Standard
Operational Excellence
May 2014
This document is for Vopak internal use only and should not be distributed outside Vopak
Vopak Operational Excellence Standards contain confidential information regarding Vopak and its
relevant subsidiaries and have been prepared with a view to inform and instruct Vopak employees.
For that reason none of these standards - whether in original or copies, including but not limited to any
medium including paper or electronic formats like file copies, word documents, pdf files, on electronic
storage devices or by email - is to be shown, given or loaned to any third party, including external
companies and persons not directly employed by Vopak. No exceptions are permitted without the
written authorisation of the Director Corporate Operational Excellence.
This document has only been made available to Vopak employees who have agreed to return it to
Vopak immediately upon first request, together with any copies and any other information that was
provided. Persons who are not employed by Vopak and who have nevertheless received this
document must be aware that it is likely they have received it in breach of a confidentiality obligation.
Such persons may not rely on, use, duplicate or disclose any information contained in this document
and should forthwith return it, together with any copies if any, to Vopak.
This copy is not controlled, for the latest revision check on Vopak Intranet.
Page
1 INTRODUCTION 5
5 TYPES OF ROOFS 9
5.1 Non Contact Roof 9
5.2 Full Contact Roof 10
5.3 Comparison of Full Contact Roof with Non Contact Roof 11
6 SEALS 13
6.1 Mechanical Shoe Seals 13
6.2 Vapour Mounted Seals 14
6.3 Liquid Mounted Seals 14
7 SELECTION CRITERIA 15
7.1 General 15
7.1.1 Life Cycle Cost 15
7.1.2 Track Record 15
7.1.3 Service Life 15
7.2 Environment, Health and Safety 16
7.2.1 Retardancy 16
7.2.2 Vapour Reduction 16
7.2.3 Heat Losses 17
7.3 Constructability 17
7.3.1 Installation Time 17
7.4 Operability 17
7.4.1 Tank Cleaning 17
7.4.2 High Filling Rate 18
7.4.3 Vulnerability of Physical Damage 18
7.4.4 Loss of Storage Capacity 18
7.4.5 Dead Stock 18
7.4.6 Landing of Roof 19
7.5 Maintenance and Inspection 19
7.5.1 Maintenance 19
7.5.2 Inspection 19
This document is for Vopak internal use only and should not be distributed outside Vopak
10 DESIGN 25
10.1 Material Selection 25
10.2 Legs or Suspension 25
10.3 Calculations 26
10.4 Mountings 26
10.5 Diffuser 26
10.6 Floating Suction 27
10.7 Earthing 27
10.8 Gas Venting Capability 27
10.9 Quality Control 28
12 INVESTMENT COST 30
12.1 CAPEX 30
12.2 OPEX 30
This document is for Vopak internal use only and should not be distributed outside Vopak
This standard is intended primarily to direct terminals in the selection of internal floating roofs in
order to minimise in-service problems and extend the useful life of the floating roof.
This document describes the Vopak requirements for internal floating roofs and shall be used in
combination with the applicable national / international codes and local regulations. For this
reason, this document will also describe the aspects where the Vopak experience deviates from
the standards and / or will provide a better basis to achieve the Vopak business principles.
It is proposed that available types of roofs be evaluated against each other. In addition, material
compatibility issues will also be included. Internal floating roofs shall only be selected if benefit
has been proofed.
This document is for Vopak internal use only and should not be distributed outside Vopak
Covering an External Floating Roof with a fixed roof, for example by means of an Aluminium
Geodesic Dome roof is outside the scope of this document.
The selection of the IFRs shall be based on the latest editions of the following documents (in
sequence of importance):
2.1 Background
IFR’s have been in use since the early 1960s and gained popularity from 1980 onwards in the
oil and chemical industry. Reasons for using a floating roof are to:
- Reduce evaporative emissions e.g. breathing and filling losses and hence air pollution.
