SE-704 MANUAL

EARTH-LEAKAGE MONITOR
January 18, 2008

REVISION 2

G E M O N IT O R
EARTH LEAKA
CT TRIP
PW R 0 50 0
15 0 20 0 30 0 40 60 0
10 0 30 0 20 0 80 0
80 40 0 10550 10 00
60
30 1 0 50 0 30
IME (ms)
LE V EL (m A ) T
RE SE T
TEST
S TI NA R T CTOD.
SE-704
ENG EERING L

Copyright © 2008 by Startco Engineering Ltd.

All rights reserved.

Publication: SE-704-M
Document: S95-C704-00000
Printed in Canada.
This page intentionally left blank.
Startco Engineering Ltd. Page i
SE-704 Earth-Leakage Monitor Rev. 2

TABLE OF CONTENTS LIST OF FIGURES


PAGE PAGE
Table of Contents .................................................................... i 1. SE-704 Outline and Mounting Details ...................... 2
List of Figures.......................................................................... i 2. Typical Connection Diagram..................................... 3
List of Tables ........................................................................... i 3. SE-CS30-26 Current Sensor ...................................... 5
4. SE-CS30-70 Current Sensor ...................................... 6
1. General ....................................................................... 1 5. PMA-55 Panel-Mount Adapter.................................. 7
6. PMA-60 Panel-Mount Adapter.................................. 8
2. Operation ................................................................... 1 7. Earth-Fault-Test Circuit ........................................... 11
2.1 Configuration-Switch Settings ................................... 1
2.1.1 Relay Operating Mode .................................... 1
2.1.2 Filter Selection................................................. 1
2.1.3 CT Verification................................................ 1 LIST OF TABLES
2.1.4 Reset Mode ...................................................... 1 PAGE
2.2 Front-Panel Controls................................................... 1 1. Trip-Features Comparison ......................................... 4
2.2.1 Earth-Leakage Trip Level ............................... 1 2. Earth-Fault-Test Record........................................... 11
2.2.2 Earth-Leakage Trip Time................................ 1
2.2.3 Reset................................................................. 1
2.2.4 Test................................................................... 1
2.3 Front-Panel Indication ................................................ 3
2.3.1 Power ............................................................... 3 DISCLAIMER
2.3.2 Trip................................................................... 3
2.3.3 CT Verification................................................ 3 Specifications are subject to change without notice.
2.4 Analog Output............................................................. 3 Startco Engineering Ltd. is not liable for contingent or
2.5 Self Diagnostics .......................................................... 3 consequential damages, or for expenses sustained as a
result of incorrect application, incorrect adjustment, or a
3. Installation ................................................................. 3 malfunction.

4. SE-704 Compatibility ............................................... 4

5. Technical Specifications ........................................... 9

6. Ordering Information ............................................10

7. Warranty..................................................................10

8. Performance Test....................................................11

Pub. SE-704-M, January 18, 2008.


Startco Engineering Ltd. Page ii
SE-704 Earth-Leakage Monitor Rev. 0

This page intentionally left blank.

Pub. SE-704-M, January 18, 2008.


