W353-E1-06 CPM - ProgrManual
W353-E1-06 CPM - ProgrManual
W353-E1-06 CPM - ProgrManual
W353-E1-06
SYSMAC CPM1/CPM1A/CPM2A/CPM2C/SRM1(-V2)
Programmable Controllers
PROGRAMMING MANUAL
CPM1/CPM1A/CPM2A/CPM2C/SRM1(-V2)
Programmable Controllers
Programming Manual
Revised February 2008
iv
Notice:
OMRON products are manufactured for use according to proper procedures by a qualified operator and only for the purposes described in this manual. The following conventions are used to indicate and classify precautions in this manual. Always heed the information provided with them. Failure to heed precautions can result in injury to people or damage to property. !
DANGER
Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
! WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury, or property damage.
! Caution
Visual Aids
The following headings appear in the left column of the manual to help you locate different types of information. Note Indicates information of particular interest for efficient and convenient operation of the product. 1, 2, 3... 1. Indicates lists of one sort or another, such as procedures, checklists, etc.
OMRON, 1999
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of OMRON. No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
vi
TABLE OF CONTENTS
PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 Intended Audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Operating Environment Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Application Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
xvii
xviii xviii xviii xx xxi
SECTION 1 PC Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1 1-2 1-3 PC Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Basic PC Operation and I/O Processes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CPM2C Changes in SW2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1
2 16 21
25
26 45 77 94 97 131 134 146 147 147 147 148 150 153 157 158 159 160 163
165
166 193 214 219
225
226 227 231 268 281
307
308 313 323
vii
333
334 334 335 354 356 358 360
361
364 364 364 366 367 370 376 377 381 381 381 383 385 385 388 404 411 421 432 439 457 467 471 479 483 484 487 497 501 505
511
512 523 537
viii
TABLE OF CONTENTS
SECTION 9 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9-1 9-2 9-3 9-4 9-5 9-6 9-7 9-8 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Programming Console Operation Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Programming Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . User-defined Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Operating Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Error Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Host Link Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Troubleshooting Flowcharts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
549
550 550 551 552 553 555 557 557
Appendices
A B C D E F G Programming Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Error and Arithmetic Flag Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Memory Areas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I/O Assignment Sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Program Coding Sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . List of FAL Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Extended ASCII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 559 565 569 587 589 593 595
597 603
ix
Note
1. Version 2 (-V2) of the SRM1 is included beginning with following revision of the manual: W318-E1-3. 2. Refer to sections on the CPM2C for information on CPM2C instructions and Expansion Units.
For programming the CPM1, CPM1A, CPM2A, CPM2C (including the CPM2C-S), and SRM1(-V2) PCs, use the CX-Programmer, special Support Software that runs in a Windows environment. The SYSMAC Support Software and SYSMAC-CPT Support Software can also be used. Please refer to the relevant manuals listed in the following table when using any one of Support Software.
Name CX-Programmer version 3.1 CX-Programmer version 4.0 SYSMAC Support Software Model No. Manual Catalog No. W414 W425 W247 W248 W332 W333
g p WS02-CXPC1-EV3 CX-Programmer Operation Manual WS02-CXPC1-EV4 C500-ZL3AT1-E SYSMAC Support Software Operation Manual: Basic SYSMAC Support Software Operation Manual: C-series PCs WS02-CPTB1-E SYSMAC-CPT Support Software Quick Start Guide SYSMAC-CPT Support Software User Manual
Please read this manual carefully and be sure you understand the information provided before attempting to program or operate the PC. Section 1 explains the PC Setup. The PC Setup can be used to control the operating parameters. Section 2 explains special features of the PC. Section 3 describes how to use the CPM1A-MAD01 and CPM2C-MAD11 Analog I/O Units, the CPM1ATSjjj and CPM2C-TSjjj Temperature Sensor Units, and the CPM1A-SRT21 and CPM2C-SRT21 CompoBus/S I/O Link Units.
! WARNING Failure to read and understand the information provided in this manual may result in personal injury or death, damage to the product, or product failure. Please read each section in its entirety and be sure you understand the information provided in the section and related sections before attempting any of the procedures or operations given.
xi
xii
WARRANTY
OMRONs exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NONINFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY. In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRONS ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
xiii
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customers application or use of the products. At the customers request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product, machine, system, or other application or use. The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible uses of the products, nor is it intended to imply that the uses listed may be suitable for the products: Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this manual. Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles, safety equipment, and installations subject to separate industry or government regulations. Systems, machines, and equipment that could present a risk to life or property. Please know and observe all prohibitions of use applicable to the products. NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the users programming of a programmable product, or any consequence thereof.
xiv
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual specifications of purchased products.
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this manual is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of OMRONs test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability.
The information in this manual has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical, or proofreading errors, or omissions.
xv
xvi
PRECAUTIONS
This section provides general precautions for using the Programmable Controller (PC) and related devices. The information contained in this section is important for the safe and reliable application of the Programmable Controller. You must read this section and understand the information contained before attempting to set up or operate a PC system. 1 Intended Audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Operating Environment Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Application Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xviii xviii xviii xx xxi
xvii
Safety Precautions
Intended Audience
This manual is intended for the following personnel, who must also have knowledge of electrical systems (an electrical engineer or the equivalent). Personnel in charge of installing FA systems. Personnel in charge of designing FA systems. Personnel in charge of managing FA systems and facilities.
General Precautions
The user must operate the product according to the performance specifications described in the operation manuals. Before using the product under conditions which are not described in the manual or applying the product to nuclear control systems, railroad systems, aviation systems, vehicles, combustion systems, medical equipment, amusement machines, safety equipment, and other systems, machines, and equipment that may have a serious influence on lives and property if used improperly, consult your OMRON representative. Make sure that the ratings and performance characteristics of the product are sufficient for the systems, machines, and equipment, and be sure to provide the systems, machines, and equipment with double safety mechanisms. This manual provides information for programming and operating the Unit. Be sure to read this manual before attempting to use the Unit and keep this manual close at hand for reference during operation. ! WARNING It is extremely important that a PC and all PC Units be used for the specified purpose and under the specified conditions, especially in applications that can directly or indirectly affect human life. You must consult with your OMRON representative before applying a PC System to the above-mentioned applications.
Safety Precautions
! WARNING Do not attempt to take any Unit apart while the power is being supplied. Doing so may result in electric shock. ! WARNING Do not attempt to disassemble, repair, or modify any Units. Any attempt to do so may result in malfunction, fire, or electric shock. ! WARNING Always turn OFF the power supply to the PC before attempting any of the following. Not turning OFF the power supply may result in malfunction or electric shock. Assembling the Units. Mounting or dismounting I/O Units, CPU Units, or any other Units. Connecting or wiring the cables. Connecting or disconnecting the connectors. Setting DIP switches. Replacing the battery ! WARNING Do not touch any of the terminals or terminal blocks while the power is being supplied. Doing so may result in electric shock.
xviii
Safety Precautions
! WARNING Always ground the system to 100 or less when installing the Units. Not connecting to a ground of 100 or less may result in electric shock. ! WARNING Provide safety measures in external circuits (i.e., not in the Programmable Controller), including the following items, to ensure safety in the system if an abnormality occurs due to malfunction of the PC or another external factor affecting the PC operation. Not doing so may result in serious accidents. Emergency stop circuits, interlock circuits, limit circuits, and similar safety measures must be provided in external control circuits. The PC will turn OFF all outputs when its self-diagnosis function detects any error or when a severe failure alarm (FALS) instruction is executed. As a countermeasure for such errors, external safety measures must be provided to ensure safety in the system. The PC outputs may remain ON or OFF due to deposition or burning of the output relays or destruction of the output transistors. As a countermeasure for such problems, external safety measures must be provided to ensure safety in the system. When the 24-VDC output (service power supply to the PC) is overloaded or short-circuited, the voltage may drop and result in the outputs being turned OFF. As a countermeasure for such problems, external safety measures must be provided to ensure safety in the system. ! WARNING When handling the Memory Backup Battery, never drop, disassemble, distort, short-circuit, recharge, heat to a temperature exceeding 100C, or throw into fire. The Battery may explode, catch fire, or leak fluid if mishandled in any of these ways. ! Caution Execute online edit only after confirming that no adverse effects will be caused by extending the cycle time. Otherwise, input signals may not be readable. When transferring programs to other nodes, or when making changes to I/O memory, confirm the safety of the destination node before transfer. Not doing so may result in injury. Tighten the screws on the terminal block of the AC Power Supply Unit to the torque specified in the operation manual. The loose screws may result in fire or malfunction. When connecting the PC to a personal computer or other peripheral device, either ground the 0-V side of the PC or do not ground the PC at all. Although some grounding methods short the 24-V side, as shown in the following diagram, never do so with the PC.
INCORRECT Grounding: Shorting the 24-V side of the Power Supply Non-isolated DC power supply 24 V
! Caution
! Caution
! Caution
0V
0V
0V
PC
Peripheral device
xix
xx
Application Precautions
Application Precautions
Observe the following precautions when using the PC System. ! Caution Failure to abide by the following precautions could lead to faulty operation of the PC or the system, or could damage the PC or PC Units. Always heed these precautions.
Fail-safe measures must be taken by the customer to ensure safety in the event of incorrect, missing, or abnormal signals caused by broken signal lines, momentary power interruptions, or other causes. Construct a control circuit so that power supply for the I/O circuits does not come ON before power supply for the Unit. If power supply for the I/O circuits comes ON before power supply for the Unit, normal operation may be temporarily interrupted. If the operating mode is changed from RUN or MONITOR mode to PROGRAM mode, with the IOM Hold Bit ON, the output will hold the most recent status. In such a case, ensure that the external load does not exceed specifications. (If operation is stopped because of an operating error, including errors generated by FALS instructions, the values in the internal memory of the CPU Unit will be saved, but the outputs will all turn OFF.) For models with only the super-capacitor installed, the contents of the READ/ WRITE enable area of the DM area, HR area, AR area, and CNT data area may be damaged if the power is turned OFF for a long time. To prevent such damage, provide ladder program that will check AR 1314 to ensure proper operation of the system. The life of relays largely varies depending on switching conditions. Be sure to test operating conditions using actual Units and use the product within the specified number of switchings so as not to cause any performance problems. Using the product with performance problems may result in defective insulation between circuits or burning of the relays.
Installation
Install the Units properly as specified in the relevant operation manual(s). Improper installation of the Units may result in malfunction. Do not install the PC or PC Units in places where the Units may be affected by excessive noise. Doing so may result in malfunction. Install the Units properly so that they will not fall off. Be sure that all the mounting screws, terminal screws, and cable connector screws are tightened to the torque specified in the relevant manuals. Incorrect tightening torque may result in malfunction. Install the Expansion I/O Unit connector cover to the last Expansion I/O Unit to prevent dust or foreign matter from entering inside the Unit. Not doing so may result in malfunction. Be sure that the terminal blocks, expansion cables, and other items with locking devices are properly locked into place. Improper locking may result in malfunction. Be sure to use cables as specified in the relevant manual(s). Install external breakers and take other safety measures against short-circuiting in external wiring. Insufficient safety measures against short-circuiting may result in burning. When wiring signal lines, do not place them in the same duct as high-voltage lines or power lines. Doing so may result in malfunction.
xxi
Application Precautions
5
Be sure that terminal blocks and connectors are connected in the specified direction with the correct polarity. Not doing so may result in malfunction. Leave the labels attached CPM1 or CPM2A Units when wiring to prevent wiring cuttings from entering the Units. Attach the labels supplied with CPM1A or CPM2C Units or provide other protective covers when wiring to prevent dust or wiring cuttings from entering the Units. Remove the labels after the completion of wiring to ensure proper heat dissipation. Leaving the labels attached may result in malfunction. Use the connectors and wiring materials specified in the relevant manual(s). Be sure to wire according to the relevant manual(s). Incorrect wiring may result in burning.
Disconnect the functional ground terminal when performing withstand voltage tests. Always use the power supply voltages specified in the operation manual(s). An incorrect voltage may result in malfunction or burning. Take appropriate measures to ensure that the specified power with the rated voltage and frequency is supplied. Be particularly careful in places where the power supply is unstable. Do not apply voltages to the input terminals in excess of the rated input voltage. Excess voltages may result in burning. Do not apply voltages or connect loads to the output terminals in excess of the maximum switching capacity. Excess voltage or loads may result in burning. Double-check all wiring and switch settings before turning ON the power supply. Incorrect wiring may result in burning. Check the user program for proper execution before actually running it on the Unit. Not checking the program may result in an unexpected operation. When using, storing, or transporting the product, keep within the specifications listed in the relevant manual(s). Confirm that no adverse effect will occur in the system before attempting any of the following. Not doing so may result in an unexpected operation. Changing the operating mode of the PC. Force-setting/force-resetting any bit in memory. Changing the present value of any word or any set value in memory. Before touching a Unit, be sure to first touch a grounded metallic object to discharge any static built-up. Not doing so may result in malfunction or damage. Do not touch the Expansion I/O Unit Connecting Cable while the power is being supplied to prevent any malfunction due to static electricity. Do not pull on the cables or bend the cables beyond their natural limit. Doing either of these may break the cables. Do not place objects on top of the cables. Doing so may break the cables. When disposing of Units or other products, be sure to do so according to local laws and regulations. When using a Temperature Sensor Unit with a thermocouple input (CPM1A-TS001/002, CPM2C-TS001), observe the following precautions: With the CPM1A-TS001/002, do not remove the cold junction compensator attached at the time of delivery. If the cold junction compensator is removed the Unit will not be able to measure temperatures correctly.
Handling Precautions
xxii
Application Precautions
5
With the CPM1A-TS001/002, each of the input circuits is calibrated with the cold junction compensator attached to the Unit. If the Unit is used with the cold junction compensator from other Units, the Unit will not be able to measure temperatures correctly. With the CPM1A-TS001/002 or the CPM2C-TS001, do not touch the cold junction compensator. Doing so may result in incorrect temperature measurement.
Maintenance
When replacing a part, be sure to confirm that the rating of a new part is correct. Not doing so may result in malfunction or burning. When the CPU Unit is replaced, resume operation only after transferring to the new CPU Unit the contents of the DM and HR Areas required for operation. Not doing so may result in an unexpected operation. When transporting the Units, use special packing boxes. Do not subject the Units or other products to excessive vibration or shock during transportation and do not to drop them. Store the Units within the following temperature and humidity ranges: Storage temperature: 25 to 65C Storage humidity: 25% to 85% (with no icing or condensation)
xxiii
SECTION 1 PC Setup
This section explains the PC Setup in the CPM1, CPM1A, CPM2A, CPM2C (including the CPM2C-S), and SRM1(-V2) PCs. The PC Setup can be used to control the operating parameters. To change the PC Setup, refer to the Operation Manual of the PC for Programming Console procedures. Refer to the SSS Operation Manual: C-series PCs for SSS procedures. Refer to the SYSMAC-CPT Support Software Quick Start Guide (W332) and User Manual (W333) for SYSMAC-CPT Support Software procedures. If you are not familiar with OMRON PCs or ladder diagram program, you can read 1-1 PC Setup as an overview of the operating parameters available for the CPM1/CPM1A, CPM2A/CPM2C, and SRM1(-V2). You may then want to read Section 5 Memory Areas, Section 6 Ladder-diagram Programming, and related instructions in Section 7 Instruction Set before completing this section. 1-1 PC Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1-1 Changing the PC Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1-2 CPM1/CPM1A PC Setup Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1-3 CPM2A/CPM2C PC Setup Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1-4 SRM1(-V2) PC Setup Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Basic PC Operation and I/O Processes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2-1 Startup Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2-2 Hold Bit Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2-3 Program Memory Write-protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2-4 RS-232C Port Servicing Time (CPM2A/CPM2C/SRM1(-V2) Only) . . . . . . . . . 1-2-5 Peripheral Port Servicing Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2-6 Cycle Monitor Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2-7 Minimum Cycle Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2-8 Input Time Constants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2-9 Error Log Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CPM2C Changes in SW2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 2 3 7 13 16 16 17 17 18 18 18 19 19 21 21
1-2
1-3
PC Setup
Section
1-1
1-1
PC Setup
The PC Setup comprises various operating parameters that control PC operation. In order to make the maximum use of PC functionality when using interrupt processing and communications functions, the PC Setup may be customized according to operating conditions. At the time of shipping, the defaults are set for general operating conditions, so that the PC can be used without having to change the settings. You are, however, advised to check the default values before operation.
Default Values
The default values for the PC Setup are 0000 for all words (except for the low battery error enable in DM 6655 bits 12 to 15 for CPM2A CPU Units). The default values can be reset at any time by turning ON SR 25210 in PROGRAM mode. ! Caution When data memory (DM) is cleared from a Programming Device, the PC Setup settings will also be cleared to all zeros.
PC Setup
Section
1-1
Startup Processing (DM 6600 to DM 6614) The following settings are effective after transfer to the PC only after the PC is restarted. DM 6600 00 to 07 Startup mode (effective when bits 08 to 15 are set to 02). 00: PROGRAM; 01: MONITOR 02: RUN 08 to 15 Startup mode designation 00: According to communications port setting switch and peripheral port connection (See table at the bottom of this page.) 01: Continue operating mode last used before power was turned OFF. 02: Setting in 00 to 07 DM 6601 00 to 07 Not used. 08 to 11 12 to 15 DM 6602 00 to 03 IOM Hold Bit (SR 25212) Status at Startup 0: Reset; 1: Maintain (See note 3.) Forced Status Hold Bit (SR 25211) Status at Startup 0: Reset; 1: Maintain (See note 3.) Program memory write-protection 0: Program memory unprotected 1: Program memory write-protected (except DM 6602 itself) Programming Console display language 0: English; 1: Japanese Not used. Not used. 00: If data could not be saved with the built-in capacitor (AR 1314 ON), a memory error will not be generated. 01: If data could not be saved with the built-in capacitor (AR 1314 ON), a memory error will be generated. Not used. Not used. 16
17
17
04 to 07 08 to 15 00 to 15 00 to 07
DM 6603 DM 6604
The following settings are effective after transfer to the PC the next time operation is started. DM 6615, 00 to 15 Not used. DM 6616 DM 6617 00 to 07 Servicing time for peripheral port (effective when bits 08 to 15 are set to 01) 00 to 99 (BCD): Percentage of cycle time used to service peripheral. 08 to 15 Peripheral port servicing setting enable 00: 5% of the cycle time 01: Use time in 00 to 07. DM 6618 00 to 07 Cycle monitor time (effective when bits 08 to 15 are set to 01, 02, or 03) 00 to 99 (BCD): Setting (see 08 to 15) 08 to 15 Cycle monitor enable (Setting in 00 to 07 x unit; 99 s max.) 00: 120 ms (setting in bits 00 to 07 disabled) 01: Setting unit: 10 ms 02: Setting unit: 100 ms 03: Setting unit: 1 s DM 6619 00 to 15 Cycle time 0000: Variable (no minimum) 0001 to 9999 (BCD): Minimum time in ms
18
18
19
PC Setup
Word(s) Bit(s) Function
Section
1-1
Page
Interrupt Processing (DM 6620 to DM 6639) The following settings are effective after transfer to the PC the next time operation is started. DM 6620 00 to 03 Input constant for IR 00000 to IR 00002 0: 8 ms; 1: 1 ms; 2: 2 ms; 3: 4 ms; 4: 8 ms; 5: 16 ms; 6: 32 ms; 7: 64 ms; 8: 128 ms 04 to 07 Input constant for IR 00003 and IR 00004 (Setting same as bits 00 to 03) 08 to 11 Input constant for IR 00005 and IR 00006 (Setting same as bits 00 to 03) 12 to 15 Input constant for IR 00007 to IR 00011 (Setting same as bits 00 to 03) DM 6621 00 to 07 Input constant for IR 001 00: 8 ms; 01: 1 ms; 02: 2 ms; 03: 4 ms; 04: 8 ms; 05: 16 ms; 06: 32 ms; 07: 64 ms; 08: 128 ms DM 6622 DM 6623 DM 6624 DM 6625 DM 6626 to DM 6627 DM 6628 08 to 15 00 to 07 08 to 15 00 to 07 08 to 15 00 to 07 08 to 15 00 to 07 08 to 15 00 to 15 00 to 03 04 to 07 08 to 11 12 to 15 00 to 15 Input constant for IR 002 (Setting same as for IR 001.) Input constant for IR 003 (Setting same as for IR 001.) Input constant for IR 004 (Setting same as for IR 001.) Input constant for IR 005 (Setting same as for IR 001.) Input constant for IR 006 (Setting same as for IR 001.) Input constant for IR 007 (Setting same as for IR 001.) Input constant for IR 008 (Setting same as for IR 001.) Input constant for IR 009 (Setting same as for IR 001.) Not used. Not used. Interrupt enable for IR 00003 (0: Normal input; 1: Interrupt input; 2: Quick-response) Interrupt enable for IR 00004 (0: Normal input; 1: Interrupt input; 2: Quick-response) Interrupt enable for IR 00005 (0: Normal input; 1: Interrupt input; 2: Quick-response) Interrupt enable for IR 00006 (0: Normal input; 1: Interrupt input; 2: Quick-response) Not used. 79 19
The following settings are effective after transfer to the PC the next time operation is started. DM 6640 to 00 to 15 Not used. DM 6641 DM 6642 00 to 03 High-speed counter mode 0: Up/down counter mode; 4: Incrementing counter mode 04 to 07 High-speed counter reset mode 0: Z phase and software reset; 1: Software reset only 08 to 15 High-speed counter enable 00: Dont use high-speed counter; 01: Use high-speed counter with settings in 00 to 07 DM 6643, 00 to 15 Not used. DM 6644
86
PC Setup
Word(s) Bit(s) Function
Section
1-1
Page
Peripheral Port Settings The following settings are effective after transfer to the PC. DM 6645 to 00 to 15 Not used. DM 6649 DM 6650 00 to 07 Port settings 00: Standard (1 start bit, 7-bit data, even parity, 2 stop bits, 9,600 bps) 01: Settings in DM 6651 08 to 11 12 to 15 (Other settings will cause a non-fatal error and AR 1302 will turn ON.) Link area for 1:1 PC Link via peripheral port: 0: LR 00 to LR 15 Communications mode 0: Host Link; 2: 1:1 PC Link Slave; 3: 1:1 PC Link Master; 4: 1:1 NT Link (Other settings will cause a non-fatal error and AR 1302 will turn ON.) DM 6651 00 to 07 Baud rate 00: 1.2K, 01: 2.4K, 02: 4.8K, 03: 9.6K, 04: 19.2K, 05 to 07: Cannot be used (see note 2) (Other settings will cause a non-fatal error and AR 1302 will turn ON.) Frame format Start Length Stop Parity 00: 1 bit 7 bits 1 bit Even 01: 1 bit 7 bits 1 bit Odd 02: 1 bit 7 bits 1 bit None 03: 1 bit 7 bits 2 bits Even 04: 1 bit 7 bits 2 bits Odd 05: 1 bit 7 bits 2 bits None 06: 1 bit 8 bits 1 bit Even 07: 1 bit 8 bits 1 bit Odd 08: 1 bit 8 bits 1 bit None 09: 1 bit 8 bits 2 bits Even 10: 1 bit 8 bits 2 bits Odd 11: 1 bit 8 bits 2 bits None (Other settings will cause a non-fatal error and AR 1302 will turn ON.) DM 6652 00 to 15 Transmission delay (Host Link) (See note 4.) 0000 to 9999: In ms. (Other settings will cause a non-fatal error and AR 1302 will turn ON.) DM 6653 00 to 07 Node number (Host Link) 00 to 31 (BCD) (Other settings will cause a non-fatal error and AR 1302 will turn ON.) 08 to 15 Not used. DM 6654 00 to 15 Not used. Error Log Settings (DM 6655) The following settings are effective after transfer to the PC. DM 6655 00 to 03 Style 0: Shift after 7 records have been stored 1: Store only first 7 records (no shifting) 2 to F: Do not store records 04 to 07 Not used. 08 to 11 Cycle time monitor enable 0: Detect long cycles as non-fatal errors 1: Do not detect long cycles 12 to 15 Not used. 21 226
08 to 15
Note
1. When the startup mode is set to continue the operating mode last used before the power was turned off, that operating mode will be retained by the built-in capacitor. If the power remains off for longer than the backup time of the capacitor, the data may be lost. (For details on the holding time, refer to the CPM1A or CPM1 Operation Manual.)
PC Setup
Section
1-1
2. Do not set to 05 to 07. If set to this value, the CPM1/CPM1A will not operate properly and the RUN PC Setup Error Flag (AR 1302 ON) will not turn ON. 3. Retention of IOM Hold Bit (SR 25212) Status If the IOM Hold Bit Status at Startup (DM 6601, bits 08 to 11) is set to Maintain with the IOM Hold Bit (SR 25212) turned ON, operation can be started with the I/O memory (I/O, IR, LR) status just as it was before the power was turned OFF. (The input area is refreshed at startup, however, so it is overwritten by the most recently updated input status.) Retention of Forced Status Hold Bit (SR 25211) Status If the Forced Status Hold Bit Status at Startup (DM 6601, bits 12 to 15) is set to Maintain with the Forced Status Hold Bit (SR 25211) turned ON, operation can be started with the forced set/reset status just as it was before the power was turned OFF. (When starting up in RUN Mode, however, the forced set/reset status is cleared.) Even if the IOM Hold Bit Status at Startup or Forced Status Hold Bit Status at Startup is set to Maintain, the IOM Hold Bit (SR 25212) or Forced Status Hold Bit (SR 25211) status may be cleared if the power remains OFF for longer than the backup time of the built-in capacitor. (For details on the holding time, refer to the CPM1A or CPM1 Operation Manual.) At this time the I/O memory will also be cleared, so set up the system so that clearing the I/O memory will not cause problems. 4. The transmission delay is the delay between the previous transmission and the next transmission.
Host computer Command Command
Programmable Controller
Response
5. If an out-of-range value is set, the following communications conditions will result. In that case, reset the value so that it is within the permissible range. Communications mode: Host Link Communications format: Standard settings (1 start bit, 7-bit data; even parity, 2 stop bits, 9,600 bps) Transmission delay: No Node number: 00
PC Setup
Section
1-1
17
04 to 07 08 to 11
161
DM 6603 DM 6604
12 to 15 00 to 15 00 to 07 08 to 15 00 to 15
DM 6605 to DM 6614
Note For CPM2C PCs with lot number of 3180O or earlier, the startup operating mode will be as shown in the following table if bits 08 to 15 of DM 6600 are set to 00.
Peripheral p p port connected to d Nothing Programming Console Other Programming Device Communications port setting switch SW2 OFF PROGRAM Mode set on Programming Console mode switch PROGRAM (The CPM2C will not be able to communicate with Programming Device.) SW2 ON RUN PROGRAM (The CPM2C will not be able to communicate with Programming Console.) PROGRAM
PC Setup
Word(s) Bit(s) Function
Section
1-1
Page
Cycle Time Settings (DM 6615 to DM 6619) The following settings are effective after transfer to the PC the next time operation is started. DM 6615 DM 6616 00 to 15 00 to 07 08 to 15 Not used. Servicing time for RS-232C port (Effective when bits 08 to 15 are set to 01.) 00 to 99 (BCD): Percentage of cycle time used to service RS-232C port. RS-232C port servicing setting enable 00: 5% of the cycle time 01: Use time in bits 00 to 07. Servicing time for peripheral port (Effective when bits 08 to 15 are set to 01.) 00 to 99 (BCD): Percentage of cycle time used to service peripheral. Peripheral port servicing setting enable 00: 5% of the cycle time 01: Use time in bits 00 to 07. Cycle monitor time (Effective when bits 08 to 15 are set to 01, 02, or 03.) 00 to 99 (BCD): Setting (See bits 08 to 15, below.) A fatal error will be generated and PC operation will stop if the cycle time exceeds the cycle monitor time set here. Cycle monitor enable (Setting in 00 to 07 units; 99 s max.) 00: 120 ms (setting in bits 00 to 07 disabled) 01: Setting units: 10 ms 02: Setting units: 100 ms 03: Setting units: 1 s Minimum cycle time 0000: Variable (no minimum) 0001 to 9999 (BCD): Minimum time in ms 19 18
DM 6617
00 to 07 08 to 15
18
DM 6618
00 to 07
18
08 to 15
DM 6619
00 to 15
Interrupt Processing (DM 6620 to DM 6639) The following settings are effective after transfer to the PC the next time operation is started. DM 6620 00 to 03 04 to 07 08 to 11 12 to 15 00 to 07 Input time constant for IR 00000 to IR 00002 0: 10 ms; 1: 1 ms; 2: 2 ms; 3: 3 ms; 4: 5 ms; 5: 10 ms; 6: 20 ms; 7: 40 ms; 8: 80 ms Input time constant for IR 00003 and IR 00004 (Setting same as bits 00 to 03) Input time constant for IR 00005 and IR 00006 (Setting same as bits 00 to 03) Input time constant for IR 00007 to IR 00011 (Setting same as bits 00 to 03) Input time constant for IR 001 00: 10 ms 01: 1 ms 02: 2 ms 03: 3 ms 04: 5 ms 05: 10 ms 06: 20 ms 07: 40 ms 08: 80 ms Input constant for IR 002 (Setting same as for IR 001.) Input constant for IR 003 (Setting same as for IR 001.) Input constant for IR 004 (Setting same as for IR 001.) Input constant for IR 005 (Setting same as for IR 001.) Input constant for IR 006 (Setting same as for IR 001.) Input constant for IR 007 (Setting same as for IR 001.) Input constant for IR 008 (Setting same as for IR 001.) Input constant for IR 009 (Setting same as for IR 001.) Not used. Not used. Interrupt enable for IR 00003 (0: Normal input; 1: Interrupt input; 2: Quick-response) Interrupt enable for IR 00004 (0: Normal input; 1: Interrupt input; 2: Quick-response) Interrupt enable for IR 00005 (0: Normal input; 1: Interrupt input; 2: Quick-response) (Set to 0 in CPM2C CPU Units with 10 I/O points.) Interrupt enable for IR 00006 (0: Normal input; 1: Interrupt input; 2: Quick-response) (This input does not exist in CPM2C CPU Units with 10 I/O points.) 30 19
DM 6621
08 to 15 00 to 07 08 to 15 00 to 07 08 to 15 00 to 07 08 to 15 00 to 07 08 to 15 00 to 15 00 to 03 04 to 07 08 to 11 12 to 15
PC Setup
Word(s) DM 6629 Bit(s) 00 to 03 04 to 07 08 to 15 00 to 15 Function PV coordinate system for pulse output 0 0: Relative coordinates; 1: Absolute coordinates PV coordinate system for pulse output 1 0: Relative coordinates; 1: Absolute coordinates Not used. Not used.
Section
1-1
Page 101
The following settings are effective after transfer to the PC the next time operation is started. DM 6640 to 00 to 15 Not used. DM 6641 DM 6642 00 to 03 High-speed counter mode 0: Differential phase mode (5 kHz) 1: Pulse + direction input mode (20 kHz) 2: Up/down input mode (20 kHz) 4: Increment mode (20 kHz) 04 to 07 08 to 15 High-speed counter reset mode 0: Z phase and software reset; 1: Software reset only High-speed counter/Synchronized pulse control for IR 00000 to IR 00002 00: Dont use either function. 01: Use as high-speed counters. 02: Use for synchronized pulse control (10 to 500 Hz). 03: Use for synchronized pulse control (20 Hz to 1 kHz). 04: Use for synchronized pulse control (300 Hz to 20 kHz). Not used.
47, 56
The following settings are effective after transfer to the PC. If the CPM2A CPU Units Communications Switch is ON, communications through the CPM2As RS-232C port are governed by the default settings (all 0) regardless of the settings in DM 6645 through DM 6649. If pin 2 of the CPM2C CPU Units DIP switch is ON, communications through the CPM2Cs RS-232C port are governed by the default settings (all 0) regardless of the settings in DM 6645 through DM 6649. DM 6645 226 00 to 03 Port settings 0: Standard (1 start bit, 7 data bits, even parity, 2 stop bits, 9,600 bps), Host Link unit number: 0 1: Settings in DM 6646 (Any other setting will cause a non-fatal error and AR 1302 will turn ON.) 04 to 07 CTS control setting 0: Disable CTS control; 1: Enable CTS control (Any other setting will cause a non-fatal error and AR 1302 will turn ON.) 08 to 11 12 to 15 Link words for 1:1 data link 0: LR 00 to LR 15 (Any other settings are ineffective.) Communications mode 0: Host Link; 1: No-protocol; 2: 1:1 PC Link Slave; 3: 1:1 PC Link Master; 4: NT Link (Any other setting causes a non-fatal error and turns ON AR 1302.)
PC Setup
Word(s) DM 6646 Bit(s) 00 to 07 08 to 15 Function Baud rate 00: 1,200 bps; 01: 2,400 bps; 02: 4,800 bps; 03: 9,600 bps; 04: 19,200 bps Frame format Start bits Data bits Stop bits Parity 00: 1 bit 7 bits 1 bit Even 01: 1 bit 7 bits 1 bit Odd 02: 1 bit 7 bits 1 bit None 03: 1 bit 7 bits 2 bits Even 04: 1 bit 7 bits 2 bits Odd 05: 1 bit 7 bits 2 bits None 06: 1 bit 8 bits 1 bit Even 07: 1 bit 8 bits 1 bit Odd 08: 1 bit 8 bits 1 bit None 09: 1 bit 8 bits 2 bits Even 10: 1 bit 8 bits 2 bits Odd 11: 1 bit 8 bits 2 bits None
Section
1-1
Page 226
DM 6647
00 to 15
(Any other setting specifies standard settings (1 start bit, 7 data bits; even parity, 2 stop bits, 9,600 bps), causes a non-fatal error, and turns ON AR 1302.) Transmission delay (0000 to 9999 BCD sets a delay of 0 to 99,990 ms.) 226 (Any other setting specifies a delay of 0 ms, causes a non-fatal error, and turns ON AR 1302.)
DM 6648
00 to 07
Node number (Host Link) 00 to 31 (BCD) (Any other setting specifies a node number of 00, causes a non-fatal error, and turns ON AR 1302.) Start code selection for no-protocol communications 0: Disables start code; 1: Enables start code in DM 6649 (Any other setting disables the start code, causes a non-fatal error, and turns ON AR 1302.) End code selection for no-protocol communications 0: Disables end code; 1: Enables end code in DM 6649; 2: Sets end code of CR, LF. (Any other setting disables the end code, causes a non-fatal error, and turns ON AR 1302.) Start code (00 to FF) (This setting is valid only when bits 8 to 11 of DM 6648 are set to 1.) When bits 12 to 15 of DM 6648 set to 0: Sets the number of bytes to receive. (00: 256 bytes; 01 to FF: 1 to 255 bytes) When bits 12 to 15 of DM 6648 set to 1: Sets the end code. (00 to FF)
226
08 to 11
12 to 15
DM 6649
00 to 07 08 to 15
226
10
PC Setup
Word(s) Bit(s) Function
Section
1-1
Page
Peripheral Port Communications Settings The following settings are effective after transfer to the PC. If the CPM2A CPU Units Communications Switch is ON, communications through the peripheral port are governed by the default settings (all 0) regardless of the settings in DM 6650 through DM 6654. The CPM2As Communications Switch setting has no effect on communications with a Programming Console connected to the peripheral port or Support Software set for peripheral bus communications. The CPM2A CPU Unit will auto-detect either Programming Device and automatically establish communications. SW2 on the CPM2C CPU Unit must be OFF in order for communications through the CPM2Cs peripheral port to be governed by the settings in DM 6650 through DM 6654. DM 6650 226 00 to 03 Port settings 00: Standard (1 start bit, 7 data bits, even parity, 2 stop bits, 9,600 bps), Host Link unit number: 0 01: Settings in DM 6651 (Any other setting specifies standard settings, causes a non-fatal error, and turns ON AR 1302.) Not used. Communications mode 0: Host Link or peripheral bus; 1: No-protocol (Any other setting specifies Host Link, causes a non-fatal error, and turns ON AR 1302.) Baud rate 00: 1,200 bps; 01: 2,400 bps; 02: 4,800 bps; 03: 9,600 bps; 04: 19,200 bps Frame format Start bits Data bits Stop bits Parity 00: 1 bit 7 bits 1 bit Even 01: 1 bit 7 bits 1 bit Odd 02: 1 bit 7 bits 1 bit None 03: 1 bit 7 bits 2 bits Even 04: 1 bit 7 bits 2 bits Odd 05: 1 bit 7 bits 2 bits None 06: 1 bit 8 bits 1 bit Even 07: 1 bit 8 bits 1 bit Odd 08: 1 bit 8 bits 1 bit None 09: 1 bit 8 bits 2 bits Even 10: 1 bit 8 bits 2 bits Odd 11: 1 bit 8 bits 2 bits None (Any other setting specifies standard settings (1 start bit, 7 data bits; even parity, 2 stop bits, 9,600 bps), causes a non-fatal error, and turns ON AR 1302.) 226 Transmission delay (0000 to 9999 BCD sets a delay of 0 to 99,990 ms.) (Any other setting specifies a delay of 0 ms, causes a non-fatal error, and turns ON AR 1302.) DM 6653 00 to 07 Node number (Host Link) 00 to 31 (BCD) (Any other setting specifies a node number of 00, causes a non-fatal error, and turns ON AR 1302.) Start code selection for no-protocol communications 0: Disables start code; 1: Enables start code in DM 6649 (Any other setting disables the start code, causes a non-fatal error, and turns ON AR 1302.) End code selection for no-protocol communications 0: Disables end code; 1: Enables end code in DM 6649; 2: Sets end code of CR, LF. (Any other setting disables the end code, causes a non-fatal error, and turns ON AR 1302.)
04 to 11 12 to 15
DM 6651
00 to 07 08 to 15
DM 6652
00 to 15
08 to 11
12 to 15
11
PC Setup
Word(s) DM 6654 Bit(s) 00 to 07 08 to 15 Start code (00 to FF) (This setting is valid only when bits 8 to 11 of DM 6648 are set to 1.) When bits 12 to 15 of DM 6648 set to 0: Sets the number of bytes to receive. (00: 256 bytes; 01 to FF: 1 to 255 bytes) Function
Section
1-1
Page 226
When bits 12 to 15 of DM 6648 set to 1: Sets the end code. (00 to FF) Error Log Settings (DM 6655) The following settings are effective after transfer to the PC. DM 6655 00 to 03 Style 0: Shift after 7 records have been stored 1: Store only first 7 records (no shifting) 2 to F: Do not store records 04 to 07 Not used. 08 to 11 Cycle time monitor enable 0: Generate a non-fatal error for a cycle time that is too long. 1: Do not generate a non-fatal error. 12 to 15 Low battery error enable 0: Generate a non-fatal error for low battery voltage. 1: Do not generate a non-fatal error. Low battery error detection is disabled (i.e., set to 1) by default in CPU Units that do not have a clock. If the PC Setup is cleared, the setting will changed to 0 and a low battery error will occur. Bits 12 to 15 should always be set to 0 when the optional CPM2C-BAT01 is mounted. 21
12
PC Setup
Section
1-1
Startup Processing (DM 6600 to DM 6614) The following settings are effective after transfer to the PC only after the PC is restarted. DM 6600 00 to 07 Startup mode (effective when bits 08 to 15 are set to 02). 00: PROGRAM; 01: MONITOR 02: RUN 08 to 15 Startup mode designation 00: Programming Console switch 01: Continue operating mode last used before power was turned off 02: Setting in 00 to 07 DM 6601 00 to 07 Not used. 08 to 11 IOM Hold Bit (SR 25212) Status 0: Reset; 1: Maintain (See caution on page 17.) 12 to 15 Forced Status Hold Bit (SR 25211) Status 0: Reset; 1: Maintain DM 6602 00 to 03 Program memory write-protection 0: Program memory unprotected 1: Program memory write-protected (except DM 6602 itself) 04 to 07 08 to 11 12 to 15 00 to 03 Programming Console display language 0: English; 1: Japanese Expansion Instructions 0: Default settings; 1: User settings Not used. Maximum number of CompoBus/S devices 0: Max. no. 32 1: Max. no. 16 CompoBus/S communications mode setting (V2 only) 0: High-speed communications 1: Long-distance communications Not used. 00: If data could not be saved for a power interruption (AR 1314 ON), a memory error will not be generated. 01: If data could not be saved for a power interruption (AR 1314 ON), a memory error will be generated. Not used. Not used. 16
17
17
DM 6603
04 to 07
DM 6604
08 to 15 00 to 07
The following settings are effective after transfer to the PC the next time operation is started. DM 6615 00 to 15 Not used. DM 6616 00 to 07 Servicing time for RS-232C port (effective when bits 08 to 15 are set) 00 to 99 (BCD): Percentage for cycle time used to service peripheral. 08 to 15 RS-232C port servicing enable 00: 5% of the cycle time 01: Use time in 00 to 07. DM 6617 00 to 07 Servicing time for peripheral port (effective when bits 08 to 15 are set to 01) 00 to 99 (BCD): Percentage of cycle time used to service peripheral. 08 to 15 Peripheral port servicing setting enable 00: 5% of the cycle time 01: Use time in 00 to 07.
18
18
13
PC Setup
Word(s) DM 6618 Bit(s) 00 to 07 08 to 15 Function Cycle monitor time (effective when bits 08 to 15 are set to 01, 02, or 03) 00 to 99 (BCD): Setting (see 08 to 15) Cycle monitor enable (Setting in 00 to 07 x unit; 99 s max.) 00: 120 ms (setting in bits 00 to 07 disabled) 01: Setting unit: 10 ms 02: Setting unit: 100 ms 03: Setting unit: 1 s Cycle time 0000: Variable (no minimum) 0001 to 9999 (BCD): Minimum time in ms Not used.
Section
1-1
Page 18
DM 6619
00 to 15
19
DM 6620 to DM 6644
00 to 15
RS-232C Port Settings The following settings are effective after transfer to the PC. DM 6645 00 to 03 Port settings 0: Standard (1 start bit, 7-bit data, even parity, 2 stop bits, 9,600 bps) 1: Settings in DM 6646 CTS control settings 0: Disable; 1: Set When using a 1:1 data link: Sets the link area for 1:1 PC Link. 0: LR 00 to LR 15 Not 0: Disable When using a 1:N NT Link: Sets the maximum PT node number. 1 to 7 12 to 15 Communications mode 0: Host Link; 1: No-protocol; 2: 1:1 PC Link Slave; 3: 1:1 PC Link Master; 4: 1:1 NT Link; 5: 1:N NT Link (Any other setting specifies Host Link mode, causes a non-fatal error, and turns ON AR 1302.) The 1:N NT Link is supported by SRM1-C02-V2 only. DM 6646 00 to 07 08 to 15 Baud rate 00: 1.2K, 01: 2.4K, 02: 4.8K, 03: 9.6K, 04: 19.2K Frame format Start Length Stop 00: 1 bit 7 bits 1 bit 01: 1 bit 7 bits 1 bit 02: 1 bit 7 bits 1 bit 03: 1 bit 7 bits 2 bits 04: 1 bit 7 bits 2 bits 05: 1 bit 7 bits 2 bits 06: 1 bit 8 bits 1 bit 07: 1 bit 8 bits 1 bit 08: 1 bit 8 bits 1 bit 09: 1 bit 8 bits 2 bits 10: 1 bit 8 bits 2 bits 11: 1 bit 8 bits 2 bits Other: 1 bit 7 bits 2 bits 268
04 to 07 08 to 11
Parity Even Odd None Even Odd None Even Odd None Even Odd None Even
DM 6647 DM 6648
00 to 15 00 to 07 08 to 11 12 to 15
AR 1302 will turn ON to indicate a non-fatal system setting error if any value not between 00 and 11 is set. Transmission delay (Host Link) 0000 to 9999 (BCD): Set in units of 10 ms, e.g., setting of 0001 equals 10 ms Node number (Host Link, effective when bits 12 to 15 of DM 6645 are set to 0.) 00 to 31 (BCD) Start code enable (RS-232C, effective when bits 12 to 15 of DM 6645 are set to 1.) 0: Disable; 1: Set End code enable (RS-232C, effective when bits 12 to 15 of DM 6645 are set to 1.) 0: Disable (number of bytes received) 1: Set (specified end code) 2: CR, LF
14
PC Setup
Word(s) DM 6649 Bit(s) 00 to 07 08 to 15 Function Start code (RS-232C) 00 to FF (binary) When bits 12 to 15 of DM 6648 are set to 0: Number of bytes received 00: Default setting (256 bytes) 01 to FF: 1 to 255 bytes
Section
1-1
Page 268
When bits 12 to 15 of DM 6648 are set to 1: End code (RS-232C) 00 to FF (binary) Peripheral Port Settings The following settings are effective after transfer to the PC. DM 6650 00 to 03 Port settings 00: Standard (1 start bit, 7-bit data, even parity, 2 stop bits, 9,600 bps) 01: Settings in DM 6651 04 to 07 08 to 11 12 to 15 (Other settings will cause a non-fatal error and AR 1302 will turn ON.) Not used. Not used. Communications mode 0: Host Link; 1: No-protocol (Other settings will cause a non-fatal error and AR 1302 will turn ON.) DM 6651 00 to 07 08 to 15 Baud rate 00: 1.2K, 01: 2.4K, 02: 4.8K, 03: 9.6K, 04: 19.2K Frame format Start Length Stop 00: 1 bit 7 bits 1 bit 01: 1 bit 7 bits 1 bit 02: 1 bit 7 bits 1 bit 03: 1 bit 7 bits 2 bits 04: 1 bit 7 bits 2 bits 05: 1 bit 7 bits 2 bits 06: 1 bit 8 bits 1 bit 07: 1 bit 8 bits 1 bit 08: 1 bit 8 bits 1 bit 09: 1 bit 8 bits 2 bits 10: 1 bit 8 bits 2 bits 11: 1 bit 8 bits 2 bits Other: 1 bit 7 bits 2 bits 268
Parity Even Odd None Even Odd None Even Odd None Even Odd None Even
AR 1302 will turn ON to indicate a non-fatal system setting error if any value not between 00 and 11 is set. DM 6652 00 to 15 Transmission delay (Host Link) 0000 to 9999 (BCD): Set in units of 10 ms. (Other settings will cause a non-fatal error and AR 1302 will turn ON.) DM 6653 00 to 07 Node number (Host Link) 00 to 31 (BCD) (Other settings will cause a non-fatal error and AR 1302 will turn ON.) 08 to 11 Start code enable (RS-232C, effective when bits 12 to 15 of DM6650 are set to 1.) 0: Disable 1: Set End code enable (RS-232C, effective when bits 12 to 15 of DM6650 are set to 1.) 0: Disable (number of bytes received) 1: Set (specified end code) 2: CR, LF 268
12 to 15
15
Section
1-2
Page 268
08 to 15
21
12 to 15
Note If an out-of-range value is set, the following communications conditions will result. In that case, reset the value so that it is within the permissible range. Communications mode: Communications format: Host Link Standard settings (1 start bit, 7-bit data; even parity, 2 stop bits, 9,600 bps) No 00
1-2
Startup Mode Designation 00: Programming Console Mode Selector (If not connected: RUN mode) 01: Operating mode last used before power was turned off 02: Mode set in bits 00 to 07 Startup Mode (Bits 08 to 15: Valid when bits 00 to 07 are set to 02) 00: PROGRAM mode 01: MONITOR mode 02: RUN mode Default: Programming Console Mode Selector or RUN mode when Programming Console is not connected.
16
Section
1-2
Note When the startup mode designation is set to 00 and pin 2 of the CPM2C CPU Units DIP switch is ON, the CPM2C will enter RUN mode automatically, regardless of the Programming Consoles mode switch setting.
SR 25211 setting 0: Clear status 1: Retain status SR 25212 setting 0: Clear status 1: Retain status Default: Clear both.
Always 00
The Forced Status Hold Bit (SR 25211) determines whether or not the forced set/reset status is retained when changing from PROGRAM mode to MONITOR mode. The IOM Hold Bit (SR 25212) determines whether or not the status of IR bits and LR bits is retained when PC operation is started and stopped. ! Caution In PCs with capacitor backup, do not use the I/O Hold Bit Status and Forced Status Hold Bit Status Bits (DM 6601) when the power to the PC is going to be turned off longer than the memory backup time of the internal capacitor. If the memory backup time is exceeded, memory status will be unstable even if the I/O Hold Bit Status and Forced Status Hold Bit Status Bits are used. Unpredictable results may occur if operation is attempted with unstable memory status. 1. The memory backup time of the internal capacitor varies with the ambient temperature, but is 20 days at 25_C. Refer to hardware specifications for more details. 2. The memory backup time assumes that the internal capacitor is fully charged before power is turned off. Fulling charging the capacitor requires that power is supplied to the CPU Unit for at least 15 minutes.
Note
Always 00 Programming Console messages 0: English 1: Japanese Program memory 0: Not write-protected 1: Write-protected Default: English displays, not write-protected
17
Section
1-2
Note DM 6602 itself can still be changed after the program memory has been writeprotected by setting bits 04 to 07 of DM 6602 to 1.
Servicing time setting enable 00: Disabled (5% used) 01: Enabled (setting in bits 00 to 07 used) Servicing time (%, valid with bits 08 to 15 are 01) 00 to 99 (BCD, two digits) Default: 5% of cycle time
Example: If DM 6616 is set to 0110, the RS-232C port will be serviced for 10% of the cycle time. The servicing time will be 0.34 ms minimum. The entire servicing time will not be used unless processing requests exist.
Servicing time setting enable 00: Disabled (5% used) 01: Enabled (setting in bits 00 to 07 used) Servicing time (%, valid with bits 08 to 15 are 01) 00 to 99 (BCD, two digits) Default: 5% of cycle time
Example: If DM 6617 is set to 0115, the peripheral port will be serviced for 15% of the cycle time. The servicing time will be 0.34 ms minimum. The entire servicing time will not be used unless processing requests exist.
Cycle Monitor Time Enable and Units 00: Setting disabled (time fixed at 120 ms) 01: Setting in 00 to 07 enabled; units:10 ms 02: Setting in 00 to 07 enabled; units:100 ms 03: Setting in 00 to 07 enabled; units:1 s Cycle monitor time setting (When bits 08 to 15 are not 00) 00 to 99 (2 digits BCD; units set in bits 08 to 15.) Default: 120 ms.
18
Section
1-2
The cycle monitor time is used for checking for extremely long cycle times, as can happen when the program goes into an infinite loop. If the cycle time exceeds the cycle monitor setting, a fatal error (FALS 9F) will be generated. Note 1. The units used for the maximum and current cycle times recorded in the AR area (AR 14 and AR 15) are determined by the setting for the cycle monitor time in DM 6618, as shown below. Bits 08 to 15 set to 01: Bits 08 to 15 set to 02: Bits 08 to 15 set to 03: 0.1 ms 1 ms 10 ms
2. If the cycle time is 1 s or longer, the cycle time read from Programming Devices will be 999.9 ms. The correct maximum and current cycle times will be recorded in the AR area. Example If 0230 is set in DM 6618, an FALS 9F error will not occur until the cycle time exceeds 3 s. If the actual cycle time is 2.59 s, the current cycle time stored in the AR area will be 2590 (ms), but the cycle time read from a Programming Device will be 999.9 ms. A cycle time over error (non-fatal) will be generated when the cycle time exceeds 100 ms unless detection of long cycle times is disable using the setting in DM 6655.
Cycle time (4 digits BCD) 0000:Cycle time variable 0001 to 9999: Minimum cycle time (Unit: 1 ms) Default: Cycle time variable
If the actual cycle time is shorter than the minimum cycle time, execution will wait until the minimum time has expired. If the actual cycle time is longer than the minimum cycle time, then operation will proceed according to the actual cycle time. AR 2405 will turn ON if the minimum cycle time is exceeded.
19
Section
1-2
Set the input time constants for CPM1/CPM1A inputs from a Programming Device. Input Time Constants for IR 000
Bit 15 DM 6620 Time constant for IR 00007 to IR 00011 (1 digit BCD; see below.) Time constant for IR 00005 to IR 00006 (1 digit BCD; see below.) Time constant for IR 00003 to IR 00004 (1 digit BCD; see below.) Time constant for IR 00000 to IR 00002 (1 digit BCD; see below.) Default: 0000 (8 ms for each) 0
Time constant for IR 002, IR 004, IR 006, and IR 008 Time constant for IR 001, IR 003, IR 005, IR 007, and IR 009 Default: 0000 (8 ms for each)
The nine possible settings for the input time constant are shown below. (Set only the rightmost digit for each setting for IR 000.) 00: 8 ms 05: 16 ms 01: 1 ms 06: 32 ms 02: 2 ms 07: 64 ms 03: 4 ms 08: 128 ms 04: 8 ms
The CPM1/CPM1As I/O response time is the input time constant (1 ms to 128 ms; default is 8 ms) + the cycle time. Refer to 8-1 CPM1/CPM1A Cycle Time and I/O Response Time for more details. CPM2A/CPM2C PCs Set the input time constants for CPM2A/CPM2C inputs from a Programming Device. Input Time Constants for IR 000
Bit 15 DM 6620 Time constant for IR 00007 to IR 00011 (1 digit BCD; see below.) Time constant for IR 00005 to IR 00006 (1 digit BCD; see below.) Time constant for IR 00003 to IR 00004 (1 digit BCD; see below.) Time constant for IR 00000 to IR 00002 (1 digit BCD; see below.) Default: 0000 (10 ms for each) 0
Time constant for IR 002, IR 004, IR 006, and IR 008 Time constant for IR 001, IR 003, IR 005, IR 007, and IR 009 Default: 0000 (10 ms for each)
20
Section
1-3
The nine possible settings for the input time constant are shown below. (Set only the rightmost digit for IR 000.) 00: 10 ms 01: 1 ms 02: 2 ms 03: 3 ms 04: 5 ms 05: 10 ms 06: 20 ms 07: 40 ms 08: 80 ms
0
Always 0
Low battery voltage detection 0: Detect 1: Dont detect Cycle time over detection 0: Detect 1: Dont detect
Error log storage method 0: Error records for the 7 most recent errors always stored (older errors deleted). 1: Only the first 7 error records stored (no errors stored beyond that point). 2 to F: Error records not stored. Default: Low battery voltage and cycle time over errors detected, and error records stored for the 7 most recent errors.
Battery errors and cycle time overrun errors are non-fatal errors. For details on the error log, refer to Section 9 Troubleshooting. Note The low battery error is applicable to CPM2A/CPM2C only. This digit isnt used in CPM1/CPM1A/SRM1(-V2) PCs and CPM2C PCs that arent equipped with a battery.
1-3
21
Section
1-3
The following instructions apply to CPU Units with lot numbers of 3180O (August 2000) or earlier. The previous CPU Units do not detect a Programming Console connected to the peripheral port, and SW2 of the DIP switch was used to set either Programming Console or Other device. SW2 Setting
Communications Switch
Setting OFF ON
Meaning Programming Console connected to peripheral port. Device other than Programming Console connected to peripheral port.
SW1 Setting
Setting OFF ON Meaning Use PC Setup settings for RS-232C port (DM 6645 to DM 6649). Use default settings for RS-232C port.
The relationship between the PC Setup settings, the setting of SW2, and the startup operating mode for previous CPU Units is shown in the following table.
PC Setup Address DM6600 Bits 08 to 15 Setting 00 Hex CPM2C Operating Mode p g According to communications switch SW2 and peripheral port device. Peripheral device p SW2 setting Nothing connected Programming Console Other OFF PROGRAM mode According to Programming Console key switch. PROGRAM mode (See note.) ON RUN mode PROGRAM mode (See note.) PROGRAM mode
00 to 07
Note: Communications will not be possible between the CPM2C and the peripheral device for these combinations. Mode used immediately before power interruption Mode specified in bits 00 to 07. PROGRAM mode MONITOR mode RUN mode
Note
1. The default setting for DM 6600, bits 06 to 15 is 00 Hex, i.e., according to the communications switch on the front panel. If SW2 is set for connecting a device other than a Programming Console to the peripheral connector, the CPU Unit will start in RUN mode as soon as power is turned ON. Be sure that adequate precautions are taken to ensure safety. 2. If SW2 is for connecting a device other than a Programming Console to the peripheral connector, the CPU Unit will start in RUN mode as soon as power is turned ON even it a device is connected to the RS-232C port. Be sure that adequate precautions are taken to ensure safety.
22
Section
1-3
CPM2C-CN111
XW2Z-200S-V XW2Z-500S-V
CS1W-CN118
23
2-2 2-3
2-4 2-5
2-6
2-7 2-8 2-9 2-10 2-11 2-12 2-13 2-14 2-15 2-16
25
Section
2-1
2-1
Types of Interrupts
Interrupt programs are defined as interrupt subroutines within the user program. Just like ordinary subroutines, an interrupt subroutine is defined by SBN(92) and RET(93). It is written at the end of the normal program.
Normal program
Interrupt program
Subroutine
1, 2, 3...
1. A new interrupt can be defined in an interrupt subroutine, and an existing one can be cleared. 2. Within any given interrupt subroutine, it is not possible to write another subroutine for processing another interrupt. Do not nest another interrupt subroutine between the SBN(92) and RET(93) instructions.
26
Section
2-1
3. It is not possible to write a subroutine program within an interrupt subroutine. Do not nest an ordinary subroutine program between the SBN(92) and RET(93) instructions. 4. It is not possible to write an interrupt subroutine within an ordinary subroutine program. Do not nest an interrupt subroutine between the SBN(92) and RET(93) instructions. When an interrupt subroutine is defined, an SBS UNDEFD error will be generated during the program check but execution will be normal. ! Caution Although IORF(97) can be used in interrupt subroutines, you must be careful of the interval between IORF(97) executions. If IORF(97) is executed too frequently, a fatal system error may occur (FALS 9F), stopping operation. The interval between executions of IORF(97) should be at least 1.3 ms + total execution time of the interrupt subroutine. The order of priority for interrupts is as follows:
Count-up interrupts
>
If an interrupt with a higher priority is generated. during interrupt program execution, the interrupt that is currently being processed will be stopped and the new interrupt will be processed first. Then the original interrupt will be resumed after the higher-priority interrupt processing has been completed. If interrupts of the same priority are generated simultaneously, they will be processed in the following order: Interrupt input 0 Interrupt input 1 Interrupt input 2 Interrupt input 3 (including count-up mode) Interval timer interrupt High-speed counter interrupt
2-1-1 Processing the Same Memory Locations with the Main Program and Interrupt Subroutines
If a memory location is manipulated both by the main program and an interrupt subroutine, an interrupt mask must be set to disable interrupts. When an interrupt occurs, execution of the main program will be interrupted immediately, even during execution of an instruction. The intermediate processing results is saved for use after completing the interrupt subroutine, i.e., when the interrupt subroutine has been executed, execution of the main program is started from the same position with data restored to the previous condition. If any of the memory locations being used by the main program are changed in the interrupt subroutine, the changes will be lost when data is restored to the previous state when restarting execution of the main program. It is thus necessary to disable interrupts before and enable interrupts after any instructions that should be executed to completion even if an interrupt occurs. Processing Interrupted between 1st and 3rd Operands
27
Section
2-1
When the interrupt occurs while processing ADD, the addition result, 1235, is saved temporarily in memory and not stored in DM 0000. Although #0010 is moved to DM 0000 in the interrupt program, the addition result that was saved is written to DM 0000 as soon as processing returns to the main program, effectively undoing the results of the interrupt program. Countermeasure for Above Problem
28
Section
2-1
Processing was interrupted for BSET when #1234 was not yet written to DM 0010. Therefore, in the comparison at point *1, the contents of DM 0000 and DM 0001 are not equal and processing stops with A in the OFF state. As a result, although the contents of DM 0000 and DM 0010 agree at the value 1234, an incorrect comparison result is reflected in comparison result output A. Countermeasure for Above Problem
29
Section
2-1
Normal program
Interrupt program
Subroutine
Note Input points 00005 and 00006 do not exist in CPM2C CPU Units with only 10 I/O points or in CPM2C-S CPU Units.
Input number (Note 1) 00003 00004 00005 (See note 3.) 00006 (See note 3.) 0 1 2 3 Interrupt number Subroutine number (Note 2) 000 001 002 003 Minimum input signal width 50 s Interrupt response time 0.3 ms (from ( when i h input turns ON until program execution)
Note
1. Input numbers 00003 to 00006 can be used for any of the following functions: interrupt inputs, interrupt inputs (counter mode), or quick-response inputs. When not being used for any of these, they can be used as ordinary inputs. 2. Subroutine numbers 000 to 003 are the subroutine numbers for interrupt programs started up when interrupt inputs or count-up interrupts for interrupt inputs (counter mode) are generated. When not being used for this purpose, they can be used as ordinary inputs. 3. Input points 00005 and 00006 do not exist in CPM2C CPU Units with only 10 I/O points or in CPM2C-S CPU Units.
30
Section
2-1
The following table shows the relationships between interrupt inputs and the CPM2A/CPM2C PCs other functions.
Function Synchronized pulse control Interrupt inputs Interval timer interrupts High-speed counters Interrupt inputs (counter mode) Pulse outputs Quick-response inputs Input time constant Clock Interrupt inputs (counter mode) Can be used simultaneously. See note 1. Can be used simultaneously. Can be used simultaneously. See note 1. Can be used simultaneously. See note 1. See note 2. Can be used simultaneously.
Note
1. The same input number (from 00003 to 00006) cannot be used for more than one of the following functions: interrupt inputs, interrupt inputs (counter mode), or quick-response inputs. 2. When inputs 00003 to 00006 are set for use as interrupt inputs (counter mode), the input time constants for the relevant inputs are disabled. The input time constants remain in effect, however, for the values for refreshing the relevant input relay area.
INT(89): For masking and unmasking interrupt inputs. SBN(92) and RET(93): For creating interrupt subroutines.
31
Section
2-1
Interrupt input
Interrupt input 0
Interrupt is generated.
Interrupt input 1
(93)
Interrupt input 2
Interrupt input 3
PC Setup DM 6628
Note Input points 00005 and 00006 do not exist in CPM2C CPU Units with only 10 I/O points or in CPM2C-S CPU Units. Setting the Interrupt Input Number With interrupt inputs (interrupt input mode), the subroutine numbers executed for the input numbers are fixed.
Input number 00003 00004 00005 (See note.) 00006 (See note.) 0 1 2 3 Interrupt number Subroutine number 000 001 002 003
The same input number (from 00003 to 00006) cannot be used for more than one of the following functions: interrupt inputs, interrupt inputs (counter mode), or quick-response inputs. Wiring the Inputs With a CPM2A, wire to the input terminals as shown in the following illustration.
Input number 00003: Interrupt input 0 Input number 00004: Interrupt input 1 Input number 00005: Interrupt input 2 Input number 00006: Interrupt input 3
32
Section
2-1
With a CPM2C, wire to the input terminals as shown in the following illustration.
(See note 2.) Input terminals Input connector (Example for Fujitsu-compatible connector.) 00004 00003 00006 00005 00004 00003
Note
1. Refer to the operation manual for your CPU Unit for information on wiring. 2. Input terminal and pin numbers depend on the model. Refer to the CPM2C Operation Manual (W356) for details.
PC Setup
The following table shows the settings in the PC Setup area related to interrupt input usage.
Word DM 6628 Bits 00 to 03 04 to 07 08 to 11 12 to 15 Function Interrupt setting for 0: Normal input input 00003 1: Interrupt input Interrupt setting for (interrupt input mode or input 00004 counter mode) Interrupt setting for 2: Quick-response input input 00005* Interrupt setting for input 00006* Setting 1
Note *Input points 00005 and 00006 do not exist in CPM2C CPU Units with only 10 I/O points and in CPM2C-S CPU Units. The settings will go into effect when the mode is changed (from PROGRAM to MONITOR/RUN) or when the power supply is turned ON to the CPM2A/ CPM2C. Ladder Diagram Programming The following table shows the instruction operations related to interrupt input control.
Instruction (@)INT(89) Control Mask/unmask interrupt inputs Clear interrupt inputs Read current mask status Mask all interrupts Operation Prohibits or permits specified interrupts. Clears the cause of a prohibited interrupt input. Reads the permitted/prohibited status of an interrupt input. Prohibits all interrupts, including interrupt inputs, interval timer interrupts, high-speed counters, etc. Permits all interrupts, including interrupt inputs, interval timer interrupts, high-speed counters, etc.
33
Section
2-1
Masking or Unmasking Interrupt Inputs This function is used to mask or unmask input numbers 00003 to 00006 (interrupt inputs 0 to 3).
(@)INT(89) 000 000 C2
Interrupt control designation (000: Mask/unmask interrupt inputs) Fixed at 000. Control data word
Specifies/stores 0. Specifies input 00006 (interrupt input 3). Specifies input 00005 (interrupt input 2). Specifies input 00004 (interrupt input 1). Specifies input 00003 (interrupt input 0).
0: Clear mask (interrupt input permitted). 1: Set mask (interrupt input prohibited).
All interrupt inputs are prohibited at the beginning of operation (in either PROGRAM mode or in RUN/MONITOR mode). To use interrupt inputs, use INT(89) to permit them. Clearing Interrupt Inputs This function is used to clear input numbers 00003 to 00006 (interrupt inputs 0 to 3). Since interrupt inputs are recorded, masked interrupts will be serviced after the mask is removed unless they are cleared first. Use INT(89) to clear the cause of the interrupt inputs so that they will not be executed when interrupt inputs are permitted (i.e., when the mask is removed).
(@)INT(89) 001 000 C2
Interrupt control designation (001: Clear interrupt inputs) Fixed at 000. Control data word
Specifies/stores 0. Specifies input 00006 (interrupt input 3). Specifies input 00005 (interrupt input 2). Specifies input 00004 (interrupt input 1). Specifies input 00003 (interrupt input 0). 0: Retain cause of interrupt input. 1: Clear cause of interrupt input.
While interrupt inputs are masked, one cause is recorded for each interrupt input.
34
Section
2-1
Reading Current Mask Status This function is used to read the current mask status for input numbers 00003 to 00006 (interrupt inputs 0 to 3).
(@)INT(89) 002 000 C2
Interrupt control designation (002: Read current mask status) Fixed at 000. Control data word
Specifies/stores 0. Specifies input 00006 (interrupt input 3). Specifies input 00005 (interrupt input 2). Specifies input 00004 (interrupt input 1). Specifies input 00003 (interrupt input 0). 0: Mask is cleared (interrupt inputs permitted). 1: Mask is set (interrupt inputs prohibited).
Masking or Unmasking All Interrupts This function is used to mask or unmask all interrupt processing, including interrupt inputs (interrupt input mode and counter mode), interval timer interrupts, and high-speed counters. Masked inputs are recorded, but ignored. Masking All Interrupts
(@)INT(89) 100 000 000
Interrupt control designation (100: Mask all interrupts) Fixed at 000. Fixed at 000.
Interrupt control designation (200: Unmask all interrupts) Fixed at 000. Fixed at 000.
The masking or unmasking all interrupts cannot be executed within an interrupt subroutine. If causes for interrupts occur while all interrupts are masked, the causes will be recorded for each interrupt but the interrupt processing will not be executed. When unmask all interrupts is executed, the processing will then be carried out according to the interrupt mask status at that point in time. Interrupt masks cannot be cleared simply by executing unmask all interrupts. Executing unmask all interrupts merely restores the status that was in effect prior to the execution of mask all interrupts. Note INT(89) must be executed in order, with mask all interrupts followed by unmask all interrupts.
35
Section
2-1
In this example, an interrupt subroutine is executed by turning input 00003 from OFF to ON. The interrupt subroutine adds 1 to DM 0000. The following diagram shows input wiring in the CPM2A.
Input device
Input device
PC Setup
15 DM 6628 0 0 0 1 0
Input 00003 is used as an interrupt input. (Inputs 00004 to 00006 are used as ordinary inputs.)
36
Section
2-1
(89)
Normal program
Interrupt program
Subroutine
Scheduled-interrupt mode
Interrupt is executed once Interrupts are executed at when time has elapsed. regular intervals. 0.5 to 316,968 ms (Unit: 0.1 ms) 0.3 ms (from when time has elapsed until execution of interrupt program)
37
Section
2-1
The following table shows the relationships between interval timer interrupts and the CPM2A/CPM2Cs other functions.
Interval timer interrupts Synchronized pulse control Interrupt inputs Interval timer interrupts High-speed counters Interrupt inputs (counter mode) Pulse outputs Quick-response inputs Input time constant Clock Can be used simultaneously. Can be used simultaneously. --Can be used simultaneously. Can be used simultaneously. Can be used simultaneously. Can be used simultaneously. Can be used simultaneously. Can be used simultaneously.
STIM(69)
Interval timer
Interrupt is executed.
RET(93)
Select either the one-shot mode or the scheduled-interrupt mode. One-shot Mode
Normal program
38
Section
2-1
Normal program
Interrupt program Interval timer interrupt Interval timer operation Start timer
In the scheduled-interrupt mode, the timer is reset each time the interrupt program is called when the set time elapses, and then the interval timer operates again. Be careful with regard to the interrupt programs execution time and the interval timers set time. If the interrupt programs execution time exceeds the interval timers set time, scheduled interrupts cannot be executed properly. Ladder Diagram Programming The following table shows the instruction operations related to interrupt input control.
Instruction Control (@)STIM(69) Start one-shot timer ( ) ( ) Start scheduled-interrupt timer Read timer PV Stop timer (@)INT(89) Mask all interrupts Operation Starts interval timer in one-shot mode. Starts interval timer in scheduled-interrupt mode. Reads the timer PV. Stops timer operations. Prohibits all interrupts, including interrupt inputs, interval timer interrupts, high-speed counters, etc. Permits all interrupts, including interrupt inputs, interval timer interrupts, high-speed counters, etc.
Starting Timers This function sets the mode (one-shot or scheduled-interrupt) and the timers SV, and starts the interval timer. One-shot Mode
(@)STIM(69) 000 C2 C3
Control designation (000: Start one-shot timer) First word of timer SV Subroutine number (4 digits BCD: 0000 to 0049)
Scheduled-interrupt Mode
(@)STIM(69) 003 C2 C3
Control designation (003: Start scheduled-interrupt timer) First word of timer SV Subroutine number (4 digits BCD): 0000 to 0049
C2 C2+1
Decrementing counter initial value (4 digits Hex): 0000 to 9999 Decrementing time interval (4 digits BCD; unit: 0.1 ms): 0005 to 0320 (0.5 to 32 ms)
39
Section
2-1
The interval from when STIM(69) is executed until the set time elapses is calculated as follows: (Content of word C2) x (Content of words C2 + 1) x 0.1 ms (0.5 to 319,968 ms) When a constant is set for C2, that value will be taken as the decrementing counter initial value, and the decrementing time interval will become 10 (1 ms). (The SV is specified just as it is, in units of ms.) Reading Timer PVs This function reads interval timer PVs.
(@)STIM(69) 006 C2 C3
C2 C2+1 C3
Number of times decrementing timer is decremented (4 digits Hex) Decrementing time interval (4 digits BCD; unit: 0.1 ms) Time elapsed since last decrement (4 digits BCD; unit: 0.1 ms)
Masking or Unmasking All Interrupts For details on masking/unmasking all interrupts, refer to 2-1-2 Interrupt Inputs and 7-29 Interrupt Control Instructions.
40
Section
2-1
Explanation In this example, the timer is started when the execution condition (00005) turns from OFF to ON. When the time (approx. 1 s) has elapsed, the interrupt subroutine is executed one time. When the interrupt subroutine is executed, 1 is added to DM 0000. Elapsed time: 100 x 100 x 0.1 = 1,000 ms Programming
ON for 1 cycle at beginning of operation Clears Increment Area (DM 0000).