A tank without a floating roof can have an annual vapour loss of 3% of the total tank
content;
- Reduce ingress of contaminants e.g. rust, condensed water and airborne particles;
- Minimise nuisance from odours;
- Reduce hazards of static ignition associated with highly charged liquids;
- Provide thermal insulation in fuel oil storage as an alternative of lagging;
- Local authority requirements.
This Standard applies to all existing terminals owned by Vopak and its joint venture companies.
This document is for Vopak internal use only and should not be distributed outside Vopak
This document is for Vopak internal use only and should not be distributed outside Vopak
This document is for Vopak internal use only and should not be distributed outside Vopak
- Non-Contact Roofs
- Full-Contact Roofs
Various alternatives
Besides constructional differences, the big difference between the two groups is the existence
of a vapour space between the liquid and the membrane of the roof. In case of a non-contact
roof, the membrane is not in contact with the liquid enabling to form a significant amount of
vapour under the deck. In case of a full contact roof no vapour exists between the roof and the
liquid. As a result, any hole or leak in a non contact roof will result in a strong reduction of the
efficiency of the roof, while with full contact roofs in case of a leak, only the exposed area
releases vapour.
This most common type is the Aluminium Pontoon deck type. The design is more or less
common albeit many different suppliers. The roof and pontoons can be constructed from:
This document is for Vopak internal use only and should not be distributed outside Vopak
This type of roof can be installed in many varieties however the list below classifies the different
types into groups.
This document is for Vopak internal use only and should not be distributed outside Vopak
This type, panels of polyurethane core wrapped in aluminium foil are vulnerable and due to the
frame, required to hold the modules, difficult to replace. Also the modules can absorb product in
case the foil would break or damage. Therefore not allowed in Vopak.
Appendix A provides an overview in more detail of pro’s and con’s of each type of roof.
When a full contact roof is compared with a non contact roof, some basic features are
distinguished. Typical features of a full contact roof:
This document is for Vopak internal use only and should not be distributed outside Vopak
*) Product Transport lines shall be design in such a way that gas or vapour slugs introduced by
pigging, stripping or other reasons are captured or relieved before entering the tank.
This document is for Vopak internal use only and should not be distributed outside Vopak
Types a and c show much better emission reduction figures than the seals in type b. If only one
seal is selected this is called a primary seal. If two seals are mounted above each other, the
seal above the primary seal is called secondary seal. According BAT – Best Available
Technology it is allowed to select only one (primary) seal for IFR. When selecting a seal, using a
single seal (Primary seal only) is recommended. The type that is BAT and therefore has strong
preference is a liquid mounted Metallic (SS) shoe plate seal. If product resistance of this seal is
a problem selection of other materials or type of seal is accepted.
Some seals require the use of a bumperbar. The purpose of such a bar is to assure a minimum
gap between the tankshell and the IFR in case this IFR moves to one side. Some seals could
damage severely if not remaining this minimum distance. Ask supplier for specific requirements
on this subject.
Typical for mechanical shoe seals are the metal plates that press the shell due to a spring or
weight. The shoe plate penetrates into the liquid and forms a small vapour space which is
closed by a vapour tight fabric. If shoe does not touch the shell, only the liquid between the shell
and shoe will generate emission. Emissions form this type of seal are expected to be low
because of this small area.
This document is for Vopak internal use only and should not be distributed outside Vopak
Below are some examples of vapour mounted seals. If a vapour mounted seal does not touch
the tank shell at any point around the circumference, the whole circumferential vapour ring
below the seal can pass the seal. Always use bumper bars to protect the seal and make sure
earthing to tank shell is working.
This seal is mounted in the liquid. Most of the time the seal is a bag filled with liquid or foam. In
fact it is one of the best seals from a point of emission reduction, since it can follow the
unevenness in the tank shell very well and therefore no openings are around circumference.
However at the same time the most vulnerable. Always use bumper bars to protect seal.
