User Manual ELK38
User Manual ELK38
User Manual ELK38
Bruger manual
Vr. 02 (ENG) - cod.: ISTR 06261
Newtronic ApS
Stensballe Strandvej 181 8700 Horsens Danmark Tlf.:7669 7090 Fax :7627 7090 [email protected] www.newtronic.dk
INSTRUMENT DESCRIPTION GENERAL DESCRIPTION FRONT PANEL DESCRIPTION PROGRAMMING FAST PROGRAMMING OF SET POINT SELECTION OF CONTROL STATE AND PARAMETER PROGRAMMING 2.3 PARAMETER PROGRAMMING LEVELS 2.4 CONTROL STATES 2.5 ACTIVE SET POINT SELECTION 3 INFORMATION ON INSTALLATION AND USE 3.1 PERMITTED USE 3.2 MECHANICAL MOUNTING 3.3 ELECTRICAL CONNECTIONS 3.4 ELECTRICAL WIRING DIAGRAM 4 FUNCTIONS 4.1 MEASURING AND VISUALIZATION 4.2 OUTPUTS CONFIGURATION 4.3 ON/OFF CONTROL 4.4 NEUTRAL ZONE ON/OFF CONTROL 4.5 SINGLE ACTION PID CONTROL 4.6 DOUBLE ACTION PID CONTROL 4.7 AUTO-TUNING AND SELF-TUNING FUNCTIONS 4.8 REACHING OF SET POINT AT CONTROLLED SPEED AND AUTOMATIC COMMUTATION BETWEEN TWO SET POINTS 4.9 SOFT-START FUNCTION 4.10 ALARM FUNCTIONS 4.10.1 ALARM OUTPUT CONFIGURATION 4.10.2 ALARM HYSTERESIS 4.11 LOOP BREAK ALARM FUNCTION 4.12 FUNCTION OF KEY U 4.13 PARAMETERS CONFIGURATION BY KEY01 5 PROGRAMMABLE PARAMETERS 5.1 PARAMETERS TABLE 5.2 PARAMETERS DESCRIPTION 6 PROBLEMS , MAINTENANCE AND GUARANTEE 6.1 ERROR SIGNALLING 6.2 CLEANING 6.3 GUARANTEE AND REPAIRS 7 TECHNICAL DATA 7.1 ELECTRICAL DATA 7.2 MECHANICAL DATA 7.3 MECHANICAL DIMENSIONS, PANEL CUT-OUT AND MOUNTING 7.4 FUNCTIONAL DATA 7.5 MEASUREMENT RANGE TABLE 7.6 INSTRUMENT ORDERING CODE 1 - INSTRUMENT DESCRIPTION
FOREWORD: This manual contains the information necessary for the product to be installed correctly and also instructions for its maintenance and use; we therefore recommend that the utmost attention is paid to the following instructions. Though this manual has been issued with the greatest care, ELCO S.r.l. will not take any responsibility deriving from its use. The same applies to each person or Company involved in the issuing of this manual. This document is the exclusive property of ELCO S.r.l. which forbids any reproduction and divulgation , even in part, of the document, unless expressly authorized. ELCO S.r.l. reserves the right to make any formal or functional changes at any moment and without any notice.
1.1 - GENERAL DESCRIPTION ELK 38 is a single loop digital microprocessor-based controller, with ON/OFF, Neutral Zone ON/OFF, PID single action, PID dual action (direct and reverse) control and with AUTO-TUNING FAST function, SELF-TUNING function and automatic calculation of the FUZZY OVERSHOOT CONTROL parameter for PID control. The PID control has a particular algorithm with TWO DEGREES OF FREEDOM that optimises the instruments features independently in the event of process disturbance and Set Point variations. The process value is visualized on 4 red displays, while the output status is indicated by 2 LED displays. The instrument is equipped with a 3 LED programmable shift indexes . The instrument provides for the storage of 4 Set Points and can have up to 2 outputs: relay type or can drive solid state relays type (SSR). Depending on the model required the input accept: C: Thermocouples temperature probes (J,K,S and ELCO IRS Infrared sensors), mV signals (0..50/60 mV, 12..60 mV), Thermoresistances PT100.
ELK 38
PAG. 1
2.2 - SELECTION OF THE CONTROL STATE AND PARAMETER PROGRAMMING By pushing key "P" and holding it down for approx. 2 sec. it is possible to enter into the main selection menu. Using the "UP" or DOWN keys, it is then possible to roll over the selections: to enter into the operating parameters menu "OPEr" to enter into the configuration parameters menu "ConF" to swap the regulator into the OFF state "OFF" 1.2 - FRONT PANEL DESCRIPTION to swap the regulator into the automatic control state "rEG" to activate the Auto-tuning or Self-tuning function "tunE" "OPLO" to swap the regulator to the manual control state and ELK therefore to program the % control value using the UP and DOWN keys Once the desired item has been selected, push key P to confirm. Selecting "OPEr" and "ConF" gives the possibility of accessing other menus containing additional parameters and more precisely : "OPEr" - Operating parameters Menu: this normally contains the Set Point parameters but it can contain all the desired parameters (see par. 2.3). "ConF" - Configuration parameters Menu: this contains all the 1 - Key P : This is used to access the programming parameters and operating parameters and the functioning configuration parameters to confirm selection. (alarm configuration, control, input, etc.) 2 - Key DOWN : This is used to decrease the values to be set and to select the parameters. If the key is held down, the user returns to the previous programming level until he exits the programming mode. Outside the programming mode it permits visualisation of the current measured by the TAHB input. 3 - Key UP : This is used to increase the values to be set and to select the parameters. If the key is held down, the user returns to the previous programming level until he exits the programming mode. Outside the programming mode it permits visualisation of the output control power. 4 - Key U : This is a key with a function programmable by par. USrb. It can be set to : Activate Auto-tuning and Self-tuning functions, swap the instrument to manual control, silence the alarm, change the active Set Point, deactivate control. 5 - Led OUT1 : indicates the state of output OUT1 6 - Led OUT2 : indicates the state of output OUT2 7 - Led SET : when flashing, it indicates access to the programming mode. 8 - Led AT/ST : indicates that the Self-tuning function is activated (light on) or that Auto-tuning (flashing ) is in progress. 9 - Led Shift index: indicates that the process value is lower than the one programmed on par. AdE. 10 - Led = Shift index: indicates that the process value is within the range [SP+AdE ... SP-AdE] 11 - Led + Shift index: indicates that the process value is higher than the one set on par. AdE. 2 - PROGRAMMING 2 .1 - FAST PROGRAMMING OF THE SET POINT This procedure permits rapid programming of the active Set Point and possibly the alarm thresholds (see par 2.3) Push key P, then release it and the display will visualise SP n (where n is the number of the Set Point active at that moment) alternatively to the programmed value. To modify the value, press UP key to increase it or the DOWN key to decrease it. These keys change the value one digit at a time but if they are pressed for more than one second, the value increases or decreases rapidly and, after two seconds in the same condition, the changing speed increases in order to allow the desired value to be reached rapidly. Once the desired value has been reached, by pushing key P it is possible to exit by the fast programming mode or it is possible to visualise the alarm thresholds (see par. 2.3). To exit the fast Set programming it is necessary to push key P, after the visualisation of the last Set Point, or alternatively, if no key is pressed for approx. 15 seconds, the display will return to normal functioning automatically. To enter the menu OPEr, select the option OPEr and press the key P. The display will now show the code identifying the first group of ] parameters ( SP ) and by pressing the UP and DOWN keys it will be possible to select the group of parameters to be modified. Once the desired group of parameters has been selected, the code identifying the first parameter of the selected group will be visualised by pushing the P key. Again using the UP and DOWN keys, it is possible to select the desired parameter and, if the key P is pressed, the display will alternatively show the parameters code and its programming value, which can be modified by using the UP or DOWN keys. Once the desired value has been programmed, push key P once more: the new value will be memorised and the display will show only the code of the selected parameter. By using the UP or DOWN keys, it is then possible to select a new parameter (if present) and modify it as described above. To select another group of parameters, keep the UP or DOWN key pressed for approx. 2 sec., afterwards the display will return to visualise the code of the group of parameters.
E : Thermocouples temperature probes (J,K,S and ELCO IRS Infrared sensors), mV signals (0..50/60 mV, 12..60 mV), Thermistors PTC and NTC. I : normalized analogue signals 0/4..20 mA V : normalized analogue signals 0..1 V, 0/1..5 V, 0/2..10 V Other important available functions are: Loop-Break Alarm function, reaching of the Set Point at controlled speed, ramp and dwell function, Soft-Start function, protection compressor function for neutral zone control, parameters protection on different levels.
ELK 38
PAG. 2
Release the key and by using the UP and DOWN keys, it will be possible to select a new group (if present). To exit the programming mode, no key should be pressed for approx. 20 seconds, or keep the UP or DOWN pressed until exit from the programming mode is obtained. To enter the menu "ConF" a PASSWORD is required. At this request, enter, using keys UP and DOWN, the number reported on the last page of this manual and push key P. If an incorrect password is entered, the instrument returns to the previous control state. If the password is correct, the display will visualise the code ] identifying the first group of parameters ( SP ) and with keys UP and DOWN it will be possible to select the desired group of parameters The programming and exit modes for the ConF menu are the same as those described for menu OPEr.