Decrement counter setting Count: 100 (0000 to 9999 BCD) Count interval setting Count interval setting: 10 ms (0005 to 0320 BCD) (69) (Execution condition) Starts interval timer in one-shot mode.
41
Section
2-1
Explanation In this example, the timer is started when the execution condition (00005) turns from OFF to ON. Then the interrupt subroutine is executed each time that the set time (approx. 1 s) elapses. Each time the interrupt subroutine is executed, 1 is added to DM 0000. Elapsed time: 100 x 100 x 0.1 = 1,000 ms Programming
Decrement counter setting Count: 100 (0000 to 9999 BCD) Count interval setting Count interval setting: 10 ms (0005 to 0320 BCD)
42
Section
2-1
A problem can occur in the situation shown below because processing of the ADD instruction could be interrupted between the 1st and 3rd operands and the MOV instruction then executed in the interrupt program.
Interrupt Program ADD (30) DM0000 #0001 DM0000 MOV (21) #0010 DM0000
Main Program
Flow of Processing The processing that would occur when the ADD instruction above is interrupted is illustrated below.
DM0000 Contents of DM 0000 read (1234) 1234
0010
Processing continued
1235
Processing is interrupted before the result of the add operation can be written to DM 0000 and the result is buffered. The interrupt program writes #0010 to DM 0000, but this is immediately overwritten by the result of the add (1235) as soon as execution of the interrupt program has been completed. In other words, the result of the interrupt program have been consequently nullified. Solution The INT instruction can be used to enable and disable interrupts before and after the add operation as shown below.
Main program INT (89) 100 Interrupts disabled. 000 000 ADD (30) DM0000 #0001 DM0000 INT (89) 200 000 000 Interrupts enabled.
43
Section
2-1
A problem can occur in the situation shown below because processing of the BSET instruction could be interrupted before all of the data for BSET has been written and the CMP instruction then executed in the interrupt program.
Main Program BEST (71) #1234 DM0000 DM0010 Interrupt Program CMP (20) DM0000 DM0010 25506 (=) A
Flow of Processing The processing that would occur when the BSET instruction above is interrupted is illustrated below.
DM0000 DM0001 #1234 transferred to DM 0000 #1234 transferred to DM 0001 Interrupt generated
Processing interrupted
DM0002 0502
DM0010 ABCD
A OFF
1234
003E 1234
DM 0000 read. Processing for CMP DM 0010 read. DM 0000 and DM 0010 compared Comparison result output
BSET instruction
Processing continued
0502 #1234 transferred to DM 0002 #1234 transferred to DM 0010 1234 1234 1234 1234 ABCD 12342 OFF
Processing is interrupted before #1234 can be written to DM 0010. Bit A in the interrupt program is thus turned OFF and will remain OFF when execution of the main program is resumed even though the contents of DM 0000 and DM 0010 will be the same as soon as the main program is resumed, i.e., the result of the comparison is not correct Solution The INT instruction can be used to enable and disable interrupts before and after the BSET instruction as shown below.
Main program INT (89) 100 000 000 BEST (71) #1234 DM0000 DM0010 INT (89) 200 000 000
Interrupts disabled.
Interrupts enabled.
44
Section
2-2
2-2
Interrupt inputs (counter mode) 4 points (2 points in CPM2C CPU Units with 10 I/O points and CPM2C-S CPU Units)
The CPM2A/CPM2C provides both a built-in high-speed counter and built-in interrupt inputs. High-speed Counter The built-in high-speed counter is a counter based on inputs to the CPU Units built-in points 00000 to 00002. The high-speed counter itself has one point, and it can provide either an incrementing/decrementing or just an incrementing count depending on the mode setting.
Input No. (See note.) 00000 00001 0000 00002 Response frequency 5 kHz 20 kHz Input mode (count value) Differential phase input mode (-8388608 to 8388607) Pulse + direction input mode(-8388608 to 8388607) Up/down pulse input mode (-8388608 to 8388607) Increment mode (0 to 16777215) Control method Target value comparison interrupts co pa so e up s Range comparison interrupts
Note Input points not used for counter inputs can be used as ordinary inputs. Interrupt Inputs (Counter Mode) Interrupt inputs (counter mode) are counters based on inputs to the CPU Units built-in points 00003 to 00006 (00003 to 00004 in CPM2C CPU Units with 10 I/O points and in CPM2C-S CPU Units). These counters have four points, and they can provide either an incrementing or decrementing count depending on the mode setting. Since this function utilizes interrupt inputs for counting, it is not possible to use the same inputs for other interrupt inputs.
Input No. (See note.) 00003 00004 00005 00006 Response frequency 2 kHz Input mode (count value) Incrementing counter g (0000 to FFFF) Decrementing counter (0000 to FFFF) Control method Count-up interrupts p p
Note
1. Input points not used for counter inputs can be used as ordinary inputs.
45
Section
2-2
2. Input points 00005 and 00006 do not exist in CPM2C CPU Units with 10 I/O points and CPM2C-S CPU Units. High-speed Counter Interrupts Interrupts by High-speed Counter (Count-check Interrupts) Target Value Comparison Interrupts The current count is compared to each target value in the order that they are registered in the table. When the count is the same as the current target value, an interrupt subroutine is executed. Up to 16 target values and interrupt subroutines can be registered in the table in either the incrementing or decrementing direction.
Current count
Interrupt processing can be executed when the current count matches a target value in either the incrementing or decrementing direction.
Range Comparison Interrupts A range comparison table contains up to eight ranges which are each defined by a lower limit and an upper limit, as well as their corresponding subroutine numbers. The corresponding subroutine is called and executed when the current count (the counter PV) falls within a given range.
Counter PV Upper limit 1 Lower limit 1
Upper limit 2
Lower limit 2
Interrupt processing can be executed when a range comparison condition is satisfied. Furthermore, when the counter PV is within a range between an upper limit and a lower limit, the corresponding bits (from 0 to 7) in AR 11 will turn ON.
Count-up Interrupts by Interrupt Inputs (Counter Mode) An interrupt subroutine is executed each time the condition is satisfied that the counter PV equals the counter SV (in incrementing mode) or 0 (in decrementing mode).
46
Section
2-2
Counter inputs
Reset input
Sensor
Rotary encoder
Item Input p number b Input method Response frequency Count value Counter PV storage destination (See note 2.) Interrupts Target value comparison Range comparison Counter reset method 00000 00001 00002
Input mode Differential phase Pulse + direction Up/down input Phase-A inputs Pulse inputs CW inputs Phase-B inputs Direction inputs CCW inputs Phase-Z inputs (Reset inputs) (See note 1.) Differential phase Phase inputs Phase inputs inputs (4X) 5 kHz 20 kHz 20 kHz 8388608 to 8388607 Words SR 248 (rightmost digit) and SR 249 (leftmost digit) Up to 16 target values and interrupt subroutine numbers can be registered in either the incrementing or decrementing direction. Up to eight ranges (with upper and lower limits) and subroutine numbers can be registered. Phase-Z signal + software reset: Counter is reset when IR 00002 turns ON while SR 25200 is ON. Software reset: Counter is reset when SR 25200 turns ON. Increment Pulse inputs See note 1. Phase inputs 20 kHz 0 to 16777215
Note
1. Input points not used for counter inputs can be used as ordinary inputs. 2. When not used for the counter PV storage destination, these words can be used as ordinary IR words. 3. SR 25200 is read once each cycle. Up to one cycle may be required for a reset to occur on the leading edge of phase Z. The following table shows the relationships between the high-speed counter and the CPM2A/CPM2Cs other functions.
47
Section
Interval timer interrupts Cannot be used simultaneously. Can be used simultaneously. Can be used simultaneously. --Can be used simultaneously. Can be used simultaneously. Can be used simultaneously. See note. Can be used simultaneously.
2-2
Note When inputs 00000 to 00002 are set for use as a high-speed counter, the input time constants for the relevant inputs are disabled. The input time constants remain in effect, however, for the values for refreshing the relevant input relay area.
Operation Example
Select the input mode and reset method. Input mode: Differential phase input, pulse + direction input, up/down input, or increment Reset method: Phase-Z + software reset, or software reset
No interrupts (Read high-speed counter PV, or read range comparison results) Select the interrupts to be used. Target value comparison interrupts Range comparison interrupts
High-speed counter setting PC Setup (DM 6642) Input mode: Differential phase input, pulse + direction input, up/down input, or increment Reset method: Phase-Z + software reset, or software reset
CTBL(63): Register comparison table, start comparison Create a ladder diagram program. INI(61): Change PV, start comparison PRV(62): Read high-speed counter PV, read high-speed counter comparison status, read range comparison results SBN(92) and RET(93): Create interrupt subroutine program (when count-check interrupts are used)
48
Section
2-2
Encoder inputs
Input mode
Differential phase input Pulse + direction input
SBN(92)
RET(93)
Each time PRV(62) HIGH-SPEED COUNTER PV READ instruction Read PV Read comparison status
Read range comparison results
49
Section
2-2
Pulse + Direction Input Mode In the pulse + direction input mode, pulse signals and direction signals are input, and the count is incremented or decremented according to the direction signal status. Maximum frequency: 20 kHz
ON Pulse inputs OFF Direction inputs ON OFF Count Nms Frequency = 1,000 N
Up/Down Pulse Input Mode In the up/down pulse input mode, CW signals (up pulses) and CCW signals (down pulses) are input, and the count is incremented or decremented accordingly. Maximum frequency: 20 kHz
ON CW inputs OFF ON CCW inputs OFF Count Incremented Nms Frequency = Decremented 1,000 N
Increment Mode In the increment mode, pulse signals are input and the count is incremented with each pulse. IR 00001 can be used as an ordinary input. Maximum frequency: 20 kHz
ON Pulse inputs OFF
When the differential phase input mode is used, the inputs must be 4X differential phase inputs. When an encoder is connected in this mode, the number of counts per revolution will be four times the encoder resolution. When selecting an encoder take into account the relationship with the number of counts that are possible.
50
Section
2-2
Count Values The range of numbers counted by the high-speed counter are in linear mode only. If the count is outside of the permissible range, an overflow or underflow will result. The PV will become 0FFFFFFF if an overflow occurs, or FFFFFFFF if an underflow occurs, and the comparison will be stopped.
Differential phase input mode Pulse + direction input mode Up/down pulse input mode Increment mode Underflow (FFFFFFFF) Overflow (0FFFFFFF)
Overflow (0FFFFFFF)
To restart the count following an overflow or underflow, reset the PV. (The PV is automatically reset whenever operation is started or stopped.) Reset Method Either of the following two methods can be selected for resetting the counter PV to 0. Phase-Z Signal (Reset Input) + Software Reset The PV is reset when a phase-Z signal (i.e., a reset input) turns ON while the High-speed Counter Reset Flag (25200) is ON.
1 scan
Phase Z
Reset
Reset
Not reset
Reset
Not reset
Software Reset The PV is reset when the High-speed Counter Reset Flag (25200) turns ON.
1 scan
Reset
Not reset
Not reset
Not reset
The High-speed Counter Reset Flag (25200) is refreshed with every scan, so it must remain ON for at least one cycle time to be certain it is read. Even when the PV is reset, the comparison table registration status, the comparison execution status, and the range comparison results are all retained just as they were before the PV reset. (If a comparison was underway prior to the PV reset, that comparison will be continued with no change following the reset.) Following the reset, the High-speed Counter Reset Flag (25200) must be turned OFF in order to be able to execute the next reset. To be certain that it is turned OFF, it must be remain OFF for at least one cycle time.
51
Section
2-2
For details regarding interrupt priorities, refer to Order of Priority for Interrupts under 2-1 Interrupts. If an interrupt is generated during execution of one of the high-speed counter control instructions, i.e., CTBL(63), INI(61), or PRV(62), these instructions will not be executed within the interrupt program. Target Value Comparison Interrupts Up to 16 combinations of comparison conditions (target value and count direction) and interrupt subroutine numbers can be registered in the comparison table. The specified subroutine is executed when the counter PV matches a target value in the comparison table.
Comparison table
Target value: 5,000 Count direction: Increment Subroutine number: 10
PV
Increment direction
Decrement direction
Subroutine 8 executed
Subroutine 10 executed
Subroutine 9 executed
The relationship between the target value comparison count check and the comparison table is different for the CPM1/CPM1A. Refer to the individual manuals for details. It is not possible to specify more than one comparison direction condition for the same target value in the comparison table. Either target value comparison or range comparison can be used for high-speed counter interrupts. Range Comparison Interrupts Up to eight combinations of comparison conditions (upper limit and lower limit) and interrupt subroutine numbers can be registered in the comparison table. The specified subroutine is executed once when the counter PV is greater than or equal to the lower limit and less than or equal to the upper limit in the comparison table.
Comparison table
Lower limit: 1,000 Upper limit: 4,000 Subroutine number: 10
PV
Time
Interrupt Interrupt Interrupt Interrupt
Subroutine 10 executed
52
Section
2-2
If two or more comparison conditions are satisfied simultaneously (in the same cycle), the interrupt for the condition closest to the beginning of the comparison table will be executed. Either target value comparison or range comparison can be used for high-speed counter interrupts. If an interrupt is generated during execution of one of the high-speed counter control instructions, i.e., CTBL(63), INI(61), or PRV(62), these instructions will not be executed within the interrupt program. If an interrupt is generated while an instruction controlling the high-speed counter is being executed in the normal program area, the CTBL(63), INI(61), and PRV(62), instructions will not be executed within the interrupt program. This situation can be avoided by means of the following programming.
Method 1 Prohibit interrupts in the normal program area while executing the instruction. Method 2 In the normal program area, re-execute the instruction that could not be executed. Normal program area Interrupt program area
Interrupt processing subroutines are defined by SBN(92) and RET(93), just like ordinary subroutines. An SBS UNDEFD error will be generated during the program check while an interrupt processing subroutine is being defined, but execution will be normal.
53
Section
2-2
Wire the inputs as shown in the following illustrations, according to the input mode and the reset method. CPM2A Inputs
Differential Phase Input Mode 00000: Phase-A input 00001: Phase-B input 00002: Phase-Z input
Up/Down Pulse Input Mode 00000: CW input 00001: CCW input 00002: Reset input
Pulse + Direction Input Mode 00000: Pulse input 00001: Direction input 00002: Reset input
CPM2C Inputs Note The following examples are for Fujitsu-compatible connectors. Input bit addresses and connector pin numbers depend on the models. Refer to the CPM2C Operation Manual (W356) or the CPM2C-S Operation Manual (W377) for details.
Differential Phase Input Mode Input terminals Input connector (See above note.)
54
Section
2-2
Pulse + Direction Input Mode Input terminals Input connector (See above note.)
When phase-Z and reset inputs are not used, 00002 can be used as an ordinary input.
55
Section
2-2
Input mode
DM 6642, bits 00 to 03
DM 6642, bits 04 to 07
Word DM 6642
Bits 00 to 03
Function High-speed counter input mode setting 0: Differential phase input 5 kHz 1: Pulse + direction input 20 kHz 2: Up/down input 20 kHz 4: Increment 20 kHz High-speed counter reset method setting 0: Phase-Z signal + software reset 1: Software reset High-speed counter usage setting 00: Do not use. 01: Use as high-speed counter 02: Use as pulse synchronization control (10 Hz to 500 Hz) 03: Use as pulse synchronization control (20 Hz to 1 kHz) 04: Use as pulse synchronization control (300 Hz to 20 kHz)
Setting 0, 1, 2, or 4
04 to 07
0 or 1
08 to 15
01
The new settings for the System Setup go into effect when operation begins (when PROGRAM mode is changed to MONITOR or RUN mode), or when the CPM2A/CPM2Cs power is turned ON.
56
Section
2-2
The following table shows the instructions related to high-speed counter control.
Instruction (@)CTBL(63) Control Register target value comparison table Register range comparison table Register target value comparison table and start comparison Register range comparison table and start comparison (@)INI(61) Start comparison Operation Registers target value comparison table. Registers range comparison table. Registers target value comparison table and starts comparison. Registers range comparison table and starts comparison.
( ) (@)PRV(62) ( )
(@)INT(89)
Starts comparison with registered comparison table. Stop comparison Stops comparison. Change PV Changes the high-speed counter PV. Read PV Reads the high-speed counter PV. Read status Reads the high-speed counter status. Read range comparison Reads range comparison result. result Mask all interrupts Prohibits all interrupts, including interrupt inputs, interval timer interrupts, high-speed counters, etc. Unmask all interrupts Permits all interrupts, including interrupt inputs, interval timer interrupts, high-speed counters, etc.
The following table shows the data areas related to high-speed counter control.
Word 248 249 252 Bits 00 to 15 00 to 15 00 Name High-speed counter PV g p High-speed counter reset Contents Reads high-speed counter g p PV. PV When this bit turns ON, a software reset is triggered for the high-speed counter. ON: Condition satisfied OFF: Condition not satisfied ON: Comparison in progress OFF: Comparison stopped ON: Overflow/underflow OFF: Normal
AR11
00 to 07 08 09
High-speed counter range comparison results High-speed counter comparison High-speed counter PV overflow/underflow
Register Target Value Comparison Table Register Target Value Comparison Table and Start Comparison These functions register a comparison table to the CPM2A/CPM2C for the purpose of count checking in target value comparison. It is also possible to start the comparison along with the registration. Register Target Value Comparison Table
Port specifier (000: High-speed counter) Mode designation (002: Register target value comparison table only) Beginning word of comparison table
57
Section
2-2
Port specifier (000: High-speed counter) Mode designation (000: Register target value comparison table and start comparison) Beginning word of comparison table
Number of comparisons Target value 1 (rightmost) Target value 1 (leftmost) Subroutine number Target value 2 (rightmost) Target value 2 (leftmost) Subroutine number
Number of comparisons 0001 to 0016 BCD Target value (rightmost, leftmost) Comparison 1 setting Register the counter value to be compared. The leftmost digit shows the sign (+/). Differential phase input mode Pulse + direction input mode Comparison 2 setting Up/down pulse input mode When incrementing: F8388607 to 08388607 When decrementing: F8388608 to 08388606 Increment mode 00000001 to 16777215 The range that can be specified depends on the mode when target comparison interrupts are specified. Subroutine number Register the direction of comparison and the subroutine number to be executed when there is a match. The leftmost digit shows the direction (increment/decrement). Increment direction: 0000 to 0049 Decrement direction: F000 to F049
It is not possible to specify more than one comparison direction condition for the same target value in the comparison table. Once a comparison table has been registered, it will be saved in the CPM2A/ CPM2C as long as no other comparison table is registered and the mode is not changed to PROGRAM mode (and as long as the power is not turned OFF). Register Range Comparison Table Register Range Comparison Table and Start Comparison These functions register a comparison table to the CPM2A/CPM2C for the purpose of count checking in range comparison. It is also possible to start the comparison along with the registration. Register Range Comparison Table
(@)CTBL(63) 000 003 S
Port specifier (000: High-speed counter) Mode designation (003: Register range comparison table only) Beginning word of comparison table
Port specifier (000: High-speed counter) Mode designation (001: Register range comparison table and start comparison) Beginning word of comparison table
58
Section
2-2
Eight range comparison conditions consisting of upper and lower limits and subroutine numbers must be set. Range comparison condition 1 Upper and lower limits (rightmost, leftmost) Register the upper and lower limits. The leftmost digit shows the sign (+/). Differential phase input mode Pulse + direction input mode Up/down pulse input mode F8388608 to 08388607 Increment mode 00000000 to 16777215
Lower limit 8 (rightmost) Lower limit 8 (leftmost) Upper limit 8 (rightmost) Upper limit 8 (leftmost) Subroutine number
Subroutine number Register the subroutine number to be executed when the range comparison condition is satisfied. Range comparison condition 8 0000 to 0049 If the set values do not reach 8, set FFFF.
If two or more comparison conditions are satisfied simultaneously (in the same cycle), the interrupt for the condition closest to the beginning of the comparison table will be executed. Once a comparison table has been registered, it will be saved in the CPM2A/ CPM2C as long as no other comparison table is registered and the mode is not changed to PROGRAM mode (and as long as the power is not turned OFF). Start/Stop Comparison The comparison can be started or stopped according to the table that has already been registered to the CPM2A/CPM2C by CTBL(63). Start Comparison
(@)INI(61) 000 000 000
Port specifier (000: High-speed counter) Control designation (000: Start comparison) Fixed: 000
Stop Comparison
(@)INI(61) 000 001 000
Port specifier (000: High-speed counter) Control designation (001: Stop comparison) Fixed: 000
59
Section
2-2
Port specifier (000: High-speed counter) Control designation (002: Change PV) Beginning word of PV data to change PV data to change (Rightmost and leftmost) Register the PV data to be changed. The leftmost digit shows the sign (+/). Differential phase input mode Pulse + direction input mode Up/down pulse input mode F8388608 to 08388607 Increment mode 00000000 to 16777215
C2 C2+1
No interrupt will occur during a target value comparison even if the target value registered in the comparison table is changed by INI(61). Read PV This function reads the high-speed counter PV. Using an Instruction
Port specifier (000: High-speed counter) Control designation (000: Read PV) Beginning word for storing PV
D D+1
PV (Rightmost and leftmost) The read PV will be stored here. The leftmost digit shows the sign (+/). Differential phase input mode Pulse + direction input mode Up/down pulse input mode F8388608 to 08388607 Increment mode 00000000 to 16777215
Using Data Areas The high-speed counter PV is stored in words 248 and 249 as shown below.
SR 248 SR 249 PV (Rightmost word) PV (Leftmost word)
Words 248 and 249 are refreshed with every scan, so there may be a discrepancy from the exact PV at any given time. When the high-speed counter is not used, words 248 and 249 can be used as work words. When the PV is read by executing PRV(62), words 248 and 249 are refreshed with the same timing.
60
Section
2-2
Read Status This function reads the high-speed counter status, such as whether a comparison operation is in progress or whether an overflow or underflow has occurred. Using an Instruction
(@)PRV(62) 000 001 D
Port specifier (000: High-speed counter) Control designation (001: Read status) Word for storing status
Using Data Areas The status is stored in AR 1108 and AR 1109 as shown below.
AR 1108 and AR 1109 are refreshed with every scan, so there may be a discrepancy from the exact status at any given time. When the status is read by executing PRV(62), AR 1108 and AR 1109 are refreshed with the same timing. Read Range Comparison Result This function reads the result of a range comparison showing whether or not the PV is within a range. Using an Instruction
(@)PRV(62) 000 002 D
Port specifier (000: High-speed counter) Control designation (002: Read range comparison result) Beginning word for storing range comparison result
Match with 1st condition (0: No match; 1: Match) Match with 2nd condition (0: No match; 1: Match) Match with 3rd condition (0: No match; 1: Match) Match with 4th condition (0: No match; 1: Match) Match with 5th condition (0: No match; 1: Match) Match with 6th condition (0: No match; 1: Match) Match with 7th condition (0: No match; 1: Match) Match with 8th condition (0: No match; 1: Match)
Using Data Areas The range comparison result is stored in AR 1100 through AR 1107, as shown below.
Match with 1st condition (0: No match; 1: Match) Match with 2nd condition (0: No match; 1: Match) Match with 3rd condition (0: No match; 1: Match) Match with 4th condition (0: No match; 1: Match) Match with 5th condition (0: No match; 1: Match) Match with 6th condition (0: No match; 1: Match) Match with 7th condition (0: No match; 1: Match) Match with 8th condition (0: No match; 1: Match)
61
Section
2-2
AR 1100 through AR 1107 are refreshed with every scan, so there may be a discrepancy from the exact PV range comparison result at any given time. When the range comparison result is read by executing PRV(62), AR 1100 through AR 1107 are refreshed with the same timing. Mask/Unmask All Interrupts For details regarding masking and unmasking all interrupts, refer to 2-1-2 Interrupt Inputs.
Application Examples
Target Value Comparison Explanation In this example, specified interrupt subroutines are executed by matching the high-speed counters PV with five values set as a target value comparison table. With each interrupt, the data in DM 0000 to DM 0004 is incremented by one. Wiring (CPM2A)
Orange
Brown
62
Section
2-2
Note The following examples are for Fujitsu-compatible connectors. Input bit addresses and connector pin numbers depend on the models. Refer to the CPM2C Operation Manual (W356) or the CPM2C-S Operation Manual (W377) for details.
Input terminals Blue Rotary encoder Brown
PC Setup
15 DM 6642 0 1 0 0 0: Differential phase input 0: Reset by phase-Z signal + software reset 01: Use as high-speed counter 0
63
Section
2-2
(71)
High-speed counter Register target value comparison table and begin comparison Beginning word of comparison table
(92)
Number of comparisons: 5 Target value: 00010000
Always ON
(38)
Comparison 2
(93) (92)
Always ON
(38)
Comparison 4
(93)
(92)
Always ON
(38)
Comparison 5
(93)
(92)
Always ON
(38)
Comparison 1
(93)
(92)
Always ON
(38)
Comparison 3
(93)
(01)
64
Section
2-2
Explanation In this example, specified interrupt subroutines are executed by matching the high-speed counters PV with five range set as a range comparison table. With each interrupt, the data in DM 0000 to DM 0004 is incremented by one. Wiring (CPM2A)
Orange
Brown
65
Section
2-2
Note The following examples are for Fujitsu-compatible connectors. Input bit addresses and connector pin numbers depend on the models. Refer to the CPM2C Operation Manual (W356) or the CPM2C-S Operation Manual (W377) for details.
Input terminals Blue Rotary encoder Brown
PC Setup
15 DM 6642 0 1 0 0 0: Differential phase input 0: Reset by phase-Z signal + software reset 01: Use as high-speed counter 0
66
Section
2-2
(71)
High-speed counter Register range comparison table and begin comparison Beginning word of comparison table
(92)
Lower limit: 9,000 Upper limit: 10,000 Subroutine 040 Lower limit: 7,000 Upper limit: 8,000
Comparison 1
Always ON
(38)
Comparison 1
(93)
Comparison 2
(92)
Always ON
(38)
Comparison 2
Comparison 3
Upper limit: 3,000
(93)
(92)
Always ON
(38)
Comparison 4
Upper limit: 7,000
Comparison 3
(93)
Comparison 5
(92)
Subroutine 043
Always ON
(38)
Comparison 4
(93)
Comparison 6
Not used.
(92)
Always ON
(38)
Comparison 7 Comparison 5
Not used.
(93)
Comparison 8
Not used.
(01)
67
Section
2-2
Counter input
Counter input
Normal program
Interrupt program
Subroutine
Count
Subroutine Response number (Note 3) frequency 2 kHz 000 001 002 003
Note
1. Input number 00005 and 00006 cannot be used in CPM2C CPU Units with 10 I/O points and CPM2C-S CPU Units. 2. Input numbers 00003 to 00006 can be used for any of the following functions: interrupt inputs, interrupt inputs (counter mode), or quick-response inputs. When not being used for any of these, they can be used as ordinary inputs. 3. Subroutine numbers 000 to 003 are the subroutine numbers for interrupt programs started up when interrupt inputs or count-up interrupts for interrupt inputs (counter mode) are generated. When not being used for this purpose, they can be used as ordinary inputs.
68
Section
2-2
Although IORF(97) can be used in interrupt subroutines, you must be careful of the interval between IORF(97) executions. If IORF(97) is executed too frequently, a fatal system error may occur (FALS 9F), stopping operation. The interval between executions of IORF(97) should be at least 1.3 ms + total execution time of the interrupt subroutine. The following table shows the relationships between interrupt inputs (counter mode) and the CPM2A/CPM2Cs other functions.
Function Synchronized pulse control Interrupt inputs Interval timer interrupts High-speed counters Interrupt inputs (counter mode) Pulse outputs Quick-response inputs Input time constant Clock Interrupt inputs (counter mode) Can be used simultaneously. See note 1. Can be used simultaneously. Can be used simultaneously. See note 1. Can be used simultaneously. See note 1. See note 2. Can be used simultaneously.
Note
1. The same input number (from 00003 to 00006) cannot be used for more than one of the following functions: interrupt inputs, interrupt inputs (counter mode), or quick-response inputs. 2. When inputs 00003 to 00006 are set for use as interrupt inputs (counter mode), the input time constants for the relevant inputs are disabled. The input time constants remain in effect, however, for the values for refreshing the relevant input relay area.
Input numbers: 00003 to 00006 (00003 or 00004 for CPM2C CPU Units with 10 I/O points and CPM2C-S CPU Units.)
INI(61): Change counter PV INT(89): Refresh counter SV* PRV(62): Read counter PV SBN(92) and RET(93): For creating interrupt subroutines.* *Used only for count-up interrupts.
69
Section
2-2
Interrupt input
Counter (2 kHz) 0
Interrupt generated
SBN(92)
Counter (2 kHz) 1
RET(93)
Counter (2 kHz) 3
Every scan Counter SV Counter 0 Counter 1 Counter 2 Counter 3 SR 244 SR 245 SR 246 SR 247
Immediately PRV(62)
HIGH-SPEED COUNTER PV READ instruction
Read counter PV
With interrupt inputs in counter mode, the subroutine to be executed is determined by the interrupt corresponding to the input number.
Input number 00003 00004 00005* 00006* 0 1 2 3 Interrupt number Subroutine number 000 001 002 003
Note *Input numbers 00005 and 00006 cannot be used for CPM2C CPU Units with 10 I/O points and for CPM2C-S CPU Units. The same input number (from 00003 to 00006) cannot be used for more than one of the following functions: interrupt inputs, interrupt inputs (counter mode), or quick-response inputs.
70
Section
2-2
Either an incrementing or decrementing count can be used with interrupt inputs in counter mode. Incrementing Counter Mode As the set value (SV) is refreshed, the count is incremented from 0, and the interrupt subroutine is executed when the present value (PV) matches the SV.
PV The subroutine is executed when the count is up, and the PV is reset to 0. SV Incrementing Incrementing
Time
Interrupt Interrupt
Subroutine executed.
Subroutine executed.
Decrementing Counter Mode As the set value (SV) is refreshed, the count is is decremented toward 0, and the interrupt subroutine is executed when the present value (PV) reaches 0.
PV The subroutine is executed when the count is up, and the PV is reset to the SV. SV
Decrementing
Decrementing Time
Interrupt Interrupt
Subroutine executed.
Subroutine executed.
With the CPM2A, wire the input terminals as shown in the following illustration.
Input 00003: Input interrupt (counter mode) 0 Input 00004: Input interrupt (counter mode) 1 Input 00005: Input interrupt (counter mode) 2 Input 00006: Input interrupt (counter mode) 3
With the CPM2C, wire the input terminals as shown in the following illustration.
71
Section
2-2
Note The following examples are for Fujitsu-compatible connectors. Input bit addresses and connector pin numbers depend on the models. Refer to the CPM2C Operation Manual (W356) or the CPM2C-S Operation Manual (W377) for details.
Input terminals
00004: Input interrupt (counter mode) 1 00003: Input interrupt (counter mode) 0
00006: Input interrupt (counter mode) 3 00005: Input interrupt (counter mode) 2 00004: Input interrupt (counter mode) 1 00003: Input interrupt (counter mode) 0
Note Inputs 00006 and 00005 cannot be used with CPU Units that have only 10 I/O points.
PC Setup
The following table shows the settings in the PC Setup area related to interrupt input usage.
Word DM 6628 Bits 00 to 03 04 to 07 08 to 11 12 to 15 Interrupt setting for input 00003 Interrupt setting for input 00004 Interrupt setting for input 00005* Interrupt setting for input 00006* Function 0: Normal input 1: Interrupt input (interrupt input mode or counter mode) 2: Quick-response input Setting 1
Note *Input number 00005 and 00006 cannot be used in CPM2C CPU Units with 10 I/O points and in CPM2C-S CPU Units. The setting will go into effect when the mode is changed (from PROGRAM to MONITOR/RUN) or when the power supply is turned ON to the CPM2A/ CPM2C.
72
Section
2-2
The following table shows the instruction operations related to interrupt input (counter mode) control.
Instruction (@)INT(89) Control Refresh incrementing counter SV Refresh decrementing counter SV Mask all interrupts Operation Refreshes the counters SV and starts the incrementing count. Refreshes the counters SV and starts the decrementing count. Prohibits all interrupts, including interrupt inputs, interval timer interrupts, high-speed counters, etc. Permits all interrupts, including interrupt inputs, interval timer interrupts, high-speed counters, etc. Changes the counters PV. Reads the counters PV.
(@)INI(61)
Change PV
(@)PRV(62) Read PV
The functions related to input interrupts (counter mode) are executed according to the data areas shown in the following table.
Word 240 241 242 243 244 245 246 247 Bits 00 to 15 00 to 15 00 to 15 00 to 15 00 to 15 00 to 15 00 to 15 00 to 15 Name SV area for input interrupt (counter mode) 0 SV area for input interrupt (counter mode) 1 SV area for input interrupt (counter mode) 2 SV area for input interrupt (counter mode) 3 PV area for input interrupt (counter mode) 0 PV area for input interrupt (counter mode) 1 PV area for input interrupt (counter mode) 2 PV area for input interrupt (counter mode) 3 Contents Stores the counters set value (SV). (SV)
Refresh Incrementing Counter SV / Refresh Decrementing Counter SV These functions store the counters set values in data areas and refresh them by means of INT(89). In this way, they start the count operation for interrupt inputs (counter mode) and they permit interrupts. Storing Set Values in Data Areas The counters set values are stored in words 240, 241, 242, and 243.
SR 240 SR 241 SR 242 SR 243 SV for interrupt input (count mode) 0: 0000 to FFFF SV for interrupt input (count mode) 1: 0000 to FFFF SV for interrupt input (count mode) 2: 0000 to FFFF SV for interrupt input (count mode) 3: 0000 to FFFF
73
Section
2-2
Interrupt control designation (004: Refresh incrementing counter SV) Fixed: 000 Control data word
Decrementing Counter
(@)INT(89) 003 000 C2
Interrupt control designation (003: Refresh decrementing counter SV) Fixed: 000 Control data word
Specify and store 0 Specify interrupt input (counter mode) 3 Specify interrupt input (counter mode) 2 Specify interrupt input (counter mode) 1 Specify interrupt input (counter mode) 0 0: Refresh SV 1: Do not refresh SV
Note When INT(89) is executed to mask interrupts during counter operation (interrupt control designation 000), counter operation will be stopped and the counter PV will be reset. To use the counter again, start the counter operation again as described above. Change PV This function refreshes the counters present value (PV).
(@)INT(89) P 002 C2
Port specifier (100. 102, 102, 103: Interrupt inputs (counter mode) 0 to 3) Control designation (002: Change PV) Change PV data word C2 Change PV data Registers the PV data to be changed. 0000 to FFFF
Read PV This function reads the counters present value (PV). Using an Instruction
(@)PRV(62) P 000 D
Port specifier (100. 102, 102, 103: Interrupt inputs (counter mode) 0 to 3) Control designation (000: Read PV) Word for storing PV D Read PV data The PV that is read is stored here. 0000 to FFFF
74
Section
2-2
Using Data Areas The high-speed counters present value (PV) is stored in words SR 244 to SR 247 as shown below.
SR 244 SR 245 SR 246 SR 247 PV PV PV PV Interrupt input (counter mode) 0 Interrupt input (counter mode) 1 Interrupt input (counter mode) 2 Interrupt input (counter mode) 3
Words SR 244 to SR 247 are refreshed with every scan, so there may be a discrepancy from the exact PV at any given time. Words SR 244 to SR 247 cannot be used as work word even when the interrupt inputs (counter mode) are not used. When the PV is read by executing PRV(62), words 244 to 247 are refreshed with the same timing. Mask/Unmask All Interrupts For details regarding masking and unmasking all interrupts, refer to 2-1-2 Interrupt Inputs.
Application Example
Explanation In this example, the PV is decremented every time input 00003 is turned ON, and DM 0000 is incremented by 1 by an interrupt subroutine every 100 times (64 Hex) that input 00003 is turned ON. The following diagram shows input wiring in the CPM2A.
Wiring
Input device
75
Section
2-2
Note The following examples are for Fujitsu-compatible connectors. Input bit addresses and connector pin numbers depend on the models. Refer to the CPM2C Operation Manual (W356) or the CPM2C-S Operation Manual (W377) for details.
Input terminals
Input device
PC Setup
15 DM 6628 0 0 0 1 0
Specifies bit 00003 as an interrupt input (counter mode). Inputs 00004 to 00006 are used as ordinary inputs.
Programming
ON for 1 cycle at beginning of operation Clears Increment Area (DM 0000).
Decrement counter setting Counter SV: 64 Hex (100 times) Stores SV in word 240. (89) Starts counter with bit 00003 as interrupt input (counter mode). Refreshes counter SV (decrement counter). Always 000. Specifies bit 00003. (Others are masked.)
76
Section
2-3
2-3
77
Section
2-3
The following methods can be used to circumvent this limitation: Method 1 All interrupt processing can be masked while the instruction is being executed.
@INT(89) 100 000 000 INI(61) 000 000 000 @INT(89) 200 000 000
Method 2 Execute the instruction again in the main program. 1, 2, 3... 1. This is the program section from the main program:
@PRV(62) 000 002 DM 0000 LR 0000 CTBL(63) 000 000 DM 0000 RSET LR 0000
LR 0000
Note
1. Define interrupt routines at the end of the main program with SBN(92) and RET(93) instructions, just like regular subroutines. 2. When defining an interrupt routine, a SBS UNDEFD error will occur during the program check operation, but the program will be executed normally.
78
Section
2-3
NC 24VDC
CPM1A PCs
10-pt CPU Units (CPM1A-10CDR-j) 20-, 30-, and 40-pt CPU Units (CPM1A-20CDR-j, CPM1A-30CDR-j, and CPM1A-40CDR-j)
CPU Unit CPM1-10CDR-j j CPM1A-10CDj-j CPM1A 10CDj j CPM1-20CDR-j CPM1A-20CDj-j CPM1A 20CDj j
Interrupt p number b 00 01 00 01 02 03
Response time Interrupt mode Counter mode 0.3 ms max. 1 kHz (Time until the interrupt program is ) executed.)
00004 CPM1-30CDR-j(-V1) CPM1 30CDR j( V1) 00003 CPM1A 30CDj j CPM1A-30CDj-j 00004 CPM1A-40CDj-j
Note If input interrupts are not used, use inputs 00003 to 00006 as regular inputs.
79
Section
2-3
Inputs 00003 to 00006 must be set as interrupt inputs in DM 6628 if they are to be used for input interrupts in the CPM1/CPM1A. Set the corresponding digit to 1 if the input is to be used as an interrupt input (input interrupt or counter mode); set it to 0 if it is to be used as a regular input.
Word DM 6628 Setting 0: Regular input (default setting) 1: Interrupt input 2: Quick-response input Quick response
Bit 15 DM 6628 0
Setting for input 00006: Set to 1 Setting for input 00005: Set to 1 Setting for input 00004: Set to 1 Setting for input 00003: Set to 1
Interrupt Subroutines
Interrupts from inputs 00003 to 00006 are allocated interrupt numbers 00 to 03 and call subroutines 000 to 003. If the input interrupts arent being used, subroutines 000 to 003 can be used in regular subroutines.
Input number 00003 00004 00005 00006 Interrupt number 0 1 2 3 Subroutine number 000 001 002 003
Input Refreshing
If input refreshing is not used, input signal status within the interrupt routine will not be reliable. Depending on the input time constant, the input signals might not go ON even if input refreshing is used. This includes the status of the interrupt input bit that activated the interrupt. For example, IR 00000 would not be ON in interrupt routine for input interrupt 0 unless it was refreshed. In this case, use the Always ON Flag, SR 25313 in the interrupt routine instead of IR 00000. When an input interrupt signal is received, the main program is interrupted and the interrupt program is executed immediately, regardless of the point in the cycle in which the interrupt is received. The signal must be ON for 200 s or more to be detected.
Main program Main program
Interrupt program
Input interrupt
Use the following instructions to program input interrupts using the Input Interrupt Mode. Masking/Unmasking of Interrupts With the INT(89) instruction, set or clear input interrupt masks as required.
(@)INT(89) 000 000 D
Make the settings with word D bits 0 to 3, which correspond to input interrupts 0 to 3. 0: Mask cleared. (Input interrupt enabled.) 1: Mask set. (Input interrupt disabled.)
80
Section
2-3
All of the input interrupts are masked when PC operation is started. If input interrupt mode is being used, be sure to enable the inputs by executing INT(89) as shown above. Clearing Masked Interrupts If the bit corresponding to an input interrupt turns ON while masked, that input interrupt will be saved in memory and will be executed as soon as the mask is cleared. In order for that input interrupt not to be executed when the mask is cleared, the interrupt must be cleared from memory. Only one interrupt signal will be saved in memory for each interrupt number. With the INT(89) instruction, clear the input interrupt from memory.
(@)INT(89) 001 000 D
If D bits 0 to 3, which correspond to input interrupts 0 to 3, are set to 1, then the input interrupts will be cleared from memory. 0: Input interrupt retained. 1: Input interrupt cleared.
Reading Mask Status With the INT(89) instruction, read the input interrupt mask status.
(@)INT(89) 002 000 D
The status of the rightmost digit of the data stored in word D (bits 0 to 3) show the mask status. 0: Mask cleared. (Input interrupt enabled.) 1: Mask set. (Input interrupt disabled.)
Program Example When input 00003 (interrupt no. 0) goes ON, operation moves immediately to the interrupt program with subroutine number 000. Inputs for DM 6628 have been set to 0001.
25315 First Cycle Flag ON for 1 cycle @INT(89) 000 000 #000E
Mask/unmask input interrupts. Unmasks 00003 (interrupt input 0), masks others.
SBN(92)
000
Interrupt program
RET(93)
Counter Mode
External signal inputs are counted at high speed and an interrupt is generated when the count reaches the set value. When an interrupt is generated, the main program is interrupted and the interrupt program is executed. Signals up to 1 kHz can be counted.
Main program Main program
Interrupt program
Input interrupt
Set value
81
Section
2-3
Use the following steps to program input interrupts using the Counter Mode. 1, 2, 3... 1. Write the set values for counter operation to the SR words shown in the following table. The set values are written between 0000 and FFFF (0 to 65,535). A value of 0000 will disable the count operation until a new value is set and step 2, below, is repeated.
Interrupt Input interrupt 0 Input interrupt 1 Input interrupt 2 Input interrupt 3 SR 240 SR 241 SR 242 SR 243 Word
The SR words used in the Counter Mode (SR 240 to SR 243) contain hexadecimal data, not BCD. If the Counter Mode is not used, these words can be used as work bits. Note These SR words are cleared at the beginning of operation, and must be written from the program. 2. With the INT(89) instruction, refresh the Counter Mode set value and enable interrupts.
(@)INT(89) 003 000 D
If D bits 0 to 3, which correspond to input interrupts 0 to 3, are set to 0, then the set value will be refreshed and interrupts will be permitted. 0: Counter mode set value refreshed and mask cleared. 1: Not refreshed.
Be sure to set the corresponding bit to 1 if an input interrupt isnt being controlled. The input interrupt for which the set value is refreshed will be enabled in Counter Mode. When the counter reaches the set value, an interrupt will occur, the counter will be reset, and counting/interrupts will continue until the counter is stopped. Note 1. If the INT(89) instruction is used during counting, the present value (PV) will return to the set value (SV). You must, therefore, use the differentiated form of the instruction or an interrupt may never occur. 2. The set value will be set when the INT(89) instruction is executed. If interrupts are already in operation, then the set value will not be changed just by changing the content of SR 240 to SR 243, i.e., if the contents are changed, the set value must be refreshed by executing the INT(89) instruction again. Interrupts can be masked using the same process used with the Input Interrupt Mode, but if the masked interrupts are cleared using the same process, the interrupts will operate in Input Interrupt Mode, not Counter Mode. Interrupt signals received for masked interrupts can also be cleared using the same process as for the Input Interrupt Mode. Counter PV in Counter Mode When input interrupts are used in Counter Mode, the counter PV will be stored in the SR word corresponding to input interrupts 0 to 3. Values are 0000 to FFFE (0 to 65,534) and will equal the counter PV minus one.
Interrupt Input interrupt 0 Input interrupt 1 Input interrupt 2 Input interrupt 3 SR 244 SR 245 SR 246 SR 247 Word
Example: The present value for an interrupt whose set value is 000A will be recorded as 0009 immediately after INT(89) is executed. Note Even if input interrupts are not used in Counter Mode, these SR bits cannot be used as work bits.
82
Section
2-3
Program Example When input 00003 (interrupt no. 0) goes ON 10 times, operation moves immediately to the interrupt program with subroutine number 000. The following table shows where the counters set values and present values 1 are stored. Inputs for DM 6628 have been set to 0001.
Interrupt Input 00003 (input interrupt 0) Input 00004 (input interrupt 1) Input 00005 (input interrupt 2) Input 00006 (input interrupt 3) Word containing SV SR 240 SR 241 SR 242 SR 243 Word containing PV1 SR 244 SR 245 SR 246 SR 247
Sets the SV to 10. (0000 to FFFF) Word containing the SV (SR 240)
SBN(92)
000
Interrupt program
RET(93)
If an interrupt is generated while interrupts are masked, interrupt processing will not be executed but the interrupt will be recorded for the input, interval timer, and high-speed counter interrupts. The interrupts will then be serviced as soon as interrupts are unmasked.
83
Section
2-3
C1: Interval timer, one-shot mode (000) C2: Timer set value (first word address) C3: Subroutine no. (4 digits BCD): 0000 to 0049
1, 2, 3...
1. When C2 is entered as a word address: C2: Decrementing counter set value (4 digits BCD): 0000 to 9999 C2 + 1: Decrementing time interval (4 digits BCD; unit: 0.1 ms): 0005 to 0320 (0.5 ms to 32 ms) Each time that the interval specified in word C2 + 1 elapses, the decrementing counter will decrement the present value by one. When the PV reaches 0, the designated subroutine will be called just once and the timer will stop. The time from when the STIM(69) instruction is executed until time elapses is calculated as follows: (Content of C2) (Content of C2 + 1) 0.1 ms = (0.5 to 319,968 ms) 2. When C2 is entered as a constant: The set value of the decrementing counter will equal the specified constant (in ms) and the decrementing time interval will be 10 (1 ms). Starting Up in Scheduled Interrupt Mode Use the STIM(69) instruction to start the interval timer in the scheduled interrupt mode.
(@)STIM(69) C1 C2 C3
C1: Interval timer, scheduled interrupt mode (003) C2: Timer set value (leading word no.) C3: Subroutine no. (4 digits BCD): 0000 to 0049
1, 2, 3...
1. When C2 is entered as a word address: C2: Decrementing counter set value (4 digits BCD): 0000 to 9999 C2 + 1: Decrementing time interval (4 digits BCD; unit: 0.1 ms): 0005 to 0320 (0.5 ms to 32 ms) The meanings of the settings are the same as for the one-shot mode, but in the scheduled interrupt mode the timer PV will be reset to the set value and decrementing will begin again after the subroutine has been called. In the scheduled interrupt mode, interrupts will continue to be repeated at fixed intervals until the operation is stopped.
84
Section
2-3
The settings are the same as for the one-shot mode, but interrupts will continue to be repeated at fixed intervals until the operation is stopped. Reading the Timers Elapsed Time Use the STIM(69) instruction to read the timers elapsed time.
(@)STIM(69) C1 C2 C3
C1: Read elapsed time (006) C2: Leading word of parameter 1 C3: Parameter 2
C2: Number of times the decrementing counter has ben decremented (4 digits BCD) C2 + 1: Decrementing counter time interval (4 digits BCD; unit: 0.1 ms) C3: Elapsed time from previous decrement (4 digits BCD; unit: 0.1 ms) The time from when the interval timer is started until the execution of this instruction is calculated as follows: {(Content of C2) (Content of C2+1) + (Content of C3)} 0.1 ms If the specified interval timer is stopped, then 0000 will be stored. Stopping the Timer Use the STIM(69) instruction to stop the interval timer. The interval timer will be stopped.
(@)STIM(69) C1 000 000
In this example, an interrupt is generated 2.4 ms (0.6 ms 4) after input 00005 goes ON; the interrupt executes interrupt subroutine number 23.
Sets the decrementing time interval to 0.6 ms. (BCD: 0005 to 0320)
Starts the interval timer in one-shot mode. Specifies the first word containing the set value. Specifies the subroutine number (23).
SBN(92)
023
Interrupt program
RET(93)
85
Section
2-3
In this example, an interrupt is generated every 4.0 ms (1.0 ms 4) after input 00005 goes ON; the interrupts execute interrupt subroutine number 23.
25315 First Cycle Flag ON for 1 cycle MOV(21) #0004 DM 0010
Sets the decrementing time interval to 1.0 ms. (BCD: 0005 to 0320)
Starts the interval timer in scheduled interrupt mode. Specifies the first word containing the set value. Specifies the subroutine number (23).
SBN(92)
023
Interrupt program
RET(93)
00001
86
00002
Section
2-3
Mode Up/Down
Input functions 00000: Phase-A input 00001: Phase-B input 00002: Phase-Z input 00000: Count input 00001: See note. 00002: Reset input
Count Count frequency range Phase-difference, 2.5 kHz max. 32767 4 inputs to 32767 Individual inputs 5.0 kHz max. 0 to 65535
Input method
Control methods Target value control: Up to 16 target values and interrupt subroutine numbers can be registered. Zone comparison control: Z i t l Up to 8 sets of upper limit values, lower limit values, and interrupt subroutine numbers can be registered.
Incrementing
Note In incrementing mode, input 00001 can be used as a regular input. When the reset method is used for the software reset, input 00002 can be used as a regular input. Also, even when used for the phase-Z signal and software reset, the input status is reflected inn 00002 of the I/O memory. High-speed Counter Settings The following settings must be made in DM 6642 when using the CPM1/CPM1As high-speed counter function.
DM 6642 Bit Bits 00 to 03 Function Sets the counter mode: 0: Up/down 4: Incrementing Sets the reset method: 0: Phase-Z + software reset 1: Software reset Sets the counter: 00: Counter not being used. 01: Counter being used. Settings Incrementing Up/Down 4 0 Not used 0 or 4
04 to 07
0 or 1
0 or 1
0 or 1
08 to 15
01
01
00
Count Range
The CPM1/CPM1As high-speed counter uses linear operation and the count (present value) is stored in SR 248 and SR 249. (The upper four digits are stored in SR 249 and the lower four digits are stored in SR 248.)
Mode Up/Down Count range F003 2767 to 0003 2767 (32,767 to 32,767) The leftmost digit in SR 248 indicates the sign. F is negative, 0 is positive. 0000 0000 to 0006 5535 (0 to 65,535)
Incrementing
87
Section
2-3
An overflow will occur if the count exceeds the upper limit in the count range and an underflow will occur if the count goes below the lower limit in the count range.
Error Overflow Underflow Incrementing Occurs when the count is incremented from 65,535. --Up/Down Present value 0FFF FFFF
Occurs when the count is incremented from 32,767. Occurs when the count is FFFF FFFF decremented from 32,767.
Processing
Two types of signals can be input from a pulse encoder. The count mode used for the high-speed counter will depend on the signal type. The count mode and reset mode are set in DM 6642; these settings become effective when the power is turned on or PC operation is started. Up/Down Mode: Phase-A difference 4 two-phase signal (phase-A and phase-B) and a phase-Z signal are used for inputs. The count is incremented or decremented according to differences in the 2-phase signals. Incrementing Mode: One single-phase pulse signal and a count reset signal are used for inputs. The count is incremented according to the single-phase signal.
Up/Down Mode ON Phase A OFF ON Phase B OFF Count
1 2 3 4 5 6 7 8 7 6 5 4 3 2 1 0 1 2
Count
Incremented
Decremented
Incremented only
Note One of the reset methods described below should always be used to reset the counter when restarting it. The counter will be automatically reset when program execution is started or stopped. The following signal transitions are handled as forward (incrementing) pulses: Phase-A leading edge to phase-B leading edge to phase-A trailing edge to phase-B trailing edge. The following signal transitions are handled as reverse (decrementing) pulses: Phase-B leading edge to phase-A leading edge to phase-B trailing edge to phase-A trailing edge. The Up/Down Mode always uses a 4 phase-difference input. The number of counts for each encoder revolution would be 4 times the resolution of the counter. Select the encoder based on the countable ranges. Reset Methods Either of the two methods described below may be selected for resetting the PV of the count (i.e., setting it to 0). Phase-Z signal + software reset: The PV is reset when the phase-Z signal (reset input) is turned ON while the High-speed Counter Reset Bit (SR 25200) is ON. Software reset: The PV is reset when the High-speed Counter Reset Bit (SR 25200) is turned ON.
88
Section
2-3
25200
(2)
(3)
(4)
(5)
Not reset
Reset
Reset
Not reset
Operation timing
Reset
Phase-Z signal turns ON when Not reset. SR 25200 turns OFF. Phase-Z signal turns ON within one Not reset. cycle after SR 25200 turns ON. Phase-Z signal turns ON after at least Reset with phase-Z leading edge. one cycle elapses after SR 25200 turns ON. Phase-Z signal turns ON within one cycle after SR 25200 turns OFF. SR 25200 turns ON when phase-Z signal is ON. Reset with phase-Z leading edge. Not reset.
(4) (5)
Note The High-speed Counter Reset Bit (SR 25200) is refreshed once every cycle, so in order for it to be read reliably it must be ON for at least one cycle. The Z in phase-Z is an abbreviation for Zero. It is a signal that shows that the encoder has completed one cycle. High-speed Counter Interrupt Count For high-speed counter 0 interrupts, a comparison table is used instead of a count up. The count check can be carried out by either of the two methods described below. In the comparison table, comparison conditions (for comparing to the PV) and interrupt routine combinations are saved. Target value: A maximum of 16 comparison conditions (target values and count directions) and interrupt routine combinations are saved in the comparison table. When the counter PV and the count direction match the comparison conditions, then the specified interrupt routine is executed. Range (zone) comparison: Eight comparison conditions (upper and lower limits) and interrupt routine combinations are saved in the comparison table. When the PV is greater than or equal to the lower limit and less than or equal to the upper limit, then the specified interrupt routine is executed.
89
Section
2-3
The current count is compared to the target values in the order that target values are set in the comparison table and interrupts are generated as the count equals each target value. Once the count has equaled all of the target values in the table, the target value is set to the first target value in the table, which is again compared to the current counted until the two values are equal.
Count
Interrupts
Comparison Table Target value 1 Target value 2 Target value 3 Target value 4 Target value 5
Range Comparisons
The current count is compared in cyclic fashion to all of the ranges at the same time and interrupts are generated based on the results of the comparisons.
Comparison Table 0 Count 1 2 3 4 Rage setting 1 Rage setting 2 Rage setting 3 Rage setting 4
Note When performing target value comparisons, do not repeatedly use the INI instruction to change the current value of the count and start the comparison operation. The interrupt operation may not work correctly if the comparison operation is started immediately after changing the current value from the program. (The comparison operation will automatically return to the first target value once an interrupt has been generated for the last target value. Repetitious operation is thus possible merely by changing the current value.) Programming Use the following steps to program the high-speed counter. The high-speed counter begins the counting operation when the proper PC Setup settings are made, but comparisons will not be made with the comparison table and interrupts will not be generated unless the CTBL(63) instruction is executed. The high-speed counter is reset to 0 when power is turned ON and when operation begins. The present value of high-speed counter is maintained in SR 248 and SR 249. Controlling High-speed Counter Interrupts 1, 2, 3... 1. Use the CTBL(63) instruction to save the comparison table in the CPM1/CPM1A and begin comparisons.
(@)CTBL(63) P C TB
C: (3 digits BCD) 000: Target table set and comparison begun 001: Range table set and comparison begun 002: Target table set only 003: Range table set only TB: Beginning word of comparison table
90
Section
2-3
If C is set to 000, then comparisons will be made by the target matching method; if 001, then they will be made by the range comparison method. The comparison table will be saved, and, when the save operation is complete, then comparisons will begin. While comparisons are being executed, high-speed interrupts will be executed according to the comparison table. For details on the contents of the comparison tables that are saved, refer to the explanation of the CTBL(63) instruction in Section 7 Instruction Set. Note The comparison results are normally stored in AR 1100 through AR 1107 while the range comparison is being executed. If C is set to 002, then comparisons will be made by the target matching method; if 003, then they will be made by the range comparison method. For either of these settings, the comparison table will be saved, but comparisons will not begin, and the INI(61) instruction must be used to begin comparisons. 2. To stop comparisons, execute the INI(61) instruction as shown below.
(@)INI(61) 000 001 000
To start comparisons again, set the second operand to 000 (execute comparison), and execute the INI(61) instruction. Once a table has been saved, it will be retained in the CPM1/CPM1A during operation (i.e., during program execution) as long as no other table is saved. Reading the PV There are two ways to read the PV. The first is to read it from SR 248 and SR 249, and the second to use the PRV(62) instruction. Reading SR 248 and SR 249 The PV of high-speed counter is stored in SR 248 and SR 249 as shown below. The leftmost bit will be F for negative values.
Leftmost 4 digits SR 249 Rightmost 4 digits SR 248 Up/Down Mode F0032767 to 00032767 (32767) Incrementing Mode 00000000 to 00065535
Note
1. These words are refreshed only once every cycle, so there may be a difference from the actual PV. 2. When high-speed counter is not being used, the bits in these words can be used as work bits.
Using the PRV(62) Instruction Read the PV of the high-speed counter by using the PRV(62) instruction.
(@)PRV(62) 000 000 P1
The PV of the high-speed counter is stored as shown below. The leftmost bit will be F for negative values.
Leftmost 4 digits P1+1 Rightmost 4 digits P1 Up/Down Mode F0032767 to 00032767 (32767) Incrementing Mode 00000000 to 00065535
91
Section
2-3
The PV is read when the PRV(62) instruction is actually executed. Changing the PV There are two ways to change the PV of high-speed counter. The first way is to reset it by using the reset methods. (In this case the PV is reset to 0.) The second way is to use the INI(61) instruction. The method using the INI(61) instruction is explained here. For an explanation of the reset method, refer to the beginning of this description of high-speed counter. Change the timer PV by using the INI(61) instruction as shown below.
(@)INI(61) 000 002 D
To specify a negative number in up/down mode, set F in the leftmost digit. Application Example (Incrementing Mode) This example shows a program that uses the high-speed counter with singlephase inputs in the Incrementing Mode, making comparisons by means of the target matching method. The comparison conditions (target values and count directions) are stored in the comparison table with the subroutine numbers. Up to 16 target values can be stored. The corresponding subroutine is executed when the counters PV matches the target value. The following data is stored for the comparison table: DM 0000 0002 Number of comparison conditions: 2 DM 0001 1000 Target value 1: 1000 DM 0002 0000 DM 0003 0030 Comparison 1 interrupt subroutine no.: 30 DM 0004 2000 Target value 2: 2000 DM 0005 0000 DM 0006 0031 Comparison 2 interrupt subroutine no.: 31 The following diagram shows the example ladder program. DM 6642 must be set to 01j4, where j is the reset method which can be set to 0 or 1.
25315 (ON for first cycle) CTBL(63) 000 000 DM 0000
Registers comparison table, target value mode First word of the comparison table
SBN(92)
030
Interrupt program 30
RET(93)
SBN(92)
031
Interrupt program 31
RET(93)
92
Section
2-3
This example shows a program that uses the high-speed counter with phase-difference inputs in the Up/Down Mode, making comparisons by means of the range comparison method. The comparison conditions (upper/lower limits of the ranges) are stored in the comparison table with the subroutine numbers. Up to 8 separate ranges can be defined. The corresponding subroutine is executed when the counters PV is within the range. Note Always set 8 ranges. If fewer than 8 ranges are needed, set the remaining subroutine numbers to FFFF. A value of FFFF indicates that no subroutine is to be executed. The following data is stored for the comparison table: DM 0000 1500 DM 0001 0000 Lower limit 1: 1,500 counts DM 0002 3000 DM 0003 0000 Upper limit 1: 3,000 counts DM 0004 0040 Range 1 interrupt subroutine no.: 40 DM 0005 7500 DM 0006 0000 Lower limit 2: 7,500 counts DM 0007 0000 DM 0008 0001 Upper limit 2: 10,000 counts DM 0009 0041 Range 2 interrupt subroutine no.: 41 DM 0010 0000 DM 0011 0000 DM 0012 0000 DM 0013 0000 DM 0014 FFFF Range 3 interrupt subroutine not executed . . . . . . . . . . . . . . . DM 0035 0000 DM 0036 0000 DM 0037 0000 DM 0038 0000 DM 0039 FFFF Range 8 interrupt subroutine not executed
93
Section
2-4
The following diagram shows the example ladder program. DM 6642 must be set to 01j0, where j is the reset method which can be set to 0 or 1.
25315 (ON for first cycle) CTBL(63) 000 001 DM 0000
table,
SBN(92)
040
Interrupt program 40
RET(93)
SBN(92)
041
Interrupt program 41
RET(93)
2-4
C1: Interval timer, one-shot mode (000) C2: Timer set value (first word address) C3: Subroutine no. (4 digits BCD): 0000 to 0049
94
Section
2-4
C2: Decrementing counter set value (4 digits BCD): 0000 to 9999 C2 + 1: Decrementing time interval (4 digits BCD; unit: 0.1 ms): 0005 to 0320 (0.5 ms to 32 ms) Each time that the interval specified in word C2 + 1 elapses, the decrementing counter will decrement the present value by one. When the PV reaches 0, the designated subroutine will be called just once and the timer will stop. The time from when the STIM(69) instruction is executed until time elapses is calculated as follows: (Content of C2) (Content of C2 + 1) 0.1 ms = (0.5 to 319,968 ms) 2. When C2 is entered as a constant: The set value of the decrementing counter will equal the specified constant (in ms) and the decrementing time interval will be 10 (1 ms). Starting Up in Scheduled Interrupt Mode Use the STIM(69) instruction to start the interval timer in the scheduled interrupt mode.
(@)STIM(69) C1 C2 C3
C1: Interval timer, scheduled interrupt mode (003) C2: Timer set value (leading word no.) C3: Subroutine no. (4 digits BCD): 0000 to 0049
1, 2, 3...
1. When C2 is entered as a word address: C2: Decrementing counter set value (4 digits BCD): 0000 to 9999 C2 + 1: Decrementing time interval (4 digits BCD; unit: 0.1 ms): 0005 to 0320 (0.5 ms to 32 ms) The meanings of the settings are the same as for the one-shot mode, but in the scheduled interrupt mode the timer PV will be reset to the set value and decrementing will begin again after the subroutine has been called. In the scheduled interrupt mode, interrupts will continue to be repeated at fixed intervals until the operation is stopped. 2. When C2 is entered as a constant: The settings are the same as for the one-shot mode, but interrupts will continue to be repeated at fixed intervals until the operation is stopped. Reading the Timers Elapsed Time Use the STIM(69) instruction to read the timers elapsed time.
(@)STIM(69) C1 C2 C3
C1: Read elapsed time (006) C2: Leading word of parameter 1 C3: Parameter 2
C2: Number of times the decrementing counter has been decremented (4 digits BCD) C2 + 1: Decrementing counter time interval (4 digits BCD; unit: 0.1 ms) C3: Elapsed time from previous decrement (4 digits BCD; unit: 0.1 ms) The time from when the interval timer is started until the execution of this instruction is calculated as follows: {(Content of C2) (Content of C2+1) + (Content of C3)} 0.1 ms If the specified interval timer is stopped, then 0000 will be stored.
95
Section
2-4
Use the STIM(69) instruction to stop the interval timer. The interval timer will be stopped.
(@)STIM(69) C1 000 000
In this example, an interrupt is generated 2.4 ms (0.6 ms 4) after input 00005 goes ON; the interrupt executes interrupt subroutine number 23.
25315 First Cycle Flag ON for 1 cycle MOV(21) #0004 DM 0010
Sets the decrementing time interval to 0.6 ms. (BCD: 0005 to 0320)
Starts the interval timer in one-shot mode. Specifies the first word containing the set value. Specifies the subroutine number (only lower bytes are effective).
SBN(92)
023
Interrupt program
RET(93)
In this example, an interrupt is generated every 4.0 ms (1.0 ms 4) after input 00005 goes ON; the interrupts execute interrupt subroutine number 23.
25315 First Cycle Flag ON for 1 cycle MOV(21) #0004 DM 0010
Sets the decrementing time interval to 1.0 ms. (BCD: 0005 to 0320)
Starts the interval timer in scheduled interrupt mode. Specifies the first word containing the set value. Specifies the subroutine number (only the lower bytes are effective).
SBN(92)
023
Interrupt program
RET(93)
96
Section
2-5
2-5
Motor controller
Pulse outputs
Item
Single-phase pulse ou pu s pu se outputs i without accel/decel PULS(65) and SPED(64) Pulse output 0 (See note 1.) Pulse output 1 (See note 1.) 10 Hz to 10 kHz 10 Hz ----Continuous, Independent 1 to 16777215 50% Yes No No No
Variable duty ratio pulse a o pu se outputs PWM() Pulse output 0 (See note 1.) Pulse output 1 (See note 1.) 0.1 to 999.9 Hz 0.1 Hz ----Continuous --0 to 100% No No No Yes
Single-phase pulse outputs with trapezoidal acceleration/deceleration Pulse + direction outputs PULS(65) and ACC() Pulse Pulse output output 0 ou pu Direction output 10 Hz to 10 kHz 10 Hz 10 Hz (See note 2.) 10 Hz Continuous, Independent 1 to 16777215 50% Yes Yes Yes No Up/down pulse outputs
Execution instructions Output number u be 01000 01001 Output frequency range Pitch Up/down frequency pitch Start speed pitch Output mode Number of pulses Duty ratio (See note 3.) Control Movement method e od specification Accel/decel specification Start speed specification Duty specification
Pulse CW pulse output 0 output ou pu CCW pulse output 10 Hz to 10 kHz 10 Hz 10 Hz (See note 2.) 10 Hz Continuous, Independent 1 to 16777215 50% Yes Yes Yes No
97
Section
2-5
1. With single-phase pulse outputs, pulse outputs 0 and 1 can each be output independently. 2. Pulse outputs can be accelerated or decelerated in units of 10 Hz every 10 ms. 3. Actual pulses are affected by the transistor outputs ON response time (20 s max.) and OFF response time (40 s max.). The following table shows the relationships between the high-speed counter and the CPM2A/CPM2Cs other functions.
Interval timer interrupts Synchronized pulse control Interrupt inputs Interval timer interrupts High-speed counters Interrupt inputs (counter mode) Pulse outputs Quick-response inputs Input time constant Clock Cannot be used simultaneously. Can be used simultaneously. Can be used simultaneously. Can be used simultaneously. Can be used simultaneously. See note. Can be used simultaneously. Can be used simultaneously. Can be used simultaneously.
Note The number of simultaneous outputs varies according to the type of pulse output, as shown in the following table.
Combination Single-phase pulse output Variable duty ratio Can use one point at a time (independently). Can use two points simultaneously (independently). Cannot be used. Cannot be used. Pulse + direction output Cannot be used. Up/down p p pulse output Cannot be used.
Fixed duty ratio Single-phase Fixed duty Can use two points pulse output ratio simultaneously (independently). Variable duty ratio Pulse + direction output Up/down pulse output Can use one point at a time (independently). Cannot be used. Cannot be used.
Cannot be used.
Cannot be used.
Up to two points can be output simultaneously with only single-phase pulse outputs, so two-point output is possible when fixed duty ratio and variable duty ratio are used in combination. Outputs are possible for only one point at a time with pulse + direction outputs and up/down pulse outputs, so no other pulses can be output. Types of Pulse Outputs There are three types of pulse outputs: Single-phase pulse outputs without acceleration and deceleration, variable duty ratio pulse outputs, and single-phase pulse outputs with trapezoidal acceleration and deceleration. Single-phase Pulse Outputs Without Acceleration and Deceleration Frequency: Output destination: 10 Hz to 10 kHz (Set in units of 10 Hz.) Output number 01000 (Word 010, bit 00) Output number 01001 (Word 010, bit 01) (Pulses can be output simultaneously and independently from two points. Continuous or Independent 1 to 16,777,215
98
Section
2-5
With PULS(65), the number of pulses is set for each point (in independent mode only). With SPED(64), the output mode and target frequency are set for each point, and pulses are output.
Instruction execution: PULS(65) + SPED(64) (Independent mode) Independent mode Number of set pulses The output is stopped automatically when the set number of pulses has been output.
Instruction execution: SPED(64) (Continuous mode) Continuous mode Pulses continue to be output at the set frequency until stopped by the instruction.
Variable Duty Ratio Pulse Outputs Duty ratio: Frequency: 0% to 100% (Set in units of 1%.) 0.1 to 999.9 Hz (Set in units of 0.1 Hz.) Output number 01000 (Word 010, bit 00) Output number 01001 (Word 010, bit 01) (Pulses can be output simultaneously and independently from two points.) Continuous PWM()
Output destination:
Pulses are output at the set frequency until stopped. Duty ratio (D) = ton T
Single-phase Pulse Outputs With Trapezoidal Acceleration/Deceleration Frequency: 10 Hz to 10 kHz (Set in units of 10 Hz.) Acceleration/deceleration rate: 10 Hz/10 ms to 10 kHz/10 ms (Set in units of 10 Hz.) Pulse + Direction Outputs For CW Output: Output number 01001 (Word 010, bit 01) turned OFF. Pulses output from output number 01000 (Word 010, bit 00). For CCW Output: Output number 01001 (Word 010, bit 01) turned ON. Pulses output from output number 01000 (Word 010, bit 00).
01000 Pulse outputs 01001 Direction outputs (OFF: CW operation; ON: CCW operation)
99
Section
2-5
For CW output: Pulses output from output number 01000 (Word 010, bit 00). For CCW output: Pulses output from output number 01001 (Word 010, bit 01).
01000 CW operation 01001 CCW operation
Output mode: Continuous and Independent Number of pulses: 1 to 16,777,215 Instructions: PULS(65) and ACC() With PULS(65), the number of pulses is set (in independent mode only). With ACC(), the output mode, starting frequency, target frequency, and acceleration/deceleration rate are set, and the pulse outputs are started. From when the pulse outputs are started until they are stopped, they are controlled at a constant-ratio frequency change. Independent Mode
Pulse output frequency Instruction execution: PULS(65) + ACC() (Independent mode) In independent mode, deceleration is carried out at the acceleration/ deceleration rate in effect at the start.
Time
Continuous Mode
Pulse output frequency Target frequency 2 Target frequency 3 Target frequency 1 0 Hz Acceleration/ deceleration Acceleration/deceleration Acceleration/deceleration Start Acceleration or Acceleration or deceleration deceleration ACC() ACC() ACC() Time Instruction execution: ACC() (Continuous mode)
100
Section
2-5
2-5-1 Using Single-phase Pulse Outputs Without Acceleration and Deceleration (Fixed Duty Ratio)
PULS(65): For setting the number of output pulses. SPED(64): For pulse output control without acceleration and deceleration. INI(61): For stopping pulse outputs and changing the pulse output PV. PRV(62): For reading the pulse output PV and status.
PULS(65)
SPED(64)
Start pulse outputs. Every scan Pulse output status AR 11 AR 12 Every scan Pulse output PV
SR 228 SR 230 SR 229 SR 231
INI(61)
Immediately
PRV(62) HIGH-SPEED COUNTER PV READ instruction Read pulse output PV. Read pulse output status.