Startco Engineering Ltd. Page 1
SE-704 Earth-Leakage Monitor Rev. 2

1. GENERAL 2.1.3 CT VERIFICATION


Switch 3 is used to enable CT verification. In the
The SE-704 is a microprocessor-based earth-leakage ON position, a trip will occur if the SE-CS30 current
monitor for ac power supply systems that require earth- sensor is disconnected.
leakage detection as low as 10 mA. It is uniquely suited
for very sensitive earth-fault protection on systems with 2.1.4 RESET MODE
significant harmonic content. Its output relay can operate Switch 4 is used to select autoreset or latching trips.
in the fail-safe or non-fail-safe mode for undervoltage or See Section 2.2.3.
shunt-trip applications. The SE-704 has one output relay
with isolated normally open and normally closed contacts 2.2 FRONT-PANEL CONTROLS
for use in independent control circuits. Additional 2.2.1 EARTH-LEAKAGE TRIP LEVEL
features include LED trip and power indication, autoreset The LEVEL (mA) selection switch is used to set the
or latching trips with front-panel and remote reset, trip earth-leakage trip level. For earth-leakage detection, the
memory, test switch, self diagnostics, 0- to 5-V analog earth-leakage trip level must be substantially below the
output, CT verification with LED indication, digital prospective earth-fault current. To avoid sympathetic
selector switches, and switch-selectable algorithms for tripping, the trip level must be above the charging current of
fixed-frequency or variable-frequency applications. the protected feeder.
Earth-leakage current is sensed by an SE-CS30-series
core-balance earth-fault current transformer. The trip 2.2.2 EARTH-LEAKAGE TRIP TIME
level of the earth-leakage circuit is digital-switch The SE-704 has a definite-time trip characteristic. The
selectable from 10 to 500 mA. Trip time is digital-switch TIME (ms) selector switch is used to set the earth-leakage
selectable from 30 to 1,000 ms. trip time for coordination with upstream and downstream
earth-fault devices. Coordination requires the same trip
2. OPERATION level for all earth-leakage devices in a system and the trip
time to progressively increase upstream. The amount of
2.1 CONFIGURATION-SWITCH SETTINGS equipment removed from the system will be a minimum if
See Fig. 1. the first earth-leakage device to operate is the one
immediately upstream from the fault.
2.1.1 RELAY OPERATING MODE
Switch 1 is used to set the operating mode of the output 2.2.3 RESET
relay. In the fail-safe mode, the output relay energizes If the Reset Mode switch is in the LATCHING
when the earth-leakage circuit is not tripped. In the fail- position, a trip remains latched until the RESET switch
safe mode, non-volatile memory retains the trip status of is pressed or the remote-reset terminals (6 and 7) are
the SE-704. If tripped, and the supply voltage is cycled, momentarily connected. In the non-fail-safe relay
the SE-704 will remain tripped, with the trip relay operating mode, cycling the supply voltage will also
de-energized and the TRIP LED on, until reset. reset the SE-704.
In the non-fail-safe mode, the output relay energizes If the Reset Mode switch is in the AUTORESET
when an earth-leakage trip occurs. In the non-fail-safe position, a trip will reset when the fault is removed.
mode, trip status is not retained in non-volatile memory. The reset circuit responds only to a momentary
closure so that a jammed or shorted switch will not
2.1.2 FILTER SELECTION prevent a trip. The front-panel RESET switch is
Switch 2 is used to select the filtering algorithm for a inoperative when the remote-reset terminals are
fixed-frequency (50/60 Hz) or variable-frequency connected.
application. The FIXED FREQUENCY setting uses a
DFT filter that allows lower trip levels to be used by 2.2.4 TEST
rejecting harmonics that can cause nuisance tripping. The TEST switch is used to test the earth-leakage
The VARIABLE FREQUENCY setting uses a peak- circuit, the indication, and the output relay. When the
detection algorithm with a wider band width for fault TEST switch is pressed for one second, a test signal is
detection in variable-frequency drive applications. applied to the earth-leakage-detection circuit, the circuit
will trip, the TRIP LED will light, and the output relay
will operate.

Pub. SE-704-M, January 18, 2008.


Startco Engineering Ltd. Page 2
SE-704 Earth-Leakage Monitor Rev. 2

55.0
(2.17)
8.7 37.5
(0.34) (1.48)

CONFIGURATION
SWITCHES
NOTE 2
RESET MODE LATCHING 4 AUTORESET

CT VERIFICATION OFF 3 ON
FIXED VARIABLE
FILTER SELECTION 2

(2.95)
FREQUENCY FREQUENCY

(2.41)
61.2

75.0
RELAY OPERATING MODE FAIL-SAFE 1 NON-FAIL-SAFE

NOTE 5

S1 S2 RS

(0.27)
6.9
CT RESET ANALOG
1 2 3 4 5 6
OUTPUT
7 8
MOUNTING DETAIL

113.0 (NOTE 3)
(4.45)
110.0
TOP
(4.33) 6.3
55.0
(2.17) (0.25)

EARTH LEAKAGE MONITOR

PWR CT TRIP
100 150 200 300 400 500
80 300 200 600
(2.95)
75.0

60 400 100 800


30 500 55 1000
10 30
LEVEL (mA) T I M E ( m s )

TEST RESET
STARTCO SE-704
ENGINEERING LTD.