During automatic control it is possible to visualize the control power on the display by pushing key UP. The range of the power values goes from H100 (100% of the output power with reverse action) to C100 (100% of the output power with direct action). CONTROL OFF (OFF) The instrument can be swapped into the OFF state, i.e. the control and the relative outputs are deactivated. The alarm outputs are instead working normally. BUMPLESS MANUAL CONTROL (OPLO) By means of this option it is possible to manually program the power percentage given as output by the controller by deactivating automatic control. When the instrument is swapped to manual control, the power percentage is the same as the last one supplied and can be modified using the UP and DOWN keys. As in the case of automatic control, the programmable values range from H100 (+100%) to C100 (-100%). To return to automatic control, select "rEG" in the selection menu. 2.5 - ACTIVE SET POINT SELECTION This instrument permits pre-programming of up to 4 different Set points (SP1, SP2, SP3, SP4) and then selection of which one must be active. The maximum number of Set points is determined by the par. "nSP" located in the group of parameters ] SP . The active Set point can be selected : ] - by parameter "SPAt" in the group of parameters SP . - by key U if par. "USrb" = CHSP - Automatically between SP1 and SP2 if a time dur.t (see par. 4.8) has been programmed. Set Points SP1, SP2, SP3, SP4 will be visible depending on the maximum number of Set Points selected on par. nSP and they can be programmed with a value that is between the value programmed on par. SPLL and the one programmed on par. SPHL. Note : in all the following examples the Set point is indicated as "SP", however the instrument will act according to the Set point selected as active. 3 - INFORMATION ON INSTALLATION AND USE 3.1 - PERMITTED USE The instrument has been projected and manufactured as a measuring and control device to be used according to EN61010-1 for the altitudes operation until 2000 ms. The use of the instrument for applications not expressly permitted by the above mentioned rule must adopt all the necessary protective measures. The instrument CANNOT be used in dangerous environments (flammable or explosive) without adequate protection. The installer must ensure that EMC rules are respected, also after the instrument installation, if necessary using proper filters. Whenever a failure or a malfunction of the device may cause dangerous situations for persons, thing or animals, please remember that the plant has to be equipped with additional devices which will guarantee safety. 3.2 MECHANICAL MOUNTING The instrument, in case 33 x 75 mm, is designed for flush-in panel mounting. Make a hole 29 x 71 mm and insert the instrument, fixing it with the provided special bracket. We recommend that the gasket is mounted in order to obtain the front protection degree as declared. Avoid placing the instrument in environments with very high humidity levels or dirt that may create condensation or introduction of conductive substances into the instrument. Ensure adequate ventilation to the instrument and avoid installation in containers that house devices which may overheat or which may cause the instrument to function at a higher temperature than the one permitted and declared.
2.3 - PARAMETERS PROGRAMMING LEVELS The menu OPEr normally contains the parameters used to program the Set Point; however it is possible to make all desired parameters appear or disappear on this level, by following this procedure: Enter the menu ConF and select the parameter to be made programmable or not programmable in the menu OPEr. Once the parameter has been selected, if the LED SET is switched off, this means that the parameter is programmable only in the menu ConF, if instead the LED is on, this means that the parameter is also programmable in the menu OPEr. To modify the visibility of the parameter, push key U : the LED SET will change its state indicating the parameter accessibility level (on = menu OPEr and ConF; off = menu ConF only). The active Set Point and the alarm thresholds will only be visible on the Set Point fast programming level (described in par. 2.1) if the relative parameters are programmed to be visible (i.e. if they are present in the menu OPEr). The possible modification of these Sets, with the procedure described in par. 2.1, is instead subordinate to what is programmed ] in par. Edit (contained in the group PAn ). This parameter can be programmed as : =SE : The active Set Point can be modified while the alarm thresholds cannot be modified. =AE : The active Set Point cannot be modified while the alarm thresholds can be modified =SAE : Both the active Set Point and the alarm thresholds can be modified =SAnE : Both the active Set Point and the alarm thresholds cannot be modified 2.4 - CONTROL STATES The controller can act in 3 different ways : automatic control (rEG), control off (OFF) and manual control (OPLO). The instrument is able to pass from one state to the other : - by selecting the desired state from the main selection menu suing the keyboard. - By using the key U on the keyboard; suitably programming par. USrb (USrb = tunE; USrb = OPLO; USrb = OFF) it is possible to pass from rEG state to the state programmed on the parameter and vice versa. - Automatically (the instrument swaps into "rEG" state at the and of the auto-tuning execution) When switched on, the instrument automatically reassumes the state it was in when it was last switched off. AUTOMATIC CONTROL (rEG) Automatic control is the normal functioning state of the controller.
ELK 38
PAG. 3
Connect the instrument as far away as possible from sources of I : normalized analogue signals 0/4..20 mA electromagnetic disturbances such as motors, power relays, relays, V : normalized analogue signals 0..1 V, 0/1..5 V, 0/2..10 V solenoid valves, etc. Depending on the model, using par. SEnS, its possible to select the type of input probe, which can be : 3.3 - ELECTRICAL CONNECTION - for thermocouples J (J), K (CrAL), S (S) or for infrared sensors Carry out the electrical wiring by connecting only one wire to each serie ELCO IRTC1 with linearization J (Ir.J) or K (Ir.CA) terminal, according to the following diagram, checking that the - for thermoresistances Pt100 IEC (Pt1) or thermistors PTC KTY81power supply is the same as that indicated on the instrument and 121 (Ptc) or NTC 103AT-2 (ntc) that the load current absorption is no higher than the maximum - for normalised signals in current 0..20 mA (0.20) or 4..20 mA electricity current permitted. (4.20) As the instrument is built-in equipment with permanent connection - for normalised signals in tension 0..1 V (0.1), 0..5 V (0.5), 1..5 V inside housing, it is not equipped with either switches or internal (1.5), 0..10 V (0.10) or 2..10 V (2.10). devices to protect against overload of current: the installation will - for normalised signals in tension 0..50 mV (0.50), 0..60 mV (0.60), include a two-phase circuit-breaker, placed as near as possible to 12..60 mV (12.60). the instrument, and located in a position that can easily be reached We recommend to switch on and off the instrument when these by the user and marked as instrument disconnecting device which parameters are modified, in order to obtain a correct measuring. interrupts the power supply to the equipment. For the instruments with input for temperature probes (tc, rtd) its It is also recommended that all the electrical circuits connected to possible to select, through par. Unit, the unit of measurement the instrument must be protect properly, using devices (ex. fuses) ( and, through par. dP (Pt100, PTC and NTC only) the C, F) proportionate to the circulating currents. desired resolution (0=1 1=0,1 ; ). It is strongly recommended that cables with proper insulation, Instead, with regards to the instruments with normalised analogue according to the working voltages and temperatures, be used. input signals, it is first necessary to program the desired resolution Furthermore, the input cable of the probe has to be kept separate on par. dP (0=1; 1=0,1; 2=0,01; 3=0,001) and then, on par. from line voltage wiring. If the input cable of the probe is screened, it "SSC", the value that the instrument must visualise at the beginning has to be connected to the ground with only one side. of the scale (0/4 mA, 0/12 mV, 0/1 V o 0/2 V) and, on par. "FSC", Whether the instrument is 12 V version its recommended to use an the value that the instrument must visualise at the end of the scale external transformer TCTR, or with equivalent features, and to use (20 mA, 50 mV, 60 mV, 5 V or 10 V). only one transformer for each instrument because there is no The instrument allows for measuring calibration, which may be used insulation between supply and input. to recalibrate the instrument according to application needs, by We recommend that a check should be made that the parameters using par. OFSt and rot. are those desired and that the application functions correctly before Programming par. rot=1,000, in par. OFSt it is possible to set a connecting the outputs to the actuators so as to avoid positive or negative offset that is simply added to the value read by malfunctioning that may cause irregularities in the plant that could the probe before visualisation, which remains constant for all the cause damage to people, things or animals. measurements. ELCO S.r.l. and its legal representatives do not assume any If instead, it is desired that the offset set should not be constant for responsibility for any damage to people, things or animals all the measurements, it is possible to operate the calibration on deriving from violation, wrong or improper use or in any case any two points. not in compliance with the instruments features. In this case, in order to decide which values to program on par. OFSt and rot, the following formulae must be applied : 3.4 - ELECTRICAL WIRING DIAGRAM rot = (D2-D1) / (M2-M1) OFSt = D2 - (rot x M2) where: M1 =measured value 1 D1 = visualisation value when the instrument measures M1 M2 =measured value 2 ELK D2 = visualisation value when the instrument measures M2 It then follows that the instrument will visualise : DV = MV x rot + OFSt where: DV = visualised value MV= measured value Example 1: It is desired that the instrument visualises the value effectively measured at 20 but that, at 200 it visualises a value , lower than 10 (190 ). Therefore : M1=20 ; D1=20 ; M2=200 ; D2=190 rot = (190 - 20) / (200 - 20) = 0,944 OFSt = 190 - (0,944 x 200) = 1,2 Example 2: It is desired that the instrument visualises 10 whilst the value actually measured is 0 but, at 500 it visualises a 50 higher , value (550 ). Therefore : M1=0 ; D1=10 ; M2=500 ; D2=550 rot = (550 - 10) / (500 - 0) = 1,08 OFSt = 550 - (1,08 x 500) = 10 By using par. FiL it is possible to program time constant of the software filter for the input value measured, in order to reduce noise sensitivity (increasing the time of reading). In case of measurement error, the instrument supplies the power as programmed on par. OPE. This power will be calculated according to cycle time programmed for the PID controller, while for the ON/OFF controllers the cycle time is automatically considered to be equal to 20 sec. (e.g. In the event of probe error with ON/OFF control and OPE=50, the control output will be activated for 10 sec., then it will be deactivated for 10 sec. and so on until the measurement error remains.).