101
Section
2-5
Wire the CPM2A outputs as shown in the following illustration. (Pulses can be output independently from pulse outputs 0 and 1.)
Output 01000: Pulse output 0 (single-phase output) Output 01001: Pulse output 1 (single-phase output)
Wire the CPM2C outputs as shown in the following illustration. (Pulses can be output independently from pulse outputs 0 and 1.) Note The following examples are for Fujitsu-compatible connectors. Output bit addresses and connector pin numbers depend on the models. Refer to the CPM2C Operation Manual (W356) or the CPM2C-S Operation Manual (W377) for details.
Output connector (See above note.)
01000: Pulse output 0 (single-phase output) 01001: Pulse output 1 (single-phase output)
102
Section
2-5
Function Pulse 0 PV coordinate 0: Relative coordinate y system system Pulse 1 PV coordinate system High-speed counter setting 1: Absolute coordinate system 00: Do not use.
Setting Either 0 or 1
Either 00 or 01: Use as high-speed 01 counter 02: Use as synchronized pulse control (10 to 500 Hz). 03: Use as synchronized pulse control (20 Hz to 1 kHz). 04: Use as synchronized pulse control (300 Hz to 20 kHz).
If absolute pulses are specified with PULS(65), be sure to set the absolute coordinate system (1). Synchronized pulse control cannot be used simultaneously. The settings will go into effect when the mode is changed (from PROGRAM to MONITOR/RUN) or when the power supply is turned ON to the PC. Ladder Diagram Programming The following table shows the instruction operations related to pulse outputs without acceleration and deceleration (fixed duty ratio).
Instruction (@)PULS(65) (@)SPED(64) Control Set number of pulses Set frequency and start pulse outputs Change frequency Operation Sets the number of pulses to be output in independent mode. Sets the frequency for outputs in the independent mode or continuous mode, and starts the pulse outputs. Changes the frequency for outputs in the independent mode or continuous mode.
Stops the pulse outputs (by changing the speed to a frequency of 0 Hz). Stop pulse outputs Stops the pulse outputs. Change pulse output PV Changes the pulse output PV. Read pulse output PV Reads the pulse output PV. Read pulse output status Reads the pulse output status.
The following table shows which instructions can be executed during pulse outputs without acceleration and deceleration.
PULS(65) Continuous mode Independent mode No No SPED(64) Yes (See note 2.) Yes (See note 2.) INI(61) Yes (See note 1.) Yes (See note 1.) PRV(62) Yes Yes ACC() No No PWM() No No
Note
1. This instruction can be executed only while pulse outputs are stopped. The PV cannot be changed while pulses are being output. If the PV needs to be changed, be sure to stop the pulse output first. 2. This instruction can be used only for changing the frequency and stopping the pulse output. It cannot be used for switching between independent mode and continuous mode.
103
Section
2-5
The following table shows the words and bits related to pulse outputs without acceleration and deceleration (fixed duty ratio).
Word 228 229 230 231 252 AR 11 Bits 00 to 15 00 to 15 00 to 15 00 to 15 04 05 12 13 14 Name Pulse output PV 0, rightmost 4 digits Pulse output PV 0, leftmost 4 digits Pulse output PV 1, rightmost 4 digits Pulse output PV 1, leftmost 4 digits Pulse output 0 PV reset Pulse output 1 PV reset Pulse output 0 PV overflow/underflow Contents Cannot be used as work bi even when k bits h not used as pulse outputs.
Clears PV 0 when ON. Clears PV 1 when ON. ON: Occurred OFF: Normal Number of pulses set for pulse output 0 ON: Set (by PULS(65)) OFF: Not set Pulse output completed for pulse ON: Completed (by output 0 SPED(64)) OFF: Not completed Pulse output in progress for pulse output 0 Pulse output 1 PV overflow/underflow ON: In progress (by SPED(64)) OFF: Stopped
15
AR 12
12 13 14
ON: Occurred OFF: Normal Number of pulses set for pulse output 1 ON: Set (by PULS(65)) OFF: Not set Pulse output completed for pulse ON: Completed (by output 1 SPED(64)) OFF: Not completed Pulse output in progress for pulse output 0 ON: In progress (by SPED(64)) OFF: Stopped
15
Set Number of Pulses Specify the number of pulses to be output in independent mode.
(@)PULS(65) P D N
Port specifier (000: Pulse output 0; 010: Pulse output 1) Type of Pulse Output (000: Relative pulses; 001: Absolute pulses) (See note.) Beginning word of setting for number of pulses Number of pulses (Rightmost, leftmost digits) Register the number of pulses to be set. 96,777,215 to 16,777,215 Negative numbers are expressed by turning ON the leftmost bit.
N N+1
Type of Pulse Output 000: 001: Relative pulses (SV for number of pulses = Number of pulses moved) Absolute pulses (SV for number of pulses = The next PV on the absolute coordinate system, i.e., the pulse output PV + number of pulses moved)* *Absolute pulses can only be specified by PULS(65) when the PV coordinate system in the PC Setup is set for an absolute coordinate system.
Set Frequency and Start Pulse Outputs Change Frequency These functions set the pulse output number, the output mode, and the frequen-
104
Section
2-5
cy, and begin pulse outputs. They can also be used to change the frequency if pulse outputs are already in progress.
(@)SPED(64) P M F
Port specifier (000: Pulse output 0; 010: Pulse output 1) Mode designation (000: Independent; 001: Continuous) Target frequency data word F Target frequency Register the target frequency data to be set. #0001 to #1000 (4 digits BCD): 10 Hz to 10 kHz #0000: Pulse output stopped
Change Pulse Output PV Resetting Pulse Output PV This function changes the pulse output present value (PV). The PV can also be cleared by using SR 25204 and SR 25205.
(@)INI(61) P 004 C2
Port specifier (000: Pulse output 0; 010: Pulse output 1) Control designation (004: Change pulse output PV) Beginning word for PV change data Change PV data (Rightmost, leftmost digits) Register the PV data to be changed. 96,777,215 to 16,777,215 Negative numbers are expressed by turning ON the leftmost bit.
C2 C2+1
The pulse output PV can only be changed or reset while pulse outputs are stopped. Check to be sure that the Pulse Output In Progress Flags (AR 1115 and AR 1215) have been turned OFF. Stop Pulse Outputs This function stops the pulse outputs. Using SPED(64)
(@)SPED(64) P M F
Port specifier (000: Pulse output 0; 010: Pulse output 1) Mode designation (000: Independent; 001: Continuous) Target frequency data word F #0000 Specifies a frequency of 0 Hz.
Using INI(61)
(@)INI(61) P 003 000
Port specifier (000: Pulse output 0; 010: Pulse output 1) Control designation (003: Stop pulse outputs) Fixed: 000
Besides executing the instructions shown above, it is also possible to stop pulse outputs by stopping operation (PROGRAM mode). Read Pulse Output PV This function reads the pulse output PV.
105
Section
2-5
Port specifier (000: Pulse output 0; 010: Pulse output 1) Control designation (003: Read pulse output PV) Beginning word for storing pulse output PV
D D+1
Pulse output PV (rightmost, leftmost digits) The PV data that is read is stored here. 96,777,215 to 16,777,215 Negative numbers are expressed by turning ON the leftmost bit.
Using Data Areas As shown in the following illustration, the pulse output PV for pulse output 0 is stored in words 228 and 229, and the pulse output PV for pulse output 1 is stored in words 230 and 231.
Pulse Output 0 Word 228 Word 229 PV (Rightmost) PV (Leftmost) Pulse Output 1 Word 230 Word 231 PV (Rightmost) PV (Leftmost)
Words 228 to 231 are refreshed with every scan, so there may be a discrepancy from the exact PV at any given time. Words 228 to 231 cannot be used as work words even when pulse outputs are not being used. When the PV is read by executing PRV(62), words 228 to 231 are refreshed with the same timing. Read Pulse Output Status This function reads the pulse output status. Using an Instruction
(@)PRV(62) P 001 D
Port specifier (000: Pulse output 0; 010: Pulse output 1) Control designation (001: Read pulse output status) Word for storing pulse output status
Pulse output status 0: Constant speed; 1: Accelerating/decelerating Pulse output PV overflow/underflow 0: Normal; 1: Overflow or underflow occurred Pulse output in progress 0: Stopped 1: Output in progress
Number of pulses 0: Not set 1: Set Pulse output completion 0: Not completed 1: Completed
Using Data Areas As shown in the following illustration, the pulse output status for pulse output 0 is stored in AR 11, and the pulse output status for pulse output 1 is stored in AR 12.
AR 11: Pulse output 0 AR 12: Pulse output 1 Pulse output in progress 0: Stopped 1: Output in progress Pulse output completion 0: Not completed 1: Completed Pulse output status: 0: Constant speed; 1: Accelerating/decelerating Pulse output PV overflow/underflow 0: Normal 1: Overflow or underflow occurred Number of pulses 0: Not set 1: Set
106
Section
2-5
Note The flags in AR 11 and AR 12 are refreshed once each cycle, so the values in these words may not reflect the actual status during each cycle, but the flags in AR 11 and AR 12 are refreshed when the status is read with PRV(62).
Continuous Mode
Frequency
Time PULS(65) execution SPED(64) execution INI(61) execution Output in progress Output completed
107
Section
2-5
Explanation In this example, when the execution condition (00005) turns ON, 100 pulses are output from output 01000 (pulse output 0) at a frequency of 60 Hz.
Frequency 60 Hz Number of pulses Execution condition (00005)
Wiring Wire the CPM2A to the motor driver as shown in the following illustration.
Motor Driver
Wire the CPM2C to the motor driver as shown in the following illustration. In this case, a CPU Unit with sinking transistor outputs is used. Note The following examples are for Fujitsu-compatible connectors. Output bit addresses and connector pin numbers depend on the models. Refer to the CPM2C Operation Manual (W356) or the CPM2C-S Operation Manual (W377) for details.
Output connector
Motor Driver
24 VDC
108
Section
2-5
Sets the coordinate system for pulse output 0 as relative. Set for other than synchronized pulse control. (Set to 01jj when using the high-speed counter.)
Programming
00005 (Execution condition)
(13)
Detects turning ON of execution condition. Sets number of pulses. Pulse output 0 Relative pulses Beginning word for pulse SV data Pulse output 0 Independent mode Frequency: 60 Hz
PLUS(65)
DM 0000 DM 0001
JOG Operation Explanation In this example, when the execution condition (00005) turns ON, JOG pulses are output at a frequency of 100 Hz from either output 01000 (pulse output 0) or output 01001 (pulse output 1). When the execution condition (00005) turns OFF, the output is stopped. Switching between output 01000 (pulse output 0) and output 01001 (pulse output 1) is performed by means of the direction designator (00006).
Frequency (direction)
Time
Wiring Wire the CPM2A to the motor driver as shown in the following illustration.
Motor Driver
109
Section
2-5
Wire the CPM2C to the motor driver as shown in the following illustration. In this case, a CPU Unit with sinking transistor outputs is used. Note The following examples are for Fujitsu-compatible connectors. Output bit addresses and connector pin numbers depend on the models. Refer to the CPM2C Operation Manual (W356) or the CPM2C-S Operation Manual (W377) for details.
Output connector (See above note.)
Motor Driver
24 VDC
Note Refer to page operation manual for details on wiring outputs. PC Setup
15 DM 6629 DM 6642 0 0 0 0 0 Sets the coordinate system for pulse outputs 0 and 1 as relative. Set for other than synchronized pulse control. (Set to 01jj when using the high-speed counter.)
Programming
00005 (Execution condition)
(13) (14)
Detects turning ON of execution condition. Detects turning OFF of execution condition. Output in CW direction Pulse output 0 Continuous mode Output frequency: 100 Hz Output in CCW direction Pulse output 1 Continuous mode Output frequency: 100 Hz
(Direction designator)
SPED(64)
SPED(64)
INI(61)
110
Section
2-5
PWM(): For setting the frequency and duty ratio. Create a ladder diagram program. INI(61): For stopping pulse outputs. PRV(62): For reading the pulse output status.
PWM()
PULSE WITH VARIABLE DUTY RATIO instruction (Note: The duty ratio is the ratio of ON time to pulse frequency.) Every scan MODE CONTROL instruction Pulse output status AR 11 AR 12 Every scan (Either 01000 or 01001 can be used.)
INI(61)
Immediately HIGH-SPEED COUNTER PV PRV(62) READ instruction Read pulse output status.
Wire the CPM2A outputs as shown in the following illustration. (Pulses can be output independently from pulse outputs 0 and 1.)
Output 01000: Pulse output 0 (single-phase output) Output 01001: Pulse output 1 (single-phase output)
Wire the CPM2C outputs as shown in the following illustration. (Pulses can be output independently from pulse outputs 0 and 1.)
111
Section
2-5
Note The following examples are for Fujitsu-compatible connectors. Output bit addresses and connector pin numbers depend on the models. Refer to the CPM2C Operation Manual (W356) or the CPM2C-S Operation Manual (W377) for details.
Output connector (See above note.)
01000: Pulse output 0 (single-phase output) 01001: Pulse output 1 (single-phase output)
PC Setup
Synchronized pulse control cannot be used simultaneously. The settings will go into effect when the mode is changed (from PROGRAM to MONITOR/RUN) or when the power supply is turned ON to the PC. Ladder Diagram Programming The following table shows the instruction operations related to pulse outputs with variable duty ratio.
Instruction (@)PWM() Control Pulse output with variable duty ratio Change duty ratio Operation Sets the frequency and duty ratio and starts the pulse outputs. Changes the duty ratio during pulse while pulse outputs with variable duty ratio are already in progress. Stops the pulse outputs.
(@)INI(61) (@)PRV(62)
Read pulse output status Reads the pulse output status (during pulse outputs).
The following table shows which instructions can be executed during pulse outputs without acceleration and deceleration.
PULS(65) SPED(64) No No INI(61) PRV(62) ACC() No PWM() Yes (See note 2.) Yes (See note 1.) Yes
Note
1. This instruction can be used only for stopping pulse outputs. 2. This instruction can be used only for changing the duty ratio. The frequency cannot be changed while pulses are being output. If the frequency needs to be changed, be sure to stop the pulse output first.
112
Section
2-5
The following table shows the words and bits related to pulse outputs with variable duty ratio.
Word AR 11 Bit 15 Name Pulse output in progress for pulse output 0 Pulse output in progress for pulse output 1 Contents ON: In progress (by SPED(64), ACC(), or PWM()) OFF: Stopped ON: In progress (by SPED(64), ACC(), or PWM()) OFF: Stopped
AR 12
15
Pulse Output With Variable Duty Ratio Change Duty Ratio These functions set the position for outputting pulses (01000, 01001), the frequency, and the duty ratio, and start the pulse outputs. By changing the duty ratio setting and executing PWM() again, it is also possible to change the duty ratio while pulse outputs with variable duty ratio are already in progress.
(@PWM() P F D
Port specifier (000: Pulse output 0; 010: Pulse output 1) Target frequency data word Duty ratio data word Target frequency Register the target frequency to be set. #0001 to #9999 (4 digits BCD): 0.1 Hz to 999.9 Hz
Duty ratio Register the duty ratio to be set. #0000 to #0100 (4 digits BCD): 0% to 100%
The pulse frequency cannot be changed while pulses are being output. Stop Pulse Outputs This function stops pulse outputs.
(@)INI(61) P 003 000
Port specifier (000: Pulse output 0; 010: Pulse output 1) Control designation (003: Stop pulse outputs) Fixed: 000
Note The pulse outputs can also be stopped by switching the PC to PROGRAM mode. Read Pulse Output Status This function reads the pulse output status. Using an Instruction
(@)PRV(62) P 001 D
Port specifier (000: Pulse output 0; 010: Pulse output 1) Control designation (001: Read pulse output status) Beginning word for storing pulse output status
113
Section
2-5
Using Data Areas As shown in the following illustration, the pulse output status for pulse output 0 is stored in AR 1115, and the pulse output status for pulse output 1 is stored in AR 1215.
AR 11: Pulse output 0 AR 12: Pulse output 1 Pulse output in progress 0: Stopped 1: Output in progress
Note AR 1115 and AR 1215 are refreshed once each cycle, so the values in these words may not reflect the actual status during each cycle, but AR 1115 and AR 1215 are refreshed when the status is read with PRV(62).
Time PWM() execution INI(61) execution Output in progress Output completion Set number of pulses
Application Example
Explanation In this example, when the execution condition (00005) turns ON, variable duty pulses are output from output 01000 (pulse output 0) at a frequency of 100 Hz. The duty ratio at this time can be changed with the thumbwheel switch 0. Wiring Wire the CPM2A to the motor driver and thumbwheel switch as shown in the following illustration.
Motor Driver
Wire the CPM2C to the motor driver and thumbwheel switch as shown in the following illustration. In this case, a CPU Unit with sinking transistor outputs is used.
114
Section
2-5
Note The following examples are for Fujitsu-compatible connectors. I/O bit addresses and connector pin numbers depend on the models. Refer to the CPM2C Operation Manual (W356) or the CPM2C-S Operation Manual (W377) for details.
Output connector
Input connector
Motor Driver
DIV(33) Changes analog control 0 value to a value from 0 to 100. Value in SR 250 (Analog control 0 in CPM2A PCs) (see note) Divide value by 2. Duty ratio setting PWM() Pulse outputs with variable duty Pulse output 0 Output frequency: 100 Hz Duty ratio setting INI(61) Stops pulse output 0.
Note The CPM2C is not provided with an analog control. For external settings, specify the input word connected to the thumbwheel switch.
115
Section
2-5
Detects OFF to ON transition in execution condition. Reads the value from the thumb rotary switch.
Duty ratio setting Variable duty pulse output Pulse output 0 Output frequency: 100 Hz Duty ratio setting Stops pulse output 0
END (01)
116
Section
2-5
PULS(65): For setting the number of output pulses. Create a ladder diagram program. ACC(): For controlling pulse outputs with trapezoidal acceleration and deceleration INI(61): For stopping pulse outputs and changing the pulse output PV. PRV(62): For reading the pulse output PV and status.
PULS(65)
ACC()
Specify relative or absolute pulses. Number of output pulses set value (8 digits BCD)
Mode designation
Starting frequency: 0 Hz to 10 kHz Target frequency: 10 Hz to 10 kHz Acceleration/deceleration rate: 10 ms increase/decrease 10 Hz to 10 kHz
AR 11
SR 228
117
Section
2-5
Select the pulse output direction control method according to the type of signal used.
Up/down Pulse Outputs
Wire the CPM2C outputs as shown in the following illustration. Note The following examples are for Fujitsu-compatible connectors. Output bit addresses and connector pin numbers depend on the models. Refer to the CPM2C Operation Manual (W356) or the CPM2C-S Operation Manual (W377) for details.
Pulse + Direction Outputs (See above note.) Output connector 01000: Pulse output 01001: Direction output
Up/down Pulse Outputs (See above note.) Output connector 01000: CW output 01001: CCW output
118
Section
2-5
Setting Either 0 or 1
0: Relative coordinate system 1: Absolute coordinate system 00: Do not use. 01: Use as high-speed counter 02: Use as synchronized pulse control (10 to 500 Hz). 03: Use as synchronized pulse control (20 Hz to 1 kHz). 04: Use as synchronized pulse control (300 Hz to 20 kHz).
DM 6642
08 to 15
Either 00 or 01
If absolute pulses are specified with PULS(65), be sure to set the absolute coordinate system (1). Synchronized pulse control cannot be used simultaneously. The settings will go into effect when the mode is changed (from PROGRAM to MONITOR/RUN) or when the power supply is turned ON to the PC. Ladder Diagram Programming The following table shows the instruction operations related to pulse outputs with trapezoidal acceleration and deceleration (fixed duty ratio).
Instruction (@)PULS(65) (@)ACC() Control Set number of pulses Set frequency and start pulse outputs Operation Sets the number of pulses to be output in independent mode. Sets the target frequency, starting frequency, and acceleration/deceleration rate for outputs in independent mode or continuous mode, and starts the pulse outputs. Changes the frequency during pulse output in continuous mode by accelerating or decelerating according to the specified acceleration/deceleration rate. Decelerates pulse outputs to a stop according to the specified acceleration/deceleration rate. Stops the pulse outputs. Changes the pulse output PV. Reads the pulse output PV. Reads the pulse output status.
Change frequency
(@)INI(61)
( ) (@)PRV(62) ( )
Stop (decelerate stop) pulse outputs Change pulse output PV Read pulse output PV Read pulse output status
The following table shows which instructions can be executed during pulse outputs with trapezoidal acceleration and deceleration.
PULS(65) Continuous mode Independent mode No No No No SPED(64) INI(61) Yes (See note 1.) Yes (See note 1.) PRV(62) Yes Yes No Yes (See note 2.) ACC() PWM() No No
Note
1. This instruction can be executed only while pulse outputs are stopped. The PV cannot be changed while pulses are being output. If the PV needs to be changed, be sure to stop the pulse output first. 2. This instruction can be used only for changing the frequency and stopping the pulse output. It cannot be used for switching between independent mode and continuous mode. Moreover, ACC() cannot be received during acceleration or deceleration.
119
Section
2-5
The following table shows the words and bits related to pulse outputs with trapezoidal acceleration and deceleration (fixed duty ratio).
Word 228 229 252 AR 11 Bits Name 00 to 15 Pulse output PV 0, rightmost 4 digits 00 to 15 Pulse output PV 0, leftmost 4 digits 04 11 Pulse output 0 PV reset Pulse output status for pulse output 0 Contents Cannot be used as work bits even when not used as pulse outputs. Clears PV 0 when ON. ON: Accelerating or decelerating OFF: Constant speed
12 13 14 15
ON: Occurred OFF: Normal Number of pulses set for pulse output 0 ON: Set OFF: Not set Pulse output completed for pulse ON: Completed output 0 OFF: Not completed Pulse output in progress for pulse ON: In progress (by output 0 SPED(64), ACC(), or PWM()) OFF: Stopped
Set Number of Pulses Specify the number of pulses to be output in independent mode.
(@)PULS(65) 000 D N
Fixed at 000: Pulse output 0 Type of Pulse Output (000: Relative pulses; 001: Absolute pulses) (See note.) Beginning word of setting for number of pulses Number of pulses (Rightmost, leftmost digits) Register the number of pulses to be set. 96,777,215 to 16,777,215 Negative numbers are expressed by turning ON the leftmost bit.
N N+1
Type of Pulse Output 000: Relative pulses (SV for number of pulses = Number of pulses moved) 001: Absolute pulses (SV for number of pulses = The next PV on the absolute coordinate system, i.e., the pulse output PV + number of pulses moved)* *Absolute pulses can only be specified by PULS(65) when the PV coordinate system in the PC Setup is set for an absolute coordinate system.
120
Section
2-5
Set Frequency and Start Pulse Outputs Change Frequency These functions set the output mode, the target frequency, the starting frequency, and the acceleration/deceleration rate, and they begin pulse outputs. They can also be used to change the frequency, by accelerating or decelerating at the specified acceleration/deceleration rate, if pulse outputs are already in progress in continuous mode. Setting the Frequencies, Acceleration/Deceleration, and Starting Pulse Outputs in Independent Mode
(@)ACC() 000 M T
Fixed at 000: Pulse output 0 Output mode designation Beginning word of settings table
Output mode Specify the output mode. 000: Up/down pulse outputs, independent mode 002: Pulse + direction outputs, independent mode
T T+1 T+2
Acceleration/deceleration rate (#0001 to #1000 BCD: 10 Hz to 10 kHz) Target frequency (#0001 to #1000 BCD: 10 Hz to 10 kHz) Starting frequency (#0000 to #1000 BCD: 0 to 10 kHz)
Register the data for each frequency. The acceleration/deceleration rate is the increase or decrease in the frequency every 10 ms. Pulse output frequency Target frequency Starting frequency Number of pulses
0 Hz
Time In independent mode, the acceleration and deceleration points are determined from the number of pulses, the acceleration/deceleration rate, the target frequency, and the the starting frequency.
121
Section
2-5
Setting the Frequency and Acceleration/Deceleration, Starting Pulse Outputs, and Changing the Frequency in Continuous Mode
(@)ACC() 000 M T
Fixed at 000: Pulse output 0 Output mode designation Beginning word of settings table Output mode Specify the output mode. 010: Up/down pulse output, CW, continuous mode 011: Up/down pulse output, CCW, continuous mode 012: Pulse + direction output, CW, continuous mode 013: Pulse + direction output, CCW, continuous mode
T T+1 T+2
Acceleration/deceleration rate (#0001 to #1000 BCD: 10 Hz to 10 kHz) Target frequency (#0001 to #1000 BCD: 10 Hz to 10 kHz) Starting frequency (#0000 to #1000 BCD: 0 to 10 kHz)
Register the data for each frequency. The acceleration/deceleration rate is the increase or decrease in the frequency every 10 ms.
Pulse output frequency Target frequency Starting frequency 0 Hz Time In continuous mode, pulses are output at the target frequency until stopped. The next ACC() instruction cannot be received except during acceleration or deceleration.
Change Pulse Output PV This function changes the pulse output PV.
Fixed at 000: Pulse output 0 Control designation (004: Change pulse output PV) Beginning word for PV change data
C2 C2+1
Change PV data (Rightmost, leftmost digits) Register the PV data to be changed. 96,777,215 to 16,777,215 Negative numbers are expressed by turning ON the leftmost bit.
Note The pulse output PV can be changed only while the pulse output is stopped.
122
Section
2-5
Fixed at 000: Pulse output 0 Control designation (003: Stop pulse outputs) Fixed at 000
Fixed at 000: Port specifier Mode designation Beginning word of settings table
T T+1 T+2
Acceleration/deceleration rate (#0001 to #1000 BCD: 10 Hz to 10 kHz) Target frequency (#0000 to #1000 BCD: 0 Hz to 10 kHz) Starting frequency (#0000 to #1000 BCD: 0 to 10 kHz)
Register the data for each frequency. The acceleration/deceleration rate is the increase or decrease in the frequency every 10 ms.
Note The pulse outputs can also be stopped by switching the PC to PROGRAM mode. Read Pulse Output PV This function reads the pulse output PV. Using an Instruction
(@)PRV(62) 000 003 D
Fixed at 000: Pulse output 0 Control designation (003: Read pulse output PV) Beginning word for storing pulse output PV
D D+1
Pulse output PV (rightmost, leftmost digits) The PV data that is read is stored here. 96,777,215 to 16,777,215 Negative numbers are expressed by turning ON the leftmost bit.
Using Data Areas As shown in the following illustration, the pulse output PV for pulse output 0 is stored in words 228 and 229.
Pulse Output 0 Word 228 Word 229 PV (Rightmost) PV (Leftmost)
SR 228 and SR 229 are refreshed once each cycle, so the values in these words may not reflect the actual status during each cycle. SR 228 and SR 229 are refreshed immediately when their status is read with PRV(62). SR 228 to SR 231 are refreshed with every scan, so there may be a discrepancy from the exact PV at any given time.
123
Section
2-5
SR 228 to SR 231 cannot be used as work words even when pulse outputs are not being used. When the PV is read by executing PRV(62), SR 228 to SR 231 are refreshed with the same timing. Read Pulse Output Status This function reads the pulse output status. Using an Instruction
(@)PRV(62) 000 001 D
Fixed at 000: Pulse output 0 Control designation (001: Read pulse output status) Word for storing pulse output status
Pulse output status 0: Constant rate 1: Accelerating or decelerating Pulse output PV overflow/underflow 0: Normal; 1: Overflow or underflow occurred Pulse output in progress 0: Stopped 1: Output in progress
Number of pulses 0: Not set 1: Set Pulse output completion 0: Not completed 1: Completed
Using Data Areas As shown in the following illustration, the pulse output status for pulse output 0 is stored in AR 1111 to AR 1115.
AR 11: Pulse output 0 Pulse output in progress 0: Stopped 1: Output in progress Pulse output completion 0: Not completed 1: Completed Pulse output status 0: Constant rate 1: Accelerating or decelerating Pulse output PV overflow/underflow 0: Normal 1: Overflow or underflow occurred Number of pulses 0: Not set 1: Set
Note AR 1111 through AR 1115 are refreshed once each cycle, so the values of these flags may not reflect the actual status, but these flags are refreshed immediately when their status is read with PRV(62).
124
Section
2-5
Time PULS(65) execution ACC() execution Output 0 in progress Output 1 in progress Output completion Output status Set number of pulses
Time ACC() execution (1) ACC() execution (2) INI(61) execution Output 0 in progress Output 1 in progress Output completion Output status Set number of pulses
Time ACC() execution (Stop) Output 0 in progress Output 1 in progress Output completion Output status Set number of pulses
125
Section
2-5
Time PULS(65) execution ACC() execution INI(61) execution Output 0 in progress Output 1 in progress Output completion Output status Set number of pulses
Time PULS(65) execution ACC() execution ACC() execution Output 0 in progress Output 1 in progress Output completion Output status Set number of pulses
Application Example
Positioning Explanation In this example, when the execution condition (00005) turns ON, 1000 pulses are output from output 01000 (pulse output 0) in a trapezoidal acceleration/deceleration pattern as shown in the following diagram.
Frequency (Hz) Acceleration/deceleration rate 500 200 10 Hz 10 ms Number of pulses Execution condition (00005)
126
Section
2-5
Wiring Wire the CPM2A to the motor driver as shown in the following illustration.
Motor Driver
Wire the CPM2C to the motor driver as shown in the following illustration. In this case, a CPU Unit with sinking transistor outputs is used. Note The following examples are for Fujitsu-compatible connectors. Output bit addresses and connector pin numbers depend on the models. Refer to the CPM2C Operation Manual (W356) or the CPM2C-S Operation Manual (W377) for details.
Output connector
Motor Driver
24 VDC
127
Section
2-5
Sets frequency and starts pulse output. Pulse output 0 Independent mode, up/down pulse output Beginning word of Acceleration/deceleration rate: 10 Hz/10 ms settings table Target frequency: 500 Hz Starting frequency: 200 Hz
Jogging Explanation In this example, when the execution condition (00005) turns ON, JOG pulses are output at a frequency of 100 Hz from either output 01000 (CW direction) or output 01001 (CCW direction). When the execution condition (00005) turns OFF, the output is stopped. As shown in the following diagram, the JOG pulses are accelerated and decelerated at the start and stop of the operation. Switching between output 01000 (CW direction) and output 01001 (CCW direction) is performed by means of the direction designator (00006).
Frequency (Hz) Acceleration/deceleration rate Time 10 Hz 10 ms
Wiring Wire the CPM2A to the motor driver as shown in the following illustration.
Motor Driver
128
Section
2-5
Wire the CPM2C to the motor driver as shown in the following illustration. In this case, a CPU Unit with sinking transistor outputs is used. Note The following examples are for Fujitsu-compatible connectors. Output bit addresses and connector pin numbers depend on the models. Refer to the CPM2C Operation Manual (W356) or the CPM2C-S Operation Manual (W377) for details.
Output connector (See above note.)
Motor Driver
24 VDC
129
Section
2-5
Detects turning ON of execution condition. Detects turning OFF of execution condition. Output in CW direction Pulse output 0 Continuous mode, up/down pulses, CW direction Beginning word of settings table Output in CCW direction Pulse output 0 Continuous mode, up/down pulses, CCW direction Beginning word of settings table Acceleration/deceleration rate: 10 Hz/10 ms Target frequency: 500 Hz Starting frequency: 200 Hz
(Direction designator)
AR1115
(14) ACC()
(Direction designator)
ACC()
(14) ACC()
Deceleration stop Pulse output 0 Beginning word of settings table Acceleration/deceleration rate: 10 Hz/10 ms Target frequency: 0 Hz
130
Section
2-6
2-6
Pulses are output at the specified frequency until stopped. Continuous mode
Pulse output is stopped automatically when the specified number of pulses has been output. Independent mode Specified number of pulses
Stepping motor
Stepping motor
Control input
Motor controller
Note
1. The CPM1A uses a single-phase pulse output. The control signal for the direction of rotation (CW/CCW) for the motor driver must be written in the program. 2. Be sure to use a CPU Unit with transistor outputs.
131
Section
2-6
In N, set the beginning word address of the words where the number of pulses is set. Store the number of pulses in words N and N+1, in eight digits BCD, with the leftmost four digits in N+1 and the rightmost four digits in N. Make the setting within a range of 00000001 to 16777215 (BCD).
132
Section
2-6
With SPED(64), set the bit location for pulse outputs (IR 01000 or IR 01001), the output mode (independent, continuous), and the pulse frequency to begin the pulse output.
@SPED(64) P M F
000: Outputs to IR 01000 010: Outputs to IR 01001 000: Independent mode 001 Continuous mode For the beginning pulse output frequency, specify a constant or word contents. The specified value and set frequency are as follows: Specified value: 0002 to 0200 Set frequency: 20 to 2,000 Hz
Note
1. Pulses can be output from only one bit at a time. 2. When pulse output is begun in independent mode, the number of pulses is read when SPED(64) is executed. PULS(65) cannot be used to change the number of pulses while pulses are being output.
Same as at beginning of pulse output. Same as at beginning of pulse output. For the changed pulse output frequency, specify a constant or word contents. The specified value and set frequency are as follows: Specified value: 0002 to 0200 Set frequency: 20 to 2,000 Hz
133
Section
2-7
2-7
Main motor
Rotary encoder
Motor driver
Item
Input mode Differential phase Pulse + direction Up/down pulse input mode input mode input mode Phase-A input Count input CW input Phase-B input Direction input CCW input Differential phase Single-phase input Single-phase input input (4X) 10 to 500 Hz (accuracy 1 Hz) 20 Hz to 1 kHz (accuracy 1 Hz) 300 Hz to 20 kHz (accuracy 25 Hz) (See note 2.) Pulse output 0 Pulse output 1 Single-phase output 10 Hz to 10 kHz (accuracy 10 Hz) 1% to 1,000% (Can be specified in units of 1%.) 10 ms Increment mode Count input (See note 1.) Single-phase input
00000 00001
01000 01001
Note
1. Can be used as an ordinary input. 2. When 10 kHz or less, then the accuracy is 10 Hz. 3. Either can be selected as the output number, using SYNC().
134
Section
2-7
The directions of pulse inputs are all ignored. The frequency of a pulse that has been input is read, without regard to the direction. The following table shows the relationships between synchronized pulse control and the CPM2As other functions.
Function Synchronized pulse control Interrupt inputs Interval timer interrupts High-speed counters Interrupt inputs (counter mode) Pulse outputs Quick-response inputs Input time constant Clock --Can be used simultaneously. Can be used simultaneously. Cannot be used simultaneously. Can be used simultaneously. Cannot be used simultaneously. Can be used simultaneously. See note. Can be used simultaneously. Synchronized pulse control
Note When inputs 00000 and 00001 are set for use as synchronized pulse control inputs, the input time constant settings for the affected inputs are disabled. The input time constants remain in effect, however, for the values for refreshing the relevant input data area. The relationship between the pulse input frequency and the pulse output frequency is shown below.
Frequency ratio
Rough pulse output frequency Values are rounded off in units of 10 Hz.
A value less than 10 Hz is regarded as 0 Hz. A value greater than 10 kHz is regarded as 10 kHz. Pulse output frequency (10 Hz to 10 kHz)
The scaling factor control cycle is 10 ms, and the pulse output frequency is changed at intervals of 10 ms with respect to the pulse input frequency.
Frequency
Time
135
Section
2-7
Input numbers: 00000, 00001, and 0002 Output numbers: 01000 and 01001
SYNC(): For beginning synchronized pulse control and changing the scaling factor. Create a ladder diagram program. INI(61): For stopping synchronized pulse control. PRV(62): For reading the high-speed counter frequency and the synchronized pulse control status.
Immediately Every scan HIGH-SPEED COUNTER PV Synchronized pulse PRV(62) READ instruction control status
Read high-speed counter frequency Read synchronized pulse control status AR 1100 to AR 1107
136
Section
2-7
Select the differential phase input mode, the pulse + direction input mode, the up/down pulse input mode, or the increment mode. These modes are explained below. Select one of the following as the input frequency range: 10 Hz to 500 Hz, 20 Hz to 1 kHz, or 300 Hz to 20 kHz. For more information on input frequencies, refer to the following diagrams. Differential Phase Input Mode In the differential phase input mode, the count is incremented or decremented according to two differential phase signals (phase A and phase B) with a multiplication factor of 4.
ON Phase A OFF ON Phase B OFF
Nms Frequency =
1,000 N
Pulse + Direction Input Mode In the pulse + direction input mode, pulse signals and direction signals are input, and the count is incremented or decremented according to the direction signal status.
ON OFF Direction inputs ON OFF
Pulse inputs
Nms Frequency =
1,000 N
Up/Down Pulse Input Mode In the up/down pulse input mode, CW signals (up pulses) and CCW signals (down pulses) are input, and the count is incremented or decremented accordingly.
ON CW inputs OFF ON CWW inputs OFF
Decremented 1,000 N
137
Section
2-7
Increment Mode In the increment mode, pulse signals are input and the count is incremented with each pulse. Phase-B inputs can be used as ordinary inputs.
ON Pulse inputs OFF
Nms Frequency =
1,000 N
Wiring the Inputs Input Wiring Wire the CPM2A inputs as shown in the following diagram.
Differential Phase Input Mode 00000: Phase-A input 00001: Phase-B input 00002: Phase-Z input Up/Down Pulse Input Mode 00000: CW input 00001: CCW input
Pulse + Direction Input Mode 00000: Pulse input 00001: Direction input
138
Section
2-7
Note The following examples are for Fujitsu-compatible connectors. Input bit addresses and connector pin numbers depend on the models. Refer to the CPM2C Operation Manual (W356) or the CPM2C-S Operation Manual (W377) for details.
Differential Phase Input Mode Input connector (See above note.) Up/Down Pulse Input Mode Input connector (See above note.)
00002: Phase-Z input 00001: Phase-B input 00000: Phase-A input Pulse + Direction Input Mode Input connector (See above note.) Increment Mode Input connector (See above note.) 00001: CCW input 00000: CW input
Output Wiring Wire the CPM2A outputs as shown in the following diagram.
Output Wiring
139
Section
2-7
Output connector
PC Setup
The settings in the PC Setup related to synchronized pulse control are listed in the following table.
Word DM 6642 Bits 00 to 03 Function High-speed counter input mode setting 0: Differential phase input 5 kHz 1: Pulse + direction input 20 kHz 2: Up/down input 20 kHz 4: Increment 20 kHz High-speed counter reset method setting 0: Phase-Z signal + software reset 1: Software reset High-speed counter setting 00: Do not use. 01: Use as high-speed counter 02: Use as synchronized pulse control (10 Hz to 500 Hz) 03: Use as synchronized pulse control (20 Hz to 1 kHz) 04: Use as synchronized pulse control (300 Hz to 20 kHz) Setting 0, 1, 2, or 4
04 to 07
0 or 1
08 to 15
02, 03, 04
The settings will go into effect when the mode is changed (from PROGRAM to MONITOR/RUN) or when the power supply is turned ON to the PC. Ladder Diagram Programming The following table shows the instruction operations related to synchronized pulse control.
Instruction Control (@)SYNC() Start synchronized control Change frequency scaling factor (@)INI(61) Stop synchronized control (@)PRV(62) ( ) ( ) Read input frequency Read synchronized control status Operation Specifies the frequency scaling factor and the output port, and outputs pulses. Changes the frequency scaling factor during pulse output. Stops the pulse outputs. Reads the input frequency. Reads the synchronized control status.
140
Section
2-7
The following table shows the words and bits related to synchronized pulse control.
Word 248 249 AR 11 AR 12 Bits 00 to 15 00 to 15 15 15 Name Input frequency PV, rightmost digits Input frequency PV, leftmost digits Pulse output in progress for pulse output 0 Pulse output in progress for pulse output 1 Contents Reads the input p frequency PV f PV. ON: Output in progress OFF: Stopped O S opped
Start Frequency Control This function specifies the bits for pulse outputs (01000, 01001) and the frequency scaling factor (1% to 1,000%), and starts the pulse output.
(@)SYNC() 000 P2 C
Pulse input port designation (000: High-speed counter) Pulse output port designation (000: Pulse output 0; 010: Pulse output 1) Frequency scaling factor setting Frequency scaling factor Register the frequency scaling factor to be set. #0001 to #1000 (4 digits BCD): 1 to 1,000%
Note When using SYNC() to specify a frequency scaling factor, be careful to keep the pulse output frequency below 10 kHz. Change Frequency Scaling Factor This function changes the frequency scaling factor during synchronized control (during pulse output) by specifying the bits for pulse outputs (01000, 01001) and the frequency scaling factor (1% to 1,000%) and executing SYNC(). Stop Synchronized Control This function stops the pulse outputs.
(@)INI(61) 000 005 000
Port specifier (000: High-speed counter) Control designation (005: Stop synchronized control) Fixed: 000
Note The pulse output can also be stopped by switching the PC to PROGRAM mode. Read Input Frequency This function reads the input frequency PV. Using an Instruction
(@)PRV(62) 000 000 D
Fixed: 000 Control designation (000: Read high-speed counter input frequency) Beginning word for storing input frequency PV
D D+1
Using Data Areas As shown in the following illustration, the input frequency is stored in words 248 and 249.
Word 248 Word 249 Input frequency PV (Rightmost) Input frequency PV (Leftmost)
141
Section
2-7
Words 248 and 249 are refreshed with every scan, so there may be a discrepancy from the exact PV at any given time. When the PV is read by executing PRV(62), words 248 and 249 are refreshed with the same timing. Read Synchronized Control Status This function reads the synchronized control status. Using an Instruction
(@)PRV(62) 000 001 D
Port specifier (000: Pulse output 0; 010: Pulse output 1) Control designation (001: Read synchronized control status) Beginning word for storing synchronized control status
Using Data Areas As shown in the following illustration, the status of pulse output 0 is stored in AR 1115, and the status of pulse output 1 is stored in AR 1215.
AR 1115 and AR 1215 are refreshed once each cycle, so there may be a discrepancy from the exact PV at any given time. When the PV is read by executing PRV(62), AR 1112 and AR 1212 are refreshed immediately.
142
Synchronized Pulse Control (CPM2A/CPM2C Only) Relationship Between Status and Operation
Frequency
Section
2-7
Application Example
Explanation In this example, when the execution condition (00005) turns ON, synchronized pulse control is started and pulses are output from output 01000 (pulse output 0) according to the pulses input by the high-speed counter. At this time, the frequency scaling factor can be changed by means of analog control 0. When the execution condition (00005) turns OFF, synchronized pulse control is stopped. Wiring Wire the CPM2A as shown in the following illustration.
Orange White Black Blue
Rotary encoder
Brown
Motor driver
Wire the CPM2C as shown in the following illustration. In this case, a CPU Unit with sinking transistor outputs is used.
143
Section
2-7
Note The following examples are for Fujitsu-compatible connectors. I/O bit addresses and connector pin numbers depend on the models. Refer to the CPM2C Operation Manual (W356) or the CPM2C-S Operation Manual (W377) for details.
Input connector
Output connector
Motor Driver
Blue
Note For details regarding motor driver wiring to outputs and rotary encoder wiring to inputs, refer to the CPM2A Operation Manual (W352)/CPM2C (W356) Operation Manual CPM2C-S Operation Manual (W377). PC Setup
15 DM 6642 0 2 0 0 0: Differential phase input 02: Use as pulse synchronization output. 0
Sets DM 0000 to 1 when analog control 0 is set to 0. MOV(21) (The analog controls are built into the CPM2A PCs, but not CPM2C PCs.)
SYNC()
SYNCHRONIZED PULSE CONTROL execution HIgh-speed counter Pulse output port 0 Beginning word of frequency scaling factor Stops synchronized pulse control.
INI(61)
144
Section
2-7
Detects OFF to ON transition in execution condition. Executes synchronized pulse control. High-speed counter Pulse output 0 First word containing frequency factor Stops synchronized pulse control.
END (01)
145
Section
2-8
2-8
Delay Pulse output Maximum delay (ms) = One period of the current pulse output 2 + 10 + instruction execution time
Frequency Error
There will be an error between the frequency of the output pulse and the set frequency of less than 1% due to internal processing error.
The following diagram shows the delay that will occur between starting synchronized pulse control and the start of actual pulse output.
There will be a delay before a change in the frequency during pulse output is actually applied to the output when performing synchronized pulse control, as shown below.
Delay
Pulse input Pulse output Maximum delay (ms) = One period of the current pulse output 2 + 10
The following diagram shows the delay that will occur between stopping synchronized pulse control (0 Hz) and the end of actual pulse output during synchronized pulse control.
Delay
Pulse input Pulse output Maximum delay (ms) = Setting in DM 6642 (see below) + One period of the current pulse output B 2 + 10
Delay
146
Section 2-11
There will be an error between the frequencies of the input pulse and output pulse, as described below. The error consists of error in the input pulse frequency measurement and error in the output pulse frequency. Input Pulse Frequency Measurement Error The error in measuring the frequency of the input pulse depends on the setting in DM 6642, as shown below. If a multiplication factor is specified for synchronized pulse control, the error given in the table must also be multiplied by the same factor.
Setting of DM 6642 bits 08 to 15 02 03 04 Frequency range 10 to 500 Hz 20 Hz to 1 kHz 300 Hz to 20 kHz 1 Hz 1 Hz 10 Hz Error
Output Pulse Frequency Error There will be an error between the frequency of the output pulse and the set frequency of less than 1% due to internal processing error. Example DM 6642 bits 08 to 15: 4 (frequency range: 300 Hz to 20 kHz) Multiplication factor: 300% Input frequency: 1 kHz (error: 0%) If synchronized pulse control is performed under the above conditions, there will be an error of 10 Hz in measuring the frequency range of the input pulse. The input frequency will thus be 990 to 1010 Hz. The multiplication factor of 300%, however, would make this 2970 to 3030 Hz. There would also be an error of 1% in the frequency of the output pulse, so the output would be in the range 2940 to 3060 Hz.
2-9
147
Section 2-12
The communications mode and maximum number of nodes are set in the PC Setup, as shown in the following table.
Word Bit(s) DM 6603 00 to 03 Function Maximum number of CompoBus/S nodes 0: 32 nodes 1: 16 nodes CompoBus/S communications mode 0: High-speed communications 1: Long-distance communications Not used. Setting 0 or 1
04 to 07
0 or 1
08 to 15
00
Note When changes are made to these settings, always turn the power off and on again to make the new setting effective. Slave Interrupts Input bits in IR 000 to IR 007 and output bits in IR 010 to IR 017 are used as interrupts for CompoBus/S I/O Terminals. The CompoBus/S I/O Terminal interrupts (IN 0 to 15 and OUT 0 to 15) are allocated as indicated in the following table. IN0 to IN15 are the node addresses for the Input Terminals and OUT0 to OUT15 are the node addresses for the Output Terminals.
Word Input p IR 000 IR 001 IR 002 IR 003 IR 004 IR 005 IR 006 IR 007 IR 010 IR 011 IR 012 IR 013 IR 014 IR 015 IR 016 IR 017 15 14 13 12 11 10 9 IN1 IN3 IN5 IN7 IN9 IN11 IN13 IN15 OUT1 OUT3 OUT5 OUT7 OUT9 OUT11 OUT13 OUT15 Bit 8 7 6 5 4 3 2 IN0 IN2 IN4 IN6 IN8 IN10 IN12 IN14 OUT0 OUT2 OUT4 OUT6 OUT8 OUT10 OUT12 OUT14 1 0
Output p
Note
1. When the maximum number of CompoBus/S nodes is set to 16, IN8 to IN15 can be used as work bits. 2. CompoBus/S Terminals with less than 8 points are allocated bit addresses from either 0 or 8.
148
Section 2-12
3. CompoBus/S Terminals with 16 points can be set for only even number addresses. 4. Analog Terminals can be set for only even number addresses. Status Flags The communications status between CompoBus/S terminals is output through AR04 to AR07 Slave Add Flags and Slave Communications Error Flags.
Lower Bits: Slave Add Flags 7 OUT 7 IN7 OUT 15 IN15 6 OUT 6 IN6 OUT 14 IN14 5 OUT 5 IN5 OUT 13 IN13 4 OUT 4 IN4 OUT 12 IN12 3 OUT 3 IN3 OUT 11 IN11 2 OUT 2 IN2 OUT 10 IN10 1 OUT 1 IN1 OUT 9 IN9 0 OUT 0 IN0 OUT 8 IN8
Uppermost bits: Slave Communications Error Flags 15 OUT 7 IN7 OUT 15 IN15 14 OUT 6 IN6 OUT 14 IN14 13 OUT 5 IN5 OUT 13 IN13 12 OUT 4 IN4 OUT 12 IN12 11 OUT 3 IN3 OUT 11 IN11 10 OUT 2 IN2 OUT 10 IN10 9 OUT 1 IN1 OUT 9 IN9 8 OUT 0 IN0 OUT 8 IN8
Note
1. IN0 to IN15 are the input terminals and OUT0 to OUT15 are the output terminals. 2. When the maximum number of CompoBus/S units is set to 16, IN8 to IN15 and OUT8 to OUT15 cannot be used. 3. The Slave Add Flag turns ON when a slave joins the communications. When the power to the CPU Unit is turned OFF and ON again all bits will turn OFF. 4. The Slave Communications Error Flag turns ON when a slave participating in the network is separated from the network. The bit will turn OFF when the slave re-enters the network. 5. For the SRM1, an error will not occur even if the same node address is allocated to more than one slave. Errors will also not occur when communications go down or communications errors, such as broken lines, occur. Set all node addresses very carefully and confirm slave operation by including a section of ladder program using the Status Flags. An example is shown below. Example
Disconnection (2)
149
Section 2-13
If the addresses for Slave 1 and Slave 3 are the same, the Master will not be able to read input from Slave 3. If a communications error is generated, the status of IR 00100 will be the same as before the error and so the change in the status of the actual input will not be detected.
00100
00000
02800 20000
00100
02900 20100
150
Section 2-13
The storage words are refreshed once with every CPU Unit cycle.
CPM1 The analog setting for control 0 is in SR 250. The analog setting for control 1 is in SR 251.
CPM1A/CPM2A
The analog setting for control 0 is in SR 250. The analog setting for control 1 is in SR 251.
Note The above diagram shows the CPM2A, but the settings are the same for the CPM1A. ! Caution The analog setting may change with changing temperatures. Do not use the analog adjustment controls for applications that require a precise, fixed setting.
151
Section 2-13
Connect a Programming Device such as a Programming Console, and check the values stored in SR 250 and SR 251.
Read the values in SR 250 and SR 251 with the ladder diagram program.
Analog control 0
Analog control 1
SR 251 SR 250
Analog control 1 set value (SV) Analog control 0 set value (SV)
Use a Phillips screwdriver to adjust the analog controls. The set values can be checked by connecting a Programming Device such as a Programming Console and reading the values stored in SR 250 and SR 251.
Analog control 0 Analog control 1
The following table shows the words and bits where the analog settings are stored.
Word SR 250 SR 251 Bit 00 to 15 00 to 15 Name Analog control 0 SV storage area Analog control 1 SV storage area Value 0000 to 0200 (BCD)
In the following example program, the analog control SV (0000 to 0200 BCD) stored in SR 250 is set as a timer SV. The timers set range is 0.0 s to 20.0 s.
Start bit Specifies SR 250 for the timer SV.
152
Quick-response Inputs
Section 2-14
CPU Unit 10-point CPU Units 20-, 30-, 40-point CPU Units
The input bits in the above table can be set as quick-response inputs in DM 6628, as shown in the following table.
Word DM 6628 Settings 0: Normal input 1: Interrupt input 2: Quick response input Quick-response (Default tti (D f lt setting: 0)
Bit 15 DM 6628
Setting for input 00006: Set to 2 Setting for input 00005: Set to 2 Setting for input 00004: Set to 2 Setting for input 00003: Set to 2
Mask/unmask input interrupts. Unmasks 00003 (interrupt input 0), masks others.
153
Quick-response Inputs
Section 2-14
Shared processing
Calculation processing
I/O refresh
Shared processing
Calculation processing
I/O refresh
00003 1 cycle
Input number (See note.) 00003 00004 00005 00006 (See note 2.)
Note
1. Input numbers 00003 to 00006 can be used as interrupt inputs, 2-kHz highspeed counter inputs, or quick-response inputs. If they are not used for any of these purposes, then they can be used as ordinary inputs. 2. Input number 00006 does not exist in CPM2C CPU Units with 10 I/O points. The following table shows the relationships between quick-response inputs and the CPM2A/CPM2Cs other functions.
Function Synchronized pulse control Interrupt inputs Interval timer interrupts High-speed counters Interrupt inputs (counter mode) Pulse outputs Quick-response inputs Input time constant Clock Interval timer interrupts Can be used simultaneously. See note 1. Can be used simultaneously. Can be used simultaneously. See note 2. Can be used simultaneously. See note 3. See note 4. Can be used simultaneously.
Note
1. Quick-response inputs utilize the interrupt input function, so the same input number from 00003 to 00006 cannot be assigned for both a quick-response input and an interrupt input in the PC Setup. 2. A quick-response input and an interrupt in counter mode cannot be assigned the same input number in the PC Setup. 3. The input numbers allocated for quick-response inputs are 00003 to 00006. These inputs can be set and operated as quick-response inputs. 4. Input time constants are disabled for all inputs that are set as quick-response inputs.
154
Section 2-14
Quick-response inputs
Quick-response input 0
Quick response
Quick-response input 1
Quick-response input 2
Quick-response input 3
PC Setup DM 6628
155
Quick-response Inputs
Section 2-14
Wire the CPM2Cs inputs as shown in the following diagram. Note The following examples are for Fujitsu-compatible connectors. Input bit addresses and connector pin numbers depend on the models. Refer to the CPM2C Operation Manual (W356) or the CPM2C-S Operation Manual (W377) for details. CPU Units with 10 I/O Points
Input terminal
Input connector
00006: Quick-response input 3* 00005: Quick-response input 2* 00004: Quick-response input 1 00003: Quick-response input 0
PC Setup
To use quick-response inputs with the CPM2A or CPM2C, make the following settings in the System Setup Area (DM 6628) from a Programming Device.
Word DM 6628 Bits 00 to 03 04 to 07 08 to 11 12 to 15 Interrupt setting for input number 3 Interrupt setting for input number 4 Interrupt setting for input number 5* Interrupt setting for input number 6* Function 0: Ordinary input 1: Interrupt input (interrupt input mode or counter mode) 2: Quick-response input Setting 2
156
Macro Function
Section 2-15
Note *Input numbers 00005 and 00006 does not exist in CPM2C CPU Units with 10 I/O points. The settings will go into effect when the mode is changed (from PROGRAM to MONITOR/RUN) or when the power supply is turned ON to the PC.
When MCRO(99) is executed, operation will proceed as follows: 1, 2, 3... 1. The contents of the four consecutive words beginning with the first input word will be transferred to SR 232 through SR 235. 2. The specified subroutine will be executed until RET(93) (Subroutine Return) is executed. 3. The contents of SR 236 through SR 239 (results of the subroutine execution) will be transferred to the four consecutive words beginning with the first output word. 4. MCRO(99) will then be finished. When MCRO(99) is executed, the same instruction pattern can be used as needed simply by changing the first input word or the first output word. The following restrictions apply when the macro function is used. The only words that can be used for each execution of the macro are the four consecutive words beginning with the first input word number (for input) and the four consecutive words beginning with the first output word (for output). The specified inputs and outputs must correctly correspond to the words used in the subroutine. Even when the direct output method is used for outputs,subroutine results will be actually reflected in the specified output words only when the subroutine has been completed (step 3 above). Note SR 232 through SR 239 can be used as work bits when MCRO(99) is not used. The first input word and the first output word can be specified not with I/O bits, but also with other bits (such as HR bits, work bits, etc.) or with DM words. Subroutines called by MCRO(99) are defined by SBN(92) and RET(93), just as are ordinary subroutines.
157
Section 2-16
20000
000 200
00001
00002 20001
00200
20501
20500
00201
005 210
00500
21001
21000
00501
SBN(92)
030
01000
22001
23600 23600
22000
00101
00102 22001
23201
23202 23201
RET(93)
158
Differential Monitor
Section 2-17
159
Section 2-18
Note
1. Set the PC model to CQM1 when setting the expansion instructions for the SRM1(-V2) or CPM2A/CPM2C from the SSS. 2. The PC Setup must be set for user-defined expansion instruction function codes in order for function codes to be assigned. Set bits 08 to 11 of DM 6602 to 1.
160
Section 2-18
161
Section 2-18
Note *SCL(66), NEG(), PID(), and ZCP () are supported by the SRM1-C0j-V2 CPUs only.
162
Section 2-19
8 7
0 2 digits BCD each. (Only the last 2 digits of the year are given.) 00 to 06: Sunday to Saturday
AR 2115 Clock Set Bit AR 2114 Clock Stop Bit AR 2113 30-Second Adjustment Bit
163
3-2
3-3 3-4
165
Section
3-1
3-1
Note The CPM1-30CDR-j-V1 is the only CPM1 CPU Unit to which 3 Expansion Units or Expansion I/O Units can be connected. Only one Expansion Unit or Expansion I/O Unit can be connected to models without the V1 suffix. Analog Units cannot be connected to 10-point or 20-point CPM1A CPU Units. You must use a 30-point or 40-point CPU Unit to connect to the CPM1A.
166
1 analog output
2 analog inputs
Section
Current I/O
3-1
Max. external output current Allowable external output load resistance Resolution Accuracy Set data Conversion time Isolation method
2 0 to 10 V/1 to 5 V 4 to 20 mA 15 V 30 mA 1 M min. 250 rated current 1/256 1.0% full scale 8-bit binary 1 0 to 10 V or 4 to 20 mA 10 to 10 V 5 mA ----350 1/256 (1/512 when the output signal range is 10 to 10 V) 1.0% of full scale 8-bit signed binary 10 ms max. per Unit (See note 2.) Photocoupler isolation between I/O terminals and PC signals. No isolation between analog I/O signals.
Note
1. With analog outputs it is possible to use both voltage outputs and current outputs at the same time. In this case however, the total output current must not exceed 21 mA. 2. The conversion time is the total time for 2 analog inputs and 1 analog output.
Part Names
Expansion connector
Connected to analog I/O devices. Connected to the CPU Unit or previous Expansion Unit. The cable is provided with the Unit and cannot be removed.
! Caution
Do not touch the cables during operation. Static electricity may cause operating errors.
Expansion Connector
167
Section
3-1
1V
3V
Input signal
Input signal
Input signal
Set value
Set value
4 to 20 mA outputs
0 to 10 V output
Set value
168
Section
3-1
Write the range code. Create a ladder program Analog input: Analog output: Read converted data. Write set value.
Analog Inputs
CPU Unit Analog I/O Unit
Ladder program
Word (n + 1)
Range code
Analog input 1 conversion value Analog input 2 conversion value
Word (m + 1) Word (m + 2)
Analog devices
Temperature sensor
Where m is the last input word and n is the last output word allocated to the CPU Unit, or previous Expansion Unit or Expansion I/O Unit.
169
Section
3-1
Range code
Analog output set value
Analog devices Where n is the last output word allocated to the CPU Unit, or previous Expansion Unit or Expansion I/O Unit.
Adjustment equipment Servo Controller Variable speed device
Recorder Other
Note Word (n + 1) can be used for either the range code or the analog output set value.
The I/O signal range is set by wiring the I/O terminal and by writing the range code to the Analog I/O Units output word.
I/O Terminal Arrangement
Note When using current inputs, short terminal V IN1 with I IN1 and terminal V IN2 with I IN2.
Voltage output Current output Output common Voltage input 1 Current input 1 Input common 1 Voltage input 2 Current input 2 Input common 2
Range Code The range code must be set for the Analog I/O Unit to convert data. The 8 range code settings provide 8 combinations of signal ranges for the analog inputs and analog output, as shown in the following table.
170
Section
3-1
Write the range code to the Analog I/O Units output word (n + 1) in the first cycle of program execution.
SR 25315 First Cycle Flag ON for 1 cycle
(21)
1 to 5 V/4 to 20 mA 0 to 10 V 0 to 10 V/4 to 20 mA
The Analog I/O Unit will not start converting analog I/O values until the range code has been written. Once the range code has been set, it is not possible to change the setting while power is being supplied to the CPU Unit. To change the I/O range, turn the CPU Unit OFF then ON again. Note If a range code other than those specified in the above table is written to n+1, the range code will not be received by the Analog I/O Unit and analog I/O conversion will not start. Analog I/O Unit Connection This section describes how to connect an Analog I/O Unit to the CPU Unit. A maximum of 3 Expansion Units or Expansion I/O Units, including Analog I/O Units, can be connected to one PC. When the Analog I/O Unit is used in combination with other Expansion Units or Expansion I/O Units, there are no restrictions on the connection order.
CPM1/CPM1A/CPM2A CPU Unit Analog I/O Unit
I/O Allocation I/O is allocated for the Analog I/O Unit in the same way as other Expansion Units or Expansion I/O Units starting from the next word following the last allocated word on the CPU Unit, or previous Expansion Unit or Expansion I/O Unit. When m is the last allocated input word and n the last allocated output word on the
171
Section
3-1
CPU Unit, or previous Expansion Unit or Expansion I/O Unit, the allocation will be as follows:
Analog I/O Unit
(m + 1) (m + 2) 2 analog inputs 1 analog output (n + 1)
For example, in the following diagram an Analog I/O Unit is connected to a CPU Unit with 30 I/O points.
Input address IR 000 IR 001 30-point CPU Unit Output address IR 010 IR 011 IR 002 IR 003 Analog I/O Unit IR 012
250
10 k 250
10 k
Current Outputs
Analog I/O Unit 2-core shielded twisted-pair cable
172
Section
3-1
For analog outputs it is possible to use both voltage outputs and current outputs at the same time, but the total current output must not exceed 21 mA. Note 1. Use 2-core shielded twisted-pair cables. 2. Wire away from power lines (AC power supply wires, power lines, etc.) 3. When an input is not being used, short V IN and I IN to the COM terminal. 4. Use crimp terminals. (Tighten terminals to a torque of 0.5 Nm.) 5. When using current inputs, short V IN to I IN. 6. When there is noise in the power supply line, install a noise filter on the input section and the Power Supply Unit. Ladder Program Specifying the Range Code Specify the I/O signal range by writing the range code to the Analog I/O Units output word from the ladder program in the first cycle of program execution. The Analog I/O Unit will start to convert analog I/O values once the range code has been specified. (Refer to page 170.) Write the range code to the Analog I/O Units output word in the first cycle of operation; the Analog I/O Units output word is n+1 when n is the last word allocated to the CPU Unit, or previous Expansion Unit or Expansion I/O Unit in the configuration. Reading Converted Analog Input Values A ladder program can be used to read the memory area where the converted values are stored. Values are output to the next two words (m + 1, m + 2) following the last input word (m) allocated to the CPU Unit, or previous Expansion Unit or Expansion I/O Unit.
(m + 1)
(m + 2)
Note The Open-circuit Detection Flag is turned ON when the input signal range is set to 1 to 5 V or 4 to 20 mA and the input signal falls below 1 V or 4 mA. (Open circuits are not detected when the input signal range is set to 0 to 10 V.)
173
Section
3-1
Writing Analog Output Set Values A ladder program can be used to write data to the output word where the set value is stored. The output word will be n+1 when n is the last output word allocated to the CPU Unit, or previous Expansion Unit or Expansion I/O Unit.
(n + 1)
1, 2, 3...
1. The set value range is 0000 to 00FF when the output signal range is 0 to 10 V/4 to 20 mA. 2. The set value range is divided into two parts: 8000 to 80FF (10 to 0 V) and 0000 to 00FF (0 to 10 V) when the output signal range is 10 to 10 V. 3. If FFjj is input, 0 V/4 mA will be output. 4. If an output value is specified, the following bits will be ignored. Output range of 10 to 10 V: Bits 08 to 14 Output range of 0 to 10 V/4 to 20 mA: Bits 08 to 15 Startup Operation After power is turned ON, it will require two cycle times plus approx. 100 ms before the first data is converted. The following instructions can be placed at the beginning of the program to delay reading converted data from analog inputs until conversion is actually possible.
Note Analog input data will be 0000 until initial processing has been completed. Analog output data will be 0 V or 0 mA until the range code has been written. After the range code has been written, the analog output data will be 0 V or 4 mA if the range is 0 to 10 V, 10 to 10 V, or 4 to 20 mA.
TIM 000 will start as soon as power turns ON. After 0.2 to 0.3 s (200 to 300 ms), the Completion Flag for TIM 000 will turn ON, and the converted data from analog input will be read from IR 001 and stored in DM 0000.
Handling Unit Errors If an error occurs in an Analog I/O Unit, the Error Flags in AR 0200 to AR 0204 will be turned ON. The addresses of the Error Flags are in the order that the Expansion Units and Expansion I/O Units are connected in the PC, with AR 0200 used for the Expansion Unit or Expansion I/O Unit closest to the CPU Unit. Use these flags in the program when it is necessary to detect errors. When an error occurs in the Analog I/O Unit, analog input data will be 0000 and 0 V or 4 mA will be output as the analog output.
174
Section
3-1
011
TIM000
Execution condition
MOV (21)
#0003
001 DM0000
TIM000
Execution condition
00215
01000
TIM000
Execution condition
MOV (21) 002
TIM000
Execution condition
MOV (21)
DM0001
DM0010 011
The content of DM 0010 is written to the output word as the analog output set value.
Example
Analog Input Program Example Analog I/O Unit Connection In this example, an Analog I/O Unit is connected to a CPU Unit with 30 I/O points. I/O words are allocated to the Analog I/O Unit beginning with the next word address following the last words allocated to the CPU Unit.
Input words IR 000 IR 001 CPU Unit with 30 I/O points Output words IR 010 IR 011 IR 002 IR 003 Analog I/O Unit IR 012
175
Section
3-1
Analog I/O Settings Input 1 signal range: Input 2 signal range: Output signal range: Range Code Setting:
0 to 10 V 4 to 20 mA 0 to 10 V FF04
Program
25135 (First Cycle ON Flag)
MOV (21) #FF04
012
TIM000
Execution condition
MOV (21)
#0003
002 DM0000
TIM000
Execution condition
MOV (21) 003
TIM000
Execution condition
MOV (21)
DM0001
DM0010 012
The content of DM0010 is written to the output word as the analog output set value.
176
Section
3-1
1 analog output
2 analog inputs
A maximum of 5 Expansion Units or Expansion I/O Units, including up to 4 CPM2C-MAD11 Analog I/O Units, can be connected to a CPM2C (A maximum of 3 Units can be connected to the CPM2C-S). One Analog I/O Unit allows 2 analog inputs and 1 analog output. With the maximum of 4 Analog I/O Units connected, 8 analog inputs and 4 analog outputs are possible.
CPM2C CPU Unit
Two analog inputs and one analog output for each Unit
The analog input range can be set to 0 to 5 VDC, 1 to 5 VDC, 0 to 10 VDC, 10 to 10 VDC, 0 to 20 mA, or 4 to 20 mA. The inputs have a resolution of 1/6000. An open-circuit detection function can be used with the 1 to 5 VDC and 4 to 20 mA settings. The analog output range can be set to 1 to 5 VDC, 0 to 10 VDC, 10 to 10 VDC, 0 to 20 mA, or 4 to 20 mA. The outputs have a resolution of 1/6000.
177
Section
Current I/O 0 to 20 mA or 4 to 20 mA 30 mA 250 0.4% full scale 0.8% full scale
3-1
Averaging function Open-circuit detection function Number of outputs Output signal range Allowable external output load resistance External output impedance Resolution Overall accuracy y 25C 0 to 55C Set data (D/A conversion)
Full scale for 10 to 10 V: F448 to 0BB8 Hex Full scale for other ranges: 0000 to 1770 Hex Supported (Settable for individual inputs via DIP switch) Supported 1 output (1 word allocated) 1 to 5 VDC, 0 to 10 VDC, or 0 to 20 mA or 4 to 20 mA 10 to 10 VDC, 1 k min. 600 max. 0.5 max. 1/6000 (full scale) 0.4% full scale 0.8% full scale 16-bit binary (4-digit hexadecimal) ---
Full scale for 10 to 10 V: F448 to 0BB8 Hex Full scale for other ranges: 0000 to 1770 Hex 2 ms/point (6 ms/all points) Photocoupler isolation between analog I/O terminals and internal circuits. No isolation between analog I/O signals.
DIP switch
Expansion connector
Connected to analog I/O devices. Connected to the CPU Unit or previous Expansion Unit. The cable is provided with the Unit and cannot be removed. Do not touch the cables during operation. Static electricity may cause operating errors.
Expansion Connector
178
Section
3-1
DIP switch
Connected to analog I/O devices. Used to specify current or voltage inputs and to enable or disable averaging.
Average processing for analog input 0 (OFF: Average processing not performed; ON: Average processing performed) Average processing for analog input 1 (OFF: Average processing not performed; ON: Average processing performed) Input type for analog input 0 (OFF: Voltage input; ON: Current input) Input type for analog input 1 (OFF: Voltage input; ON: Current input)
2 3 4
! Caution
Do not touch the DIP switch during operation. Static electricity may cause operating errors. Connected to the expansion I/O output connector on the CPU Unit or previous Expansion (I/O) Unit. Connected to the expansion I/O input connector on the next Expansion (I/O) Unit. 1. A maximum of 5 Expansion (I/O) Units can be connected to the CPU Unit and the total number of allocated words must be 10 maximum for inputs and 10 maximum for outputs.
179
Section
3-1
2. Use the connector cover provided with the CPU Unit to protect the output connector when it is not used. ! Caution Do not touch the cables during operation. Static electricity may cause operating errors.
Lock Levers
11 V 10 V
0000 (0) 0V 10 V 11 V
0 to 10 V The 0- to 10-V range corresponds to the hexadecimal values 0000 to 1770 (0 to 6000). The entire data range is FED4 to 189C (300 to 6300). A negative voltage is expressed as a twos complement.
Converted Data Hexadecimal (Decimal) 189C (6300) 1770 (6000)
180
Section
3-1
0 to 5 V The 0- to 5-V range corresponds to the hexadecimal values 0000 to 1770 (0 to 6000). The entire data range is FED4 to 189C (300 to 6300). A negative voltage is expressed as a twos complement.
Converted Data Hexadecimal (Decimal) 189C (6300) 1770 (6000)
1 to 5 V The 1- to 5-V range corresponds to the hexadecimal values 0000 to 1770 (0 to 6000). The entire data range is FED4 to 189C (300 to 6300). Inputs between 0.8 and 1 V are expressed as twos complements. If the input falls below 0.8 V, open-circuit detection will activate and converted data will be 8000.
Converted Data Hexadecimal (Decimal) 189C (6300) 1770 (6000)
0 to 20 mA The 0- to 20-mA range corresponds to the hexadecimal values 0000 to 1770 (0 to 6000). The entire data range is FED4 to 189C (300 to 6300). A negative voltage is expressed as a twos complement.
Converted Data Hexadecimal (Decimal) 189C (6300) 1770 (6000)
0000 (0)
1 mA FED4 (300) 0 mA 20 mA 21 mA
181
Section
3-1
4 to 20 mA The 4- to 20-mA range corresponds to the hexadecimal values 0000 to 1770 (0 to 6000). The entire data range is FED4 to 189C (300 to 6300). Inputs between 3.2 and 4 mA are expressed as twos complements. If the input falls below 3.2 mA, open-circuit detection will activate and converted data will be 8000.
