Rittal AC Unit

Basics

Service
Tech Guide
Manual

Document Title: Tech Guide ~ Rittal AC Unit Basics


Document Revision: v1.0.1

18805 Adams Ct., #110 ~ Morgan Hill, CA 95037, USA ~ +1-408.924.0808 ~ www.washlinksystems.com ~ [email protected]
WASHLINK SYSTEMS Rittal AC Unit Basics

This document provides comprehensive information for Rittal AC Unit Basic Settings.

When emailing or calling for assistance, you must have the following information available:

Location Name: ______________________________

Contact Person: ______________________________

Contact Phone: ______________________________

Distributor Name: ______________________________

COPYRIGHT

2017 Washlink Systems. All rights reserved.


THIS DOCUMENT IS THE EXCLUSIVE PROPERTY OF WASHLINK SYSTEMS AND IS PREPARED
ONLY FOR USE BY THE COMPANY PURCHASING THE EQUIPMENT. EDITING, COPYING,
DISTRIBUTING, AND/OR SELLING THIS DOCUMENT IS STRICTLY PROHIBITED WITHOUT PRIOR
WRITTEN CONSENT FROM WASHLINK SYSTEMS. WASHLINK SYSTEMS RESERVES THE RIGHT
TO EDIT THIS DOCUMENT IN ANY MANNER DEEMED NECESSARY, AT ANY TIME, AND WITHOUT
PRIOR NOTICE.

Document Title: Tech Guide ~ Rittal AC Unit Basics 1 of 6


Document Revision: v1.0.1
Comfort Controller

Legend
1. Programming button, also display of the set
temperature Unit (degrees Celsius)
2. Set button
3. Programming button, also display of the set
temperature unit (degrees Fahrenheit)
4. 7-segment display

Document Title: Tech Guide ~ Rittal AC Unit Basics 2 of 6


Document Revision: v1.0.1
General programming information
Using buttons 1, 2 and 3 (see page 2 for Comfort Controller) you can change
parameters within the preset ranges.
Note on temperature settings:
With the Comfort Controller, the temperature is preset at the factory to +35C.
In order to save energy, and due to the risk of increased condensation, do
not set the temperature lower than what is actually necessary.
Note on useful cooling output:
Interactive performance diagrams for calculating the useful cooling output
may be fount at www.rittal.com.
• In principle, the programming is identical for all editable parameters.
To enter programming mode:
Press button 2 Set for approx. 5 seconds. The controller is now in programming
mode, if you do not press any buttons for approx. 30 seconds, the display will first flash,
then the controller will switch back to normal display mode. The Esc display indicates
that any made changes have not been saved.
• Press the Programming buttons (C) or (F) to switch between parameters (see
page 4)
Press button 2 Set to select the displayed parameter for editing.
The current value of the parameter is displayed.
• Press one of the programming buttons (C) or (F), the Cod display will appear.
In order to be able to change a value, you must enter the authorization code
• Keep the Programming button (C) held down until appears.
• Press button Set to confirm the code. You can now alter the parameter.
• Press programming buttons (C) or (F) until the required value appears.
• Press button 2 Set to confirm the change. You can now alter other parameters in
the same way. There is no need to re-enter the authorization code
• To exit programming mode, press button Set again for approx. 5 seconds.
Acc will appear in the display to indicate that the changes have been saved. The
display will then switch back to regular operation (enclosure internal temperature).
You can also program the Comfort Controller using Rittal diagnosis software
#SK3159.100.

Document Title: Tech Guide ~ Rittal AC Unit Basics 3 of 6


Document Revision: v1.0.1
Editable parameters

Progr. Display Parameter Min. Max. Factory Description


level screen value value setting
1 St Internal 20 55 35 The setting of the enclosure internal
enclosure temperature is preset at the factory to
35C and may be alerted within a range
temperature of 20-55C.
setpoint Ti

2 Fi Filter mat 10 60 99 To activate filter mat monitoring, set the


monitoring (= off) display to at least 10 K above the
temperature differential displayed in
programming mode Fi Filter mat
monitoring is preset to deactivated in
the factory (99=off).

3 Ad Master- 0 19 0 See Full Manual section 6.2.7


slave
identifier

4 CF Temperature 0 1 0 The temperature display can be


conversion switched from C (0) to F (1). The
corresponding LED displays the current
C/F
unit of temperature.

5 H1 Setting for 2 10 5 The cooling unit is preset in the factory


switching to a switching hysteresis of 5 K. This
parameter should only be changed in
difference consultation with Rittal. Please contact
(hysteresis) Rittal for advise.

6 H2 Differential 3 15 5 If the internal enclosure temperature


for error exceeds the set value by fore then 5 K,
then error message A2 (enclosure
message A2 internal temperature too high) appears
on the display terminal. If necessary,
the differential may be alerted here
within the range of 3-15 K.

Document Title: Tech Guide ~ Rittal AC Unit Basics 4 of 6


Document Revision: v1.0.1
Document Title: Tech Guide ~ Rittal AC Unit Basics 5 of 6
Document Revision: v1.0.1
Resetting the Comfort Controller
After the occurrence of faults A03, A06 and A07, you will need to reset
the Comfort Controller.

• Press buttons (C) or (F) simultaneously for 5 seconds.


• The system messages will disappear and the temperature display will be shown.

For more information please visit www.rittal.com.