4 - FUNCTIONS 4.1 - MEASURING AND VISUALIZATION All the parameters referring measurements are contained in the ] group InP. Depending on the model required the input accept: C: Thermocouples temperature probes (J,K,S and ELCO IRS Infrared sensors), mV signals (0..50/60 mV, 12..60 mV), Thermoresistances PT100. E : Thermocouples temperature probes (J,K,S and ELCO IRS Infrared sensors), mV signals (0..50/60 mV, 12..60 mV), Thermistors PTC and NTC.
ELK 38
PAG. 4
By using par. InE it is also possible to decide the conditions of the input error, allowing the instrument to give the power programmed on par. OPE as output. The possibilities of par. InE are : = Or : the condition occurs in case of over-range or probe breakage = Ur : the condition occurs in case of under-range or probe breakage = Our : the condition occurs in case of over-range or under-range or probe breakage ] Using par. diSP, located in the group PAn, it is possible to set normal visualization of the display which can be the process variable (dEF), the control power (Pou), the active Set Point (SP.F) the Set Point operating when there are active ramps (SP.o) or alarm threshold AL1 (AL1). ] Again in the group PAn the par. AdE is present that defines the 3 led shift index functioning. The lighting up of the green led = indicates that the process value is within the range [SP+AdE ... SP-AdE], the lighting up of the led indicates that the process value is lower than [SP-AdE] and the lighting up of the led + indicates that the process value is higher than [SP+AdE].
4.4 - NEUTRAL ZONE ON/OFF CONTROL (1rEG - 2rEG) All the parameters referring to Neutral Zone ON/OFF control are ] contained in the group rEG. This type of control can be obtained when 2 outputs are programmed respectively as 1rEG and 2rEG and the par. Cont = nr . The Neutral Zone control is used to control plants in which there is an element which causes a positive increase (ex. Heater, humidifier, etc.) and an element which causes a negative increase (ex. Cooler, de-humidifier, etc). The control functions works on the programmed outputs depending on the measurement, on the active Set Point SP and on the hysteresis "HSEt". The control works in the following way : it deactivates the outputs when the process value reaches the Set Point and it activates the output 1rEG when the process value goes below value [SP - HSEt], or it activates the output 2rEG when the process value goes above [SP + HSEt]. Consequently, the element causing a positive increase has to be connected to the output programmed as 1rEG while the element causing a negative increase has to be connected to the output programmed as 2rEG.
4.2 - OUTPUTS CONFIGURATION The instruments outputs can be programmed by entering the group ] of parameters Out, where the relative parameters O1F and O2F (depending on the number of outputs available on the instrument) are located. The outputs can be set for the following functions : - Main control output (1.rEG) - Secondary control output (2.rEG) - Alarm output normally open (ALno) - Alarm output normally closed (ALnc) - Alarm output normally closed with led reverse indication (ALni) - Output deactivated (OFF) The coupling outputs number outputs number alarms can be ] If 2rEG output is used to control compressor is possible to use the made in the group referring to the alarm to the alarm ( AL1). Compressor Protection function that has the meaning to avoid compressor short cycles. 4.3 ON/OFF CONTROL (1rEG) All the parameters referring to the ON/OFF control are contained in This function allows a control by time on the output 2rEG activation, ] independently by the temperature control request. the group rEG. This type of control can be obtained by programming par."Cont" = The protection is a delayed after deactivation type. On.FS or = On.FA and works on the output programmed as 1.rEG, This protection permits to avoid the output activation for a time depending on the measure, on the active Set Point SP, on the programmable on par. CPdt (expressed in sec.); the output activation will occurs only after the elapsing of time CPdt. functioning mode "Func and on the hysteresis "HSEt". The instrument carries out an ON/OFF control with symmetric The time programmed on parameter CPdt is counted starting from hysteresis if Cont" = On.FS or with asymmetrical hysteresis if the last output deactivation. Obviously, whether during the time delay caused by the compressor Cont = On.Fa. The control works in the following way : in the case of reverse protection function, the regulator request should stop, the output action, or heating (FunC=HEAt), it deactivates the output, when activation foreseen after time CPdt would be erased. the process value reaches [SP + HSEt] in case of symmetrical The function is not active programming CPdt =OFF. hysteresis, or [SP] in case of asymmetrical hysteresis and is then The led relative to 2rEG output blinks during the phases of output activated again when the process value goes below value [SP - activation delay, caused by Compressor Protection function. HSEt]. Vice versa, in case of direct action or cooling ("Func=CooL), it 4.5 - SINGLE ACTION PID CONTROL (1rEG) deactivates the output, when the process value reaches [SP - HSEt] All the ] parameters referring to PID control are contained in the in case of symmetrical hysteresis, or [SP] in case of asymmetrical group rEG. hysteresis and is activated again when the process value goes The Single Action PID control can be obtained by programming par."Cont" = Pid and works on the output 1rEG depending on the above value [SP + HSEt]. active Set Point SP, on the functioning mode "Func and on the instruments PID algorithm with two degree of freedom.
ELK 38
PAG. 5
In order to obtain good stability of the process variable, in the event of fast processes, the cycle time tcr1 has to have a low value with a very frequent intervention of the control output. In this case use of a solid state relay (SSR) is recommended for driving the actuator. The Single Action PID control algorithm foresees the setting of the following parameters : "Pb" Proportional Band "tcr1" Cycle time of the output 1rEG "Int" Integral Time "rS" Manual Reset (if Int =0 only) "dEr" Derivative Time FuOC - Fuzzy Overshoot Control This last parameter allows the variable overshoots at the start up of the process or at the changing of the Set Point to be avoided. Please remember that a low value on this parameter reduces the overshoot while a high value increase it.
The AUTO-TUNING function permits the calculation of thePID parameters by means of a FAST type tuning cycle and, at the end of this operation, the parameters are stored into the instruments memory and remain constant during control. The SELF-TUNING function (rule based "TUNE-IN") instead allows control monitoring and the continuous calculation of the parameters during control. Both functions automatically calculate the following parameters : "Pb" Proportional Band "tcr1" Cycle time of the output 1rEG "Int" Integral Time "dEr" Derivative Time FuOC - Fuzzy Overshoot Control and, for the Double Action PID control, also : tcr 2 Cycle time of the output 2rEG "Prat" - Ratio P 2rEG/ P 1rEG To activate the AUTO-TUNING function proceed as follows : 1) Program and activate the desired Set Point. 2) Program par. "Cont" =Pid. 3) Program par. "Func" according to the process to be controlled through output 1rEG. 4) Program an output as 2rEG if the instrument controls a plant with double action 5) Program par. "Auto" as: - "1 if auto-tuning is desired automatically, each time the instrument is switched on, on the condition that the process value is lower (with Func =HEAt) than [SP- |SP/2|] or higher (with Func =CooL) than [SP+ |SP/2|]. - "2" if auto-tuning is desired automatically, the next time the instrument is switched on, on the condition that the process value is lower (with Func =HEAt) than [SP- |SP/2|] or higher (with Func =CooL) than [SP+ |SP/2|], and once the tuning is finished, the par. Auto is automatically swapped to the OFF state - "3" - if manual auto-tuning is desired, by selecting par. tunE in the main menu or by correctly programming key U as USrb = tunE. In this case the auto-tuning starts without any control on the process value condition. It is recommended to use this option, starting the auto-tuning when the process value is as far as possible from the Set Point because, in order to feature the Auto-tuning FAST with its best performances , it is preferable to respect this condition. - "4" - if its desired to activate the autotuning automatically at the end of programmed Soft-Start cycle. The Autotuning will start at the condition that the process value is lower (with Func =HEAt) than [SP- |SP/2|] or higher (with Func =CooL) than [SP+ |SP/2|]. 6) Exit from the parameter programming. 7) Connect the instrument to the controlled plant. 8) Activate the Auto-tuning by selecting par. tunE in the main menu (or by correctly programming key U ). At this point the Auto-tuning function is activated and is indicated by the flashing led AT/ST. The regulator carries out several operations on the connected plant in order to calculate the most suitable PID parameters. If Auto = 1 or Auto = 2, and if, at the Auto-tuning start, the condition for the lower process value is not found (with Func =HEAt) than [SP- |SP/2|] or higher (with Func =CooL) than [SP+ |SP/2|], the display will show ErAt and the instrument will be swapped to normal control conditions according to the previously programmed parameters. To make the error ErAt disappear, swap the instrument to the OFF control (OFF) and then turn it to automatic control (rEG). The Auto-tuning cycle duration has been limited to 12 hours maximum. If Auto-tuning is not completed within 12 hours, the instrument will show "noAt" on the display. In case of probe error, the instrument automatically stops the cycle in progress. The values calculated by Auto-tuning are automatically stored in the instruments memory at the end of the correct PID parameters tuning. Note : The instrument is already programmed in our factory to carry out auto-tuning at every instrument switch on ("Auto" = 1).