Converted Data Hexadecimal (Decimal) 189C (6300) 1770 (6000)
The Analog I/O Unit converts the digital output data to analog values. The analog values depend on the output signal ranges, as shown in the following diagrams. 10 to 10 V The hexadecimal values F448 to 0BB8 (3000 to 3000) correspond to an analog voltage range of 10 to 10 V. The entire output range is 11 to 11 V. Specify a negative voltage as a twos complement.
11 V 10 V
10 V 11 V
0 to 10 V The hexadecimal values 0000 to 1770 (0 to 6000) correspond to an analog voltage range of 0 to 10 V. The entire output range is 0.5 to 10.5 V. Specify a negative voltage as a twos complement.
10.5 V 10 V
182
Section
3-1
1 to 5 V The hexadecimal values 0000 to 1770 (0 to 6000) correspond to an analog voltage range of 1 to 5 V. The entire output range is 0.8 to 5.2 V.
5.2 V 5V
1V 0.8 V 0V 8000 FED4 (300) 0000 (0) 1770 189C (6000) (6300) Conversion Data Hexadecimal 7FFF (Decimal)
0 to 20 mA The hexadecimal values 0000 to 1770 (0 to 6000) correspond to an analog current range of 0 to 20 mA. The entire output range is 0 to 21 mA.
21 mA 20 mA
4 to 20 mA The hexadecimal values 0000 to 1770 (0 to 6000) correspond to an analog current range of 4 to 20 mA. The entire output range is 3.2 to 20.8 mA.
20.8 mA 20 mA
4 mA 3.2 mA 0 mA 8000 FED4 0000 (0) (300) 1770 189C (6000) (6300) Conversion Data Hexadecimal 7FFF (Decimal)
The averaging function can be enabled for inputs using the DIP switch. The averaging function stores the average (a moving average) of the last eight input values as the converted value. Use this function to smooth inputs that vary at a short interval. The open-circuit detection function is activated when the input range is set to 1 to 5 V and the voltage drops below 0.8 V, or when the input range is set to 4 to 20 mA and the current drops below 3.2 mA. When the open-circuit detection function is activated, the converted data will be set to 8000.
183
Section
3-1
The open-circuit detection function is enabled or cleared when data is converted. If the input returns to the convertible range, the open-circuit detection is cleared automatically and the output returns to the normal range.
Analog inputs: 0 to 5 VDC, 1 to 5 VDC, 0 to 10 VDC, 10 to 10 VDC, 0 to 20 mA, or 4 to 20 mA Analog output: 1 to 5 VDC, 0 to 10 VDC, 10 to 10 VDC, 0 to 20 mA, or 4 to 20 mA Set inputs as voltage or analog and set the averaging function.
Write the range code. Analog inputs: Read converted data. Analog output: Write set values.
Analog Inputs
CPU Unit Analog I/O Unit
Ladder program
Word (n + 1)
Range code
Analog input 0 converted value Analog input 1 converted value
Word (m + 1) Word (m + 2)
Analog devices Where m is the last input word and n is the last output word allocated to the CPU Unit, or previous Expansion Unit or Expansion I/O Unit.
Temperature sensor Pressure sensor Speed sensor Flow sensor Voltage/current meter Other
184
Section
3-1
Range code
Analog output set value
Analog devices Where n is the last output word allocated to the CPU Unit, or previous Expansion Unit or Expansion I/O Unit.
Adjustment equipment Servo Controller Variable speed device
Recorder Other
Note Word (n + 1) can be used for either the range code or the analog output set value.
This section describes how to connect an Analog I/O Unit to the CPU Unit. A maximum of 3 Expansion Units or Expansion I/O Units, including up to 3 Analog I/O Units, can be connected to one CPM2A or CPM1A PC. When the Analog I/O Unit is used in combination with other Expansion Units or Expansion I/O Units, there are no restrictions on the connection order.
CPM1A/CPM2A CPU Unit CPM1A-MAD11 Analog I/O Unit
I/O Allocation I/O is allocated for the Analog I/O Unit in the same way as other Expansion Units or Expansion I/O Units starting from the next word following the last allocated word on the CPU Unit or previous Expansion Unit or Expansion I/O Unit. When m is the last allocated input word and n the last allocated output word on the CPU Unit, or previous Expansion Unit or Expansion I/O Unit, the allocation will be as follows:
CPM1A-MAD11 Analog I/O Unit
Analog input 0: Word m+1 Analog input 1: Word m+2
32 inputs 16 outputs
185
Section
3-1
For example, in the following diagram an Analog I/O Unit is connected to a CPU Unit with 30 I/O points.
Inputs IR 000 IR 001 30-point CPU Unit IR 010 IR 011 IR 002 IR 003 CPM1A-MAD11 Analog I/O Unit IR 012
Outputs
This section describes how to connect an Analog I/O Unit to the CPU Unit. A maximum of 5 Expansion Units or Expansion I/O Units (a maximum of 3 Units for the CPM2C-S), including up to 3 (see note.) Analog I/O Units, can be connected to one CPM2C PC. When the Analog I/O Unit is used in combination with other Expansion Units or Expansion I/O Units, there are no restrictions on the connection order. Note When using the CPM2C-PA201, there is a limit to the number of CPM2C-MAD11 Units that can be connected. This limit ensures that the power consumption of the CPU Unit, Expansion Units, and Expansion I/O Units does not exceed the total power capacity of the service power supply from the Power Supply Unit (24 V 600 mA = 14.4 W). CPU Unit with 4-W power consumption: Connect no more than two CPM2CMAD11 Units CPU Unit with 3-W power consumption: Connect no more than three CPM2CMAD11 Units
CPU Unit CPM2C-MAD11 Analog I/O Units Expansion I/O Unit
I/O Allocation I/O is allocated for the Analog I/O Unit in the same way as other Expansion Units or Expansion I/O Units starting from the next word following the last allocated word on the CPU Unit or previous Expansion Unit or Expansion I/O Unit. When m is the last allocated input word and n the last allocated output word on the CPU Unit, or previous Expansion Unit or Expansion I/O Unit, the allocation will be as follows:
CPM2C-MAD11 Analog I/O Unit
186
Section
3-1
For example, in the following diagram an Analog I/O Unit is connected to a CPU Unit with 20 I/O points.
CPU Unit CPM2C-MAD11 Analog I/O Unit
IR 010 IR 011
I/O signal ranges are set by writing a range code to the output word of the Analog I/O Unit. The range code must be set for the Analog I/O Unit to convert data. The range code settings provide the combinations of signal ranges for the analog inputs and analog output, as shown in the following table. Voltage/current selections for the CPM1A-MAD11 are made by connecting the appropriate terminals. Refer to page 188 for details. Voltage/current selections for the CPM2C-MAD11 are made using pins 3 and 4 on the DIP switch. refer to page 179 for details.
Range Analog input 0 code signal range 000 10 to 10 V 001 010 011 100 0 to 10 V 1 to 5 V or 4 to 20 mA 0 to 5 V or 0 to 20 mA --Analog input 1 signal range Analog output signal range 10 to 10 V 0 to 10 V 1 to 5 V 0 to 20 mA 4 to 20 mA
Note Be sure to write the correct terminals. Write the range codes to the Analog I/O Units output word (n + 1) in the first cycle of program execution.
n+1 15 8 7 1 0 0 0 0 0 0 6 5 4 3 2 1 0
Analog output
Analog input 1
Analog input 0
Example The following instructions set analog input 0 to 4 to 20 mA, analog input 1 to 0 to 10 V, and the analog output to 10 to 10 V.
SR 25315 (First Cycle Flag)
MOV (21) #800A 011
4 to 20 mA 0 to 10 V 10 to 10 V
The Analog I/O Unit will not start converting analog I/O values until the range code has been written. Until conversion starts, inputs will be 0000, and 0 V or 0 mA will be output. After the range code has been set, 0 V or 0 mA will be output for the 0 to 10-V, 10 to 10-V, or 0 to 20-mA ranges, and 1 V or 4 mA will be output for the 1 to 5-V and 4 to 20-mA ranges until a convertible value has been written to the output word.
187
Section
3-1
Once the range code has been set, it is not possible to change the setting while power is being supplied to the CPU Unit. To change the I/O range, turn the CPU Unit OFF then ON again. Wiring Analog I/O Devices CPM1A-MAD11 Internal Circuits
Analog Inputs Input 0 V IN Internal circuits
250 510 k
510 k
Internal circuits
I IN 0 COM 0 () Input 1 V IN 1
I IN 1 COM 1 () AG
Analog ground
I OUT
NC NC
NC
V IN0 NC
COM0 I IN1
AG
V OUT COM
I IN0
V IN0 COM1
Label V OUT I OUT COM V IN0 I IN0 COM0 V IN1 I IN1 COM1
Signal Voltage output Current output Output common Voltage input 0 Current input 0 Input common 0 Voltage input 1 Current input 1 Input common 1
Note For current inputs, short V IN0 to I IN0 and V IN1 to I IN1 Wiring for Analog Inputs
+ Analog device with voltage output V IN I IN COM Analog I/O Unit Analog device with current output + V IN I IN COM Analog I/O Unit
188
Section
3-1
Note
1. Use shielded twisted-pair cables, but do not connect the shield. 2. When an input is not being used, short the + and terminals. 3. Separate wiring from power lines (AC power supply lines, high-voltage lines, etc.) 4. When there is noise in the power supply line, install a noise filter on the input section and the Power Supply Unit. CPM2C-MAD11 Internal Circuits
Analog Outputs
Analog Inputs
510 k
V+ Output
Internal circuits
510 k
Input 1 1+ AG
I+ NC NC Analog ground
Analog ground
Analog Input Terminals IN Analog input 0 + Analog input 0 Analog input 1 + Analog input 1 Analog ground
Analog Output Terminals OUT Analog voltage output Output common Analog current output Not used Not used
0+ 0 1+ 1 AG
V+ I+ NC NC
V+
+ Analog
I+
+ Analog
189
Section
1. Use shielded twisted-pair cables, but do not connect the shield. 2. When an input is not being used, short the + and terminals.
3-1
3. Separate wiring from power lines (AC power supply lines, high-voltage lines, etc.) 4. When there is noise in the power supply line, install a noise filter on the input section and the Power Supply Unit. Reference Information Consider the following information on open input circuits when using voltage inputs. If the same power supply is used as shown in the following diagram and an open circuit occurs at point A or B, an unwanted current flow will occur as shown by the dotted lines in the diagram, creating a voltage at the other input of about 1/3 to 1/2. If the 1 to 5-V range is being used, the open-circuit detection function will not operate. Also, if there is an open circuit at C, the open-circuit detection function will not operate because the negative sides are the same.
24 VDC
For example, if analog input device 2 is outputting 5 V and the same power supply is being used as shown above, about 1/3, or 1.6 V, will be applied at the input for input device 1. To eliminate the above problem, either use separate power supplies, or install an isolator at each input. This problem will not occur for current inputs even if the same power supply is used. Note When power is supplied (when setting the range code), or when there is a power interruption, pulse-form analog output of up to 1 ms may be generated. If this causes problems with operation, take countermeasure such as those suggested below. Turn ON the power supply for the CPU Unit first, and then turn ON the power supply for the load after confirming correct operation.
190
Section
3-1
Turn OFF the power supply for the load before turning OFF the power supply for the CPU Unit. Ladder Program Specifying the Range Code Specify the I/O signal range by writing the range code to the Analog I/O Units output word from the ladder program in the first cycle of program execution. The Analog I/O Unit will start to convert analog I/O values once the range code has been specified and convertible values are provided. (Refer to page 170.) Write the range code to the Analog I/O Units output word in the first cycle of operation; the Analog I/O Units output word is n+1 when n is the last word allocated to the CPU Unit, or previous Expansion Unit or Expansion I/O Unit in the configuration. Reading Converted Analog Input Values The ladder program can be used to read the memory area where the converted values are stored. Values are output to the next two words (m + 1, m + 2) following the last input word (m) allocated to the CPU Unit or previous Expansion Unit or Expansion I/O Unit. Writing Analog Output Set Values The ladder program can be used to write data to the output word where the set value is stored. The output word will be n+1 when n is the last output word allocated to the CPU Unit, or previous Expansion Unit or Expansion I/O Unit. Startup Operation After power is turned ON, it will require two cycle times plus approx. 50 ms before the first data is converted. The following instructions can be placed at the beginning of the program to delay reading converted data from analog inputs until conversion is actually possible. Note Analog input data will be 0000 until initial processing has been completed. Analog output data will be 0 V or 0 mA until the range code has been written. After the range code has been written, the analog output data will be 0 V or 0 mA if the range is 0 to 10 V, 10 to 10 V, or 0 to 20 mA, or it will be 1 V or 4 mA if the range is 1 to 5 V or 4 to 20 mA.
SR 25315 (Always ON Flag)
TIM 005 #0002 T005 MOV (21) 001 DM0000
TIM 005 will start as soon as power turns ON. After 0.1 to 0.2 s (100 to 200 ms), the Completion Flag for TIM 005 will turn ON, and the converted data from analog input will be read from IR 001 and stored in DM 0000.
Handling Unit Errors If an error occurs in an Analog I/O Unit, the Error Flags in AR 0200 to AR 0204 for the CPM2C and AR 0200 to AR 0202 for the CPM1A/CPM2A will be turned ON. The addresses of the Error Flags are in the order that the Expansion Units and Expansion I/O Units are connected in the PC, with AR 0200 used for the Expansion Unit or Expansion I/O Unit closest to the CPU Unit. Use these flags in the program when it is necessary to detect errors. When an error occurs in the Analog I/O Unit, analog input data will be 0000 and 0 V or 0 mA will be output as the analog output. If a CPU error or an I/O bus error (fatal errors) occurs at the CPU Unit and the analog output is set to 1 to 5 V or 4 to 20 mA, 0 V or 0 mA will be output. For any other fatal errors at the CPU Unit, 1 V or 4 mA will be output.
191
Section
3-1
011
TIM005
Execution condition
MOV (21)
#0002
001
TIM005
Execution condition
CMP (20)
DM0000
002 #8000
25506(=)
01000
Open-circuit alarm
TIM005
Execution condition
MOV (21) 002
TIM005
Execution condition
MOV (21)
DM0001
DM0010 011
The content of DM 0010 is written to the output word as the analog output set value.
192
Section
3-2
3-2
Temperature inputs
Specifications
Item Temperature sensors CPM1A-TS001 Thermocouples Switchable between K and J, but same type must be used for all inputs. 2 4 2 3 4 1 CPM1A-TS002 CPM1A-TS101 CPM1A-TS102 Platinum resistance thermometer Switchable between Pt100 and JPt100, but same type must be used for all inputs. 2 4 2 3 4 1
Number of inputs Allocated input words Max. number of Units (See note 1.) Accuracy Conversion time Converted temperature data Isolation
(The larger of 0.5% of converted value or 2_C) 1 digit max. (See note 2.) 250 ms for 2 or 4 input points 16-bit binary data (4-digit hexadecimal)
Note
1. If only the CPM1A-TS001 and CPM1A-TS101 are connected, then up to 3 Units including Expansion I/O Units and other Expansion Units can be connected. If the CPM1A-TS002 or CPM1A-TS102 is connected, then only one other Expansion I/O Unit or Expansion Unit can be connected. The CPM1ATS001 or CPM1A-TS101 may be the other Unit, but another CPM1A-TS002 or CPM1A-TS102 cannot be connected.
193
Section
2. Accuracy for a K-type sensor at 100C or less is 4_C 1 digit max.
3-2
Specifications
Item Temperature sensors CPM2C-TS001 Thermocouples Switchable between K and J, but same type must be used for all inputs. Number of inputs Allocated input words Max. number of Units (See note 1.) Accuracy 2 2 4 (The larger of 0.5% of converted value or 2_C) 1 digit max. (See note.) 250 ms for 2 input points 4 (The larger of 0.5% of converted value or 1_C) 1 digit max. CPM2C-TS101 Platinum resistance thermometer Switchable between Pt100 and JPt100, but same type must be used for all inputs.
16-bit binary data (4-digit hexadecimal) Photocouplers between all temperature input signals
Note
1. Accuracy for a K-type sensor at 100C or less is 4_C 1 digit max. 2. The error deviation for temperatures in F is double that for C.
194
Section
3-2
Set the temperature unit, 2-decimal-place Mode if required, and set the temperature input range. Refer to 3-2-5 Setting Temperature Ranges.
Read temperature data stored in the input word. Refer to 3-2-7 Ladder Programming.
Temperature 2 inputs Sensor Units Expansion I/O Units Analog I/O Units CompoBus/S I/O Link Unit
Up to 3 Units can be connected. There are no co ec ed eeae o restrictions on the order in which Units are connected.
195
Section
3-2
Word Allocations The CPM1A-TS001 and CPM1A-TS101 are allocated two words each (one for each input point). No output words are allocated.
IR 000 IR 001
IR 010 IR 011
IR 012
None
None
Temperature Sensor Units with 4 Inputs (4 Words Allocated): CPM1A-TS002 and CPM1A-TS102
CPM1A or CPM2A CPU Unit (with 20, 30, 40, or 60 I/O points) CPM1A-20EDR1 CPM1A-TS002/TS102 Expansion I/O Unit Temperature Sensor Unit
4 inputs 2 inputs
Expansion I/O Units Analog I/O Units CompoBus/S I/O Link Unit
Up to 2 Units can be connected. There a e co ec ed e e are no restrictions on the order in which Units connected. are connected
Word Allocations The CPM1A-TS002 and CPM1A-TS102 are allocated four words each (one for each input point). No output words are allocated.
60-point CPU Unit IR 000 IR 001 IR 002 IR 010 IR 011 IR 012 20-point Expansion I/O Unit IR 003 CPM1A-TS002/102 Temperature Sensor Unit IR 004 IR 005 IR 006 IR 007
IR 013
None
196
Section
3-2
cluding the Temperature Sensor Units.) Up to three Units can be connected to the CPM2C-S. No matter how many Units are connected, however, no more than 0 input words and 10 output words can be allocated in one PC. There are no restrictions on the order in which Units can be connected.
Example CPM2C CPU Unit CPM2C-TS001/101 Temperature Sensor Units Expansion I/O Unit
Word Allocation Words are allocated to Temperature Sensor Units just like other Expansion I/O Units and Expansion Units: In the order in which the Units are connected. A CPM2C-TS001 or CPM2C-TS101 Temperature Sensor Unit will thus be allocated the next two input words after the Unit to which it is connected (CPU Unit or other Unit). No output words are allocated.
20-point CPU Unit CPM2C-TS001 Temperature Sensor Unit Inputs IR 001 IR 002 CPM2C-TS001 Temperature Sensor Unit Inputs IR 003 IR 004 CPM2C-TS101 Temperature Sensor Unit Inputs IR 005 IR 006 CPM2C-TS101 Temperature Sensor Unit Inputs IR 007 IR 008 CPM2C-24EDTC Expansion I/O Unit
Inputs IR 000
Inputs IR 009
Outputs IR 010
Outputs None
Outputs None
Outputs None
Outputs None
Outputs IR 011
197
Section
3-2
Cold junction compensator (TS001 only) DIP Switch Used to set the temperature unit and the number of decimal places used.
The DIP switch is used to set the temperature unit (C or F) and the number of decimal places used.
CPM1A-TSjjj CPM2C-TSjjj
ON ON ON F
SW1
C
0.01
1 2 1 or 0.1
SW1 1 2
Setting Temperature unit p Number of decimal places used p aces OFF ON OFF ON C F Normal (0 or 1 digit after the decimal point, depending on the input range) 2-decimal-place Mode (e.g., 0.01)
198
Section
3-2
1. Turn OFF the power supply before changing the temperature range setting. 2. Do not touch the DIP switch or rotary switches while power is turned ON. Static electricity may cause malfunctions. The rotary switch is used to set the temperature range. Set the temperature range according to the type of temperature sensor connected to the Unit. Temperature data will not be converted correctly if the temperature range does not match the sensor. Do not set the temperature range to any values other than those for which temperature ranges are given in the following table. An incorrect setting may cause operating errors.
Setting CPM1A-TS001/002 CPM2C-TS001 Input type 0 1 2 3 4 to F --J K Range Range (C) (F) 200 to 300 to 1,300 2,300 0.0 to 0.0 to 500.0 900.0 100 to 100 to 850 1,500 0.0 to 0.0 to 400.0 750.0 Setting not possible CPM1A-TS101/102 CPM2C-TS101 Input type Pt100 JPt100 ------Range Range (C) (F) 200.0 to 300.0 to 650.0 1,200.0 200.0 to 300.0 to 650.0 1,200.0 Setting not possible
! Caution
199
Section
3-2
Input 1
Temperature input 0
Temperature input 1
CPM1A-TS002 Either K or J thermocouples can be connected, but all four of the thermocouples must be of the same type and the same input range must be used for each.
Input 0 + Input 0 Input 1 + NC NC Input 2 + NC Input 3 + Input 3 NC
Input 1
Input 2
Temperature input 2
Temperature input 1
Temperature input 3
Note When using a Temperature Sensor Unit with a thermocouple input, observe the following precautions: Do not remove the cold junction compensator attached at the time of delivery. If the cold junction compensator is removed, the Unit will not be able to measure temperatures correctly. Each of the input circuits is calibrated with the cold junction compensator attached to the Unit. If the Unit is used with the cold junction compensator from other Units, the Unit will not be able to measure temperatures correctly. Do not touch the cold junction compensator. Doing so may result in incorrect temperature measurement.
200
Section
3-2
CPM1A-TS101 Either Pt100 or JPt100 platinum resistance thermometers can be connected, but both of the thermometers must be of the same type and the same input range must be used for each.
Input 0 A Input 0 B
Input 1 A
Input 1 B NC
NC NC
NC NC
NC NC
NC
Input 0 B
Input 1 B
Pt
Pt
Temperature input 0
Temperature input 1
CPM1A-TS102 Either Pt100 or JPt100 platinum resistance thermometers can be connected, but all four of the thermometers must be of the same type and the same input range must be used for each.
Input 0 A Input 0 B
Input 1 A
Input 1 B NC
NC
Input 2 A
Input 3 A
Input 3 B
Input 0 B
Input 1 B
Input 2 B
Input 2 B
Input 3 B
Pt
Pt
Pt
Pt
Temperature input 0
Temperature input 1
Temperature input 2
Temperature input 3
201
Section
3-2
CPM2C-TS001 (Thermocouples) Either K or J thermocouples can be connected, but both of the thermocouples must be of the same type and the same input range must be used for each.
0+ Temperature input 0 0 NC 1+ Temperature input 1 1 NC
Note When using a Temperature Sensor Unit with a thermocouple input, observe the following precautions: Do not touch the cold junction compensator. Doing so may result in incorrect temperature measurement. CPM2C-TS101 (Platinum Resistance Thermometers) Either Pt100 or JPt100 platinum resistance thermometers can be connected, but both of the thermometers must be of the same type and the same input range must be used for each.
0A Pt Temperature input 0 Pt Temperature input 1 0B 0B 1A 1B NC
CPM1A-TS002/TS102 m is the last word allocated to the CPU Unit, Expansion I/O Unit, or Expansion Unit connected immediately before the Temperature Sensor Unit.
Word m+1 m+2 m+3 m+4 Contents Converted temperature data from input 0 Converted temperature data from input 1 Converted temperature data from input 2 Converted temperature data from input 3
All Temperature Sensor Units Negative values are stored as 2s complements. Data for range codes that in-
202
Section
3-2
clude one digit after the decimal point are stored without the decimal point, i.e., 10 times the actual value is stored. Some examples are provided in the following table.
Input Unit: 1 Unit: 0.1 K or J K, J, Pt100 or JPt100 Data conversion examples 850 0352 Hex 200 FF38 Hex 10 500.0 5000 1388 Hex 20.0 200 FF38 Hex 200.0 2000 F830 Hex
If the input temperature exceeds the range that can be converted, the converted temperature data will be held at the maximum or minimum value in the range. If the input temperature exceeds the range by more than a specified amount, the open-circuit detection function will detect an open-circuit and the converted temperature data will be set to 7FFF. The open-circuit detection function will also operate if the cold junction compensator is faulty. The open-circuit detection function will be automatically cleared and normal input temperature conversion will begin automatically when the input temperature returns to the convertible range. Startup Operation After power is turned ON, it will require approximately 1 s before the first data is converted. The following instructions can be placed at the beginning of the program and then IR 02000 can be used to delay reading converted data until conversion is actually begun.
Note Input data will be 7FFE until actual conversion starts. Handling Unit Errors If an error occurs in an Expansion Unit, the Error Flags in AR 0200 to AR 0204 will be turned ON ( AR 0200 to AR 0202 for the CPM1A/CPM2A). Refer to page 572 for details. The addresses of the Error Flags are in order that the Expansion Units are connected in the PC, with AR 0200 used for the Expansion Unit closest to the CPU Unit. Use these flags in the program when it is necessary to detect errors. When an error occurs in a Temperature Sensor Unit, converted temperature data will be 7FFF. Note The status of AR 0200 to AR 0204 will not change for the open-circuit detection function. Programming Example 1 The following programming example shows how to convert the input data from 2 temperature sensor inputs to BCD and store the result in DM 0000 and DM 0001. The following system configuration is used.
203
Section
3-2
Outputs IR 010
Outputs None
Temperature unit setting: Two-decimal-place Mode: Input range setting: Temperature input 0 storage word: Temperature input 1 storage word:
204
Section
3-2
25506 02001
02000
Detects an open-circuit alarm or Unit error by checking converted temperature data for the error code 7FFF.
ON when an open-circuit alarm or Unit error has been detected for input 0.
Checks to see if the temperature data in IR 001 has exceeded 500.0C (1388 Hex without decimal point).
25505(>) 01001
25507(<) BCD (24) 001 DM0000 02001 Execution condition CMP (20) 002 #7FFF 25506(=) 01002
Converts the contents of IR 001 (temperature data for input 0) to BCD and stores the result in DM 0000.
Detects an open-circuit alarm or Unit error by checking converted temperature data for the error code 7FFF.
ON when an open-circuit alarm or Unit error has been detected for input 1.
Checks to see if the temperature data in IR 002 has exceeded 500.0C (1388 Hex without decimal point).
25505(>) 01003
Converts the contents of IR 002 (temperature data for input 1) to BCD and stores the result in DM 0001.
205
Section
3-2
The following programming example shows how to convert the data for temperature input 0 to BCD and store the result in DM 0000 and DM 0001. 0001 is stored in DM 0001 when the input data is a negative value. The following system configuration is used.
Temperature Sensor Unit Inputs IR 001 IR 002
Outputs IR 010
Outputs None
Temperature unit setting: Two-decimal-place Mode: Input range setting: Temperature input 0 storage word:
02000
02000
Detects an open-circuit alarm or Unit error by checking converted temperature data for the error code 7FFF.
25506(=) 01000
ON when an open-circuit alarm or Unit error has been detected for input 0.
25506(=)
When the input temperature data is non-negative, converts the contents of IR 001 (temperature data for input 0) to BCD and stores the result in DM 0000. Stores #0000 in DM 0001.
When the input temperature data is negative, converts the contents of IR 001 to the absolute value of the actual temperature and stores the result in DM 0000. Converts the contents of DM 0000 (absolute value of negative temperature data for input 0) to BCD and stores the result in DM 0000.
206
Section
3-2
25313 (Always ON Flag) CMP (20) 001 #7FFE Detects completion of initialization.
02000 Execution condition CMP (20) 001 #7FFF Detects an open-circuit alarm.
25506(=) SCL2 () 001 DM0010 DM0000 Parameter settings for data conversion: DM0010 DM0011 DM0012 25504(CY) MOV (21) #0000 DM0001 25504(CY) MOV (21) #0001 DM0001 When the converted value is negative, stores #0001 in DM 0001. When the converted value is non-negative, stores #0000 in DM 0001. #0000 #0001 #0001 Offset X (Hex) Y (BCD)
Operation
IR 001 163 162 161 160 DM 0001 0 0 0 1/0 Binary to BCD conversion
1: Negative, 0: Non-negative 0: If data non-negative, 0000 stored in DM 0001 1: If data negative, 0001 stored in DM 0001
207
Section
3-2
The structure of the data stored in memory is shown below. The value will be 100 times the actual temperature.
14
13
Open-circuit Flag 0: Normal 1: Error
12
Not used. Always 0
13
Open-circuit Flag 0: Normal 1: Error
12
Not used. Always 0
Leftmost/Rightmost Flag: Indicates whether the leftmost or rightmost 3 digits are provided. Temperature Unit Flag: Open-circuit Flag: Indicates whether the temperature is in C or F. Turns ON (1) when an open-circuit is detected. The temperature data will be 7FF FFF if this flag is ON.
208
Section
3-2
Some examples of the data stored for various temperature inputs are provided below. Example 1 Temperature: 1,130.25C 100: 113025 Temperature Data: 01B981 (hexadecimal for 113025)
Leftmost 3 Digits and Flags Flags Bits Data 15 14 13 12 0 0 0 0 x165 08 to 11 0 x164 04 to 07 1 x163 00 to 03 B Flags 0 0 1 B
Normal C Leftmost Rightmost 3 Digits and Flags Flags Bits Data 15 14 13 12 1 0 0 0 Normal C Rightmost x162 08 to 11 9 x161 04 to 07 8 x160 00 to 03 1
Temperature data
8 Flags
Temperature data
Example 2 Temperature: 100.12C 100: 10012 Temperature Data: FFD8E4 (hexadecimal for 10012)
Leftmost 3 Digits and Flags Flags Bits Data 15 14 13 12 0 0 0 0 Normal C Leftmost Rightmost 3 Digits and Flags Flags Bits Data 15 14 13 12 1 0 0 0 x162 08 to 11 8 x161 04 to 07 E x160 00 to 03 4 Flags 8 8 E 4 Flags Temperature data x165 08 to 11 F x164 04 to 07 F x163 00 to 03 D 0 F F D
Normal C Rightmost
Temperature data
209
Section
3-2
Leftmost 3 Digits and Flags Flags Bits Data 15 14 13 12 0 0 0 0 Normal F Leftmost Rightmost 3 Digits and Flags Flags Bits Data 15 14 13 12 1 0 0 0 x162 08 to 11 1 x161 04 to 07 D x160 00 to 03 4 Flags C 1 D 4 Flags Temperature data x165 08 to 11 F x164 04 to 07 F x163 00 to 03 B 4 F F B
Normal F Rightmost
Temperature data
Leftmost 3 Digits and Flags Flags Bits Data 15 14 13 12 0 1 1 0 x165 08 to 11 7 x164 04 to 07 F x163 00 to 03 F Flags 6 7 F F
Error F Leftmost Rightmost 3 Digits and Flags Flags Bits Data 15 14 13 12 1 1 1 0 x162 08 to 11 F x161 04 to 07 F x160 00 to 03 F
Temperature data
Error F Rightmost
Note
1. Leftmost digits are stored in the lower memory addresses. Treat the data in the lower memory address as the leftmost digits when programming. 2. Be sure that the data is read at least once every 125 ms to allow for the CPU Units cycle time and communications time. Correct data may not be obtained if the read cycle is greater than 125 ms.
210
Section
3-2
The following programming example shows how to use 2-decimal-place Mode for the following PC configuration.
20-point Expansion I/O Unit Temperature Sensor Unit
Inputs IR 000
Inputs IR 001
Temperature unit setting: OFF (C) Two-decimal-place Mode: ON (2 digits after decimal point stored)
Outputs IR 010
Outputs IR 011
Outputs None
In this example, 100 times the temperature data for temperature input 0 is stored in binary form in DM 0100 to DM 0102.
Temperature input 0 IR 002 Leftmost data Rightmost data IR 200
x160 x164 0
211
Section
3-2
DM0103
002 #7FFE
25506(=)
02000
02000
02001
(3) Leftmost and rightmost digits rearranged and moved to IR 202 and IR 201. (4)
(5)
212
Section
3-2
(6) If the temperature data is non-negative, the binary data in IR 202 and IR 201 is converted to BCD and placed in DM 0101 and DM 0100. (7) If the temperature data is negative, the 2s complement data in IR 202 and IR 201 is converted to binary data representing the absolute value of the temperature input and placed in HR 01 and HR 00.
(8) The binary data in HR 01 and HR 00 is converted to BCD and placed in DM 0101 and DM 0100. (9) 1 is written to the bit in DM 0101 indicating negative data.
Note The BCDL(59) instruction is only available with the CPM2A and CPM2C. The data movements corresponding to the numbers in the above ladder programming example are illustrated in the following diagram.
IR 002: Leftmost 3 digits of temperature data 0 165 164 (2) IR 200 0 165 164 (5) IR 202 0 0 165 164 IR 201 164 163 161 160 163 (4) 163 IR 002: Rightmost 3 digits of temperature data 1 162 161 160 (3)
DM0101 0/8
3 DM0100 10
102
101 100
(6) If the temperature data is non-negative, the binary data in IR 202 and IR 201 is converted to BCD and placed in DM 0101 and DM 0100. (8) If the temperature data is negative, the binary data in HR 01 and HR 00 is converted to BCD and placed in DM 0101 and DM 0100.
(1) DM0103
#0100 0 1
(9) If temperature data is negative, 8 is written here (i.e., 1 is written to the bit indicating negative data). (1) #0000 0 0 DM0102 IR 201 0 0 0 0
IR 202
2s complement data
2s complement data
HR 01
165 164
HR 00
163
162
161 160
(7) The 2s complement data in IR 202 and IR 201 is subtracted, as binary data, from the data in DM 0103 and DM 0102 and placed in HR 01 and HR 00.
213
Section
3-3
3-3
CompoBus/S Master Unit (or SRM1 CompoBus/S Master Control Unit) CPM1A/CPM2A CPU Unit
Special Flat Cable, 2-core VCTF cable, or 4-core VCTF cable (You cannot mix Special Flat Cable, 2-core VCTF cable, and 4-core VCTF cable. Use only one type of cable.)
Model SCA1-4F10
Specifications 4-core flat cable, 0.75 mm2 0.75 mm2 2 cores or 0.75 mm2 4 cores (JIS C 3306)
From the standpoint of the CPU Unit, the 8 input bits and 8 output bits allocated to the CompoBus/S I/O Link Unit are identical to input and output bits allocated to Expansion I/O Units even though the CompoBus/S I/O Link Unit does not control actual inputs and outputs. The input and output bits allocated to the CompoBus/S I/O Link Unit are one side of an I/O link between the slave CPU Unit and the CPU Unit to which the Master Unit is connected.
Master PC (CS Series) CPU Unit I/O memory 8 bits Output 2000 Input 2004 8 bits CompoBus/S Master Unit Unit No. 0
CPM1A, CPM2A, or CPM2C CPU Unit with 30 I/O points I/O memory 8 bits 8 bits Input IR 002 Output IR 012 Node number: 0 CompoBus/S I/O Link Unit
214
Section
3-3
CPM1A-SRT21 CPM2C-SRT21
(Allocated in the same way as Expansion I/O Units and other Expansion Units) Set using the DIP switch (Set before turning on the CPU Units power supply.) 50 mA Meaning Communications in progress. Communications stopped or error has occurred. A communications error has occurred. Indicates normal communications or stand-by.
LED Indicators
Usage Procedure
Connect the Unit. Connect the CompoBus/S I/O Link Unit.
Determine the node address of the CompoBus/S I/O Link Unit and set the DIP switch.
The node number should be a unique number between 0 and 15. Use the DIP switch to set the CompoBus/S I/O Link Units node number, communications mode, and the status of output data when a communications error occurs.
Connect the CompoBus/S I/O Link Unit to the CPU Unit. The number of CompoBus/S I/O Link Units that can be connected depends on the PC. Three Units can be connected to the CPM1A/CPM2A, five Units can be connected to the CPM2C, and three Units can be connected to the CPM2C-S. When Expansion I/O Units or other Expansion Units are also connected, they can be connected in any order from the CPU Unit.
CPM1A-SRT21 CompoBus/S I/O Link Unit CPM2C or CPM2C-S CompoBus/S I/O CPU Unit Link Unit
I/O Allocation I/O words are allocated to the CompoBus/S I/O Link Unit in the same way as Expansion I/O Units or other Expansion Units, the next available input and output words are allocated. When m is the last allocated input word and n is the
215
Section
3-3
last allocated output word, the CompoBus/S I/O Link Unit is allocated m+1 as its input word and n+1 as its output word.
CompoBus/S I/O Link Unit
Word m+1 bits 00 to 07
8 inputs 8 outputs
Word n+1 bits 00 to 07
In the following example, a CompoBus/S I/O Link Unit is connected to a CPU Unit with 30 I/O points.
Input words IR 000 IR 001 CPU Unit with 30 I/O points Output words IR 010 IR 011 IR 002 CompoBus/S I/O LInk Unit IR 012
The input word (m+1) contains the 8 bits of data from the Master Unit and two CompoBus/S communications flags.
15 Word m+1 0 0 0 0 0 0 Data from the Master Unit 09 08 07 00
CompoBus/S Communications Error Flag 0: Normal; 1: Error CompoBus/S Communication Status Flag 0: Stopped; 1: Communicating
Write the data to be transmitted to the Master Unit in the output word (n+1).
15 Word n+1 0 0 0 0 0 0 0 0 Data to be transferred to the Master Unit 07 00
The 8 bits of I/O data are not always transmitted simultaneously. In other words, 8 bits of data transmitted from the Master CPU Unit at the same time will not always reach the Slave CPU Unit simultaneously, and 8 bits of data transmitted from the Slave CPU Unit at the same time will not always reach the Master CPU Unit simultaneously. When the 8 bits of input data must be read together, modify the ladder program in the CPU Unit receiving the data. For example, read the input data twice in succession and accept the data only when the two values match. Unused bits in the CompoBus/S I/O Link Units output word can be used as work bits, but unused bits in the output slaves cannot be used as work bits. Unused bits in input word cannot be used as work bits. Determining the Node Number and Making DIP Switch Settings Node Number The CompoBus/S I/O Link Unit is a Slave Unit with 8 input bits and 8 output bits. The node number setting is made using the DIP switch; the inputs and outputs share the same node number. The range of possible node number settings is determined by the type of PC the Master Unit is mounted to and the settings on the Master Unit. For details refer to the CompoBus/S Operation Manual.
216
Section
3-3
DIP Switch Settings Use the DIP switch to set the CompoBus/S I/O Link Units node number, communications mode, and the status of output data when a communications error occurs.
CPM1A-SRT21 DIP switch
CPM2C-SRT21
Pin labels 1, 2, 4, Node Address Setting and 8 Pins Address 0 1 2 3 4 5 6 7 1 = ON, 0 = OFF DR HOLD ON OFF ON OFF 8421 0000 0001 0010 0011 0100 0101 0110 0111
Contents
Address 8 9 10 11 12 13 14 15
Pins 8421 1000 1001 1010 1011 1100 1101 1110 1111
Long-distance communications mode (See note 2.) High-speed communications mode Retain inputs after a communications error. Clear inputs after a communications error.
Note
1. Always turn OFF the power supply before changing the DIP switch settings. 2. Never touch the DIP switch when the Unit is operating. Static electricity may cause operating errors.
217
Section
3-3
3. The long-distance communications mode can be used only when one of the following Master Units is connected: C200HW-SRM21-V1, CQM1-SRM21-V1, or SRM1-C0j-V2. Wiring the CompoBus/S Communications Path Wire the CompoBus/S communications path as shown in the following diagrams.
CPM1A-SRT21
NC (BS+) NC (BS)
These terminals are not used. They can however be used as communications power supply relay terminals.
(BS +) (BS )
BD H
BD L
BD L
NC
218
Section
3-4
3-4
PC supporting DeviceNet master, e.g., CS, C200HX/HG/HE (-Z), CVM1, CV-series, etc.
DeviceNet slave
DeviceNet slave
Each Unit enables remote I/O communications for 32 input and 32 output points as a DeviceNet slave.
From the standpoint of the CPU Unit, the 32 input bits and 32 output bits allocated to the DeviceNet I/O Link Unit are identical to input and output bits allocated to Expansion I/O Units even though the DeviceNet I/O Link Unit does not control external inputs and outputs. The input and output bits allocated to the DeviceNet I/O Link Unit are one side of an I/O link between the slave CPU Unit and the CPU Unit to which the Master Unit is connected.
Master PC (CS Series with fixed allocations) CPU Unit I/O memory Outputs CIO 50 CIO 51 Inputs CIO 350 CIO 351 32 bits 32 bits DeviceNet Master Unit Unit No. 0 CPM1A or CPM2A CPU Unit with 30 I/O points I/O memory 32 bits Inputs IR 002 IR 003 32 bits Output IR 012 IR 013 Node number: 0 DeviceNet I/O Link Unit
Note Refer to the DeviceNet Slaves Operation Manual (W347) for details on DeviceNet networks.
219
Section
3-4
(Allocated in the same way as Expansion I/O Units and other Expansion Units) Set using the rotary switches (Set before turning ON the CPU Units power supply.) 30 mA
LED Indicators
Indicator MS
Meaning Normal status Switch settings being read Fatal hardware error (watchdog timer) Nonfatal error: Incorrect switch settings. Power not supplied. Waiting for initialization to start. Reset in progress.
NS
Green
Lit Flashing
Red
Lit
Network normal and communications established. Network normal and communications not established. Fatal communications error: Unit has detected network status preventing normal communications. Node number duplications Bus OFF detected.
Flashing
Nonfatal communications error: Communications timeout or communications error for one or more slaves. Waiting for node number check by master. Switch setting error. Power not supplied.
---
OFF
If an error occurs in the DeviceNet I/O Link Unit, the Error Flags in AR 0200 to AR 0202 will be turned ON. The addresses of the Error Flags are in the order that the Expansion Units are connected in the PC, with AR 0200 used for the Expansion Unit closest to the CPU Unit. Use these flags in the program when it is necessary to detect errors.
Usage Procedure
Connect the Unit. Connect the DeviceNet I/O Link Unit.
Determine the node number of the DeviceNet I/O Link Unit and set the rotary switches.
The node number should be a unique number between 0 and 63. Use the DIP switch to set the DeviceNet I/O Link Units baud rate and the status of output data when a communications error occurs.
220
Section
3-4
Connect the DeviceNet I/O Link Unit to the CPU Unit. Up to three Units can be connected to the CPM1A/CPM2A. When Expansion I/O Units or other Expansion Units are also connected, they can be connected in any order from the CPU Unit.
CPM1A-DRT21 DeviceNet I/O Link Unit
I/O Allocation I/O words are allocated to the DeviceNet I/O Link Unit in the same way as Expansion I/O Units or other Expansion Units, the next available input and output words are allocated. When m is the last allocated input word and n is the last allocated output word, the DeviceNet I/O Link Unit is allocated m+1 as its input word and n+1 as its output word.
DeviceNet I/O Link Unit
Word m+1 bits 00 to 15 Word m+2 bits 00 to 15
32 inputs 32 outputs
Word n+1 bits 00 to 15 Word n+2 bits 00 to 15
In the following example, a DeviceNet I/O Link Unit is connected to a CPU Unit with 30 I/O points.
Input words IR 000 IR 001 CPU Unit with 30 I/O points Output words IR 010 IR 011
IR 002 IR 003
All of the words allocated to the DeviceNet I/O Link Unit are used to read and write data between the CPU Unit of the DeviceNet I/O Link Unit and the CPU Unit of the DeviceNet master, as shown in the following illustration.
DeviceNet master I/O memory
IR 000 IR 001 (m) IR 002 (m+1) IR 003 (m+2)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Input bits IR 00000 to IR 00011: 12 bits IR 00100 to IR 00105: 6 bits IR 00200 to IR 00215: 16 bits IR 00300 to IR 00315: 16 bits CPU Unit DeviceNet I/O Link Unit
Do not use.
32 bits
15 14 13 12 11 10 9
8 7
5 4
3 2
1 0
Output bits IR 01000 to IR 01007: 8 bits IR 01100 to IR 01103: 4 bits IR 01200 to IR 01215: 16 bits IR 01300 to IR 01315: 16 bits CPU Unit DeviceNet I/O Link Unit
32 bits
The 32 bits each of I/O data are not always transmitted simultaneously. In other words, 32 bits of data transmitted from the Master CPU Unit at the same time will not always reach the Slave CPU Unit simultaneously, and 32 bits of data transmitted from the Slave CPU Unit at the same time will not always reach the Master CPU Unit simultaneously.
221
Section
3-4
When the 32 bits of input data must be read together, modify the ladder program in the CPU Unit receiving the data. For example, read the input data twice in succession and accept the data only when the two values match. Unused bits in the DeviceNet I/O Link Units output words can be used as work bits if they are not used for output from the slave. Unused bits in input word cannot be used as work bits.
DIP Switch
The settings of the DIP switch pins are shown in the following table. All pins are set to OFF at the factory.
Pin 1 2 3 4 Baud rate Not used Hold/clear remote outputs for communications error Function Setting See the next table. OFF OFF: ON: Clear remote outputs Hold remote outputs
Baud Rate Pins 1 and 2 are used to set the baud rate as shown in the following table.
Pin 1 OFF ON OFF ON Pin 2 OFF OFF ON ON 125 kbps 250 kbps 500 kbps Not allowed. Baud rate Max. transmission path length (reference) 500 m 250 m 100 m ---
Note
1. Always turn OFF the PC before changing the DIP switch settings. 2. Set the same baud rate on all of the nodes (Master and Slaves) in the Network. Any slaves with baud rates different from the masters rate wont be able to participate in communications and may cause a communications error between nodes that have been set properly.
222
Section
3-4
Hold/Clear Remote Outputs When the DeviceNet Unit is used as a slave, pin 4 is used to set whether to hold or clear remote outputs when a communications error occurs. Note When using AR 02 (Expansion Unit Error Flags) in the program, turn ON pin 4 on the DIP switch. If communications are set to be cleared, the timing for clearing outputs and setting the Error Flags may not agree. Wiring the DeviceNet Communications Path Wire the DeviceNet communications path as shown in the following diagram.
Connector provided with Unit (XW4B-05C1-H1-D) Black (V) Blue (CAN low) Shield White (CAN high) Red (V+) Multidrop Connector (XW4B-05C4-TF-D)
XW4B-05C4-TF-D
Note Use the XW4B-05C4-TF-D when wiring multidrop connections using Thick Cables. Use the following screwdriver for the above connector.
XW4Z-00C 3.5 mm 0.6 mm
223
Section
3-4
Refer to the DeviceNet Slaves Operation Manual (W347) for details on the response time. The data read/write time for one cycle for the CPM1A-DRT21 is approximately 0.5 ms. Add a maximum of 1 ms to the I/O response time.
224
4-3
4-4
4-5
225
Introduction
Section
4-1
4-1
Introduction
The CPM1/CPM1A can execute a variety of communications through its peripheral port via an RS-232C Adapter or an RS-422 Adapter. Host Link Communications The CPM1/CPM1A PCs are compatible with the Host Link System, which allows up to 32 PCs to be controlled from a host computer. An RS-232C Adapter is used for 1:1 communications and an RS-422 Adapter and B500-AL004 Link Adapter are used for 1:N communications. A CPM1/CPM1A equipped with an RS-232C Adapter can also communicate with a OMRON Programmable Terminal using host link commands. Refer to 4-2-1 CPM1/CPM1A Host Link Communications in this manual and 1-2-2 Host Link Communications in the CPM1 Operation Manual or 1-2-2 Host Link Communications in the CPM1A Operation Manual for more details. One-to-one PC Link A data link can be created with a data area in another CPM1, CPM1A, CPM2A, CPM2C, CQM1, C200HX/HG/HE, or C200HS PC. An RS-232C Adapter is used to make the 1:1 connection. Refer to 4-2-3 CPM1/CPM1A 1:1 PC Link Communications in this manual and 1-2-3 One-to-one PC Communications Links in the CPM1 Operation Manual or 1-2-3 One-to-one PC Communications Links in the CPM1A Operation Manual for more details. One-to-one NT Link Using the 1:1 NT Link, the CPM1/CPM1A PC can connected to the OMRON Programmable Terminal (NT Link Interface) through an RS-232C Adapter. Refer to 4-2-2 CPM1/CPM1A 1:1 NT Link Communications in this manual and 1-2-4 One-to-one NT Link Communications in the CPM1 Operation Manual or NT Link Communications in the CPM1A Operation Manual for more details. The following types of communications can be executed through the ports of the CPM2A/CPM2C. Host Link communications with a host computer RS-232C communications with a computer or other device One-to-one PC Link communications with another PC One-to-one NT Link communications with OMRON Programmable Terminals This section explains the required PC Setup and methods for using these types of communications. The following types of communications can be executed through the ports of the SRM1(-V2). Host Link communications with a host computer RS-232C communications with a computer or other device One-to-one PC Link communications with another PC One-to-one NT Link communications with OMRON Programmable Terminals
4-1-1 Overview
CPM1/CPM1A Communications
CPM2A/CPM2C Communications
SRM1(-V2) Communications
Note One-to-one NT Link communications are not possible with the SRM1-C01, which is equipped with only a peripheral port. The SRM1-C01 may be connected to a PT through an RS-232C Adapter in Host Link mode.
226
Section
4-2
4-2
08 to 11
12 to 15 DM 6651 00 to 07
08 to 15
Stop 1 bit 1 bit 1 bit 2 bit 2 bit 2 bit 1 bit 1 bit 1 bit 2 bit 2 bit 2 bit
Parity Even Odd None Even Odd None Even Odd None Even Odd None
DM 6652 00 to 15 DM 6653 00 to 07 08 to 15
Note
1. If an improper setting is used, a non-fatal error will occur, AR 1302 will be turned ON, and the default setting (0, 00, or 0000) will be used. 2. For information on the Host Link settings for another OMRON PC, refer to that PCs Operation Manual.
227
Section
4-2
3. If an out-of-range value is set, the following communications conditions will result. In that case, reset the value so that it is within the permissible range. Communications mode: Communications format: Host Link Standard settings (1 start bit, 7-bit data; 2 stop bits, even parity, 9,600 bps) No 00
This example shows a BASIC program that reads the status of the CPM1s inputs in IR 000. For more details, refer to 4-5 Host Link Commands. An FCS (frame check sequence) check isnt performed on the received response data in this program. Be sure that the host computers RS-232C port is configured correctly before executing the program. 1010 1020 1030 1040 1050 1060 1070 1080 1090 1100 1110 1120 1130 1140 1150 1160 1170 1180 CPM1 SAMPLE PROGRAM SET THE COMMAND DATA S$=@00RR00000001 FCS=0 FOR I=1 TO LEN(S$) FCS=FCS XOR ASC(MID$(S$,I,1)) NEXT I FCS$=(FCS):IF LEN(FCS$)=1 THEN FCS$=0+FCS$ CLOSE 1 CLS PRINT SENDING COMMAND OPEN COM:E73 AS #1 PRINT #1,S$ + FCS + CHR$(13); CLS PRINT RECEIVING RESPONSE DATA LINE INPUT #1,A$ PRINT A$ END
RS-232C Adapter
RS-232C Cable
228
Section
4-2
RS-232C Cable
PC Setup Settings
Word Bit DM 6650 00 to 07
The settings relating to 1:1 NT Link PC communications must be set as shown in the following table.
Function Port 00: Standard (1 start bit, 7-bit data, 2 stop bits, even parity, 9,600 bps) 01: Settings in DM 6651 Link area for 1:1 PC Link via peripheral port 0: LR 00 to LR 15 Communications mode1 0: Host Link; 2: 1:1 PC Link Slave; 3: 1:1 PC Link Master; 4: 1:1 NT Link settings1 Setting 00 (Any value is OK) 0 (Any value is OK) 4
08 to 11
12 to 15
Note
1. If an improper setting is used, a non-fatal error will occur, AR 1302 will be turned ON, and the default setting (0 or 00) will be used. 2. For information on the NT Link settings for another OMRON PC, refer to that PCs Operation Manual. 3. If an out-of-range value is set, the following communications conditions will result. In that case, reset the value so that it is within the permissible range. Communications mode: Host Link Communications format: Standard settings (1 start bit, 7-bit data; 2 stop bits, even parity, 9,600 bps) Transmission delay: No Node number: 00
229
Section
4-2
The following diagram shows a 1:1 PC Link between two CPM1s PCs. Refer to the CPM1A Operation Manual for the corresponding information on the CPM1A.
RS-232C Cable
RS-232C Adapter
The words used for the 1:1 PC Link are as shown below.
LR00 Write data Read data LR07 LR08 LR15 Master Area for writing Area for reading Slave Area for reading Area for writing LR07 LR08 LR15 LR00 Read data Write data
Only the 16 LR words from LR 00 to LR 15 can be linked in the CPM1/CPM1A, so use only those 16 words in the CQM1 or C200HS when making a 1:1 PC Link with one of those PCs. A 1:1 PC Link cannot be made to a CPM1/CPM1A PC using LR 16 through LR 63 in the CQM1, C200HX/HG/HE, or C200HS. The settings relating to 1:1 PC Link communications must be set as shown in the following table.
Function Setting (Master) 00 (Any value is OK) 0 Setting (Slave) 00 (Any value is OK) 0 (Any value is OK) 2
PC Setup Settings
Word Bit
DM 6650 00 to 07
Port settings1 00: Standard (1 start bit, 7-bit data, 2 stop bits, even parity, 9,600 bps) 01: Settings in DM 6651 Link area for 1:1 PC Link via peripheral port 0: LR 00 to LR 15 Communications mode1 0: Host Link; 2: 1:1 PC Link Slave; 3: 1:1 PC Link Master; 4: 1:1 NT Link
08 to 11
12 to 15
Note
1. If an improper setting is used, a non-fatal error will occur, AR 1302 will be turned ON, and the default setting (0 or 00) will be used. 2. For information on the 1:1 PC Link settings for another OMRON PC, refer to that PCs Operation Manual. 3. For information on CPM1/CPM1A 1:1 PC Link connections and wiring diagrams refer to 3-4-7 Host Link Connections in the CPM1 Operation Manual or CPM1A Operation Manual. For the SRM1(-V2) refer to 3-4-4 RS-232C Port Wiring in the SRM1 Master Control Unit Operation Manual. 4. If an out-of-range value is set, the following communications conditions will result. In that case, reset the value so that it is within the permissible range. Communications mode: Host Link Communications format: Standard settings (1 start bit, 7-bit data; 2 stop bits, even parity, 9,600 bps) Transmission delay: No Node number: 00
230
Section
4-3
This example shows ladder programs that copy the status of IR 000 in each CPM1/CPM1A to SR 200 in the other CPM1/CPM1A. Program in the Master
25313 (Always ON) MOV(21) 000 LR00
LR00 IR 000 SR 200 Write Read LR07 LR08 LR15 Writing area Reading area Reading area Writing area
4-3
231
Section
4-3
OMRON Programmable Terminal Commands Commands CPM2A RS-232C port connection (See note.) Responses
Note When connecting to the peripheral port, an RS-232C Adapter or computer connection cable (CQM1-CIF01 or CQM1-CIF02) is necessary.
232
Responses
Section
4-3
CPM2C-CN111 (0.15 m)
CS1W-CN118 (0.1 m)
CPM2C-CIF11
CPM2C-CIF21
Note The CSW1-CN226/626 can be connected directly to the CPU Unit. With the CPM2C-CIF01-V1, the cable switch (SW1) can be turned ON to enable connecting to a personal computer with a CS1W-CN226/CN626 Connecting Cable.
233
Section
4-3
Responses
Commands
234
Section
4-3
B500-AL004 or NT-AL001 (requires +5 V) (See notes 1 and 2.) RS-422 (Total length: 500 m max.) When using the port as a peripheral port CPM2C CPU Unit CPM2C CPU Unit CPM2C CPU Unit
CPM2-CIF11
CPM2-CIF11
CPM2-CIF11
235
Section
4-3
In Host Link communications, the host computer ordinarily has the transmission right first and initiates the communications. The CPM2A/CPM2C then automatically sends a response. Commands and responses are exchanged in the order shown in the illustration below. The block of data transferred in a single transmission is called a frame. A single frame is configured of a maximum of 131 characters of data. The right to send a frame is called the transmission right. The Unit that has the transmission right is the one that can send a frame at any given time. The transmission right is traded back and forth between the host computer and the CPM2A/ CPM2C each time a frame is transmitted. The transmission right is passed from the transmitting Unit to the receiving Unit when either a terminator (the code that marks the end of a command or response) or a delimiter (the code that sets frames apart) is received.
Frame (command) Unit no. Header code Host computer Text FCS Terminator Next frame transmission enabled (i.e., transmission right transferred) Unit no. Header code End code CPM2A/CPM2C Text FCS Terminator Frame (response)
Unit no. Header code End code Text FCS Terminator Frame (response)
Slave-initiated Communications
Data transmissions from the PC to the host computer can be initiated by the CPU Unit using TXD(48).
Host computer
Unit no. Header code CPM2A/CPM2C Text FCS Terminator Frame (response)
236
Section
4-3
This section explains the formats for the commands and responses that are exchanged in Host Link communications. Command Format When transmitting a command from the host computer, prepare the command data in the format shown below.
x 101 x 100 * Header code Text FCS
Node No.
Terminator
@ An @ symbol must be placed at the beginning. Node No. Identifies the CPM2A/CPM2C PC communicating with the host computer. Specify the CPM2A/CPM2Cs node number in the PC Setup (DM 6648, DM 6653). Header Code Set the 2-character command code. Text Set the command parameters. FCS Set a 2-character Frame Check Sequence code. See page 239. Terminator Set two characters, * and the carriage return (CHR$(13)) to indicate the end of the command. Response Format The response from the CPM2A/CPM2C is returned in the format shown below. Prepare a program so that the response data can be interpreted and processed.
x 161 x 160 * Text FCS
x 101 x 100
Node No.
Header code
End code
Terminator
@, Node No., Header Code Contents identical to those of the command are returned. End Code The completion status of the command (e.g., whether or not an error has occurred) is returned. Text Text is returned only when there is data such as read data. FCS The set 2-character Frame Check Sequence is returned. Terminator Set two characters, * and the carriage return (CHR$(13)) to indicate the end of the response.
Long Transmissions
The largest block of data that can be transmitted as a single frame is 131 characters. A command or response of 132 characters or more must therefore be divided into more than one frame before transmission. When a transmission is split, the ends of the first and intermediate frames are marked by a delimiter instead of a terminator.
237
Section
4-3
As each frame is transmitted by the host computer, the computer waits for the delimiter to be transmitted from the CPM2A/CPM2C. After the delimiter has been transmitted, the next frame will then be sent. This procedure is repeated until the entire command has been transmitted.
Frame 2 (command) Frame 3 (command)
Frame 1 (command) Unit no. Header code Host computer Text FCS Delimiter
CPM2A/CPM2C
Delimiter
Delimiter
Unit no. Header code End code Text FCS Terminator Frame (response)
Dividing Responses
As each frame is received by the host computer, a delimiter is transmitted to the CPM2A/CPM2C. After the delimiter has been transmitted, the CPM2A/CPM2C will transmit the next frame. This procedure is repeated until the entire response has been transmitted.
Frame (command) Unit no. Header code Host computer Text FCS Terminator Delimiter Delimiter
Unit no. Header code End code CPM2A/CPM2C Text FCS Delimiter Frame1 (response)
238
Section
4-3
When dividing commands such as WR, WL, WC, or WD that execute write operations, be careful not to divide into separate frames data that is to be written into a single word. As shown in the illustration below, be sure to divide frames so that they coincide with the divisions between words.
Frame 1 @
(131 characters maximum) 0 0 x101 x100 Node No. W D Data One word of data FCS Delimiter
Header code
Data from the same word is not divided. Frame 2 (128 characters maximum) Data * FCS
One word of data Data from the same word is not divided.
Terminator
0 Text
4 FCS
Terminator
ASCII code @ 1 0 R 0 0 to 0 40 31 30 52 30 30 30 31
Leftmost 0100 XOR 0011 XOR 0011 XOR 0101 XOR 0011 XOR 0011 XOR 0011 XOR 0011 0100 4 2
Rightmost 0000 0001 0000 0010 0000 0000 0000 0001 0010 Converted to hexadecimal. Handled as ASCII characters.
1 Calculation results
239
Section
4-3
This example shows a BASIC subroutine program for executing an FCS check on a frame received by the host computer. Normal reception data includes the FCS, delimiter or terminator, and so on. When an error occurs in transmission, however the FCS or some other data may not be included. Be sure to program the system to cover this possibility. 400 *FCSCHECK 410 L = LEN ( RESPONSE$ ) . ........................ Data transmitted and received 420 Q = 0 : FCSCK$ = 430 A$ = RIGHT$ ( RESPONSE$ , 1) 440 PRINT RESPONSE$ , A$ , L 450 IF A$ = * THEN LENGS = LEN ( RESPONSE$ ) 3 ELSE LENGS = LEN ( RESPONSE$ ) 2 460 FCSP$ = MID$ ( RESPONSE$ , LENGS + 1 , 2 ) . ......... FCS data received 470 FOR I = 1 TO LENGS . ........................ Number of characters in FCS 480 Q = ASC ( MID$ ( RESPONSE$ , I , 1 ) ) XOR Q 490 NEXT I 500 FCSD$ = HEX$ ( Q ) 510 IF LEN ( FCS0$ ) = 1 THEN FCSD$ = 0 + FCSD$ . ........ FCS result 520 IF FCSD$ < > FCSP$ THEN FCSCK$ = ERR 530 PRINT FCSD$ = ; FCSD$ , FCSP$ = ; FCSP$ , FCSCK$ = ; FCSCK$ 540 RETURN
240
Section
4-3
Page g 281 282 282 282 283 283 284 285 285 286 286 287 288 288 289 290 291 292 293 294 295 296 297 298 299 300 300 301 301 302 304 304 304 305
241
Section
4-3
Corrective measures --Check the relation between the command and the PC mode.
02
04 0B
Check the program. This code is not presently being used. Check the FCS calculation method. If there was influence from noise, transfer the command again. Check the format and transfer the command again. Correct the areas and transfer the command again. Check the address and instruction.
13
14 15 16
18 19 23 A3 A4 A5 A8 Other
Frame length error Not executable User memory write-protected Aborted due to FCS error in transmit data Aborted due to format error in transmit data Aborted due to entry number data error in transmit data Aborted due to frame length error in transmit data ---
Divide the command into multiple frames. Execute QQ to register items to read before attempting batch read. Change the setting in the PC Setup (DM 6602). Check for corrupted frames, correct if necessary, and try the transfer ecessa y, a d y e a s e again.
Application Procedure
Setting the CPU Units communications switch Set the CPM2A CPU Units communications switch or the CPM2C CPU Units DIP switch.
242
Section
4-3
The CPM2As communications are controlled by the communications switch on the front of the CPU Unit and the CPM2Cs communications are controlled by the DIP switch on the front of the CPU Unit. CPM2A Communications Switch Setting When the communications switch is set to OFF, communications through the peripheral port and RS-232C port are governed by the settings in the PC Setup. When the communications switch is set to ON, communications through the peripheral port and RS-232C port are governed by the standard Host Link settings (1 start bit, 7 data bits, 2 stop bits, even parity, and 9,600 bps baud rate). Note When a Programming Console is connected to the peripheral port, communications with the Programming Console are unaffected by either the communications switch or PC Setup.
Communications switch
Peripheral port
RS-232C port
An RS-232C Adapter is needed to perform Host Link communications from a peripheral port.
243
Section
4-3
CPM2C DIP Switch Settings When SW2 is set to OFF, communications through the peripheral port are set to Programming Console protocol, regardless of the setting of pin 1 or the settings in the PC Setup. Front View
CPU Unit with Relay Outputs via Terminal Block CPU Unit with Transistor Outputs via Fujitsu-compatible Connector 4. Status indicators 7. Communications port 6. Output indicators 5. Input indicators 8. Communications switch 9. Customize switch 2. Input terminals 3. Output terminals 2. Input connector 3. Output connector (8) (9) DIP switch for Units with 10/20 I/O points
CPU Unit with Transistor Outputs via MIL Connector 4. Status indicators 7. Communications port 6. Output indicators 5. Input indicators 8. Communications switch 9. Customize switch 2. Input connector 3. Output connector (9) DIP switch for Units with 32 I/O points
(8)
When SW 2 is set to ON, the status of SW 1 determines whether communications through the peripheral port and RS-232C port are governed by the settings in the PC Setup or the standard settings (1 start bit, 7 data bits, 2 stop bits, even parity, and 9,600 bps baud rate).
SW1 OFF Communications settings The communications settings for the peripheral port and RS-232C port will be determined by the settings in the PC Setup (DM 6645 to DM 6649, DM 6650 to DM 6654). If a Programming Console is connected to the peripheral port, however, operation for that port will be in the Programming Console mode. The communications settings for the peripheral port and RS-232C port will be the standard settings. If a Programming Console is connected to the peripheral port, however, operation for that port will be in the Programming Console mode.
ON
An RS-232C Adapter is needed to perform Host Link communications from a peripheral port. Note When performing host link communications via the peripheral port of a CPU Unit with a manufacturing number of 3180O or earlier (i.e., manufactured on or before April 31, 2000), set SW2 to ON. See above for details of the settings of SW2. When using a CPU Unit with a manufacturing number of 3180O or earlier (i.e., manufactured on or before April 31, 2000), do not change the setting of SW2 with a Programming Console, the CPM2C-CIF01-V1/11, or the CQM1-CIF01/02 connected. If the setting of SW2 is changed in this state, communications will be interrupted, and a communications error will be generated or the Programming Console will enter a no-response state (i.e., pressing the keys of the Programming Console will have no effect and the display will stay the same).
244
Section
4-3
One-to-one Connections The RS-232C port on the Host Link computer and the RS-232C port on the CPM2A/CPM2C or CPM1-CIF01 RS-232C Adapter are connected as shown in the following diagram when there is no CTS control on the RS-232C port. With the CPM2C, the CPM2C-CN111 and CS1W-CN118 connecting cables can be used in place of the RS-232C Adapter.
IBM PC/AT or compatible Signal Pin No. RS-232C port Signal Pin No.
Hood
One-to-N Connections Set the DIP switch on the NT-AL001 RS-232C/RS-422 Conversion Adapter.
Normally ON ON when the Unit is at the end of the transmission path. OFF in all other cases. Used as a 4-conductor method. (Both switches set to OFF) According to RS-232C CTS control (5: OFF, 6: ON)
The RS-232C port with the NT-AL001 RS-232C/RS-422 Conversion Adapter and the RS-232C port of the CPM2A/CPM2C or CPM1-CIF01 RS-232C Adapter are connected as shown in the following diagram when there is no CTS control on the RS-232C port. A power supply of 5 VDC is supplied to the RS-232C/RS-422 Conversion Adapter. With the CPM2C, the CPM2C-CN111 and CS1W-CN118 connecting cables can be used in place of the RS-232C Adapter.
NT-AL001 RS-232C/RS-422 Conversion Adapter Signal Pin No.
Hood
Note Do not connect external devices other than the NT-AL001 Conversion Adapter to the 5 VDC power supply of pin number 6 on the CPM2A/CPM2Cs RS-232C port. Doing so may result in damage to the CPM2A/CPM2C or to the external device.
245
Section
4-3
The PC Setup settings that are required depend on whether a peripheral port or an RS-232C port is used. Settings for RS-232C Port Note If SW1 on the front panel of the CPU Unit is ON, the RS-232C port will operate with the default settings regardless of the settings in DM 6645 to DM 6649.
Word DM 6645
Bit 00 to 03
Function Port settings 0: Standard (1 start bit, 7-bit data, 2 stop bits, even parity, 9,600 bps; Host Link unit number: 0) 1: Settings in DM 6646 (Other settings will cause a non-fatal error, the default setting will be used, and AR 1302 will turn ON.) CTS control settings 0: Disable; 1: Set Link words for 1:1 PC Link 0: LR 00 to LR 15; Other: Not effective Communications mode 0: Host Link (default setting); 1: RS-232C (no-protocol); 2: 1:1 PC Link Slave; 3: 1:1 PC Link Master; 4: 1:1 NT Link (Other settings will cause a non-fatal error, the Host Link setting will be used, and AR 1302 will turn ON.)
04 to 07 08 to 11 12 to 15
0 or 1 Any 0
DM 6646
00 to 07 08 to 15
Baud rate: 00: 1,200 bps 01: 2,400 bps 02: 4,800 bps 03: 9,600 bps 04: 19,200 bps Frame format Start Length Stop Parity 00: 1 7 1 Even 01: 1 7 1 Odd 02: 1 7 1 None 03: 1 7 2 Even 04: 1 7 2 Odd 05: 1 7 2 None 06: 1 8 1 Even 07: 1 8 1 Odd 08: 1 8 1 None 09: 1 8 2 Even 10: 1 8 2 Odd 11: 1 8 2 None (Other settings will cause a non-fatal error, the default settings (03) will be used, and AR 1302 will turn ON.) Transmission delay (Host Link) 0000 to 9999 (BCD): Set in units of 10 ms, e.g., setting of 0001 equals 10 ms (Other settings will cause a non-fatal error, the default setting (0000) will be used, and AR 1302 will turn ON.)
DM 6647
00 to 15
0000 to 9999
DM 6648
00 to 07
00 to 31 (BCD): Node number (Host Link) (Other settings will cause a non-fatal error, the default setting (00) will be used, and AR 1302 will turn ON.) Start code enable (RS-232C) 0: Disable; 1: Use start code in DM 6649. End code enable (RS-232C) 0: Disable (number of bytes received) 1: Use end code in DM 6649. 2: CR, LF (Other settings will cause a non-fatal error, the disable setting will be used, and AR 1302 will turn ON.)
00 to 31
08 to 11 12 to 15
Any Any
246
Section
Setting Any Any
4-3
04 to 11 12 to 15
0 0
(Other settings will cause a non-fatal error, the default settings (03) will be used, and AR 1302 will turn ON.) DM 6652 00 to 15 Transmission delay (Host Link) 0000 to 9999 (BCD): Set in units of 10 ms. (Other settings will cause a non-fatal error, the default setting (0000) will be used, and AR 1302 will turn ON.) 0000 to 9999
Note
1. If SW1 on the front panel of the CPU Unit is ON, the peripheral port will operate with the default settings regardless of the settings in DM 6645 to DM 6649. 2. When connecting a computer running Support Software via the peripheral bus, turn OFF SW1 on the front panel of the CPU Unit and set DM 6650 to 0001 (Host Link). The CPU Unit will automatically switch to peripheral bus communications for the serial communications port.
247
Section
Setting 00 to 31
4-3
Any
12 to 15
Any
Any
08 to 15
Any
248
Section
4-3
This example shows a BASIC program that reads the status of the CPM2A/ CPM2Cs inputs in IR 000. For more details see 4-5 Host Link Commands. An FCS (frame check sequence) check isnt performed on the received response data in this program. Be sure that the host computers RS-232C port is configured correctly before executing the program. 1000 1010 CPM2A/CPM2C Sample Program for BASIC 1020 1050 1060 Set value RS232C SPEED:9600BPS,PARITY:EVEN,DATA:7,STOP:2 1070 OPEN COM:E73 AS #1 1080 *REPEAT 1090 Transmission data input 1100 INPUT send data : ,send$ 1110 FCS Calculation 1120 FCS=0 1130 FOR IFCS = 1 TO LEN ( send$ ) 1140 FCS = FCS XOR ASC( MID$ ( SEND$ , IFCS , 1 ) ) 1150 NEXT 1160 FCS$ = RIGHT$ ( 0 + HEX$ ( FCS ) , 2 ) 1170 Communications execute 1180 ZZZ$ = SEND$ + SCS$ + * + CHR$(13) 1190 PRINT #1 , ZZZ$ ; 1200 Response check 1210 RECCNT = 0 : TMP$ 1220 *DRECLOOP 1230 IF LOC ( 1 ) < > 0 THEN *DREC1 1240 RECCNT = RECCNT + 1 1250 IF RECCNT = 5000 THEN *DRECERR ELSE *DRECLOOP 1260 *DREC1 1270 TMP$ = TMP$ + INPUT$ ( LOC (1 ) , #1 ) 1280 IF RIGHT$ ( TMP$ , 1 ) = CHR$ (13) THEN *DRECEND ELSE RECCNT = 0 : GOTO * DRECLOOP 1290 *DRECERR 1300 TMP$ = No response !! + CHR$ ( 13 ) 1310 *DRECEND 1320 PRINT receive data : ; RECV$ 1340 Go to transmission data input 1350 GOTO *REPEAT 1360 Processing complete 1370 CLOSE #1 1380 END
249
Section
4-3
Host Link communications are controlled with the following AR area flags.