Seals are subject to wear and tear and should regularly be inspected. All seals have fabric or
rubber parts or components, subject to brittleness or aging over time. Therefore the lifetime
hardly ever exceeds 10 years.
This document is for Vopak internal use only and should not be distributed outside Vopak
7.1 General
7.1.1 Life Cycle Cost
Life cycle cost is the total cost during the expected life of the roof and seal. This means the sum
of CAPEX and the sum of future OPEX. When selecting and IFR and or seal one shall focus on
minimum life time cost and not primarily selection based on the lowest CAPEX.
Many suppliers are on the market of which only some of them are good performers.
Investigating the track record of a supplier is essential to work together.
Subjects to be investigated:
The Service life of an IFR and seal is strongly related to the usage during its lifetime. The
following fields of activities are affecting the service life:
Operational
- Product Portfolio Matrix: Always check the compatibility of the materials of the floating
roof and seal (!) and the products to be stored. If a product change is intended in a tank,
take material compatibility of seal and IFR into account during Management of Change
process;
- Do not operate a tank in a way that physical overstress can occur. Typical examples:
o Never overfill a tank,
o Product circulation by jet nozzle
o Do not release gas into the tank during pigging.
o Smooth landing of a roof
o Prevent water load during cleaning
Repair
- Select only approved materials;
- Repair properly, so not “easy fix”-solutions: select long term solutions.
Note 1: reference is made to the inspection frequencies as defined in the Tank Maintenance and Inspection Minimum standard
This document is for Vopak internal use only and should not be distributed outside Vopak
For internal floating roofs a rim fire can develop into a full surface fire when the roof sinks or
catches fire and looses integrity. Therefore:
- Only use flame retardant materials in a floating roof.
- Design the roof with sufficient buoyancy according API 650, Appendix H. Take
in consideration the load on the roof due to foam (if applicable) added on top of
the roof or underneath the primary or secondary seal.
NFPA 30 states that for all metal roofs the fire fighting system shall be capable to fight a rim fire,
while for a GRE roof, according to the standards the fire fighting system in the tank must be
designed for a full service fire when choosing GRE.
One of the main reasons for selecting a floating roof is to reduce emissions. Emissions are
vapours released from the tank to the environment.
The exact amount of these losses shall be calculated and reference is made to “Manual of
Petroleum Measurement Standards chapter 19, Section 1 – Evaporative losses from Fixed roof
Tanks” [2]. EPA supplies free downloadable “Tanks” software that contains the formulas of
reference [2]. In general calculating a fixed number for efficiency of a certain type Floating roof
is not possible. The true efficiency of a floating roof is dependant of many variables, such as
type of selected roof, number of turnovers per year, product stored, operational procedures
(pigging, roof landings), type of seal and level of maintenance. See table below:
This document is for Vopak internal use only and should not be distributed outside Vopak
Filling a tank
During filling of tanks vapour is forced to leave the tank via a vent. It is not important for this
phase whether a PVV or free vent is used for the flow out of the tank. In this phase a PVV
hardly reduces emissions from the tank.
Breathing of a tank
When the tank is filled, the sun can heat the vapours above the liquid up and by the increase of
pressure the vapour can leave the tank via the free vent or PVV. This emission loss can be
reduced by the use of PVV, depending on the pressure settings. The larger the range between
the pressure settings is, the more the reduction of these losses are. The tank design limits the
PVV settings.
The opposite of breathing out will also occur during cold periods: during the night the vapour will
cool down and outside air is sucked into the tank because of the reduction of volume. This does
not have an effect on emission until it is heated up again when the outside temperature is
increasing again.
Emptying a tank
During and after emptying a tank the remaining liquid on the shell will evaporate. This vapour
can leave the tank during outbreathing of the tank. (see “breathing of a tank”)
Gas freeing in tank (pigging, blowing lines) and landing the roof are the major sources of
emission and shall be eliminated if feasible.