1: Value FuOC OK 2: Value FuOC too high 3: Value FuOC too low 4.6 - DOUBLE ACTION PID CONTROL (1rEG - 2rEG) All the parameters referring to PID control are contained in the ] group rEG. The Double Action PID control is used to control plants where there is an element which causes a positive increase (ex. Heating) and an element which causes a negative increase (ex. Cooling). This type of control can be obtained when 2 outputs are programmed respectively as 1rEG and 2rEG and the par. Cont = Pid. The element causing a positive increase has to be connected to the output programmed as 1rEG while the element causing a negative increase has to be connected to the output programmed as 2rEG. The Double Action PID control works on the outputs 1rEG and 2rEG depending on the active Set Point SP and on the instruments PID algorithm with two degrees of freedom. In order to obtain good stability of the process variable, in case of fast processes, the cycle times tcr1 and tcr2 have to have a low value with a very frequent intervention of the control outputs. In this case use of solid state relays (SSR) to drive the actuators is recommended. The Double Action PID control algorithm needs the programming of the following parameters : "Pb" Proportional Band "tcr1" Cycle time of the output 1rEG tcr 2 Cycle time of the output 2rEG "Int" Integral Time "rS" Manual Reset (if Int =0 only) "dEr" Derivative Time FuOC - Fuzzy Overshoot Control "Prat" - Power Ratio or relation between power of the element controlled by output 2rEG and power of the element controlled by output 1rEG. If par. Prat = 0, the output 2rEG is disabled and the control behaves exactly as a single action PID controller, through output 1rEG. 4.7 - AUTOTUNING AND SELFTUNING FUNCTIONS All the parameters referring to the AUTO-TUNING and SELF] TUNING functions are contained in the group rEG. The AUTO-TUNING and SELF-TUNING functions permit the automatic tuning of the PID controller.
ELK 38
PAG. 6
To activate the SELF-TUNING function proceed as follows 1) Program and activate the desired Set Point. 2) Program par. "Cont" =Pid. 3) Program par. "Func" according to the process to be controlled through output 1rEG. 4) Program an output as 2rEG if the instrument controls a dualaction plant 5) Program par. "SELF" = yES 6) Exit from the parameter programming. 7) Connect the instrument to the controlled plant. 8) Activate Self-tuning selecting par. tunE in the main menu (or by correctly programming key U). When the Self-tuning function is active, the led AT/ST is permanently lit up and all the PID parameters ("Pb", "Int", "dEr", etc.) are no longer visualized. To stop the Auto-tuning cycle or deactivate the Self-tuning function select one of the control types : "rEG", "OPLO" or "OFF" from the menu SEL. If the instrument is switched off during Auto-tuning or with the Self-tuning function activated, these functions will remain activated the next time it is switched on. 4.8 - REACHING OF THE SET POINT AT CONTROLLED SPEED AND AUTOMATIC SWITCHING BETWEEN TWO SET POINTS (RISE RAMP, FALL RAMP AND DWELL TIME) All the parameters referring to the ramps functioning are contained ] in the group rEG. It is possible to reach the set point in a predetermined time (in any case longer than the time the plant would naturally need). This could be useful in those processes (heating or chemical treatments, etc.) where the set point has to be reached gradually, in a predetermined time. Once the instrument has reached the first Set Point (SP1) it is possible to have automatic switching to the second Set Point (SP2) after a set time, thus obtaining a simple automatic thermic cycle. These functions are available for all the programmable controls (PID single and double action, ON/OFF and Neutral Zone ON/OFF). The function is determined by the following parameters : "SLor" - Gradient of rise ramp (Process value < Set point) expressed in unit/minute "SLoF" - Gradient of fall ramp (Process value > Set point) expressed in unit/minute. "dur.t" Dwell time of Set Point SP1 before automatic switching to Set Point 2 SP2 (expressed in hrs. and min.). The functions are deactivated when the relative parameters are = InF. When the Set Point value is changed or at switch on, the instrument automatically determines which of the two values SLor or SLoF it has to use. Note: In case of PID control, if Auto-tuning is desired whilst the ramp function is active, this will not be carried out until the tuning cycle has been completed. It is therefore recommended that Auto-tuning be started avoiding activating the ramp function and, once the tuning is finished, deactivate Auto-tuning (Auto = OFF), program the desired ramps and, if it automatic tuning is desired, enable the Self-tuning function.
4.9 - SOFT-START FUNCTION All the parameters referring to the Soft -Start functioning are ] contained in the group rEG. The Soft-Start function only works through PID control and allows the limitation of control power when the instrument is switched on, for a programmable period of time. This is useful when the actuator, driven by the instrument, may be damaged excess power supplied when the application is not yet in the normal rating. (ex. for certain heating elements). The function depends on the following parameters : St.P Soft-Start power Sst Soft-Start time (expressed in hh.mm) The possible function modes are the following : 1) If both parameters are programmed with values other than OFF, when switched on the instrument gives an output power as programmed on par. St.P for the time programmed on par. SSt. Practically, the instrument works in manual condition and switches to automatic control at the elapsing of time SSt. It is advisable not to program a power St.P that is too high as the function is not deactivated when the automatic control power is found to be lower than the programmed one. 2) If par. St.P = OFF and a value is set on par. SSt , at the switch on, the power calculated by the PID controller is divided by the time SSt, in order to calculate a ramp. The output power starts from 0 and is progressively increased, depending on the calculated ramp, until the SSt time is reached or until the power overcomes the power calculated by the PID controller. To disable the Soft-Start function simply program par. Sst = OFF Whenever, a measurement errors occurs during the Soft-Start execution, the function is interrupted and the instrument gives an output power as programmed on par. OPE. If the measurement is restored, the Soft-Start is still deactivated. If its desired to activate the Autotuning with Soft-Start set par. Auto=4. The Autotuning will start automatically at the end of programmed Soft-Start cycle at the condition that the process value is lower (with Func =HEAt) than [SP- |SP/2|] or higher (with Func =CooL) than [SP+ |SP/2|]. 4.10 ALARM FUNCTIONING (AL1)
4.10.1 ALARM OUTPUT CONFIGURATION The alarm is depending on the process value (AL1) and before to set his functioning its necessary to establish to which output the alarm has to correspond to. First of all its necessary to configure, in the parameters group ] Out, the parameters relative to the outputs required as alarm (O1F , O2F) programming the parameter relative to the desired output as follows : = ALno if the alarm output has to be ON when the alarm is active, while its OFF when the alarm is not active = ALnc if the alarm output has to be ON when the alarm is not active, while its OFF when the alarm is active = ALni if the alarm output has to be ON when the alarm is not active, while it is OFF when the alarm is active but with reverse led indication (led ON= alarm OFF). ] Have now access at the group AL1, and program on par. OAL1 , to which output the alarm signal has to be sent. The alarm functioning is instead defined by parameters : "AL1t " ALARM TYPE "Ab1" ALARM CONFIGURATION AL1 ALARM THRESHOLD AL1L LOW ALARM THRESHOLD (for band alarm) OR MINIMUM SET OF AL1 ALARM THRESHOLD (for low or high alarm) AL1H - HIGH ALARM THRESHOLD (for band alarm) OR MAXIMUM SET OF AL1 ALARM THRESHOLD (for low or high alarm) HAL1 - ALARM HYSTERESIS Examples with starts from values lower than SP and with decreasing AL1d ALARM ACTIVATION DELAY (in sec.) of SP.
ELK 38
PAG. 7
IN
THE
EVENT
OF
"AL1t" ALARM TYPE : the alarm output can behave in six different ways. LoAb = ABSOLUTE LOW ALARM: The alarm is activated when the process value goes below the alarm threshold set on parameter "AL1. With this mode is possible to program the minimum and the maximum set of AL1 by AL1L and AL1H parameters.
HiAb = ABSOLUTE HIGH ALARM: The alarm is activated when the process value goes higher than the alarm threshold set on parameter "AL1". With this mode is possible to program the minimum and the maximum set of AL1 by AL1L and AL1H parameters.
LHAb = ABSOLUTE BAND ALARM: The alarm is activated when the process value goes under the alarm threshold set on parameter "AL1L" or goes higher than the alarm threshold set on parameter "AL1H".
