Mk8MMInstall Comm Guide 1
Mk8MMInstall Comm Guide 1
Mk8MMInstall Comm Guide 1
Mk8 MM
Installation and
Commissioning Guide
Mk8 MM
Installation and Commissioning Guide
Issued by:
AUTOFLAME ENGINEERING LTD
Unit 1-2, Concorde Business Centre
Airport Industrial Estate, Wireless Road
Biggin Hill, Kent TN16 3YN
Registered Holder:
Company:
Department:
A full statement of our business terms and conditions are printed on the reverse of all
invoices. A copy of these can be issued upon application, if requested in writing.
The System equipment and control concepts referred to in this Manual MUST be installed,
commissioned and applied by personnel skilled in the various technical disciplines that
are inherent to the Autoflame product range, i.e. combustion, electrical and control.
The sale of Autoflame’s systems and equipment referred to in this Manual assume that
the dealer, purchaser and installer has the necessary skills at his disposal. i.e. A high
degree of combustion engineering experience, and a thorough understanding of the
local electrical codes of practice concerning boilers, burners and their ancillary systems
and equipment.
Autoflame’s warranty from point of sale is two years on all electronic systems and
components.
One year on all mechanical systems, components and sensors.
The warranty assumes that all equipment supplied will be used for the purpose that
it was intended and in strict compliance with our technical recommendations. Auto-
flame’s warranty and guarantee is limited strictly to product build quality, and design.
Excluded absolutely are any claims arising from misapplication, incorrect installation
and/or incorrect commissioning.
Contents
1 DIMENSIONS AND WIRING .................................................................................... 1
1.1 Mk8 MM ................................................................................................................................. 1
1.1.1 Fixing Holes and Dimensions ........................................................................................... 2
1.2 Wiring Schematic ..................................................................................................................... 3
1.2.1 Mk8 MM ......................................................................................................................... 3
1.2.2 Mk8 Expansion Board ..................................................................................................... 4
1.2.3 Fuse Ratings ..................................................................................................................... 5
1.3 Electrical Specifications ........................................................................................................... 6
1.3.1 MM Inputs and Outputs ................................................................................................... 6
1.3.2 Expansion Board Inputs and Outputs .............................................................................. 7
1.3.3 Cable Specifications ........................................................................................................ 8
1.3.4 MM Terminals Description ...............................................................................................9
1.3.5 Expansion Board Terminals Description........................................................................ 13
1.4 Connection Between Mk8 MM and Mk8 EGA EVO ............................................................ 16
1.5 Connection Between Mk8 MM and Mk7 DTI ....................................................................... 17
1.6 Sequencing Connection Diagram ......................................................................................... 18
2 OPTIONS AND PARAMETERS ................................................................................. 19
2.1 Options ................................................................................................................................. 19
2.2 Parameters ............................................................................................................................ 42
2.3 Expansion Options ............................................................................................................... 51
3 COMMISSIONING FUEL-AIR CURVE ....................................................................... 69
3.1 Overview .............................................................................................................................. 69
3.2 Installation Checks ................................................................................................................ 70
3.2.1 Commissioning Checks.................................................................................................. 70
3.2.2 Operational Checks ...................................................................................................... 70
3.2.3 Installation Precautions ................................................................................................. 70
3.2.4 Maintenance and Servicing .......................................................................................... 70
3.3 Servomotors.......................................................................................................................... 71
3.3.1 Adjusting the Servomotor Potentiometer....................................................................... 71
3.3.2 Servomotor Feedback Voltage ..................................................................................... 72
3.3.3 Servomotors – Direction Change.................................................................................. 73
3.3.4 Servomotors with Autoflame Valves ............................................................................. 74
3.4 Commissioning Fuel and Air Positions................................................................................... 75
3.4.1 Starting Commissioning ................................................................................................ 76
3.4.2 Enter CLOSED Position ................................................................................................. 77
3.4.3 Enter OPEN Position ..................................................................................................... 78
3.4.4 Set up START Position ................................................................................................... 79
3.4.5 Phase Hold ................................................................................................................... 80
3.4.6 Add Trim Data During Commissioning .......................................................................... 81
3.4.7 Commissioning VSD ...................................................................................................... 83
3.4.8 Set GOLDEN START Position ........................................................................................ 84
3.4.9 Set FGR Position ........................................................................................................... 86
3.4.10 Set HIGH Position ......................................................................................................... 88
3.4.11 Set INTER Position......................................................................................................... 89
3.4.12 Set INTER or START Position ......................................................................................... 90
3.4.13 Save Commission .......................................................................................................... 91
3.5 Fuel Flow Metering ............................................................................................................... 92
3.5.1 Commissioning Fuel Flow Through MM ........................................................................ 92
3.5.2 Commissioning Fuel Flow Through 4-20mA Feedback ................................................. 94
3.5.3 Calorific Fuel Data ........................................................................................................ 95
3.5.4 Conversion Factor for Imperial Gas Flow Meters ......................................................... 96
3.5.5 Correction Factor for Burners Significantly Above Sea Level ....................................... 96
3.5.6 Gas Volume Conversion Factors ................................................................................... 97
3.6 Gas/ Air Pressure Commission ............................................................................................. 99
3.7 Single Point Change ........................................................................................................... 100
3.8 Online Changes .................................................................................................................. 105
4 ERRORS AND LOCKOUTS .................................................................................... 106
4.1 Errors .................................................................................................................................. 106
4.2 Lockouts .............................................................................................................................. 110
4.3 Alarms and Warnings ......................................................................................................... 115
4.4 Settings Conflicts ................................................................................................................. 123
4.5 Forced Commission Reasons............................................................................................... 128
4.6 Troubleshooting and Further Information ........................................................................... 130
4.6.1 UV Shutter Faults ........................................................................................................ 130
4.6.2 UV Problems ............................................................................................................... 130
4.6.3 Snubbers ..................................................................................................................... 130
4.6.4 Channel Positioning Error ........................................................................................... 131
4.6.5 Input Fault ................................................................................................................... 131
5 STANDARDS ....................................................................................................... 132
1 Dimensions and Wiring
1.1 Mk8 MM
1.2.1 Mk8 MM
Protection The unit is designed to be panel mounted in any orientation and the front facia is IP65,
Rating: NEMA4. The back of the unit is IP20, NEMA1.
230V Unit:
Outputs Terminal 57 250mA Must be connected through contactor
58 250mA Must be connected through contactor
59 1A 0.6 power factor
60 1A 0.6 power factor
61 1A 0.6 power factor Max Load 6A
62 1A 0.6 power factor
63 1A 0.6 power factor
78 100mA To drive relay only – switched neutral
79 100mA To drive relay/lamp only – switched neutral
120V Unit:
Outputs Terminal 57 250mA Must be connected through contactor
58 250mA Must be connected through contactor
59 2A 0.6 power factor
60 2A 0.6 power factor
61 2A 0.6 power factor Max Load 6A
62 2A 0.6 power factor
63 2A 0.6 power factor
78 100mA To drive relay only – switched neutral
79 100mA To drive relay/lamp only – switched neutral
Note:
1. The high and low voltage connections are not safe to touch. Protection against electric shock is
provided by correct installation. CAUTION – ELECTRIC SHOCK HAZARD.