Some products require heating of the product. The use of double layer roofs reduces heat
losses through the IFR. Metal roofs convey heat better than GRE roofs. An assessment of the
different types of IFRs should be made to select the best roof.
7.3 Constructability
7.3.1 Installation Time
Non contact pontoon type IFR, including the required tools comes in packages that can be
brought into the tank via the tank manhole. Rest of the floating roofs requires either a doorsheet
or hole in the fixed roof.
The steel single deck and double deck require significant more time to construct than the rest of
the IFR’s due to the engineering, labour intensive layout of the steel plates and welding. Also All
inspections shall be done in the field. All other IFR types are build in modules of which many
inspections quality related have already taken place in the workshop during construction of
these modules.
7.4 Operability
7.4.1 Tank Cleaning
Cleaning can be a high risk activity for the roof and seal. Always discuss and safeguard
cleaning activities with cleaners, focussing on the following before cleaning starts:
As long as the roof is not floating high filling rates must be avoided: allow maximum 1 m/s in the
pipe. Consult the supplier of the seal and/or roof for maximum flow rates on initial filling and
discharging the tank and refer to Vopak Minimum Standard on “Product Movement
Management”. The use of a diffuser will reduce the speed of the product under the roof, but
even when using a diffuser, first make sure the roof is floating. The same is valid for emptying
the tank. Reduce discharging rate when approaching the liquid level where the roof will land.
The reasons are that physical stresses are introduced at high landing speed on the bottom and
IFR.
After pigging, the pressure in the line shall be released from the system before new product
enters the tank. During filling of the tank with new product after pigging took place, gas will be
released into the tank until the product has arrived to the tank. For distributing the gas flow in
the tank, a diffuser shall be installed. See 7.5. A floating roof can severely be damaged during
pigging or blowing, even with a diffuser. This is especially the case when standing on its legs.
The use of a floating roof will always reduce the net storage capacity. The manufacturer of the
floating roof shall provide exact information on the maximum liquid level of the tank in service.
Extreme Care should be taken during a hydro test with the roof in place: Most products have a
density lower than water. The result is during hydro test that the maximum liquid level of the roof
must be compensated for the extra buoyancy.
The use of a secondary seal additionally reduces the working capacity of the tank. However, the
use of only a primary seal, except for a metallic shoe type seal, is not a good practice and
should not be recommended. Either select a double seal or a metallic shoe type seal.
Roof constructions can damage an IFR and interference shall be determined before an IFR is
selected, designed and installed.
The space under the roof, when it is resting on its supports, is called dead stock. A large part of
the total annual tank’s emission is the release of the dead stock volume above the floating roof
during initial filling. If the floating roof can be kept floating at all times this will reduce emissions
drastically. The business of Vopak often requires completely emptying and filling of a tank
frequently, inevitably resulting in higher emissions due to this dead stock, despite the use of a
floating roof.
This document is for Vopak internal use only and should not be distributed outside Vopak
When the roof lands this shall be done with low velocity, to avoid stress peaks in supports,
bottom and construction. While the roof is resting on its supports automatic bleeder vents shall
prevent overstressing the roof during both filling and emptying a tank.
During its lifetime IFR’s and seals shall be frequently inspected, and maintained. Sometimes a
repair is required. The following typical features are applicable on maintenance and inspection:
7.5.1 Maintenance
GRE
One of the benefits of GRE roofs is that they are in principle maintenance free. If repair is
required this needs special attention for temperature and humidity in the tank. Large repairs, i.e.
exchange of modules, could require openings in the fixed roof
Steel roofs
Maintenance on steel roofs normally is to replace the coating on the topdeck after 15 – 20
years. This requires sandblasting and repainting. Repair requirements are often found in welds
that have cracked and require re-welding.