ALARM DELAY: the alarm output may behave in two different ways depending on the value added to par. Ab1. +0 = ALARM NOT DELAYED: The alarm is immediately activated when the alarm condition occurs. +2 = ALARM DELAYED: When the alarm condition occurs, delay counting begins, as programmed on par. AL1d (expressed in sec.) and the alarm will be activated only after the elapsing of that time. ALARM LATCH: : the alarm output may behave in two different ways depending on the value added to par. Ab1. + 0 = ALARM NOT LATCHED: The alarm remains active in alarm conditions only. + 4 = ALARM LATCHED: The alarm is active in alarm conditions and remains active even when these conditions no longer exist, until the correctly programmed key U, (USrb=Aac) has been pushed.
LodE = DEVIATION LOW ALARM: The alarm is activated when the process value goes below the value [SP + AL1]. With this mode is possible to program the minimum and the maximum set of AL1 by AL1L and AL1H parameters.
ALARM AKNOWLEDGEMENT: : the alarm output may behave in two different ways depending on the value added to par. Ab1. + 0 = ALARM NOT AKNOWLEDGED: The alarm always remains active in alarm conditions. + 8 = ALARM AKNOWLEDGED: The alarm is active in alarm HidE = DEVIATION HIGH ALARM: The alarm is activated when the conditions and can be deactivated by key U if properly process value goes above the value [SP + AL1]. With this mode is programmed (USrb=ASi), and also if alarm conditions still exist. possible to program the minimum and the maximum set of AL1 "AL1i" - ALARM ACTIVATION IN CASE OF MEASUREMENT by AL1L and AL1H parameters. ERROR: This allows one to establish how the alarm have behave in the event of a measurement error (yES=alarm active; no=alarm deactivated). 4.10.2 - ALARMS HYSTERESIS LHdE = DEVIATION BAND ALARM: The alarm is activated when The alarm function depend s on alarm hysteresis (par. "HAL1"), the process value goes below the value [SP + AL1L] or goes above which works in asymmetric way. In the event of low alarm, the alarm will be activated when the than the value [SP + AL1H] process value goes below the alarm threshold value and will be deactivated when it goes above the alarm threshold + "HAL1" ; in case of high alarm, the alarm will be activated when the process value goes above the alarm threshold value and will be deactivated when it goes below the alarm threshold - "HAL1". "Ab1" - ALARM CONFIGURATION: This parameter can assume a value between 0 and 15. The number to be set, which will correspond to the function desired, is obtained by adding the values reported in the following descriptions : ALARM BEHAVIOUR AT SWITCH ON: the alarm output may behave in two different ways, depending on the value added to par. Ab1. +0 = NORMAL BEHAVIOUR: The alarm is always activated when there are alarm conditions. +1 = ALARM NOT ACTIVATED AT SWITCH ON: If, when switched For the band alarms, the example of the low alarm is applicable to on, the instrument is in alarm condition, the alarm is not activated. It the low threshold ("AL1L") while the example of the high alarm is will be activated only when the process value is in non-alarm applicable to the high threshold ("AL1H"). conditions and then back in alarm conditions.
ELK 38
PAG. 8
4.11 - LOOP BREAK ALARM FUNCTION All the parameters referring to the Loop Break alarm function are ] contained in the group LbA. The Loop Break alarm is available on all the instruments, which intervenes when, for any reason (short-circuit of a thermocouple, thermocouple inversion, load interruption), the loop control is interrupted. First of all, it is necessary to establish to which output the alarm has to correspond. To do this it is necessary to set the parameter relative to the output ] to be used (O1F , O2F) in the group Out, programming the parameter as : = ALno if the alarm output has to be ON when the alarm is active while it is OFF when the alarm is not active. = ALnc if the alarm output has to be ON when the alarm is not active while it is OFF when the alarm is active. = ALni if the alarm output has to be ON when the alarm is not active, while it is OFF when the alarm is active but with reverse led indication (led ON= alarm OFF). ] Enter group LbA and program which output the alarm signal has to be addressed to on par. OLbA,. The Loop Break alarm is activated if the output power remains at the 100% of the value for the time programmed on par. "LbAt" (expressed in sec.). To avoid false alarms, the value of this parameter has to be set considering the time the plant takes to reach the Set point when the measured value is a long distance from it (for example at the plant start-up). On alarm intervention, the instrument visualizes the message LbA and behaves as in the case of a measurement error giving a power output as programmed on par. OPE (programmable in the ] group InP). To restore normal functioning after the alarm, select the control mode OFF and then re-program the automatic control (rEG) after checking the correct functioning of probe and actuator. To exclude the Loop Break alarm, set OLbA = OFF. 4.12 - FUNCTIONING OF KEY U The function of key U can be set through par. USrb contained in ] the group PAn. The parameter can be programmed as : = noF : no function = tunE : Pushing the key for 1 sec. at least, it is possible to activate/deactivate Auto-tuning or Self-tuning = OPLO : Pushing the key for 1 sec. at least, it is possible to swap from automatic control (rEG) to manual one (OPLO) and vice versa. = Aac : Pushing the key for 1 sec. at least, it is possible to acknowledge the alarm. (see par. 4.10.1) = ASi : Pushing the key for 1 sec. at least, it is possible to acknowledge an active alarm (see par. 4.10.1) = CHSP : Pushing the key for 1 sec. at least, it is possible to select one of the 4 pre-programmed Set Points on rotation. = OFF : Pushing the key for 1 sec. at least, it is possible to swap from automatic control (rEG) to OFF control (OFF) and vice versa. 4.13 - PARAMETERS CONFIGURATION BY KEY01 The instrument is equipped with a connector that allows the transfer from and toward the instrument of the functioning parameters through the device ELCO KEY01 with 5 poles connector. This device its mainly useable for the serial programming of the instruments which need to have the same parameters configuration or to keep a copy of the programming of an instrument and allow its rapid retransmission. To use the device KEY01 its necessary that the device or instrument are being supplied. Instrument supplied and device not supplied
To transfer the configuration of an instrument into the device (UPLOAD) it is necessary to proceed in the following way: 1) position both dip switch of KEY 01 in the OFF mode. 2) connect the device to the instrument ELK plugging the special connector. 3) verify that the instrument or the device are supplied 4) observe the indication led on the device KEY 01: if it results green this means that a configuration is already loaded on the device while if it results green blinking or red blinking this means that it has not been loaded any valid configuration on the device . 5) press the button placed on the device. 6) observe the indication led : after having pressed the button, the led becomes red and therefore, at the end of the data transfer, it becomes green. 7) now it is possible to disconnect the device. To transfer the configuration loaded on the device onto an instrument of the same family (DOWNLOAD), it is necessary to proceed in the following way: 1) position both dip switch of KEY 01 in the ON mode. 2) connect the device to an instrument ELK having the same features of the one from which has been downloaded the desired configuration, plugging the special connector. 3) verify that the instrument or the device are supplied 4) observe the indication led on the device KEY 01: it has to result green, because if the led results green blinking or red blinking, this means that on the device it has not been downloaded any valid configuration and therefore its useless to continue. 5) if the les results green, press the button placed on the device. 6) observe the indication led : after having pressed the button, the led becomes red and therefore, at the end of the data transfer, it becomes green. 7) now it is possible to disconnect the device. For additional info, please have a look at the KEY01 instruction manual. 5 - PROGRAMMABLE PARAMETERS Here following are described all the parameters available on the instrument. Some of them could be not present or because they are depending on the type of instrument or because they are automatically disabled as unnecessary. 5.1 - PARAMETERS TABLE Group SP (parameters relative to the Set Point) Par. Description Range 1 nSP Number of the 14 programmable Set point 2 SPAt Active Set point 1 nSP 3 SP1 Set Point 1 SPLL SPHL 4 SP2 Set Point 2 SPLL SPHL
Def. 1
Note
1 0 0
ELK 38
PAG. 9
5 SP3 Set Point 3 SPLL SPHL 0 6 SP4 Set Point 4 SPLL SPHL 0 7 SPLL Low Set Point -1999 SPHL -1999 8 SPHL High Set Point SPLL 9999 9999 Group InP (parameters relative to the measure input) Par. Description Range Def. 9 SEnS Probe type input C : J J / CrAL / S / Ir.J / Ir.CA / Pt1 / 0.50 / 0.60 / 12.60 input E : Ptc J / CrAL / S / Ir.J / Ir.CA / Ptc / ntc / 0.50 / 0.60 / 12.60 input I : 4.20 0.20 / 4.20 input V : 0.10 0.1 / 0.5 / 1.5 / 0.10 / 2.10 10 SSC Low scale limit in case -1999 FSC 0 of input with V / I signals 11 FSC High scale limit in case SSC 9999 0 of input with V / I signals 12 dP Number of decimal Pt1 / Ptc / ntc: 0 figures 0/1 norm sig.: 03 / C F C 13 Unit Temperature unit of measurement 14 FiL Input digital filter 0FF 20.0 1.0 sec. 15 OFSt Measuring Offset -1999 9999 0 16 rot Rotation of the 0.000 2.000 1.000 measuring straight line 17 InE OPE functioning in Our / Or / Ur OUr case of measuring error 18 OPE Output power in case of -100 100 0 measuring error % Group Out (parameters relative to the outputs) Par. Description Range Def. 19 O1F Functioning of output 1 1.rEG / 2.rEG 1.rEG ALno / ALnc ALni / OFF 20 O2F Functioning of output 2 1.rEG / 2.rEG ALno ALno / ALnc ALni / OFF Group AL1 (parameters relative to alarm AL1) Par. Description Range Def. 21 OAL1 Output where alarm Out1 / Out2 / Out2 AL1 is addressed OFF 22 AL1t Alarm AL1 type LoAb / HiAb LoAb LHAb / LodE HidE / LHdE 23 Ab1 Alarm AL1 functioning 0 15 0 24 AL1 Alarm AL1 threshold AL1L AL1H 0 25 AL1L Low threshold band -1999 AL1H -1999 alarm AL1 or Minimum set alarm AL1 for high or low alarm 26 AL1H High threshold band AL1L 9999 9999 alarm AL1 or Maximum set alarm AL1 for high or low alarm 27 HAL1 Alarm AL1 hysteresis OFF 9999 1