2. Control voltage cabling should be maximum 10m, screened (if not screened then less than 1m,
however servomotors can be unscreened up to 10m)
3. Any cabling over 10m must have additional surge protection.
4. Low voltage cables should be screened cable as specified in section 1.3.3.
5. The burner ‘High Limit Stat’ must be a manual reset type.
Note: There is a lid (back plate) fitted onto the back of the Mk8 MM with a Warning label to prevent
any unauthorised fuse replacements.
Outputs: 120/230 V All outputs with the exception of PF are switched neutrals
Note: Max number of alarm indicators on at any time is 3 (1LV, 2LA, 2LV)
Low Voltage
The screened cable used for low voltage wiring from the MM to the servomotors, detectors and
variable speed drive must conform to the following specification:
U.V. cable length should not exceed 25m, all other screened cable should not exceed 50m.
Use the number of cores suitable for the application. A universal part numbering system appears to
have been adopted for this type of cable as follows:
16-2-2C 2 Core
16-2-3C 3 Core
16-2-4C 4 Core
16-2-6C 6 Core
16-2-8C 8 Core
Note: If using 4 Core cable and interference is detected, use 2 sets of 2 Core.
Data Cable
Data cable must be used for communication connections between MMs for sequencing applications as
well as between MMs to EGAs, MMs to a DTI and DTI to BMS systems.
Samples are available upon request. Low voltage and data cable can be ordered directly from
Autoflame Engineering, please contact Autoflame Sales.
When using a VSD, please review the manufacturer’s guidelines on installations to prevent EMC
including the recommendations for reactors and filters.
S All terminals marked S are internally connected. They are provided for connections
to the various screened cables.
1 Current Input, 0-20mA/ 4-20mA. For channel 5 only. Can be connected to the
current output of a VSD or tachometer system or 4-20mA servomotor feedback
2 Voltage Input, 0-10V. For channel 5 only. Can be connected to the voltage output
of a VSD or tachometer system
4 Current Input, 0-20mA/ 4-20mA. For channel 6 only. Can be connected to the
current output of a VSD or tachometer system or 4-20mA servomotor feedback
5 Voltage Input, 0-10V. For channel 6 only. Can be connected to the voltage output
of a VSD or tachometer system
7 Current Input, 4-20mA. Used for external modulation or external required setpoint
8 Voltage Input, 2-10V. Used for external modulation or external required setpoint
10 Current Output, 0-20mA/ 4-20mA. For channel 5 only. Can be connected to the
current input of a VSD or tachometer system or 4-20mA servomotor feedback
11 Voltage Output, 0-10V. For channel 5 only. Can be connected to the voltage input
of a VSD or tachometer system
13 Current Output, 0-20mA/ 4-20mA. For channel 6 only. Can be connected to the
current input of a VSD or tachometer system or 4-20mA servomotor feedback
14 Voltage Output, 0-10V. For channel 6 only. Can be connected to the voltage input
of a VSD or tachometer system
34 +12V supply to an Autoflame air pressure sensor and/or Autoflame gas pressure
sensor
52 Mains voltage input – external auxiliary delay to purge/ secondary proving set in
option/parameter 157
55 Mains voltage input - proving circuits, e.g. gas valve proof of closure
81 Purge position interlock/ delay purge time (selectable via option 155)
85 Mains voltage input. For use when using an external flame switch- 0V when at no
flame state
86 Mains voltage input. For use when using an external flame switch- line voltage
when at no flame state
87 Mains voltage input. Select second required setpoint- second set-point facility
88 Mains voltage input. Lead boiler select (overrides DTI) / Local – remote PID select
for external modulation
89 Mains voltage input – selects fuel 1 curve
93 Mains voltage input – warming start or night setback input (selectable via option
79)
94 Mains voltage input – selects hand operation (overrides mode set on MM screen)
95 Mains voltage input – selects low flame hold operation (overrides mode set on
MM screen)
S All terminals marked S are internally connected. They are provided for connections
to the various screened cables.
EX+ Current input, 4-20mA for external water level probe or fuel flow feedback
DP- 0V supply to draft control pressure sensor and draft control servomotor
DP+ +12V supply to draft control pressure sensor and draft control servomotor
5T+, 5T- Digital communications from bottom blowdown module and 2nd low probe
TST System test alarm inputs/ shunt switch (selectable via expansion option 21)
FUEL 1 BROWN
FUEL 2 RED
FUEL 3 YELLOW
FUEL 4 GREEN
BLUE
VIOLET
BLACK
SCREEN
BLACK
RED
DATA CABLE
CONTROL
FUSE
2.1 Options
The Options, Parameters and Expansion Options must only be changed by factory
trained and certified technicians who have a thorough appreciation of the Autoflame
combustion systems and the combustion process in general. Any person changing these
settings without the correct factory training and understanding of the boiler plant may
place themselves and others in a potentially dangerous situation.
CH1, CH2, CH3, CH4, CH5, CH6 and CH7 refer to the rows of buttons respectively
starting with CH1 at the top.
The options, parameters and expansion options and their settings are all viewable while the MM is in
run mode. In commissioning mode, all of the options, parameters and expansion options can be
adjusted according to the application. Non safety-critical options, parameters and expansion options
can be adjusted through Online Changes.
Power up the unit. If the MM has already been commissioned, press when the system
starts up. If the system is not already commissioned, the MM will go into commissioning mode
automatically.
“Enter Commissioning Password” is displayed. Use the keypad to enter the password, then press
Note: The commissioning password should not be distributed to anyone who is not a factory trained
and a certified engineer.
Note: The Times Commissioned is for the total system and will increment with every fuel commission,
single point change and commission data upload.
Press in the Commission Mode screen to access the Options. Any number of options/
parameters can be changed at one time. By pressing MM, PID, EGA, DTI or BC at the bottom of the
screen, the options/ parameters can be grouped together by feature.
When the changes have been made to suit the application’s needs, press Exit to go back to the
Commission Mode screen.
Options/ parameters 110 – 160 are the burner control settings and are safety critical; these must be
entered the same for both the option and parameter value. If these BC options and parameters do not
match, there will be an option/parameter conflict.
To set all the options, parameters and expansion options to the default values and erase the
commissioning data, set option/ parameter 160 to 5. The MM will then automatically restart and go
into Commission mode.
3 - Unused
4 - Unused
5 1 Purge Position
This purge position applies to channels 1-4 as selected in options 67-70,
however VSD channels will always purge at open position as default. This
setting applies for post-purge if set, see option/ parameter 118 and 135.
0 Channels 1 to 4 purge at HIGH position.
1 Channels 1 to 4 purge at OPEN position.
6 10 Proportional Band
The proportional band is on offset below the required setpoint; when the
actual temperature/ pressure reaches this band, the burner will begin to
modulate as it approaches the required setpoint.
5 – 2000 O
C, OF, PSI or 0.1 bar or 0.01 bar for low pressure sensor (depends on
load detector set in option 1 and metric/imperial units set in parameter 40)
7 60 Integral Time
Every ‘n’ seconds, 10% of the present offset from the required setpoint is
added or subtracted when below or above the setpoint, respectively, to the
present proportional value. The value of ‘n’ is the number of seconds set in
this option; if set to 0, there will be no integral control.
0 Disabled
1 – 250 Seconds
8 0 Servomotor Channels
Channel 1 is always enabled for fuel; this option sets the channels in use.