Seals
All seals require maintenance eventually. Non metallic parts age over time, getting brittle or
damaged, like vapour barriers or rubber lips touching the tank shell. Also parts undergoing wear
will require maintenance. A good example is a steel shoe plate. Although it is difficult to see, the
thickness of the shoe plates reduce over time due to friction with tank shell.
7.5.2 Inspection
IFRs are subject to sometimes extreme conditions, which can result in breakage of parts,
membranes or pontoons. Also general and pitting corrosion takes often place, as well as wear
and tear on the seals. For this and many other reasons, the IFR and seal system requires
regular inspections. Reference is made to Vopak Tank maintenance and inspection minimum
standard on inspection intervals and checklists. On top of the checklists some general additional
areas of interest are:
GRE
GRE roofs are black, due to the addition of Carbon particles for reduction static electricity build
up. This makes inspection for cracks or crevices more difficult therefore use enough light. The
This document is for Vopak internal use only and should not be distributed outside Vopak
Welded parts
Metal roofs with welds shall be checked for pitting, and broken welds. Often cracks in welds can
not be found by the eye and therefore require NDT techniques. Reference is made to Vopak
Tank Maintenance and Inspection minimum standard on required NDT techniques for metal
roofs.
Seals:
Primary seals can only be inspected from underside, secondary seal from upside. This means
when using double seals half of the seal area can not be inspected. It is good to understand this
is a risk. When in doubt, remove the secondary seal.
- Safety first: make sure the tank is safe to enter: legs are all vertical and touching the
floor; also the tank is gasfree. Be aware that product could be found in pontoons or
modules;
- Sufficient light. Inspection requires good light. Especially in pontoons and for GRE roof
(black colour);
- Clean roofs. Cracks, pitting holes, crevices, buckles, stressed areas etc can much
better be found at clean surfaces;
- Product can be found trapped in roof legs and shall be checked;
- Support the IFR in such a way that it’s legs can not collapse.
In IFR tanks, there are two confined spaces – below and above the roof. Entry to both locations
must be regulated or controlled under confined space requirements.
Inspect seals especially on wear and tear and aging of non metallic parts as vapour barriers for
gas tightness.
This document is for Vopak internal use only and should not be distributed outside Vopak
Seal
Preferred seal to select is a liquid mounted Metallic (SS) shoe plate seal as this is BAT – Best
Available Technique. In case product resistance is a problem for this seal, other materials or
type can be selected.
IFR
As stated before, many different suppliers are on the market, providing many different detailed
differences. For selecting an IFR that meets Vopak minimum standards, an assessment of the
above mentioned selection criteria shall be used for each project. This document presents an
assessment based on the known Best Available Techniques per type of IFR. A picture of the
assessment tool can be found in appendix E. The tool itself is available via CoOpX intranet site.
The preferred solution has minimum life time cost (CAPEX & future OPEX together) in stead of
lowest CAPEX. For that focus on:
- Good design;
- Good materials;
- Material resistancy;
- Experienced installation crew;
- Maintenance & inspection;
- Ease of repair;
- Etcetera.
This document is for Vopak internal use only and should not be distributed outside Vopak
Select Acceptable
Regulations Y
Select only Full-Contact construction material for
require Full
roofs for the assessment product range in tank
Contact Roof?
Customer Y
requires Full
Contact Roof?
Other
requirements to Y
select Full
Contact Roof?
Select Best IFR option
F.e. operational
for project
END
Add Non contact roofs
to the assessment
In any case, apart from the above mentioned exceptions, an internal floating roof shall be
selected. In the following cases a full contact roof shall be selected:
- Customer discretion;
- Regulatory requirements;
- Other requirements (such as cleaning).
This document is for Vopak internal use only and should not be distributed outside Vopak
For new tanks this does not apply and in that case reference is made to Repeatable Formula
BB1 – Tanks and Tank pits.
note 1: Columns supported roofs are no longer allowed for new roofs according to Vopak Minimum Standard “Tank Design Manual”, however if
installed this must be addressed for the design of IFR.