FRONT SIDE
NOTES:

1. DIMENSIONS IN MILLIMETRES (INCHES).


9 10 11 12 13 14 15 16 2. MOUNTING SCREWS: M4 OR 8-32.
LN2 L 1
3. OVERALL DIMENSION WHEN MOUNTED ON
DIN EN50022 35 mm x 7.5 mm TOP-HAT RAIL.

4. ADJUSTMENT KNOBS ARE REMOVABLE.

5. CONFIGURATION SWITCHES SHOWN


BOTTOM IN DEFAULT POSITION.

FIGURE 1. SE-704 Outline and Mounting Details.

Pub. SE-704-M, January 18, 2008.


Startco Engineering Ltd. Page 3
SE-704 Earth-Leakage Monitor Rev. 2

2.3 FRONT-PANEL INDICATION 3. INSTALLATION


2.3.1 POWER
The green LED labeled PWR indicates presence of This earth-leakage monitoring system consists of an
supply voltage. SE-704 earth-leakage monitor and an SE-CS30 current
sensor connected as shown in Fig. 2.
2.3.2 TRIP An SE-704 can be surface or DIN-rail mounted. See
The red LED labeled TRIP indicates a trip. A solid red Fig. 1. Panel mounting requires a PMA-55 or PMA-60
LED indicates an earth-leakage trip and a flashing LED Panel-Mount Adapter. See Figs. 5 and 6.
indicates a trip initiated by a CT fault. Two fast flashes of Pass the phase conductors through the CT window and
the TRIP LED indicate a diagnostic trip. See Section 2.5. position them in the centre of the opening (for 4-wire and
single-phase systems, also pass the neutral conductor
2.3.3 CT VERIFICATION through the CT window). Do not pass earth conductors
The green LED labeled CT indicates that an SE-CS30 through the CT window. In applications that require
sensor is connected, even if CT verification is disabled. shields or drain wires to pass through the CT window,
return them through the CT window before connecting
2.4 ANALOG OUTPUT them to earth. Connect an SE-CS30 current sensor to
The non-isolated, 0- to 5-V analog output indicates earth- terminals 4 and 5, connect the shield to terminal 5, and
leakage current sensed by the earth-leakage CT. The output earth terminal 5. See Figs. 3 and 4 for SE-CS30 current-
is 5 V when earth-leakage current is 500 mA. sensor dimensional drawings.
Remove the connection to terminal 9 for dielectric-
2.5 SELF DIAGNOSTICS strength testing.
A diagnostic trip is indicated by two fast flashes of the
TRIP LED. It can be caused by a problem detected by the
watchdog timer, or from an incorrect reading from non-
volatile memory. Press RESET or cycle supply voltage. If
the problem persists, consult Startco.

SE-CS30-X

L N
4 5

S1 S2 START
STOP O/L
13 14
1M
15 16 1M

ISOLATED CONTACTS
11 10
L1 L2
N
REMOTE RESET
SE-704
6
RS
RESET
7
LEAKAGE ANALOG
8 OUTPUT
V 9

FIGURE 2. Typical Connection Diagram

Pub. SE-704-M, January 18, 2008.


Startco Engineering Ltd. Page 4
SE-704 Earth-Leakage Monitor Rev. 2

4. SE-704 COMPATIBILITY
The current SE-704 has been enhanced with the
addition of non-volatile trip memory for the fail-safe
relay operating mode. Prior to hardware revision 01, a
mechanical flag was used instead of non-volatile trip
memory. The current revision of the SE-704 can
directly replace previous revision-00 units. The
hardware-revision number is listed on the SE-704
model/serial-number label affixed to the SE-704
enclosure. Both generations of SE-704 are compared
in Table 1.
The SE-704 was previously available with SE-704-01
120-Vac and SE-704-02 240-Vac control-voltage options.
These have been discontinued. An SE-704-0U universal
120/240-Vac/Vdc unit can directly replace an SE-704-01
or SE-704-02.