0 Channels 1 & 2
1 Channels 1, 2 & 3
2 Channels 1, 2, 3 & 4
Note: If option 8 is changed after commissioning, then the MM will need to
be re-commissioned, unless this option is returned to its previous setting.
12 0 EGA Functionality
For settings 2 or 3, the E.G.A will trim on the channel 2 air damper, once
trim data has been added. If option 12 is set to 0 or 1, then trim can be
added at a later date by changing this to 2 or 3 in online changes, going
through single point change, and added trim data for each fuel-air position.
0 Not optioned
1 Monitoring only
2 Applies trim
3 Applies trim, combustion limits tested
14 1 Warning Response
0 Warnings do not drive common system alarm output (terminal 79)
1 Warnings drive common system alarm output (terminal 79)
15 3 User Control
This option sets whether the use can turn the burner on and off, or change
the required setpoint via the flame screen on the MM
0 Burner on/off and setpoint control disabled
1 Burner on/off disabled and setpoint control enabled
2 Burner on/off enabled and setpoint control disabled
3 Burner on/off and setpoint control enabled
17 - Unused
24 - Unused
25 0 O2 Absolute Limit
If the current O2 value is below this absolute limit, an alarm/ warning (see
option13) will occur, for option 12 set to 3.
0 Disabled
1 – 200 0.1% - 20.0% O2
27 0 CO Absolute Limit
If the current CO value is above this absolute limit, an alarm/ warning (see
option13) will occur, for option 12 set to 3.
0 Disabled
1 – 200 1 – 200 ppm CO
28 20 Trim Threshold
The trim threshold is an offset from the required setpoint; if the actual value
is below this offset, then the EGA will not trim. This option should be set to 0
if trim is to be effective at all times during firing, and/or if external
modulation is optioned. No single point changes can be made if the actual
value is below this trim threshold.
0 – 50 O
C, OF, PSI or 0.1 bar or 0.01 bar for low pressure sensor (depends on
load detector set in option 1 and metric/imperial units set in parameter 40)
29 0 Golden Start
Golden start allows an optimum ignition position to be set in the fuel-air
curve, which is not necessarily low flame or part of the standard modulating
index. Parameter 15 sets how long golden start is maintained from the
point of main flame.
0 Disabled
1 Enabled
32 20 Trim Delay
After ignition, the EGA does not sample for the time delay set in this option
(if EGA is set to 2 or 3). This allows for the combustion to stabilise before
sampling commences. The delay timer starts at the ignition point.
0 – 250 Seconds
33 1 MM Identification
Each MM within a sequencing/ DTI/ Modbus/ twin burner loop must be set
with an individual ID number. For communications between the MMs, there
cannot be more than 1 MM with the same ID number.
1 – 10 ID number
34 - Unused
37 0 Derivative Time
The time taken to add/ remove an additional 10% to the firing rate based
on the actual value and the required value.
0 Disabled
1 – 200 Seconds
38 2 Derivative Deadband
This deadband is the margin above and below the required setpoint in
which no derivative control occurs.
0 Disabled
1 - 15 O
C, OF, PSI or 0.1 bar or 0.01 bar for low pressure sensor (depends on
load detector set in option 1 and metric/imperial units set in parameter 40)
39 - Unused
41 0 Warming Mode
For setting 0, the first lag is kept in a standby state with the second lag in
warming, and the remaining lag boilers off. For setting 1, the first lag boiler
is in standby, and the remaining lag boilers are in warming.
0 One MM in warming state
1 All unused MMs in warming state
42 20 Standby Setpoint
For sequencing applications where non-return valves are installed, the first
lag boiler uses a standby setpoint to keep the boiler in a standby condition.
The standby setpoint is set as an absolute value in this option. When the
standby setpoint is in effect, the burner is held at low flame hold.
5 – 9990 O
C, OF, PSI or 0.1 bar or 0.01 bar for low pressure sensor (depends on
load detector set in option 1 and metric/imperial units set in parameter 40)
43 0 Multi-Burner Function
The multi-burner function can be used for up to 10 burners, allowing the
firing rates to be synchronised for all the burners in the multi-burner loop.
For setting 1, if an error or lockout occurs on a burner, all of the other
burners will shut down; setting 1 is suitable for firetube boilers. For setting
2, if an error occurs on a burner, all if the other burners will shut down,
however if a lockout occurs, the other burners will continue to fire; setting 2
is suitable for watertube boilers. Fuel flow metering must be commissioned
accurately for the multi-burner function to operate. Please refer to the MM
Application Possibilities manual for commissioning of the multi-burner
function.
0 Disabled
1 Fully linked
2 Independent fault
44 1 Multi-Burner Id
When using the multi-burner function, the multi-burner IDs must be set on the
MMs This option should be set to 1 for the master, and 2 onwards for the
slave MMs.
1 – 10 Multi-burner Id
45 0 External Modulation
When enabled, the internal PID control is disabled and the firing rate is set
by an external controller applied to the appropriate input terminals 7, 8, 9.
This input control signal can be 0-10V (2-10V) or 4-20mA (0-20mA) set
through parameter 69, and represent zero/ low to high fire by setting
parameter 68. A manual reset high limit stat must be fitted. For setting 1, an
external working stat is required and option 9 should be set to 0. For
setting 2, option 9 should be set to 1 or 2.
0 Disabled
1 Enabled, load sensor not shown
2 Enabled, load sensor shown
52 - Unused
58 - Unused
65 - Unused
73 - Unused
74 - Unused
76 0 Trim Channel
If an EGA is optioned, then trim can be applied to either channel 2
servomotor or channel 5 VSD. For setting 1, options 91 to 98 must be set.
0 Trim on Channel 2
1 Trim on Channel 5
77 - Unused
78 - Unused
For safety reasons, options 110 – 160 also have to be entered in as Parameters. It is the responsibility
of the commissioning engineer to ensure that all settings are set in accordance with the appropriate
standards, local codes and practices. If options 110 – 160 are not identical with the parameters 110 –
160, then the MM will go straight to Commissioning Mode and an option/ parameter conflict message
will appear.
116 3 Gas Second Safety Time – Main Trial for Ignition (MTFI)
This is the time period when the main valves are open and the pilot valve is
maintained open, before the flame is checked, for firing on gas. See
option/ parameters 150 – 153. This does not apply for intermittent pilot,
see option/ parameter 111. For firing on oil, see option/ parameter 123.
3 – 10 Seconds
120 10 UV Threshold
This is the minimum flame signal strength, if the flame strength is lower than
this threshold, a lockout will occur. The UV counts will stabilise at 5 times
this value when increasing, and 3 times this value when decreasing.
5 – 50 UV counts
123 3 Oil Second Safety Time – Main Trial For Ignition (MTFI)
This is the time period when the main valves are open and the pilot valve is
maintained open, before the flame is checked, for firing on oil. See option/
parameters 150 – 153. This does not apply for intermittent pilot, see
option/ parameter 111. For firing on gas, see option/ parameter 116.
3 – 15 Seconds
131 - Unused
138 - Unused
143 0 No Pre-Purge
For setting 1, there will only be no pre-purge if the burner has recycled due
to meeting operational temperature/ pressure, and the system has gone
through VPS checks successfully. If the burner has a lockout, or is restarting
after a lockout has been cleared, then the MM will force a pre-purge. No
pre-purge is only available when the fuel is set to gas.