Out of roundness is measured with a laser distance measurement device, called Theodolite,
positioned in the middle of the tank. Use of grid system as defined in EEMUA Appendix A 1-1 is
recommended.
Verticality of tank
When a tank is tilting, the liquid surface will form an oval instead of a circle. As long as the tilting
th
is limited to 1/100 of the height, this is acceptable. If the angle is more than this, seals can
sometimes not touch the tank shell anymore, with risk of vapours released above the roof.
This document is for Vopak internal use only and should not be distributed outside Vopak
This document is for Vopak internal use only and should not be distributed outside Vopak
All Bolts and nuts, clampbars, rings, U-bolts etc. shall be Stainless Steel.
In most cases a floating roof is resting on equally divided supports. If legs are connected to the
floating roof, the legs shall be adjustable in height for operational conditions (minimum dead
stock setting) and maintenance conditions (landed condition). For Steel IFRs the supports shall
land on patch plates welded on the bottom.
At the underside of the supports, PTFE end caps shall be used, well fixed to the supports.
In case a leg operated bleeder vent is used, and the roof has been designed with adjustable
legs, also the bleeder vent must have an adjustable leg.
For some floating roofs (seamless GRE), it is allowed to weld the legs to the tank bottom and
are not adjustable in height. Patch plates and reinforcements shall be used as well as a flexible
movable disc on to of the leg, carrying the roof.
In the following two situations a suspended roof can be added to the selection process:
- For products that are extremely difficult to clean the roof when on support legs;
- For some products no floating roof is required. In that case the roof can be suspended
at the top of the roof, until another product is put in the tank, which requires again an
IFR. Stainless steel cables shall be used for suspension;
- Because of regulatory reasons from local governments related to reduced emissions
(minimise dead stock for instance in USA).
This document is for Vopak internal use only and should not be distributed outside Vopak
10.3 Calculations
The supplier of the floating roof shall as a minimum hand over a set of calculation based on the
definitions and loads as defined in the applicable codes API 650 Appendix H or EN 14015
Annex C. As a minimum this means calculations must be made of:
- Buoyancy;
- Venting capacity during filling and emptying of tank with roof landed on legs;
- Stresses in construction based on several load cases;
- Buckling of legs (define maximum allowable angle of leg);
- Any point defined by Vopak as critical of which proof is required.
10.4 Mountings
For an overview of mountings on IFRs in tanks reference is made to Repeatable Formula BB1 –
Tanks and Tank pits.
A foam dam shall extend the highest point of the seal by at least 50 mm.
For IFRs in existing tanks it is important to select the type, number and position of the
mountings in such a way that the IFR can function and move freely.
10.5 Diffuser
A diffuser shall be installed on the main inlet gas slugs can enter a tank equipped with an IFR to
prevent damage of the IFR. A diffuser needs to be designed based on the typical operational
boundaries of that tank. The figure below shows a typical example of a diffuser
This document is for Vopak internal use only and should not be distributed outside Vopak
It is important to reiterate that pigging gas should be prevented from entering the tank in the first
place. The diffusers and IFR vents are acting as insurance IN CASE gases get in. The terminal
should never allow that a diffuser gives the license to allow gases into the tank.
Floating suction units are connected to the underside of the floating roof. If in any case dirt like
rust, sand or water (condensation) is collected in the product it will settle to the bottom. The
floating suction unit will displace the liquid level just beneath this floating roof. The
contamination is much less likely to be pumped out of the tank this way. It is often used for jet
fuels like Kerosene and Avgas.
10.7 Earthing
Most rim fires started due to electrical discharge between IFR and shell. The potential difference
between a roof and the tank shell must be safeguarded by low electrical resistance of the roof
and the use of Stainless Steel multi-strand earthing or anti-static cables. These cables should
2
have a min cross section of 3 mm .