TABLE 1. TRIP-FEATURES COMPARISON


HARDWARE REVISION
00 ≥ 01
LED trip indication Yes Yes
Mechanical flag trip indication Yes No
Non-volatile trip memory No Yes
Trip LED: Off Trip LED: On
Fail-safe Trip relay: Energized Trip relay: De-energized
Device state after supply voltage cycled Trip flag: Red
when tripped (earth fault removed) Trip LED: Off Trip LED: Off
Non-fail-safe Trip relay: De-energized Trip relay: De-energized
Trip flag: Red

Pub. SE-704-M, January 18, 2008.


Startco Engineering Ltd. Page 5
SE-704 Earth-Leakage Monitor Rev. 1

68.0 68.0
(2.68) (2.68)

17.0 34.0
(0.67) (1.34)

P1
S1 2S2 M4 OR 8-32 TAP

(2.07)
P
(1.04)

(1.68)
52.5
26.5

42.6
M5 SCREWS

TOP MOUNTING DETAIL


110.0 MAX
(0.43)

25.0 26.5
(0.98) (1.04)

SE-CS30-26
CURRENT SENSOR
R LR 53428 STARTCO
E N G I N E E R I N G L T D.
C US

4.0 (0.16) 0
(2.83)
72.0

.0 RECESSED FOR
26 2) 7-mm HEX NUT
.0 3.0 (0.12) DEEP
(1
(1.34)
34.0

(0.87)

58.0
7.0

(2.28)

5.0 5.0 52.5


(0.20) (0.20) (2.07)

FRONT SIDE

MOUNTING FOOT
NOTES:
INSTALLATION 1. DIMENSIONS IN MILLIMETRES (INCHES).
TOOL
2. PRESS MOUNTING FEET IN PLACE USING
INSTALLATION TOOL PROVIDED (DETAIL ‘A’)
3. MOUNTING SCREWS: M4 OR 8-32.
DETAIL ‘A’

FIGURE 3. SE-CS30-26 Current Sensor.

Pub. SE-704-M, January 18, 2008.


Startco Engineering Ltd. Page 6
SE-704 Earth-Leakage Monitor Rev. 2

P1
S2 S1

121.0 121.0
(4.76) (4.76)
20.5 80.0
(0.81) (3.15)

NOTE 3

(2.21)

(1.81)
(1.18)

56.0

46.0
30.0

M5 SCREWS

TOP MOUNTING DETAIL


25.0 30.0
(0.98) (1.18)

SE-CS30-70
CURRENT SENSOR
R LR 53428 STARTCO
E N G I N E E R I N G L T D.
C US
138.0 MAX

69
.8
(5.43)

(4.96)
126.0
(2.
75
) Ø 5.0 (0.20)
RECESSED FOR
8-mm HEX NUT
1.0 (0.04) DEEP
(0.87)
22.0

5.5 110.0 5.5 56.0


(0.22) (4.33) (0.22) (2.21)

FRONT SIDE

NOTES:
MOUNTING FOOT
INSTALLATION 1. DIMENSIONS IN MILLIMETRES (INCHES).
TOOL
2. PRESS MOUNTING FEET IN PLACE USING
INSTALLATION TOOL PROVIDED (DETAIL ‘A’)
3. MOUNTING SCREWS: M4 OR 8-32.

DETAIL ‘A’

FIGURE 4. SE-CS30-70 Current Sensor.

Pub. SE-704-M, January 18, 2008.


Startco Engineering Ltd. Page 7
SE-704 Earth-Leakage Monitor Rev. 0

110.0
(4.33)
85.0
(3.35) PANEL THICKNESS
1.6 (0.06) TO 4.8 (0.19)

6-32
(1.67)
42.5

EARTH LEAKAGE MONITOR

PWR CT TRIP
100 150 200 300 400 500

(2.95)
80 300 200 600

75.0
(3.35)
60 400 100 800

85.0
30 500 55 1000 6-32
10 30
LEVEL (mA) T I M E ( m s )

TEST RESET
STARTCO SE-704
ENGINEERING LTD.