Word AR 08 Bit(s) 00 to 03 Contents RS-232C Port Error Code 0: Normal completion 1: Parity error 2: Frame error 3: Overrun error RS-232C Communications Error Flag ON: RS-232C port communications error occurred OFF: Normal RS-232C Transmit Ready Flag ON: The PC is ready to transmit data. Peripheral Port Error Code 0: Normal completion 1: Parity error 2: Frame error 3: Overrun error Peripheral Port Communications Error Flag ON: Peripheral port communications error occurred. Peripheral Port Transmit Ready Flag ON: The PC is ready to transmit data.
04
05 08 to 11
12 13
Unsolicited Communications A data transmission to the host computer is initiated by the PC.
(@)TXD(48) S C N
S: Leading address of data to be transmitted C: Control data N: Number of bytes to be transmitted (BCD: 0001 to 0061)
When Host Link communications are being used, TXD(48) converts the N-bytes of data starting at S to ASCII, adds the Host Link header, FCS, and terminator, and transmits this data as a Host Link frame. The transmitted Host Link frame will be as shown in the following diagram.
Data (ASCII)
250
Section
4-3
In the following program example TXD(48) is used to transmit data from an RS-232C port to a host computer. If AR 0805 (the RS-232C Transmit Ready Flag) is ON when IR 00100 turns ON, the ten bytes of data (DM 0100 to DM 0104) will be transmitted to the host computer, leftmost bytes first.
(48)
Leading address of data to be transmitted RS-232C port specification 10 bytes
CPM1-CIF01 RS-232C Adapter (CTS control cannot be used.) RS-232C devices Bar code reader Serial printer Other
Peripheral port
CPM2A CPU Unit RS-232C devices Bar code reader Serial printer Other CQM1-CIF01/02 RS-232C Adapter (CTS control cannot be used.)
Peripheral port
251
Section
4-3
CPM2C CPU Unit RS-232C devices Bar code reader Serial printer Other
Note A CPM1-CIF01 RS-232C Adapter can also be used for no-protocol communications through the peripheral port, or for a CPM2C, a CPM2C-CIF01-V1 Peripheral/RS-232C Adapter Unit can be used to connect to external devices. Refer to the CPM2C Operation Manual for details.
Note
1. The start and end codes are set in DM 6648 to DM 6649 (RS-232C) or DM 6653 to DM 6654 (peripheral port) in the PC Setup. 2. When there are several start or end codes in the transmission, the first of each will be effective. 3. When the end code is accidentally duplicated in the transmission data and the transmission is stopped part way through, use CR and LF as the end code. 4. The start and end codes themselves are not transmitted and received. When sending data from the CPM2A/CPM2C, check that the Transmission Enable Flag is ON for executing TXD(48). The Transmission Enable Flag will turn
Transmission Flags
252
Section
4-3
OFF while the data is being transmitted and will turn ON again when transmission is complete. After the CPM2A/CPM2C has received data, the Receive Enable Flag turns ON. When RXD(47) is executed, the data received will be written to the specified words and the Reception Complete Flag will turn OFF.
Flag Transmit Ready Flag Reception Completed Flag Peripheral port AR 0813 AR 0814 RS-232C port AR 0805 AR 0806
Note The CPM2A/CPM2C starts and completes data reception at the following points: Reception Start: Start code disabled: Continually available for reception Start code enabled: After start code is received Reception Complete: When either the end code, the specified no. of bytes, or 256 bytes are received.
Application Procedure
Setting the Communications switch Set the CPM2A CPU Units communications switch or the CPM2C CPU Units DIP switch.
Ladder program
The CPM2As communications are controlled by the communications switch on the front of the CPU Unit and the CPM2Cs communications are controlled by the DIP switch on the front of the CPU Unit. CPM2A Communications Switch Setting Turn OFF the Communications switch when using no-protocol communications. No-protocol communications will not be possible if the communications switch is ON.
Communications switch
Peripheral port
RS-232C port
253
Section
4-3
Note An RS-232C adapter is required for no-protocol communications on the peripheral port. CPM2C DIP Switch Settings Turn OFF pin 1 of the DIP switch when using no-protocol communications so that communications through the RS-232C port are governed by the settings in the PC Setup (DM 6645 to DM 6649). Front View
CPU Unit with Relay Outputs via Terminal Block CPU Unit with Transistor Outputs via Fujitsu-compatible Connector 4. Status indicators 7. Communications port 6. Output indicators 5. Input indicators 8. Communications switch 9. Customize switch 2. Input terminals 3. Output terminals 2. Input connector 3. Output connector (8) (9) DIP switch for Units with 10/20 I/O points
CPU Unit with Transistor Outputs via MIL Connector 4. Status indicators 7. Communications port 6. Output indicators 5. Input indicators 8. Communications switch 9. Customize switch 2. Input connector 3. Output connector (9) DIP switch for Units with 32 I/O points
(8)
RS-232C port communications p Governed by the PC Setup (DM 6645 to DM 6649) Governed by standard settings
Note An RS-232C Adapter is needed to perform no-protocol communications through the peripheral port. Connecting the Cables This section describes RS-232C connections. The RS-232C port on the serial device and the RS-232C port of the CPM2A/ CPM2C or CPM1-CIF01 RS-232C Adapter are connected as shown in the fol-
254
Section
4-3
lowing diagram. With the CPM2C, the CPM2C-CN111 and CS1W-CN118 connecting cables can be used in place of the RS-232C Adapter.
RS-232C port Signal Serial device RD (receive data) Serial device SD (send data) Pin No.
Recommended Cables From Fujikura Densen UL2464 AWG25X5P IFS-RVV-SB (UL-compliant) AWG28X5P IFVV-SB (not UL-compliant) From Hitachi UL2464-SB (MA) 5PX28AWG (7/0.127) (UL-compliant) CO-MA-VV-SB 5PX28AWG (7/0.127) (not UL-compliant) PC Setup The PC Setup settings that are required depend on whether a peripheral port or an RS-232C port is used. Settings for RS-232C Port
Bit 00 to 03 Function Port settings 0: Standard (1 start bit, 7-bit data, 2 stop bits, even parity, 9,600 bps; Host Link unit number: 0) 1: Settings in DM 6646 (Other settings will cause a non-fatal error, the default setting will be used, and AR 1302 will turn ON.) CTS control settings 0: Disable; 1: Set Link words for 1:1 PC Link 0: LR 00 to LR 15; Other: Not effective Communications mode 0: Host Link; 1: No-protocol; 2: 1:1 PC Link Slave; 3: 1:1 PC Link Master; 4: 1:1 NT Link (Other settings will cause a non-fatal error, the Host Link setting will be used, and AR 1302 will turn ON.) Setting As required
Word DM 6645
04 to07 08 to 11 12 to 15
Any 1
255
Section
4-3
Setting As required
(Other settings will cause a non-fatal error, the default settings (03) will be used, and AR 1302 will turn ON.) DM 6647 00 to 15 Transmission delay (Host Link) 0000 to 9999 (BCD): Set in units of 10 ms, e.g., setting of 0001 equals 10 ms (Other settings will cause a non-fatal error, the default setting (0000) will be used, and AR 1302 will turn ON.) DM 6648 00 to 07 00 to 31 (BCD): Node number (Host Link) As required (Other settings will cause a non-fatal error, the default setting (00) will be used, and AR 1302 will turn ON.) Start code enable (RS-232C) 0: Disable; 1: Use start code in DM 6649. End code enable (RS-232C) 0: Disable (number of bytes received) 1: Use end code in DM 6649. 2: CR, LF (Other settings will cause a non-fatal error, the default setting (0) will be used, and AR 1302 will turn ON.) DM 6649 00 to 07 08 to 15 Start code (00 to FF) (No-protocol, effective when bits 8 to 11 of DM 6648 are set to 1.) No. of bytes of data received (No-protocol, effective when bits 12 to 15 of DM 6648 are set to 0.) 00: 256 bytes 01 to FF: 1 to 255 bytes End code (00 to FF) (No-protocol, effective when bits 12 to 15 of DM 6648 are set to 1.) 00 to FF 00 to FF 0 or 1 0 to 2 0000 to 9999
08 to 11 12 to 15
00 to FF
Note If SW1 on the front panel of the CPU Unit is ON, the RS-232C port will operate with the default settings regardless of the settings in DM 6645 to DM 6649. Settings for Peripheral Port
Word DM 6650 Bit 00 to 03 Function Port settings 0: Standard (1 start bit, 7-bit data, 2 stop bits, even parity, 9,600 bps; Host Link unit number: 0) 1: Settings in DM 6651 (Other settings will cause a non-fatal error, the default setting (0) will be used, and AR 1302 will turn ON.) Not used Communications mode 0: Host Link or peripheral bus; 1: No-protocol (Other settings will cause a non-fatal error, the Host Link setting will be used, and AR 1302 will turn ON.) Setting As required
04 to 11 12 to 15
0 1
256
Section
4-3
DM 6652
00 to 15
Baud rate 00: 1,200 bps; 01: 2,400 bps; 02: 4,800 bps; 03: 9,600 bps; 04: 19,200 bps Frame format Start Length Stop Parity 00: 1 7 1 Even 01: 1 7 1 Odd 02: 1 7 1 None 03: 1 7 2 Even 04: 1 7 2 Odd 05: 1 7 2 None 06: 1 8 1 Even 07: 1 8 1 Odd 08: 1 8 1 None 09: 1 8 2 Even 10: 1 8 2 Odd 11: 1 8 2 None (Other settings will cause a non-fatal error, the default settings (03) will be used, and AR 1302 will turn ON.) Transmission delay (Host Link) 0000 to 9999 (BCD): Set in units of 10 ms. (Other settings will cause a non-fatal error, the default setting (0000) will be used, and AR 1302 will turn ON.)
Setting As required
0000 to 9999
DM 6653
00 to 07
As required
08 to 11
(Other settings will cause a non-fatal error, the default setting (00) will be used, and AR 1302 will turn ON.) Start code enable (Peripheral port) 0 or 1 0: Disable 1: Use start code in DM 6654. End code enable (Peripheral port) 0: Disable (number of bytes received) 1: Use end code in DM 6654. 2: CR. LF (Other settings will cause a non-fatal error, the default setting (0) will be used, and AR 1302 will turn ON.) 0 to 2
12 to 15
DM 6654
00 to 07 08 to 15
Start code (00 to FF) (Peripheral port, effective when bits 8 to 11 of DM 6653 are set to 1.) No. of bytes of data received (Peripheral port, effective when bits 12 to 15 of DM 6653 are set to 0.) 00: 256 bytes 01 to FF: 1 to 255 bytes End code (00 to FF) (Peripheral port, effective when bits 12 to 15 of DM 6653 are set to 1)
00 to FF 00 to FF
00 to FF
Note
1. If SW1 on the front panel of the CPU Unit is ON, the peripheral port will operate with the default settings regardless of the settings in DM 6645 to DM 6649. 2. When connecting a computer running Support Software via the peripheral bus, turn OFF SW1 on the front panel of the CPU Unit and set DM 6650 to 0001 (Host Link). The CPU Unit will automatically switch to peripheral bus communications for the serial communications port.
Program
(@)RXD(47)
257
Section
4-3
04
05 06 07 08 to 11
12
13 14 15 AR 09 AR 10 00 to 15 00 to 15
S: Leading address of data to be transmitted C: Control data N: Number of bytes to be transmitted (BCD: 0001 to 0256)
Storage order 0: Leftmost bytes first 1: Rightmost bytes first Communications port 0: RS-232C port 1: Peripheral port
When no-protocol communications are being used, TXD(48) transmits N bytes of data beginning at S.
258
Section
4-3
D: Leading address for storing reception data C: Control data N: Number of bytes to receive (BCD: 0001 to 0256)
The following program example is for no-protocol communications conducted through a RS-232C port using TXD(48) and RXD(47) instructions. If AR 0805 (the RS-232C Transmit Ready Flag) is ON when 00100 turns ON, then data from DM 0100 to DM 0104 is transmitted from leftmost bytes to rightmost bytes. When AR 0806 (the Reception Completed Flag) turns ON, 256 bytes of received data are read and written to DM 0200 from leftmost bytes to rightmost bytes.
00100 DIFU(13) 00101 00101 AR 0805 @TXD(48) DM 0100 #0000 #0010 AR 0806 RXD(47) DM 0200 #0000 #0256 First word to store received data. Use the RS-232C port; store transmitted data from leftmost bytes to rightmost bytes. Receive 256 bytes. First word holding send data. Use the RS-232C port; transmit data from leftmost bytes to rightmost bytes. Transmit 10 bytes. No-protocol communications start
259
Section
4-3
260
Section
4-3
RS-232C connection
CPM2C-CN111 (0.15 m)
CS1W-CN118 (0.1 m)
RS-422 connection
RS-422 peripheral port NT-AL001 RS-232C Adapter RS-232C port XW2Z-070T-1 (0.7 m) XW2Z-200T-1 (2 m) CPM2C-CIF11
Note The Programmable Terminal cannot be connected using a peripheral port connection when communicating via a 1:1 NT Link.
Application Procedure
Setting communications. Use the settings in the PC Setup (DM6645 to DM 6649) for RS-232C communications. (Turn OFF the Communications switch on the CPM2As CPU Unit or pin 1 of the DIP Switch on the CPM2Cs CPU Unit.)
The CPM2As communications are controlled by the communications switch on the front of the CPU Unit and the CPM2Cs communications are controlled by the DIP switch on the front of the CPU Unit.
261
Section
4-3
CPM2A Communications Switch Setting Turn OFF the communications switch when using 1:1 NT Link communications. One-to-one NT Link communications will not be possible if the communications switch is ON.
RS-232C port
CPM2C DIP Switch Settings Turn OFF pin 1 of the DIP switch when using 1:1 NT Link communications so that communications through the RS-232C port are governed by the settings in the PC Setup (DM 6645 to DM 6649). Front View
CPU Unit with Relay Outputs via Terminal Block CPU Unit with Transistor Outputs via Fujitsu-compatible Connector 4. Status indicators 7. Communications port 6. Output indicators 5. Input indicators 8. Communications switch 9. Customize switch 2. Input terminals 3. Output terminals 2. Input connector 3. Output connector (8) (9) DIP switch for Units with 10/20 I/O points
CPU Unit with Transistor Outputs via MIL Connector 4. Status indicators 7. Communications port 6. Output indicators 5. Input indicators 8. Communications switch 9. Customize switch 2. Input connector 3. Output connector (9) DIP switch for Units with 32 I/O points
(8)
RS-232C port communications p Governed by the PC Setup (DM 6645 to DM 6649) Governed by standard settings
262
Section
4-3
When using an NT Link with a CPM2A/CPM2C PC, the following settings must be made to the PC Setup (DM 6645) using a Programming Device.
Bit 00 to 03 Function Port settings 0: Standard (1 start bit, 7-bit data, 2 stop bits, even parity, 9,600 bps; Host Link unit number: 0) 1: Settings in DM 6646 (Other settings will cause a non-fatal error, the default setting (00) will be used, and AR 1302 will turn ON.) CTS control settings Any 0: Disable 1: Set Link area for 1:1 PC Link 0: LR 00 to LR 15 (Other settings: Disabled) Communications mode 0: Host Link; 1: No-protocol; 2: 1:1 PC Link Slave; 3: 1:1 PC Link Master; 4: 1:1 NT Link (Other settings will cause a non-fatal error, the Host Link setting will be used, and AR 1302 will turn ON.) Any Setting Any
Word DM 6645
04 to 07
08 to 11
12 to 15
For information on the 1:1 NT Link settings of an OMRON Programmable Terminal, refer to that PTs Operation Manual. Connecting the Cables This section describes RS-232C connections. The RS-232C port on the Programmable Terminal and the RS-232C port on the CPM2A/CPM2C or CPM1-CIF01 RS-232C Adapter are connected as shown in the following diagram when there is no CTS control on the RS-232C port. With the CPM2C, the CPM2C-CN111 and CS1W-CN118 connecting cables are used.
263
Section
4-3
RS-232C port
RS-232C port
264
Section
1:1 Link Slave CPM2C CPU Unit
4-3
CPM2C-CN111 (0.1 m)
CS1W-CN118 (0.1 m)
CPM2C-CIF01-V1
CPM2C-CIF01-V1
CPM2C-CIF11
CPM2C-CIF11
OMRON PC (CQM1, CPM1, CPM1A, CPM2A, SRM1(-V2), C200HS, or C200HX/HG/HE) Master Link bits LR00 Write LR07 LR08 Read LR15 Write area Read area
OMRON PC (CQM1, CPM1, CPM1A, CPM2A, SRM1(-V2), C200HS, or C200HX/HG/HE) Slave Link bits LR00 Read area Write area Read LR07 LR08 Write LR15
Note Even though the peripheral port on the CPM2C-CIF01-V1 can output RS-232C, this port cannot be used for one-to-one link communications.
265
Section
4-3
The link relay area on CPM2A/CPM2C PCs is only 16 words, LR00 to LR15. When performing a 1:1 PC Link with a CPM2A/CPM2C PC and a CQM1, C200HS, or C200HX/HE/HG use the corresponding 16 words, LR00 to LR15 on the CQM1, C200HS, or C200HX/HE/HG PC. A 1:1 PC Link with a CPM2A/ CPM2C PC cannot be formed using LR16 to LR 63.
Application Procedure
Setting communications. Use the settings in the PC Setup (DM6645 to DM 6649) for RS-232C communications. (Turn OFF the Communications switch on the CPM2As CPU Unit or pin 1 of the DIP Switch on the CPM2Cs CPU Unit.)
The CPM2As communications are controlled by the communications switch on the front of the CPU Unit and the CPM2Cs communications are controlled by the DIP switch on the front of the CPU Unit. CPM2A Communications Switch Setting Turn OFF the Communications switch when using 1:1 PC Link communications. One-to-one PC Link communications will not be possible if the communications switch is ON.
RS-232C port
266
Section
4-3
CPM2C DIP Switch Settings Turn OFF pin 1 of the DIP switch when using 1:1 PC Link communications so that communications through the RS-232C port are governed by the settings in the PC Setup (DM 6645 to DM 6649). Front View
CPU Unit with Relay Outputs via Terminal Block CPU Unit with Transistor Outputs via Fujitsu-compatible Connector 4. Status indicators 7. Communications port 6. Output indicators 5. Input indicators 8. Communications switch 9. Customize switch 2. Input terminals 3. Output terminals 2. Input connector 3. Output connector (8) (9) DIP switch for Units with 10/20 I/O points
CPU Unit with Transistor Outputs via MIL Connector 4. Status indicators 7. Communications port 6. Output indicators 5. Input indicators 8. Communications switch 9. Customize switch 2. Input connector 3. Output connector (9) DIP switch for Units with 32 I/O points
(8)
RS-232C port communications p Governed by the PC Setup y p (DM 6645 to DM 6649) Governed by standard settings y g
267
Section
4-4
When creating a 1:1 PC Link with a CPM2A/CPM2C PC, use a Programming Device to make the following settings to the PC Setup (DM 6645) in the Master and Slave.
Bit 00 to 03 Function Port settings 00: Standard (1 start bit, 7-bit data, 2 stop bits, even parity, 9,600 bps) 01: Settings in DM 6646 (Other settings will cause a non-fatal error, the default setting (00) will be used, and AR 1302 will turn ON.) CTS control settings 0: Disable 1: Set Link area for 1:1 PC Link 0: LR 00 to LR 15 (Other settings: Disabled) Communications mode 0: Host Link; 1: No-protocol; 2: 1:1 PC Link Slave; 3: 1:1 PC Link Master; 4: 1:1 NT Link (Other settings will cause a non-fatal error, the Host Link setting will be used, and AR 1302 will turn ON.) Master Setting Any Slave Setting Any
Word DM 6645
04 to07
08 to 11
12 to 15
For information on the 1:1 PC Link settings of another OMRON PC, refer to that PCs Operation Manual. Connecting the Cables This section describes the RS-232C connection. The RS-232C cable used for 1:1 PC Links is a cross connection cable. When there is no CTS control on the RS-232C port, the connection is made as shown in the following diagram. With the CPM2C, the CPM2C-CN111 and CS1WCN118 connecting cables are used.
RS-232C port Signal Pin No. RS-232C port Signal Pin No.
Hood
4-4
268
Section
4-4
mands. The SRM1(-V2) supports C-mode commands only. For details on Host Link communications, refer to 4-5 Host Link Commands. PC Setup Settings
Word Bit
The SRM1(-V2)s peripheral port and RS-232C port settings must be set properly in order to use the Host Link communications, as shown in the following table.
Function Setting
Peripheral Port Settings The following settings are effective after transfer to the PC. DM 6650 00 to 03 Port settings 0: Standard (1 start bit, 7-bit data, 2 stop bits, even parity, 9,600 bps) 1: Settings in DM 6651 (Other settings will cause a non-fatal error, the default setting (0) will be used, and AR 1302 will turn ON.) 04 to 07 08 to 11 12 to 15 Not used. Not used. Communications mode 0: Host Link; 1: No-protocol (Other settings will cause a non-fatal error, the default setting (0) will be used, and AR 1302 will turn ON.) Baud rate 00: 1.2K, 01: 2.4K, 02: 4.8K, 03: 9.6K, 04: 19.2K Frame format Start 00: 1 bit 01: 1 bit 02: 1 bit 03: 1 bit 04: 1 bit 05: 1 bit 06: 1 bit 07: 1 bit 08: 1 bit 09: 1 bit 10: 1 bit 11: 1 bit 0 0 0: Host Link To match host parameters
DM 6651
00 to 07
08 to 15
Length 7 bits 7 bits 7 bits 7 bits 7 bits 7 bits 8 bits 8 bits 8 bits 8 bits 8 bits 8 bits
Stop 1 bit 1 bit 1 bit 2 bit 2 bit 2 bit 1 bit 1 bit 1 bit 2 bit 2 bit 2 bit
Parity Even Odd None Even Odd None Even Odd None Even Odd None
DM 6652
00 to 15
(Other settings will cause a non-fatal error, the default setting (00) will be used, and AR 1302 will turn ON.) Transmission delay (Host Link) 0000 to 9999 (BCD): Set in units of 10 ms. (Other settings will cause a non-fatal error, the default setting (0000) will be used, and AR 1302 will turn ON.) Node number (Host Link) 00 to 31 (BCD) (Other settings will cause a non-fatal error, the default setting (0000) will be used, and AR 1302 will turn ON.) Start code enable (RS-232C, effective when bits 12 to 15 of DM 6650 are set to 1.) 0: Disable 1: Set End code enable (RS-232C, effective when bits 12 to 15 of DM 6650 are set to 1.) 0: Disable (number of bytes received) 1: Set (specified end code) 2: CR, LF
DM 6653
00 to 07
08 to 11
Any
12 to 15
Any
269
Section
4-4
Setting Any
08 to 15
Any
Note If an out-of-range value is set, the following communications conditions will result. In that case, reset the value so that it is within the permissible range. Communications mode: Communications format: Host Link Standard settings (1 start bit, 7-bit data; 2 stop bits, even parity, 9,600 bps) No 00
Function Setting
The following settings are effective after transfer to the PC. DM 6645 00 to 03 Port settings 0: Standard (1 start bit, 7-bit data, 2 stop bits, even parity, 9,600 bps) 1: Settings in DM 6646 04 to 07 08 to 11 CTS control settings 0: Disable; 1: Set When using a 1:1 PC Link: Sets the link words for 1:1 PC Link. 0: LR 00 to LR 15 Not 0: Disable When using a 1:N NT Link: Sets the maximum PT node number. 1 to 7 12 to 15 Communications mode 0: Host Link; 1: No-protocol; 2: 1:1 PC Link Slave; 3: 1:1 PC Link Master; 4: 1:1 NT Link; 5: 1:N NT Link (Any other setting specifies Host Link mode, causes a non-fatal error, and turns ON AR 1302.) DM 6646 00 to 07 The 1:N NT Link is supported by SRM1-C02-V2 only. Baud rate 00: 1.2K, 01: 2.4K, 02: 4.8K, 03: 9.6K, 04: 19.2K Frame format Start Length Stop Parity 00: 1 bit 7 bits 1 bit Even 01: 1 bit 7 bits 1 bit Odd 02: 1 bit 7 bits 1 bit None 03: 1 bit 7 bits 2 bit Even 04: 1 bit 7 bits 2 bit Odd 05: 1 bit 7 bits 2 bit None 06: 1 bit 8 bits 1 bit Even 07: 1 bit 8 bits 1 bit Odd 08: 1 bit 8 bits 1 bit None 09: 1 bit 8 bits 2 bit Even 10: 1 bit 8 bits 2 bit Odd 11: 1 bit 8 bits 2 bit None Transmission delay (Host Link) 0000 to 9999 (BCD): Set in units of 10 ms, e.g., setting of 0001 equals 10 ms
08 to 15
DM 6647
00 to 15
270
Section
4-4
DM 6649
00 to 07
Node number (Host Link, effective when bits 12 to 15 of DM 6645 are set to 0.) 00 to 31 (BCD) Start code enable (RS-232C, effective when bits 12 to 15 of DM 6645 are set to 1.) 0: Disable; 1: Set End code enable (RS-232C, effective when bits 12 to 15 of DM 6645 are set to 1.) 0: Disable (number of bytes received) 1: Set (specified end code) 2: CR, LF Start code (RS-232C) 00: 256 bytes 01 to FF: 1 to 255 bytes End code enable (RS-232C) 00 to FF (BIN)
Any
08 to 15
Any
Note If an out-of-range value is set, the following communications conditions will result. In that case, reset the value so that it is within the permissible range. Communications mode: Communications format: Host Link Standard settings (1 start bit, 7-bit data; 2 stop bits, even parity, 9,600 bps) No 00
This example shows a BASIC program that reads the status of the SRM1(-V2)s inputs in IR 000. For more details, refer to 4-5 Host Link Commands. An FCS (frame check sequence) check isnt performed on the received response data in this program. Be sure that the host computers RS-232C port is configured correctly before executing the program.
1000 1010 1020 1050 1060 1070 1080 1090 1100 1110 1120 1130 1140 1150 1160 1170 1180 1190 1200 1210 1220 1230 1240 1250 1260 1270 1280 1290
SRM1 Sample Program for BASIC Set value RS-232C SPEED:9600BPS,PARITY:EVEN,DATA:7,STOP:2 OPEN COM:E73 AS #1 *REPEAT Transmission data input INPUT send data:,SEND$ FCS Calculation FCS=0 FOR IFCS=1 TO LEN(SEND$) FCS=FCS XOR ASC(MID$(SEND$;IFCS,1) NEXT FCS$=RIGHT$(0+HEX$(FCS),2) Communications execute ZZZ$=SEND$+FCS$+*+CHR$(13) PRINT #1,ZZZ$; Response check RECCNT=0:TMP$= *DRECLOOP IF LOC(1)<>0 THEN *DREC1 RECCNT=RECCNT+1 IF RECCNT=5000 THEN *DRECERR ELSE *DRECLOOP *DREC1 TMP$=TMP$+INPUT$(LOC(1),#1) IF RIGHT$(TMP$,1)=CHR$(13) THEN *DRECEND ELSE RECCNT=0:GOTO *DRECLOOP *DRECERR
271
Section
4-4
(@)TXD(48) S C N
S: Leading word no. of data to be transmitted C: Control data N: Number of bytes to be transmitted (4 digits BCD), 0000 to 0256
From the time this instruction is executed until the data transmission is complete, AR 0805 ( or AR0813 for the peripheral port) will remain OFF. (It will turn ON again upon completion of the data transmission.) Start and end codes are not included when the number of bytes to be transmitted is specified. The largest transmission that can be sent with or without start and end codes in 256 bytes, N will be between 254 and 256 depending on the designations for start and end codes. If the number of bytes to be sent is set to 0000, only the start and end codes will be sent.
256 bytes max.
Start code
Data
End code
To reset the RS-232C port (i.e., to restore the initial status), turn on SR 25209. To reset the peripheral port, turn on SR 25208. These bits will turn OFF automatically after the reset. Receptions 1, 2, 3... 1. Confirm that AR 0806 (RS-232C Reception Complete Flag) or AR 0814 (Peripheral Reception Complete Flag) is ON.
272
Section
4-4
(@)RXD(47) D C N
D: Leading word no. for storing reception data C: Control data Bits 00 to 03 0: Leftmost bytes first 1: Rightmost bytes first Bits 12 to 15 0: RS-232C port 1: Peripheral port N: Number of bytes stored (4 digits BCD), 0000 to 0256
3. The results of reading the data received will be stored in the AR area. Check to see that the operation was successfully completed. The contents of these bits will be reset each time RXD(47) is executed.
RS-232C port AR 0800 to AR 0803 AR 0804 AR 0807 Peripheral port AR 0808 to AR 0811 AR0812 AR0815 Error RS-232C port error code (1 digit BCD) 0: Normal completion 1: Parity error 2: Framing error 3: Overrun error Communications error Reception Overrun Flag (After reception was completed, the subsequent data was received before the data was read by means of the RXD(47) instruction.) Number of bytes received
AR 09
AR10
To reset the RS-232C port (i.e., to restore the initial status), turn ON SR 25209. To reset the peripheral port, turn ON SR 25208. These bits will turn OFF automatically after the reset. The start code and end code are not included in AR 09 or AR 10 (number of bytes received). The data will be as follows: 31323132313231323132CR LF Peripheral Port Settings When the peripheral port is used to conduct no-protocol communications, the following settings must be made from the Programming Device to DM 6650 to DM 6653 in the SRM1(-V2).
Function Setting
Word
Bit
Peripheral Port Settings The following settings are effective after transfer to the PC. DM 6650 00 to 03 Port settings 0: Standard (1 start bit, 7-bit data, 2 stop bits, even parity, 9,600 bps) 1: Settings in DM 6651 (Other settings will cause a non-fatal error, the default setting (0) will be used, and AR 1302 will turn ON.) 04 to 07 08 to 11 12 to 15 Not used. Not used. Communications mode 0: Host Link; 1: No-protocol (Other settings will cause a non-fatal error, the default setting (0) will be used, and AR 1302 will turn ON.) 0 0 1: No-protocol As required
273
Section
4-4
Parity Even Odd None Even Odd None Even Odd None Even Odd None
DM 6652
00 to 15
(Other settings will cause a non-fatal error, the default setting (00) will be used, and AR 1302 will turn ON.) Transmission delay (Host Link) 0000 to 9999 (BCD): Set in units of 10 ms. (Other settings will cause a non-fatal error, the default setting (0000) will be used, and AR 1302 will turn ON.) Node number (Host Link) 00 to 31 (BCD) (Other settings will cause a non-fatal error, the default setting (0000) will be used, and AR 1302 will turn ON.) Start code enable (RS-232C, effective when bits 12 to 15 of DM 6650 are set to 1.) 0: Disable 1: Set End code enable (RS-232C, effective when bits 12 to 15 of DM 6650 are set to 1.) 0: Disable (number of bytes received) 1: Set (specified end code) 2: CR, LF Start code (effective when bits 08 to 11 of DM6650 are set to 1.) 00: 256 bytes 01 to FF: 1 to 255 bytes End code (no-protocol) When bits 12 to 15 of DM6653 are set to 0: 00: 256 bytes 01 to FF: 1 to 255 bytes When bits 12 to 15 of DM6653 are set to 1: Setting: 00 to FF (Hex)
DM 6653
00 to 07
08 to 11
As required As required
12 to 15
DM 6654
00 to 07
As required As required
08 to 15
Note If an out-of-range value is set, the following communications conditions will result. In that case, reset the value so that it is within the permissible range. Communications mode: Communications format: Host Link Standard settings (1 start bit, 7-bit data; 2 stop bits, even parity, 9,600 bps) No 00
When the RS-232C port is used to conduct no-protocol communications, the following settings must be made from the Programming Device to DM 6645 to DM 6649 in the SRM1(-V2).
274
Section
4-4
Setting
RS-232C Port Settings The following settings are effective after transfer to the PC. DM 6645 00 to 03 Port settings 0: Standard (1 start bit, 7-bit data, 2 stop bits, even parity, 9,600 bps) 1: Settings in DM 6646 04 to 07 08 to 11 CTS control settings 0: Disable; 1: Set When using a 1:1 PC link: Sets the link words for 1:1 PC Link. 0: LR 00 to LR 15 Not 0: Disable When using a 1:N NT Link: Sets the maximum PT node number. 1 to 7 12 to 15 The 1:N NT Link is supported by SRM1-C02-V2 only. Communications mode 0: Host Link; 1: No-protocol; 2: 1:1 PC Link Slave; 3: 1:1 PC Link Master; 4: 1:1 NT Link; 5: 1:N NT Link (Any other setting specifies Host Link mode, causes a non-fatal error, and turns ON AR 1302.) DM 6646 00 to 07 08 to 15 The 1:N NT Link is supported by SRM1-C02-V2 only. Baud rate 00: 1.2K, 01: 2.4K, 02: 4.8K, 03: 9.6K, 04: 19.2K Frame format Start Length Stop Parity 00: 1 bit 7 bits 1 bit Even 01: 1 bit 7 bits 1 bit Odd 02: 1 bit 7 bits 1 bit None 03: 1 bit 7 bits 2 bit Even 04: 1 bit 7 bits 2 bit Odd 05: 1 bit 7 bits 2 bit None 06: 1 bit 8 bits 1 bit Even 07: 1 bit 8 bits 1 bit Odd 08: 1 bit 8 bits 1 bit None 09: 1 bit 8 bits 2 bit Even 10: 1 bit 8 bits 2 bit Odd 11: 1 bit 8 bits 2 bit None Transmission delay (Host Link) 0000 to 9999 (BCD): Set in units of 10 ms, e.g., setting of 0001 equals 10 ms Node number (Host Link, effective when bits 12 to 15 of DM 6645 are set to 0.) 00 to 31 (BCD) Start code enable (RS-232C, effective when bits 12 to 15 of DM 6645 are set to 1.) 0: Disable; 1: Set End code enable (RS-232C, effective when bits 12 to 15 of DM 6645 are set to 1.) 0: Disable (number of bytes received) 1: Set (specified end code) 2: CR, LF Start code (RS-232C) 00: 256 bytes 01 to FF: 1 to 255 bytes End code enable (RS-232C) 00 to FF (BIN) As required As required 1 As required
DM 6647 DM 6648
00 to 15 00 to 07 08 to 11 12 to 15
DM 6649
00 to 07
08 to 15
Note If an out-of-range value is set, the following communications conditions will result. In that case, reset the value so that it is within the permissible range. Communications mode: Communications format: Host Link Standard settings (1 start bit, 7-bit data; 2 stop bits, even parity, 9,600 bps) No
Transmission delay:
275
Section
4-4
When no-protocol communications are used, TXD(48) is used to send data and RXD(47) to receive data. The maximum amount of data that can be either sent or received is 259 bytes, including the start/end code. No Start or End Code:
Data (256 bytes max.)
Note
1. The start and end codes are set in DM 6648 to DM 6649 and DM 6653 to DM 6654 of the PC Setup. 2. When there are several start and end codes, the first part of each will be effective. 3. When the end code duplicates the transmission data and the transmission is stopped part way through, use CR or LF as the end code. 4. The start and end codes are not stored. When sending data from the SRM1(-V2), check that the Transmission Enable Flag is ON for executing the TXD(48) instruction. The Transmission Enable Flag will turn OFF while the data is being transmitted and will turn ON again when transmission is complete. After the SRM1(-V2) has received data, the Receive Enable Flag turns ON. When the RXD instruction is executed, the data received will be written to the specified words and the Reception Complete Flag will turn OFF.
Flag Transmission Enable Flag Reception Complete Flag Peripheral port AR 0813 AR 0814 RS-232C port AR 0805 AR 0806
Transmission Flags
Note The timing from data reception starting to completion for the SRM1(-V2) is as indicated below. Reception Start: Without start code: With start code: Normal reception status After start code is received.
276
Section
4-4
Reception Complete: When either the end code, the specified no. of bytes, or 256 bytes are received. Program Example The following program example is for no-protocol communication conducted through a RS-232C port using TXD(48) and RXD(47) instructions. If AR 0805 (Transmission Enable Flag) is ON when 00100 is ON, then data from DM0100 to DM0104 is transmitted from higher to lower values. When AR 0806 (Reception Enable Flag) turns ON, 256 bytes of received data are read and written to DM 0200 from higher to lower values.
00100 DIFU(13) 00101 00100 AR0805 @TXD DM0100 #0000 #0010 AR0806 @RXD DM0200 #0000 256 First word to store receive data. Using the RS-232C port data is stored from higher to lower values 256 bytes transmitted First word holding send data. Using the RS-232C port data is stored from higher to lower values 10 bytes transmitted No-protocol communications start
The 1:1 NT Link is possible only with the SRM1-C02-V1/-V2 PCs, which have an RS-232C port. PC Setup Settings
Word Bit DM 6645 00 to 03
The settings relating to 1:1 NT Link PC communications must be set as shown in the following table.
Function Port 00: Standard (1 start bit, 7-bit data, 2 stop bits, even parity, 9,600 bps) 01: Settings in DM 6646 CTS control settings 0: Disable 1: Set settings1 Setting 00 or 01
04 to 07
0 or 1
277
Section
4-4
Setting Any
The 1:N NT Link is supported by SRM1-C02-V2 only. Communications mode1 0: Host Link; 1: No-protocol; 2: 1:1 PC Link Slave; 3: 1:1 PC Link Master; 4: 1:1 NT Link; 5: 1:N NT Link The 1:N NT Link is supported by SRM1-C02-V2 only.
Note
1. If an improper setting is used, a non-fatal error will occur, AR 1302 will be turned ON, and the default setting (0 or 00) will be used. 2. For information on the NT Link settings for another OMRON PC, refer to that PCs Operation Manual. 3. If an out-of-range value is set, the following communications conditions will result. In that case, reset the value so that it is within the permissible range. Communications mode: Host Link Communications format: Standard settings (1 start bit, 7-bit data; 2 stop bits, even parity, 9,600 bps) Transmission delay: No Node number: 00
The 1:N NT Link is possible only with the SRM1-C02-V2 PCs, which have an RS-232C port.
278
Section
4-4
Refer to the SRM1 Master Control Units Operation Manual for information on cable connections in a 1:N NT Link. When the RS-232C port is used for a 1:N NT Link, make the following PC Setup settings from a Programming Device.
Function Port 00: Standard (1 start bit, 7-bit data, 2 stop bits, even parity, 9,600 bps) 01: Settings in DM 6646 CTS control settings 0: Disable 1: Set When using a 1:1 PC link: Sets the link words for 1:1 PC Link. 0: LR 00 to LR 15 Not 0: Disable When using a 1:N NT Link: Sets the maximum PT node number. 1 to 7 settings1 Setting 00 or 01
04 to 07
0 or 1
08 to 11
1 to 7
12 to 15
The 1:N NT Link is supported by SRM1-C02-V2 only. Communications mode1 0: Host Link; 1: No-protocol; 2: 1:1 PC Link Slave; 3: 1:1 PC Link Master; 4: 1:1 NT Link; 5: 1:N NT Link The 1:N NT Link is supported by SRM1-C02-V2 only.
Note
1. If an improper setting is used, a non-fatal error will occur, AR 1302 will be turned ON, and the default setting (0 or 00) will be used. 2. For information on 1:N NT Link settings for OMRON PTs, refer to the PTs Operation Manual. 3. If an out-of-range value is set, the following communications conditions will result. In that case, reset the value so that it is within the permissible range. Communications mode: Communications format: Host Link Standard settings (1 start bit, 7-bit data; 2 stop bits, even parity, 9,600 bps) No 00
RS-232C Port
RS-232C Port
279
Section
4-4
A 1:1 PC Link is possible only with the SRM1-C02-V1/V2 PCs, which are equipped with an RS-232C port. Only the 16 LR words from LR 00 to LR 15 can be linked in the SRM1, so use only those 16 words in the CQM1 or C200HS when making a 1:1 PC Link with one of those PCs. A 1:1 PC Link cannot be made to an SRM1 PC using LR 16 through LR 63 in the CQM1 or C200HS.
Cable Connections
Refer to the SRM1 Master Control Units Operation Manual for information on cable connections in a 1:1 PC Link. When an SRM1(-V2) is used in a 1:1 PC Link, make the following PC Setup settings from a Programming Device.
Function Port settings1 00: Standard (1 start bit, 7-bit data, 2 stop bits, even parity, 9,600 bps) 01: Settings in DM 6651 CTS Control settings 0: Disable 1: Set When using a 1:1 PC Link: Sets the link words for 1:1 PC Link. 0: LR 00 to LR 15 Not 0: Disable When using a 1:N NT Link: Sets the maximum PT node number. 1 to 7 Setting Setting (Master) (Slave) 00 or 01 00 or 01
PC Setup Settings
Word
Bit
DM 6645 00 to 03
04 to 07
08 to 11
12 to 15
Communications mode1 0: Host Link; 1: No-protocol; 2: 1:1 PC Link Slave; 3: 1:1 PC Link Master; 4: 1:1 NT Link; 5: 1:N NT Link
Note
1. If an improper setting is used, a non-fatal error will occur, AR 1302 will be turned ON, and the default setting (0 or 00) will be used. 2. For information on the 1:1 PC Link settings for another OMRON PC, refer to that PCs Operation Manual. 3. If an out-of-range value is set, the following communications conditions will result. In that case, reset the value so that it is within the permissible range. Communications mode: Communications format: Host Link Standard settings (1 start bit, 7-bit data; 2 stop bits, even parity, 9,600 bps) No 00
280
Section
4-5
This example shows ladder programs that copy the status of IR 000 in each SRM1 to IR 200 in the other SRM1. Program in the Master
25313 (Always ON) MOV(21) 000 LR00
LR00 IR 000 IR 200 Write Read LR07 LR08 LR15 Writing area Reading area Reading area Writing area
4-5
Node no.
Header code
Beginning word*
Terminator
Note *Beginning word: 0000 to 0049 and 0200 to 0255 in CPM2A/CPM2C PCs, 0000 to 0019 and 0200 to 0255 in CPM1/CPM1A/SRM1(-V2) PCs. (A response of 0000 will be returned for non-existent IR and SR words.) Response Format
@ x 101 x 100 R
Node no.
Header code
End code
Terminator
Note
1. Words 0050 to 0199 cannot be specified in CPM2A/CPM2C PCs and words 0020 to 0199 cannot be specified in CPM1/CPM1A/SRM1(-V2) PCs. If an attempt to read any of these words is made, a response of 0000 will be returned. 2. The response will be divided when reading more than 30 words of data. Read Data (Response) The contents of the number of words specified by the command are returned in hexadecimal as a response. The words are returned in order, starting with the specified beginning word.
Parameters
281
Section
4-5
Node no.
Header code
Terminator
1. Beginning word: 0000 to 0015 2. No. of words: 0001 to 0016 An end code of 00 indicates normal completion.
L x 161 x 160 x 163 x 162 x 161 x 160 : FCS
Node no.
Header code
End code
Terminator
Parameters
Read Data (Response) The contents of the number of words specified by the command are returned in hexadecimal as a response. The words are returned in order, starting with the specified beginning word.
Node no.
Header code
Terminator
1. Beginning word: 0000 to 0019 2. No. of words: 0001 to 0020 An end code of 00 indicates normal completion.
H x 161 x 160 x 163 x 162 x 161 x 160 : FCS
Node no.
Header code
End code
Terminator
Parameters
Read Data (Response) The contents of the number of words specified by the command are returned in hexadecimal as a response. The words are returned in order, starting with the specified beginning word.
4-5-4 PV READ RC
Reads the contents of the specified number of timer/counter PVs (present values), starting from the specified timer/counter.
282
Section
4-5
Node no.
Header code
Terminator
Note
1. Beginning T/C: 0000 to 0255 in CPM2A/CPM2C PCs, 0000 to 0127 in CPM1/CPM1A/SRM1(-V2) PCs 2. No. of T/Cs: 0001 to 0256 in CPM2A/CPM2C PCs, 0001 to 0128 in CPM1/CPM1A/SRM1(-V2) PCs An end code of 00 indicates normal completion.
Response Format
@ x 101 x 100 R
: FCS
Node no.
Header code
End code
Terminator
The response will be divided when reading more than 30 words of data. Parameters Read Data (Response) The number of present values specified by the command is returned in hexadecimal as a response. The PVs are returned in order, starting with the specified beginning timer/counter.
Node no.
Header code
Terminator
Note
1. Beginning T/C: 0000 to 0255 in CPM2A/CPM2C PCs, 0000 to 0127 in CPM1/CPM1A/SRM1(-V2) PCs 2. No. of T/Cs: 0001 to 0256 in CPM2A/CPM2C PCs, 0001 to 0128 in CPM1/CPM1A/SRM1(-V2) PCs An end code of 00 indicates normal completion.
@ x 101 x 100 Node no. R G x 161 x 160 ON/ OFF End code Read data (1 timer/counter) Read data (for number of TC read) FCS :
Response Format
Header code
Terminator
The response will be divided when reading the status of more than 123 timer/ counters. Parameters Read Data (Response) The status of the number of Completion Flags specified by the command is returned as a response. 1 indicates that the Completion Flag is ON.
283
Section
4-5
Node no.
Header code
Beginning word*
Terminator
Note Beginning word: DM 0000 to DM 1023 and DM 6144 to DM 6655 in CPM1/CPM1A PCs DM 0000 to DM 2047 and DM 6144 to DM 6655 in CPM2A/CPM2C/SRM1(-V2) PCs. (A response of 0000 will be returned for non-existent DM words.) Response Format
@ x 101 x 100 R
Node no.
Header code
End code
Terminator
Note
1. Words DM 1024 to DM 6143 in CPM1/CPM1A PCs and words DM 2048 to DM 6143 in CPM2A/CPM2C/SRM1(-V2) PCs cannot be specified. If an attempt to read any of these words is made, a response of 0000 will be returned. 2. The response will be divided when reading more than 30 words of data. Read Data (Response) The contents of the number of words specified by the command are returned in hexadecimal as a response. The words are returned in order, starting with the specified beginning word.
Parameters
Note Be careful about the configuration of the DM area, as it varies depending on the CPU Unit model.
Node no.
Header code
Terminator
Note
1. Beginning word: 0000 to 0023 in CPM2A/CPM2C PCs, 0000 to 0015 in CPM1/CPM1A/SRM1(-V2) PCs 2. No. of words: 0001 to 0024 in CPM2A/CPM2C PCs, 0001 to 0016 in CPM1/CPM1A/SRM1(-V2) PCs
Response Format
@ x 101 x 100 R
Node no.
Header code
End code
Terminator
284
Section
4-5
Read Data (Response) The contents of the number of words specified by the command are returned in hexadecimal as a response. The words are returned in order, starting with the specified beginning word.
Node no.
Header code
Beginning word*
Terminator
Note
1. Beginning word: 0000 to 0049 and 0200 to 0252 in CPM2A/CPM2C PCs, 0000 to 0019 and 0200 to 0252 in CPM1/CPM1A/SRM1(-V2) PCs. 2. Divide the command when writing more than 30 words of data. An end code of 00 indicates normal completion.
@ x 101 x 100 W R x 161 x 160 : FCS
Response Format
Node no.
Header code
End code
Terminator
Note Words 0050 to 0199 cannot be specified in CPM2A/CPM2C PCs and words 0020 to 0199 cannot be specified in CPM1/CPM1A/SRM1(-V2) PCs. If an attempt is made to write to any of these words, the writing operation will not be executed and normal completion occurs. Parameters Write Data (Command) Specify in order the contents of the number of words to be written to the IR or SR area in hexadecimal, starting with the specified beginning word. Note If data is specified for writing which exceeds the allowable range, an error will be generated and the writing operation will not be executed. If, for example, 252 is specified as the beginning word for writing,and two words of data are specified, then 253 will become the last word for writing data, and the command will not be executed because SR 253 is beyond the writable range.
Node no.
Header code
Beginning word*
Terminator
285
Section
4-5
Node no.
Header code
End code
Terminator
Parameters
Write Data (Command) Specify in order the contents of the number of words to be written to the LR area in hexadecimal, starting with the specified beginning word. Note If data is specified for writing which exceeds the allowable range, an error will be generated and the writing operation will not be executed. If, for example, 12 is specified as the beginning word for writing and five words of data are specified, then 16 will become the last word for writing data, and the command will not be executed because LR 16 is beyond area boundary.
Node no.
Header code
Beginning word*
Terminator
Note Beginning word:0000 to 0019 Response Format An end code of 00 indicates normal completion.
x 101 x 100 x 161 x 160 : FCS
Node no.
Header code
End code
Terminator
Parameters
Write Data (Command) Specify in order the contents of the number of words to be written to the HR area in hexadecimal, starting with the specified beginning word. Note If data is specified for writing which exceeds the allowable range, an error will be generated and the writing operation will not be executed. If, for example, 18 is specified as the beginning word for writing, and three words of data are specified, then 20 will become the last word for writing data, and the command will not be executed because HR 20 is beyond area boundary.
4-5-11 PV WRITE WC
Writes the PVs (present values) of timers/counters starting from the specified timer/counter.
286
Section
4-5
: FCS
Node no.
Header code
Beginning timer/counter*
Terminator
Note
1. Beginning T/C: 0000 to 0255 in CPM2A/CPM2C PCs, 0000 to 0127 in CPM1/ CPM1A/SRM1(-V2) PCs 2. Divide the command when writing more than 29 words of data. An end code of 00 indicates normal completion.
@ x 101 x 100 W C x 161 x 160 : FCS
Response Format
Node no.
Header code
End code
Terminator
Parameters
Write Data (Command) Specify in decimal numbers (BCD) the present values for the number of timers/ counters that are to be written, starting from the beginning timer/counter. Note 1. When this command is used to write data to the PV area, the Completion Flags for the timers/counters that are written will be turned OFF. 2. If data is specified for writing which exceeds the allowable range, an error will be generated and the writing operation will not be executed. If, for example, 126 is specified as the beginning word for writing in a CPM1 PC, and three words of data are specified, then 128 will become the last word for writing data, and the command will not be executed because TC 128 is beyond area boundary.
Node no.
Header code
Terminator
Note
1. Beginning T/C: 0000 to 0255 in CPM2A/CPM2C PCs, 0000 to 0127 in CPM1/ CPM1A/SRM1(-V2) PCs 2. Divide the command when writing the status of more than 118 timer/counters. An end code of 00 indicates normal completion.
@ x 101 x 100 W G x 161 x 160 : FCS
Response Format
Node no.
Header code
End code
Terminator
287
Section
4-5
Write Data (Command) Specify the status of the Completion Flags, for the number of timers/counters to be written, in order (from the beginning word) as ON (i.e., 1) or OFF (i.e., 0). When a Completion Flag is ON, it indicates that the time or count is up. Note If data is specified for writing which exceeds the allowable range, an error will be generated and the writing operation will not be executed. If, for example, 126 is specified as the beginning word for writing in a CPM1 PC, and three words of data are specified, then 128 will become the last word for writing data, and the command will not be executed because TC 128 is beyond area boundary.
Header code
Terminator
Note
1. Beginning word: DM 0000 to DM 1023 and DM 6144 to DM 6655 in CPM1/CPM1A PCs DM 0000 to DM 2047 and DM 6144 to DM 6655 in CPM2A/CPM2C/ SRM1(-V2) PCs 2. Divide the command when writing more than 29 words of data. An end code of 00 indicates normal completion.
@ x 101 x 100 W D x 161 x 160 : FCS
Response Format
Node no.
Header code
End code
Terminator
Note Words DM 1024 to DM 6143 in CPM1/CPM1A PCs and words DM 2048 to DM 6143 in CPM2A/CPM2C/SRM1(-V2) PCs cannot be specified. If an attempt is made to write to any of these words, the writing operation will not be executed for these words and the command will end normally. Parameters Write Data (Command) Specify in order the contents of the number of words to be written to the DM area in hexadecimal, starting with the specified beginning word. Note 1. If data is specified for writing which exceeds the allowable range, an error will be generated and the writing operation will not be executed. If, for example, 1022 is specified as the beginning word for writing in a CPM1 PC, and three words of data are specified, then 1024 will become the last word for writing data, and the command will not be executed because DM 1024 is beyond the writable range. 2. Be careful about the configuration of the DM area, as it varies depending on the CPU Unit model.
288
Section
4-5
: FCS
Node no.
Header code
Beginning word*
Write data (1 word) Write data (for the number of words to write)
Terminator
Note Beginning word: 0000 to 0023 in CPM2A/CPM2C PCs, 0000 to 0015 in CPM1/CPM1A and SRM1(-V2) PCs Response Format An end code of 00 indicates normal completion.
x 101 x 100 Node no. x 161 x 160 End code
:: FCS
Header code
Terminator
Parameters
Write Data (Command) Specify in order the contents of the number of words to be written to the AR area in hexadecimal, starting with the specified beginning word. Note If data is specified for writing which exceeds the allowable range, an error will be generated and the writing operation will not be executed. If, for example, 12 is specified as the beginning word for writing in a CPM1 PC, and five words of data are specified, then 16 will become the last word for writing data, and the command will not be executed because AR 16 is beyond the writable range.
4-5-15 SV READ 1 R#
Searches for the first instance of a timer or counter instruction (TIM, TIMH(15), TIML(), TMHH(), CNT, or CNTR(12)) with the specified TC number in the users program and reads the PV, which is assumed to be set as a constant. The SV that is read is a 4-digit decimal number (BCD). The program is searched from the beginning, which may take as much as 10 seconds to produce a response. Command Format
@ x 101 x 100 Node no. R # OP1 OP2 OP3 OP4 x 103 x 102 x 101 x 100 Name TC number* : FCS
Header code
Terminator
Note TC number: 0000 to 0255 in CPM2A/CPM2C PCs and 0000 to 0127 in CPM1/CPM1A/SRM1(-V2) PCs Response Format
@ x 101 x 100 R # x 161 x 160 x 103 x 102 x 101 x 100 : FCS
Node no.
Header code
End code
SV
Terminator
289
Section
4-5
Name, TC Number (Command) Specify the instruction for reading the SV in Name. Make this setting in 4 characters. In TC number, specify the timer/counter number used for the instruction.
Name OP1 T T T T C C I I I M N N OP2 OP3 M M M H T T OP4 (Space) TIMER H L H R HIGH-SPEED TIMER LONG TIMER VERY HIGH-SPEED TIMER REVERSIBLE COUNTER Instruction name
(Space) COUNTER
SV (Response) The constant SV is returned. Note 1. The instruction specified under Name must be in four characters. 2. If the same instruction is used more than once in a program, only the first one will be read. 3. Use this command only when it is definite that a constant SV has been set. 4. The response end code will indicate an error (16) if the SV wasnt entered as a constant.
4-5-16 SV READ 2 R$
Reads the constant SV or the word address where the SV is stored. The SV that is read is a 4-digit decimal number (BCD) written as the second operand for the TIM, TIMH(15), TIML(), TMHH(), CNT, or CNTR(12) instruction at the specified program address in the users program. This can only be done with a program of less than 10K. Command Format
x 101 x 100
x 103 x 102 x 101 x 100 OP1 OP2 OP3 OP4 x 103 x 102 x 101 x 100
: FCS
Node no.
Header code
Program address
Name
TC number*
Terminator
Note TC number: 0000 to 0255 in CPM2A/CPM2C PCs and 0000 to 0127 in CPM1/CPM1A/SRM1(-V2) PCs Response Format An end code of 00 indicates normal completion.
x 101 x 100
x 161 x 160 OP1 OP2 OP3 OP4 x 103 x 102 x 101 x 100
: FCS
Node no.
Header code
End code
Operand
SV
Terminator
290
Section
4-5
Name, TC Number (Command) Specify the name of the instruction for reading the SV in Name. Make this setting in 4 characters. In TC number, specify the timer/counter number used by the instruction.
Name OP1 T T T T C C I I I M N N OP2 M M M H T T OP3 OP4 (Space) H L H (Space) R TIMER HIGH-SPEED TIMER LONG TIMER VERY HIGH-SPEED TIMER COUNTER REVERSIBLE COUNTER Instruction name
Operand, SV (Response) The name that indicates the SV classification is returned to Operand, and either the word address where the SV is stored or the constant SV is returned to SV.
Operand OP1 OP2 C L H A D D C I R R R M M O OP3 O OP4 (Space) IR or SR Classification Constant or word address CPM2A/ CPM2C PCs 0000 to 0049 0200 to 0255 0000 to 0015 0000 to 0019 0000 to 0023 0000 to 6655 0000 to 6655 0000 to 9999 CPM1 PCs 0000 to 0019 0200 to 0255 0000 to 0015 0000 to 0019 0000 to 0015 0000 to 6655 0000 to 6655 0000 to 9999
(Space) (Space) LR (Space) (Space) HR (Space) (Space) AR (Space) (Space) DM : N (Space) DM (indirect) (Space) Constant
Note The instruction name specified under Name must be in four characters. Fill any gaps with spaces to make a total of four characters.
4-5-17 SV CHANGE 1 W#
Searches for the first instance of the specified TIM, TIMH(15), TIML(), TMHH(), CNT, or CNTR(12) instruction in the users program and changes the SV to new constant SV specified in the second word of the instruction. The program is searched from the beginning, and it may therefore take approximately 10 seconds to produce a response. Command Format
@ x 101 x 100 W # OP1 OP2 OP3 OP4 x 103 x 102 x 101 x 100 x 103 x 102 x 101 x 100 : FCS
Node no.
Header code
Name
TC number*
SV (0000 to 9999)
Terminator
Note TC number: 0000 to 0255 in CPM2A/CPM2C PCs and 0000 to 0127 in CPM1/CPM1A/SRM1(-V2) PCs Response Format An end code of 00 indicates normal completion.
@ x 101 x 100 W # x 161 x 160 : FCS
Node no.
Header code
End code
Terminator
291
Section
4-5
Name, TC Number (Command) In Name, specify the name of the instruction, in four characters, for changing the SV. In TC number, specify the timer/counter number used for the instruction.
Instruction name OP1 T T T T C C I I I M N N OP2 M M M H T T OP3 OP4 (Space) H L H (Space) R TIMER HIGH-SPEED TIMER LONG TIMER VERY HIGH-SPEED TIMER COUNTER REVERSIBLE COUNTER Classification
4-5-18 SV CHANGE 2 W$
Changes the contents of the second word of the TIM, TIMH(15), TIML(), TMHH(), CNT, or CNTR(12) at the specified program address in the users program. This can only be done with a program of less than 10K. Command Format
@ x 101 x 100 W $ x 103 x 102 x 101 x 100 OP1 OP2 OP3 OP4 x 103 x 102 x 101 x 100
Node no.
Header code
Program address
Name
TC number
: FCS
Operand
SV
Terminator
Note TC number: 0000 to 0255 in CPM2A/CPM2C PCs and 0000 to 0127 in CPM1/CPM1A/SRM1(-V2) PCs Response Format An end code of 00 indicates normal completion.
@ x 101 x 100 W $ x 161 x 160 :
Node no.
Header code
End code
FCS
Terminator
Parameters
Name, TC Number (Command) In Name, specify the name of the instruction, in four characters, for changing the SV. In TC number, specify the timer/counter number used for the instruction.
Instruction name OP1 T T T T C C I I I M N N OP2 M M M H T T OP3 OP4 (Space) H L H (Space) R TIMER HIGH-SPEED TIMER LONG TIMER VERY HIGH-SPEED TIMER COUNTER REVERSIBLE COUNTER Classification
292
Section
4-5
Operand, SV (Response) In Operand, specify the name that indicates the SV classification. Specify the name in four characters. In SV, specify either the word address where the SV is stored or the constant SV.
Operand OP1 C L H A D D C OP2 I R R R M M O OP3 O OP4 (Space) IR or SR Classification Constant or word address CPM2A/ CPM2C PCs 0000 to 0049 0200 to 0252 0000 to 0015 0000 to 0019 0000 to 0023 0000 to 2047 6144 to 6655 0000 to 2047 6144 to 6655 0000 to 9999 CPM1/CPM1A/ SRM1(-V2) PCs 0000 to 0019 0200 to 0252 0000 to 0015 0000 to 0019 0000 to 0015 0000 to 1023* 6144 to 6655 0000 to 1023* 6144 to 6655 0000 to 9999
(Space) (Space) LR (Space) (Space) HR (Space) (Space) AR (Space) (Space) DM : N (Space) DM (indirect) (Space) Constant
Node no.
Header code
Terminator
Response Format
@ x 101 x 100 M
Node no.
Header code
End code
Status data
Message
Terminator
293
Section
4-5
Status Data, Message (Response) Status data consists of four digits (two bytes) hexadecimal. The leftmost byte indicates CPU Unit operation mode, and the rightmost byte indicates the size of the program area.
x 163 x 162 12 11 10 9 8
Bit 15
14
13
0
Bit 1: Fatal error generated 9 0 1 1 8 0 0 1 PROGRAM mode RUN mode MONITOR mode This area is different from that of STATUS WRITE. Operation mode
1: FALS generated
x 161 Bit 7 6 5 4 3
x 160 2 1 0
0
Program area write-protection 0: Write-protected 1: Not write-protected
Bit 6 0 0 0 5 0 0 1 4 0 1 0
The Message parameter is a 16-character message that exists when MSG(47) has been executed. When there is no message, this parameter is omitted.
Node no.
Header code
Mode data
FCS
Terminator
Response Format
x 101 x 100
x 161 x 160
Node no.
Header code
End code
FCS
Terminator
294
Section
4-5
Mode Data (Command) Mode data consists of two digits (one byte) hexadecimal. With the leftmost two bits, specify the PC operating mode. Set all of the remaining bits to 0.
x 161 Bit 7 6 5 4 3 x 160 2 1 0
0
Bit 1 0 1 1 0 0 0 1 PROGRAM mode MONITOR mode RUN mode Operation mode
Node no.
Header code
Error clear
FCS
Terminator
Response Format
@ x 101 x 100 M F
Node no.
Header code
End code
FCS
Terminator
Parameters
Error Clear (Command) Specify 01 to clear errors and 00 to not clear errors (BCD). Fatal errors can be cleared only when the PC is in PROGRAM mode. Error Information (Response) The error information comes in two words.
295
Section
4-5
ON: Battery alarm (F7) ON: System error (FAL) ON: Memory error (Error code F1) ON: I/O bus error (Error code C0) ON: No end instruction error (FALS) ON: System error (FAL) 2nd word x 163 Bit 15 14 13 12 11 x 162 10 9 8 7 x 161 6 5 4 3 x 160 2 1 0
FAL, FALS No. (00 to FF) ON: Cycle time overrun (Error code F8) ON: I/O Unit overflow (Error code E1)
SRM1(-V2) PCs
1st word x 163 Bit 15 14 13 12 11 x 162 10 9 8 7 x 161 6 5 4 3 x 160 2 1 0
ON: System error (FAL) ON: Memory error (Error code F1) ON: No end instruction error (FALS) ON: System error (FAL) 2nd word x 163 Bit 15 14 13 12 11 x 162 10 9 8 7 x 161 6 5 4 3 x 160 2 1 0
FAL, FALS No. (00 to 99) ON: Cycle time overrun (Error code F8)
296
Section
4-5
Node no.
Header code
Name
Word address
Bit
FCS
Terminator
Response Format
Node no.
Header code
End code
Terminator
Parameters
Name, Word address, Bit (Command) In Name, specify the area (i.e., IR, SR, LR, HR, AR, or TC) that is to be forced set. Specify the name in four characters. In Word address, specify the address of the word, and in Bit the number of the bit that is to be forced set.
Classification OP4 (Space) IR or SR (Space) (Space) (Space) (Space) H L H (Space) R LR HR AR Completion Flag (timer) Completion Flag (high-speed timer) Completion Flag (long timer) Completion Flag (very high-speed timer) Completion Flag (counter) Completion Flag (reversible counter) Word address setting range CPM2A/ CPM2C PCs 0000 to 0049 0200 to 0252 0000 to 0015 0000 to 0019 0000 to 0023 0000 to 0255 CPM1/ CPM1A/ SRM1(-V2) PCs 0000 to 0019 0200 to 0252 0000 to 0015 0000 to 0019 0000 to 0015 0000 to 0127 Bit OP3 O (Space) (Space) (Space) M M M H T T
00 to 15 (dec a ) (decimal)
Always y 00
Note The area specified under Name must be in four characters. Add spaces after the data area name if it is shorter than four characters.
Node no.
Header code
Name
Word address
Bit
FCS
Terminator
Response Format
Node no.
Header code
End code
Terminator
297
Section
4-5
Name, Word address, Bit (Command) In Name, specify the area (i.e., IR, SR, LR, HR, AR, or TC) that is to be forced reset. Specify the name in four characters. In Word address, specify the address of the word, and in Bit the number of the bit that is to be forced reset.
Classification OP4 Word address setting range CPM2A/ CPM2C PCs 0000 to 0049 0200 to 0252 0000 to 0015 0000 to 0019 0000 to 0023 0000 to 0255 CPM1/CPM1A /SRM1(-V2) PCs 0000 to 0019 0200 to 0252 0000 to 0015 0000 to 0019 0000 to 0015 0000 to 0127 00 to 15 (dec a ) (decimal) Bit
C L H A T T T T C C
I R R R I I I M N N
(Space) IR or SR (Space) (Space) (Space) (Space) H L H (Space) R LR HR AR Completion Flag (timer) Completion Flag (high-speed timer) Completion Flag (long timer) Completion Flag (very high-speed timer) Completion Flag (counter) Completion Flag (reversible counter)
Always 00 y
Note The area specified under Name must be in four characters. Add spaces after the data area name if it is shorter than four characters.
x 101 x 100
Node no.
Header code
Name
Word address :
Terminator
Bit
15
14
13
12
11
10
Response Format
x 101 x 100
x 161 x 160
: FCS
Node no.
Header code
End code
Terminator
298
Section
4-5
Name, Word address (Command) In Name, specify the area (i.e., IR, SR, LR, HR, AR, or TC) that is to be forced set or reset. Specify the name in four characters. In Word address, specify the address of the word that is to be forced set or reset.
Classification OP4 (Space) IR or SR Word address setting range CPM2A/CPM2C PCs 0000 to 0049 0200 to 0252 0000 to 0015 0000 to 0019 0000 to 0023 0000 to 0255 0000 to 0255 CPM1/CPM1A/ SRM1(-V2) PCs 0000 to 0019 0200 to 0252 0000 to 0015 0000 to 0019 0000 to 0015 0000 to 0127 0000 to 0127 0000 to 0127 0000 to 0127 OP3 O
(Space) (Space) LR (Space) (Space) HR (Space) (Space) AR M M M H T T (Space) Completion Flag (timer) H L Completion Flag (high-speed timer) Completion Flag (long timer)
0000 to 0255 H Completion Flag (very high-speed timer) 0000 to 0255 (Space) Completion Flag (counter) R Completion Flag (reversible counter)
Forced set/Reset/Cancel data (Command) If a timer or counter completion flag is specified, only bit 15 is effective and all other bits will be ignored. Only force-setting and force-resetting are possible for timers/counters. If a word address is specified, the content of the word specifies the desired process for each bit in the specified word, as shown in the following table.
Hexadecimal setting 0000 0002 0003 0004 0005 0008 Reset Set Forced-reset Forced-set Forced set/reset status cancel Process No action (bit status not changed)
The bits that are merely set or reset may change status the next time the program is executed, but bits that are force-set or force-reset will maintain the forced status until it is cleared. Response Format An end code of 00 indicates normal completion.
@ x 101 x 100 F K x 161 x 160 : FCS
Node no.
Header code
End code
Terminator
Node no.
Header code
Terminator
299
Section
4-5
Node no.
Header code
End code
Terminator
Node no.
Header code
Terminator
Response Format
Node no.
Header code
End code
Model code
Terminator
Parameters
Model Code Model code indicates the PC model in two digits hexadecimal.
Model code 01 02 03 0E 10 11 12 20 21 22 40 41 42 C250 C500 C120 C2000 C1000H C2000H/CQM1/CPM2A/CPM2C/CPM1/CPM1A/SRM1(-V2) C20H/C28H/C40H/C200H/C200HS CV500 CV1000 CV2000 CVM1-CPU01-E CVM1-CPU11-E CVM1-CPU21-E Model
4-5-27 TEST TS
Returns, unaltered, one block of data transmitted from the host computer. Command Format
@ x 101 x 100 T S 122 characters max. : FCS
Node no.
Header code
Characters
Terminator
300
Section
4-5
: FCS
Node no.
Header code
Characters
Terminator
Parameters
Characters (Command, Response) For the command, this setting specifies any characters other than the carriage return (CHR$(13)). For the response, the same characters as specified by the command will be returned unaltered if the test is successful.
Node no.
Header code
Terminator
Response Format
Node no.
Header code
End code
Terminator
Parameters
Program (Response) The program is read from the entire program area. Note To stop this operation in progress, execute the ABORT (XZ) command.
Node no.
Header code
1 byte
Terminator
Response Format
Node no.
Header code
End code
Terminator
Parameters
301
Section
4-5
,
Data break
Node no.
Header code
Sub-header code
Read area
Data format
,
Data break
OP1 OP2 OP3 OP4 x 103 x 102 x 101 x 100 OP1 OP2
: FCS
Read area
Data format
Terminator
Response Format
Node no.
Header code
Terminator
Parameters
Read Area (Command) Specify in four-character code the area that is to be read. The codes that can be specified are listed in the following table.
302
Section
4-5
Read Word address, Data Format (Command) Depending on the area and type of data that are to be read, the information to be read is as shown in the following table. The read data is specified in four digits BCD, and the data format is specified in two digits BCD.
Area l ifi ti classification Read data Read area Read word CPM2A/ CPM2C PCs CPM1/ CPM1A/ SRM1(-V2) PCs 0000 to 0019 0200 to 0255 Data format
IR or SR LR HR AR Timer High-speed timer g p Long timer g Very high-speed timer y g p Counter Reversible counter DM
Bit Word Bit Word Bit Word Bit Bit Completion Flag PV Completion Flag PV Completion Flag PV Completion Flag PV Completion Flag PV Completion Flag PV Word
CIO( ) (S) LR( )( ) (S) (S) H R (S) (S) ( )( ) AR( )( ) (S) (S) T I M (S) ( ) TIMH TIML TMHH C N T (S) ( ) CNTR D M (S) (S)
0000 to 0049 0200 to 0255 0000 to 0015 0000 to 0019 0000 to 0023 0000 to 0255 0000 to 0255 0000 to 0255 0000 to 0255 0000 to 0255 0000 to 0255 0000 to 2047 6144 to 6655
00 to 15 (decimal) CH 0000 to 0015 00 to 15 (decimal) CH 0000 to 0019 00 to 15 (decimal) CH 0000 to 0015 00 to 15 (decimal) CH 0000 to 0127 2 characters other than CH CH 0000 to 0127 2 characters other than CH CH Not used. 2 characters other than CH CH Not used. 2 characters other than CH CH 0000 to 0127 2 characters other than CH CH 0000 to 0127 2 characters other than CH CH 0000 to 1023* Any 2 characters 6144 to 6655
Note *For SRM1(-V2) PCs, the DM range is from 0000 to 2047. (S): Space Data Break (Command) The read information is specified one item at a time separated by a break code (,). The maximum number of items that can be specified is 128. (When the PV of a timer/counter is specified, however, the status of the Completion Flag is also returned, and must therefore be counted as two items.)