The electrical resistance between the tank shell and any part of the roof shall be maximum 100
MΩ when measured by an approved method. The cables must be connected or installed in a
manner so that maintenance inspection and testing can be carried out while the tank is in
service.
For non metal IFR’s the roof itself shall be able to convey electricity over its entire area and not
build it up, for example by adding carbon to the composition.
IFRs are meant to capture vapours from leaving the tank. During initial filling, it is unavoidable
that the dead stock collected under the roof is pushed through a vent, the bleeder vent and
collect above the IFR. This vent shall however automatically close when the roof is floating. An
IFR must always have a bleeder vent.
This document is for Vopak internal use only and should not be distributed outside Vopak
Before the start of construction the contractor shall hand over a quality document, in which
critical areas of the IFR installation which can influence the quality of the roof are described.
Examples:
The contractor installing the IFR shall frequently inspect the IFR during construction. Any defect
or damage shall be solved before the hand-over to Vopak.
This document is for Vopak internal use only and should not be distributed outside Vopak
Other roofs
For other roofs, supplier must follow content of this document.
This document is for Vopak internal use only and should not be distributed outside Vopak
12.1 CAPEX
The following overview can be given as estimate CAPEX for 36 m tank (base date 2007). For
each project actual prices shall be received from suppliers, since material prices, location,
currency rates etc. can vary strongly over time.
12.2 OPEX
Next to the CAPEX, the sum of future OPEX is essential to analyse. Steel roofs shall be
sandblasted and painted after a period of time (average 15 – 20 years).
All seals have fabric or rubber parts or components and are therefore, subject to brittleness or
aging over time. Therefore the lifetime hardly ever exceeds 10 years.
History shows that Aluminium non contact pontoon type roofs are subject to repair more often
for pontoons and skin.
This document is for Vopak internal use only and should not be distributed outside Vopak
This type of roof is designed with the deck floating above the liquid surface and supported by
closed pontoon compartments (normally tubular pontoons). The roof deck is designed utilizing
a small light weight girder, aluminum sheeting of a minimum 0.020” thickness and a rim utilizing
a light weight aluminum skirt material. Pontoons are the main structural support for the roof
normally containing support gussets on the ends of the pontoons for connecting to other
pontoons and support leg assemblies.
This type of roof is designed with the deck floating above the liquid surface and supported by
closed pontoon compartments (normally tubular pontoons). The roof deck is designed utilizing
a taller and wider support girders, cross girders, aluminum sheeting of a minimum 0.025
thickness and an outer rim utilizing an extruded aluminum channel. Pontoons are not the main
structural support for the roof and are not connected by support gussets or support leg
assemblies. Support legs are installed at the junction of main support girders and cross girders.
- Higher in cost than the conventional aluminum skin and pontoon IFR, cost normally falls
between a conventional skin & pontoon aluminum IFR and a full contact aluminum IFR;
- Installation is similar to the conventional aluminum and faster than other aluminum and
steel type roofs, all components of this roof will normally fit through a 24” shell manway.
Minimal welding (anti-rotation cable connections) is required for installation;
- Caution must be taken prior to any repairs in the tank to verify that the pontoons do not
contain product or product vapors. Due to possible pin holes that may occur from
corrosion;
This document is for Vopak internal use only and should not be distributed outside Vopak
This type of roof is designed with the deck floating above the liquid surface and supported by
closed pontoon compartments (normally tubular pontoons). The roof deck is designed utilizing
aluminum girders and aluminum sheeting. All wet able parts such as pontoons, pontoon straps,
leg housing assemblies, outer rim of the roof, drain tubes, column wells, float wells manway
skirts etc. will all be designed utilizing austenitic stainless steel materials. If leg support all
support legs will be of an austenitic stainless material. The overall design can be either a
conventional or heavy duty type IFR.
