Colour code is the use of different coloured insulated wires for purposes of
identification in a multi-conductor cable.
COMPOSITE CABLE- A cable consisting of two or more different types or sizes of wire and/or
cable.
CONDUCTIVITY - The capability of a material to carry electrical current, usually expressed as a
percentage of copper conductivity (copper being 100%). The reciprocal of resistivity.
CONDUCTOR - A material that offers a low resistance to the passage of electric current. When
a potential difference is applied across it, a relatively large current flow. A conductor usually
consists of copper, aluminium, steel, silver, or other materials.
CONDUIT - A tube or trough for protecting electrical wires or cables.
CONTINUITY CHECK - A test performed on a length of finished wire or cable to determine if the
electrical current flows continuously throughout the length. Each conductor may also be
checked against each other to ascertain that no shorts exist between conductors.
EARTH FAULT - A fault that occurs when a conductor is accidentally connected to earth or
when the resistance to earth of an insulator falls below a specific value.
FAULT CURRENT - A current that may flow through a circuit or device as a result of a fault,
such as a defect in the insulation.
HEAT SHRINK - A material that shrinks when heated. Heat shrink tubing is used for insulation,
sealing, and protecting wire connections, terminations, and splices.
HOOK-UP WIRE- A wire used for low current, low voltage (under 1,000 volts) applications
within en-closed electronic equipment, usually 12 AWG and smaller.
LOOP RESISTANCE-The total resistance of two conductors measured round-trip from one end.
RIP CORD - A parallel construction of two or more insulated conductors which may be easily
separated leaving the insulation of the conductors undisturbed.
TINNED COPPER - Tin coating added to a copper conductor or braid to aid in soldering and
inhibit corrosion.
VSWR - Abbreviation for Voltage Standing Wave Ratio. The ratio of the voltage maximum to
voltage minimum which exists in a transmission line. Caused when there is reflection of the
incident wave, due to a discontinuity or improper match to the transmission line.
GLOSSARY
A F
aerial, 1 failure, 13, 43, 54, 60,
alignment, 2, 26, 31, 33, 62 fiber, 1,
allocation, 31, 33, 65 flux,
annealed, 10, 13, 14, 17, 28 foil, 7, 14, 31, 50,
attenuation, 5, 19, 26, 30, 58, 64 foreign, 1, 61
availability, 1, 33, 63 frequency, 3, 4, 8, 14, 15, 22, 30, 62,
axis, 3 G
B galvanised, 29,
backbone, 13, 15 gauge, 4, 7,
balancing, 5, 30 glossy,
bandwidth, 3, 27 gloves,
bending, 43 ground, 8, 23, 32, 36, 38, 39, 97, 98,
C H
harmonic, 22, 59,
canister, 45, 50, 51, 52 hazardous, 24,
capacitance, 3, 4, 5, 6, 17, 21 homogeneous, 10,
capacitive, 4, 6 I
catenary, 21, 22 impairment, 39,
channel, 51, 52 impedance, 3, 4, 10, 15, 30, 44, 62,
characteristic, 3, 4, 5, 15 impregnated, 28, 29,
clamp, 56 improper, 39, 63,
coaxial, 1, 15 induction, 21, 22, 23, 39, 59,
codal, 61 inductive, 4, 22, 39,
condenser, integrity, 66, 67, 68, 69
conductance, 3, 46 introduced, 3, 13, 26, 27
conduit, 7, 100 introduction, 23, 27
connector, 13, 15, 48, 53, 54 isolation,
control, 31, 44 J
corrosive, 36, jacket, 6, 7, 14, 15, 17, 20, 27
couplings, 3, 6, jelly, 7, 16, 17, 27, 28, 45, 48, 53, 54, 56,
crimping, 48, 54, 61,
crosstalk, 5, 12, 13, 59, joint, 5, 34, 35, 37, 38, 43, 44, 45, 46, 52,
culvert, 37, 38, 63, 54, 60, 61, 63
D K
db, 60, 66, 67, 68, 69, kink, 62
dbm, kit, 45, 46, 51, 52, 54, 60
derivation, 34, 35, 44, 45, 49, 51, krone,
disconnection, 63, L
discrete, 54, layer, 6, 15, 29, 36
disparity, 57, laying, 4, 3, 30, 32, 35, 36, 37, 38, 39, 57,
duct, 32, 36, 60,
dummy, leakage, 3,
dwc, lightning, 60, 63,
E loading, 4, 5, 30, 44,
earthing, 25, 31, 38, 39, 63, localization, 57, 61,
effect, 4, 12, 15, 22, 26, 34, 59, longitudinal, 17, 23, 28, 37,
electrification, loop, 10, 16, 19, 35, 57, 60, 61,
electrified, 26, M
electromagnetic, 3, 6, 13, 15, 21, 24, 59 magnetic, 4, 21, 22, 23,
electrostatic, 3, 21, 23, 59, magnitude, 21, 62,
embossed, 11, 20 matching, 44,
emf, 21, megger, 28, 46,
excavation, 36, 37 metallic, 10, 11, 22, 23, 24, 25, 26, 38, 39
extend, 11,
IRISET 110 TC1 - Telecom Cables (Copper)
Glossary
© IRISET