Batch Reading
The bit, word, and timer/counter status is read as a batch according to the read information that was registered with QQ. Command Format
x 101 x 100
: FCS
Node no.
Header code
Sub-header code
Terminator
303
Section
An end code of 00 indicates normal completion.
I R x 161 x 160 ON/ x 103 x 102 x 101 x 100 OFF ,
4-5
Node no.
Header code
Data break Timer/counter If PV is specified the status of the Completion Flag is also returned.
ON/ OFF
: FCS
Terminator
Parameters
Read Data (Response) Read data is returned according to the data format and the order in which read information was registered using QQ. If Completion Flag has been specified, then bit data (ON or OFF) is returned. If Word has been specified, then word data is returned. If PV has been specified for timers/counters, however, then the PV is returned following the Completion Flag. Data Break (Response) The break code (, ) is returned between sections that are read.
4-5-31 ABORT XZ
Aborts the Host Link operation that is currently being processed, and then enables reception of the next command. The ABORT command does not receive a response. Command Format
@ x 101 x 100 X Z : FCS
Node no.
Header code
Terminator
4-5-32 INITIALIZE ::
Initializes the transmission control procedure of all the PCs connected to the host computer. The INITIALIZE command does not use node numbers or FCS, and does not receive a response. Command Format
@ : :
304
Section
4-5
: FCS
Node no.
Header code
Terminator
Parameters
Characters (Response) This is the data specified in TXD(48) that has been converted to ASCII.
Node no.
Header code
Terminator
305
5-2
5-3
307
Section
5-1
5-1
AR 00 to AR 15 AR 0000 to AR 1515 (16 words) (256 bits) LR 00 to LR 15 LR 0000 to LR 1515 (16 words) (256 bits) TC 000 to TC 127 (timer/counter numbers)3
Work bits can be freely used within the program. These bits serve specific functions such as flags and control bits. These bits are used to temporarily store ON/OFF status at program branches. These bits store data and retain their ON/ OFF status when power is turned off, or operation starts or stops. They are used in the same way as work bits. These bits serve specific functions such as flags and control bits. Used for a 1:1 PC Link with another PC. Timers and counters use the TIM, TIMH(15), CNT and CNTR(12) instructions. The same numbers are used for both timers and counters. DM area data can be accessed in word units only. Word values are retained when the power is turned off, or operation started or stopped. Read/write areas can be read and written freely within the program. Used to store the time of occurrence and error code of errors that occur. These words can be used as ordinary read/write DM when the error log function is not being used. Cannot be overwritten from program. Used to store various parameters that control PC operation.
DM area Read/write2
Error log
Read-only4 PC Setup4
Note
1. IR and LR bits that are not used for their allocated functions can be used as work bits. 2. The contents of the HR area, AR area, Counter area, and read/write DM area are backed up by a capacitor. The backup time varies with the ambient temperature, but at 25_C, the capacitor will back up memory for 20 days. If the power supply is off longer than the backup time, memory contents will be cleared and AR1314 will turn ON. (This flag turns ON when data can no longer be retained by the built-in capacitor.) Refer to 2-1-2 Characteristics in the CPM1 and CPM1A Operation Manual for a graph showing the backup time vs. temperature. 3. When accessing a PV, TC numbers are used as word data; when accessing Completion Flags, they are used as bit data. 4. Data in DM 6144 to DM 6655 cannot be overwritten from the program, but they can be changed from a Programming Device.
308
Section
The following memory areas can be used with the CPM2A/CPM2C.
Words Bits IR 00000 to IR 00915 (160 bits) IR 01000 to IR 01915 (160 bits) IR 02000 to IR 04915, IR 20000 to IR 22715 (928 bits) Function
5-1
IR 000 to IR 009 (10 words) IR 010 to IR 019 (10 words) IR 020 to IR 049, IR 200 to IR 227 (58 words) SR 228 to SR 255 (28 words) --HR 00 to HR 19 (20 words)
SR 22800 to SR 25515 These bits serve specific functions such as (448 bits) flags and control bits. TR 0 to TR 7 (8 bits) HR 0000 to HR 1915 (320 bits) These bits are used to temporarily store ON/OFF status at program branches. These bits store data and retain their ON/ OFF status when power is turned OFF, or operation starts or stops. They are used in the same way as work bits. These bits serve specific functions such as flags and control bits. Used for a 1:1 PC Link with another PC. Timers and counters use the TIM, TIMH(15), CNT, CNTR(12), TMHH(), and TIML() instructions. The same numbers are used for both timers and counters. DM area data can be accessed in word units only. Word values are retained when the power is turned off, or operation started or stopped. Read/write areas can be read and written freely within the program. Used to store the time of occurrence and error code of errors that occur. These words can be used as ordinary read/write DM when the error log function isnt being used. Cannot be overwritten from program. Used to store various parameters that control PC operation.
DM area Read/write2
Error log
Read-only4,5 PC Setup4,5
Note
1. IR and LR bits that are not used for their allocated functions can be used as work bits. 2. The contents of the HR area, AR area, Counter area, and read/write DM area are backed up by the CPU Units battery. If the battery is removed or fails, the contents of these areas will be lost and returned to default values. (In CPM2C CPU Units without a battery, these areas are backed up by a capacitor.) 3. When a TC numbers is used as a word operand, the timer or counter PV is accessed; when used as a bit operand, its Completion Flag is accessed. 4. Data in DM 6144 to DM 6655 cannot be overwritten from the program, but they can be changed from a Programming Device. 5. The program and data in DM 6144 to DM 6655 are stored in flash memory.
309
Section
The following memory areas can be used with the SRM1(-V2).
Words Bits IR 00000 to IR 00715 (128 bits) IR 01000 to IR 01715 (128 bits) Function
5-1
IR 000 to IR 007 (8 words) IR 010 to IR 017 (8 words) IR 008 to IR 009 IR 018 to IR 019 IR 200 to IR 239 (44 words) SR 240 to SR 255 (16 words) --HR 00 to HR 19 (20 words)
These bits are allocated to the external I/O terminals. The ON/OFF status of the I/O bits will be the same as the ON/OFF status of the I/O terminals
Output area
Work area
(When the CompoBus/S is used in 128-bit mode, IR 004 to IR 007 and IR 014 to IR 017 can also be used as work bits.) IR 00800 to IR 00915 Work bits can be freely used within the proIR 01800 to IR 01915 gram. IR 232 to IR 239 however, are used IR 20000 to IR 23915 as the MACRO input area when MCRO(99) (704 bits) is being used. SR 24000 to SR 25507 These bits serve specific functions such as (248 bits) flags and control bits. TR 0 to TR 7 (8 bits) HR 0000 to HR 1915 (320 bits) These bits are used to temporarily store ON/OFF status at program branches. These bits store data and retain their ON/ OFF status when power is turned off, or operation starts or stops. They are used in the same way as work bits. These bits serve specific functions such as flags and control bits. AR 04 to 07 are used as slaves. Refer to AR Area. Used for a 1:1 PC Link with another PC. Timers and counters use the TIM, TIMH(15), CNT and CNTR(12) instructions. The same numbers are used for both timers and counters. DM area data can be accessed in word units only. Word values are retained when the power is turned off, or operation started or stopped. Read/write areas can be read and written freely within the program. Used to store the time of occurrence and error code of errors that occur. These words can be used as ordinary read/write DM when the error log function is not being used. Cannot be overwritten from program. Used to store various parameters that control PC operation.
AR area2
DM area Read/write2
Error log
Read-only4 PC Setup4
Note
1. IR and LR bits that are not used for their allocated functions can be used as work bits. 2. The contents of the HR area, AR area, Counter area, and read/write DM area are backed up by a capacitor or a battery. Refer to 2-1-2 Characteristics in the SRM1 Master Control Unit Operation Manual for a graph showing the backup time vs. temperature. 3. When accessing a PV, TC numbers are used as word data; when accessing Completion Flags, they are used as bit data. 4. Data in DM 6144 to DM 6655 cannot be overwritten from the program, but they can be changed from a Programming Device.
310
Section
5-1
5-1-2 Functions
IR Area The functions of the IR area are explained below. With CPM1, CPM1A, CPM2A, and CPM2C PCs, IR area bits from IR 00000 to IR 01915 are allocated to terminals on the CPU Unit and Expansion I/O Units. With the SRM1(-V2), IR area bits from IR 00000 to IR 00715 and IR 01000 to IR 01715 are allocated to CompoBus/S Slaves. They reflect the ON/OFF status of input and output signals. Input bits begin at IR 00000, and output bits begin at IR 01000. IR words that are not allocated to inputs or outputs can be used as work words. In addition, unused bits in IR words allocated to outputs can be used as work bits. The work bits can be used freely within the program. They can only be used within the program, however, and not for direct external I/O. Note 1. The input bits shown in the following tables can operate as normal inputs or they can be assigned special functions in the PC Setup. Special functions for input bits IR 00000 through IR 00002 are set in DM 6642:
Bit dd address IR 00000 IR 00001 IR 00002 PC Setup setting (DM 6642 bits 08 to15) 00 Used as normal inputs. inputs 01 Used as high-speed counter inputs. inputs 02, 03, or 04 Used as inputs for synchronized pulse control. Used as a normal input.
Work Bits
Special functions for input bits IR 00003 through IR 00006 are set in DM 6628:
Bit address dd IR 00003 IR 00004 IR 00005* IR 00006* Bits in DM 6628 00 to 03 04 to 07 08 to 11 12 to 15 PC Setup setting (in DM 6628) 0 Used as normal inputs. i 1 Used as interrupt inputs i i (including counter mode). 2 Used as quick-response i k inputs. inputs
Note *Input 00006 does not exist and input 00005 must be used as a normal input in CPM2C CPU Units with 10 I/O points. 2. Output bits IR 01000 and IR 01001 can operate as normal inputs or they can be used for pulse outputs with PULS(65), SYNC(), or PWM(). (Use a CPU Unit with transistor outputs for the pulse output functions.)
Instruction PULS(65) Function With SPED(64): Single-phase pulse output without acceleration or deceleration With ACC(): Single-phase pulse output with trapezoidal acceleration and deceleration Synchronized pulse control output Variable duty-ratio pulse output
SYNC() PWM()
SR Area
These bits mainly serve as flags to PC operation or contain present and set values for various functions. For details on the various bit functions, refer to relevant sections in this manual or to Appendix C Memory Areas. Some SR area words can be used as work words when they are not used for their assigned purpose. When a complex ladder diagram cannot be programmed in mnemonic code just as it is, these bits are used to temporarily store ON/OFF execution conditions at
TR Area
311
Section
5-1
program branches. They are used only for mnemonic code. When programming directly with ladder diagrams using the SYSMAC Support Software (SSS) or the SYSMAC-CPT Support Software, TR bits are automatically processed for you. The same TR bits cannot be used more than once within the same instruction block, but can be used again in different instruction blocks. The ON/OFF status of TR bits cannot be monitored from a Programming Device. Examples showing the use of TR bits in programming are provided on page 350. HR Area These bits retain their ON/OFF status even after the PC power supply has been turned off or when operation begins or stops. They are used in the same way as work bits. These bits mainly serve as flags related to PC operation. These bits retain their status even after the PC power supply has been turned off or when operation begins or stops. For details on the various bit functions, refer to relevant sections in this manual or to Appendix C Memory Areas. When the CPM1/CPM1A/CPM2A/CPM2C/SRM1(-V2) is linked 1:1 with another CPM1/CPM1A/CPM2A/CPM2C/SRM1(-V2), a CQM1, an C200HS or C200HX/HG/HE PC, these bits are used to share data. For details, refer to page 229. LR bits can be used as work bits when not used for 1:1 PC Links. This area is used to manage timers and counters created with TIM, TIMH(15), TMHH()*, TIML()*, CNT, and CNTR(12). The same numbers are used for both timers and counters and each number can be used only once in the user program. Do not use the same TC number twice even for different instructions. Use TC numbers 000 through 003 for TIMH(15) and TC numbers 004 to 007 for TMHH()*. When these timer numbers are used, timing is performed as an interrupt process and the cycle timer does not affect timer operation. TC numbers are used to create timers and counters, as well as to access Completion Flags and present values (PVs). If a TC number is designated for word data, it will access the present value (PV); if it is used for bit data, it will access the Completion Flag for the timer/counter. Refer to instructions beginning on page 388 for details on timers and counters. DM area data is accessed in word units only. The contents of the DM area are retained even after the PC power supply has been turned off or when operation begins or stops. CPM1/CPM1A DM words DM 0000 through DM 0999, DM 1022, and DM 1023 can be used freely in the program; other DM words are allocated specific functions, described below. DM 1000 through DM 1021 contain the error log information. Refer to Section 9 Troubleshooting for details on the error log. CPM2A/CPM2C DM words DM 0000 through DM 1999 and DM 2022 through DM 2047 can be used freely in the program; other DM words are allocated specific functions, described below. DM 2000 through DM 2021 contain the error log information. Refer to Section 9 Troubleshooting for details on the error log. SRM1(-V2) DM words DM 0000 through DM 1999 can be used freely in the program; other DM words are allocated specific functions, described below. DM 2000 through DM 2021 contain the error log information. Refer to Section 9 Troubleshooting for details on the error log. Note DM 6600 through DM 6655 contain the PC Setup. Refer to 1-1 PC Setup for details.
AR Area
LR Area
Timer/Counter Area
DM Area
312
Section
5-2
5-2
CPM1
6 inputs: 00000 to 00005 4 outputs: 01000 to 01003 12 inputs: 00000 to 00011 8 outputs: 01000 to 01007 18 inputs: 00000 to 00011 00100 to 00105 12 outputs: 01000 to 01007 01100 to 01103 18 inputs: 00000 to 00011 00100 to 00105 12 outputs: 01000 to 01007 01100 to 01103
Output
30
CPM1-30CDR-j-V1
Input
3 (see note 2)
90
Output
313
Section
5-2
1. The values for the maximum number of I/O in the above table include I/O on Expansion I/O Units. 2. When using a CPM1 CPU Unit other than the CPM1-30CDR-j-V1, one of the following 20-point Expansion I/O Units can be connected to the PC: CPM1-20EDR (relay outputs) CPM1A-20EDRT (sinking transistor outputs) CPM1A-20EDT1 (sourcing transistor outputs) 3. When using the CPM1-30CDR-j-V1, up to 3 CPM1/CPM1A Expansion I/O Units or CPM1A-MAD01 Analog I/O Units can be connected to the PC.
CPM1A
No. of I/O (on CPU Unit) 10 Model number I/O Allocated bits Max. No. of Expansion I/O Units None Max. No. of I/O (see note 1) 10
6 inputs: 00000 to 00005 4 outputs: 01000 to 01003 12 inputs: 0000 to 00011 8 outputs: 01000 to 01007 18 inputs: 00000 to 00011 00100 to 00105 12 outputs: 01000 to 01007 01100 to 01103 24 inputs: 00000 to 00011 00100 to 00111 16 outputs: 01000 to 01007 01100 to 01107
20
None
20
30
3 (see note)
90
Output
40
Inputs
3 (see note)
100
Output
Note
1. The values for the maximum number of I/O in the above table include I/O on Expansion I/O Units. 2. When using a CPM1A CPU Unit with 30 or 40 I/O points, up to 3 Expansion Units or Expansion I/O Units can be connected to the PC.
314
Section
5-2
12 inputs: 0000 to 00011 8 outputs: 01000 to 01007 18 inputs: 00000 to 00011 00100 to 00105 12 outputs: 01000 to 01007 01100 to 01103 24 inputs: 00000 to 00011 00100 to 00111 16 outputs: 01000 to 01007 01100 to 01107 36 inputs: 00000 to 00011 00100 to 00111 00200 to 00211 24 outputs: 01000 to 01007 01100 to 01107 01200 to 01207
30
90
Output
40
Input
100
Output
60
Input
120
Output
Note
1. The values for the maximum number of I/O in the above table include the I/O on Expansion I/O Units. 2. When using a CPM2A CPU Unit, up to 3 Expansion Units or Expansion I/O Units can be connected to the PC.
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Do not use
Outputs IR 010
315
Section
5-2
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Do not use
Outputs IR 010
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Do not use
24 inputs IR 00000 to IR 00011 IR 00100 to IR 00111 16 outputs IR 01000 to IR 01007 IR 01100 to IR 01107
CPM1A-40CDj-j CPM2A-40CDj-j
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Do not use
316
Section
5-2
CPM1A-60CDj-j CPM2A-60CDj-j
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Do not use
20
20
Note m: m denotes the last input word allocated to the CPU Unit, or to the previous Expansion Unit or Expansion I/O Unit if one is already connected. n: n denotes the last output word allocated to the CPU Unit, or to the previous Expansion Unit or Expansion I/O Unit if one is already connected.
317
Section
5-2
CPM1A-8ED
No outputs
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Do not use
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Do not use
Note
1. m: m denotes the last input word allocated to the CPU Unit, or to the previous Expansion Unit or Expansion I/O Unit if one is already connected.
318
Section
5-2
n: n denotes the last output word allocated to the CPU Unit, or to the previous Expansion Unit or Expansion I/O Unit if one is already connected. 2. Only CPM1 CPU Units with the -V1 suffix can have 3 Analog I/O Units connected. CPU Units without the -V1 suffix can only have one Analog I/O Unit connected. 3. Only one CPM1A-TS002/102 Temperature Sensor Unit can be connected to the PC. If a CPM1A-TS002/102 Temperature Sensor Unit is connected to the PC, one more Expansion Unit (other than another CPM1A-TS002/102 Temperature Sensor Unit) or Expansion I/O Unit can be connected. Analog I/O Unit CPM1A-MAD01/MAD11
2 analog inputs Input 0: word (m+1) Input 1: word (m+2) 1 analog output Output 0: word (n+1)
CPM1A-TS002/TS102
4 temperature inputs Input 0: word (m+1) Input 1: word (m+2) Input 2: word (m+3) Input 3: word (m+4) No outputs
No outputs
CompoBus/S I/O Link Unit and DeviceNet I/O Link Unit CPM1A-SRT21
8 bits Input: word (m+1)
CPM1A-DRT21
32 bits Input: word (m+1, m+2)
Note Input bits 00 to 07 in word (m+1) are for outputs from the Master. Output bits 00 to 07 in word (n+1), are for inputs to the Master.
319
Section
5-2
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
IR 00000 to IR 00011 and IR 00100 to IR 00111 are allocated as input bits. IR 00012 to 00015 cannot be used. IR 01000 to IR 01007 and IR 01100 to IR 01107 are allocated as output bits. IR 01108 to IR 01115 can be used as work bits. IR 002 to IR 009 of the input words and IR 012 to IR 019 of the output words can all be used as work words. Example: CPU Unit with 30 I/O Points + 3 Expansion I/O Units with 20 I/O Points
Bits IR 000 IR 001 Inputs IR 002 IR 003 IR 004 IR 010 IR 011 Outputs IR 012 IR 013 IR 014
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Do not use Do not use Do not use Do not use Do not use
320
Section
5-2
Bits IR 000 IR 001 Inputs IR 002 IR 003 IR 004 IR 010 IR 011 Outputs IR 012 IR 013 IR 014 IR 015
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Do not use Do not use Do not use Do not use Do not use
321
Section
5-2
Example: Configuration Including Analog I/O Unit, Temperature Sensor Unit, and Expansion I/O Unit CPU Unit (60 I/O points)
36 inputs IR 00000 to IR 00011 IR 00100 to IR 00111 IR 00200 to IR 00211
No outputs
Bits IR 000 IR 001 Inputs IR 002 IR 003 IR 004 IR 005 IR 006 IR 007 IR 010 IR 011 Outputs IR 012 IR 013 IR 014
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Do not use Do not use Do not use Used for input 0 of the Analog I/O Unit Used for input 1 of the Analog I/O Unit Used for input 0 of the Temperature Sensor Unit Used for input 1 of the Temperature Sensor Unit Do not use
With the exception of CPM1A-TS002/102 Temperature Sensor Units, up to 3 Expansion Units (Analog I/O Units, Temperature Sensor Units, or CompoBus/S Units) can be connected to a CPM1A or CPM2A PC. Only one CPM1A-TS002/102 Temperature Sensor Unit can be connected. (See page 323 for an example of CPM1A-TS002/102 allocations.)
322
Section
5-3
Example: Configuration Including Temperature Sensor Unit with 4 Inputs and CompoBus/S Link Unit CPU Unit (60 I/O points)
36 inputs IR 00000 to IR 00011 IR 00100 to IR 00111 IR 00200 to IR 00211
No outputs
Bits IR 000 IR 001 Inputs IR 002 IR 003 IR 004 IR 005 IR 006 IR 007 IR 010 Outputs IR 011 IR 012 IR 013
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Do not use Do not use Do not use Used for input 0 of the Temperature Sensor Unit Used for input 1 of the Temperature Sensor Unit Used for input 1 of the Temperature Sensor Unit Used for input 1 of the Temperature Sensor Unit Do not use
Only one 4-input Temperature Sensor Unit (CPM1A-TS002/102) can be connected to the PC. The CPM1A-TS002/102 can, however, be connected together with an Expansion I/O Unit or a different Expansion Unit.
5-3
6 inputs: 00000 to 00005 4 outputs: 01000 to 01003 12 inputs: 00000 to 00011 8 outputs: 01000 to 01007 16 inputs: 00000 to 00007 and 00100 to 00107 Outputs 16 outputs: 01000 to 01007 and 01100 to 01107
Note
1. The values for the maximum number of I/O in the above table include the I/O on Expansion I/O Units. 2. Although only up to 5 Expansion Units or Expansion I/O Units can be connected to a CPM2C PC, no more than 10 input words and 10 output words can be allocated.
323
Section
5-3
In the following diagrams, shaded areas indicate bits actually used for inputs or outputs. Input bits are allocated starting from IR 00000. Output bits are allocated starting from IR 01000. Bits in the output words that are not used as output bits can be used as work bits. Bits in the input words that are not used as input bits cannot be used as work bits.
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Do not use
Outputs IR 010
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Do not use
Outputs IR 010
324
Section
5-3
02
01
00
Do not use
02
01
00
16 10 20 24 32
Note m: m denotes the last input word allocated to the CPU Unit, or to the previous Expansion Unit or Expansion I/O Unit if one is already connected. n: n denotes the last output word allocated to the CPU Unit, or to the previous Expansion Unit or Expansion I/O Unit if one is already connected.
In the following diagrams, shaded areas indicate bits actually used for inputs or outputs. Input bits are allocated to Expansion I/O Units starting from word (m+1), where m is the last input word allocated to the CPU Unit, or to the previous Expansion Unit or Expansion I/O Unit if one is already connected. Output bits are allocated to Expansion I/O Units starting from word (n+1), where n is the last output word allocated to the CPU Unit, or to the previous Expansion Unit or Expansion I/O Unit if one is already connected.
325
Section
5-3
Bits in the output words that are not used as output bits can be used as work bits. Bits in the input words that are not used as input bits can be used as work bits. Expansion I/O Unit with 8 Inputs
8 inputs Word (m+1), bit 00 to Word (m+1), bit 07
CPM2C-8EDC CPM2C-8EDM
No outputs
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Do not use
CPM2C-16EDC CPM2C-16EDM
No outputs
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
326
Section
5-3
CPM2C-10EDR
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Do not use
CPM2C-20EDR
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Do not use
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
327
Section
5-3
16 inputs Word (m+1), bit 00 to Word (m+1), bit 15 16 outputs Word (n+1), bit 00 to Word (n+1), bit 15
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Note
1. m: m denotes the last input word allocated to the CPU Unit, or to the previous Expansion Unit or Expansion I/O Unit if one is already connected. n: n denotes the last output word allocated to the CPU Unit, or to the previous Expansion Unit or Expansion I/O Unit if one is already connected. 2. Because the CPM2C-MAD11 Analog I/O Unit and the CPM2C-TS001/101 Temperature Sensor Units require 2 I/O words each, only 4 of these Units can be connected to the PC. (The CPU Unit itself requires one input word and one output word.) A different Unit, such as an Expansion I/O Unit or the CPM2C-SRT21 CompoBus/S I/O Link Unit, can, however, be connected in addition to 4 Analog I/O Units or Temperature Sensor Units. Analog I/O Unit
CPM2C-MAD11
2 analog inputs Input 0: word (m+1) Input 1: word (m+2)
328
Section
5-3
No outputs
Note Input bits 00 to 07 in word (m+1) are for outputs from the Master. Output bits 00 to 07 in word (n+1), are for inputs to the Master.
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Do not use
329
Section
5-3
Expansion I/O Unit (32 I/O points) 16 inputs IR 00200 to IR 00215 16 outputs IR 01200 to IR 01215
Expansion I/O Unit (32 I/O points) 16 inputs IR 00300 to IR 00315 16 outputs IR 01300 to IR 012315
Expansion I/O Unit (32 I/O points) 16 inputs IR 00400 to IR 00415 16 outputs IR 01400 to IR 01415
Expansion I/O Unit (32 I/O points) 16 inputs IR 00500 to IR 00515 16 outputs IR 01500 to IR 01515
Expansion I/O Unit (32 I/O points) 16 inputs IR 00600 to IR 00615 16 outputs IR 01600 to IR 01615
16 outputs
IR 01000 to IR 01007 and IR 01100 to IR 01107
Bits IR 000 IR 001 Inputs IR 002 IR 003 IR 004 IR 005 IR 006 IR 010 Outputs IR 011 IR 012 IR 013 IR 014 IR 015 IR 016
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Do not use
Example: Configuration Including Expansion I/O Units and a CompoBus/S I/O Link Unit
CPU Unit (20 I/O points)
12 inputs IR 00000 to IR 00011
No outputs
No outputs
Bits IR 000 Inputs IR 001 IR 002 IR 003 IR 010 IR 011 Outputs IR 012 IR 013
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Do not use
Do not use
330
Section
5-3
Example: Configuration Including Analog I/O Units, Temperature Sensor Units, and Expansion I/O Unit
CPU Unit (20 I/O points)
12 inputs IR 00000 to IR 00011 8 outputs IR 01000 to IR 01007
No outputs
No outputs
Bits IR 000 IR 001 IR 002 IR 003 Inputs IR 004 IR 005 IR 006 IR 007 IR 008 IR 009 IR 010 Outputs IR 011 IR 012 IR 013
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Do not use Used for input 0 of Analog I/O Unit 1 Used for input 1 of Analog I/O Unit 1 Used for input 0 of Temperature Sensor Unit 1 Used for input 1 of Temperature Sensor Unit 1 Used for input 0 of Analog I/O Unit 2 Used for input 1 of Analog I/O Unit 2 Used for input 0 of Temperature Sensor Unit 2 Used for input 1 of Temperature Sensor Unit 2
Used for the output of Analog I/O Unit 1 Used for the output of Analog I/O Unit 2
331
6-4
Basic Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Instruction Terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Basic Ladder Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3-1 Basic Terms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3-2 Mnemonic Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3-3 Ladder Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3-4 OUTPUT and OUTPUT NOT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3-5 The END Instruction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3-6 Logic Block Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3-7 Coding Multiple Right-hand Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3-8 Branching Instruction Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3-9 Jumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Controlling Bit Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4-1 SET and RESET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4-2 DIFFERENTIATE UP and DIFFERENTIATE DOWN . . . . . . . . . . . . . . . . . . . . 6-4-3 KEEP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4-4 Self-maintaining Bits (Seal) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Work Bits (Internal Relays) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Programming Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Program Execution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
334 334 335 335 336 337 340 341 341 349 349 353 354 354 355 355 356 356 358 360
333
Instruction Terminology
Section
6-2
6-1
Basic Procedure
There are several basic steps involved in writing a program. Sheets that can be copied to aid in programming are provided in Appendix D I/O Assignment Sheet and Appendix E Program Coding Sheet. 1, 2, 3... 1. 2. 3. 4. Obtain a list of all I/O devices and the I/O points that have been assigned to them and prepare a table that shows the I/O bit allocated to each I/O device. If you are using LR bits to link two PCs, prepare sheet showing the used of these bits. Determine what words are available for work bits and prepare a table in which you can allocate these as you use them. Also prepare tables of TC numbers and jump numbers so that you can allocate these as you use them. Remember, the function of a TC number can be defined only once within the program; jump numbers 01 through 99 can be used only once each. (TC number are described in 7-15 Timer and Counter Instructions; jump numbers are described later in this section.) Draw the ladder diagram. Input the program into the CPU Unit. When using the Programming Console, this will involve converting the program to mnemonic form. Check the program for syntax errors and correct these. Execute the program to check for execution errors and correct these. After the entire Control System has been installed and is ready for use, execute the program and fine tune it if required.
5. 6. 7. 8. 9.
The basics of ladder-diagram programming and conversion to mnemonic code are described in 6-3 Basic Ladder Diagrams. Preparing for and inputting the program via the Programming Console are described in the CPM1 Operation Manual, the CPM1A Operation Manual, the CPM2A Operation Manual, the CPM2C Operation Manual, and the SRM1 Master Control Units Manual and via the SSS in the SSS Operation Manual: C-series PCs. The rest of Section 6 covers more advanced programming, programming precautions, and program execution. All special application instructions are covered in Section 7 Instruction Set. Debugging is described in the CPM1 Operation Manual, the CPM1A Operation Manual, the CPM2A Operation Manual, the CPM2C Operation Manual, the SRM1 Master Control Units Manual, and SSS Operation Manual: C-series PCs. Section 9 Troubleshooting also provides information required for debugging.
6-2
Instruction Terminology
There are basically two types of instructions used in ladder-diagram programming: instructions that correspond to the conditions on the ladder diagram and are used in instruction form only when converting a program to mnemonic code and instructions that are used on the right side of the ladder diagram and are executed according to the conditions on the instruction lines leading to them. Most instructions have at least one or more operands associated with them. Operands indicate or provide the data on which an instruction is to be performed. These are sometimes input as the actual numeric values, but are usually the addresses of data area words or bits that contain the data to be used. For instance, a MOVE instruction that has IR 000 designated as the source operand will move the contents of IR 000 to some other location. The other location is also designated as an operand. A bit whose address is designated as an operand is called an operand bit; a word whose address is designated as an operand is called an operand word. If the actual value is entered as a constant, it is preceded by # to indicate that it is not an address.
334
Section
6-3
Other terms used in describing instructions are introduced in Section 7 Instruction Set.
6-3
00000 20000
25208
HR 0109
LR 0003
20001
20002 Instruction
00001
00501
00502
00503
00504
00100 00002
00003 HR 0050
00403
00405 Instruction
00010
21001
21002
00011
21005
21007
As shown in the diagram above, instruction lines can branch apart and they can join back together. The vertical pairs of lines are called conditions. Conditions without diagonal lines through them are called normally open conditions and correspond to a LOAD, AND, or OR instruction. The conditions with diagonal lines through them are called normally closed conditions and correspond to a LOAD NOT, AND NOT, or OR NOT instruction. The number above each condition indicates the operand bit for the instruction. It is the status of the bit associated with each condition that determines the execution condition for following instructions. The way the operation of each of the instructions corresponds to a condition is described below. Before we consider these, however, there are some basic terms that must be explained. Note When displaying ladder diagrams with the SSS, a second bus bar will be shown on the right side of the ladder diagram and will be connected to all instructions on the right side. This does not change the ladder-diagram program in any functional sense. No conditions can be placed between the instructions on the right side and the right bus bar, i.e., all instructions on the right must be connected directly to the right bus bar. Refer to the SSS Operation Manual: C-series PCs for details.
6-3-1
Basic Terms
Each condition in a ladder diagram is either ON or OFF depending on the status of the operand bit that has been assigned to it. A normally open condition is ON if the operand bit is ON; OFF if the operand bit is OFF. A normally closed condition is ON if the operand bit is OFF; OFF if the operand bit is ON. Generally speaking, you use a normally open condition when you want something to happen when a
335
Section
6-3
bit is ON, and a normally closed condition when you want something to happen when a bit is OFF.
00000 Instruction
Instruction is executed when IR bit 00000 is ON. Instruction is executed when IR bit 00000 is OFF.
Execution Conditions
In ladder diagram programming, the logical combination of ON and OFF conditions before an instruction determines the compound condition under which the instruction is executed. This condition, which is either ON or OFF, is called the execution condition for the instruction. All instructions other than LOAD instructions have execution conditions. The operands designated for any of the ladder instructions can be any bit in the IR, SR, HR, AR, LR, or TC areas. This means that the conditions in a ladder diagram can be determined by I/O bits, flags, work bits, timers/counters, etc. LOAD and OUTPUT instructions can also use TR area bits, but they do so only in special applications. Refer to 6-3-8 Branching Instruction Lines for details. The way that conditions correspond to what instructions is determined by the relationship between the conditions within the instruction lines that connect them. Any group of conditions that go together to create a logic result is called a logic block. Although ladder diagrams can be written without actually analyzing individual logic blocks, understanding logic blocks is necessary for efficient programming and is essential when programs are to be input in mnemonic code. An instruction block consists of all the instructions that are interconnected across the ladder diagram. One instruction block thus consists of all the instructions between where you can draw a horizontal line across the ladder diagram without intersecting any vertical lines and the next place where you can draw the same type of horizontal line.
Operand Bits
Logic Blocks
Instruction Block
6-3-2
Mnemonic Code
The ladder diagram cannot be directly input into the PC via a Programming Console; the SSS is required. To input from a Programming Console, it is necessary to convert the ladder diagram to mnemonic code. The mnemonic code provides exactly the same information as the ladder diagram, but in a form that can be typed directly into the PC. Actually you can program directly in mnemonic code, although it in not recommended for beginners or for complex programs. Also, regardless of the Programming Device used, the program is stored in memory in mnemonic form, making it important to understand mnemonic code. Because of the importance of the Programming Console as a Programming Device and because of the importance of mnemonic code in complete understanding of a program, we will introduce and describe the mnemonic code along with the ladder diagram. Remember, you will not need to use the mnemonic code if you are inputting via the SSS (although you can use it with the SSS if you prefer).
The program is input into addresses in Program Memory. Addresses in Program Memory are slightly different to those in other memory areas because each address does not necessarily hold the same amount of data. Rather, each address holds one instruction and all of the definers and operands (described in more
336
Section
6-3
detail later) required for that instruction. Because some instructions require no operands, while others require up to three operands, Program Memory addresses can be from one to four words long. Program Memory addresses start at 00000 and run until the capacity of Program Memory has been exhausted. The first word at each address defines the instruction. Any definers used by the instruction are also contained in the first word. Also, if an instruction requires only a single bit operand (with no definer), the bit operand is also programmed on the same line as the instruction. The rest of the words required by an instruction contain the operands that specify what data is to be used. When converting to mnemonic code, all but ladder diagram instructions are written in the same form, one word to a line, just as they appear in the ladder diagram symbols. An example of mnemonic code is shown below. The instructions used in it are described later in the manual.
DM 00007 CMP(20) DM HR 00008 00009 00010 AND OUT MOV(21) DM DM 00011 00012 00013 LD AND OUT
000 0000 0000 00 25505 20000 0000 0500 00502 00005 20001
The address and instruction columns of the mnemonic code table are filled in for the instruction word only. For all other lines, the left two columns are left blank. If the instruction requires no definer or bit operand, the operand column is left blank for first line. It is a good idea to cross through any blank data column spaces (for all instruction words that do not require data) so that the data column can be quickly scanned to see if any addresses have been left out. When programming, addresses are automatically displayed and do not have to be input unless for some reason a different location is desired for the instruction. When converting to mnemonic code, it is best to start at Program Memory address 00000 unless there is a specific reason for starting elsewhere.
6-3-3
Ladder Instructions
The ladder instructions are those instructions that correspond to the conditions on the ladder diagram. Ladder instructions, either independently or in combination with the logic block instructions described next, form the execution conditions upon which the execution of all other instructions are based.
337
Section
6-3
The first condition that starts any logic block within a ladder diagram corresponds to a LOAD or LOAD NOT instruction. Each of these instruction requires one line of mnemonic code. Instruction is used as a dummy instruction in the following examples and could be any of the right-hand instructions described later in this manual.
00000
A LOAD instruction.
00000
When this is the only condition on the instruction line, the execution condition for the instruction at the right is ON when the condition is ON. For the LOAD instruction (i.e., a normally open condition), the execution condition would be ON when IR 00000 was ON; for the LOAD NOT instruction (i.e., a normally closed condition), it would be ON when 00000 was OFF.
When two or more conditions lie in series on the same instruction line, the first one corresponds to a LOAD or LOAD NOT instruction; and the rest of the conditions, to AND or AND NOT instructions. The following example shows three conditions which correspond in order from the left to a LOAD, an AND NOT, and an AND instruction. Again, each of these instructions requires one line of mnemonic code.
00000
00100
LR 0000 Instruction
LR
The instruction would have an ON execution condition only when all three conditions are ON, i.e., when IR 00000 was ON, IR 00100 was OFF, and LR 0000 was ON. AND instructions in series can be considered individually, with each taking the logical AND of the execution condition (i.e., the total of all conditions up to that point) and the status of the AND instructions operand bit. If both of these are ON, an ON execution condition will be produced for the next instruction. If either is OFF, the result will also be OFF. The execution condition for the first AND instruction in a series is the first condition on the instruction line. Each AND NOT instruction in a series would take the logical AND between its execution condition and the inverse of its operand bit.
338
Section
6-3
When two or more conditions lie on separate instruction lines running in parallel and then joining together, the first condition corresponds to a LOAD or LOAD NOT instruction; the rest of the conditions correspond to OR or OR NOT instructions. The following example shows three conditions which correspond in order from the top to a LOAD NOT, an OR NOT, and an OR instruction. Again, each of these instructions requires one line of mnemonic code.
00000 Instruction 00100
LR 0000
LR
The instruction would have an ON execution condition when any one of the three conditions was ON, i.e., when IR 00000 was OFF, when IR 00100 was OFF, or when LR 0000 was ON. OR and OR NOT instructions can be considered individually, each taking the logical OR between its execution condition and the status of the OR instructions operand bit. If either one of these were ON, an ON execution condition would be produced for the next instruction. Combining AND and OR Instructions When AND and OR instructions are combined in more complicated diagrams, they can sometimes be considered individually, with each instruction performing a logic operation on the execution condition and the status of the operand bit. The following is one example. Study this example until you are convinced that the mnemonic code follows the same logic flow as the ladder diagram.
00000 00001 00002 00003 Instruction 00200
Here, an AND is taken between the status of IR 00000 and that of IR 00001 to determine the execution condition for an OR with the status of IR 00200. The result of this operation determines the execution condition for an AND with the status of IR 00002, which in turn determines the execution condition for an AND with the inverse (i.e., and AND NOT) of the status of IR 00003.
339
Section
6-3
In more complicated diagrams, however, it is necessary to consider logic blocks before an execution condition can be determined for the final instruction, and thats where AND LOAD and OR LOAD instructions are used. Before we consider more complicated diagrams, however, well look at the instructions required to complete a simple input-output program.
6-3-4
00001 01001
In the above examples, IR 01000 will be ON as long as IR 00000 is ON and IR 01001 will be OFF as long as IR 00001 is ON. Here, IR 00000 and IR 00001 would be input bits and IR 01000 and IR 01001 output bits assigned to the Units controlled by the PC, i.e., the signals coming in through the input points assigned IR 00000 and IR 00001 are controlling the output points assigned IR 01000 and IR 01001, respectively. The length of time that a bit is ON or OFF can be controlled by combining the OUTPUT or OUTPUT NOT instruction with Timer instructions. Refer to Examples under 7-15-1 Timer TIM for details.
340
Section
6-3
6-3-5
END(01)
If there is no END instruction anywhere in the program, the program will not be executed at all. Now you have all of the instructions required to write simple input-output programs. Before we finish with ladder diagram basic and go onto inputting the program into the PC, lets look at logic block instruction (AND LOAD and OR LOAD), which are sometimes necessary even with simple diagrams.
6-3-6
AND LOAD
Although simple in appearance, the diagram below requires an AND LOAD instruction.
00000 00002 Instruction 00001 00003
341
Section
6-3
The two logic blocks are indicated by dotted lines. Studying this example shows that an ON execution condition will be produced when: either of the conditions in the left logic block is ON (i.e., when either IR 00000 or IR 00001 is ON), and when either of the conditions in the right logic block is ON (i.e., when either IR 00002 is ON or IR 00003 is OFF). The above ladder diagram cannot, however, be converted to mnemonic code using AND and OR instructions alone. If an AND between IR 00002 and the results of an OR between IR 00000 and IR 00001 is attempted, the OR NOT between IR 00002 and IR 00003 is lost and the OR NOT ends up being an OR NOT between just IR 00003 and the result of an AND between IR 00002 and the first OR. What we need is a way to do the OR (NOT)s independently and then combine the results. To do this, we can use the LOAD or LOAD NOT instruction in the middle of an instruction line. When LOAD or LOAD NOT is executed in this way, the current execution condition is saved in special buffers and the logic process is begun over. To combine the results of the current execution condition with that of a previous unused execution condition, an AND LOAD or an OR LOAD instruction is used. Here LOAD refers to loading the last unused execution condition. An unused execution condition is produced by using the LOAD or LOAD NOT instruction for any but the first condition on an instruction line. Analyzing the above ladder diagram in terms of mnemonic instructions, the condition for IR 00000 is a LOAD instruction and the condition below it is an OR instruction between the status of IR 00000 and that of IR 00001. The condition at IR 00002 is another LOAD instruction and the condition below is an OR NOT instruction, i.e., an OR between the status of IR 00002 and the inverse of the status of IR 00003. To arrive at the execution condition for the instruction at the right, the logical AND of the execution conditions resulting from these two blocks would have to be taken. AND LOAD does this. The mnemonic code for the ladder diagram is shown below. The AND LOAD instruction requires no operands of its own, because it operates on previously determined execution conditions. Here too, dashes are used to indicate that no operands needs designated or input. OR LOAD The following diagram requires an OR LOAD instruction between the top logic block and the bottom logic block. An ON execution condition would be produced for the instruction at the right either when IR 00000 is ON and IR 00001 is OFF or when IR 00002 and IR 00003 are both ON. The operation of and mnemonic code for the OR LOAD instruction is exactly the same as those for a AND LOAD instruction except that the current execution condition is ORed with the last unused execution condition.
00000 00001 Instruction 00002 00003
Naturally, some diagrams will require both AND LOAD and OR LOAD instructions.
342
Section
6-3
To code diagrams with logic block instructions in series, the diagram must be divided into logic blocks. Each block is coded using a LOAD instruction to code the first condition, and then AND LOAD or OR LOAD is used to logically combine the blocks. With both AND LOAD and OR LOAD there are two ways to achieve this. One is to code the logic block instruction after the first two blocks and then after each additional block. The other is to code all of the blocks to be combined, starting each block with LOAD or LOAD NOT, and then to code the logic block instructions which combine them. In this case, the instructions for the last pair of blocks should be combined first, and then each preceding block should be combined, working progressively back to the first block. Although either of these methods will produce exactly the same result, the second method, that of coding all logic block instructions together, can be used only if eight or fewer blocks are being combined, i.e., if seven or fewer logic block instructions are required. The following diagram requires AND LOAD to be converted to mnemonic code because three pairs of parallel conditions lie in series. The two means of coding the programs are also shown.
00000
00002
00004 20000
00001
00003
00005
Address 00000 00001 00002 00003 00004 00005 00006 00007 00008
Address 00000 00001 00002 00003 00004 00005 00006 00007 00008
Again, with the method on the right, a maximum of eight blocks can be combined. There is no limit to the number of blocks that can be combined with the first method. The following diagram requires OR LOAD instructions to be converted to mnemonic code because three pairs of conditions in series lie in parallel to each other.
00002 00003
00004 00005
343
Section
6-3
The first of each pair of conditions is converted to LOAD with the assigned bit operand and then ANDed with the other condition. The first two blocks can be coded first, followed by OR LOAD, the last block, and another OR LOAD, or the three blocks can be coded first followed by two OR LOADs. The mnemonic code for both methods is shown below.
Address 00000 00001 00002 00003 00004 00005 00006 00007 00008 Instruction LD AND NOT LD NOT AND NOT OR LD LD AND OR LD OUT Operands 00000 00001 00002 00003 00004 00005 20001 Address 00000 00001 00002 00003 00004 00005 00006 00007 00008 Instruction LD AND NOT LD NOT AND NOT LD AND OR LD OR LD OUT Operands 00000 00001 00002 00003 00004 00005 20001
Again, with the method on the right, a maximum of eight blocks can be combined. There is no limit to the number of blocks that can be combined with the first method. Combining AND LOAD and OR LOAD Both of the coding methods described above can also be used when using AND LOAD and OR LOAD, as long as the number of blocks being combined does not exceed eight. The following diagram contains only two logic blocks as shown. It is not necessary to further separate block b components, because it can coded directly using only AND and OR.
00000 00001 00002 00003 20001
00201
00004
Block a
Block b
Although the following diagram is similar to the one above, block b in the diagram below cannot be coded without separating it into two blocks combined with OR LOAD. In this example, the three blocks have been coded first and then OR LOAD has been used to combine the last two blocks followed by AND LOAD to combine the execution condition produced by the OR LOAD with the execution condition of block a.
344
Section
6-3
When coding the logic block instructions together at the end of the logic blocks they are combining, they must, as shown below, be coded in reverse order, i.e., the logic block instruction for the last two blocks is coded first, followed by the one to combine the execution condition resulting from the first logic block instruction and the execution condition of the logic block third from the end, and on back to the first logic block that is being combined.
Block b1 00000 00001 00002 00003 20002
00004 00202
Block b2
Block a
Block b
Address 00000 00001 00002 00003 00004 00005 00006 00007 00008
Complicated Diagrams
When determining what logic block instructions will be required to code a diagram, it is sometimes necessary to break the diagram into large blocks and then continue breaking the large blocks down until logic blocks that can be coded without logic block instructions have been formed. These blocks are then coded, combining the small blocks first, and then combining the larger blocks. Either AND LOAD or OR LOAD is used to combine the blocks, i.e., AND LOAD or OR LOAD always combines the last two execution conditions that existed, regardless of whether the execution conditions resulted from a single condition, from logic blocks, or from previous logic block instructions. When working with complicated diagrams, blocks will ultimately be coded starting at the top left and moving down before moving across. This will generally mean that, when there might be a choice, OR LOAD will be coded before AND LOAD.
345
Section
6-3
The following diagram must be broken down into two blocks and each of these then broken into two blocks before it can be coded. As shown below, blocks a and b require an AND LOAD. Before AND LOAD can be used, however, OR LOAD must be used to combine the top and bottom blocks on both sides, i.e., to combine a1 and a2; b1 and b2.
00002 00003
00006 00007
Block a2
Block b2
Block a
Block b
Address 00000 00001 00002 00003 00004 00005 00006 00007 00008 00009 00010 00011
Operands 00000 00001 00002 00003 00004 00005 00006 00007 20003
Blocks a1 and a2
The following type of diagram can be coded easily if each block is coded in order: first top to bottom and then left to right. In the following diagram, blocks a and b would be combined using AND LOAD as shown above, and then block c would be coded and a second AND LOAD would be used to combined it with the execution condition from the first AND LOAD. Then block d would be coded, a third AND LOAD would be used to combine the execution condition from block d with the execution condition from the second AND LOAD, and so on through to block n.
20000
Block a
Block b
Block c
Block n
346
Section
6-3
The following diagram requires an OR LOAD followed by an AND LOAD to code the top of the three blocks, and then two more OR LOADs to complete the mnemonic code.
00000 00001 LR 0000 00002 00003
Address 00000 00001 00002 00003 00004 00005 00006 00007 00008 00009 00010 00011 00012
Operands 00000 00001 00002 00003 --00004 00005 -00006 00007 -0000
00004
00005
00006
00007
LR
Although the program will execute as written, this diagram could be drawn as shown below to eliminate the need for the first OR LOAD and the AND LOAD, simplifying the program and saving memory space.
00002 00003 00000 LR 0000 00001
Address 00000 00001 00002 00003 00004 00005 00006 00007 00008 00009 00010
Operands 00002 00003 00001 00000 00004 00005 -00006 00007 -0000
00004
00005
00006
00007
LR
The following diagram requires five blocks, which here are coded in order before using OR LOAD and AND LOAD to combine them starting from the last two blocks and working backward. The OR LOAD at program address 00008 combines blocks d and e, the following AND LOAD combines the resulting execution condition with that of block c, etc.
00000 00001 00002 LR 0000 Block b Block a Block c 00003 00004 Block d 00005
Address 00000 00001 00002 00003 00004 00005 00006 00007 00008 00009 00010 00011 00012
Operands 00000 00001 00002 00003 00004 00005 00006 00007 ----0000
00006
Block e
Block c with result of above Block b with result of above Block a with result of above
LR
347
Section
6-3
Again, this diagram can be redrawn as follows to simplify program structure and coding and to save memory space.
00006
00007
00003
00004
00000 LR 0000
Address 00000 00001 00002 00003 00004 00005 00006 00007 00008 00009
Operands 00006 00007 00005 00003 00004 00001 00002 -00000 0000
00005
00001
00002
LR
The next and final example may at first appear very complicated but can be coded using only two logic block instructions. The diagram appears as follows:
Block a 00000 00001 00002 00003 00004 00005 20000 01000 01001 00006
The first logic block instruction is used to combine the execution conditions resulting from blocks a and b, and the second one is to combine the execution condition of block c with the execution condition resulting from the normally closed condition assigned IR 00003. The rest of the diagram can be coded with OR, AND, and AND NOT instructions. The logical flow for this and the resulting code are shown below.
Block a 00000 00001 Block b 01000 01001
LD AND
00000 00001
LD AND
01000 01001
Address 00000 00001 00002 00003 00004 00005 00006 00007 00008 00009 00010 00011 00012
Operands 00000 00001 01000 01001 -20000 00002 00003 00004 00005 00006 -20000
OR LD
Block c 20000 00004 00005
OR
20000
LD AND 00006
00004 00005
00002
00003
OR
00006
AND LD
20000
348
Section
6-3
6-3-7
00000
00003 HR 0001
Address 00000 00001 00002 00003 00004 00005 00006 00007 00008
Operands 00000 00001 00002 0000 00003 0001 20000 00004 20001
HR HR
HR 0000
6-3-8
00000
Branching point
Instruction 1 00002 Instruction 2
Branching point
If, as shown in diagram A, the execution condition that existed at the branching point cannot be changed before returning to the branch line (instructions at the far right do not change the execution condition), then the branch line will be executed correctly and no special programming measure is required. If, as shown in diagram B, a condition exists between the branching point and the last instruction on the top instruction line, the execution condition at the branching point and the execution condition after completing the top instruction line will sometimes be different, making it impossible to ensure correct execution of the branch line. There are two means of programming branching programs to preserve the execution condition. One is to use TR bits; the other, to use interlocks (IL(02)/IL(03)).
349
Section
6-3
The TR area provides eight bits, TR 0 through TR 7, that can be used to temporarily preserve execution conditions. If a TR bit is placed at a branching point, the current execution condition will be stored at the designated TR bit. When returning to the branching point, the TR bit restores the execution status that was saved when the branching point was first reached in program execution. The previous diagram B can be written as shown below to ensure correct execution. In mnemonic code, the execution condition is stored at the branching point using the TR bit as the operand of the OUTPUT instruction. This execution condition is then restored after executing the right-hand instruction by using the same TR bit as the operand of a LOAD instruction
TR
In terms of actual instructions the above diagram would be as follows: The status of IR 00000 is loaded (a LOAD instruction) to establish the initial execution condition. This execution condition is then output using an OUTPUT instruction to TR 0 to store the execution condition at the branching point. The execution condition is then ANDed with the status of IR 00001 and instruction 1 is executed accordingly. The execution condition that was stored at the branching point is then re-loaded (a LOAD instruction with TR 0 as the operand), this is ANDed with the status of IR 00002, and instruction 2 is executed accordingly. The following example shows an application using two TR bits.
TR 0 00000 00001
Address 00000 00001 00002 00003 00004 00005 00006 00007 00008 00009 00010 00011 00012 00013 00014
Instruction LD OUT AND OUT AND Instruction 1 LD AND Instruction 2 LD AND Instruction 3 LD AND NOT Instruction 4
TR
TR
TR
In this example, TR 0 and TR 1 are used to store the execution conditions at the branching points. After executing instruction 1, the execution condition stored in TR 1 is loaded for an AND with the status IR 00003. The execution condition stored in TR 0 is loaded twice, the first time for an AND with the status of IR 00004 and the second time for an AND with the inverse of the status of IR 00005.
350
Section
6-3
TR bits can be used as many times as required as long as the same TR bit is not used more than once in the same instruction block. Here, a new instruction block is begun each time execution returns to the bus bar. If, in a single instruction block, it is necessary to have more than eight branching points that require the execution condition be saved, interlocks (which are described next) must be used. When drawing a ladder diagram, be careful not to use TR bits unless necessary. Often the number of instructions required for a program can be reduced and ease of understanding a program increased by redrawing a diagram that would otherwise required TR bits. In both of the following pairs of diagrams, the bottom versions require fewer instructions and do not require TR bits. In the first example, this is achieved by reorganizing the parts of the instruction block: the bottom one, by separating the second OUTPUT instruction and using another LOAD instruction to create the proper execution condition for it. Note Although simplifying programs is always a concern, the order of execution of instructions is sometimes important. For example, a MOVE instruction may be required before the execution of a BINARY ADD instruction to place the proper data in the required operand word. Be sure that you have considered execution order before reorganizing a program to simplify it.
00000
00003 Instruction 1
Instruction 2 00001
TR 0 00002
00001
00002
00003 Instruction 1
00000
00001
00004 Instruction 2
Note TR bits are must be input by the user only when programming using mnemonic code. They are not necessary when inputting ladder diagrams directly because they are processed for you automatically. The above limitations on the number of branching points requiring TR bits, and considerations on methods to reduce the number of programming instructions, still hold.
Interlocks
The problem of storing execution conditions at branching points can also be handled by using the INTERLOCK (IL(02)) and INTERLOCK CLEAR (ILC(03)) instructions to eliminate the branching point completely while allowing a specific execution condition to control a group of instructions. The INTERLOCK and INTERLOCK CLEAR instructions are always used together.
351
Section
6-3
When an INTERLOCK instruction is placed before a section of a ladder program, the execution condition for the INTERLOCK instruction will control the execution of all instruction up to the next INTERLOCK CLEAR instruction. If the execution condition for the INTERLOCK instruction is OFF, all right-hand instructions through the next INTERLOCK CLEAR instruction will be executed with OFF execution conditions to reset the entire section of the ladder diagram. The effect that this has on particular instructions is described in 7-11 INTERLOCK and INTERLOCK CLEAR IL(02) and ILC(03). Diagram B can also be corrected with an interlock. Here, the conditions leading up to the branching point are placed on an instruction line for the INTERLOCK instruction, all of lines leading from the branching point are written as separate instruction lines, and another instruction line is added for the INTERLOCK CLEAR instruction. No conditions are allowed on the instruction line for INTERLOCK CLEAR. Note that neither INTERLOCK nor INTERLOCK CLEAR requires an operand.
00000 IL(02) 00001 Instruction 1 00002 Instruction 2
ILC(03)
If IR 00000 is ON in the revised version of diagram B, above, the status of IR 00001 and that of IR 00002 would determine the execution conditions for instructions 1 and 2, respectively. Because IR 00000 is ON, this would produce the same results as ANDing the status of each of these bits. If IR 00000 is OFF, the INTERLOCK instruction would produce an OFF execution condition for instructions 1 and 2 and then execution would continue with the instruction line following the INTERLOCK CLEAR instruction. As shown in the following diagram, more than one INTERLOCK instruction can be used within one instruction block; each is effective through the next INTERLOCK CLEAR instruction.
00000 IL(02) 00001 Instruction 1 00002 IL(02) 00003 00004 Instruction 2 00005 Instruction 3 00006 Instruction 4
Address 00000 00001 00002 00003 00004 00005 00006 00007 00008 00009 00010 00011 00012 00013
Instruction LD IL(02) LD Instruction 1 LD IL(02) LD AND NOT Instruction 2 LD Instruction 3 LD Instruction 4 ILC(03)
ILC(03)
352
Section
6-3
If IR 00000 in the above diagram is OFF (i.e., if the execution condition for the first INTERLOCK instruction is OFF), instructions 1 through 4 would be executed with OFF execution conditions and execution would move to the instruction following the INTERLOCK CLEAR instruction. If IR 00000 is ON, the status of IR 00001 would be loaded as the execution condition for instruction 1 and then the status of IR 00002 would be loaded to form the execution condition for the second INTERLOCK instruction. If IR 00002 is OFF, instructions 2 through 4 will be executed with OFF execution conditions. If IR 00002 is ON, IR 00003, IR 00005, and IR 00006 will determine the first execution condition in new instruction lines.
6-3-9
Jumps
A specific section of a program can be skipped according to a designated execution condition. Although this is similar to what happens when the execution condition for an INTERLOCK instruction is OFF, with jumps, the operands for all instructions maintain status. Jumps can therefore be used to control devices that require a sustained output, e.g., pneumatics and hydraulics, whereas interlocks can be used to control devices that do not required a sustained output, e.g., electronic instruments. Jumps are created using the JUMP (JMP(04)) and JUMP END (JME(05)) instructions. If the execution condition for a JUMP instruction is ON, the program is executed normally as if the jump did not exist. If the execution condition for the JUMP instruction is OFF, program execution moves immediately to a JUMP END instruction without changing the status of anything between the JUMP and JUMP END instruction. All JUMP and JUMP END instructions are assigned jump numbers ranging between 00 and 99. There are two types of jumps. The jump number used determines the type of jump. A jump can be defined using jump numbers 01 through 99 only once, i.e., each of these numbers can be used once in a JUMP instruction and once in a JUMP END instruction. When a JUMP instruction assigned one of these numbers is executed, execution moves immediately to the JUMP END instruction that has the same number as if all of the instruction between them did not exist. Diagram B from the TR bit and interlock example could be redrawn as shown below using a jump. Although 01 has been used as the jump number, any number between 01 and 99 could be used as long as it has not already been used in a different part of the program. JUMP and JUMP END require no other operand and JUMP END never has conditions on the instruction line leading to it.
JME(05) 01
This version of diagram B would have a shorter execution time when IR 00000 was OFF than any of the other versions.
353
Section
6-4
The other type of jump is created with a jump number of 00. As many jumps as desired can be created using jump number 00 and JUMP instructions using 00 can be used consecutively without a JUMP END using 00 between them. It is even possible for all JUMP 00 instructions to move program execution to the same JUMP END 00, i.e., only one JUMP END 00 instruction is required for all JUMP 00 instruction in the program. When 00 is used as the jump number for a JUMP instruction, program execution moves to the instruction following the next JUMP END instruction with a jump number of 00. Although, as in all jumps, no status is changed and no instructions are executed between the JUMP 00 and JUMP END 00 instructions, the program must search for the next JUMP END 00 instruction, producing a slightly longer execution time. Execution of programs containing multiple JUMP 00 instructions for one JUMP END 00 instruction is similar to that of interlocked sections. The following diagram is the same as that used for the interlock example above, except redrawn with jumps. The execution of this diagram would differ from that of the diagram described above (e.g., in the previous diagram interlocks would reset certain parts of the interlocked section, however, jumps do not affect the status of any bit between the JUMP and JUMP END instructions).
00000 JMP(04) 00 00001 Instruction 1 00002 JMP(04) 00 00003 00004 Instruction 2 00005 Instruction 3 00006 Instruction 4
Address 00000 00001 00002 00003 00004 00005 00006 00007 00008 00009 00010 00011 00012 00013
Instruction LD JMP(04) LD Instruction 1 LD JMP(04) LD AND NOT Instruction 2 LD Instruction 3 LD Instruction 4 JME(05)
JME(05) 00
6-4
6-4-1
354
Section
6-4
SET will turn ON the operand bit when the execution condition goes ON, but unlike the OUTPUT instruction, SET will not turn OFF the operand bit when the execution condition goes OFF. RESET will turn OFF the operand bit when the execution condition goes OFF, but unlike OUTPUT NOT, RESET will not turn ON the operand bit when the execution condition goes OFF. In the following example, IR 20000 will be turned ON when IR 00100 goes ON and will remain ON until IR 00101 goes ON, regardless of the status of IR 00100. When IR 00101 goes ON, RESET will turn IR 20000 OFF.
Address
SET 20000
00100
Note SET and RSET do not have function codes. To input them from the Programming Console, press the FUN and SET Keys or FUN and RSET Keys followed by the bit address.
6-4-2
Here, IR 20001 will be turned ON for one cycle after IR 00000 goes ON. The next time DIFU(13) 20001 is executed, IR 20001 will be turned OFF, regardless of the status of IR 00000. With the DIFFERENTIATE DOWN instruction, IR 20002 will be turned ON for one cycle after IR 00001 goes OFF (IR 20002 will be kept OFF until then), and will be turned OFF the next time DIFD(14) 20002 is executed.
6-4-3
KEEP
The KEEP instruction is used to maintain the status of the operand bit based on two execution conditions. To do this, the KEEP instruction is connected to two instruction lines. When the execution condition at the end of the first instruction line is ON, the operand bit of the KEEP instruction is turned ON. When the execution condition at the end of the second instruction line is ON, the operand bit of the KEEP instruction is turned OFF. The operand bit for the KEEP instruction will maintain its ON or OFF status even if it is located in an interlocked section of the diagram.
355
Section
6-5
In the following example, HR 0000 will be turned ON when IR 00002 is ON and IR 00003 is OFF. HR 0000 will then remain ON until either IR 00004 or IR 00005 turns ON. With KEEP, as with all instructions requiring more than one instruction line, the instruction lines are coded first before the instruction that they control.
00002 00003
Address
S: set input
00004
KEEP(11) HR 0000
00005
R: reset input
HR
6-4-4
00002
00003
HR 0000
HR
HR
6-5
356
Section
6-5
Examples given later in this subsection show two of the most common ways to employ work bits. These should act as a guide to the almost limitless number of ways in which the work bits can be used. Whenever difficulties arise in programming a control action, consideration should be given to work bits and how they might be used to simplify programming. Work bits are often used with the OUTPUT, OUTPUT NOT, DIFFERENTIATE UP, DIFFERENTIATE DOWN, and KEEP instructions. The work bit is used first as the operand for one of these instructions so that later it can be used as a condition that will determine how other instructions will be executed. Work bits can also be used with other instructions, e.g., with the SHIFT REGISTER instruction (SFT(10)). An example of the use of work words and bits with the SHIFT REGISTER instruction is provided in 7-16-1 SHIFT REGISTER SFT(10). Although they are not always specifically referred to as work bits, many of the bits used in the examples in Section 7 Instruction Set use work bits. Understanding the use of these bits is essential to effective programming.
Work bits can be used to simplify programming when a certain combination of conditions is repeatedly used in combination with other conditions. In the following example, IR 00000, IR 00001, IR 00002, and IR 00003 are combined in a logic block that stores the resulting execution condition as the status of IR 21600. IR 21600 is then combined with various other conditions to determine output conditions for IR 20000, IR 20001, and IR 20002, i.e., to turn the outputs allocated to these bits ON or OFF.
00000
00001 21600
Address 00000 00001 00002 00003 00004 00005 00006 00007 00008 00009 00010 00011 00012 00013 00014 00015 00016
Instruction LD AND NOT OR OR NOT OUT LD AND AND NOT OUT LD OR NOT AND OUT LD NOT OR OR OUT
Operands 00000 00001 00002 00003 21600 21600 00004 00005 20000 21600 00004 00005 20001 21600 00006 00007 20002
00002
00003
21600
00004
00005 20000
21600
00005 20001
00004
21600 20002
00006
00007
357
Programming Precautions
Differentiated Conditions
Section
6-6
Work bits can also be used if differential treatment is necessary for some, but not all, of the conditions required for execution of an instruction. In this example, IR 20000 must be left ON continuously as long as IR 001001 is ON and both IR 00002 and IR 00003 are OFF, or as long as IR 00004 is ON and IR 00005 is OFF. It must be turned ON for only one cycle each time IR 00000 turns ON (unless one of the preceding conditions is keeping it ON continuously). This action is easily programmed by using IR 22500 as a work bit as the operand of the DIFFERENTIATE UP instruction (DIFU(13)). When IR 00000 turns ON, IR 22500 will be turned ON for one cycle and then be turned OFF the next cycle by DIFU(13). Assuming the other conditions controlling IR 20000 are not keeping it ON, the work bit IR 22500 will turn IR 20000 ON for one cycle only.
Address 00000 00001 00002 00003 00004 00005 00006 00007 00008 00009 00010
Operands 00000 22500 22500 00001 00002 00003 --00004 00005 --20000
00004
00005
6-6
Programming Precautions
The number of conditions that can be used in series or parallel is unlimited as long as the memory capacity of the PC is not exceeded. Therefore, use as many conditions as required to draw a clear diagram. Although very complicated diagrams can be drawn with instruction lines, there must not be any conditions on lines running vertically between two other instruction lines. Diagram A shown below, for example, is not possible, and should be drawn as diagram B. Mnemonic code is provided for diagram B only; coding diagram A would be impossible.
00000 00002 Instruction 1 00004 00001 00003 Instruction 2
00001
00004
00002 Instruction 1
Address 00000 00001 00002 00003 00004 00005 00006 00007 00008 00009
00000
00000
00004
00003 Instruction 2
00001
358
Programming Precautions
Section
6-6
The number of times any particular bit can be assigned to conditions is not limited, so use them as many times as required to simplify your program. Often, complicated programs are the result of attempts to reduce the number of times a bit is used. Except for instructions for which conditions are not allowed (e.g., INTERLOCK CLEAR and JUMP END, see below), every instruction line must also have at least one condition on it to determine the execution condition for the instruction at the right. Again, diagram A , below, must be drawn as diagram B. If an instruction must be continuously executed (e.g., if an output must always be kept ON while the program is being executed), the Always ON Flag (SR 25313) in the SR area can be used.
Instruction
25313 Instruction
Instruction LD Instruction
Operands 25313
There are a few exceptions to this rule, including the INTERLOCK CLEAR, JUMP END, and step instructions. Each of these instructions is used as the second of a pair of instructions and is controlled by the execution condition of the first of the pair. Conditions should not be placed on the instruction lines leading to these instructions. Refer to Section 7 Instruction Set for details. When drawing ladder diagrams, it is important to keep in mind the number of instructions that will be required to input it. In diagram A, below, an OR LOAD instruction will be required to combine the top and bottom instruction lines. This can be avoided by redrawing as shown in diagram B so that no AND LOAD or OR LOAD instructions are required. Refer to 7-7-2 AND LOAD and OR LOAD for more details.
00000 20007
00001 20007
Diagram A
Address
20007
00001 20007
00000
Diagram B
359
Program Execution
Section
6-7
6-7
Program Execution
When program execution is started, the CPU Unit scans the program from top to bottom, checking all conditions and executing all instructions accordingly as it moves down the bus bar. It is important that instructions be placed in the proper order so that, for example, the desired data is moved to a word before that word is used as the operand for an instruction. Remember that an instruction line is completed to the terminal instruction at the right before executing an instruction lines branching from the first instruction line to other terminal instructions at the right. Program execution is only one of the tasks carried out by the CPU Unit as part of the cycle time. Refer to Section 8 PC Operations and Processing Time for details.
360
7-7
7-8
361
7-16 Shift Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-16-1 SHIFT REGISTER SFT(10) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-16-2 WORD SHIFT WSFT(16) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-16-3 ARITHMETIC SHIFT LEFT ASL(25) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-16-4 ARITHMETIC SHIFT RIGHT ASR(26) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-16-5 ROTATE LEFT ROL(27) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-16-6 ROTATE RIGHT ROR(28) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-16-7 ONE DIGIT SHIFT LEFT SLD(74) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-16-8 ONE DIGIT SHIFT RIGHT SRD(75) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-16-9 REVERSIBLE SHIFT REGISTER SFTR(84) . . . . . . . . . . . . . . . . . . . . . . . . . . 7-16-10 ASYNCHRONOUS SHIFT REGISTER ASFT(17) . . . . . . . . . . . . . . . . . . . . . 7-17 Data Movement Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-17-1 MOVE MOV(21) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-17-2 MOVE NOT MVN(22) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-17-3 BLOCK TRANSFER XFER(70) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-17-4 BLOCK SET BSET(71) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-17-5 DATA EXCHANGE XCHG(73) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-17-6 SINGLE WORD DISTRIBUTE DIST(80) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-17-7 DATA COLLECT COLL(81) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-17-8 MOVE BIT MOVB(82) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-17-9 MOVE DIGIT MOVD(83) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-18 Data Control Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-18-1 SCALING SCL(66) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-18-2 SIGNED BINARY TO BCD SCALING SCL2() . . . . . . . . . . . . . . . . . . . . . . 7-18-3 BCD TO SIGNED BINARY SCALING SCL3() . . . . . . . . . . . . . . . . . . . . . . 7-18-4 PID CONTROL PID() . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-19 Comparison Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-19-1 COMPARE CMP(20) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-19-2 TABLE COMPARE TCMP(85) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-19-3 BLOCK COMPARE BCMP(68) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-19-4 DOUBLE COMPARE CMPL(60) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-19-5 AREA RANGE COMPARE ZCP() . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-19-6 DOUBLE AREA RANGE COMPARE ZCPL() . . . . . . . . . . . . . . . . . . . . . . 7-20 Conversion Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-20-1 BCD-TO-BINARY BIN(23) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-20-2 BINARY-TO-BCD BCD(24) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-20-3 DOUBLE BCD-TO-DOUBLE BINARY BINL(58) . . . . . . . . . . . . . . . . . . . . . 7-20-4 DOUBLE BINARY-TO-DOUBLE BCD BCDL(59) . . . . . . . . . . . . . . . . . . . . . 7-20-5 4-TO-16 DECODER MLPX(76) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-20-6 16-TO-4 ENCODER DMPX(77) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-20-7 7-SEGMENT DECODER SDEC(78) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-20-8 ASCII CONVERT ASC(86) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-20-9 ASCII-TO-HEXADECIMAL HEX() . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-20-10 HOURS-TO-SECONDS SEC() . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-20-11 SECONDS-TO-HOURS HMS() . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-20-12 2S COMPLEMENT NEG() . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-21 BCD Calculation Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-21-1 SET CARRY STC(40) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-21-2 CLEAR CARRY CLC(41) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-21-3 BCD ADD ADD(30) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-21-4 BCD SUBTRACT SUB(31) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-21-5 BCD MULTIPLY MUL(32) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-21-6 BCD DIVIDE DIV(33) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-21-7 DOUBLE BCD ADD ADDL(54) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-21-8 DOUBLE BCD SUBTRACT SUBL(55) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-21-9 DOUBLE BCD MULTIPLY MULL(56) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-21-10 DOUBLE BCD DIVIDE DIVL(57) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
404 404 405 405 406 406 407 408 408 409 410 411 411 412 413 414 415 415 417 419 420 421 421 423 424 426 432 432 433 434 436 437 438 439 439 440 440 441 442 444 446 449 451 453 454 455 457 457 457 457 458 460 461 462 464 466 466
362
7-22 Binary Calculation Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-22-1 BINARY ADD ADB(50) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-22-2 BINARY SUBTRACT SBB(51) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-22-3 BINARY MULTIPLY MLB(52) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-22-4 BINARY DIVIDE DVB(53) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-23 Special Math Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-23-1 DATA SEARCH SRCH() . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-23-2 FIND MAXIMUM MAX() . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-23-3 FIND MINIMUM MIN() . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-23-4 AVERAGE VALUE AVG() . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-23-5 SUM SUM() . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-24 Logic Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-24-1 COMPLEMENT COM(29) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-24-2 LOGICAL AND ANDW(34) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-24-3 LOGICAL OR ORW(35) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-24-4 EXCLUSIVE OR XORW(36) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-24-5 EXCLUSIVE NOR XNRW(37) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-25 Increment/Decrement Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-25-1 BCD INCREMENT INC(38) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-25-2 BCD DECREMENT DEC(39) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-26 Subroutine Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-26-1 SUBROUTINE ENTER SBS(91) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-26-2 SUBROUTINE DEFINE and RETURN SBN(92)/RET(93) . . . . . . . . . . . . . . . 7-26-3 MACRO MCRO(99) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-27 Pulse Output Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-27-1 SET PULSES PULS(65) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-27-2 SPEED OUTPUT SPED(64) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-27-3 ACCELERATION CONTROL ACC() . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-27-4 PULSE WITH VARIABLE DUTY RATIO PWM() . . . . . . . . . . . . . . . . . . . 7-27-5 SYNCHRONIZED PULSE CONTROL SYNC() . . . . . . . . . . . . . . . . . . . . . 7-28 Special Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-28-1 MESSAGE DISPLAY MSG(46) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-28-2 I/O REFRESH IORF(97) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-28-3 BIT COUNTER BCNT(67) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-28-4 FRAME CHECKSUM FCS() . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-29 Interrupt Control Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-29-1 INTERRUPT CONTROL INT(89) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-29-2 INTERVAL TIMER STIM(69) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-30 Communications Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-30-1 RECEIVE RXD(47) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-30-2 TRANSMIT TXD(48) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-30-3 CHANGE RS-232C SETUP STUP() . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
467 467 468 470 470 471 471 472 474 476 478 479 479 480 481 481 482 483 483 483 484 484 486 486 487 487 489 491 494 496 497 497 498 499 500 501 501 504 505 505 507 509
363
Section
7-3
7-1
Notation
In the remainder of this manual, all instructions will be referred to by their mnemonics. For example, the OUTPUT instruction will be called OUT; the AND LOAD instruction, AND LD. If youre not sure of the instruction a mnemonic is used for, refer to Appendix A Programming Instructions. If an instruction is assigned a function code, it will be given in parentheses after the mnemonic. These function codes, which are 2-digit decimal numbers, are used to input most instructions into the CPU Unit. A table of instructions listed in order of function codes is also provided in Appendix A Programming Instructions. Lists of instructions are also provided in 7-6 Instruction Tables. An @ before a mnemonic indicates the differentiated version of that instruction. Differentiated instructions are explained in 7-4 Differentiated Instructions.