0 Enabled
1 Disabled
146 - Unused
156 - Unused
159 - Unused
2.2 Parameters
Press in the Commission Mode screen to access the Parameters. Any number of
options/ parameters can be changed at one time. By pressing MM, PID, EGA, DTI or BC at the bottom
of the screen, the options/ parameters can be grouped together by feature.
When the changes have been made to suit the application’s needs, press Exit to go back to the
Commission Mode screen.
Options/ parameters 110 – 160 are the burner control settings and are safety critical; these must be
entered the same for both the option and parameter value. If these BC options and parameters do not
match, there will be an option/parameter conflict.
To set all the options, parameters and expansion options to the default values and erase the
commissioning data, set option/ parameter 160 to 5. The MM will then automatically restart and go
into Commission mode.
Para-
Default Range Description
meter
2 - Unused
5 4 Modulation Timeout
If a sequenced MM does not start modulating after being asked to by the
lead MM, it is ignored in the sequencing loop. Upon the next scan time, if
the MM modulates as required, it will be included in the sequencing loop.
1 – 50 Minutes
6 - Unused
7 - Unused
9 - Unused
10 2 EGA Version
0 Mk7 (For use with Mk7 EGA)
1 Mk8 Rev.3 (For use with Mk8 EGA)
2 Mk8 (For use with Mk8 EGA EVO)
11 - Unused
Para-
Default Range Description
meter
20 - Unused
21 - Unused
22 - Unused
25 - Unused
27 - Unused
28 - Unused
Para-
Default Range Description
meter
32 - Unused
33 - Unused
34 - Unused
35 - Unused
36 - Unused
37 - Unused
40 0 Display Units
0 Metric units
1 Imperial units
44 - Unused
45 - Unused
Para-
Default Range Description
meter
46 - Unused
47 - Unused
48 80 Integral Band
This is the percentage of the proportional band over which the integral
control is active.
0 – 100 0% - 100%
49 - Unused
50 - Unused
51 - Unused
57 10 Highest MM ID
This sets the highest MM ID number for that sequence or DTI loop.
1 –10 Sequence ID
59 - Unused
Para-
Default Range Description
meter
63 - Unused
64 - Unused
65 - Unused
66 - Unused
67 - Unused
Para-
Default Range Description
meter
73 - Unused
74 - Unused
75 - Unused
76 - Unused
77 - Unused
78 - Unused
79 - Unused
80 - Unused
81 - Unused
82 - Unused
84 - Unused
Para-
Default Range Description
meter
90 - Unused
91 - Unused
92 - Unused
93 - Unused
95 - Unused
98 - Unused
99 1 Graceful Shutdown
If enabled, when the fuel is deselected, the fuel valve outputs are de-
energised, and then a post-purge occurs before the MM restarts. This must
not be used if changeover relays are used on the system. Graceful
shutdown cannot be used with assured low fire shut off in parameter 100.
0 Disabled
1 Enabled
102 - Unused
103 - Unused
Para-
Default Range Description
meter
104 - Unused
105 - Unused
106 - Unused
109 - Unused
Parameters 110 – 160 are a repeat of their corresponding options, and will need to be entered the
same.
It is the responsibility of the commissioning engineer to ensure that all settings are set in accordance
with the appropriate standards, local codes and practices. If options 110 – 160 are not identical with
the parameters 110 – 160, then the MM will go straight to Commissioning Mode and an option/
parameter conflict message will appear.
Press in the Commission Mode screen to access the Expansion Options. Any number of
expansion options can be changed at on time. By pressing WLC, TBD, BBD, DC, Modbus FO and Flow
at the bottom of the screen, the expansion options can be grouped together by feature.
To change the expansion options, the relevant expansion feature must be unlocked. See Mk8 MM
Expansion Features Installation and Commissioning Guide for more information.
When the changes have been made to suit the application’s needs, press Exit to go back to the
Commission Mode screen.
To set all the options, parameters and expansion options to the default values and erase the
commissioning data, set option/ parameter 160 to 5. The MM will then automatically restart.
Note: The Expansion Feature must be unlocked by sending the code for that MM via
Download Manager. Please see PC Software Guide on unlocking Expansion Features.
Exp
Default Range Description
Option
3 0 Capacitance Probes
If water level control is enabled, the MM will require a minimum of two
level sensing elements. For the possible water level sensing device
combinations, please see section 3.3.
0 Capacitance probes disabled
1 One capacitance probe
2 Two capacitance probes
Exp
Default Range Description
Option
Exp
Default Range Description
Option
Exp
Default Range Description
Option
Exp
Default Range Description
Option
Exp
Default Range Description
Option
33 - Unused
34 - Unused
35 - Unused
36 - Unused
37 - Unused
38 - Unused
39 - Unused
41 0 TDS Units
The TDS units can be displayed in ppm or μS/cm.
0 Concentration in ppm
1 Conductivity in μS/cm
Exp
Default Range Description
Option
47 10 Pressure Threshold
This pressure threshold is an offset below the required pressure setpoint. If
the actual pressure is below this offset pressure, then TDS control will not
operate.
0 Disabled
1 – 100 PSI or 0.1 bar or 0.01 bar for low pressure sensor (depends on load
detector set in option 1 and metric/imperial units set in parameter 40)
48 25 Sample Time
The first stage of the TDS control cycle is the sample time, where the
solenoid valve or top blowdown servomotor is fully opened to take a
sample.
2 – 60 Seconds
49 25 Settle Time
The second stage of the TDS control cycle is the settle time. Following taking
a sample time in expansion option 48, the solenoid valve or top blowdown
servomotor goes fully closed to allow the sample to stabilise for this settle
time.
2 – 60 Seconds
50 10 Measurement Time
The third stage of the TDS control cycle is the measurement time. Following
the settle time in expansion option 49, TDS probe will a measure the TDS in
the sample every second set in the measurement time. The average across
these measurements is taken as the TDS reading for that cycle. A longer
measurement time will allow an average to be taken over more TDS probe
measurements, and so the TDS readings will be smooth.
2 – 30 Seconds
Exp
Default Range Description
Option
54 5 Derivative Time
For water level with a quickly changing TDS value in the water, a derivative
time can be added to prevent overshoot.
0 Disabled
1 – 1000 Seconds
56 - Unused
57 - Unused
58 - Unused
59 - Unused
Exp
Default Range Description
Option
65 - Unused
66 - Unused
67 - Unused
68 - Unused
69 - Unused
70 - Unused
71 - Unused
72 - Unused
73 - Unused
74 - Unused
75 - Unused
76 - Unused
77 - Unused
78 - Unused
79 - Unused
Exp
Default Range Description
Option
84 1 Maximum Compensation
The maximum compensation angle is the percentage of the commissioned
draught servomotor angle. This is the maximum correction on the stack
damper either forwards or backwards, during draught control.
0 10%
1 15%
2 20%
Exp
Default Range Description
Option
91 5 Integral Time
For a slower response to the changes in draught air pressure, increase the
integral time. For a quicker response, decrease the integral time.