Note
Note
Note
OFF 28 AL1d Activation delay of OFF 9999 sec. alarm AL1 29 AL1i Alarm AL1 activation in no / yES no case of measuring error Group LbA (parameters relative to Loop Break Alarm) Par. Description Range Def. 30 OLbA Output where alarm Out1 / Out2 / OFF LbA is addressed OFF OFF 31 LbAt Time necessary to OFF 9999 sec. activate alarm LbA Group rEG (parameters relative to the control) Par. Description Range Def. 32 Cont Control type Pid / On.FA Pid On.FS / nr 33 Func Functioning mode HEAt / CooL HEAt output 1rEg 34 HSEt Hysteresis of ON/OFF 0 9999 1 control 0 35 CPdt Compressor Protection OFF 9999 time for 2.rEG sec. 36 Auto Autotuning Fast enable OFF / 1 1/2/3/4 37 SELF Selftuning enable no / yES no 0 9999 50 38 Pb Proportional band 39 Int Integral time OFF 9999 200 sec. 40 dEr Derivative time OFF 9999 50 sec. 41 FuOc Fuzzy overshoot control 0.00 2.00 0,5 42 tcr1 Cycle time of output 0.1 130.0 20,0 1rEg sec. 43 Prat Power ratio 2rEg / 1rEg 0.01 99.99 1.00 0.1 130.0 10.0 44 tcr2 Cycle time of 2rEg sec. 45 rS Manual reset -100.0100.0 0.0 % 46 SLor Gradient of rise ramp 0.00 99.99 InF / InF unit/min. 47 dur.t Duration time 0.00 99.59 InF / InF hrs.-min. 48 SLoF Gradient of fall ramp 0.00 99.99 InF / InF unit / min. 49 St.P Soft-Start power OFF / OFF -100 100 % OFF / OFF 50 SSt Soft-Start time 0.17.59 / InF hrs.-min. Group PAn (parameters relative to the user interface) Par. Description Range Def. 51 USrb Functioning of key U noF / tunE / noF OPLO / Aac / ASi / CHSP / OFF 52 diSP Variable visualized on dEF / Pou / dEF the display SP.F / SP.o / AL1 53 AdE Shift value for the shift OFF...9999 2 index functioning 54 Edit Fast programming of SE / AE / SAE active Set Point and SAE / SAnE alarms 5.2 - PARAMETERS DESCRIPTION
Note
Note
Note
GROUP SP (PARAMETERS RELATIVE TO THE SET POINT): These allow the setting of the control Sets and the Sets function modes.
ELK 38
PAG. 10
nSP NUMBER OF PROGRAMMABLE SET POINTS: This allows definition of the number of Set Points which will be programmed and stored (from 1 to 4). SPAt ACTIVE SET POINT : If more than one Set Point is stored, this allows selection of the active Set Point. SP1 - SET POINT 1: Value of the Set Point n. 1 SP2 - SET POINT 2: Value of the Set Point n. 2 (it appears if nSP >2 only) SP3 - SET POINT 3: Value of the Set Point n. 3 (it appears if nSP >3 only) SP4 - SET POINT 4: Value of the Set Point n. 4 (it appears if nSP =4 only) SPLL LOW SET POINT: Lower value programmable as Set Point SPHL HIGH SET POINT : Higher value programmable as Set Point
= Or : the condition occurs in case of over-range or probe breakage = Ur : the condition occurs in case of under-range or probe breakage = Our : the condition occurs in case of over-range or under-range or probe breakage OPE OUTPUT POWER IN CASE OF MEASUREMENT ERROR: This permits setting of the power that the instrument has to give as output in case of measurement error. For the ON/OFF regulators the power is calculated considering a cycle time equal to 20 sec.
]
GROUP Out (PARAMETERS RELATIVE TO THE OUTPUTS): They permit to program the outputs functioning. O1F FUNCTIONING OF OUTPUT OUT 1: This defines the functioning of output OUT 1 as: control output 1 (1.rEG), control output 2 (2.rEG), alarm output as normally open (ALno), output alarm normally closed (ALnc), output alarm normally closed with led ] GROUP InP (PARAMETERS RELATIVE TO THE INPUTS): reverse indication (ALni), output not used (OFF). These permit the definition of visualization modes of the O2F - FUNCTIONING OF OUTPUT OUT 2: Similar to O1F but referring to output OUT2. variable measured by the probe. SEnS PROBE TYPE: Depending on model, it permits to select the type of probe : - thermocouples: J (J), K (CrAL), S (S) or ELCO infrared sensors IRS serie with J (Ir.J) or K (Ir.CA) linearization. - thermoresistances: Pt100 IEC (Pt1) - thermistors PTC KTY81-121 (Ptc) or NTC 103AT-2 (ntc) - normalized signals in current : 0..20 mA (0.20) or 4..20 mA (4.20) - normalized signals in tension: 0..50 mV (0.50), 0..60 mV (0.60), 12..60 mV (12.60), 0..1 V (0.1), 0..5 V (0.5), 1..5 V (1.5), 0..10 V (0.10) or 2..10 V (2.10). SSC LOW SCALE LIMIT IN EVENT OF INPUT WITH V/I SIGNALS : This is the value the instrument has to visualise when the minimum value that can be measured on the scale (0/4 mA, 0/12 mV, 0/1 V or 0/2 V) is present at the output. FSC HIGH SCALE LIMIT IN EVENT OF INPUT WITH V/I SIGNALS : This is the value the instrument has to visualise when the maximum value that can be measured on the scale (20 mA, 50 mV, 60 mV, 1 V, 5 V or 10 V) is present at the input. dP NUMBER OF DECIMAL FIGURES: It permits to decide if the measuring resolution has to be 1 (0), 0.1 (1), 0.01 (2), 0.001 (3). In case of Pt100, PTC and NTC temperature probes the allowed resolutions are 1 (0) and 0.1 (1). Unit TEMPERTURE UNIT OF MEASUREMENT : When the temperature is measured by temperature probes, this parameter permits definition if the visualisation is expressed as degree Centigrade ( or Fahrenheit ( C) F). Filt INPUT DIGITAL FILTER : This permits programming of the constant of time of the software filter referring to the measured input value (in sec.) in order to reduce noise sensitivity (increasing the time of reading). OFSt MEASURING OFFSET: Positive or negative Offset which is added to the value measured by the probe. rot ROTATION OF THE MEASURING STRAIGHT LINE: In this way the offset programmed on par. OFSt is not constant for all measurements. By programming rot=1.000, the value OFSt is simply added to the value read by the probe before visualisation and it remains constant for all the measurements. If instead one does not want the programmed offset to be constant for all the measurements, it is possible to carry out calibration on two desired values. In this case, to define the values to be programmed on par. OFSt and rot, it is necessary to enforce the following formulae : rot = (D2-D1) / (M2-M1) OFSt = D2 - (rot x M2) where: M1 =measured value 1; D1 = visualisation value when the instrument measures M1 M2 =measured value. 2; D2 = visualisation value when the instrument measures M2 It then follows that the instrument will visualise : DV = MV x rot + OFSt where: DV = visualised value; MV= measured value InE OPE FUNCTIONING IN CASE OF MEASUREMENT ERROR: This defines the error conditions of the input allowing the instrument to give the power programmed on par. OPE as output. The possibilities are : GROUP AL1 (PARAMETERS RELATIVE TO ALARM AL1): These permit setting of the process alarm AL1 function. OAL1 OUTPUT WHERE ALARM AL1 IS ADDRESSED: It defines to which output the alarm AL1 has to be addressed. AL1t ALARM AL1 TYPE: permits the choice of behaviour for alarm A1, by 6 different selections: = LoAb ABSOLUTE LOW ALARM : The alarm is activated when the process value goes below the alarm threshold set on parameter "AL1". = HiAb - ABSOLUTE HIGH ALARM: The alarm is activated when the process value goes above the alarm threshold set on parameter "AL1". = LHAb - ABSOLUTE BAND ALARM: The alarm is activated when the process value goes below the alarm threshold set on parameter "AL1L" or goes higher than alarm set on parameter "AL1H". = LodE DEVIATION LOW ALARM: The alarm is activated when the process value goes below the value [SP + AL1] = HidE DEVIATION HIGH ALARM: The alarm is activated when the process value goes above the value [SP + AL1] = LHdE DEVIATION BAND ALARM: The alarm is activated when the process value goes below the value [SP + AL1L] or goes above the value [SP + AL1H] Ab1 ALARM AL1 FUNCTION: This permits definition of alarm AL1 functions, by entering a number between 0 and 15. The number to be programmed, that corresponds to the desired function, is obtained adding the values reported in the following description : ALARM BEHAVIOUR AT SWITCH ON: +0 = NORMAL BEHAVIOUR: The alarm is always activated when there are alarm conditions. +1 = ALARM NOT ACTIVATED AT SWITCH ON: If, at switch on, the instrument is in alarm condition, the alarm is not activated. It will be activated only when the process value goes beyond and then returns to alarm conditions. ALARM DELAY: +0 = ALARM NOT DELAYED: The alarm is immediately activated when the alarm condition occurs. +2 = ALARM DELAYED: When the alarm condition occurs, delay counting starts as programmed on par. ALnd (expressed in sec.) and the alarm will be activated only after this time has elapsed. ALARM LATCH: : + 0 = ALARM NOT LATCHED: The alarm remains active in alarm conditions only. + 4 = ALARM LATCHED: The alarm is active in alarm conditions and remains active even if these conditions no longer exist, until the correctly programmed key U (USrb=Aac) has been pushed ALARM AKNOWLEDGEMENT: : + 0 = ALARM NOT AKNOWLEDGED: The alarm remains always active in alarm conditions. + 8 = ALARM AKNOWLEDGED: The alarm is active in alarm conditions and can be deactivated through key U if properly programmed (USrb=ASi), also if alarm conditions still exist. AL1 ALARM AL1 THRESHOLD : Alarm AL1 threshold for low and high alarms.