7-2
Instruction Format
Most instructions have at least one or more operands associated with them. Operands indicate or provide the data on which an instruction is to be performed. These are sometimes input as the actual numeric values (i.e., as constants), but are usually the addresses of data area words or bits that contain the data to be used. A bit whose address is designated as an operand is called an operand bit; a word whose address is designated as an operand is called an operand word. In some instructions, the word address designated in an instruction indicates the first of multiple words containing the desired data. Each instruction requires one or more words in Program Memory. The first word is the instruction word, which specifies the instruction and contains any definers (described below) or operand bits required by the instruction. Other operands required by the instruction are contained in following words, one operand per word. Some instructions require up to four words. A definer is an operand associated with an instruction and contained in the same word as the instruction itself. These operands define the instruction rather than telling what data it is to use. Examples of definers are TC numbers, which are used in timer and counter instructions to create timers and counters, as well as jump numbers (which define which Jump instruction is paired with which Jump End instruction). Bit operands are also contained in the same word as the instruction itself, although these are not considered definers.
7-3
364
Section
7-3
The Flags subsection lists flags that are affected by execution of an instruction. These flags include the following SR area flags.
Abbreviation ER CY GR EQ LE Name Instruction Execution Error Flag Carry Flag Greater Than Flag Equals Flag Less Than Flag Bit 25503 25504 25505 25506 25507
ER is the flag most commonly used for monitoring an instructions execution. When ER goes ON, it indicates that an error has occurred in attempting to execute the current instruction. The Flags subsection of each instruction lists possible reasons for ER being ON. ER will turn ON if operands are not entered correctly. Instructions are not executed when ER is ON. A table of instructions and the flags they affect is provided in Appendix B Error and Arithmetic Flag Operation. Indirect Addressing When the DM area is specified for an operand, an indirect address can be used. Indirect DM addressing is specified by placing an asterisk before the DM: *DM. When an indirect DM address is specified, the designated DM word will contain the address of the DM word that contains the data that will be used as the operand of the instruction. If, for example, *DM 0001 was designated as the first operand and LR 00 as the second operand of MOV(21), the contents of DM 0001 was 1111, and DM 1111 contained 5555, the value 5555 would be moved to LR 00.
Indirect address
Indicates DM 1111.
When using indirect addressing, the address of the desired word must be in BCD and it must specify a word within the DM area. In the above example, the content of DM 0001 has to be in BCD and has to specify an address in the DM area of the PC being used. (Refer to Section 5 Memory Areas for DM area details.) Designating Constants Although data area addresses are most often given as operands, many operands and all definers are input as constants. The available value range for a given definer or operand depends on the particular instruction that uses it. Constants must also be entered in the form required by the instruction, i.e., in BCD or in hexadecimal.
365
Differentiated Instructions
Section
7-4
7-4
Differentiated Instructions
Most instructions are provided in both differentiated and non-differentiated forms. Differentiated instructions are distinguished by an @ in front of the instruction mnemonic. A non-differentiated instruction is executed each time it is scanned as long as its execution condition is ON. A differentiated instruction is executed only once after its execution condition goes from OFF to ON. If the execution condition has not changed or has changed from ON to OFF since the last time the instruction was scanned, the instruction will not be executed. The following two examples show how this works with MOV(21) and @MOV(21), which are used to move the data in the address designated by the first operand to the address designated by the second operand.
00000 MOV(21) HR 10
Instruction LD MOV(21)
Diagram A
DM 0000
00000 @MOV(21) HR 10
Instruction LD @MOV(21)
Diagram B
DM 0000
In diagram A, the non-differentiated MOV(21) will move the content of HR 10 to DM 0000 whenever it is scanned with 00000. If the cycle time is 80 ms and 00000 remains ON for 2.0 seconds, this move operation will be performed 25 times and only the last value moved to DM 0000 will be preserved there. In diagram B, the differentiated @MOV(21) will move the content of HR 10 to DM 0000 only once after 00000 goes ON. Even if 00000 remains ON for 2.0 seconds with the same 80 ms cycle time, the move operation will be executed only once during the first cycle in which 00000 has changed from OFF to ON. Because the content of HR 10 could very well change during the 2 seconds while 00000 is ON, the final content of DM 0000 after the 2 seconds could be different depending on whether MOV(21) or @MOV(21) was used. All operands, ladder diagram symbols, and other specifications for instructions are the same regardless of whether the differentiated or non-differentiated form of an instruction is used. When inputting, the same function codes are also used, but NOT is input after the function code to designate the differentiated form of an instruction. Most, but not all, instructions have differentiated forms. Refer to 7-11 INTERLOCK and INTERLOCK CLEAR IL(02) and IL(03) for the effects of interlocks on differentiated instructions. The CPM2A/CPM2C also provides differentiation instructions: DIFU(13) and DIFD(14). DIFU(13) operates the same as a differentiated instruction, but is used to turn ON a bit for one cycle. DIFD(14) also turns ON a bit for one cycle, but does it when the execution condition has changed from ON to OFF. Refer to 7-8-4 DIFFERENTIATE UP and DOWN - DIFU(13) and DIFD(14) for details.
366
Section
7-5
7-5
367
Section
7-5
The following diagram and corresponding mnemonic code illustrates the points described previously.
00000 00001 DIFU(13) 21600 00002
Address Instruction 00000 00001 00002 LD AND OR DIFU(13) LD AND NOT LD AND NOT AND NOT OR LD AND BCNT(67)
Data 00000 00001 00002 21600 00100 00200 01001 01002 LR 0000 21600 # 0001 004 HR 00 00005 000 # 0150 000 HR LR 00 00 0015 01000
00100
00200
21600 BCNT(67)
01001 01002
LR 0000
00012
HR 0015 01000
LD TIM
00013
00014 00015
LD MOV(21)
TIM
00016 00017
LD OUT NOT
HR
368
Section
7-5
If a right-hand instruction requires multiple instruction lines (such as KEEP(11)), all of the lines for the instruction are entered before the right-hand instruction. Each of the lines for the instruction is coded, starting with LD or LD NOT, to form logic blocks that are combined by the right-hand instruction. An example of this for SFT(10) is shown below.
Address Instruction
I SFT(10) P HR 00
00001
Data 00000 00001 00002 00100 00200 01001 01002 LR 0000 21600 HR HR 00 00 0015 01001
00200
21600
HR 00
00003 00004
01001 01002
LR 0000
HR 0015 01001
00011 00012
LD OUT NOT
HR
369
Instruction Tables
Section
7-6
7-6
Instruction Tables
This section provides tables of the instructions supported by the CPM1/CPM1A, CPM2A/CPM2C, and SRM1(-V2) PCs. The first few tables can be used to find instructions by function code. The last table can be used to find instructions by mnemonic. In both tables, the @ symbol indicates instructions with differentiated forms.
2
IL INTERLOCK
3
ILC INTERLOCK CLEAR DIFU DIFFERENTIATE UP (@) BIN BCD TO BINARY (@) DIV BCD DIVIDE --JMP JUMP
5
JME JUMP END
6
(@) FAL FAILURE ALARM AND RESET (@) WSFT WORD SHIFT (@) ASR SHIFT RIGHT (@) XORW EXCLUSIVE OR (@) MSG MESSAGE DISPLAY (@) MULL DOUBLE BCD MULTIPLY ---
7
FALS SEVERE FAILURE ALARM (@) ASFT ASYNCHRONOUS SHIFT REGISTER (@) ROL ROTATE LEFT (@) XNRW EXCLUSIVE NOR ---
8
STEP STEP DEFINE ---
9
SNXT STEP START
KEEP KEEP
CNTR REVERSIBLE COUNTER (@) MVN MOVE NOT (@) MUL BCD MULTIPLY ---
DIFD DIFFERENTIATE DOWN (@) BCD BINARY TO BCD (@) ANDW LOGICAL AND ---
TIMH HIGHSPEED TIMER (@) ASL SHIFT LEFT (@) ORW LOGICAL OR ---
---
2 3 4 5
(@) MOV MOVE (@) SUB BCD SUBTRACT (@) CLC CLEAR CARRY (@) SBB BINARY SUBTRACT (@) INI MODE CONTROL
(@) MLB BINARY MULTIPLY (@) PRV HIGHSPEED COUNTER PV READ ---
(@) DVB BINARY DIVIDE (@) CTBL COMPARISON TABLE LOAD (@) XCHG DATA EXCHANGE (@) MOVD MOVE DIGIT
(@) ADDL DOUBLE BCD ADD (@) SPED SPEED OUTPUT (see note) (@) SLD ONE DIGIT SHIFT LEFT (@) SFTR REVERSIBLE SHIFT REGISTER ---
(@) SUBL DOUBLE BCD SUBTRACT (@) PULS SET PULSES (see note)
---
---
(@) XFER BLOCK TRANSFER (@) DIST SINGLE WORD DISTRIBUTE ---
(@) SRD ONE DIGIT SHIFT RIGHT (@) TCMP TABLE COMPARE ---
---
---
370
Instruction Tables
Section
7-6
2
IL INTERLOCK
3
ILC INTERLOCK CLEAR DIFU DIFFERENTIATE UP (@) BIN BCD TO BINARY (@) DIV BCD DIVIDE --JMP JUMP
5
JME JUMP END
6
(@) FAL FAILURE ALARM AND RESET (@) WSFT WORD SHIFT (@) ASR SHIFT RIGHT (@) XORW EXCLUSIVE OR (@) MSG MESSAGE DISPLAY (@) MULL DOUBLE BCD MULTIPLY (@) SCL SCALING
7
FALS SEVERE FAILURE ALARM (@) ASFT ASYNCHRONOUS SHIFT REGISTER (@) ROL ROTATE LEFT (@) XNRW EXCLUSIVE NOR (@) RXD RECEIVE (@) DIVL DOUBLE BCD DIVIDE (@) BCNT BIT COUNTER
8
STEP STEP DEFINE ---
9
SNXT STEP START
KEEP KEEP
CNTR REVERSIBLE COUNTER (@) MVN MOVE NOT (@) MUL BCD MULTIPLY ---
DIFD DIFFERENTIATE DOWN (@) BCD BINARY TO BCD (@) ANDW LOGICAL AND ---
TIMH HIGHSPEED TIMER (@) ASL SHIFT LEFT (@) ORW LOGICAL OR ---
---
2 3 4 5
(@) MOV MOVE (@) SUB BCD SUBTRACT (@) CLC CLEAR CARRY (@) SBB BINARY SUBTRACT
(@) ROR ROTATE RIGHT (@) INC INCREMENT (@) TXD TRANSMIT (@) BINL DOUBLE BCD-TODOUBLE BINARY (@) BCMP BLOCK COMPARE
(@) CTBL COMPARISON TABLE LOAD (@) XCHG DATA EXCHANGE (@) MOVD MOVE DIGIT
(@) XFER BLOCK TRANSFER (@) DIST SINGLE WORD DISTRIBUTE ---
(@) SLD ONE DIGIT SHIFT LEFT (@) SFTR REVERSIBLE SHIFT REGISTER ---
(@) SRD ONE DIGIT SHIFT RIGHT (@) TCMP TABLE COMPARE ---
---
---
Note The shaded areas are function codes to which expansion instructions are allocated by default or to which the user can allocate expansion instructions. The following expansion instructions are available in addition to the ones listed above with default function codes.
Mnemonic (@)ACC AVG (@)FCS (@)HEX (@)HMS (@)MAX (@)MIN (@)NEG PID (@)PWM (@)SCL2 Name ACCELERATION CONTROL AVERAGE VALUE FCS CALCULATE ASCII-TO-HEXADECIMAL SECONDS TO HOURS FIND MAXIMUM FIND MINIMUM 2S COMPLEMENT PID CONTROL PULSE WITH VARIABLE DUTY RATIO SIGNED BINARY TO BCD SCALING Mnemonic (@)SCL3 (@)SEC (@)SRCH (@)STUP (@)SUM SYNC TIML TMHH ZCP ZCPL Name BCD TO SIGNED BINARY SCALING HOURS TO SECONDS DATA SEARCH CHANGE RS-232C SETUP SUM CALCULATE SYNCHRONIZED PULSE CONTROL LONG TIMER VERY HIGH-SPEED TIMER AREA RANGE COMPARE DOUBLE AREA RANGE COMPARE CO
371
Instruction Tables
Section
7-6
2
IL INTERLOCK
3
ILC INTERLOCK CLEAR DIFU DIFFERENTIATE UP (@) BIN BCD TO BINARY (@) DIV BCD DIVIDE --JMP JUMP
5
JME JUMP END
6
(@) FAL FAILURE ALARM AND RESET (@) WSFT WORD SHIFT (@) ASR SHIFT RIGHT (@) XORW EXCLUSIVE OR (@) MSG MESSAGE DISPLAY (@) MULL DOUBLE BCD MULTIPLY (@) SCL SCALING (@) MLPX 4-TO-16 DECODER (@) ASC ASCII CONVERT ---
7
FALS SEVERE FAILURE ALARM (@) ASFT ASYNCHRONOUS SHIFT REGISTER (@) ROL ROTATE LEFT (@) XNRW EXCLUSIVE NOR (@) RXD RECEIVE (@) DIVL DOUBLE BCD DIVIDE (@) BCNT BIT COUNTER (@) DMPX 16-TO-4 ENCODER ---
8
STEP STEP DEFINE ---
9
SNXT STEP START
KEEP KEEP
CNTR REVERSIBLE COUNTER (@) MVN MOVE NOT (@) MUL BCD MULTIPLY ---
DIFD DIFFERENTIATE DOWN (@) BCD BINARY TO BCD (@) ANDW LOGICAL AND ---
TIMH HIGHSPEED TIMER (@) ASL SHIFT LEFT (@) ORW LOGICAL OR ---
---
2 3 4 5
(@) MOV MOVE (@) SUB BCD SUBTRACT (@) CLC CLEAR CARRY (@) SBB BINARY SUBTRACT ---
(@) ROR ROTATE RIGHT (@) INC INCREMENT (@) TXD TRANSMIT ---
---
6 7
CMPL DOUBLE COMPARE (@) XFER BLOCK TRANSFER (@) DIST SINGLE WORD DISTRIBUTE ---
---
(@) SLD ONE DIGIT SHIFT LEFT (@) SFTR REVERSIBLE SHIFT REGISTER ---
(@) SRD ONE DIGIT SHIFT RIGHT (@) TCMP TABLE COMPARE ---
---
---
---
Note The shaded areas are function codes to which expansion instructions are allocated by default or to which the user can allocate expansion instructions. The following expansion instructions are available in addition to the ones listed above with default function codes.
Mnemonic (@)FCS (@)HEX (@)NEG* PID* (@)STUP ZCP* Name FCS CALCULATE ASCII-TO-HEXADECIMAL 2S COMPLEMENT PID CONTROL CHANGE RS-232C SETUP AREA RANGE COMPARE
Note *SCL(66), NEG(), PID(), and ZCP () are supported by the SRM1-C0j-V2 CPUs only.
372
Instruction Tables
Section
7-6
ANDW (@) 34
373
Instruction Tables
Mnemonic ILC INC (@) INI (@) INT (@) IORF (@) JME JMP KEEP LD LD NOT MAX (@) MIN (@) MLB (@) MLPX (@) MOV (@) MOVB (@) MOVD (@) MSG (@) MUL (@) MULL (@) MVN (@) NEG (@) NOP OR OR LD OR NOT ORW (@) OUT OUT NOT PID PRV (@) PULS (@) PWM (@) RET ROL (@) ROR (@) RSET RXD (@) SBB (@) SBN SBS (@) SCL (@) SCL2 (@) SCL3 (@) SDEC (@) SEC SET Code 03 38 61 89 97 05 04 11 None None 52 76 21 82 83 46 32 56 22 00 None None None 35 None None 62 65 93 27 28 None 47 51 92 91 66 78 None Words 1 2 4 4 3 2 2 2 1 1 4 4 4 4 4 3 4 4 2 4 4 3 4 1 1 1 1 4 2 2 4 4 4 4 1 2 2 2 4 4 2 2 4 4 4 4 4 2 INCREMENT MODE CONTROL INTERRUPT CONTROL I/O REFRESH JUMP END JUMP KEEP LOAD LOAD NOT FIND MAXIMUM MACRO FIND MINIMUM BINARY MULTIPLY 4-TO-16 DECODER MOVE MOVE BIT MOVE DIGIT MESSAGE BCD MULTIPLY DOUBLE BCD MULTIPLY MOVE NOT 2S COMPLEMENT NO OPERATION OR OR LOAD OR NOT LOGICAL OR OUTPUT OUTPUT NOT PID CONTROL HIGH-SPEED COUNTER PV READ SET PULSES PULSE WITH VARIABLE DUTY RATIO SUBROUTINE RETURN ROTATE LEFT ROTATE RIGHT RESET RECEIVE BINARY SUBTRACT SUBROUTINE DEFINE SUBROUTINE ENTRY SCALING SIGNED BINARY TO BCD SCALING BCD TO SIGNED BINARY SCALING 7-SEGMENT DECODER HOURS TO SECONDS SET Name INTERLOCK CLEAR All All All All All except SRM1 All All All All All CPM2A/CPM2C All CPM2A/CPM2C All All All All All All All All All CPU Units
Section
7-6
Page 381 483 399 501 498 383 383 379 376 376 472 486 474 470 442 411 419 420 497 460 466 412 455 381 376 377 376 481 377 377 426 401 487 494 486 406 407 378 505 468 486 484 421 423 424 446 453 378
MCRO (@) 99
CPM2A/CPM2C/SRM1(-V2) All All All All All All All CPM2A/CPM2C/SRM1(-V2) All except SRM1 CPM1A/CPM2A/CPM2C (Transistor outputs only) CPM2A/CPM2C All All All All CPM2A/CPM2C/SRM1 All All All CPM2A/CPM2C/SRM1(-V2) CPM2A/CPM2C CPM2A/CPM2C CPM2A/CPM2C CPM2A/CPM2C All
374
Instruction Tables
Mnemonic SFT SFTR (@) SLD (@) SNXT SPED (@) SRCH (@) SRD (@) STC (@) STEP STIM (@) STUP SUB (@) SUBL (@) SUM (@) SYNC (@) TCMP (@) TIM TIMH TIML TMHH TXD (@) WSFT (@) XCHG (@) XFER (@) XNRW (@) ZCP ZCPL Code 10 84 74 09 64 75 40 08 69 31 55 85 None 15 48 16 73 70 37 Words 3 4 3 2 4 4 3 1 2 4 3 4 4 4 4 4 2 3 4 4 4 3 3 4 4 4 4 4 SHIFT REGISTER REVERSIBLE SHIFT REGISTER ONE DIGIT SHIFT LEFT STEP START SPEED OUTPUT DATA SEARCH ONE DIGIT SHIFT RIGHT SET CARRY STEP DEFINE INTERVAL TIMER CHANGE RS-232C SETUP BCD SUBTRACT DOUBLE BCD SUBTRACT SUM SYNCHRONIZED PULSE CONTROL TABLE COMPARE TIMER HIGH-SPEED TIMER LONG TIMER VERY HIGH-SPEED TIMER TRANSMIT WORD SHIFT DATA EXCHANGE BLOCK TRANSFER EXCLUSIVE NOR EXCLUSIVE OR AREA RANGE COMPARE DOUBLE AREA RANGE COMPARE Name All All All All CPU Units
Section
7-6
Page 404 409 408 385 489 471 408 457 385 504 509 458 464 478 496 433 389 390 392 391 507 405 415 413 482 481 437 438
CPM1A/CPM2A/CPM2C (Transistor outputs only) CPM2A/CPM2C All All All All CPM2A/CPM2C/SRM1 All All CPM2A/CPM2C CPM2A/CPM2C All All All CPM2A/CPM2C CPM2A/CPM2C CPM2A/CPM2C/SRM1 All All All All All CPM2A/CPM2C/SRM1(-V2) CPM2A/CPM2C
XORW (@) 36
375
Section
7-7
7-7
7-7-1 LOAD, LOAD NOT, AND, AND NOT, OR, and OR NOT
Ladder Symbols
B
LOAD LD
AND AND
B: Bit
OR OR
B: Bit
OR NOT OR NOT
Limitations
There is no limit to the number of any of these instructions, or restrictions in the order in which they must be used, as long as the memory capacity of the PC is not exceeded. These six basic instructions correspond to the conditions on a ladder diagram. As described in Section 6 Ladder-diagram Programming, the status of the bits assigned to each instruction determines the execution conditions for all other instructions. Each of these instructions and each bit address can be used as many times as required. Each can be used in as many of these instructions as required. The status of the bit operand (B) assigned to LD or LD NOT determines the first execution condition. AND takes the logical AND between the execution condition and the status of its bit operand; AND NOT, the logical AND between the execution condition and the inverse of the status of its bit operand. OR takes the logical OR between the execution condition and the status of its bit operand; OR NOT, the logical OR between the execution condition and the inverse of the status of its bit operand.
Description
Flags
376
Section
7-8
Ladder Symbol
00001
00003
OR LOAD OR LD
00000 00001
Ladder Symbol
00002 00003
Description
When instructions are combined into blocks that cannot be logically combined using only OR and AND operations, AND LD and OR LD are used. Whereas AND and OR operations logically combine a bit status and an execution condition, AND LD and OR LD logically combine two execution conditions, the current one and the last unused one. In order to draw ladder diagrams, it is not necessary to use AND LD and OR LD instructions, nor are they necessary when inputting ladder diagrams directly, as is possible from the SSS. They are required, however, to convert the program to and input it in mnemonic form. In order to reduce the number of programming instructions required, a basic understanding of logic block instructions is required. For an introduction to logic blocks, refer to 6-3-6 Logic Block Instructions. There are no flags affected by these instructions.
Flags
7-8
Ladder Symbol
Limitations Description
Any output bit can generally be used in only one instruction that controls its status. OUT and OUT NOT are used to control the status of the designated bit according to the execution condition.
377
Section
7-8
OUT turns ON the designated bit for an ON execution condition, and turns OFF the designated bit for an OFF execution condition. With a TR bit, OUT appears at a branching point rather than at the end of an instruction line. Refer to 6-3-8 Branching Instruction Lines for details. OUT NOT turns ON the designated bit for a OFF execution condition, and turns OFF the designated bit for an ON execution condition. OUT and OUT NOT can be used to control execution by turning ON and OFF bits that are assigned to conditions on the ladder diagram, thus determining execution conditions for other instructions. This is particularly helpful and allows a complex set of conditions to be used to control the status of a single work bit, and then that work bit can be used to control other instructions. The length of time that a bit is ON or OFF can be controlled by combining the OUT or OUT NOT with TIM. Refer to Examples under 7-15-1 TIMER TIM for details. Flags There are no flags affected by these instructions.
RSET B
Description
SET turns the operand bit ON when the execution condition is ON, and does not affect the status of the operand bit when the execution condition is OFF. RSET turns the operand bit OFF when the execution condition is ON, and does not affect the status of the operand bit when the execution condition is OFF. The operation of SET differs from that of OUT because the OUT instruction turns the operand bit OFF when its execution condition is OFF. Likewise, RSET differs from OUT NOT because OUT NOT turns the operand bit ON when its execution condition is OFF. Note On the Programming Console, input SET by pressing the FUN and SET Keys and input RSET by pressing the FUN and RESET Keys.
Precautions
The status of operand bits for SET and RSET programmed between IL(02) and ILC(03) or JMP(04) and JME(05) will not change when the interlock or jump condition is met (i.e., when IL(02) or JMP(04) is executed with an OFF execution condition). There are no flags affected by these instructions. The following examples demonstrate the difference between OUT and SET/ RSET. In the first example (Diagram A), IR 20000 will be turned ON or OFF whenever IR 00000 goes ON or OFF.
Flags Examples
378
Section
7-8
In the second example (Diagram B), IR 10000 will be turned ON when IR 00001 goes ON and will remain ON (even if IR 00001 goes OFF) until IR 00002 goes ON.
00000 20000
Instruction LD OUT
Diagram A
Diagram B
Limitations
Any output bit can generally be used in only one instruction that controls its status. KEEP(11) is used to maintain the status of the designated bit based on two execution conditions. These execution conditions are labeled S and R. S is the set input; R, the reset input. KEEP(11) operates like a latching relay that is set by S and reset by R. When S turns ON, the designated bit will go ON and stay ON until reset, regardless of whether S stays ON or goes OFF. When R turns ON, the designated bit will go OFF and stay OFF until reset, regardless of whether R stays ON or goes OFF. The relationship between execution conditions and KEEP(11) bit status is shown below.
Description
Status of B
Flags
379
Section
7-8
Exercise caution when using a KEEP reset line that is controlled by an external normally closed device. Never use an input bit in an inverse condition on the reset (R) for KEEP(11) when the input device uses an AC power supply. The delay in shutting down the PCs DC power supply (relative to the AC power supply to the input device) can cause the designated bit of KEEP(11) to be reset. This situation is shown below.
Input Unit A S KEEP(11)
NEVER
A R
Bits used in KEEP are not reset in interlocks. Refer to the 7-11 INTERLOCK and INTERLOCK CLEAR IL(02) and ILC(03) for details.
DIFD(14) B
Limitations Description
Any output bit can generally be used in only one instruction that controls its status. DIFU(13) and DIFD(14) are used to turn the designated bit ON for one cycle only. Whenever executed, DIFU(13) compares its current execution with the previous execution condition. If the previous execution condition was OFF and the current one is ON, DIFU(13) will turn ON the designated bit. If the previous execution condition was ON and the current execution condition is either ON or OFF, DIFU(13) will either turn the designated bit OFF or leave it OFF (i.e., if the designated bit is already OFF). The designated bit will thus never be ON for longer than one cycle, assuming it is executed each cycle (see Precautions, below). Whenever executed, DIFD(14) compares its current execution with the previous execution condition. If the previous execution condition was ON and the current one is OFF, DIFD(14) will turn ON the designated bit. If the previous execution condition was OFF and the current execution condition is either ON or OFF, DIFD(14) will either turn the designated bit OFF or leave it OFF. The designated bit will thus never be ON for longer than one cycle, assuming it is executed each cycle (see Precautions, below). These instructions are used when differentiated instructions (i.e., those prefixed with an @) are not available and single-cycle execution of a particular instruction is desired. They can also be used with non-differentiated forms of instructions that have differentiated forms when their use will simplify programming. Examples of these are shown below.
Flags
380
Section 7-11
DIFU(13) and DIFD(14) operation can be uncertain when the instructions are programmed between IL and ILC, between JMP and JME, or in subroutines. Refer to 7-11 INTERLOCK and INTERLOCK CLEAR IL(02) and ILC(03), 7-12 JUMP and JUMP END JMP(04) and JME(05), 7-26 Subroutine Instructions, and 7-29-1 INTERRUPT CONTROL INT(89). In this example, IR 20014 will be turned ON for one cycle when IR 00000 goes from OFF to ON. IR 20015 will be turned ON for one cycle when IR 00000 goes from ON to OFF.
DIFU(13) 20014
Example
00000
DIFD(14) 20015
7-9
NO OPERATION NOP(00)
NOP(00) is not generally required in programming and there is no ladder symbol for it. When NOP(00) is found in a program, nothing is executed and the program execution moves to the next instruction. When memory is cleared prior to programming, NOP(00) is written at all addresses. NOP(00) can be input through the 00 function code. There are no flags affected by NOP(00).
Description
Flags
END(01) is required as the last instruction in any program. If there are subroutines, END(01) is placed after the last subroutine. No instruction written after END(01) will be executed. END(01) can be placed anywhere in the program to execute all instructions up to that point, as is sometimes done to debug a program, but it must be removed to execute the remainder of the program. If there is no END(01) in the program, no instructions will be executed and the error message NO END INST will appear. END(01) turns OFF the ER, CY, GR, EQ, and LE flags.
Flags
ILC(03)
IL(02) is always used in conjunction with ILC(03) to create interlocks. Interlocks are used to enable branching in the same way as can be achieved with TR bits, but treatment of instructions between IL(02) and ILC(03) differs from that with TR bits when the execution condition for IL(02) is OFF. If the execution condition of IL(02) is ON, the program will be executed as written, with an ON execution condition used to start each instruction line from the point where IL(02) is located through the next ILC(03). Refer to 6-3-8 Branching Instruction Lines for basic descriptions of both methods.
381
Section 7-11
If the execution condition for IL(02) is OFF, the interlocked section between IL(02) and ILC(03) will be treated as shown in the following table:
Instruction OUT and OUT NOT TIM and TIMH(15) CNT, CNTR(12) KEEP(11) DIFU(13) and DIFD(14) All other instructions Reset. PV maintained. Bit status maintained. Not executed (see below). The instructions are not executed, and all IR, AR, LR, HR, and SR bits and words written to as operands in the instructions are turned OFF. Treatment Designated bit turned OFF.
IL(02) and ILC(03) do not necessarily have to be used in pairs. IL(02) can be used several times in a row, with each IL(02) creating an interlocked section through the next ILC(03). ILC(03) cannot be used unless there is at least one IL(02) between it and any previous ILC(03). DIFU(13) and DIFD(14) in Interlocks Changes in the execution condition for a DIFU(13) or DIFD(14) are not recorded if the DIFU(13) or DIFD(14) is in an interlocked section and the execution condition for the IL(02) is OFF. When DIFU(13) or DIFD(14) is execution in an interlocked section immediately after the execution condition for the IL(02) has gone ON, the execution condition for the DIFU(13) or DIFD(14) will be compared to the execution condition that existed before the interlock became effective (i.e., before the interlock condition for IL(02) went OFF). The ladder diagram and bit status changes for this are shown below. The interlock is in effect while 00000 is OFF. Notice that 20000 is not turned ON at the point labeled A even though 00001 has turned OFF and then back ON.
A
ON
Precautions
There must be an ILC(03) following any one or more IL(02). Although as many IL(02) instructions as are necessary can be used with one ILC(03), ILC(03) instructions cannot be used consecutively without at least one IL(02) in between, i.e., nesting is not possible. Whenever a ILC(03) is executed, all interlocks between the active ILC(03) and the preceding ILC(03) are cleared. When more than one IL(02) is used with a single ILC(03), an error message will appear when the program check is performed, but execution will proceed normally.
Flags
382
Section 7-12
The following diagram shows IL(02) being used twice with one ILC(03).
Address 00000 00001 00002 00003 00004 00005 00006 00007 00008 00009 00010 00011 00012 00013 Instruction LD IL(02) LD TIM # LD IL(02) LD AND NOT LD LD CNT LD OUT ILC(03) Operands 00000 00001 000 0015 00002 00003 00004 00100 00100 001 010 00005 01002
00005 01002
ILC(03)
When the execution condition for the first IL(02) is OFF, TIM 000 will be reset to 1.5 s, CNT 001 will not be changed, and 01002 will be turned OFF. When the execution condition for the first IL(02) is ON and the execution condition for the second IL(02) is OFF, TIM 000 will be executed according to the status of 00001, CNT 001 will not be changed, and 01002 will be turned OFF. When the execution conditions for both the IL(02) are ON, the program will execute as written.
JME(05) N
Limitations
Jump numbers 01 through 49 may be used only once in JMP(04) and once in JME(05), i.e., each can be used to define one jump only. Jump number 00 can be used as many times as desired. JMP(04) is always used in conjunction with JME(05) to create jumps, i.e., to skip from one point in a ladder diagram to another point. JMP(04) defines the point from which the jump will be made; JME(05) defines the destination of the jump. When the execution condition for JMP(04) in ON, no jump is made and the program is executed consecutively as written. When the execution condition for JMP(04) is OFF, a jump is made to the JME(05) with the same jump number and the instruction following JME(05) is executed next. If the jump number for JMP(04) is between 01 and 49, jumps, when made, will go immediately to JME(05) with the same jump number without executing any instructions in between. The status of timers, counters, bits used in OUT, bits used in OUT NOT, and all other status bits controlled by the instructions between JMP(04) and JMP(05) will not be changed. Each of these jump numbers can be used to define only one jump. Because all of instructions between JMP(04) and JME(05) are skipped, jump numbers 01 through 49 can be used to reduce cycle time.
Description
383
Section 7-12
Jump Number 00 If the jump number for JMP(04) is 00, the CPU Unit will look for the next JME(05) with a jump number of 00. To do so, it must search through the program, causing a longer cycle time (when the execution condition is OFF) than for other jumps. The status of timers, counters, bits used in OUT, bits used in OUT NOT, and all other status controlled by the instructions between JMP(04) 00 and JME(05) 00 will not be changed. jump number 00 can be used as many times as desired. A jump from JMP(04) 00 will always go to the next JME(05) 00 in the program. It is thus possible to use JMP(04) 00 consecutively and match them all with the same JME(05) 00. It makes no sense, however, to use JME(05) 00 consecutively, because all jumps made to them will end at the first JME(05) 00. DIFU(13) and DIFD(14) in Jumps Although DIFU(13) and DIFD(14) are designed to turn ON the designated bit for one cycle, they will not necessarily do so when written between JMP(04) and JME(05). Once either DIFU(13) or DIFD(14) has turned ON a bit, it will remain ON until the next time DIFU(13) or DIFD(14) is executed again. In normal programming, this means the next cycle. In a jump, this means the next time the jump from JMP(04) to JME(05) is not made, i.e., if a bit is turned ON by DIFU(13) or DIFD(14) and then a jump is made in the next cycle so that DIFU(13) or DIFD(14) are skipped, the designated bit will remain ON until the next time the execution condition for the JMP(04) controlling the jump is ON. When TIMH(15) or TMHH() is programmed between JMP(04) and JME(05), timing will be performed by interrupt if jump numbers 01 through 49 are used but timing wont be performed if jump number 00 is used. When JMP(04) and JME(05) are not used in pairs, an error message will appear when the program check is performed. This message also appears if JMP(04) 00 and JME(05) 00 are not used in pairs, but the program will execute properly as written. There are no flags affected by these instructions. Examples of jump programs are provided in 6-3-9 Jumps.
Flags Examples
384
Step Instructions
Section 7-14
7-13 User Error Instructions: FAILURE ALARM AND RESET FAL(06) and SEVERE FAILURE ALARM FALS(07)
Ladder Symbols FAL(06) N @FAL(06) N Definer Data Areas
N: FAL number # (00 to 99) N: FAL number # (01 to 99)
FALS(07) N
Description
FAL(06) and FALS(07) are provided so that the programmer can output error numbers for use in operation, maintenance, and debugging. When executed with an ON execution condition, either of these instructions will output a FAL number to bits 00 to 07 of SR 253. The FAL number that is output can be between 01 and 99 and is input as the definer for FAL(06) or FALS(07). FAL(06) with a definer of 00 is used to reset this area (see below). FAL Area
25307 25300
X101
X100
FAL(06) produces a non-fatal error and FALS(07) produces a fatal error. When FAL(06) is executed with an ON execution condition, the ALARM/ERROR indicator on the front of the CPU Unit will flash, but PC operation will continue. When FALS(07) is executed with an ON execution condition, the ALARM/ERROR indicator will light and PC operation will stop. The system also generates error codes to the FAL area. Resetting Errors FAL error codes will be retained in memory, although only one of these is available in the FAL area. To access the other FAL codes, reset the FAL area by executing FAL(06) 00. Each time FAL(06) 00 is executed, another FAL error will be moved to the FAL area, clearing the one that is already there. FAL(06) 00 is also used to clear message programmed with the instruction, MSG(46). If the FAL area cannot be cleared, as is generally the case when FALS(07) is executed, first remove the cause of the error and then clear the FAL area through the Programming Console or SSS.
SNXT(09) B
385
Step Instructions
Limitations Description
Section 7-14
All control bits must be in the same word and must be consecutive. The step instructions STEP(08) and SNXT(09) are used together to set up breakpoints between sections in a large program so that the sections can be executed as units and reset upon completion. A section of program will usually be defined to correspond to an actual process in the application. (Refer to the application examples later in this section.) A step is like a normal programming code, except that certain instructions (i.e., END(01), IL(02)/ILC(03), JMP(04)/JME(05), and SBN(92)) may not be included. STEP(08) uses a control bit in the IR or HR areas to define the beginning of a section of the program called a step. STEP(08) does not require an execution condition, i.e., its execution is controlled through the control bit. To start execution of the step, SNXT(09) is used with the same control bit as used for STEP(08). If SNXT(09) is executed with an ON execution condition, the step with the same control bit is executed. If the execution condition is OFF, the step is not executed. The SNXT(09) instruction must be written into the program so that it is executed before the program reaches the step it starts. It can be used at different locations before the step to control the step according to two different execution conditions (see example 2, below). Any step in the program that has not been started with SNXT(09) will not be executed. Once SNXT(09) is used in the program, step execution will continue until STEP(08) is executed without a control bit. STEP(08) without a control bit must be preceded by SNXT(09) with a dummy control bit. The dummy control bit may be any unused IR or HR bit. It cannot be a control bit used in a STEP(08).
386
Step Instructions
Section 7-14
Execution of a step is completed either by execution of the next SNXT(09) or by turning OFF the control bit for the step (see example 3 below). When the step is completed, all of the IR and HR bits in the step are turned OFF and all timers in the step are reset to their SVs. Counters, shift registers, and bits used in KEEP(11) maintain status. Two simple steps are shown below.
STEP(08) LR 1005
1st step
STEP(08) 20200
2nd step
STEP(08)
Address 00102
Instruction STEP(08)
Operands 20200
LR LR
Step controlled by IR 20200. 00200 00201 00202 LD SNXT(09) STEP(08) 00002 23000 ---
Steps can be programmed in consecutively. Each step must start with STEP(08) and generally ends with SNXT(09) (see example 3, below, for an exception). When steps are programmed in series, three types of execution are possible: sequential, branching, or parallel. The execution conditions for, and the positioning of, SNXT(09) determine how the steps are executed. The three examples given below demonstrate these three types of step execution. Precautions Interlocks, jumps, SBN(92), and END(01) cannot be used within step programs. Bits used as control bits must not be used anywhere else in the program unless they are being used to control the operation of the step (see example 3, below). All control bits must be in the same word and must be consecutive. If IR or LR bits are used for control bits, their status will be lost during any power interruption. If it is necessary to maintain status to resume execution at the same step, HR bits must be used.
387
Section 7-15
25407: Step Start Flag; turns ON for one cycle when STEP(08) is executed and can be used to reset counters in steps as shown below if necessary.
25407
#0003
1 cycle
Instruction LD CNT #
388
Section 7-15
Note that TIM 000 is used to designate the TIMER instruction defined with TC number 000, to designate the Completion Flag for this timer, and to designate the PV of this timer. The meaning of the term in context should be clear, i.e., the first is always an instruction, the second is always a bit operand, and the third is always a word operand. The same is true of all other TC numbers prefixed with TIM or CNT. An SV can be input as a constant or as a word address in a data area. If an IR area word assigned to an Input Unit is designated as the word address, the Input Unit can be wired so that the SV can be set externally through thumbwheel switches or similar devices. Timers and counters wired in this way can only be set externally during RUN or MONITOR mode. All SVs, including those set externally, must be in BCD.
N TC number
Limitations
SV is between 000.0 and 999.9. The decimal point is not entered. Each TC number can be used as the definer in only one TIMER or COUNTER instruction. TC numbers run from 000 through 255 in the CPM2A/CPM2C PCs and from 000 through 127 in the CPM1/CPM1A/SRM1(-V2) PCs. TC 000 through TC 003 (TC 000 through TC 015 in the CPM2A/CPM2C) should not be used in TIM if they are required for TIMH(15). Refer to 7-15-2 HIGHSPEED TIMER TIMH(15) for details. In the CPM2A/CPM2C PCs, TC 004 through TC 007 should not be used in TIM if they are required for TMHH(). Refer to 7-15-3 VERY HIGH-SPEED TIMER TMHH() for details. A timer is activated when its execution condition goes ON and is reset (to SV) when the execution condition goes OFF. Once activated, TIM measures in units of 0.1 second from the SV. If the execution condition remains ON long enough for TIM to time down to zero, the Completion Flag for the TC number used will turn ON and will remain ON until TIM is reset (i.e., until its execution condition is goes OFF). The following figure illustrates the relationship between the execution condition for TIM and the Completion Flag assigned to it.
ON
Description
Execution condition
OFF ON
Completion Flag
OFF
SV
SV
Precautions
Timers in interlocked program sections are reset when the execution condition for IL(02) is OFF. Power interruptions also reset timers. If a timer that is not reset under these conditions is desired, SR area clock pulse bits can be counted to produce timers using CNT. Refer to 7-15-5 COUNTER CNT for details.
389
Section 7-15
The Completion Flag may be turned ON one cycle late when reading its status from the user program. Always reset the timer after changing between TIM and TIMH(015) in online editing. The timer will not work properly if it is not reset. If the timers set value is set to 0000, the Completion Flag will turn ON as soon as the timers execution condition turns ON. If the timers set value is set to 0001, the Completion Flag will turn ON somewhere between 0 and 0.1 s after the timers execution condition turns ON (i.e., the timer accuracy will actually determine the time), and may turn ON as soon as the timers execution condition turns ON. Always consider the accuracy of the timer (0 to 0.1 s) in application programs. Flags ER: Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.)
N TC number
Limitations
SV is between 00.00 and 99.99. (Although 00.00 and 00.01 may be set, 00.00 will disable the timer, i.e., turn ON the Completion Flag immediately, and 00.01 is not reliably scanned.) The decimal point is not entered. Each TC number can be used as the definer in only one TIMER or COUNTER instruction. TC numbers run from 000 through 255 in the CPM2A/CPM2C PCs and from 000 through 127 in the CPM1/CPM1A/SRM1(-V2) PCs. TIMH(15) operates in the same way as TIM except that TIMH measures in units of 0.01 second. Refer to 7-15-1 TIMER TIM for operational details. Timers in interlocked program sections are reset when the execution condition for IL(02) is OFF. Power interruptions also reset timers. If a timer that is not reset under these conditions is desired, SR area clock pulse bits can be counted to produce timers using CNT. Refer to 7-15-5 COUNTER CNT for details. Timers in jumped program sections will not be reset when the execution condition for JMP(04) is OFF. The timer will stop timing if jump number 00 is used, but will continue timing if other jump numbers are used. Always reset the timer when changing between TIM and TIMH(15) in online editing. Also, when changing a TIMH(15) instruction with interrupt refreshing, do so only in PROGRAM mode. Use timer numbers 000 to 003 for TIMH(15). High-speed timers with timer numbers TC 004 through TC 127 (TC 016 through TC 255 in the CPM2A/CPM2C) may not be accurate when the cycle time exceeds 10 ms.
PC CPM2A/CPM2C CPM1, CPM1A, and SRM1(-V2) Interrupt refreshing every 10 ms TC 000 through TC 003 TC 000 through TC 003 Refreshed when TIMH(015) is executed TC 004 through TC 255 TC 004 through TC 127
Description Precautions
390
Section 7-15
In the CPM2A/CPM2C PCs, TC 004 through TC 007 should not be used in TIMH(15) if they are required for TMHH(). Refer to 7-15-3 VERY HIGHSPEED TIMER TMHH() for details. If the timers set value is set to 0000, the Completion Flag will turn ON as soon as the timers execution condition turns ON. If TIM000 to TIM003 are used, however, there may be a delay before the flag turns ON. If the timers set value is set to 0001, the Completion Flag will turn ON somewhere between 0 and 0.01 s after the timers execution condition turns ON (i.e., the timer accuracy will actually determine the time), and may turn ON as soon as the timers execution condition turns ON. Always consider the accuracy of the timer (0 to 0.01 s) in application programs. Flags Example ER: Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.)
The following example shows a timer set with a constant. CIO 01600 will be turned ON after CIO 00000 goes ON and stays ON for at least 1.5 seconds. When 00000 goes OFF, the timer will be reset and CIO 01600 will be turned OFF.
TIMH(15) 000 #0150
00000
Address
1.5 s
# TIM
This instruction is supported by the CPM2A/CPM2C only. Limitations Each TC number can be used as the definer in only one TIMER or COUNTER instruction. TC numbers run from TIM000 through TIM255. (You must enter TIM along with the actual timer number when using the Programming Console. The instruction will not work if only the number is entered.) SV is BCD between 0000 and 9999 (0 to 9.999 s). Set the third operand to 000. (This operand is ignored.) TMHH() is a decrementing ON-delay timer that times in 1-ms units. The timer set value can be 0 to 9.999 s and the timer has a accuracy of 1 ms. A very high-speed timer is activated when its execution condition goes ON and is reset (to the SV) when the execution condition goes OFF. Once activated, TMHH() times down from the SV in units of 1 ms. The timer will time out when the PV reaches #0000 (0 ms). Once the timer has timed out, the PV and Completion Flag status will be maintained. The timer can be restarted by temporarily turning its execution condition from ON to OFF or
Description
391
Section 7-15
changing its PV to a value other than #0000 with an instruction such as MOV(21). The operation of very high-speed timers in jumped program sections depends upon the TC number used to define the timer, as shown in the following table.
TC number 000 to 003, 008 to 255 004 to 007 Operation The timer will stop when the execution condition for JMP(04) is OFF. This can greatly reduce the accuracy of timers in jumped program sections. If jump number 00 is used, the timer will stop timing when the execution condition for JMP(04) is OFF. This can greatly reduce the accuracy of timers in jumped program sections. If any other jump number is used, the timer will continue timing normally when the execution condition for JMP(04) is OFF.
Precautions
Very high-speed timers with timer numbers other than TC 004 through TC 007 may not be accurate when the cycle time exceeds 1 ms. (The cycle time will not affect very high-speed timers defined with TC 004 through TC 007.) Very high-speed timers in interlocked program sections are reset (to the SV) when the execution condition for IL(02) is OFF. If the timers set value is set to 0000, the Completion Flag will turn ON as soon as the timers execution condition turns ON. If TIM004 to TIM007 are used, however, there may be a delay before the flag turns ON. If the timers set value is set to 0001, the Completion Flag will turn ON somewhere between 0 and 1 ms after the timers execution condition turns ON (i.e., the timer accuracy will actually determine the time), and may turn ON as soon as the timers execution condition turns ON. Always consider the accuracy of the timer (0 to 1 ms) in application programs. ER: N is not a valid TC number.
Flags Example
In the following example, CIO 20000 will be turned ON after CIO 00000 goes ON and stays ON for at least 1.5 seconds. When 00000 goes OFF, the timer will be reset and CIO 20000 will be turned OFF.
00000 TMHH() 004 #1500 000 1.5 s
Instruction LD TMHH() #
TIM004 20000
00002 00003
LD OUT
TIM
392
Section 7-15
Each timer number can be used as the definer in only one TIMER or COUNTER instruction. Timer numbers run from TIM000 through TIM255. (You must enter TIM along with the actual timer number when using the Programming Console. The instruction will not work if only the number is entered.) SV is BCD between 0000 and 9999 (0 to 9,999 s when C=000 and 0 to 99,990 s when C=001). C must be 000 (1-s timing units) or 001 (10-s timing units).
Description
TIML() is a decrementing ON-delay timer that can time in 1-s units or 10-s units. The timer set value can be 0 to 9,999 s (accuracy 0 to 1 s) when 1-s units are used (C=000) or 0.10 to 99,990 s (accuracy 0 to 10 s) when 10-s units are used (C=001). A long timer is activated when its execution condition goes ON and is reset (to the SV) when the execution condition goes OFF. Once activated, TIML() times down from the SV in units of 1 s or 10 s (depending upon the value of C). TIML() accuracy is 0 to 1 s with 1-s units or 0 to 10 s with 10-s units. The timer will time out when the PV reaches #0000 (0 s). Once the timer has timed out, the PV and Completion Flag status will be maintained. The timer can be restarted by temporarily turning its execution condition from ON to OFF or changing its PV to a value other than #0000 with an instruction such as MOV(21). Long timers in jumped program sections will not be reset when the execution condition for JMP(04) is OFF, but the timer will stop timing and the PV will be maintained. Timing will resume when the execution condition for JMP(04) goes ON again. This can greatly reduce the accuracy of long timers in jumped program sections.
Precautions
TIML() may not be accurate when the cycle time exceeds 1 s (C=000) or 10 s (C=001). Long timers in interlocked program sections are reset (to the SV) when the execution condition for IL(02) is OFF. The timing units in C can be changed while the long timer is timing. Changing the timing units during operation reduces the timers accuracy by up to 10 s. You must enter TIM along with the actual timer number when using TIML(). The instruction will not work if only the number is entered. If the timers set value is set to 0000, the Completion Flag will turn ON as soon as the timers execution condition turns ON. If the timers set value is set to 0001, the Completion Flag will turn ON somewhere between 0 and 1 s or between 0 and 10 s after the timers execution condition turns ON (i.e., the timer accuracy will actually determine the time), and may turn ON as soon as the timers execution condition turns ON. Always consider the accuracy of the timer (0 to 1 s or 0 to 10 s) in application programs.
Flags
ER:
393
Section 7-15
In the following example, CIO 20000 will be turned ON after CIO 00000 goes ON and stays ON for at least 1,500 seconds. When 00000 goes OFF, the timer will be reset and CIO 20000 will be turned OFF.
00000 TIML() 002 #0150 001 1500 s
Instruction LD TIML() #
TIM002 20000
00002 00003
LD OUT
TIM
N TC number
Limitations
Each TC number can be used as the definer in only one TIMER or COUNTER instruction. TC numbers run from 000 through 255 in the CPM2A/CPM2C PCs and from 000 through 127 in the CPM1/CPM1A/SRM1(-V2) PCs. CNT is used to count down from SV when the execution condition on the count pulse, CP, goes from OFF to ON, i.e., the present value (PV) will be decremented by one whenever CNT is executed with an ON execution condition for CP and the execution condition was OFF for the last execution. If the execution condition has not changed or has changed from ON to OFF, the PV of CNT will not be changed. The Completion Flag for a counter is turned ON when the PV reaches zero and will remain ON until the counter is reset. CNT is reset with a reset input, R. When R goes from OFF to ON, the PV is reset to SV. The PV will not be decremented while R is ON. Counting down from SV will begin again when R goes OFF. The PV for CNT will not be reset in interlocked program sections or by power interruptions. Changes in execution conditions, the Completion Flag, and the PV are illustrated below. PV line height is meant only to indicate changes in the PV.
Execution condition on count pulse (CP) Execution condition on reset (R)
ON OFF ON OFF ON
Description
Completion Flag
SV
PV
394
Section 7-15
Program execution will continue even if a non-BCD SV is used, but the SV will not be correct. ER: Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.)
Flags Example
In the following example, CNT is used to create extended timers by counting SR area clock pulse bits. CNT 001 counts the number of times the 1-second clock pulse bit (SR 25502) goes from OFF to ON. Here again, IR 00000 is used to control the times when CNT is operating. Because in this example the SV for CNT 001 is 700, the Completion Flag for CNT 002 turns ON when 1 second x 700 times, or 11 minutes and 40 seconds have expired. This would result in IR 20002 being turned ON.
CP CNT 001
00000 25502
00001
#0700
# CNT
! Caution
The shorter clock pulses will not necessarily produce accurate timers because their short ON times might not be read accurately during longer cycles. In particular, the 0.02-second and 0.1-second clock pulses should not be used to create timers with CNT instructions.
N TC number
Limitations
Each TC number can be used as the definer in only one TIMER or COUNTER instruction. TC numbers run from 000 through 255 in the CPM2A/CPM2C PCs and from 000 through 127 in the CPM1/CPM1A/SRM1(-V2) PCs. The CNTR(12) is a reversible, up/down circular counter, i.e., it is used to count between zero and SV according to changes in two execution conditions, those in the increment input (II) and those in the decrement input (DI). The present value (PV) will be incremented by one whenever CNTR(12) is executed with an ON execution condition for II and the last execution condition for II was OFF. The present value (PV) will be decremented by one whenever CNTR(12) is executed with an ON execution condition for DI and the last execution condition for DI was OFF. If OFF to ON changes have occurred in both II and DI since the last execution, the PV will not be changed.
Description
395
Section 7-15
If the execution conditions have not changed or have changed from ON to OFF for both II and DI, the PV of CNT will not be changed. When decremented from 0000, the present value is set to SV and the Completion Flag is turned ON until the PV is decremented again. When incremented past the SV, the PV is set to 0000 and the Completion Flag is turned ON until the PV is incremented again. CNTR(12) is reset with a reset input, R. When R goes from OFF to ON, the PV is reset to zero. The PV will not be incremented or decremented while R is ON. Counting will begin again when R goes OFF. The PV for CNTR(12) will not be reset in interlocked program sections or by the effects of power interruptions. Changes in II and DI execution conditions, the Completion Flag, and the PV are illustrated below starting from part way through CNTR(12) operation (i.e., when reset, counting begins from zero). PV line height is meant to indicate changes in the PV only.
Execution condition on increment (II) Execution condition on decrement (DI)
ON OFF ON OFF ON
Completion Flag
OFF
SV
PV
SV 2
SV 1
Precautions
Program execution will continue even if a non-BCD SV is used, but the SV will not be correct. ER: Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.)
Flags
This instruction is not supported by SRM1(-V2) PCs. Limitations The first and last comparison table words must be in the same data area. (The length of the comparison table varies according to the settings.) P must be 000 and C must be between 000 and 003. When the execution condition is OFF, CTBL(63) is not executed. When the execution condition is ON, CTBL(63) registers a comparison table for use with the high-speed counter PV. Depending on the value of C, comparison with the high-speed counter PV can begin immediately or it can be started separately with INI(61).
Description
396
Section 7-15
The port specifier (P) specifies the high-speed counter that will be used in the comparison. Always set P to 000. The function of CTBL(63) is determined by the control data, C, as shown in the following table. These functions are described after the table.
C 000 001 002 003 CTBL(63) function Registers a target value comparison table and starts comparison. (See note.) Registers a range comparison table and starts comparison. (See note.) Registers a target value comparison table. Start comparison with INI(61). Registers a range comparison table. Start comparison with INI(61).
Note If C is set to 000 or 001, CTBL(63) will continue the comparison operation even when executed only once. As a rule, use the differentiated form (@) of the instruction or an input condition that turns ON for only one cycle. When the PV agrees with a target value or falls within a specified range, the specified subroutine is called and executed. Refer to 2-3-5 High-speed Counter Interrupts for more details on table comparison. If the high-speed counter is enabled in the PC Setup (DM 6642), it will begin counting from zero when the CPM2A/CPM2C begins operation. The PV will not be compared to the comparison table until the table is registered and comparison is initiated with INI(61) or CTBL(63). Comparison can be stopped and started, or the PV can be reset with INI(61). Common Characteristics of Target Value and Range Comparisons 1, 2, 3... The operation of a target value comparison is different from a range comparison, but the two functions share some common characteristics. 1. Subroutine numbers 000 to 049 can be used and the same subroutine number can be used more than once in the table. 2. An undefined subroutine number or FFFF can be set for the subroutine number if interrupt processing is not required. 3. Comparison can be stopped with INI(61). A registered table is valid until PC operation stops or a new comparison table is registered. 4. CTBL(62) cannot be executed if the high-speed counter is disabled in the PC Setup (DM 6642). (An error will occur if CTBL(63) is executed when the high-speed counter is disabled.) Target Value Comparison A target value comparison table contains up to sixteen target values. A subroutine number is also registered for each target value. The corresponding subroutine is called and executed when the PV matches a target value. (When interrupt processing is not required, an undefined subroutine number may be entered.) In the CPM1/CPM1A, target value comparisons are performed one item at a time in order of the comparison table. When the PV reaches the first target value in the table, the interrupt subroutine is executed and comparison continues to the next value in the table. When processing has been completed for the last target value in the table, comparison returns to the first value in the table and the process is repeated. In the CPM2A/CPM2C, the PV is compared to all of the target values in the table each time CTBL(63) is executed. When the PV matches a target value the corresponding subroutine is called and executed.
397
Section 7-15
The following diagram shows the structure of a target value comparison table. Target values must be unique; an error will occur if a target value appears in the table more than once.
TB TB+1 TB+2 TB+3 Number of target values (0001 to 0016, BCD) Target value #1, lower 4 digits (BCD) Target value #1, upper 4 digits (BCD) Subroutine number for #1 (See note.)
Note The subroutine number can be F000 to F049 to activate the subroutine when decrementing and can be 0000 to 0049 to activate the subroutine when incrementing. An error will occur if the high-speed counter is set to increment mode but a decrementing subroutine number (F000 to F049) is specified. Range Comparison A range comparison table contains 8 ranges which are defined by an 8-digit lower limit and an 8-digit upper limit, as well as their corresponding subroutine numbers. The comparison is performed once each cycle at the end of program execution and can be performed during program execution with INI(61). When the PV falls within a given range the corresponding subroutine is called and executed. (When interrupt processing is not required, an undefined subroutine number may be entered.) Ranges can overlap, so the PV can fall within more than one range; in the PV is within two or more ranges, the subroutine for the first of the ranges will be executed. The following diagram shows the structure of a range comparison table. Always set 8 ranges. If fewer than 8 ranges are needed, set the remaining subroutine numbers to FFFF.
TB TB+1 TB+2 TB+3 TB+4 Lower limit #1, lower 4 digits (BCD) Lower limit #1, upper 4 digits (BCD) Upper limit #1, lower 4 digits (BCD) Upper limit #1, upper 4 digits (BCD) Subroutine number (See note 2.)
Lower limit #8, lower 4 digits (BCD) Lower limit #8, upper 4 digits (BCD) Upper limit #8, lower 4 digits (BCD) Upper limit #8, upper 4 digits (BCD) Subroutine number (See note 2.)
Note
1. Each ranges lower limit must be less than its upper limit. An error will occur if the lower limit is greater than the upper limit. 2. The subroutine number can be 0000 to 0049 and the subroutine will be executed as long as the counters PV is within the specified range. A value of FFFF indicates that no subroutine is to be executed. 3. Since the comparison is usually performed just once each cycle, be sure to take the cycle time into account when the upper and lower limits represent time values. 4. A subroutine number can be used more than once in the table. ER: The comparison table exceeds the data area boundary, or there is an error in the comparison table settings. Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.)
Flags
398
Section 7-15
There is a CTBL(63) instruction using a different comparison format in the subroutine called by another CTBL(63) instruction. A CTBL(63) instruction using a different comparison format is executed during comparison. CTBL(63) is executed in an interrupt subroutine while a pulse I/O or high-speed counter instruction (INI(61), PRV(62), CTBL(63), SPED(64), PULS(65), ACC(), PWM(), or SYNC()) is being executed in the main program. Target Value Comparison Errors: The number of target values (in TB) is not between 0001 and 0016. A target value is not between F838 8608 and 0838 8607 (differential phase mode, pulse + direction input mode, and up/down input mode). A target value is not between 0000 0001 and 1677 7215 or a subroutine number is not between 0000 and 0049 (increment mode). If 0000 0000 is set in increment mode, 25503 (ER) will turn ON and the instruction will not be executed. Range Comparison Errors: A ranges upper limit value is less than its lower limit value. A target value is not between F838 8608 and 0838 8607 (differential phase mode, pulse + direction input mode, and up/down input mode). A target value is not between 0000 0000 and 1677 7215 or a subroutine number is not between 0000 and 0049 (increment mode).
This instruction is not supported by SRM1(-V2) PCs. Limitations In the CPM1/CPM1A PCs, P must be 000 and C must be 000 to 003. In CPM2A/CPM2C PCs, P must be 000, 010, 100, 101, 102, or 103 and C must be 000 to 005. P1 must be 000 unless C is 002 or 004. P1 and P1+1 must be in the same data area. If a DM address is used for P1, it must be read/write DM. When the execution condition is OFF, INI(61) is not executed. When the execution condition is ON, INI(61) is used to control high-speed counter operation and stop pulse output.
Description
399
Section 7-15
The port specifier (P) specifies the high-speed counter or pulse output that will be controlled.
P 000 Function Specifies high-speed counter input (inputs 00000, 00001, and 00002), single-phase pulse output 0 with no acceleration/deceleration (output 01000 or 01001), single-phase pulse output 0 with trapezoidal acceleration/deceleration (output 01000). Specifies single-phase pulse output 1 with no acceleration/deceleration (output 01001). Specifies interrupt input 0 in counter mode (input 00003). Specifies interrupt input 1 in counter mode (input 00004). Specifies interrupt input 2 in counter mode (input 00005). Specifies interrupt input 3 in counter mode (input 00006).
Note *These settings can be used in CPM2A/CPM2C PCs only. The function of INI(61) is determined by the control data, C.
C 000 001 002 003 004* 005* 000 000 New PV 000 New PV 000 P1 INI(61) function Starts CTBL(63) table comparison. Stops CTBL(63) table comparison. Changes PV of the high-speed counter or an interrupt input in counter mode. Stops pulse output. Changes PV of the pulse output. Stops synchronized pulse control output.
Note *These settings can be used in CPM2A/CPM2C PCs only. Start or Stop Comparison (C=000 or C=001) If C is 000 or 001, INI(61) starts or stops comparison of the high-speed counters PV to the comparison table registered with CTBL(63). An error will occur if this function is executed without first registering a comparison table with CTBL(63). In general, @INI(61) should be used when C=000 because the instruction needs to be executed only one time to start table comparison. If C is 002, INI(61) changes the PV of the specified high-speed counter or interrupt input (counter mode). High-speed Counter PV (P=000) INI(61) changes the PV of the specified high-speed counter to the 8-digit BCD value in P1 and P1+1. The new PV can be F838 8608 to 0838 8607 in differential phase mode, pulse + direction input mode, or up/down input mode. (The hexadecimal F in the first digit acts as a minus sign.) The new PV can be 0000 0000 to 1677 7215 in increment mode. Interrupt Input PV (P=100 to 103) INI(61) changes the PV of the specified interrupt input (counter mode) to the 4-digit hexadecimal value (0000 to FFFF) in P1. If C is 003, INI(61) stops the pulse output. INI(61) changes the PV of the pulse output to the 8-digit BCD value in P1 and P1+1. The PV cannot be changed while the pulse output is in progress. The new PV can be 16,777,215 to 16,777,215. Bit 15 of P1+1 acts as a sign bit; the number is negative if bit 15 is ON, positive if it is OFF. If C is 003, INI(61) stops the synchronized pulse control output.
Change PV (C=002)
400
Section 7-15
The port specifier and control data are incompatible. (For example: P=010 and C=000) There is an error in the operand settings or the specified PV is not within the acceptable range. The address specified for P1 or P1+1 exceeds the data area boundary. Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) The specified function is incompatible with actual PC operation. For example, do not set C=005 if synchronized pulse control is not being used. INI(61) is executed to change the PV of a pulse output (C=004) while the pulse output is operating. INI(61) is executed in an interrupt subroutine while a pulse I/O or highspeed counter instruction (INI(61), PRV(62), CTBL(63), SPED(64), PULS(65), ACC(), PWM(), or SYNC()) is being executed in the main program. INI(61) is executed in an interrupt subroutine while a pulse I/O or highspeed counter instruction is being executed in the main program.
Ladder Symbols
PRV(62) P C D @PRV(62)
This instruction is not supported by SRM1(-V2) PCs. Limitations In the CPM1/CPM1A PCs, P must be 000 and C must be 000 to 002. In CPM2A/CPM2C PCs, P must be 000, 010, 100, 101, 102, or 103 and C must be 000 to 003. D and D+1 must be in the same data area. If a DM address is used for D, it must be read/write DM. Description When the execution condition is OFF, PRV(62) is not executed. When the execution condition is ON, PRV(62) controls the high-speed counter PV, pulse output PV, interrupt input (counter mode) PV, or input frequency for synchronized control as specified by P and C.
401
Section 7-15
The port specifier (P) specifies the high-speed counter or pulse output that will be controlled.
P 000 Function Specifies high-speed counter input (inputs 00000, 00001, and 00002), input frequency for synchronized pulse control (inputs 00000, 00001, and 00002), single-phase pulse output 0 with no acceleration/deceleration (outputs 01000 and 01001), single-phase pulse output 0 with trapezoidal acceleration/deceleration (output 01000), or synchronized pulse control output 0 (output 01000/01001). Specifies single-phase pulse output 1 with no acceleration/deceleration (output 01001) or synchronized pulse control output 1 (output 01001). Specifies interrupt input 0 in counter mode (input 00003). Specifies interrupt input 1 in counter mode (input 00004). Specifies interrupt input 2 in counter mode (input 00005). Specifies interrupt input 3 in counter mode (input 00006).
Note *These settings can be used in CPM2A/CPM2C PCs only. The control data, C, determines which type of data will be accessed.
C 000 Function Reads the PV of the high-speed counter or interrupt input (counter mode) or the input frequency of the synchronized pulse control. Reads the status of the high-speed counter or pulse output. Reads the results of range comparison. Reads the PV of the pulse output. Destination word(s) D and D+1
D D D and D+1
Read PV (C=000)
If C is 000, PRV(62) reads the PV of the specified high-speed counter or interrupt input (counter mode). High-speed Counter PV or Input Frequency (P=000) When the output is used for a high-speed counter, PRV(62) reads the PV of the specified high-speed counter and writes the 8-digit BCD value in D and D+1. (The leftmost 4 digits are written to D+1.) The PV can be F838 8608 to 0838 8607 in differential phase mode, pulse + direction input mode, or up/down input mode. (The hexadecimal F in the first digit acts as a minus sign.) The PV can be 0000 0000 to 1677 7215 in increment mode. When the output is used for synchronized pulse control, PRV(62) reads the input frequency and writes the 8-digit BCD value in D and D+1. The input frequency can be 0000 0000 to 0002 0000. Interrupt Input PV (P=100 to 103) PRV(62) reads the PV of the specified interrupt input (counter mode) and writes the 4-digit hexadecimal value (0000 to FFFF) in D.
If C is 001, PRV(62) reads the operating status of the specified high-speed counter or pulse output and writes the data to D.
402
Section 7-15
High-speed Counter or Pulse Output 0 Status (P=000) The following table shows the function of the bits in D when P=000. Bits not listed in the table are not used and will always be 0.
Usage High-speed counter cou e Bit 00 01 Pulse output 05 06 07 08 09 Function High-speed counter comparison status. (0: Stopped; 1: Comparing) High-speed counter underflow/overflow. (0: Normal; 1: Underflow/Overflow occurred.) Total number of pulses specified for pulse output 0. (0: Not specified; 1: Specified.) Pulse output 0 completed. (0: Not completed; 1: Completed) Pulse output 0 status (0: Stopped; 1: Outputting) Pulse output 0 PV underflow/overflow. (0: Normal; 1: Underflow/Overflow occurred.) Pulse output 0 acceleration 0: Constant; 1: Accelerating or decelerating
Pulse Output 1 Status (P=010) The following table shows the function of the bits in D when P=010. Bits not listed in the table are not used and will always be 0.
Bit 05 06 07 08 09 Function Total number of pulses specified for pulse output 1. (0: Not specified; 1: Specified.) Pulse output 1 completed. (0: Not completed; 1: Completed) Pulse output 1 status (0: Stopped; 1: Outputting) Pulse output 1 PV underflow/overflow. (0: Normal; 1: Underflow/Overflow occurred.) Pulse output 1 acceleration (0: Constant; 1: Accelerating or decelerating)
If C is 002, PRV(62) reads the results of the comparison of the PV to the 8 ranges defined by CTBL(63) and writes this data to D. Bits 00 through 07 of D contain the Comparison Result Flags for ranges 1 to 8. (0: Not in range; 1: In range) If C is 003, PRV(62) reads the pulse output PV and writes the 8-digit BCD value in D and D+1. (The leftmost 4 digits are written to D+1.) The PV can be 16,777,215 to 16,777,215. Bit 15 of D+1 acts as a sign bit; the number is negative if bit 15 is ON, positive if it is OFF.
Flags
ER:
The port specifier and control data are incompatible. (For example: P=010 and C=000) The address specified for D or D+1 exceeds the data area boundary. There is an error in the operand settings. Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) PRV(62) is executed in an interrupt subroutine while a pulse I/O or highspeed counter instruction (INI(61), PRV(62), CTBL(63), SPED(64), PULS(65), ACC(), PWM(), or SYNC()) is being executed in the main program.
403
Shift Instructions
Section 7-16
Limitations
E must be greater than or equal to St, and St and E must be in the same data area. If a bit address in one of the words used in a shift register is also used in an instruction that controls individual bit status (e.g., OUT, KEEP(11)), an error (COIL/OUT DUPL) will be generated when program syntax is checked on the Programming Console or another Programming Device. The program, however, will be executed as written. See Example 2: Controlling Bits in Shift Registers for a programming example that does this.