1 – 1000 Seconds
92 - Unused
93 - Unused
94 - Unused
95 - Unused
96 - Unused
97 - Unused
98 - Unused
99 - Unused
Exp
Default Range Description
Option
106 - Unused
107 - Unused
108 - Unused
109 - Unused
111 - Unused
112 - Unused
113 - Unused
114 - Unused
115 - Unused
116 - Unused
Exp
Default Range Description
Option
117 - Unused
118 - Unused
119 - Unused
Exp
Default Range Description
Option
130 - Unused
131 - Unused
132 - Unused
133 - Unused
134 - Unused
135 - Unused
136 - Unused
137 - Unused
138 - Unused
139 - Unused
Exp
Default Range Description
Option
Exp
Default Range Description
Option
Exp
Default Range Description
Option
158 - Unused
159 - Unused
160 - Unused
3.1 Overview
Important Note: Prior to commissioning, the fuel and air servomotors must be calibrated to ensure
that the position of the valves and damper correspond to the potentiometer feedback signal as
displayed on the MM. When the valve is fully closed, the MM should display zero degrees. If it does
not, please adjust the servomotor potentiometer.
The fundamental idea of the system is to set a fuel valve position and then set a
corresponding air damper position. Care must be taken when adjusting the fuel and air
positions so as not to create any unstable or hazardous combustion conditions, e.g.
moving the fuel valve to the open position without increasing the air damper position.
Improper use may result in property damage, serious physical injury or death.
If the MM is commissioned without an EGA then a combustion analyser is required to check the
exhaust gases. If the system does have an EGA, then a combustion analyser is not necessary as the
EGA performs all normal exhaust gas measurements. When burning oil a smoke detection device is
also necessary to check that the smoke generated is within safe limits.
Once a start position has been entered, the high fire position is entered next, then descending fuel/air
positions are entered consecutively until finally the low fire position is entered. CH1 and CH2 positions
must always be less than the ones previously entered; however CH3 to CH7 can be set lower or higher
than the previous position. CH7 is used for the draught servomotor (unlockable expansion feature).
On a newly installed system the following procedures should be carried out as listed:
1. Check all interconnecting wiring between the MM and external components is correct.
2. Set options, parameters and expansion options required (refer to section 2).
3. Commission bottom blowdown module if optioned.
4. Commission water level probes and external level sensor if optioned (refer to Expansion
Features Installation and Commissioning Guide).
5. Set up servomotors.
6. Program fuel/air positions.
When all the installation and burner adjustments are completed, the entire burner control system
should be tested in accordance with the manufacturer’s instructions. The procedure should verify the
correct operation of:
The reliability of the equipment may be impaired if used in environments where strong electromagnetic
fields exist e.g. if the equipment is installed in a boiler house where radio systems exist then additional
EMC (Electro Magnetic Compatibility) measures may have to be considered. Please contact Autoflame
for more information.
The Micro-Modulation unit uses solid state technology. It requires no routine maintenance.
The servomotors/gas/oil/FGR valves do require routine maintenance. Any fault associated with these
parts is usually diagnosed by the MM. Contact Autoflame for preventative maintenance procedures,
please refer to the Valves and Servomotors manual for general checks.
3.3 Servomotors
Autoflame supply three standard sizes of servomotors – small, large and industrial, which can be used
for all channels. Autoflame fuel valves require small or large servomotors only. Both small and large
servomotors can be configured to drive clockwise or counter clockwise to open a valve or damper.
Servomotors can be installed in any orientation; 2 fixed rotation positions if using Autoflame valves.
For layout of the small, large and industrial servomotors please refer to the Valves and Servomotors
manual.
Viewing the shaft end-on, from the potentiometer end, all servomotors drive in a clockwise direction if
power is applied between the LIVE and CW terminals, and counter clockwise if the power is applied
between the LIVE and CCW terminal.
The operation of fuel valves and air dampers is often such that they open in a clockwise direction. If the
operation needs to be reversed, it is necessary to swap various wiring connections between the MM
and the servomotor(s). An example of reversing the operation of a servomotor is shown in Figure
3.3.3.
Note: Servomotors are supplied by the factory set at 0.0o position. Remember that this
position may not necessarily automatically position the damper at 0.0o or a closed
position. This must be physically checked. Failure to do so can result in serious injury or
death.
Before a burner is fired it is essential to set up each Micro-Modulation servomotor. A tamper proof
screwdriver is required (please contact Autoflame).
Usually control valves/air dampers that the servomotors drive, move through up to 90.0o angular
degrees. The MM system has the ability to drive valves through 360.0o degrees, but the MM will only
display from -6.0o to 96.0o degrees.
All Channel 1 to 4 and 7 readings displayed on the MM are in angular degrees. It is necessary to
adjust the potentiometer in the servomotor assembly so that the MM reads 0.0o when the relevant
valve/damper is at its fully closed position. The technician must physically check the mechanical
position of the dampers and valves, whilst all servomotors are set to 0.0o before leaving the factory this
may have changed during shipping. DO NOT ASSUME THEY HAVE BEEN PREVIOUSLY SET
CORRECTLY.
Put the MM into the commissioning mode and press CLOSE to position the valve/damper mechanically
by using the appropriate up and down buttons (see section 3.4.2).
**WARNING**
ELECTRICAL CONNECTIONS ARE LIVE/HOT AND INCORRECT APPLICATION MAY
RESULT IN SERIOUS PHYSICAL INJURY OR DEATH.
Use the channel 2 up/down buttons on the MM to position the air damper to its physically closed
position. Loosen the two tamper proof screws just enough to enable the potentiometer to rotate. Rotate
the potentiometer clockwise or counter clockwise until the relevant channel reads 0.0. Tighten the two
tamper proof screws gently until the potentiometer is secure. Do not over tighten the screws. Check that
the display still reads 0.0. If incorrect repeat the adjustment process.
On Autoflame gas, oil and gas/oil piggy-back valves it is necessary to remove the servomotor.
Manually position the oil/gas valve slot to its closed position. Observe the position of the drive pin on
the servomotor. Use the relevant channel up/down buttons to position the pin so that when the
servomotor is reassembled to the valve it is in line with the slot. Reassemble the servomotor to the
valve, loosen the two tamper proof screws and proceed to adjust the potentiometer position until 0.0o is
displayed. Use the external position indicator to ensure the valve is in the fully closed position.
In applications where the servomotor is not positioned close to the display then it is possible to measure
the feedback voltage from the servomotor in order to ensure that 0.0 degrees is displayed. By testing
the DC voltage between the blue and green wires (wiper and 0V) on the servomotor low voltage
terminals this will read 0.21V DC when the reading on the display is 0O. The same can be done for
when the servomotor is at 96.0O where the voltage will be 3.6V.
On threaded valves, the pin on the top of the valve is 90 degrees opposite from the position of the
butterfly valve.
On flanged valves, the pin on the top of the valve is in line with the position of the butterfly valve.
For both valves the external visual position indicator is in line with the position of the butterfly valve.
Regardless of the type of valve being used, the servomotor is dispatched from the factory with the
potentiometer in the zero position. The same servomotor will be correct for both types of valve, as the
servomotor for the threaded valve is mounted at 90 degrees different from the flanged valve.
The following procedure is shown for commissioning the EGA with option 12 set to 0 (Not Optioned),
or 1 (Monitoring only). Trim can be added later by setting option 12 to 2 (Applies trim) or 3 (Applies
trim, combustion limits tested). Please see section 3.7 for adding/adjusting the trim data later during
Single Point Change. If the EGA is optioned later in Online Changes, the MM will not require a full re-
commission; the trim data can be added in Single Point Change.