BRACKET
55 mm (2.2) WIDE
MONITOR

FRONT VIEW SIDE VIEW

85.0
(3.35)
72.0
(2.83)
6.0 60.0 6.0
(0.37)
9.5

(0.24) (2.36) (0.24)

INSTALLATION INSTRUCTIONS:
2.0 (0.08) RAD 1. REMOVE BEZEL AND LATCH MONITOR TO
MAXIMUM
BRACKET.
(1.67)
42.5

4.0 (0.16) DIA


(1.18)

2. INSERT BRACKET THROUGH FRONT OF PANEL


30.0

8.7 (0.34) DIA CUTOUT AND SECURE WITH FLAT WASHERS


AND LOCKNUTS PROVIDED.
(2.36)

(3.11)
60.0

79.0

4.3 (0.17) RAD


3. CONNECT WIRING TO TERMINALS.
ALTERNATE
CONFIGURATIONS 4. INSTALL BEZEL USING 6-32 x 0.31 SCREWS
PROVIDED.

NOTE:
1. DIMENSIONS IN MILLIMETRES (INCHES)
(0.37)
9.5

PANEL CUTOUT DETAIL

FIGURE 5. PMA-55 Panel-Mount Adapter.

Pub. SE-704-M, January 18, 2008.


Startco Engineering Ltd. Page 8
SE-704 Earth-Leakage Monitor Rev. 0

116.0
(4.57)
99.0
(3.90) PANEL THICKNESS
1.6 (0.06) TO 4.8 (0.19)

M4
(1.73)
44.0

EARTH LEAKAGE MONITOR

PWR CT TRIP
100 150 200 300 400 500

(2.95)
80 300 200 600

75.0
(3.46)
60 400 100 800

88.0
30 500 55 1000 M4
10 30
LEVEL (mA) T I M E ( m s )

TEST RESET
STARTCO SE-704
ENGINEERING LTD.

BRACKET
55 mm (2.2) WIDE
MONITOR
TRANSPARENT
COVER (NOTE 2)
FRONT VIEW SIDE VIEW

99.0
(3.90)
72.0
(2.83)
6.0 60.0 6.0
(0.37)
9.5

(0.24) (2.36) (0.24)

INSTALLATION INSTRUCTIONS:
2.0 (0.08) RAD 1. WITH COVER REMOVED LATCH MONITOR TO
MAXIMUM
BRACKET.
(1.73)
44.0

4.5 (0.18) DIA


(1.18)

2. INSERT BRACKET THROUGH FRONT OF PANEL


30.0

8.7 (0.34) DIA CUTOUT AND SECURE WITH FLAT WASHERS


AND LOCKNUTS PROVIDED.
(2.36)

(3.11)
60.0

79.0

4.3 (0.17) RAD


3. CONNECT WIRING TO TERMINALS.
ALTERNATE
CONFIGURATIONS 4. ATTACH COVER USING THUMB SCREWS
PROVIDED.

NOTE:
1. DIMENSIONS IN MILLIMETRES (INCHES).
(0.37)
9.5

2. MEETS NEMA3, IP53.


PANEL CUTOUT DETAIL

FIGURE 6. PMA-60 Panel-Mount Adapter.

Pub. SE-704-M, January 18, 2008.


Startco Engineering Ltd. Page 9
SE-704 Earth-Leakage Monitor Rev. 0

5. TECHNICAL SPECIFICATIONS Functional Test ............................ Front-Panel Switch

Supply: Output Relay:


