Ehsx 04 P 30 A
Ehsx 04 P 30 A
Operating instructions
English
Daikin Altherma integrated solar unit
Daikin Altherma
EHS(X/H)04P30A
EHS(X/H)B04P30A
EHS(X/H)08P30A
EHS(X/H)B08P30A
EHS(X/H)08P50A
EHS(X/H)B08P50A
EHS(X/H)16P50A
EHS(X/H)B16P50A
Using filling water and top-up water which does not meet the
stated quality requirements can cause a considerably reduced
service life of the equipment. The responsibility for this lies solely
with the operator.
Fig. 2-2 Design and components of the Daikin Altherma EHS(X/H)...P30A (external view and internal design)
For legend descriptions see tab. 2-1
Fig. 2-3 Design and components of the Daikin Altherma EHS(X/H)B...P30A (external view and internal design)
For legend descriptions see tab. 2-1
Fig. 2-4 Design and components of the Daikin Altherma EHS(X/H)...P50A (external view and internal design)
For legend descriptions see tab. 2-1
Fig. 2-5 Design and components of the Daikin Altherma EHS(X/H)B...P50A (external view and internal design)
For legend descriptions see tab. 2-1
7 2
Pressing
Pressfor more After switching on and successful initialisation, the display auto-
– Special level is called up.
than 5 secs. matically shows the standard display with rotary switch
position .
In the first commissioning, the setting for language selection is
displayed first.
● Select the language using the rotary switch.
Tab. 3-4 Functions of the exit button ● Confirm the changes with a brief press of the rotary switch.
Adaption to the special installation configuration is
carried out in the "Configuration" rotary switch
position (see section 3.4.8).
Keylock Function During the defrosting function, heat is drawn from the hot water
storage tank and the backup heater is turned on if required. De-
On pending on the heat demand for the defrosting function, heating
of the direct heating circuit may be interrupted temporarily.
After 8 minutes at most, the system returns to normal mode.
Keylock Function
3.4.1 System information (Info)
In this rotary switch position, the rotary switch can be used to call
up all the system temperatures, the type of Daikin Altherma
EHS(X/H), various software information and the operating sta-
tuses of all system components, one after the other. The number
of displayed parameters depends on the connected components.
No settings can be made to these values.
Keylock Function
● Place the rotary switch in the "Info" position.
Off
Standard display is shown (see fig. 3-2).
● Press the rotary switch briefly.
The parameter overview is displayed.
● Select the desired information level with the rotary switch.
Fig. 3-4 Activating and deactivating the key lock ● Confirm the changes with a brief push of the rotary switch.
The value is displayed (for example, see fig. 3-6).
● Select the individual information with the rotary switch.
More detailed explanations and possible setting values for this rotary switch setting
can be seen in chapter 6.10.
Page 3
windows.
storage tank, secondary sensor (tDHW2)
Short Explanation of the displayed value Tliq2 Current coolant temperature (tL2)
designation TA2 Actual outdoor temperature (measured by tem-
Mode Current mode of the heat pump: perature sensor of the external heat pump)
: Heating quiet Shows the status of the whisper mode
: Cooling
: Domestic hot water generation Tab. 3-5 Description of the operating data displayed as an overview
: Automatic defrosting function active
Ext Current energy mode of the heat pump:
LT: EVU function active and low tariff. Info
HT: EVU function active and standard tariff.
SGN: SMART GRID - Function active, normal
mode. Overview
SG1: SMART GRID - Function active, Discon- Water Pressure
nection: no heat pump operation, no frost
protection function.
SG2: SMART GRID - Function active, Switching
on recommendation, Operation with higher target
temperatures, cheaper electricity.
SG3: SMART GRID - Function active, Command
to switch on and storage tank charging to 70 °C,
cheaper electricity
- - -: No external mode active, heat pump works in
Page 1
normal mode.
