Substation Automation
Substation Automation
6
Distribution Automation
Equipment
6.1 Introduction
Modern electric power systems are supplied by large central generators that feed power into
a high voltage interconnected transmission network. The power, often transmitted over long
distances, is then passed down through a series of distribution transformers to final circuits for
delivery to customers (Figure 6.1, also refer to Plate 1).
Operation of the generation and transmission systems is monitored and controlled by Su-
pervisory Control and Data Acquisition (SCADA) systems. These link the various elements
through communication networks (for example, microwave and fibre optic circuits) and con-
nect the transmission substations and generators to a manned control centre that maintains
system security and facilitates integrated operation. In larger power systems, regional control
centres serve an area, with communication links to adjacent area control centres. In addition
to this central control, all the generators use automatic local governor and excitation control.
Local controllers are also used in some transmission circuits for voltage control and power
flow control, for example, using phase shifters (sometimes known as quadrature boosters).
Traditionally, the distribution network has been passive with limited communication be-
tween elements. Some local automation functions are used such as on-load tap changers and
shunt capacitors for voltage control and circuit breakers or auto-reclosers for fault manage-
ment. These controllers operate with only local measurements and wide-area coordinated
control is not used.
Over the past decade, automation of the distribution system has increased in order to
improve the quality of supply and allow the connection of more distributed generation. The
connection and management of distributed generation are accelerating the shift from passive
to active management of the distribution network. Network voltage changes and fault levels
are increasing due to the connection of distributed generation [1]. Without active management
of the network, the costs of connection of distributed generation will rise and the connection
of additional distributed generation may be limited [2].
113
P1: TIX/XYZ P2: ABC
JWST134-c06 JWST134-Ekanayake January 18, 2012 21:39 Printer Name: Markono
The connection of large intermittent energy sources and plug-in electric vehicles will lead
to an increase in the use of Demand-Side Integration and distribution system automation.
However, the real-time operation of the protection and voltage control systems was through
hard-wired connections.
The configuration of a modern substation automation system is illustrated in Figure 6.3. Two
possible connections (marked by boxes) of the substation equipment are shown in Figure 6.3.
Although it may vary from design to design, generally it comprises three levels:
r The station level includes the substation computer, the substation human machine interface
(which displays the station layout and the status of station equipment) and the gateway to
the control centre.
r The bay level includes all the controllers and intelligent electronic devices (which provide
protection of various network components and a real-time assessment of the distribution
network).
r The process level consists of switchgear control and monitoring, current transformers (CTs),
voltage transformers (VTs) and other sensors.
P1: TIX/XYZ P2: ABC
JWST134-c06 JWST134-Ekanayake January 18, 2012 21:39 Printer Name: Markono
In connection 1, analogue signals are received from CTs and VTs (1 A or 5 A and 110 V)
as well as status information and are digitised at the bay controller and IEDs. In connection
2, analogue and digital signals1 received from CTs and VTs are digitised by the interfacing
unit. The process bus and station bus take these digital signals to multiple receiving units,
such as IEDs, displays, and the station computer that are connected to the Ethernet network.
To increase reliability, normally two parallel process buses are used (only one process bus is
shown in Figure 6.3) [5].
The station bus operates in a peer-to-peer mode. This bus is a LAN formed by connecting
various Ethernet switches through a fibre-optic circuit. The data collected from the IEDs
is processed for control and maintenance by SCADA software that resides in the station
computer.
The hard-wiring of traditional substations required several kilometres of secondary wiring
in ducts and on cable trays. This not only increased the cost but also made the design inflexible.
In modern substations as inter-device communications are through Ethernet and use the same
communication protocol, IEC 61850, both the cost and physical footprint of the substation
have been reduced.
1 Optical CTs and VTs provide digital signals whereas conventional CTs and VTs provide an analogue signal (see
Example 6.1
Part of a distribution circuit is shown in Figure 6.4. The CT used is a 10 VA Class 10P
20 and has a secondary resistance of 0.6 and a magnetising reactance of j15 . Using
the equivalent circuit of the CT [3, 10], obtain the percentage current magnitude error
and phase displacement error for the rated current and for the current at the accuracy
limit when the rated burden is connected to the secondary.