0U Option..............................2.5 VA, 120 to 240 Vac, Contact Configuration ........... Isolated N.O. and N.C.
(+20, -55%) 50/60 Hz, Operating Mode ..................... Fail-Safe or Non-Fail-Safe
2.0 W, 100 to 240 Vdc, CSA/UL Rating ..................... 8 A Resistive, 250 Vac,
(+20, -25%) 8 A Resistive, 30 Vdc
0D Option..............................2.0 W, 12 to 30 Vdc, Supplemental Contact Ratings:
(+20, -25%) Make/Carry 0.2 s .............. 20 A
0T Option ..............................2.0 W, 40 to 55 Vdc, Carry Continuous.............. 8 A
(+20, -25%) Break:
03 Option...............................2.5 VA, 24 Vac, dc.................................. 30 W Resistive,
(+15%, -40%), 50/60 Hz 15 W Inductive
(L/R = 0.04)
Trip-Level Settings.......................10, 30, 60, 80, 100, 150, ac.................................. 2,000 VA Resistive
200, 300, 400, and 1,400 VA Inductive
500 mA (PF = 0.4)
Subject to maximums of 8 A and 250 V (ac or dc).
Trip-Time Settings........................30, 55, 100, 200, 300,
400, 500, 600, 800, and Operating Mode........................... Latching or Autoreset
1,000 ms
Terminals ..................................... Wire Clamping,
Accuracies: (1, 2) 24 to 12 AWG
Trip Level: (3, 4) (0.2 to 2.5 mm2) conductors
> 60 mA................................+ 0, -10%
= 60 mA................................+ 0, -10 mA Dimensions:
= 30 mA................................+ 0, -6 mA Height ..................................75 mm (3.0")
= 10 mA................................2 mA Width...................................55 mm (2.2")
Trip Time (5) ..............................10 ms Depth ...................................115 mm (4.5")

Input: Shipping Weight.........................0.45 kg (1 lb.)


Algorithms...............................DFT Digital or Peak
DFT 3 dB Frequency Resp ... 32 to 86 Hz Environment:
Peak 3 dB Frequency Resp ... 20 to 420 Hz Operating Temperature ....... -40°C to 60°C
CT .............................................SE-CS30 Current Sensor Storage Temperature........... -55°C to 80°C
CT Detection ........................Open-Circuit Detection Humidity.............................. 85% Non-Condensing
Thermal Withstand:
Continuous ...........................25 A Earth-Fault Surge Withstand ...................... ANSI/IEEE 37.90.1-1989
Current (Oscillatory and Fast
1-Second...............................400 A Earth-Fault Transient)
Current
EMC Tests:
Analog Output: Verification tested in accordance with EN 50263:2000
Range.......................................0 to 5 Vdc, 10 mV per mA Electrostatic Discharge......IEC 61000-4-2, EN 61000-4-2,
Output Impedance...................220 Ω 6 kV Contact Discharge
8 kV Air Discharge
Reset..............................................Front-Panel Switch and
Remote N.O. Contact Radiated RF.......................IEC 61000-4-3, EN 61000-4-3
10 V/m, 80-1000 MHz,
80% AM (1 kHz)
10 V/m, 900 MHz,
200 Hz Pulse Modulated

Pub. SE-704-M, January 18, 2008.


Startco Engineering Ltd. Page 10
SE-704 Earth-Leakage Monitor Rev. 0

Fast Transient.................... IEC 61000-4-4, EN 61000-4-4 6. ORDERING INFORMATION


±2 kV Common Mode
±1 kV Differential Mode SE-704-0

Surge Immunity................. IEC 61000-4-5, EN 61000-4-5 U Universal 120/240-Vac/Vdc Supply


±2.0 kV Common Mode D 12/24-Vdc Supply
±1.0 kV Differential Mode T 48-Vdc Supply
3 24-Vac Supply
Conducted RF ................... IEC 61000-4-6, EN 61000-4-6
10Vrms, 0.15-80 MHz, SE-CS30-26 .........Current Sensor,
80% AM (1 kHz) 26.0 mm (1.02”) Window
SE-CS30-70 .........Current Sensor c/w Flux Conditioner,
Magnetic Field .................. IEC 61000-4-8, EN 61000-4-8 69.8 mm (2.75”) Window
50 Hz, 30 A/m (continuous) PMA-55 ...............Panel-Mount Adapter, NEMA 1
50 Hz, 300 A/m PMA-60 ...............Panel-Mount Adapter, NEMA 3, IP53
(1 to 3 seconds) PMA-3..................Adapter Plate, GEC/MCGG
PMA-6..................Adapter Plate, FPL-GFRM
Voltage Interruption.......... IEC 255-22-11, EN 60255-11 PMA-15 ...............Adapter Plate, MGFR
100% for 2, 5, 10, 20, 50,
100, & 200 ms Consult factory for custom mounting adapters.