RT Parameter [Room thermostat] / [Interlink fct]
= Off: - - -
Parameter [Room thermostat] = On:
– : Heating or cooling demand
– : No heating demand
Parameter [Interlink fct] = On (priority):
– - - -: Only frost protection
– IL1: Normal inflow target temperature
– IL2:
– Increased inflow target temperature in
heating operation
– Decreased inflow target temperature in
cooling operation
Pump Actual output of the internal heating circulation
pump in % Off
EHS Current output of the backup heater in kW
BPV Current position of the mixing valve 3UVB1
(100% = A, 0% = B)
TV Current inflow temperature after the plate heat Fig. 3-5 Display operating data overview
exchanger (tV1)
TVBH Current heating inflow temperature or temp. after
heating support heat exchanger (tV, BH)
TR Current heating return flow temperature (tR1)
Page 2
Summer
Standby Automatic 1
Reducing Automatic 2
Info
Overview
Water Pressure
T-HS
Operating Mode
Summer
Automatic 1
Automatic 2
Water Pressure
Fig. 3-7 Switching the operating mode
(e.g.: from "Standby" to "Automatic 1")
The hot water set temperatures for hot water generation for each Adjustment
individual timer programme are determined in the rotary switch In the rotary switch position we set the time intervals for
setting . the heating circuit, the integrated hot water generation and the
optional circulation pump.
● Place the rotary switch in the "DHW Set Temp" position.
● Place the rotary switch in the "Time Program"
The end figures of the parameter designations (1 - 3) position.
within this rotary switch setting designate the associ- An overview is displayed.
ation with each individual cycle of the timer programme.
● Select the timer programme to be set with the rotary switch.
● Confirm the changes with a brief push of the rotary switch.
● Select the temperature block to be set with the rotary switch. Settings are displayed.
● Confirm the changes with a brief push of the rotary switch.
● Select and change the value to be set with the rotary switch.
Settings are displayed. ● Confirm the changes with a brief push of the rotary switch.
● Set the temperature. More detailed explanations and possible setting values for this rotary switch setting
● Confirm the changes with a brief push of the rotary switch. can be seen in chapter 6.8 "Rotary switch setting: Time Program".
Change has been accepted. Jump back to previous dis- Permanent timer programmes
play. For the connected heating circuits and the storage tank charging
More detailed explanations and possible setting values for this rotary switch setting circuit, timer programmes regulate the heating circuit tempera-
can be seen in chapter 6.7. tures or the operating times for the circulation pump in ac-
cordance with the stipulated switching cycles. The switching
3.4.6 Unscheduled hot water generation cycles are saved in time blocks for which various set tempera-
You can charge the hot water up manually outside a hot water tures apply.
timer programme to the preset temperature set in parameter In the switching cycles the heating system is regulated differen-
[T-DHW Setpoint 1] in the rotary switch position . Heating up tiated into day and economy mode.
is carried out as a priority and independently of any other heating
The target room temperatures for these timer programmes are
programmes.
set in "Set Temp Day" , "Set Temp Night" and "DHW
● Place the rotary switch in the "DHW Install" position. Set Temp" .
An overview is displayed. The following switching time programmes are available:
● Select the parameter to be set with the rotary switch. – 2 timer programmes for the heating circuit, each with
– [1x Hot Water]: Activating one-off hot water generation. 3 possible time cycles
● Confirm the changes with a brief push of the rotary switch. – [HC Program 1]
● Setting parameters – [HC Program 2]
● Confirm the changes with a brief push of the rotary switch.
A separate input for each individual day of the week is
Begin unscheduled hot water generation.
possible, or in blocks of "Monday to Friday", "Saturday
to Sunday" and "Monday to Sunday".
Keylock Function
Access Rights
Expert
Outdoor type
Configuration
Setup
System Configuration Heating
Configuration
System Configuration
HC Configuration
DHW Configuration Heat-Slope
TA External temperature TV Flow temperature
TR Room temperature set value
Fig. 3-14 Heat curves
More detailed explanations and possible setting values for this function can be seen
HC Configuration in chapter 6.2.
More detailed explanations and possible setting values for this function can be seen
1 Parameter [Start T-Out Cooling] TA External temperature in sections 6.2.3 and 6.12.2.
2 Parameter [Max T-Out Cooling] TV Flow temperature
3 Parameter [T-Flow Cooling start] ― Cooling characteristic 3.6.5 Frost protection function
4 Parameter [T-Flow Cooling max] curve
5 Parameter [Min T-Flow Cooling] --- Possible parallel dis- If the outdoor temperature is below the parameter value [T-Frost
6 Target room temperature placement of the cool- Protect], the integrated heating circulation pump is switched on in
7 Cooling operation possible ing characteristic order to prevent the heating system from freezing.
curve
Fig. 3-15 Parameter-dependency of characteristic cooling curve In addition, the inflow, storage tank and connected room temper-
ature sensors are continually monitored. If the temperature
More detailed explanations and possible setting values for this function can be seen measured by any of these sensors drops below 7°C (in the case
in chapter 6.2.3.
of room temperature: 5°C), the frost protection function is auto-
matically activated.
