What's New in AC Power June 2022
What's New in AC Power June 2022
What's New in AC Power June 2022
AC Power
Tim Easterday
Technical Sales Manager
June 2022
Americas Power Switching & Distribution Portfolio
Critical Power Infrastructure Remote
Power Panel
Busway
Generator ATS/Paralleling
Thermal Systems
“House” Power Rack
Distribution
Power Systems /
Integrated Power Skid
Modular Enclosure
3
UL Three-Phase UPS Portfolio Transfomer free modular
Transfomer free monolithic
Transformer-based
Liebert® Highest efficiency, Trinergy™ Control, Dynamic Online mode, Circular Redundancy
Trinergy™ Cube 400, 800, 1200, 1600 kVA
50 – 250 kVA
Liebert® EXM
10 – 200 kVA
Scalable / Redundant
208V
Liebert® EXS
10-30
kVA
208V
8-10
Liebert® ITA2
kVA
208V
100 200 300 400 500 600 700 800 900 1000 1100 1200 1400 1600
Capacity (kVA) Confidential. Property of Vertiv. 4
CE Three-Phase UPS Portfolio - EMEA Transfomer free modular
Transfomer free monolithic
Highest efficiency, Trinergy™ Control, Dynamic Online mode, Circular Redundancy
Liebert® 200, 400, 600, 800, 1000, 1200, 1400, 1600 kVA
Trinergy™ Cube 400, 800, 1200, 1600, 2000, 2400, … 3400 kVA
Liebert® ITA2 10-20 kVA Flexible power protection for rack or tower installation High efficiency, ECO mode
L Large Power
F Firmware
L 138% booster operation F Maintenance Release F Common Code F DGS & Export
Maximum Availability with Class 1 UPS Can’t ensure perfect power quality
Class 1 Transfer
< 0.5 Output
ms Voltages
Input
Voltages
Confidential. Property
Confidential. of Vertiv.
Property of Vertiv. 11
Coming Soon to EXL S1 - Integration with Fuel Cells
Data Center today
Server &
Main Power UPS Battery Storage Auxiliaries
Backup Power
Data Center with PEM FC as Backup Power Data Center with SOFC Prime Power
implementation
with growing FC Prime Power: SOFC
acceptance and H2
infrastructure
PHASE-OUT
L Large Power
F Firmware
Benefits:
• Cost savings: no load banks to rent
• Quick operation: no temporary load connections to make
• Green operation: no wasted energy
• Safe operation: less hazardous due to minor electrical activities
18
UL Power Switching and Distribution Products
Static Transfer Switches
Liebert STS2/PDU 250, 400, 600, 800A
Liebert STS2 100, 250, 400, 600, 800, 1000A
Liebert STS2 SR 400, 600A
Liebert PPC 15, 30, 50, 75, 100, 125, 150, 200, 225, 300, 400, 430, 500, 600, 700,
0
750, 800kVA
Liebert PPC ISO 200, 225, 300, 450, 500kVA
Distribution Center
Liebert FDC 4 x 42 Pole Panel Boards
In Room
1800A 4P Chassis CE & RCM 1800A Switch Cab 1600A 3P Switch Cab UL
1250A 3P UL System LAUNCHED
CE & RCM
PHASE-OUT
P Liebert FPC, 15-300kVA
E 950kVA UL
B Modular Busway
F Firmware
R RPP
LAUNCHED
R Liebert RXV, 225A-400A
PHASE-OUT
AMER / UL Versions EMEA / CE Versions
Obsolete
B Modular Busway
B Liebert MBX, 250-800A
Transitioned to E+I F Firmware
E ETO-C
DOE2016 compliant
UL62638 & UL60950 compliant
Efficiency & Protection
Up to ANSI/IEEE C62.41 Category B3
Operates up to 40C
Live serviceability of LV components
LIFETM compatible
Complete Service Designed and Manufactured
transformers for 40+ years
12-Month warranty
Voltage test jacks for increased safety
RDU101 card
Monitoring & Management On-screen programming
Intelligent UI
Three-level security access to
Observer/User/Admin
DPM was designed based on direct user feedback to address common use cases:
Daily Reviews, Issue Investigation & Resolution, and Configuration Changes
Confidential. Property of Vertiv. 25
Liebert PPC, 300-500kVA Spotlight
PPC
• 60”W x 42”D
• Available features:
• Up to 500kVA
• Up to (8) 400A SF Breakers or
• Up to (10) 250A SF Breaker
• IR Scan Door
• Liebert LDMF Monitoring
• Isolated transformer /
Distribution Cabinets
• Front access only
60” 42”
PPC
• 60”W x 48”D
• Available features:
• Up to 750kVA
• Up to (8) 400A SF Breakers or
• Up to (10) 250A SF Breaker
• Liebert LDMF Monitoring
• Isolated monitoring components
• One side access required for
service and maintenance
• 6” rear clearance required