MHz Burst......................... IEC 255-22-1, EN 60255-22-1


1 kV Differential Mode 7. WARRANTY
2.5 kV Common Mode The SE-704 Earth-Leakage Monitor is warranted to be
free from defects in material and workmanship for a
RFI Compliance ..................... FCC Part 15, Subpart B, period of five years from the date of purchase.
Class A – Unintentional Startco Engineering Ltd. will (at Startco’s option)
Radiators repair, replace, or refund the original purchase price of
an SE-704 that is determined by Startco to be defective if
Certification .............................. CSA (Canada and USA) it is returned to the Startco factory, freight prepaid,
within the warranty period. This warranty does not
apply to repairs required as a result of misuse,
Australia negligence, an accident, improper installation,
tampering, or insufficient care. Startco Engineering Ltd.
does not warrant products repaired or modified by non-
Startco Engineering Ltd. personnel.

(1)
For earth-fault current in kA < 150 divided by the
trip setting in mA. [Ie < (150/level) x 1,000 A]
(2)
At 50 or 60 Hz.
(3)
SE-CS30-series CT included.
(4)
Maximum lead resistance of 2 Ω.
(5)
Trip Time at 3 x trip-level setting.

Pub. SE-704-M, January 18, 2008.


Startco Engineering Ltd. Page 11
SE-704 Earth-Leakage Monitor Rev. 0

8. PERFORMANCE TEST SE-CS30

Some jurisdictions require periodic earth-fault FROM


performance tests. A test record form is provided for POWER LOAD
SOURCE
recording the date and the result of the performance
tests. The following earth-fault system tests are to be
conducted by qualified personnel. 4 5

a) Evaluate the interconnected system in accordance S1 S2


with the overall equipment manufacturer’s detailed R1 L
11
L1
instructions. 10 SE-704
N L2/N
b) Verify proper location of the SE-CS30 current

ITEST
R2
sensor. Ensure the cables pass through the current-
sensor window. This check can be done visually 11 12
OP1 OP2
with knowledge of the circuit. The connection of the
3
current-sensor secondary to the SE-704 is not polarity L L1
5
sensitive. N L2
1 SE-400
c) Verify that the system is correctly earthed and that
alternate earth paths do not exist that bypass the
8 RMT1
current sensor. High-voltage testers and resistance REMOTE
bridges can be used to determine the existence of TEST 9
RMT2
alternate earth paths.
R1 = 10 W, 10 W, 1%
d) Verify proper reaction of the circuit-interrupting R2 = 0.1 W, 10 W, 1%
device in response to a simulated or controlled earth- ITEST = 1/10 SE-400 SETTING
fault current. To simulate earth-fault current, use CT- FIGURE 7. Earth-Fault-Test Circuit.
primary current injection. Fig. 7 shows a test circuit
using a Startco SE-400 Ground-Fault-Relay Test
Unit. The SE-400 has a programmable output of 0.5 TABLE 2. EARTH-FAULT-TEST RECORD
to 9.9 A for a duration of 0.1 to 9.9 seconds. Fig. 7
DATE TEST RESULTS
shows the use of resistors that reduce the injected
current to 10% of the SE-400 setting. Set the test
current to 120% of the SE-704 setting. Inject the test
current through the current-sensor window for at
least 2.5 seconds. Verify that the circuit under test
has reacted properly. Correct any problems and re-
test until the proper reaction is verified.
e) Record the date and the results of the test on the
attached test-record form.

NOTE: Do not inject test current directly into current-


sensor-input terminals 4 and 5.

Retain this record for the authority having jurisdiction.

Pub. SE-704-M, January 18, 2008.