]
ELK 38
PAG. 11
AL1L LOW ALARM AL1 : Alarm AL1 low threshold when the alarm is a band type or minimum set of AL1 alarm threshold when the alarm is low or high type. AL1H HIGH ALARM AL1: Alarm AL1 high threshold when the alarm is a band type or maximum set of AL1 alarm threshold when the alarm is low or high type. HAL1 - ALARM AL1 HYSTERESIS: Asymmetrical semi-band relative to alarm AL1 threshold which defines the deactivation value of alarm AL1. AL1d ACTIVATION DELAY OF ALARM AL1: This permits definition of alarm delay activation AL1 when the delay function on par. Ab1 is activated. AL1i ALARM AL1 ACTIVATION IN CASE OF MEASUREMENT ERROR: This permits a definition of measurement error conditions, i.e whether the alarm has to be active ("yES") or not ("no"). GROUP LbA (PARAMETERS RELATIVE TO THE LOOP BREAK ALARM): this contains the parameters relative to the Loop Break alarm (control loop interruption), which intervenes when, for any reason (short-circuit of a thermocouple, load interruption, etc) the control loop is interrupted. OLbA OUTPUT WHERE THE LOOP BREAK ALARM IS ADDRESSED: This defines to which output the LOOP BREAK alarm has to be addressed. LbAt TIME NECESSARY TO ACTIVATE THE LOOP BREAK ALARM : Delay time to the intervention of the Loop Break alarm. The alarm intervenes when the output power remains at 100% for the time programmed on this parameter (in sec.)
]
GROUP rEG (PARAMETERS RELATIVE TO THE CONTROL): this contains the parameters relative to control functions. Cont CONTROL TYPE: This permits selection of one of the possible control modes offered by the instrument : PID (Pid), ON/OFF with asymmetrical hysteresis (On.FA), ON/OFF with symmetrical hysteresis (On.FS), Neutral Zone ON/OFF (nr). Func FUNCTIONING MODE OUTPUT 1rEG: this permits one to decide whether the control output 1rEG has to carry out a reverse action, as for example a Heating process ("HEAt") or a direct action, as for example a Cooling process ("CooL"). HSEt ON/OFF CONTROL HYSTERESIS: Semi-band relative to the Set Point which defines the activation and deactivation values of the control output/s in case of ON/OFF control (On.FA, On.FS, nr). CPdt COMPRESSOR PROTECTION DELAY TIME: The delay time is counted starting from the last 2rEG output switch off , when its used as Neutral zone control mode, during which the output is kept in off state. The output will be switched on when the temperature regulator requires it at this time is elapsed. The function in deactivated programming "CPdt" = OFF. Auto AUTO-TUNING FAST ENABLE : this parameter allows one to decide how Auto-tuning has to be carried out. The possible selections are : = 1 if auto-tuning is desired automatically, each time the instrument is switched on, on the condition that the process value is lower (with Func =HEAt) than [SP- |SP/2|] or higher (with Func =CooL) than [SP+ |SP/2|]. = 2 if auto-tuning is desired automatically, the next time the instrument is switched on, on the condition that the process value is lower (with Func =HEAt) than [SP- |SP/2|] or higher (with Func =CooL) than [SP+ |SP/2|], and once the tuning is finished, the par. Auto is automatically swapped to the OFF state = 3 - if manual auto-tuning is desired, by selecting par. tunE in the main menu or by correctly programming key U as USrb = tunE. In this case the auto-tuning starts without any control on the process value condition. It is recommended to use this option, starting the auto-tuning when the process value is as far as possible from the Set Point because, in order to feature the Auto-tuning FAST with its best performances , it is preferable to respect this condition. = 4 - if its desired to activate the autotuning automatically at the end of programmed Soft-Start cycle. The Autotuning will start at the GROUP ]PAn (PARAMETERS RELATIVE TO THE USER condition that the process value is lower (with Func =HEAt) than INTERFACE) : This contains the parameters relative to the key [SP- |SP/2|] or higher (with Func =CooL) than [SP+ |SP/2|]. U and display functions. = OFF - Autotuning disabled.
When its occurring an Autotuning cycle, led AT blinks. SELF SELF-TUNING ENABLE: Parameter used to enable (yES) or disable (no) the Self-tuning function. Once the function has been enabled, the Self-tuning has to be started by selecting item tunE, in the main menu, or through key U properly programmed (USrb = tunE).When the Self-tuning function is active, led AT is permanently lit, and all the PID parameters ("Pb", "Int", "dEr", ecc.) are no longer visualised. Pb PROPORTIONAL BAND: Width of the band around the Set Point within which the proportional control is performed. Int INTEGRAL TIME: Integral time to be programmed in the PID algorithm, expressed in sec. dEr DERIVATIVE TIME: : Derivative time to be programmed in the PID algorithm, expressed in sec. FuOc - FUZZY OVERSHOOT CONTROL: Parameter that permits the elimination of the variable over-shoots at the start up of the process or at the changing of the Set Point. A low value of this parameter reduces the overshoot while a high value increase it. tcr1 CYCLE TIME OF OUTPUT 1rEG : Cycle time of output 1rEG with PID control mode, expressed in sec.. Prat POWER RATIO 2rEG / 1rEG : Parameter where it is possible to program the power ratio between the element controlled by output 2rEG (ex.Cooling) and the element controlled by output 1rEG (ex. Heating) in case of PID double action control. tcr2 - CYCLE TIME OF OUTPUT 2rEG : Cycle time of output 2rEG with PID double action control mode, expressed in sec.. rS - MANUAL RESET: Power Offset added to the power increase of the proportional term, in order to eliminate the error when it is not present the integral value. This parameter is only visualised when Int =0. Parameters relative to the ramps, allowing the Set Point to be reached in a predetermined time. Furthermore, once the first Set (SP1) has been reached, it is possible to have automatic switching to the second Set (SP2) after a programmable time, thus obtaining a simple thermal cycle (functions available for all the control types) SLor GRADIENT OF RISE RAMP: Gradient of rise ramp to be carried out when the process value is lower than the active Set Point, expressed in unit/minute. Programming the parameter = InF the ramp is not active. dur.t - DWELL TIME: Dwell time of the Set Point SP1 before the automatic switching to SP2 (expressed in hrs. and min.) Using this parameter, once the first Set (SP1) has been reached, it is possible to have automatic switching to the second Set (SP2) after a programmable time, thus obtaining a simple thermal cycle. Programming the parameter = InF the function is not active. SLoF - GRADIENT OF FALL RAMP: Gradient of fall ramp to be carried out when the process value is higher than the active Set Point, expressed in unit/minute. Programming the parameter = InF the ramp is not active. Parameters relative to the Soft-Start function, which allows limitation of control power, when the instrument is switched on, for a predetermined time. This function is only available for PID control. St.P - SOFT START POWER: If parameter SSt is programmed with a value other than OFF, this is the power given as output at the instrument switch on, for the time SSt. Practically speaking, the instrument works in manual condition and switches to automatic control at the elapsing of time SSt. If instead par. St.P = OFF and a value is set on par. SSt at switch on, the power calculated by the PID controller is divided by the time SSt, in order to calculate a ramp. The output power starts from 0 and is progressively increased, according to the calculated ramp, until the time SSt is reached or until the power overcomes the power calculated by the PID controller. SSt - SOFT START TIME (for PID control only): Duration time in hours and min. of the Soft-Start described on pa. St.P. To disable the Soft-Start function set par. SSt = OFF.