For option 12 set to 0 or 1 during commissioning, omit section 3.4.6. For option 12 set to 2 or 3 during
commissioning, please include section 3.4.6.
The fuel and air positions need to be programmed for the following points: CLOSED, OPEN, GOLDEN
START (if optioned), FGR START (if optioned), LOW FIRE (START), INTER POINTS, and HIGH FIRE.
There must be a minimum of 3 INTER points entered on the fuel-air curve, and a maximum of 18. Points
can be added/removed in Single Point Change mode (see section 3.7).
During commissioning the required setpoint is not active; the internal stat remains on at all times
regardless of the actual value. Ensure that the high limit stat is set correctly and wired into the recycling
interlock (T53), as this will turn the burner off in the event that the safe working maximum temperature
or pressure of the boiler is exceeded.
The high limit stat should be set below the rating of the safety valve, please see the manufacturer’s
guidelines for the safety valve for that boiler.
Note: If a fault occurs, the boiler goes above the high limit stat or power is lost to the MM during
commissioning, no data is stored. The points entered are only stored within the MM once the
commission has been completed.
Once the options, parameters and expansion options have been set, press on the
Commission Mode screen in Figure 2.1.ii. If the MM has already been commissioned, then press
Figure 3.4.1.i shows the Commissioning screen. In the Commissioning screen, the 7 channel positions
will be shown, with the unused channels greyed out.
Once the MM goes through its internal relay checks and VPS (if optioned), the message ‘Select
Commissioning’ will display.
The MM is now waiting for the CLOSED position to be entered. Press to enter this
position.
Note: No error checking of the servomotors is enabled at this stage, therefore, do not to drive the
servomotors/ dampers beyond any mechanical limitations that may be present on the damper/valve.
This may cause damage to the servomotor and/or the damper/valve.
Note: Double check the damper/valve is physically at the 0.0 (closed) position. This can be achieved
by checking for external indications on the damper assembly or the fuel valve. It is the engineer’s
responsibility to ensure that the servomotors are correctly calibrated. Incorrect calibration can cause
serious injury or death.
Press to store the CLOSED position. The burner motor output T58 will energise at this
point. A message will then be displayed ‘Enter OPEN Position.’
Press and then drive the fuel and air servomotors to their OPEN position. The button hold
facility allows multiple channels to be driven up or down at the same time. Press on the blue circles
next to the channels; once selected they will appear as to indicate the channels are selected.
Use the buttons to drive both servomotors to the OPEN position simultaneously. This is
normally 90.0 o for Autoflame gas butterfly valves and burner air dampers, but may be set to less than
90.0 o if there are mechanical stops/limits on third party valves. Channels 5 and 6 cannot be adjusted
at this stage, its calibration is dictated by the drive set-up and relevant options.
Pressing on the Fuel-Air tab at any time will give you a graph showing the fuel and air servomotor
angles.
Once the system has purged (see options/ parameters 75 and 112), the message ‘Set up START
Position’ will display on the MM.
Press and drive the servomotors to their START position. To enter a fuel START position
which is less than 10 degrees below the OPEN position, you must drive the servomotor below this
band, and then back open. For example, if the CH1 OPEN position is set at 90.0O, to set a CH1 START
position of 83.0O, you must drive the CH1 servomotor to below 80.0O and then to 83.0O.
Press to enter the START position, where a light off can take place. These fuel and air
positions are not stored permanently as it is just a light-off position to put a flame in the boiler and
begin the commissioning process.
When the system is in commissioning mode only, the Phase Hold feature enables the commissioning
engineer to pause the ignition sequence of the burner to make adjustments to the gas regulator if
needed.
The phase hold feature can be used in pilot open, pilot proving and main flame proving. If the phase is
held in the pilot open stage and the flame goes out, a lockout will occur after 20 seconds. However, if
the phase is held in either the pilot proving or main flame proving stages, the MM will lockout
immediately if the flame scanner does not detect a flame.
If the flame is present and the ‘phase hold’ condition is left indefinitely the ‘Freeze Timeout’ lockout will
occur after 10 minutes. When the system is in a run mode the facility is disabled.
To make adjustments with the gas manually, press to keep the system at its current phase
positions, a little blue dot on this ‘button’ will appear to indicate that the phase is held. Ensure that the
main fuel valve is manually isolated until the pilot flame has been successfully established. Once this
has been successfully established, gradually introduce the main fuel supply to the burner while
observing the flame stability. Continue to introduce fuel until the manual operated main fuel isolation
valve is fully open providing safe and stable combustion that can be maintained. If the combustion is
not safe and stable, then adjust the fuel/air ratio accordingly. Once the adjustments have been made,
**WARNING**
If option 12 is set to 2 or 3 during commissioning, when setting the servomotors for the HIGH, INTER,
GOLDEN START, FGR START and START positions, the trim data will also need to be saved for the fuel
rich and air rich trim conditions. The message ‘Waiting for EGA readings’ will display.
After you press to save those servomotor positions, the EGA will carry out its fuel rich and
air rich trim.
Once these trim values have been saved, the system will continue with the commissioning process.
Note: If the MM has not been enabled for trim during commissioning, this can be added later by
setting option12 for trim, and going into Single Point Change to add trim to each point, see section 3.7.
Press on the VSD tab to view the VSD output and input signal during commissioning.
If the MM has been enabled with VSD for commissioning and then disabled, or vice versa, a conflict
message will appear ‘VSD configuration does not match commissioning.’
If there is little movement required with the VSD signal, the feedback fault tolerance should be set
accordingly. If the tolerance is not set according to the variation, an error ‘VSD feedback change too
small’ will occur.
Please see options 99 and 109 for the VSD fault tolerance, which ensures that a VSD can be verified
to be at the correct speed at low fire and different to that of high fire. This also ensures that VSD signal
is checked for fixed values and cannot be bypassed, preventing an unsafe condition with reduced air
than commissioned. The minimum feedback variation applies to both the upper and lower limits so the
total commission must allow for the two combined.
If Golden Start has been enabled in option 29 on a new system which has not been commissioned, the
message ‘Set Golden Start Position’ will display after the START position has been entered.
Press to enter the GOLDEN START position. After entering the GOLDEN START position,
proceed to the commissioning steps in section 3.4.9 if FGR START has been enabled, or 3.4.10 if no
FGR START is enabled.
Press on the home screen and once the system goes through its internal relay tests, the
message ‘Select Commissioning’ will appear.
Press to go through the commissioning process and enter the CLOSED, OPEN and light-off
START positions. After the entering the light-off START position, the message ‘Set Golden Start Position’
will appear; press to enter the stored GOLDEN START position and continue with the full
commissioning procedure. in section 3.4.9 if FGR START has been enabled, or 3.4.10 if no FGR START
is enabled.
Alternatively, to just add the Golden Start position and not go through the whole commissioning
procedure, press on the home screen, and once the system has gone through its
internal relay tests the message ‘Select Commissioning’ will appear. Press and the MM will
go through purge. The message ‘Set up START position’ will appear to ignite a flame in the burner, see
section 3.4.4. Once the burner is firing, the message ‘Set Golden Start Position’ will appear. Press
to enter the GOLDEN START position. The message ‘Save Commission’ will appear, press
to save the GOLDEN START position and then press to return to run mode.