3.6.4 Weather-controlled flow temperature regulation
When the frost protection function is active, the Controller RoCon
If the weather-controlled flow temperature regulation is active, HP standard display shows the symbol alongside the time.
the inflow target temperature (see info parameter [T-HS Set-
point], section 6.10) is determined automatically in accordance If the inflow heating temperature drops below 7°C, the Daikin Al-
with the set heating/cooling curve depending on the outside tem- therma EHS(X/H) heats up until the temperature reaches at least
perature. 12°C once more.
In delivery status, this function is activated. It can only be deacti- The function ceases once the outside temperature has risen to
vated or reactivated with the technician code (set point control). the set parameter value [T-Frost Protect] + 1 K is reached and
Contact your specialist heating technician for this. there are no other activation conditions present.
The weather-controlled flow temperature regulation can be opti- If low tariff functions are activated; with certain tech-
mised with the RoCon OT1 optional external temperature probe, nician settings the operation of the heat pumps by the
which can be installed on the north face of the building. If no energy supply company can be completely switched off
RoCon OT1 is installed, the Controller RoCon HP uses the value for a limited period of time. In such cases, no additional
for the outside temperature measured in the exterior heat pump heating is carried out and the internal device heating
unit. circulation pump is not switched on, even in frost-pro-
tection conditions.
If the room station (EHS157034) is additionally connected to the
Daikin Altherma EHS(X/H), the inflow target temperatures will be These situations can can arise when the "Overview" in-
controlled dependent on the weather and room temperature formation level (see section 3.4.1) in the operating data
(see tab. 6-3 / tab. 6-15, parameter [Room Influence]). field "Ext" displays the value "HT" or "SG1".
If a mixer module is connected
The heating/cooling curve setting for the assigned heating circuit
is configured as described above.
There is the option of operating the assigned heating circuit as a
a) Mixer extension
The outside temperature determined by the outside
temperature sensor connected to the Daikin Altherma
EHS(X/H) is transmitted to the mixer module via the CAN bus.
or as
b) Mixer extension with zone regulation
A separate outside temperature sensor (RoCon OT1) must
be connected to the mixer module. The assigned heating cir-
cuit is regulated based on the relevant outside temperature
for this zone.
When the terminal function is activated, the mixer module is op-
erated via the Controller RoCon HP of the Daikin Altherma
EHS(X/H), and the settings for the assigned heating circuit are
applied.
An active Legionella protection function (parameter [Anti-Le- 3. Execute the programme by briefly pressing on the rotary
gionella day]) involves heating the connected storage tank to a switch.
disinfection temperature 1 x a day or 1 x a week. The legionella The respective values are reset to the factory setting.
protection function is active for an hour. 4. Select "Return" with the rotary switch.
The maximum hot water temperature set by the user or 5. Confirm the changes with a brief push of the rotary switch.
the heating technician is ignored when hot water is
Possibility 2
heated for disinfection purposes.
Technician access rights permit all customer-specific pa-
A connected circulation pump is automatically switched rameter settings in the "Special Level" to be reset to the factory
on during thermal disinfection. setting according to tab. 6-1 to tab. 6-11.
Possibility 3
Setting the parameters for legionella protection is carried out in
If fundamental changes to the Daikin Altherma EHS(X/H)
the rotary switch setting "Configuration" in level "DHW
equipment for the function within the RoCon system are nec-
Configuration".
essary, the Basic Configuration can be reset using Technician
Using the factory settings, the storage tank is heated at 03:30 access rights to the Factory settings or can be redefined.
hours if the target hot water temperature is below 65°C at that
time.
After a reset to the factory settings via option 2 or 3, the
More detailed explanations and possible setting values for this function can be seen
in chapter 6.2.4. system must be configured again by the heating tech-
nician to the installation environment and all the cus-
tomer-specific parameters reset.