ELK 38
PAG. 12
Usrb KEY U FUNCTION : Decides which function is associated to key U. The possible selections are : = noF : no function = tunE : Pushing the key for 1 sec. at least, it is possible to activate/deactivate the Auto-tuning or the Self-tuning = OPLO : Pushing the key for 1 sec. at least, it is possible to swap from the automatic control (rEG) to the manual one (OPLO) and vice versa. = Aac : Pushing the key for 1 sec. at least, it is possible to acknowledge the alarm. = ASi : Pushing the key for 1 sec. at least, it is possible to acknowledge an active alarm = CHSP : Pushing the key for 1 sec. at least, it is possible to select one of the 4 pre-programmed Set Points on rotation. = OFF : Pushing the key for 1 sec. at least, it is possible to swap from the automatic control (rEG) to the OFF control (OFF) and vice versa. diSP - VARIABLE VISUALISED ON THE DISPLAY: Parameter through which it is possible to decide what is visualised on the display : the process variable (= dEF), the control power (= Pou), the active Set Point (= SP.F), the Set Point active when there are ramps (= SP.o) or the alarm threshold AL1 (= AL1). AdE - SHIFT VALUE FOR THE SHIFT INDEX FUNCTIONING: This allows one to decide the functioning mode of the 3 led shift indexes. The lighting of the green led = indicates that the process value is within the range [SP+AdE ... SP-AdE], the lighting of the red led - indicates that the process value is lower than the value [SP-AdE] and the lighting of the red led +indicates that the process value is higher than the value [SP+AdE]. Edit - FAST PROGRAMMING OF ACTIVE SET POINT AND ALARMS: This decides which are the Sets that can be programmed by the fast procedure. The parameter can be programmed as : =SE: The active Set Point can be modified while the alarm thresholds cannot be modified =AE :The active Set Point cannot be modified while the alarm thresholds can be modified =SAE: If the active Set Point or the alarm thresholds can be modified =SAnE: If the active Set Point or the alarm thresholds cannot be modified 6 - PROBLEMS, MAINTENANCE AND GUARANTEE 6.1 - ERROR SIGNALLING Error Reason Probe interrupted ---The measured variable uuuu is under the probes limits (under-range) The measured variable oooo is over the probes limits (over-range) Auto-tuning not ErAt possible because the process value is higher (with Func =HEAt) than [SP- |SP/2|] or lower (with Func =CooL) than [SP+ |SP/2|]. Auto-tuning not finished noAt within 12 hours
6.2 - CLEANING We recommend cleaning of the instrument with a slightly wet cloth using water and not abrasive cleaners or solvents which may damage the instrument. 6.3 - GUARANTEE AND REPAIRS The instrument is under warranty against manufacturing flaws or faulty material, that are found within 12 months from delivery date. The guarantee is limited to repairs or to the replacement of the instrument. The eventual opening of the housing, the violation of the instrument or the improper use and installation of the product will bring about the immediate withdrawal of the warrantys effects. In the event of a faulty instrument, either within the period of warranty, or further to its expiry, please contact our sales department to obtain authorisation for sending the instrument to our company. The faulty product must be shipped to ELCO with a detailed description of the faults found, without any fees or charge for ELCO, except in the event of alternative agreements. 7 - TECHNICAL DATA 7.1 ELECTRICAL DATA Power supply: 12 VAC/VDC, 24, 115, 230 VAC, 24 VAC/VDC, 100.. 240 VAC +/- 10% Frequency AC: 50/60 Hz Power consumption: 4 VA approx. Input/s: 1 input for temperature probes: tc J,K,S ; infrared sensors ELCO IRS J e K; RTD Pt 100 IEC; PTC KTY 81-121 (990 @ 25 NTC 103AT-2 (10K @ 25 or mV signals 0...50 mV, 0...60 C); C) mV, 12 ...60 mV or normalized signals 0/4...20 mA, 0..1 V, 0/1...5 V , 0/2...10 V. Normalized signals input impedance: 0/4..20 mA: 51 ; mV and V: 1 M Output/s: Up to 2 outputs. Relay SPDT (8 A-AC1, 3 A-AC3 / 250 VAC) ; or in tension to drive SSR (8mA/ 8VDC). Auxiliary supply output: 12 VDC / 20 mA Max. Electrical life for relay outputs: 100000 operat. Installation category: II Measurement category: I Protection class against electric shock: Class II for Front panel Insulation: Reinforced insulation between the low voltage part (power supply 115 or 230 V and relay outputs) and front panel; Reinforced insulation between the low voltage section (Supply 115 or 230 V and relay outputs) and the extra low voltage section (input, SSR outputs); Reinforced between power supply and relay; No insulation between supply 12 V and input. No insulation between input and SSR outputs. 7.2 MECHANICAL DATA Housing: Self-extinguishing plastic, UL 94 V0 Dimensions: 33 x 75 mm, depth 64 mm Weight: 180 g approx. Mounting: Flush in panel in 29 x 71 mm hole 2 Connections: 2,5 mm screw terminals block Degree of front panel protection : IP 65 mounted in panel with gasket Pollution situation: 2 Operating temperature: 0 ... 50 C Operating humidity: 30 ... 95 RH% without condensation Storage temperature: -10 ... +60 C
Action Verify the correct connection between probe and instrument and then verify the correct functioning of the probe
LbA
Possible anomaly of the EEPROM memory In error conditions, the instrument provides an output power as programmed on par OPE and activates the desired alarms, if the 7.3 MECHANICAL DIMENSIONS, PANEL CUT-OUT AND MOUNTING [mm] relative parameters ALni have been programmed = yES. ErEP
Swap the instrument to OFF control (OFF) and then to automatic control (rEG) in order to make the error message disappear. Once the error has been found, try to repeat the auto-tuning. Check the functioning of probe and actuator and try to repeat the autotuning. Check the working of probe and actuator and swap the instrument to (rEG) control Push key P
ELK 38
PAG. 13
ELK
PTC (KTY81-121) SEnS = Ptc NTC (103-AT2) SEnS = ntc 0..20 mA SEnS = 0.20 4..20 mA SEnS = 4.20 0 ... 50 mV SEnS = 0.50 0 ... 60 mV SEnS = 0.60 12 ... 60 mV SEnS = 12.60 0 ... 1 V SEnS = 0.1 0 ... 5 V SEnS = 0.5 1 ... 5 V SEnS = 1.5 0 ... 10 V SEnS = 0.10 2 ... 10 V SEnS = 2.10
-55 ... 150 C -67 ... 302 F -50 ... 110 C -58 ... 230 F -1999 ... 9999
-55.0 ... 150.0 C -67.0 ...302.0 F -50.0 ... 110.0 C -58.0 ... 230.0 F -199.9 ... 999.9 -19.99 ... 99.99 -1.999 ... 9.999 -199.9 ... 999.9 -19.99 ... 99.99 -1.999 ... 9.999 -199.9 ... 999.9 -19.99 ... 99.99 -1.999 ... 9.999 -199.9 ... 999.9 -19.99 ... 99.99 -1.999 ... 9.999 -199.9 ... 999.9 -19.99 ... 99.99 -1.999 ... 9.999 -199.9 ... 999.9 -19.99 ... 99.99 -1.999 ... 9.999 -199.9 ... 999.9 -19.99 ... 99.99 -1.999 ... 9.999 -199.9 ... 999.9 -19.99 ... 99.99 -1.999 ... 9.999 -199.9 ... 999.9 -19.99 ... 99.99 -1.999 ... 9.999 -199.9 ... 999.9 -19.99 ... 99.99 -1.999 ... 9.999
7.6 INSTRUMENT ORDERING CODE ELK38 a b c d ee a : POWER SUPPLY 12 = 12 VAC/VDC 24 = 24 VAC/VDC 240 = 100... 240 VAC b : INPUT C = thermocouples (J, K, S, I.R), mV, thermoresistances (Pt100) 7.4 FUNCTIONAL FEATURES E = thermocouples (J, K, S, I.R.), mV, thermistors (PTC, NTC) Control: ON/OFF, single and double action PID I = normalized signals 0/4..20 mA Measurement range: according to the used probe (see range table) V = normalized signals 0..1 V, 0/1..5 V, 0/2..10 V. Display resolution: according to the probe used 1/0,1/0,01/0,001 c : OUTPUT OUT1 Overall accuracy: +/- 0,5 % fs Max cold junction compensation drift (in tc) : 0,1 C with R = Relay C/ S = VDC for SSR operating temperature 0 ... 50 after warm-up of 20 min. C d : OUTPUT OUT2 Sampling rate: 130 ms. 2R = Relay Display: 4 Digit Red h 12 mm Compliance: ECC directive EMC 89/336 (EN 61326), ECC directive 2S = VDC for SSR - = None LV 73/23 and 93/68 (EN 61010-1) ee: SPECIAL CODES 7.5
ELK 38
PAG. 14