This type of roof is designed with the deck floating above the liquid surface and supported by
closed pontoon compartments (normally tubular pontoons). This roof is designed with all the
components being fabricated from austenitic stainless steel materials. It is higher than all of the
aluminum roofs and may fall close to the cost of a steel pontoon IFR. It is mainly used in areas
in which the stored product will be corrosive to aluminum and/or carbon steel. Also it has been
utilized in tanks in which the product will be corrosive to aluminum but a quick installation is
required ruling out the installation of a carbon steel roof. As with all the skin and pontoon
floating roofs, all the components will fit through a 24” manway.
This document is for Vopak internal use only and should not be distributed outside Vopak
- Less costly than steel type roofs, more in line with the cost of aluminum skin and
pontoon type IFR;
- Installation is faster than steel type roofs, foam core panels are bolted together instead
of being welded. Minimal welding (anti-rotation cable connections) is required for
installation;
This document is for Vopak internal use only and should not be distributed outside Vopak
- Less costly than steel type roofs, slightly more expensive than an aluminum skin and
pontoon type IFR;
- Installation is faster than steel type roofs, honeycomb panels are bolted together
instead of welded. Minimal welding (anti-rotation cable connections) is required for
installation;
- Opening in the tank (large manway over 24”, door sheet or removed panels from either
a fixed or Geodesic dome roof) is required for the installation of the roof in order to set
the panels into the tank. The smaller the panels the more deck seams that will come
into play when calculating emissions;
- Caution must be taken prior to any repairs in the tank to verify that the panels do not
contain product or product vapors;
- Due to bolted panels, deck seam emissions become a factor in considering vapor
losses calculations;
- Can be equipped with a mechanical shoe seal, secondary wiper seal or double wiper
seal;
- Panels normally float approximately 1” – 2” depth in product, have a small outer rim to
support the seal system and will provide additional filling capacity to the tank;
- The roof can be cable suspended from the fixed roof or geodesic dome eliminating
vapor emissions from the leg housings. Cable suspending will also high and low leg
roof adjustments from outside of the tank;
- Caution should be taken to assure that the aluminum roof will be compatible with the
stored product. 100% aluminum type roofs should not be used when such products as
Methanol, Products containing chlorides, salts and caustic, water, slop water or other
corrosive type products to aluminum will be stored;
- Aluminum type roofs should not be hydrotested in water for long periods of time and
potable water should be used during the hydrotest.
This document is for Vopak internal use only and should not be distributed outside Vopak
Features:
- More expensive than Aluminum Non contact IFR;
- Full contact design, therefore better emission reduction;
- Very rigid;
- Resistant to many products normally stored in floating roof tanks;
- Seamless construction, with no bolt holes through deck; legs are welded to bottom to
support “disk”;
- Maintenance free, corrosion resistant;
- Designed to accommodate both a mechanical shoe primary seal and secondary seal;
- Roofparts can be brought in the tank by only one 24" manway for access;
- Very high buoyancy, gas tight, leak proof;
- Strong enough to withstand pigging, light-end slugs and high filling rates;
- Fully engineered, tested and field proven;
- Low profile, minimal loss of storage capacity;
- Fire resistant although applicable standards say fire fighting systems for non-metallic
roofs shall be designed to cope with full service fire, while fire fighting systems of
metallic IFR’s shall only be designed to cope with rim fire;
- Roof can be cable suspended.
This document is for Vopak internal use only and should not be distributed outside Vopak
This document is for Vopak internal use only and should not be distributed outside Vopak
* Some good references are available around the company with storing ethanol in aluminium
tanks. Resistance depends on concentration of ethanol with water and other contaminations.
This table is indicative only; it does not free the user from verifying the chemical resistance
against exact used materials and the stored products, during design or MOC.
This document is for Vopak internal use only and should not be distributed outside Vopak
This document is for Vopak internal use only and should not be distributed outside Vopak
This document is for Vopak internal use only and should not be distributed outside Vopak
This document is for Vopak internal use only and should not be distributed outside Vopak