Note: If FGR START has also been enabled, this positon must be entered after the GOLDEN START
position.
The Golden Start position of the fuel and air servomotors is completely independent from the
modulating load index and commissioned value data.
The facility is particularly useful on combustion systems with large turndowns and when firing heavy oil,
as it enables the burner to start/ignite at a fuel rich position and then, after a stable flame is
established, return to the commissioned combustion curve.
The Golden Start position needs to be entered for each required fuel.
The MM holds the Golden Start position for a time set in Parameter 15; this time starts from the point of
main flame. After this time, if the Golden Start fuel position is between Low Fire and High Fire, the air
damper will open and the fuel valve will stay in the same position, until fuel/air ratio is on the
commissioned combustion curve. If the Golden Start fuel position is outside of the main curve, then both
the air damper and fuel will go to the Low Fire position. Once on the commission curve, the MM will
modulate as per load requirement.
If FGR Start has been enabled in options 48, 49 or 50 on a system which not been commissioned, the
message ‘Set FGR Position’ will display after entering the light-off START position. If Golden Start has
been enabled in option 29, this message will appear after entering the GOLDEN START position.
Press to enter the FGR START position. After entering the FGR START position, proceed to
the commissioning steps in section 3.4.10.
Press on the home screen and once the system goes through its internal relay tests, the
message ‘Select Commissioning’ will appear.
Press to go through the commissioning process and enter the CLOSED, OPEN, light-off
START and GOLDEN START (if enabled) positions. After the entering the light-off START or GOLDEN
START (if enabled) position, the message ‘Set FGR Position’ will appear; press to enter
the stored FGR START position and continue with the full commissioning procedure in section 3.4.10.
Alternatively, to just add the FGR Start position and not go through the whole commissioning
procedure, press on the home screen, and once the system has gone through its
internal relay tests the message ‘Select Commissioning’ will appear. Press and the MM
will go through purge. The message ‘Set up START position’ will appear to ignite a flame in the burner,
see section 3.4.4. Once the burner is firing, the message ‘Set FGR Position’ will appear. Press
to enter the FGR START position. The message ‘Save Commission’ will appear, press
to save the FGR START position and then press to return to run mode.
Note: If both Golden Start and FGR are optioned then the GOLDEN START position is entered before
the FGR START position.
Flue Gas Recirculation (FGR) is a method whereby a quantity (approximately 15%) of the boiler flue
gases are fed back to the burner and mixed with the combustion air. The virtue of FGR is the reduction
of NOx gases. With the FGR facility, servomotor channel 3 can be used to control the amount of flue
gas fed back. It is not good practice to feed back the gases when the flue gas is cold, so all the
elements (i.e. servomotors and VSD) can be set at ‘FGR’ positions until the gases are hot. During this
time the CH3 would normally be set closed. Once the FGR holding conditions are met, modulation
takes place in the normal way using the curve entered during commissioning.
FGR can be set as a Timer, Offset or Temperature Threshold (see options 48, 49 and 50).
Note: Golden start takes priority over FGR. Once the golden start timer has finished, the servomotors
will go straight to the FGR start position.
Once all the START, GOLDEN START and FGR START positions have been entered, the message ‘Set
HIGH Position’ will appear. Press and drive the servomotors (and VSD if optioned) to the
HIGH position by opening the air damper and fuel valve some degrees alternatively, so that more fuel
is added gradually.
It is not possible to enter the HIGH position higher than the OPEN position. The servomotors must be
driven 0.5O up/down from the previous point initially, before entering the next point, the fuel. Press
Once the HIGH position has been entered, the message ‘Set INTER Position’ will appear. Press
to drive the servomotors (and VSD) to the first INTER positon. The message ‘Move fuel
and air positions’ will appear at first, as the system must detected a 0.5O movement on CH1 and CH2
before an INTER position can be entered. Press to store this INTER position.
There must be a minimum of 3 INTER points entered on the fuel-air curve, and a maximum of 18. Points
can be added/removed in Single Point Change mode (see section 3.6).
Continue this process until all the required INTER points have been entered.
Once the minimum 3 INTER points have been added, you will be prompted to either enter another
INTER point or the START/LOW FIRE position.
Press to drive the servomotors (and VSD) to the START/ LOW FIRE position, and then
Note: If Golden Start or FGR Start are in use, the Start position is only used for Low Fire.
Once the START position has been entered, press to store this commission curve. The
message ‘Commission Complete’ will appear and press to go normal firing mode.
If the burner has been previously commissioned then the new saved curve will overwrite the previous
data for the fuel selected. Failure to save the curve will result in the commissioning data not being
stored within the unit and a power loss to the unit will result in a loss of data for the fuel selected.
If during commissioning the burner turns off, due to the ‘running interlock’ opening or a fault, or if the
power has been recycled, no points entered are stored. It is recommended to commission the MM with
a quick base curve and then adjust/add/remove the points in the Single Point Change.
Once the burner has been commissioned, the fuel flow metering will need to be entered, please go to
section 3.5 Fuel Flow Commissioning. If there is EGA trim data to be added then continue to section
3.7 Single Point Change before section 3.5 Fuel Flow Commissioning.
Note: If commissioning a fuel for the first time the default required setpoint will be
2.0bar/20PSI/20OC/20OF. The burner will shut down at commission completion due to the low default
required setpoint. Go to the Status screen to change the required setpoint.
If fuel flow metering has been enabled in option 57, the message ‘No Fuel Flow Data’ will display on
the Home screen once the burner has been commissioned. Fuel flow metering is used to rate the size or
burner and calculate the firing rate.
If fuel flow metering is not commissioned and sequencing is optioned, then MM will assume a default
burner rating which is based on the fractional fuel valve angle.
The fuel flow is commissioned from the high fire point down to low fire. The high fire point will set the
burner rating in MW if metric of MMBTu/hr if imperial.
On the Mk8 MM, fuel flow metering can be taken as the values entered in the fuel flow commissioning
screen from the fuel flow meter or through a 4-20mA signal on terminals EX- and EX+.
If a fuel flow meter is not being used and only arbitrary values are being used then make sure a good
range of values are being used (e.g. 100 to 10) with equal spaces between the values. Not doing this
could lead to problems when using IBS and the flame graphic.
When using arbitrary values it is good practice to use the following calculation to determine the heat
value for each of the 10 points.
5.4
5.4
5 0.48
9
Giving the range (5.40, 4.92, 4.44, 3.96, 3.48, 3.00, 2.52, 2.04, 1.56, 1.08), with 5.4MW as the
high fire burner rating point and 1.08MW as the low fire point derived using an estimated burner
turndown value.
Fuel flow metering serves to totalise the amount of fuel being used at each position. If any changes are
made to the curve through Single Point Change, then fuel flow will need to be re-commissioned.
Enable Fuel flow commissioning by setting set by option 57. Fuel flow commissioning is done in Run
ode while the burner is firing.
On the System Configuration screen press . You will be prompted to enter the Online
Press to access the fuel flow commissioning screen. There are 10 points which need to be
entered across the commission curve from high fire to low fire, with high fire being point 1, and low fire
point 10. Type in the heat value or ‘dummy value’ using the keypad and press the return key to save
that point.