Answer
As the rated burden is 10 VA, the corresponding secondary resistance is given by
10
Rburden = = 0.4
52
The per-phase equivalent circuit of the CT with rated current flowing is shown in
Figure 6.5:
11000
V1 = √ = 6350.9 V
3
3 × (6350.9)2
Rload = = 31.75
3.81 × 106
Transforming the primary quantities into secondary (multiplying voltage by the turns
ratio, that is, 40 and primary resistance by 402 ) the following circuit is obtained, as
shown in Figure 6.6:
254.04 × 103
Actual current in the secondary circuit =
50800 + [ j15 × 1.0/(1.0 + j15)]
= 5.0007∠0◦
5.0007 − 5
Therefore the percentage current magnitude error = × 100 = 0.014%
5
Phase angle error is 0◦ .
When the current is at the accuracy limit, that is, 200 × 20 A is flowing in the primary
circuit, instead of the Rload in the equivalent circuit, Rfault appears in the transformer
primary.
6350.9
Rfault = = 1.59
4000
254.04 × 103
New actual current in the secondary circuit =
1.59 × 402 + [ j15 × 1.0/(1.0 + j15)]
= 99.8194∠ − 0.0015◦
Therefore, the percentage current magnitude error =
99.8194 − 5 × 20
× 100 = −0.18%
5 × 20
The phase angle error is 0.0015◦ .
P1: TIX/XYZ P2: ABC
JWST134-c06 JWST134-Ekanayake January 18, 2012 21:39 Printer Name: Markono
As shown in connection 2 of Figure 6.3 (normally used in modern substations), the current
measurements from a CT are digitised and made available to the process bus and used by a
number of devices. Multiple use of the same digitised measurement requires high accuracy
CTs that measure both load and fault currents.
While iron cored CTs and hybrid CTs (an iron cored CT with an optical transmit-
ter) remain the most widely used CTs in the power system, high accuracy designs such
as the Rogowski coil formed on a printed circuit board and optical CTs [3, 11, 12]
are becoming available.
Rogowski coil CTs are used in a Gas Insulated Substations (GIS). The secondary winding
of the coil is a multi-layer printed circuit board as shown in Figure 6.7 with the upper and
lower tracks of each layer connected by metal vias (thus forming a rectangular coil). The
voltage induced on the secondary windings due to primary current (see Box 6.1) is integrated
(as a Rogowski coil gives di/dt) by the sensor electronics to obtain the value of the primary
current.
Optical CTs use the Faraday effect (Box 6.2), whereby the plane of polarisation of a light
beam when subjected to a magnetic field, is rotated through an angle. This angle of rotation
is proportional to the magnetic field thus to the primary current. Figure 6.8 shows this type
P1: TIX/XYZ P2: ABC
JWST134-c06 JWST134-Ekanayake January 18, 2012 21:39 Printer Name: Markono
of CT in its simplest form. The opto-electronics compares the polarisation of the light beam
entered into the optical fibre and that collected after being subjected to the circular magnetic
field. The angle of deflection is used to generate digital signals proportional to the line current.
The angle of rotation β in radians is given by β = νBd where B is the magnetic flux
density (in T), d is the length of the path (in m) and ν the Verdet constant for the material.
Some other designs are being developed based on the Faraday effect that use a disc
of an optically active material around the conductor [3, 7, 11]. The light enters the disc
from one side and travels around it (thus around the conductor) and is collected at the
other end.
P1: TIX/XYZ P2: ABC
JWST134-c06 JWST134-Ekanayake January 18, 2012 21:39 Printer Name: Markono
of a signal processing unit (as discussed in Sections 5.3.2 and 5.3.3), a microprocessor with
input and output devices, and a communication interface. Communication interfaces such as
EIA 232/EIA 483, Ethernet, Modbus and DNP3 are available in many IEDs.
The local measurements are first processed and made available to all the processors within
the protection IED. A user may be able to read these digitised measurements through a small
LED display as shown in Figure 6.13. Furthermore, a keypad is available to input settings or
override commands.
Various algorithms for different protection functions are stored in a ROM. For example,
the algorithm corresponding to Type 50 continuously checks the local current measurements
against a set value (which can be set by the user or can be set remotely) to determine
whether there is an over-current on the feeder to which the circuit breaker is connected. If the
current is greater than the setting, a trip command is generated and communicated to the Circuit
P1: TIX/XYZ P2: ABC
JWST134-c06 JWST134-Ekanayake January 18, 2012 21:39 Printer Name: Markono
Breaker (CB). IEDs have a relay contact that is hard-wired (in series) with the CB tripping
coil and the tripping command completes the circuit, thus opening the CB.
r CB control
r switchgear interlock check
r transformer tap change control
r programmable automatic sequence control.