Alarm Interface Test 16505-2022

1) MAN Energy Solutions recommends performing a test to verify that the auxiliary monitoring system (AMS) will not initiate an alarm, slowdown, or shutdown if it stops receiving data from the engine management system (EMS) due to a disrupted data connection. 2) The test involves disconnecting network cables or powering off the EMS computer to interrupt the EMS to AMS data flow and confirm that AMS only indicates missing values without generating out of range alarms or shutting down the engine. 3) If the test causes an engine slowdown or shutdown, it means AMS is not properly configured to handle missing EMS data, and MAN-ES should be contacted for assistance.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
177 views2 pages

Alarm Interface Test 16505-2022

1) MAN Energy Solutions recommends performing a test to verify that the auxiliary monitoring system (AMS) will not initiate an alarm, slowdown, or shutdown if it stops receiving data from the engine management system (EMS) due to a disrupted data connection. 2) The test involves disconnecting network cables or powering off the EMS computer to interrupt the EMS to AMS data flow and confirm that AMS only indicates missing values without generating out of range alarms or shutting down the engine. 3) If the test causes an engine slowdown or shutdown, it means AMS is not properly configured to handle missing EMS data, and MAN-ES should be contacted for assistance.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Page 1 of 2

To whom it may concern

Our ref: EEEEO/AJL/BSAM/16505-2022 31 March 2022

Test procedure: AMS Handling of Engine Process Values.


Applicable to MAN/ES 2 stroke ME engines with Triton and MPC controllers.

MAN-ES strongly recommend performing below test to verify that AMS will react
according to design in case no information is received from EMS.
The test is to verify that AMS will not raise alarm, slowdown or shutdown based on
missing EMS data. It is done by disrupting the EMS-AMS Modbus.

The data flow is as shown below with the red line.

Figure 1 Data flow: ECS MOP-B ->EMS MOP -> AMS


In case ECS MOP-B, EMS MOP, managed switch or any of the network cables fail, the
data flow will be interrupted. EMS-AMS Modbus will send “+32767” signifying #Bad
Value for affected Modbus registers; however, they must not result in Out of Range
Alarms (OoR) in AMS.
MAN Energy Solutions MAN PrimeServ PRODUCTION FORWARDING & RECEIVING MAN Energy Solutions
Teglholmsgade 41 Teglholmsgade 41 Teglholmsgade 35 Teglholmsgade 35 Branch of MAN Energy Solutions SE,
2450 Copenhagen SV 2450 Copenhagen SV 2450 Copenhagen SV 2450 Copenhagen SV Germany
Denmark Denmark Denmark Denmark CVR No.: 31611792
P +45 33 85 11 00 P +45 33 85 11 00 P +45 33 85 11 00 Head office: Teglholmsgade 41
P +45 33 85 11 00 F +45 33 85 10 49 F +45 33 85 10 17 F +45 33 85 10 16 2450 Copenhagen SV
F +45 33 85 10 30 [email protected] [email protected] [email protected] Denmark
[email protected] German Reg.No.: HRB 22056
www.man-es.com Amtsgericht Augsburg
-2-

Test steps:
At a convenient and safe location while operating Engine at low load, but above
slowdown limit:
1. Conduct following tests separately followed by Verification steps 2.1-3:
1.1. disconnect LAN cable 󠆯from port / MOP-B
1.2. disconnect LAN cable from port / PMI DAU
1.3. Power off the EMS computer
2. Confirm that:
2.1. no slowdown or shutdown is requested/activated by AMS
2.2. no alarms – Process value, OoR or any other type alarms are raised in AMS.
Only Acceptable AMS Alarm is one for EMS communication loss.
2.3. values missing in AMS monitoring are indicated:
As missing such as “---“, “N/A”, 󠆯“OoR” 󠆯etc. 󠆯
Not 󠆯as 󠆯physical 󠆯values 󠆯such 󠆯as 󠆯“3276.7 󠆯°C”, 󠆯“327.67 󠆯bar” 󠆯or 󠆯“327.7 󠆯g/kWh” 󠆯etc.

In case above test cause slowdown or shutdown, it is an indication that AMS is not
configured correctly. If assistance from MAN-ES is needed in this respect, please
contact MAN-ES at: [email protected]

Best regards
MAN Energy Solutions

Allan Juul Larsen


Manager Operation
Software and Electronics