4.2.1 Requirements 5. Carry out a visual inspection for leaks on all joints internally.
Seal any leaks that occur in a professional manner.
CAUTION!
6. Set the dial on the controller to the required operating mode.
Commissioning in frosty conditions can result in
7. If a Daikin solar system is connected, commission this in
damage to the entire heating system.
● Only commission at temperatures below 0 °C when accordance with instructions provided. After disconnecting
the Daikin solar system, check the level in the buffer
a water temperature of at least 5 °C can be
storage tank once again.
guaranteed in the heating system and storage
tank.
Daikin recommends that you avoid operating the
system in extremely frosty conditions.
CAUTION!
C
A heating system that is shut down can freeze in the
B
event of frost and may suffer damage.
● If there is any risk of frost, drain any water from the 1.
decommissioned heating system. B
● If the heating system is not drained and there is a A
risk of frost, the power supplies must be secured
and the external main switch must remain switched 2. D
on. E
C
If the Daikin Altherma EHS(X/H) is not required for a long time, it Fig. 5-1 Connecting the drain- Optional: Removing the connec-
can be temporarily decommissioned. age hose tion piece from the safety overflow
Daikin therefore recommends that you do not disconnect the
system from power supply, but rather only place it in "Stand-By A KFE filling connection (Ac- E Threaded piece
Mode" (consult the operating manual for the control system). cessory KFE BA) F Sealing plug
B Safety overflow G Connecting angle
The system is then protected from frost. The pumps and valve C Connection piece for safety X Valve insert
protection functions are active. overflow
D Clamping piece
If it is not possible to guarantee the power supply when there is
danger of frost, Tab. 5-1 Legend from fig. 5-1 to fig. 5-6
– completely discharge the Daikin Altherma EHS(X/H) on the
water side, or Without solar installation
– suitable antifreeze measures must be taken for the connected
heating system and hot water storage tank (e.g. draining). ● Remove the cover plate
from the filling and
If there is a danger of frost and the power supply cannot emptying fitting. E
be guaranteed for just a few days, the unit's excellent ● When using the KFE
heat insulation means that the Daikin Altherma filling connection
EHS(X/H) does not have to be drained, provided that (Accessory KFE BA):
the storage tank temperature is monitored regularly and Remove the cover plate
does not fall below +3 °C. from the handle and
However, this does not provide frost protection for the unscrew the threaded
connected heat distribution system. piece (fig. 5-2, item E)
from the storage tank con-
tainer.
Fig. 5-2 Unscrew threaded piece
CAUTION!
Storage water will gush out as soon as the sealing Fig. 5-6 Assembling the in the
connecting angle KFE
plug is removed.
filling connection
X1 X2
2 4
X3 X4
1
X4
2.
1.
Fig. 5-5 Shutting off the valve insert and removing the blanking plug
from the connecting angle
Tab. 6-2 Parameter in rotary switch setting "Configuration" level "System Configuration"
For example: If the measured temperature is 2 K below the set value, the set flow tem-
perature is raised 2-times the set value.
T-Room Adj Only if the room station is connected and assigned to the heating circuit. E E -5.0 to +5.0 kW 0.0 K 1K
Individual adaptation of the room temperature relevant for control.
Should a systematic deviation of the room temperature as measured by the EHS157034
from the actual temperature in the living area of this room be detected, the measured val-
ue can be corrected by the set value.
T-Flow Day Only if the parameter [HC Function] = 1 is in delivery status is this function activated. It E E 20 - 90°C 40 °C 1 °C
can only be changed with a technician code. Contact your specialist heating technician
in this regard:
Setting the inflow target temperature for the heating circuit during the heating time when
in operating mode: "Automatic 1", "Automatic 2", "Heating".
T-Flow Night Only if the parameter [HC Function] = 1 is in delivery status is this function activated. It E E 10 - 90°C 10 °C 1 °C
can only be changed with a technician code. Contact your specialist heating technician
in this regard:
Setting the inflow target temperature for the heating circuit during the setback time when
in operating mode: "Automatic 1", "Automatic 2", "Reducing".
Cooling ( Can be used only if the assigned heat generator has a cooling function.)
Start T-Out Cooling Only if the parameter [HC Function] = 0 is in delivery status is this function activated. It E E 15 - 45°C 24 °C 1 °C
can only be changed with a technician code. Contact your specialist heating technician
in this regard:
Setting from which outside temperature the cooling operation with the highest cooling in-
feed target temperature [T-Flow Cooling start] starts (Setting condition: operating mode
"Cooling").