Note: The servomotors will drive up to the high fire position, and then drive down as the fuel flow
commissioning points are entered. Precautions must be taken to ensure that the boiler is warm enough
for all 10 points to be entered.
As you enter the heat values for the 10 points, these will become marked on the graph to the right of
the screen. Once the fuel flow commissioning is complete, press to return to modulation in
normal firing mode.
If you press at any time during fuel flow commission, this will not store the points.
If fuel flow metering is enabled through using 4-20mA feedback on terminals EX- and EX+, the heat
value will automatically get populated according to the analogue signal at that fuel valve position.
After each heat value is displayed, press enter to go to the next fuel flow point.
(Pressure of gas at meter x 0.00228) + (0.948 – (height above sea level x 0.0001075))
1. Measure Volumetric flow of gas for 1min in ft3 (i.e. ft3/min). Note 1m3 = 35.31ft3
2. Multiply this volume flow by 60 to give volumetric flow per hour (i.e. ft3/hr).
5. Multiply the volume flow per hour by the conversion factor to obtain a volume at reference
conditions.
6. For natural gas, the calorific value is typically 1000 Btu/ft3. To obtain the firing rate of the boiler at
standard reference conditions multiply the volume at reference conditions by 1000.
Represented as an equation:-
Firing rate = (Measured Volumetric flow per minute x 60 x Conversion factor x 1000) Btu/hr
If the VPS is optioned on, the unit will run through this valve proving process. The MM will go from Low
Fire to High Fire and store the gas pressure values along the curve. Once these values are stored, the
upper and lower offset limits will be adjusted to the new commissioned gas pressure values.
If the burner turns off during the gas/air pressure commission, the gas/air pressure commission process
will be restarted. This ensures that the MM does not run with an incomplete set of gas/air pressure
readings.
To commission the air pressure sensor, in Commission Mode screen press . The air
pressure sensor commission procedure is the same as the gas pressure sensor commission procedure.
The same procedure also applies for commissioning the oil pressure sensor.
Note: If the gas or air pressure sensor is replaced with the same sensor type (same pressure range)
then the sensor will not need to be recommissioned.
Note: For applications where VPS is required after burner shutdown only, the option/parameter 129
should be set to 0 when doing the first gas sensor commission on the system to store the valve proving
gas pressure. During normal running, option/parameter 129 can be set to 1.
Single Point Change can only be accessed when the burner is firing and in Run mode. Press
in the system configuration screen and enter the password to access Single Point Change mode.
The Status screen will display the message ‘Select change to make.’
To edit a previously entered point press and make adjustments to the positions as needed
(see Figure 3.7.iiii).
To add trim data to a point press , see section 3.4.6 and Figure 3.7.iv.
Note: It is not possible to delete LOW or HIGH FIRE positions or have less than 3 INTER points.
Press to edit the fuel, air and/or VSD commissioned value of that point. Once the changes
have been made, press to save this position. If a point is overwritten, the trim data is
cleared and the trim data will need to be added.
Press to store the changes made. Press to store these changes and leave
Single Point Change mode.
The fuel flow commissioning must be entered (again) if the following changes are made in single point
change
HIGH or START position is changed.
EGA trim data has been added.
Points have been added.
The Online Changes is accessed by pressing on the system configuration screen, and then
entering the password. The Online Changes feature allows the following:
Change non-safety critical options, parameters and expansion options
Configure settings and labels for first outs
Fuel flow commissioning
Set bottom blowdown servomotor positions
Adjust water level control point
Reset burner history
Reset fuel flow data
Reset fault logs
Reset system log
Reset bottom blowdown log
Reset boiler configuration
Reset run times
Reset steam flow metering
Restart MM if the burner is in standby
4.1 Errors
Errors occur when the MM detects an internal fault, component out of range, internal check failure or
power supply issue. To clear an error, the MM must be restarted.
4.2 Lockouts
Lockouts occur when the MM detects a fault with the burner operation such as VPS, gas/air pressure
sensor and flame scanners. The lockout must be cleared and investigated on the MM.
Alarms and warnings are faults detected with the system operation. If an alarm occurs, the burner will
stop running, and if a warning occurs, the burner will continue to run. The following
options/parameters set whether system operation faults are set as alarms or warnings:
Some of the options, parameters and expansion options may require another option, parameter or
expansion option to be set. Please see the below table for these settings conflicts. A setting conflict will
result in the MM being forced in to Commission mode.
In addition to when there is a setting conflict, the MM will be forced into commission mode if any of the
forced commission reason occurs.
UV shutter fault– there are two LED’s on the back of the self-check UV. The red LED indicates the
presence of a flame; the yellow LED indicates shutter operation. The red LED will flicker in the presence
of UV light. Every 60 seconds the yellow LED will come on, indicating that the shutter is closing. The red
LED should then extinguish briefly. If this is not happening check the wiring to self-check UV sensor:
4.6.2 UV Problems
If the red LED’s fail to illuminate but the burner operates, it is likely that the 2 wires are crossed. This
must be corrected. Once corrected a full flame signal strength will be displayed/registered.
The Autoflame UV software utilises early spark termination within the internal flame safeguard control.
Therefore, detection of the ignition spark is allowed. During start-up the ignition is de-energised and the
pilot flame must be proven without the spark before the main fuel valves are open (safety shut off). Due
to the above statement it is not necessary to have a sight tube on the UV for pick-up. This, in fact, will
drastically reduce the flame pick-up.
If a non-Autoflame scanner is required then please contact Autoflame directly for technical support. For
more information on UV scanners, please refer to MM Flame Safeguard and Operation.
4.6.3 Snubbers
The Autoflame system has internal components which protects itself against voltage/current spikes and
electrical interference. In some installations this internal protection is not enough, especially when the
main fuel valve Terminals 60 and 61 have been connected to older gas valves and voltage/current
spikes have occurred when the valves have been switched on or off. This can cause internal damage to
the MM Snubbers can be used on these old gas valves to protect the MM from these spikes; they
should be fitted across the power terminals of the gas valves. Please contact Autoflame Sales for more
information.
The ‘Channel Positioning’ MM Error is caused by incorrect wiring and incorrect servomotor position. In
addition to checking the wiring, and zeroing the potentiometer, please also check that the correct
voltage is supplied to the servomotors, which should be ±10% of the required voltage, and the unit is
earthed properly. This can cause hunting issues if not at the required voltage or incorrect earthing.
The ‘Input Fault’ MM Error relates to a fault with the power supply going to the MM The MM verifies
the power supply going to the unit; the mains inputs are sampled to check the DC voltage. The diagram
below illustrates the AC voltage that comes in through the power supply with the detected signal
(digital input).
The MM checks the ON state of the digital signal in the mains input; the ON state of the digital input
should be 50%. This means that the digital input should be in the ON state for a half-wave of the AC
signal. The OFF state is safe. If the MM sees the digital input being ON for more than 75% across a
sample period, then it will get stuck in an unsafe state. This will cause an Input Fault lockout to occur.
If this lockout persists, the mains input should be checked. To troubleshoot this issue, please check for
any DC voltage in the mains voltage and contact your local power supplier.
5 STANDARDS
The Mk8 MM has been tested and approved to the following standards:
BS EN 298:2012
BS EN 12067-2:2004
BS EN 1643:2014
BS EN 1854
ISO 23522:2007
AS 4625 – 2008
AS 4630 – 2005