60” 48”
PPC
• 84”W x 50”D
• Available features:
• Up to 950kVA
• Up to (8) 400A SF Breakers or
• Up to (10) 250A SF Breaker
• Liebert DPM Monitoring (9” GHMI)
• Isolated monitoring components
• One side access required for
service and maintenance
• 6” rear clearance required
84” 50”
30
LIB Industry Adoption
>150 MW of UPS
Installed with LIB
Increasingly adoption
vs. standard solution
2000
1500
1000
500
0
2016 2017 2018 2019 2020 2021
Confidential. Property of Vertiv. 31
*Data as of Sep 2021
Energy Storage Requirements are Changing
• VRLA life is reduced by 50% for every 10oF • LIB & TPPL can operate at 28oC or 30oC within
increase above 77oF warranty
• VRLA needs air-flow to balance battery • Operating LIB at higher temperature can improve
temperature within the same cabinet runtime in some solutions
HPL7 in EMEA
LIB for EXM208V OCP 48V LIB
with CE Cert
H2, 2020 H1, 2021 H2, 2021 H1, 2022 H2, 2022
‒ Controlled air tunnels are built on both sides of the rack, creating a
‘chimney effect’ for flames and vented gases to quickly escape
through the top of the rack while limiting exposure and heat
transfer to adjacent modules
‒ Add insulating material and fire sealing materials inside the cabinet
to reduce heat transfer between module chambers
HPL Enclosure for UL9540A
Confidential. Property of Vertiv. 34
Samsung UL9540A Tested Cabinet
• Samsung successfully completed UL 9540A fire testing
‒ Report shows no propagation
‒ Report shows no re-ignition
‒ Report provided for use with permitting & AHJ approvals
• Listed to UL1973
• Modbus communication
Battery Strings BOL EOL 1 year Total 5 year Total 10 year Total 15 year Total
Runtime Runtime
Enersys HX540 9 9 6 100% 173% 252% 275%
Notes: Outlines represent battery strings only. DC Junction Cabinet not shown
(30”W x 33”D x 82”H, 485 lbs)
41
Vertiv™ DC Rack Power OCP Targeted Offerings
Front View Rear View
Typical OCP • Vertiv OCP targeted offerings
Server Deck
‒ OCPV2 Rack
‒ OCP Rack DC Bus Bars
‒ 12VDC Power Shelf
‒ 26.4kW, 2200A at 12V
‒ N+1 redundancy
• Future Vertiv OCP targeted
offerings
‒ OCPV3 Rack
‒ OCP Rack DC Bus Bars
‒ 48V DC Power Shelf
‒ Battery Back Up (BBU) Shelf
‒ Rack Liquid Cooling Server
DC
Backplanes
Headers and Piping
‒ Row and Rack Coolant
Distribution Units (CDU)
DC Power Shelf Confidential. Property of Vertiv. 42
DC Power – 48VDC Power Shelf In Development
• Power Supply Unit (PSU)
‒ ≈ 3200 watts per unit
‒ Optimal power level for six PSUs on a 277/480VAC 30A feed
‒ Connector sized for up to 4200 watts for future higher power PSUs
‒ Two efficiency options: Ultra High efficiency - 97.5% peak
High Efficiency: 96% (lower price)
‒ Two input options
‒ Dual input with automatic transfer
‒ Single input (lower price)
‒ ORing/blocking device on output
• Dual Input Shelf
‒ 1OU x 21” mounting w/ 6 PSUs and controller (for OCP V3)
‒ 1RU x 19” mounting w/ 6 PSUs and controller (for Open19 V2)
‒ 15.8kW (N+1) in 1U; 34.7kW (N+1) in 2U; 53.6kW (N+1) in 3U
‒ Universal input connectors
‒ 208VAC, 230/400VAC, 240/415VAC, 277/480VAC, 240-380VDC nominal inputs
‒ Auxiliary DC output for controller
• Controller with emphasis on reporting and minimizing power consumption
‒ ECO mode, peak shaving, AC input phase current balancing, etc.
• Design Target
• 48VDC lithium-ion BBU shelf
• 2 OU shelf space for 21’’ Open Rack
• 15 kW load with 4+1 module redundancy, 5min runtime
• Include DC/DC converter for narrow range 48VDC bus concept
• Advanced BMS control integration with Vertiv DC power shelf
• UL9540A large scale fire test
• High level compatible to OCP ORV3 spec
• Construction Concept
• 18650 cells from top tier lithium cell supplier
• Use 4+1 module concept instead of the 5+1 concept from ORV3
• Use OCP ORV3 specified DC connector
• Support OCP ORV3 specified Shelf PMC and communication
• Vertiv designed BMS, shelf and controls
• Customer prototype release in Q4 2021
Tim Easterday
Technical Sales Manager
[email protected]
+1-614-674-4431 (M)