Max T-Out Cooling Only if the parameter [HC Function] = 0 is in delivery status is this function activated. It E E 20 - 45°C 35 °C 1 °C
can only be changed with a technician code. Contact your specialist heating technician
in this regard:
Setting to determine from which outdoor temperature the lowest cooling flow tempera-
ture [T-Flow Cooling max] is stipulated (Setting condition: operating mode "Cooling").
T-Flow Cooling start Only if the parameter [HC Function] = 0 is in delivery status is this function activated. It E E 5 - 25°C 18 °C 1 °C
can only be changed with a technician code. Contact your specialist heating technician
in this regard:
Setting the cooling inflow target temperature at the start of cooling mode (outside tem-
perature = parameter [Start T-Out Cooling]).
T-Flow Cooling max Only if the parameter [HC Function] = 0 is in delivery status is this function activated. It E E 5 - 25°C 8 °C 1 °C
can only be changed with a technician code. Contact your specialist heating technician
in this regard:
Setting the minimum cooling inflow target temperature. This is kept constant relative to
the outside temperature (parameter [Max T-Out Cooling]).
T-Flow Cooling Only if the parameter [HC Function] = 1 is in delivery status is this function activated. It E E 8 - 30°C 18 °C 1 °C
can only be changed with a technician code. Contact your specialist heating technician
in this regard:
Setting the cooling inflow target temperature (fixed value) when cooling mode is active.
Cooling Setpoint adj Parallel displacement of the cooling characteristic curve to match the set value. E E -5.0 to +5.0 kW 0.0 K 1K
Tab. 6-3 Parameter in rotary switch setting "Configuration" level "HC Configuration"
Tab. 6-4 Parameter in rotary switch setting "Configuration" level "DHW Configuration"
For example: If the measured temperature is 2 K below the set value, the set flow temperature
is raised 2-times the set value.
Tab. 6-15 Parameter in rotary switch setting "Configuration" level "Mixer Config"
7.1 General Certified people are those who have proof of expertise
Regular inspection and maintenance of the Altherma EHS(X/H) for the European Community for work on stationary
reduces energy consumption and ensures a long life and smooth refrigeration systems (heat pumps) and air conditioning
operation. systems, according to the F-Gases Directive (EC).
303/2008.
RISK OF ENVIRONMENTAL DAMAGE! – up to 3 kg coolant fill quantity: Expert certificate
Important information regarding the coolant used. category II
– 3 kg coolant fill quantity or over: Expert certifi-
The entire heat pump system contains coolant with cate category I
fluorinated greenhouse gases, which are listed in the
Kyoto Protocol and, if released, are harmful to the en-
vironment. 7.2 Removing the protective cover
Coolant type: R410A
GWP* value: 1975
* GWP = Global Warming Potential
1
2. Connect the filling hose (fig. 7-3, item 1) with back flush
prevention (1/2") and an external pressure gauge (on-site) to
the KFE cock (fig. 7-3, item 2) and secure from slipping using
a hose clamp.
3. Open the water cock (fig. 7-3, item 4) in the supply line.
4. Open KFE cock (fig. 7-3, item 2) and watch the pressure
1 gauge.
5. Fill the system with water until the system target pressure is
reached on the pressure gauge (System height +2 m,
whereby 1 m water column = 0.1 bar).
The overpressure valve must not be triggered!
6. Close KFE cock (fig. 7-3, item 2).
7. Switch on the power supply of the Altherma EHS(X/H).
8. Turn the rotary switch to the operating mode "Heat".
Daikin Altherma EHS(X/H) runs in the hot water heating
mode after the start phase.
9. During the hot water heating mode, continuously check the
water pressure at the external pressure gauge. Where
necessary, refill with water via the KFE cock (fig. 7-3, item 2).
10. Vent the entire heating network (open the regulation valve. At
the same time the under floor heating system can be filled and
flushed with the under floor heating distributor.).
Air Purge
(Can only be performed by an expert heating
technician.)
3UV DHW
An integrated Protocol saves up to 15 error related or other infor- Manual Operation E75
mation messages regarding the operating status that last oc- FA failure
curred.
Depending on the operating mode, messages are also forwarded
to connected room stations or room thermostats.
8.1.3 Troubleshooting
E 9001/80 1
Fault T-return 2 Troubleshooting the electrical, coolant and hydraulic
Inside Unit: Heating Module 3 systems of the Daikin Altherma EHS(X/H) may be per-
Address: 0 4 formed only by authorised and trained heating experts.
● Set date.
Date and time are not correctly set. ● Set time.
● Check week day-switching time allocation.
Switching time program
is not working or pro- Incorrect operating mode set. ● Set to operating mode "Automatic 1" or "Automatic 2".
grammed switching times
are being carried out at 1. Place the rotary switch in the "Info" position.
the wrong time. During a switching time the user made a man-
2. Place the rotary switch in the "Operating Mode"
ual setting (e.g. changed the target tempera-
position.
ture, changed the operating mode)
3. Select correct operating mode.
● Carry out RESET of control unit. o do so, disconnect
Control unit does not
Operating system of control unit crashed. the system from the power supply for at least 10 s and
respond to entries
then switch on again.
● Carry out RESET of control unit. To do so, disconnect
the system from the power supply for at least 10 s and
Operating data are not then switch on again.
Operating system of control unit crashed.
updated ● Have the heating system checked by a Daikin heating
technician.
Heating request switched off (e.g. switching ● Check the operating mode setting.
time program is in the economy phase, exter- ● Check the request parameters.
nal temperature is too high, parameters for ● Check setting of the date, time and switching time
backup heater (EKBUxx) are set incorrectly, program on the control unit.
hot water request is active)
● Have the heating system checked by a Daikin heating
Refrigerant compressor is not working. technician.
Heating does not warm
up System is in the operating mode "Cool- ● Switch the operating mode to "Heating".
ing".
Settings for off-peak mains connection do not ● Have the heating system checked by a Daikin heating
correspond to settings for electrical connec- technician.
tions.
The power company has sent the high-cost ● Wait for the repeat off-peak rate signal which reacti-
signal. vates the power supply.
Hot water supply switched off (e.g. switching ● Check the operating mode setting.
time program is in the economy phase, ● Check the request parameters.
parameters for hot water supply have been
set incorrectly).
Storage tank charging temperature too low. ● Increase the target hot water temperature.
Hot water does not warm Draw-off rate too high. ● Reduce the draw-off rate, limit throughput.
up
● Check the switching times for room heating and hot
Output of heat pump too low.
water supply for overlaps.
"Cooling" switched off (e.g. room thermostat ● Check the operating mode setting.
Room cooler does
requires "Cooling", but switching time pro- ● Check the request parameters.
not cool
gram is in economy phase, outside tempera- ● Check setting of the date, time and switching time
ture too high). program on the control unit.
● Have the heating system checked by a Daikin heating
Coolant compressor is not working. technician.
System is in the operating mode "Heating". ● Switch the operating mode to "Cooling".
The heat pump has automatically switched to the "Heating"
operating mode so as to be able to guarantee frost protec-
Outdoor temperature < 4 °C
tion should the external temperature drop further. Room
cooling not possible.
● Check that all stop valves of the water circuit are
completely open.
● Fully vent the heating system and device-internal
circulation pump.
● On the control unit (rotary switch position "Info" )
Water flow too low.
check that there is sufficient water pressure (>0.5 bar),
if necessary, refill the heating water
● Have the heating system checked by a Daikin heating
Cooling effect of technician.
room cooling insufficient
● Check the primary pressure in the expansion
container and the water pressure, if necessary, refill
Water quantity in the heating system too low
the heating water and reset the primary pressure (see
chapter 7.5).
● Have the coolant level checked by a Daikin specialist
Quantity of coolant in the heating system too
heating technician.
low or too high.
Ancillary heater An additional heat generator (e.g. backup heater or external heating boiler) which is part of the heating
system and which helps bring the system up to the inflow target temperature in case of an insufficient
or ineffective heat pumping process.
Anti-legionella system Periodic heating of storage water to >60°C for preventative elimination of pathogenic bacteria (le-
gionella) in the hot water circuit.
Backup demand Operating situation in which the desired infeed temperature cannot be reached or cannot be achieved
efficiently through the heat pump process. As a result, an extra heater (e.g. backup heater) is used to
support the Daikin Wärmeerzeuger to generate heat.
Backup heater Optional electric ancillary heater for general support of the Daikin Wärmeerzeuger during heat gener-
ation.
Circulation circuit Is an optional ancillary circuit in the hot water circuit which serves to ensure that hot water flows out of
the discharge point as soon as the tap is turned on. In this circuit the hot water circulates via a circu-
lation pump between the hot water storage tank and the draw-off point.
Circulation pump An optional electrical circulation pump which permanently re-circulates the hot water in the hot water
pipes (feed from the tap connection back to the domestic hot water storage tank) and thus provides it
at each draw-off point without delay. Circulation is particularly effective in widely branched piping net-
works. In hot water distribution systems without a circulation pipe, at first the water cooled in the outlet
pipe escapes during the tapping process until the outlet pipe is sufficiently heated by the hot water
flowing subsequently.
Control Device electronics, with which the processes for heat generation and heat distribution for the heating
system are controlled. The Altherma EHS(X/H) consists of many electronic components. The com-
ponent that is most important to the operator is the operating element at the front of the heat generator
which has operating elements (rotary switch, rotary button and Exit key) and a display.
Direct circuit The water circuit that is heated directly by the heat generator, without additional temperature regu-
lation.
Domestic hot water gener- Operating status of the heat generator, in which heat is generated at increased temperatures and sup-
ation plied to the hot water circuit, e.g. filling the hot water storage tank.
Flow pipe Part of the hydraulic circuit that directs the heated water from heat generator to the heating surfaces.
Heat exchanger A part that transfers thermal energy from one circuit to another. Both circuits are separated from each
other hydraulically by a wall in the heat exchanger.
Heat pumping process In a closed coolant circuit, the coolant absorbs heat from the surrounding air. Compressing this coolant
results in a higher temperature which can then be transferred to the heating unit (thermodynamic
circuit).
Heating characteristic curve Mathematical relationship between the external temperature and the target flow temperature
(synonym = heating curve), in order to achieve the desired room temperature at all outside tempera-
tures.
Hot water circuit Is the water circuit in which the cold water is heated and directed to the hot water discharge point.
Low tariff mains connection A special mains connection to the energy supplier, which offers various cheaper rates during so-called
(HT/NT) low-load periods for electrical current (day-, night-, heat pump current, etc.).
Mixing circuit A heating circuit in which a heating temperature that deviates from that of the direct circuit is set by
means of the controlled mixing of the return flow of this heating circuit.
Modulation Automatic and continuous adjustment of the thermal / pump output to the particular heat requirement,
without having to switch various heating / pumping stages or cycles.
Nominal output Maximum heat output given by the heat generator at certain operating temperatures under test condi-
tions.
Operating mode User or Altherma EHS(X/H)-demanded function of the heat generator (e.g. room heating, hot water
heating, stand-by, etc.).
Parameter A value that influences the execution of programs or processes or defines specific states.
Refrigerant A material which is used for thermal transfer in a heating system. At low temperature and low pressure,
heat is absorbed and at high temperature and a high pressure, heat is emitted.
Return flow Part of the hydraulic circuit that directs the cooled water from the radiators in the rooms back to the
heat generator via the piping system.
SMART GRID (SG) Intelligent energy utilisation for economical heating. Using a special electricity meter it is possible to
receive a "SMART GRID signal" from the energy supply company.
Depending on the signal from the energy supply company, the heat pump is turned off, put into
standard mode or run in high-temperature mode.
Storage tank charging circuit Is the water circuit which heats the water stored in the hot water storage tank (not to be confused with
the hot water circuit).
Tuesday
HC Program 1
Wednesday
Thursday
Friday
Saturday
Sunday
Monday
Tuesday
HC Program 2
Wednesday
Thursday
Friday
Saturday
Sunday
Tuesday
DHW Program 1
Wednesday
Thursday
Friday
Saturday
Sunday
Monday
Tuesday
DHW Program 2
Wednesday
Thursday
Friday
Saturday
Sunday
Tuesday
Circulation Time
Wednesday
Thursday
Friday
Saturday
Sunday
10.2 Parameter
● Enter your parameter changes in the table below.
Rotary switch Parameter levels / Old value New value Date Comments
setting Parameter
008.1420944_08 05/2014