Description
SFT(10) is controlled by three execution conditions, I, P, and R. If SFT(10) is executed and 1) execution condition P is ON and was OFF the last execution, and 2) R is OFF, then execution condition I is shifted into the rightmost bit of a shift register defined between St and E, i.e., if I is ON, a 1 is shifted into the register; if I is OFF, a 0 is shifted in. When I is shifted into the register, all bits previously in the register are shifted to the left and the leftmost bit of the register is lost.
St
Lost data
Execution condition I
The execution condition on P functions like a differentiated instruction, i.e., I will be shifted into the register only when P is ON and was OFF the last time SFT(10) was executed. If execution condition P has not changed or has gone from ON to OFF, the shift register will remain unaffected. St designates the rightmost word of the shift register; E designates the leftmost. The shift register includes both of these words and all words between them. The same word may be designated for St and E to create a 16-bit (i.e., 1-word) shift register. When execution condition R goes ON, all bits in the shift register will be turned OFF (i.e., set to 0) and the shift register will not operate until R goes OFF again.
Flags
ER:
404
Shift Instructions
Example
Section 7-16
The following example uses the 1-second clock pulse bit (25502) so that the execution condition produced by 00000 is shifted into HR 00 every second. Output 20000 is turned ON whenever a 1 is shifted into HR 0007.
I SFT(10) P HR 00 R HR 00
HR HR HR
0007 20000
Limitations
St and E must be in the same data area, and E must be greater than or equal to St. DM 6144 to DM 6655 cannot be used for St or E. When the execution condition is OFF, WSFT(16) is not executed. When the execution condition is ON, WSFT(16) shifts data between St and E in word units. Zeros are written into St and the content of E is lost.
E F Lost 0000 E 3 4 5 2 1 St + 1 0 2 9 0 0 St 0 0 0 C 2 3 St + 1 4 5 2 1 0 St 2 9
Description
Flags
ER:
The St and E words are in different areas, or St is greater than E. Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.)
Limitations
405
Shift Instructions
Description
Section 7-16
When the execution condition is OFF, ASL(25) is not executed. When the execution condition is ON, ASL(25) shifts a 0 into bit 00 of Wd, shifts the bits of Wd one bit to the left, and shifts the status of bit 15 into CY.
CY Bit Bit 15 00 1 0 0 1 1 1 0 0 0 1 0 1 0 0 1 1 0
Precautions
A 0 will be shifted into bit 00 every cycle if the undifferentiated form of ASL(25) is used. Use the differentiated form (@ASL(25)) or combine ASL(25) with DIFU(13) or DIFD(14) to shift just one time. ER: CY: EQ: Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) Receives the status of bit 15. ON when the content of Wd is zero; otherwise OFF.
Flags
Limitations Description
DM 6144 to DM 6655 cannot be used for Wd. When the execution condition is OFF, ASR(25) is not executed. When the execution condition is ON, ASR(25) shifts a 0 into bit 15 of Wd, shifts the bits of Wd one bit to the right, and shifts the status of bit 00 into CY.
Bit Bit 15 00 1 1 0 0 1 0 1 1 0 0 1 1 0 0 1 0 0 CY
Precautions
A 0 will be shifted into bit 15 every cycle if the undifferentiated form of ASR(26) is used. Use the differentiated form (@ASR(26)) or combine ASR(26) with DIFU(13) or DIFD(14) to shift just one time. ER: CY: EQ: Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) Receives the data of bit 00. ON when the content of Wd is zero; otherwise OFF.
Flags
Limitations
406
Shift Instructions
Description
Section 7-16
When the execution condition is OFF, ROL(27) is not executed. When the execution condition is ON, ROL(27) shifts all Wd bits one bit to the left, shifting CY into bit 00 of Wd and shifting bit 15 of Wd into CY.
Bit 15 Bit 00
CY 0
1 0 1 1 0 0 1 1 1 0 0 0 1 1 0 1
Precautions
Use STC(41) to set the status of CY or CLC(41) to clear the status of CY before doing a rotate operation to ensure that CY contains the proper status before executing ROL(27). CY will be shifted into bit 00 every cycle if the undifferentiated form of ROL(27) is used. Use the differentiated form (@ROL(27)) or combine ROL(27) with DIFU(13) or DIFD(14) to shift just one time.
Flags
Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) Receives the data of bit 15. ON when the content of Wd is zero; otherwise OFF.
Limitations Description
DM 6144 to DM 6655 cannot be used for Wd. When the execution condition is OFF, ROR(28) is not executed. When the execution condition is ON, ROR(28) shifts all Wd bits one bit to the right, shifting CY into bit 15 of Wd and shifting bit 00 of Wd into CY.
CY 0 Bit 15 Bit 00
0 1 0 1 0 1 0 0 0 1 1 1 0 0 0 1
Precautions
Use STC(41) to set the status of CY or CLC(41) to clear the status of CY before doing a rotate operation to ensure that CY contains the proper status before execution ROR(28). CY will be shifted into bit 15 every cycle if the undifferentiated form of ROR(28) is used. Use the differentiated form (@ROR(28)) or combine ROR(28) with DIFU(13) or DIFD(14) to shift just one time.
Flags
Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) Receives the data of bit 00. ON when the content of Wd is zero; otherwise OFF.
407
Shift Instructions
Section 7-16
Limitations
St and E must be in the same data area, and E must be greater than or equal to St. DM 6144 to DM 6655 cannot be used for St or E. When the execution condition is OFF, SLD(74) is not executed. When the execution condition is ON, SLD(74) shifts data between St and E (inclusive) by one digit (four bits) to the left. 0 is written into the rightmost digit of the St, and the content of the leftmost digit of E is lost.
E 8 F C 5
Description
...
St D 7 9 1
Lost data
Precautions
If a power failure occurs during a shift operation across more than 50 words, the shift operation might not be completed. A 0 will be shifted into the least significant digit of St every cycle if the undifferentiated form of SLD(74) is used. Use the differentiated form (@SLD(74)) or combine SLD(74) with DIFU(13) or DIFD(14) to shift just one time. ER: The St and E words are in different areas, or St is greater than E. Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.)
Flags
Limitations Description
St and E must be in the same data area, and E must be less than or equal to St. DM 6144 to DM 6655 cannot be used for St or E. When the execution condition is OFF, SRD(75) is not executed. When the execution condition is ON, SRD(75) shifts data between St and E (inclusive) by one digit (four bits) to the right. 0 is written into the leftmost digit of St and the rightmost digit of E is lost.
St 3 4 5 2
...
E F 8 C 1
Lost data
408
Shift Instructions
Precautions
Section 7-16
If a power failure occurs during a shift operation across more than 50 words, the shift operation might not be completed. A 0 will be shifted into the most significant digit of St every cycle if the undifferentiated form of SRD(75) is used. Use the differentiated form (@SRD(75)) or combine SRD(75) with DIFU(13) or DIFD(14) to shift just one time.
Flags
ER:
The St and E words are in different areas, or St is less than E. Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.)
Limitations
St and E must be in the same data area and St must be less than or equal to E. DM 6144 to DM 6655 cannot be used for C, St, or E. SFTR(84) is used to create a single- or multiple-word shift register that can shift data to either the right or the left. To create a single-word register, designate the same word for St and E. The control word provides the shift direction, the status to be put into the register, the shift pulse, and the reset input. The control word is allocated as follows:
15 14 13 12 Not used. Shift direction 1 (ON): Left (LSB to MSB) 0 (OFF): Right (MSB to LSB) Status to input into register Shift pulse bit Reset
Description
The data in the shift register will be shifted one bit in the direction indicated by bit 12, shifting one bit out to CY and the status of bit 13 into the other end whenever SFTR(84) is executed with an ON execution condition as long as the reset bit is OFF and as long as bit 14 is ON. If SFTR(84) is executed with an OFF execution condition or if SFTR(84) is executed with bit 14 OFF, the shift register will remain unchanged. If SFTR(84) is executed with an ON execution condition and the reset bit (bit 15) is OFF, the entire shift register and CY will be set to zero. Flags ER: St and E are not in the same data area or ST is greater than E. Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.)
409
Shift Instructions
CY: Example
Section 7-16
Receives the status of bit 00 of St or bit 15 of E, depending on the shift direction.
In the following example, IR 00000, IR 00001, IR 00002, and IR 00003 are used to control the bits of C used in @SFTR(84). The shift register is in DM 0010, and it is controlled through IR 00004.
00000 20012 Direction
Address 00000 00001 00002 00003 00004 00005 00006 00007 00008 00009
Operands 00000 20012 00001 20013 00002 20014 00003 20015 00004 200 0010 0011
DM DM
Note ASFT(17) is an expansion instruction for the SRM1(-V2). The function code 17 is the factory setting and can be changed for the SRM1(-V2) if desired. Limitations St and E must be in the same data area, and E must be greater than or equal to St. DM 6144 to DM 6655 cannot be used for St or E. When the execution condition is OFF, ASFT(17) does nothing and the program moves to the next instruction. When the execution condition is ON, ASFT(17) is used to create and control a reversible asynchronous word shift register between St and E. This register only shifts words when the next word in the register is zero, e.g., if no words in the register contain zero, nothing is shifted. Also, only one word is shifted for each word in the register that contains zero. When the contents of a word are shifted to the next word, the original words contents are set to zero. In essence, when the register is shifted, each zero word in the register trades places with the next word. (See Example below.) The shift direction (i.e. whether the next word is the next higher or the next lower word) is designated in C. C is also used to reset the register. All of any portion of the register can be reset by designating the desired portion with St and E.
Description
410
Section 7-17
Bits 00 through 12 of C are not used. Bit 13 is the shift direction: turn bit 13 ON to shift down (toward lower addressed words) and OFF to shift up (toward higher addressed words). Bit 14 is the Shift Enable Bit: turn bit 14 ON to enable shift register operation according to bit 13 and OFF to disable the register. Bit 15 is the Reset bit: the register will be reset (set to zero) between St and E when ASFT(17) is executed with bit 15 ON. Turn bit 15 OFF for normal operation.
Note If the non-differentiated form of ASFT(17) is used, data will be shifted every cycle while the execution condition is ON. Use the differentiated form to prevent this. Flags ER: The St and E words are in different areas, or St is greater than E. Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) Example The following example shows instruction ASFT(17) used to shift words in an 11-word shift register created between DM 0100 and DM 0110 with C=#6000. Non-zero data is shifted towards St (DM 0110).
ASFT(17) #6000 DM 0100 DM 0110
00000
Instruction LD ASFT(17)
Before execution DM 0100 DM 0101 DM 0102 DM 0103 DM 0104 DM 0105 DM 0106 DM 0107 DM 0108 DM 0109 DM 0110 1234 0000 0000 2345 3456 0000 4567 5678 6789 0000 789A
After one execution 1234 0000 2345 0000 3456 4567 0000 5678 6789 789A 0000
After seven executions 1234 2345 3456 4567 5678 6789 789A 0000 0000 0000 0000
Note The zeroes are shifted upward if C=4000, and the entire shift register is set to zero if C=8000.
411
Section 7-17
When the execution condition is OFF, MOV(21) is not executed. When the execution condition is ON, MOV(21) copies the content of S to D.
Source word Bit status not changed. Destination word
Precautions
TC numbers cannot be designated as D to change the PV of the timer or counter. You can, however, easily change the PV of a timer or a counter by using BSET(71). ER: EQ: Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) ON when all zeros are transferred to D.
Flags
Example
00000
The following example shows @MOV(21) being used to copy the content of IR 001 to HR 05 when IR 00000 goes from OFF to ON.
@MOV(21) 001 HR 05
Instruction LD @MOV(21)
HR
IR 000
0 1 1 1 0 0 1 1 1 0 0 0 0 1 0 1
HR 05
0 1 1 1 0 0 1 1 1 0 0 0 0 1 0 1
Limitations Description
DM 6144 to DM 6655 cannot be used for D. When the execution condition is OFF, MVN(22) is not executed. When the execution condition is ON, MVN(22) transfers the inverted content of S (specified word or four-digit hexadecimal constant) to D, i.e., for each ON bit in S, the corresponding bit in D is turned OFF, and for each OFF bit in S, the corresponding bit in D is turned ON.
Source word Bit status inverted. Destination word
Precautions
TC numbers cannot be designated as D to change the PV of the timer or counter. However, these can be easily changed using BSET(71).
412
Section 7-17
Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) ON when all zeros are transferred to D.
The following example shows @MVN(22) being used to copy the complement of #F8C5 to DM 0010 when IR 00001 goes from OFF to ON.
Address 00000 00001 Instruction LD @MOV(21) # DM Operands 00001 F8C5 0010
#F8C5
1 1 1 1 1 0 0 0 1 1 0 0 0 1 0 1
DM 0010
0 0 0 0 0 1 1 1 0 0 1 1 1 0 1 0
Limitations Description
S and S+N must be in the same data area, as must D and D+N. DM 6144 to DM 6655 cannot be used for D. When the execution condition is OFF, XFER(70) is not executed. When the execution condition is ON, XFER(70) copies the contents of S, S+1, ..., S+N to D, D+1, ..., D+N.
S 3 4 5 2 S+1 3 4 5 1 S+2 3 4 2 2 D 3 4 5 2 D+1 3 4 5 1 D+2 3 4 2 2
S+N 6 4 5 2
D+N 6 4 5 2
Flags
ER:
N is not BCD S and S+N or D and D+N are not in the same data area.
413
Section 7-17
Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.)
Limitations
St must be less than or equal to E, and St and E must be in the same data area. DM 6144 to DM 6655 cannot be used for St or E.
Description
When the execution condition is OFF, BSET(71) is not executed. When the execution condition is ON, BSET(71) copies the content of S to all words from St through E.
S 3 4 5 2 St 3 4 5 2 St+1 3 4 5 2 St+2 3 4 5 2
E 3 4 5 2
BSET(71) can be used to change timer/counter PV. (This cannot be done with MOV(21) or MVN(22).) BSET(71) can also be used to clear sections of a data area, i.e., the DM area, to prepare for executing other instructions. It can also be used to clear words by transferring all zeros. Flags ER: St and E are not in the same data area or St is greater than E. Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) Example The following example shows how to use BSET(71) to copy a constant (#0000) to a block of the DM area (DM 0000 to DM 0500) when IR 00000 is ON.
Address
@BSET(71) #0000 DM 0000 DM 0500
00000
Instruction LD @BSET(71)
00000 00001
414
Section 7-17
Limitations Description
DM 6144 to DM 6655 cannot be used for E1 or E2. When the execution condition is OFF, XCHG(73) is not executed. When the execution condition is ON, XCHG(73) exchanges the content of E1 and E2.
E1 E2
If you want to exchange content of blocks whose size is greater than 1 word, use work words as an intermediate buffer to hold one of the blocks using XFER(70) three times. Flags ER: Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.)
C must be BCD. DM 6144 to DM 6655 cannot be used for DBs or C. DIST(80) can be used for single-word distribution or for a stack operation depending on the content of the control word, C. When bits 12 to 15 of C=0 to 8, DIST(80) can be used for a single word distribute operation. The entire contents of C specifies an offset, Of (0000 to 2047 in BCD). When the execution condition is OFF, DIST(80) is not executed. When the execution condition is ON, DIST(80) copies the content of S to DBs+Of, i.e., Of is added to DBs to determine the destination word. 1. DBs and DBs+Of must be in the same data area and cannot be between DM 6144 and DM 6655. 2. IR 000 to IR 019 or IR 000 to IR 049 is treated as a different memory area from IR 200 to IR 255 for the source data area. The entire source data area must be within one or the other of these areas. An error will occur if words from both areas are included.
Note
415
Section 7-17
Example The following example shows how to use DIST(80) to copy #00FF to HR 10 + Of. The content of LR 10 is #3005, so #00FF is copied to HR 15 (HR 10 + 5) when IR 00000 is ON.
Instruction LD @DIST(80)
LR 10 3 0 0 5
#00FF 0 0 F F
HR 10 0 0 0 0
HR 15 0 0 F F
Stack Operation
When bits 12 to 15 of C=9, DIST(80) can be used for a stack operation. The other 3 digits of C specify the number of words in the stack (000 to 999 in BCD). The content of DBs is the stack pointer. When the execution condition is OFF, DIST(80) is not executed. When the execution condition is ON, DIST(80) copies the content of S to DBs+1+the content of DBs. In other words, 1 and the content of DBs are added to DBs to determine the destination word. The content of DBs is then incremented by 1. Note 1. DIST(80) will be executed every cycle unless the differentiated form (@DIST(80)) is used or DIST(80) is used with DIFU(13) or DIFD(14). 2. Be sure to initialize the stack pointer before using DIST(80) as a stack operation. Example The following example shows how to use DIST(80) to create a stack between DM 0001 and DM 0005. DM 0000 acts as the stack pointer.
Instruction LD @DIST(80)
DM
FFFF 9005 0000 0000 0000 0000 0000 0000 First execution DM 0000 DM 0001 DM 0002 DM 0003 DM 0004 DM 0005 0001 FFFF 0000 0000 0000 0000 Second execution Stack pointer incremented DM 0000 DM 0001 DM 0002 DM 0003 DM 0004 DM 0005 0002 FFFF FFFF 0000 0000 0000
Flags
ER:
The offset or stack length in the control word is not BCD. Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.)
416
Section 7-17
During stack operation, the value of the stack pointer+1 exceeds the length of the stack. EQ: ON when the content of S is zero; otherwise OFF.
C must be BCD. DM 6144 to DM 6655 cannot be used for D. COLL(81) can be used for data collection, an FIFO stack operation, or an LIFO stack operation depending on the content of the control word, C. When bits 12 to 15 of C=0 to 7, COLL(81) is used for data collection. The entire contents of C specifies an offset, Of (0000 to 2047 in BCD). When the execution condition is OFF, COLL(81) is not executed. When the execution condition is ON, COLL(81) copies the content of SBs + Of to D, i.e., Of is added to SBs to determine the source word. Note 1. SBs and SBs+Of must be in the same data area. 2. IR 000 to IR 019 or IR 000 to IR 049 is treated as a different memory area from IR 200 to IR 255 for the source data area. The entire source data area must be within one or the other of these areas. An error will occur if words from both areas are included. Example The following example shows how to use COLL(81) to copy the content of DM 0000+Of to LR 00. The content of 200 is #0005, so the content of DM 0005 (DM 0000 + 5) is copied to LR 00 when IR 00001 is ON.
Instruction LD @DIST(80)
200 0 0 0 5
DM 0000 0 0 0 0
LR 00 0 0 F F
DM 0005 0 0 F F
When bits 12 to 15 of C=9, COLL(81) can be used for an FIFO stack operation. The other 3 digits of C specify the number of words in the stack (000 to 999, in BCD). The content of SBs is the stack pointer.
417
Section 7-17
When the execution condition is ON, COLL(81) shifts the contents of each word within the stack down by one address, finally shifting the data from SBs+1 (the first value written to the stack) to the destination word (D). The content of the stack pointer (SBs) is then decremented by one.
Note COLL(81) will be executed every cycle unless the differentiated form (@COLL(81)) is used or COLL(81) is used with DIFU(13) or DIFD(14). Example The following example shows how to use COLL(81) to create a stack between DM 0001 and DM 0005. DM 0000 acts as the stack pointer. When IR 00000 goes from OFF to ON, COLL(81) shifts the contents of DM 0002 to DM 0005 down by one address, and shifts the data from DM 0001 to IR 001. The content of the stack pointer (DM 0000) is then decremented by one.
00000 @COLL(81) DM 0000 216 001
Instruction LD @COLL(81)
9005 0005 AAAA BBBB CCCC DDDD EEEE Stack pointer decremented DM 0000 DM 0001 DM 0002 DM 0003 DM 0004 DM 0005 0004 BBBB CCCC DDDD EEEE EEEE IR 001 AAAA
When bits 12 to 15 of C=8, COLL(81) can be used for an LIFO stack operation. The other 3 digits of C specify the number of words in the stack (000 to 999). The content of SBs is the stack pointer. When the execution condition is ON, COLL(81) copies the data from the word indicated by the stack pointer (SBs+the content of SBs) to the destination word (D). The content of the stack pointer (SBs) is then decremented by one. The stack pointer is the only word changed in the stack. Note COLL(81) will be executed every cycle unless the differentiated form (@DIST(80)) is used or DIST(80) is used with DIFU(13) or DIFD(14). Example The following example shows how to use COLL(81) to create a stack between DM 0001 and DM 0005. DM 0000 acts as the stack pointer.
418
Section 7-17
When IR 00000 goes from OFF to ON, COLL(81) copies the content of DM 0005 (DM 0000 + 5) to IR 001. The content of the stack pointer (DM 0000) is then decremented by one.
Instruction LD @COLL(81)
8005 0005 AAAA BBBB CCCC DDDD EEEE Stack pointer decremented DM 0000 DM 0001 DM 0002 DM 0003 DM 0004 DM 0005 0004 AAAA BBBB CCCC DDDD EEEE IR 001 EEEE
Flags
ER:
The offset or stack length in the control word is not BCD. Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) During stack operation, the value of the stack pointer exceeds the length of the stack; an attempt was made to write to a word beyond the end of the stack.
EQ:
Limitations
The rightmost two digits and the leftmost two digits of Bi must each be between 00 and 15. DM 6144 to DM 6655 cannot be used for Bi or D.
419
Section 7-17
When the execution condition is OFF, MOVB(82) is not executed. When the execution condition is ON, MOVB(82) copies the specified bit of S to the specified bit in D. The bits in S and D are specified by Bi. The rightmost two digits of Bi designate the source bit; the leftmost two bits designate the destination bit.
Bit 15 Bit 00
Bi MSB 1 2 0 1 LSB
Bi
0 0 0 1 0 0 1 0 0 0 0 0 0 0 0 1 Bit 15 1 2 0 1 Bit 00
S
Source bit (00 to 15) Destination bit (00 to 15)
0 1 0 1 0 1 0 0 0 1 1 1 0 0 0 1 Bit 15 Bit 00
D Flags ER:
0 1 0 0 0 1 0 0 0 1 1 1 0 0 0 1
Bi is not BCD, or it is specifying a non-existent bit (i.e., bit specification must be between 00 and 15). Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.)
Limitations Description
The rightmost three digits of Di must each be between 0 and 3. DM 6144 to DM 6655 cannot be used for Di or D. When the execution condition is OFF, MOVD(83) is not executed. When the execution condition is ON, MOVD(83) copies the content of the specified digit(s) in S to the specified digit(s) in D. Up to four digits can be transferred at one time. The first digit to be copied, the number of digits to be copied, and the first digit to receive the copy are designated in Di as shown below. Digits from S will be copied to consecutive digits in D starting from the designated first digit and continued for the designated number of digits. If the last digit is reached in either S or D, further digits are used starting back at digit 0.
Digit number: 3 2 1 0
First digit in S (0 to 3) Number of digits (0 to 3) 0: 1 digit 1: 2 digits 2: 3 digits 3: 4 digits First digit in D (0 to 3) Not used. (Set to 0.)
420
Section 7-18
The following show examples of the data movements for various values of Di.
Di: 0010 S 0 1 2 3 Di: 0031 S 0 1 2 3 D 0 1 2 3 S 0 1 2 3 D 0 1 2 3 S 0 1 2 3 Di: 0023 D 0 1 2 3 Di: 0030 D 0 1 2 3
Flags
ER:
At least one of the rightmost three digits of Di is not between 0 and 3. Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.)
Limitations
This instruction is available in the CPM2A/CPM2C/SRM1(-V2) only. S must be BCD. P1 through P1+3 must be in the same data area. DM 6144 to DM 6655 cannot be used for P1 through P1+3 or R.
Description
SCL(66) is used to linearly convert a 4-digit hexadecimal value to a 4-digit BCD value. Unlike BCD(24), which converts a 4-digit hexadecimal value to its 4-digit BCD equivalent (Shex SBCD), SCL(66) can convert the hexadecimal value according to a specified linear relationship. The conversion line is defined by two points specified in the parameter words P1 to P1+3. When the execution condition is OFF, SCL(66) is not executed. When the execution condition is ON, SCL(66) converts the 4-digit hexadecimal value in S to the 4-digit BCD value on the line defined by points (P1, P1+1) and (P1+2, P1+3) and places the results in R. The results is rounded off to the nearest integer. If the results is less than 0000, then 0000 is written to R, and if the result is greater than 9999, then 9999 is written to R.
421
Section 7-18
The following table shows the functions and ranges of the parameter words:
Parameter P1 P1+1 P1+2 P1+3 Function BCD point #1 (AY) Hex. point #1 (AX) BCD point #2 (BY) Hex. point #2 (BX) Range 0000 to 9999 0000 to FFFF 0000 to 9999 0000 to FFFF --Do not set P1+1=P1+3. --Do not set P1+3=P1+1. Comments
The following diagram shows the source word, S, converted to D according to the line defined by points (AY, AX) and (BY, BX).
Value after (BCD) BY conversion
R AY
AX
BX
The results can be calculated by first converting all values to BCD and then using the following formula. Results = BY [(BY AY)/(BX AX) (BX S)] Flags ER: The value in P1+1 equals that in P1+3. Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) P1 and P1+3 are not in the same data area, or other setting error. EQ: Example ON when the result, R, is 0000.
When 00000 is turned ON in the following example, the BCD source data in DM 0100 (#0100) is converted to hexadecimal according to the parameters in DM 0150 to DM 0153. The result (#0512) is then written to DM 0200.
00000 @SCL(66) DM 0100 DM 0150 DM 0200
Instruction LD @SCL(66)
DM 0100
0100
DM 0200
0512
422
Section 7-18
Limitations
This instruction is available in the CPM2A/CPM2C only. S must be BCD. P1 through P1+2 must be in the same data area. DM 6144 to DM 6655 cannot be used for R. SCL2() is used to linearly convert a 4-digit signed hexadecimal value to a 4-digit BCD value. Unlike BCD(24), which converts a 4-digit hexadecimal value to its 4-digit BCD equivalent (Shex SBCD), SCL2() can convert the signed hexadecimal value according to a specified linear relationship. The conversion line is defined by the x-intercept and the slope of the line specified in the parameter words P1 to P1+2. When the execution condition is OFF, SCL2() is not executed. When the execution condition is ON, SCL2() converts the 4-digit signed hexadecimal value in S to the 4-digit BCD value on the line defined by the x-intercept (P1, 0) and the slope (P1+2 P1+1) and places the results in R. The result is rounded off to the nearest integer. If the result is negative, then CY is set to 1. If the result is less than 9999, then 9999 is written to R. If the result is greater than 9999, then 9999 is written to R. The following table shows the functions and ranges of the parameter words:
Parameter P1 P1+1 P1+2 Function x-intercept (signed hex.) X (signed hex.) Y (BCD) Range 8000 to 7FFF (32,768 to 32,767) 8000 to 7FFF (32,768 to 32,767) 0000 to 9999
Description
The following diagram shows the source word, S, converted to R according to the line defined by the point (P1, 0) and slope Y/X.
Value after conversion (BCD) Y R X
S X-intercept
423
Section 7-18
The result can be calculated by first converting all signed hexadecimal values to BCD and then using the following formula. R + DY DX (SP1)
Flags
ER:
Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) P1 and P1+2 are not in the same data area, or other setting error. ON when the result, R, is negative. ON when the result, R, is 0000.
When 05000 is turned ON in the following example, the signed binary source data in 200 (#FFE2) is converted to BCD according to the parameters in DM 0000 to DM 0002. The result (#0018) is then written to LR 00 and CY is turned ON because the result is negative.
05000 @SCL2() 200 DM 0000 LR 00
Instruction LD @SCL2()
DM LR
IR 200
FFE2
LR 00 0018
0018
CY=1
R + 0002 0003 +2 3
(FFE2FFFD) (1B) + 18
Limitations
This instruction is available in the CPM2A/CPM2C only. P1+1 must be BCD. P1 through P1+4 must be in the same data area. DM 6144 to DM 6655 cannot be used for R.
424
Section 7-18
SCL3() is used to linearly convert a 4-digit 4-digit BCD value to 4-digit signed hexadecimal. SCL3() converts the BCD value according to a specified linear relationship. The conversion line is defined by the y-intercept and the slope of the line specified in the parameter words P1 to P1+2. When the execution condition is OFF, SCL3() is not executed. When the execution condition is ON, SCL3() converts the 4-digit BCD value in S to the 4-digit signed hexadecimal value on the line defined by the y-intercept (0, P1) and the slope (P1+2 P1+1) and places the result in R. The result is rounded off to the nearest integer. The content of S can be 0000 to 9999, but S will be treated as a negative value if CY=1, so the effective range of S is actually 9999 to 9999. Be sure to set the desired sign in CY using STC(40) or CLC(41). Parameter words P1+3 and P1+4 define upper and lower limits for the result. If the result is greater than the upper limit in P1+3, then the upper limit is written to R. If the result is less than the lower limit in P1+4, then the lower limit is written to R.
Note The upper and lower limits for a 12-bit Analog Input Unit would be 07FF and F800. The following table shows the functions and ranges of the parameter words:
Parameter P1 P1+1 P1+2 P1+3 P1+4 Function x-intercept (signed hex.) X (BCD) Y (signed hex.) Upper limit (signed hex.) Lower limit (signed hex.) 0001 to 9999 8000 to 7FFF (32,768 to 32,767) 8000 to 7FFF (32,768 to 32,767) 8000 to 7FFF (32,768 to 32,767) Range 8000 to 7FFF (32,768 to 32,767)
The following diagram shows the source word, S, converted to R according to the line defined by the point (0, P1) and slope Y/X.
Value after conversion (Signed hexadecimal) Upper limit R X Y
Lower limit
The result can be calculated by first converting all BCD values to signed binary and then using the following formula. R+ Flags ER: DY DX S ) P1
Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) The content of S is not BCD. CY is not changed by SCL3(). (CY shows the sign of S before execution.) ON when the result, R, is 0000.
CY: EQ:
425
Section 7-18
The status of 00101 determines the sign of the BCD source word in the following example. If 00101 is ON, then the source word is negative. When 00100 is turned ON, the BCD source data in LR 02 is converted to signed binary according to the parameters in DM 0000 to DM 0004. The result is then written to DM 0100. (In the second conversion, the signed binary equivalent of 1035 is less than the lower limit specified in DM 0004, so the lower limit is written to DM 0100.)
25313 (Always ON) CLC(41) 00101 STC(40) 00100 @SCL3() LR 02 DM 0000 DM 0100
Signed hex. CY=0 6 3 0005 BCD DM 0000 DM 0001 DM 0002 DM 0003 DM 0004 0005 0003 0006 07FF F800 LR 02 0100 LR 02 CY=1 1035
DM 0100
00CD
DM 0100
F800
Limitations
This instruction is available in the CPM2A/CPM2C and SRM1(-V2) only. DM 6144 to DM 6655 cannot be used for P1 or OW. P1 to P1+32 must be in the same data area. ! Caution A total of 33 continuous words starting with P1 must be provided for PID() to operate correctly. Also, PID() may not operate dependably in any of the following situations: In interrupt programs, in subroutines, between IL(02) and ILC(03), between JMP(04) and JME(05), and in step programming (STEP(08)/SNXT(09)). Do not program PID() in these situations.
426
Section 7-18
PID() performs PID control based on the parameters specified in P1 through P1+6. When the execution condition OFF, PID() is not executed. When the execution condition is ON, PID() carries out PID control according to the designated parameters. It takes the specified input range of binary data from the contents of IW and carries out the PID action according to the parameters that are set. The result is then stored as the manipulated variable in OW. The following table shows the function of the parameter words.
Bits 00 to 15 00 to 15 00 to 15
Parameter name Set value (SV). Proportional band width. Integral time (Tik)/ sampling period ()
Function/Setting range This is the target value for PID control. It can be set to any binary number with the number of bits set by the input range parameter. This parameter specifies the proportional band width/input range ratio from 0.1% to 999.9%. It must be BCD from 0001 to 9999. Sets the strength of integral action. Increasing this value strengthens the integral action. It must be BCD from 0001 to 8191, or 9999. A setting of 9999 disables integral control. Set the integral time divided by the sampling time. Sets the strength of derivative action. Increasing this value strengthens the derivative action. It must be BCD from 0001 to 8191, or 0000. (A setting of 0000 disables derivative control.) Set the derivative time divided by the sampling time. Sets the interval between samplings of the input data. It must be BCD from 0001 to 1023. The period will be from 0.1 to 102.3 s Sets reverse or normal operation. Set to 0 to specify reverse operation or 1 to specify normal operation. Determines the strength of the input filter. The lower the coefficient, the weaker the filter. This setting must be BCD from 100 to 199, or 000. A setting of 000 sets the default value (0.65) and a setting of 100 to 199 sets the coefficient from 0.00 to 0.99.
P1+3
00 to 15
Derivative time (Tdk)/sampling period () Sampling period () Operation specifier Input filter coefficient ()
P1+4 P1+5
00 to 15 00 to 03 04 to 15
P1+6
00 to 03 08 to 15
P1+7 to P1+32
00 to 15
Determines the number of bits of output data. This setting must be between 0 and 8, which sets the output range between 8 and 16 bits. Determines the number of bits of input data. This setting must be between 00 and 08, which sets the input range between 8 and 16 bits. Do not use. (Used by the system.)
! Caution
Changes made to the parameters will not be effective until the execution condition for PID() goes from OFF to ON.
Note Do not use PID() in the following situations; it may not be executed properly. In interrupt programs In subroutine programs In interlocked program sections (between IL and ILC) In jump program sections (between JMP and JME) In step ladder program section (created with STEP) When the execution condition is ON, PID() performs the PID calculation on the input data when the sampling period has elapsed. The sampling period is the time that must pass before input data is read for processing.
427
Section 7-18
The following diagram shows the relationship between the sampling period and PID processing. PID processing is performed only when the sampling period (100 ms in this case) has elapsed.
1 cycle
70 ms
60 ms
70 ms
70 ms
PID processing No processing (70+30=100 ms, (70 ms) no carryover) PID processing PID processing No processing with initial values (130 ms, 30 ms carryover) (60 ms) (0 ms)
Execution Condition OFF All data that has been set is retained. When the execution condition is OFF, the manipulated variable can be written to the output word (OW) to achieve manual control. Rising Edge of the Execution Condition The work area is initialized based on the PID parameters that have been set and the PID control action is begin. Sudden and radical changes in the manipulated variable output are not made when starting action to avoid adverse affect on the controlled system (bumpless operation). When PID parameters are changed, they first become valid when the execution condition changes from OFF to ON. Execution Condition ON The PID action is executed at the intervals based on the sampling period, according to the PID parameters that have been set. Sampling Period and PID Execution Timing The sampling period is the time interval to retrieve the measurement data for carrying out a PID action. PID(), however, is executed according to CPU cycle, so there may be cases where the sampling period is exceeded. In such cases, the time interval until the next sampling is reduced.
PID control actions are executed by means of PID control with feed-forward control (two degrees of freedom). When overshooting is prevented with simple PID control, stabilization of disturbances is slowed (1). If stabilization of disturbances is speeded up, on the other hand, overshooting occurs and response toward the target value is slowed (2). With feed-forward PID control, there is no overshooting, and response toward the target value and stabilization of disturbances can both be speeded up (3).
Target response
Disturbance response
Overshoot
428
Section 7-18
Proportional Action (P) Proportional action is an operation in which a proportional band is established with respect to the set value (SV), and within that band the manipulated variable (MV) is made proportional to the deviation. An example for reverse operation is shown in the following illustration If the proportional action is used and the present value (PV) becomes smaller than the proportional band, the manipulated variable (MV) is 100% (i.e., the maximum value). Within the proportional band, the MV is made proportional to the deviation (the difference between from SV and PV) and gradually decreased until the SV and PV match (i.e., until the deviation is 0), at which time the MV will be 0% (i.e., the minimum value). The MV will also be 0% when the PV is larger than the SV. The proportional band is expressed as a percentage of the total input range. The smaller the proportional band, the larger the proportional constant and the stronger the corrective action will be. With proportional action an offset (residual deviation) generally occurs, but the offset can be reduced by making the proportional band smaller. If it is made too small, however, hunting will occur.
Adjusting the Proportional Band Proportional band too narrow (hunting occurring) Offset SV SV Proportional band just right Proportional band too wide (large offset)
Integral Action (I) Combining integral action with proportional action reduces the offset according to the time that has passed. The strength of the integral action is indicated by the integral time, which is the time required for the manipulated variable of the integral action to reach the same level as the manipulated variable of the proportional action with respect to the step deviation, as shown in the following illustration. The shorter the integral time, the stronger the correction by the integral action will be. If the integral time is too short, the correction will be too strong and will cause hunting to occur.
Integral Action Step response Deviation
Manipulated variable Pi Action and Integral Time Step response Deviation PI action I action P action
429
Section 7-18
Derivative Action (D) Proportional action and integral action both make corrections with respect to the control results, so there is inevitably a response delay. Derivative action compensates for that drawback. In response to a sudden disturbance it delivers a large manipulated variable and rapidly restores the original status. A correction is executed with the manipulated variable made proportional to the incline (derivative coefficient) caused by the deviation. The strength of the derivative action is indicated by the derivative time, which is the time required for the manipulated variable of the derivative action to reach the same level as the manipulated variable of the proportional action with respect to the step deviation, as shown in the following illustration. The longer the derivative time, the stronger the correction by the derivative action will be.
Derivative Action Step response Deviation
Manipulated variable PD Action and Derivative Time Ramp response Deviation PD action P action D action
PID Action PID action combines proportional action (P), integral action (I), and derivative action (D). It produces superior control results even for control objects with dead time. It employs proportional action to provide smooth control without hunting, integral action to automatically correct any offset, and derivative action to speed up the response to disturbances.
Step Response of PID Control Action Output Step response Deviation PID action I action P action D action
Manipulated variable
Ramp Response of PID Control Action Output Ramp response Deviation PID action I action P action Manipulated variable D action
430
Section 7-18
When using PID action, select either of the following two control directions. In either direction, the MV increases as the difference between the SV and the PV increases. Forward action: MV is increased when the PV is larger than the SV. Reverse action: MV is increased when the PV is smaller than the SV.
Manipulated variable
Manipulated variable
0%
0%
Low temperature
High SV temperature
Low temperature
High temperature SV
The general relationship between PID parameters and control status is shown below. When it is not a problem if a certain amount of time is required for stabilization (settlement time), but it is important not to cause overshooting, then enlarge the proportional band.
Control by measured PID SV When P is enlarged
When overshooting is not a problem but it is desirable to quickly stabilize control, then narrow the proportional band. If the proportional band is narrowed too much, however, then hunting may occur.
When P is narrowed SV Control by measured PID
When there is broad hunting, or when operation is tied up by overshooting and undershooting, it is probably because integral action is too strong. The hunting will be reduced if the integral time is increased or the proportional band is enlarged.
Control by measured PID (when loose hunting occurs) SV Enlarge I or P.
431
Comparison Instructions
Section 7-19
If the period is short and hunting occurs, it may be that the control system response is quick and the derivative action is too strong. In that case, set the derivative action lower.
Control by measured PID (when hunting occurs in a short period) SV Lower D.
Flags
ER:
There is an error in the parameter settings. The cycle time is more than twice as long as the sampling period, so PID() cannot be executed accurately. PID() will be executed in this case. P1 and P1+32 are not in the same area or a parameter setting is not within the specified range. Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.)
CY:
ON when PID processing is being performed. (OFF when the sampling period has not elapsed.)
Limitations Description
When comparing a value to the PV of a timer or counter, the value must be in BCD. When the execution condition is OFF, CMP(20) is not executed. When the execution condition is ON, CMP(20) compares Cp1 and Cp2 and outputs the result to the GR, EQ, and LE flags in the SR area. Placing other instructions between CMP(20) and the operation which accesses the EQ, LE, and GR flags may change the status of these flags. Be sure to access them before the desired status is changed. ER: EQ: LE: GR:
GR EQ LE
Precautions
Flags
Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) ON if Cp1 equals Cp2. ON if Cp1 is less than Cp2. ON if Cp1 is greater than Cp2.
Flag Address 25505 25506 25507 C1 < C2 OFF OFF ON ON OFF C1 = C2 OFF C1 > C2 ON OFF OFF
432
Comparison Instructions
Example: Saving CMP(20) Results
Section 7-19
The following example shows how to save the comparison result immediately. If the content of HR 09 is greater than that of DM 0000, 20000 is turned ON; if the two contents are equal, 20001 is turned ON; if content of HR 09 is less than that of DM 0000, 20002 is turned ON. In some applications, only one of the three OUTs would be necessary, making the use of TR 0 unnecessary. With this type of programming, 20000, 20001, and 20002 are changed only when CMP(20) is executed.
00000
TR 0 CMP(20) HR 09 DM 0000
TR HR DM
TR
00003 00004
AND OUT
Limitations Description
DM 6144 to DM 6655 cannot be used for R. When the execution condition is OFF, TCMP(85) is not executed. When the execution condition is ON, TCMP(85) compares CD to the content of TB, TB+1, TB+2, ..., and TB+15. If CD is equal to the content of any of these words, the corresponding bit in R is set, e.g., if the CD equals the content of TB, bit 00 is turned ON, if it equals that of TB+1, bit 01 is turned ON, etc. The rest of the bits in R will be turned OFF. ER: The comparison table (i.e., TB through TB+15) exceeds the data area. Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.)
Flags
433
Comparison Instructions
Example
Section 7-19
The following example shows the comparisons made and the results provided for TCMP(85). Here, the comparison is made during each cycle when IR 00000 is ON.
Instruction LD TCMP(85)
CD: HR 00
HR 00 0210
Upper limits
DM 0000 DM 0001 DM 0002 DM 0003 DM 0004 DM 0005 DM 0006 DM 0007 DM 0008 DM 0009 DM 0010 DM 0011 DM 0012 DM 0013 DM 0014 DM 0015 0100 0200 0210 0400 0500 0600 0210 0800 0900 1000 0210 1200 1300 1400 0210 1600
R: 216
IR 21000 IR 21001 IR 21002 IR 21003 IR 21004 IR 21005 IR 21006 IR 21007 IR 21008 IR 21009 IR 21010 IR 21011 IR 21012 IR 21013 IR 21014 IR 21015 0 0 1 0 0 0 1 0 0 0 1 0 0 0 1 0
Note BCMP(68) is an expansion instruction for the SRM1(-V2). The function code 68 is the factory setting and can be changed for the SRM1(-V2) if desired. Limitations Each lower limit word in the comparison block must be less than or equal to the upper limit. DM 6144 to DM 6655 cannot be used for R.
434
Comparison Instructions
Description
Section 7-19
When the execution condition is OFF, BCMP(68) is not executed. When the execution condition is ON, BCMP(68) compares CD to the ranges defined by a block consisting of CB, CB+1, CB+2, ..., CB+31. Each range is defined by two words, the first one providing the lower limit and the second word providing the upper limit. If CD is found to be within any of these ranges (inclusive of the upper and lower limits), the corresponding bit in R is set. The comparisons that are made and the corresponding bit in R that is set for each true comparison are shown below. The rest of the bits in R will be turned OFF. CB CD CB+1 Bit 00 CB+2 CD CB+3 Bit 01 CB+4 CD CB+5 Bit 02 CB+6 CD CB+7 Bit 03 CB+8 CD CB+9 Bit 04 CB+10 CD CB+11 Bit 05 CB+12 CD CB+13 Bit 06 CB+14 CD CB+15 Bit 07 CB+16 CD CB+17 Bit 08 CB+18 CD CB+19 Bit 09 CB+20 CD CB+21 Bit 10 CB+22 CD CB+23 Bit 11 CB+24 CD CB+25 Bit 12 CB+26 CD CB+27 Bit 13 CB+28 CD CB+29 Bit 14 CB+30 CD CB+31 Bit 15
Flags
ER:
The comparison block (i.e., CB through CB+31) exceeds the data area. Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.)
435
Comparison Instructions
Example
Section 7-19
The following example shows the comparisons made and the results provided for BCMP(68). Here, the comparison is made during each cycle when IR 00000 is ON.
BCMP(68) HR 00 DM 0010 LR 05
00000
Instruction LD BCMP(68)
HR 00
HR 00 0210
Lower limits
DM 0010 DM 0012 DM 0014 DM 0016 DM 0018 DM 0020 DM 0022 DM 0024 DM 0026 DM 0028 DM 0030 DM 0032 DM 0034 DM 0036 DM 0038 DM 0040 0000 0101 0201 0301 0401 0501 0601 0701 0801 0901 1001 1101 1201 1301 1401 1501
Upper limits
DM 0011 DM 0013 DM 0015 DM 0017 DM 0019 DM 0021 DM 0023 DM 0025 DM 0027 DM 0029 DM 0031 DM 0033 DM 0035 DM 0037 DM 0039 DM 0041 0100 0200 0300 0400 0500 0600 0700 0800 0900 1000 1100 1200 1300 1400 1500 1600
R:LR 05
LR 0500 LR 0501 LR 0502 LR 0503 LR 0504 LR 0505 LR 0506 LR 0507 LR 0508 LR 0509 LR 0510 LR 0511 LR 0512 LR 0513 LR 0514 LR 0515 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0
Compare data in IR 001 (which contains 0210) with the given ranges.
Note CMPL(60) is an expansion instruction for the SRM1(-V2). The function code 60 is the factory setting and can be changed for the SRM1(-V2) if desired. Limitations Cp1 and Cp1+1 must be in the same data area. Cp2 and Cp2+1 must be in the same data area. Set the third operand to 000. When the execution condition is OFF, CMPL(60) is not executed. When the execution condition is ON, CMPL(60) joins the 4-digit hexadecimal content of Cp1+1 with that of Cp1, and that of Cp2+1 with that of Cp2 to create two 8-digit hexadecimal numbers, Cp+1,Cp1 and Cp2+1,Cp2. The two 8-digit numbers are then compared and the result is output to the GR, EQ, and LE flags in the SR area. Placing other instructions between CMPL(60) and the operation which accesses the EQ, LE, and GR flags may change the status of these flags. Be sure to access them before the desired status is changed.
Description
Precautions
436
Comparison Instructions
Flags ER: GR: EQ: LE: Example: Saving CMPL(60) Results
Section 7-19
Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) ON if Cp1+1,Cp1 is greater than Cp2+1,Cp2. ON if Cp1+1,Cp1 equals Cp2+1,Cp2. ON if Cp1+1,Cp1 is less than Cp2+1,Cp2.
The following example shows how to save the comparison result immediately. If the content of HR 10, HR 09 is greater than that of DM 0001, DM 0000, then 20000 is turned ON; if the two contents are equal, 20001 is turned ON; if content of HR 10, HR 09 is less than that of DM 0001, DM 0000, then 20002 is turned ON. In some applications, only one of the three OUTs would be necessary, making the use of TR 0 unnecessary. With this type of programming, 20000, 20001, and 20002 are changed only when CMPL(60) is executed.
Address
CMPL(60) HR 09 DM 0000 ---
00000
TR 0
TR HR DM
TR
TR
Limitations Description
This instruction is available in the CPM2A/CPM2C/SRM1(-V2) only. LL must be less than or equal to UL. When the execution condition is OFF, ZCP() is not executed. When the execution condition is ON, ZCP() compares CD to the range defined by lower limit LL and upper limit UL and outputs the result to the GR, EQ, and LE flags in the SR area. The resulting flag status is shown in the following table.
Comparison result p CD < LL LL CD UL UL < CD Flag status GR (SR 25505) EQ (SR 25506) 0 0 0 1 1 0 LE (SR 25507) 1 0 0
437
Comparison Instructions
Precautions
Section 7-19
Placing other instructions between ZCP() and the operation which accesses the EQ, LE, and GR flags may change the status of these flags. Be sure to access them before the desired status is changed. ER: Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) LL is greater than UL. EQ: LE: GR: ON if LL CD UL ON if CD < LL. ON if CD > UL.
Flags
Example
In the following example, the content of IR 200 (#6FA4) is compared to the range #0010 to #AB1F. Since #0010 #6FA4 #AB1F, the EQ flag and IR 10101 are turned ON.
TR 0 ZCP() 200 #0010 #AB1F
00000
25505 01000
25506 01001 25507 01002 Less Than (below range) Equal (within range)
TR
TR
# # 00003 AND
TR
LL: #0010 0 0 1 0
<
CD: 200 F A
<
UL: #AB1F A B 1 F
438
Conversion Instructions
Limitations Description
Section 7-20
This instruction is available in the CPM2A/CPM2C only. The 8-digit value in LL+1,LL must be less than or equal to UL+1,UL. When the execution condition is OFF, ZCPL() is not executed. When the execution condition is ON, ZCPL() compares the 8-digit value in CD, CD+1 to the range defined by lower limit LL+1,LL and upper limit UL+1,UL and outputs the result to the GR, EQ, and LE flags in the SR area. The resulting flag status is shown in the following table.
Comparison result p GR (SR 25505) CD , CD+1< LL+1,LL LL+1,LL CD, CD+1 UL+1,UL UL+1,UL < CD, CD+1 0 0 1 0 1 0 Flag status EQ (SR 25506) 1 0 0 LE (SR 25507)
Precautions
Placing other instructions between ZCPL() and the operation which accesses the EQ, LE, and GR flags may change the status of these flags. Be sure to access them before the desired status is changed. ER: Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) LL+1,LL is greater than UL+1,UL. ON if LL+1,LL CD, CD+1 UL+1,UL ON if CD, CD+1 < LL+1,LL. ON if CD, CD+1 > UL+1,UL.
Flags
Limitations Description
DM 6144 to DM 6655 cannot be used for R. When the execution condition is OFF, BIN(23) is not executed. When the execution condition is ON, BIN(23) converts the BCD content of S into the numerically equivalent binary bits, and outputs the binary value to R. Only the content of R is changed; the content of S is left unchanged.
BCD S
Binary
BIN(23) can be used to convert BCD to binary so that displays on the Programming Console or any other programming device will appear in hexadecimal rather than decimal. It can also be used to convert to binary to perform binary arithmetic operations rather than BCD arithmetic operations, e.g., when BCD and binary values must be added.
439
Conversion Instructions
Flags ER: The content of S is not BCD.
Section 7-20
Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) EQ: ON when the result is zero.
Limitations
If the content of S exceeds 270F, the converted result would exceed 9999 and BCD(24) will not be executed. When the instruction is not executed, the content of R remains unchanged. DM 6144 to DM 6655 cannot be used for R.
Description
BCD(24) converts the binary (hexadecimal) content of S into the numerically equivalent BCD bits, and outputs the BCD bits to R. Only the content of R is changed; the content of S is left unchanged.
Binary S
BCD
BCD(24) can be used to convert binary to BCD so that displays on the Programming Console or any other programming device will appear in decimal rather than hexadecimal. It can also be used to convert to BCD to perform BCD arithmetic operations rather than binary arithmetic operations, e.g., when BCD and binary values must be added. Flags ER: EQ: Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) ON when the result is zero.
Limitations
This instruction is available in the CPM2A/CPM2C only. DM 6144 to DM 6655 cannot be used for R.
440
Conversion Instructions
Description
Section 7-20
When the execution condition is OFF, BINL(58) is not executed. When the execution condition is ON, BINL(58) converts an eight-digit number in S and S+1 into 32-bit binary data, and outputs the converted data to R and R+1.
S+1 S
BCD
Binary
R+1
Flags
ER:
The contents of S and/or S+1 words are not BCD. Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.)
EQ:
Limitations
This instruction is available in the CPM2A/CPM2C only. If the content of S exceeds 05F5E0FF, the converted result would exceed 99999999 and BCDL(59) will not be executed. When the instruction is not executed, the content of R and R+1 remain unchanged. DM 6144 to DM 6655 cannot be used for R.
Description
BCDL(59) converts the 32-bit binary content of S and S+1 into eight digits of BCD data, and outputs the converted data to R and R+1.
S+1 S
Binary
BCD
R+1
Flags
ER:
Content of R and R+1 exceeds 99999999. Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.)
EQ:
441
Conversion Instructions
Section 7-20
Limitations
The rightmost two digits of Di must each be between 0 and 3. All result words must be in the same data area. DM 6144 to DM 6655 cannot be used for R.
Description
When the execution condition is OFF, MLPX(76) is not executed. When the execution condition is ON, MLPX(76) converts up to four, four-bit hexadecimal digits from S into decimal values from 0 to 15, each of which is used to indicate a bit position. The bit whose number corresponds to each converted value is then turned ON in a result word. If more than one digit is specified, then one bit will be turned ON in each of consecutive words beginning with R. (See examples, below.) The following is an example of a one-digit decode operation from digit number 1 of S, i.e., here Di would be 0001.
Source word C
Bit C (i.e., bit number 12) turned ON. First result word 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0
The first digit and the number of digits to be converted are designated in Di. If more digits are designated than remain in S (counting from the designated first digit), the remaining digits will be taken starting back at the beginning of S. The final word required to store the converted result (R plus the number of digits to be converted) must be in the same data area as R, e.g., if two digits are converted, the last word address in a data area cannot be designated; if three digits are converted, the last two words in a data area cannot be designated. Digit Designator The digits of Di are set as shown below.
Digit number: 3 2 1 0
Specifies the first digit to be converted (0 to 3) Number of digits to be converted (0 to 3) 0: 1 digit 1: 2 digits 2: 3 digits 3: 4 digits Not used (Set to zero)
442
Conversion Instructions
Section 7-20
Some example Di values and the digit-to-word conversions that they produce are shown below.
Di: 0010 S 0 1 2 3 Di: 0031 S 0 1 2 3 R R+1 R+2 R+3 S 0 1 2 3 R R+1 R+2 R R+1 S 0 1 2 3 Di: 0023 R R+1 R+2 R+3 Di: 0030
Flags
ER:
Undefined digit designator, or R plus number of digits exceeds a data area. Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD or the DM area boundary has been exceeded.)
Example
The following program converts digits 1 to 3 of data from DM 0020 to bit positions and turns ON the corresponding bits in three consecutive words starting with HR 10. Digit 0 is not converted.
MLPX(76) DM 0020 #0021 HR 10
00000
Instruction LD MLPX(76)
S: DM 0020
DM 0020 DM 0020 DM 0020 DM 0020 DM 0020 DM 0020 DM 0020 DM 0020 DM 0020 DM 0020 DM 0020 DM 0020 DM 0020 DM 0020 DM 0020 DM 0020 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15
R: HR 10
HR 1000 HR 1001 HR 1002 HR 1003 HR 1004 HR 1005 HR 1006 HR 1007 HR 1008 HR 1009 HR 1010 HR 1011 HR 1012 HR 1013 HR 1014 HR 1015 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1
R+1: HR 11
HR 1100 HR 1101 HR 1102 HR 1103 HR 1104 HR 1105 HR 1106 HR 1107 HR 1108 HR 1109 HR 1110 HR 1111 HR 1112 HR 1113 HR 1114 HR 1115 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0
R+2: HR 12
HR 1200 HR 1201 HR 1202 HR 1203 HR 1204 HR 1205 HR 1206 HR 1207 HR 1208 HR 1209 HR 1210 HR 1211 HR 1212 HR 1213 HR 1214 HR 1215 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Not Converted
1 1 1 1 0 1 1 0 0 0 0 0
15
443
Conversion Instructions
Section 7-20
Limitations
The rightmost two digits of Di must each be between 0 and 3. All source words must be in the same data area. DM 6144 to DM 6655 cannot be used for SB, R, or Di.
Description
When the execution condition is OFF, DMPX(77) is not executed. When the execution condition is ON, DMPX(77) determines the position of the highest ON bit in S, encodes it into single-digit hexadecimal value corresponding to the bit number of the highest ON bit number, then transfers the hexadecimal value to the specified digit in R. The digits to receive the results are specified in Di, which also specifies the number of digits to be encoded. The following is an example of a one-digit encode operation to digit number 1 of R, i.e., here Di would be 0001.
First source word 0 0 0 1 0 0 0 1 0 0 0 1 0 1 1 0
Up to four digits from four consecutive source words starting with S may be encoded and the digits written to R in order from the designated first digit. If more digits are designated than remain in R (counting from the designated first digit), the remaining digits will be placed at digits starting back at the beginning of R. The final word to be converted (S plus the number of digits to be converted) must be in the same data area as SB. Digit Designator The digits of Di are set as shown below.
Digit numbers: 3 2 1 0
Specifies the first digit to receive converted data (0 to 3). Number of words to be converted (0 to 3) 0: 1 word 1: 2 words 2: 3 words 3: 4 words Not used.
444
Conversion Instructions
Section 7-20
Some example Di values and the word-to-digit conversions that they produce are shown below.
Di: 0011 R S S+1 0 1 2 3 Di: 0013 R S S+1 0 1 2 3 S S+1 S+2 S+3 S S+1 S+2 S+3 Di: 0032 R 0 1 2 3 Di: 0030 R 0 1 2 3
Flags
ER:
Undefined digit designator, or S plus number of digits exceeds a data area. Content of a source word is zero. Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.)
Example
When 00000 is ON, the following diagram encodes IR words 200 and 201 to the first two digits of HR 10 and then encodes LR 10 and 11 to the last two digits of HR 10. Although the status of each source word bit is not shown, it is assumed that the bit with status 1 (ON) shown is the highest bit that is ON in the word.
DMPX(77) 200 HR 10 #0010
00000
Instruction LD DMPX(77)
DMPX(77) LR 10 HR 10 #0012
HR # 00002 DMPX(77) LR HR #
B 9 1 8
Digit 2 Digit 3
LR 1015 0
445
Conversion Instructions
Section 7-20
Limitations
Di must be within the values given below. All destination words must be in the same data area. DM 6144 to DM 6655 cannot be used for D. When the execution condition is OFF, SDEC(78) is not executed. When the execution condition is ON, SDEC(78) converts the designated digit(s) of S into the equivalent 8-bit, 7-segment display code and places it into the destination word(s) beginning with D. Any or all of the digits in S may be converted in sequence from the designated first digit. The first digit, the number of digits to be converted, and the half of D to receive the first 7-segment display code (rightmost or leftmost 8 bits) are designated in Di. If multiple digits are designated, they will be placed in order starting from the designated half of D, each requiring two digits. If more digits are designated than remain in S (counting from the designated first digit), further digits will be used starting back at the beginning of S. The digits of Di are set as shown below.
Digit number: 3 2 1 0
Description
Digit Designator
Specifies the first digit of S to be converted (0 to 3). Number of digits to be converted (0 to 3) 0: 1 digit 1: 2 digits 2: 3 digits 3: 4 digits First half of D to be used. 0: Rightmost 8 bits (1st half) 1: Leftmost 8 bits (2nd half) Not used; set to 0.
446
Conversion Instructions
Section 7-20
Some example Di values and the 4-bit binary to 7-segment display conversions that they produce are shown below.
Di: 0011 S digits 0 1 2 3 D 1st half 2nd half 0 1 2 3 D+1 1st half 2nd half Di: 0112 S digits 0 1 2 3 D+1 1st half 2nd half Di: 0130 S digits 0 1 2 3 Di: 0030 S digits D 1st half 2nd half
D 1st half 2nd half D+1 1st half 2nd half D+2 1st half 2nd half
447
Conversion Instructions
Example
Section 7-20
The following example shows the data to produce an 8. The lower case letters show which bits correspond to which segments of the 7-segment display. The table underneath shows the original data and converted code for all hexadecimal digits.
00000 @ SDEC(78) DM 0010 LR 07 200
LR 07
DM 0010
IR 200 f
a b
0 1 0 0 0 0 x101 0 0 0 0 0 0 0 0 0 0 x103 Not used. 3 x102 0 or 1: 0 Bits 00 through 07 1 Bits 08 through 15. 2 0: One digit 1 x100 1: Second digit
20 21 0 22 23 20 21 22 23 20 21 22 23 20 21 22 23
0 1 0 0 0 0 0 1 0 1 1 1 1 0 1 1 8
Bit 00
1 1 1 1 1 1 1
a b c d e f g e
Bit 07
Digit 0 1 2 3 4 5 6 7 8 9 A B C D E F
Display a
448
Conversion Instructions
Flags ER:
Section 7-20
Incorrect digit designator, or data area for destination exceeded. Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.)
Limitations
Di must be within the values given below. All destination words must be in the same data area. DM 6144 to DM 6655 cannot be used for D.
Description
When the execution condition is OFF, ASC(86) is not executed. When the execution condition is ON, ASC(86) converts the designated digit(s) of S into the equivalent 8-bit ASCII code and places it into the destination word(s) beginning with D. Any or all of the digits in S may be converted in order from the designated first digit. The first digit, the number of digits to be converted, and the half of D to receive the first ASCII code (rightmost or leftmost 8 bits) are designated in Di. If multiple digits are designated, they will be placed in order starting from the designated half of D, each requiring two digits. If more digits are designated than remain in S (counting from the designated first digit), further digits will be used starting back at the beginning of S. Note Refer to Appendix G for a table of ASCII characters.
Digit Designator
Specifies the first digit to be converted (0 to 3). Number of digits to be converted (0 to 3) 0: 1 digit 1: 2 digits 2: 3 digits 3: 4 digits First half of D to be used. 0: Rightmost 8 bits (1st half) 1: Leftmost 8 bits (2nd half) Parity 0: none 1: even 2: odd
449
Conversion Instructions
Section 7-20
Some examples of Di values and the 4-bit binary to 8-bit ASCII conversions that they produce are shown below.
Di: 0011 S 0 1 2 3 D 1st half 2nd half S 0 1 2 3 D+1 1st half 2nd half Di: 0112 S 0 1 2 3 D+1 1st half 2nd half D 1st half 2nd half S 0 1 2 3 D+1 1st half 2nd half D+2 1st half 2nd half Di: 0130 D 1st half 2nd half Di: 0030 D 1st half 2nd half
Parity
The leftmost bit of each ASCII character (2 digits) can be automatically adjusted for either even or odd parity. If no parity is designated, the leftmost bit will always be zero. When even parity is designated, the leftmost bit will be adjusted so that the total number of ON bits is even, e.g., when adjusted for even parity, ASCII 31 (00110001) will be B1 (10110001: parity bit turned ON to create an even number of ON bits); ASCII 36 (00110110) will be 36 (00110110: parity bit turned OFF because the number of ON bits is already even). The status of the parity bit does not affect the meaning of the ASCII code. When odd parity is designated, the leftmost bit of each ASCII character will be adjusted so that there is an odd number of ON bits. ER: Incorrect digit designator, or data area for destination exceeded. Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.)
Flags
450
Conversion Instructions
Section 7-20
Limitations
This instruction is available in the CPM2A/CPM2C/SRM1(-V2) only. Di must be within the values given below. All source words must be in the same data area. Bytes in the source words must contain the ASCII code equivalent of hexadecimal values, i.e., 30 to 39 (0 to 9) or 41 to 46 (A to F). DM 6144 to DM 6655 cannot be used for D.
Description
When the execution condition is OFF, HEX() is not executed. When the execution condition is ON, HEX() converts the designated byte(s) of ASCII code from the source word(s) into the hexadecimal equivalent and places it into D. Up to 4 ASCII codes may be converted beginning with the designated first byte of S. The converted hexadecimal values are then placed in D in order from the designated digit. The first byte (rightmost or leftmost 8 bits), the number of bytes to be converted, and the digit of D to receive the first hexadecimal value are designated in Di. If multiple bytes are designated, they will be converted in order starting from the designated half of S and continuing to S+1 and S+2, if necessary. If more digits are designated than remain in D (counting from the designated first digit), further digits will be used starting back at the beginning of D. Digits in D that do not receive converted data will not be changed.
Digit Designator
Specifies the first digit of D to be used (0 to 3). Number of bytes to be converted (0 to 3) 0: 1 byte (2-digit ASCII code) 1: 2 bytes 2: 3 bytes 3: 4 bytes First byte of S to be used. 0: Rightmost 8 bits (1st byte) 1: Leftmost 8 bits (2nd byte) Parity 0: none 1: even 2: odd
451
Conversion Instructions
Section 7-20
Some examples of Di values and the 8-bit ASCII to 4-bit hexadecimal conversions that they produce are shown below.
Di: 0011 S 1st 2nd byte byte D 0 1 2 3 S+1 1st byte 2nd byte Di: 0023 S 1st byte 2nd byte S+1 1st byte 2nd byte D 0 1 2 3 S+1 1st byte 2nd byte S+2 1st byte 2nd byte S 1st byte 2nd byte D 0 1 2 3 Di: 0133 1st 2nd S byte byte Di: 0030 D 0 1 2 3
The following table shows the ASCII codes before conversion and the hexadecimal values after conversion. Refer to Appendix G for a table of ASCII characters.
Original data ASCII Code 30 31 32 33 34 35 36 37 38 39 41 42 43 44 45 46 * * * * * * * * * * * * * * * * 0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 Bit status (See note.) 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 1 1 0 0 0 0 0 0 0 0 0 0 1 1 1 1 0 0 0 0 0 1 1 1 0 0 1 1 0 0 1 1 0 0 0 1 1 0 0 1 0 1 0 1 0 1 0 1 0 1 1 0 1 0 1 0 Digit 0 1 2 3 4 5 6 7 8 9 A B C D E F 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 0 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 Converted data Bits 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1
Note The leftmost bit of each ASCII code is adjusted for parity. Parity The leftmost bit of each ASCII character (2 digits) is automatically adjusted for either even or odd parity. With no parity, the leftmost bit should always be zero. With odd or even parity, the leftmost bit of each ASCII character should be adjusted so that there is an odd or even number of ON bits. If the parity of the ASCII code in S does not agree with the parity specified in Di, the ER Flag (SR 25503) will be turned ON and the instruction will not be executed.
452
Conversion Instructions
Flags ER:
Section 7-20
Incorrect digit designator, or data area for destination exceeded. The source words do not contain ASCII data that can be converted to hexadecimal, i.e., values ranging from 0 to 9 or A to F. Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.)
Example
In the following example, the 2nd byte of LR 10 and the 1st byte of LR 11 are converted to hexadecimal values and those values are written to the first and second bytes of IR 200.
00000 @HEX() LR 10 HR 10 200
Instruction LD @HEX()
HR 10 0 1 1 0
LR 12
3 5 3 4
LR 11
4 2 3 2
LR 10
3 1 3 0 Conversion to hexadecimal
200 0 0 2 1
Limitations
This instruction is available in the CPM2A/CPM2C only. S and S+1 must be within the same data area. R and R+1 must be within the same data area. S and S+1 must be BCD and must be in the proper hours/minutes/seconds format. DM 6144 to DM 6655 cannot be used for R. SEC() is used to convert time notation in hours/minutes/seconds to an equivalent in just seconds. For the source data, the seconds are designated in bits 00 through 07 and the minutes are designated in bits 08 through 15 of S. The hours are designated in S+1. The maximum is thus 9,999 hours, 59 minutes, and 59 seconds. The result is output to R and R+1. The maximum obtainable value is 35,999,999 seconds. ER: S and S+1 or R and R+1 are not in the same data area. S and/or S+1 do not contain BCD.
Description
Flags
453
Conversion Instructions
Number of seconds and/or minutes exceeds 59.
Section 7-20
Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) EQ: Example ON when the result is zero.
When 00000 is OFF (i.e., when the execution condition is ON), the following instruction would convert the hours, minutes, and seconds given in HR 12 and HR 13 to seconds and store the results in DM 0100 and DM 0101 as shown.
SEC() HR 12 DM 0100 000
00000
HR 12 HR 13
3 2
2 8
0 1
7 5
DM 0100 DM 0101
5 1
9 0
2 1
7 3
10,135,927 s
Limitations
This instruction is available in the CPM2A/CPM2C only. S and S+1 must be within the same data area. R and R+1 must be within the same data area. S and S+1 must be BCD and must be between 0 and 35,999,999 seconds. DM 6144 to DM 6655 cannot be used for R.
Description
HMS() is used to convert time notation in seconds to an equivalent in hours/ minutes/seconds. The number of seconds designated in S and S+1 is converted to hours/minutes/ seconds and placed in R and R+1. For the results, the seconds are placed in bits 00 through 07 and the minutes are placed in bits 08 through 15 of R. The hours are placed in R+1. The maximum is 9,999 hours, 59 minutes, and 59 seconds.
Flags
ER:
S and S+1 or R and R+1 are not in the same data area. S and/or S+1 do not contain BCD or exceed 36,000,000 seconds. Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.)
EQ:
454
Conversion Instructions
Example
Section 7-20
When 00000 is OFF (i.e., when the execution condition is ON), the following instruction would convert the seconds given in HR 12 and HR 13 to hours, minutes, and seconds and store the results in DM 0100 and DM 0101 as shown.
HR 12 HR 13
5 1
9 0
2 1
7 3
10,135,927 s
DM 0100 DM 0101
3 2
2 8
0 1
7 5
7-20-12
2S COMPLEMENT NEG()
Ladder Symbols
NEG() S R 000 @NEG() S R: Result word R IR, SR, AR, DM, HR, LR 000 000 Not used. Set to 000.
Limitations
This instruction is available in the CPM2A/CPM2C/SRM1(-V2) only. DM 6144 to DM 6655 cannot be used for R.
Description
Converts the four-digit hexadecimal content of the source word (S) to its 2s complement and outputs the result to the result word (R). This operation is effectively the same as subtracting S from 0000 and outputting the result to R; it will calculate the absolute value of negative signed binary data. If the content of S is 0000, the content of R will also be 0000 after execution and EQ (SR 25506) will be turned on. If the content of S is 8000, the content of R will also be 8000 after execution and UF (SR 25405) will be turned on. Note Refer to 2-16 Calculating with Signed Binary Data for more details.
Flags
Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) ON when the content of R is zero after execution; otherwise OFF. ON when the content of S is 8000; otherwise OFF. ON when bit 15 of R is ON; otherwise OFF.
455
Conversion Instructions
Example
Section 7-20
The following example shows how to use NEG() to find the 2s complement of the content of DM 0005 and output the result to IR 105.
00100 NEG() DM 0005 105 000
Instruction LD NEG()
#0000
#001F
Content of DM 0005.
#FFE1
Output to IR 105.
456
Section 7-21
When the execution condition is OFF, STC(40) is not executed. When the execution condition is ON, STC(40) turns ON CY (SR 25504). Note Refer to Appendix B Error and Arithmetic Flag Operation for a table listing the instructions that affect CY.
When the execution condition is OFF, CLC(41) is not executed. When the execution condition is ON, CLC(41) turns OFF CY (SR 25504). CLEAR CARRY is used to reset (turn OFF) CY (SR 25504) to 0. Note Refer to Appendix B Error and Arithmetic Flag Operation for a table listing the instructions that affect CY.
Limitations Description
DM 6144 to DM 6655 cannot be used for R. When the execution condition is OFF, ADD(30) is not executed. When the execution condition is ON, ADD(30) adds the contents of Au, Ad, and CY, and places the result in R. CY will be set if the result is greater than 9999.
Au + Ad + CY
Flags ER: Au and/or Ad is not BCD.
CY
Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) CY: EQ: ON when there is a carry in the result. ON when the result is 0.
457
Section 7-21
If 00002 is ON, the program represented by the following diagram clears CY with CLC(41), adds the content of IR 200 to a constant (6103), places the result in DM 0100, and then moves either all zeros or 0001 into DM 0101 depending on the status of CY (25504). This ensures that any carry from the last digit is preserved in R+1 so that the entire result can be later handled as eight-digit data.
Address
CLC(41)
TR 0 00002
Operands TR 00002 0
ADD(30) 200 #6103 DM 0100 25504 MOV(21) #0001 DM 0101 25504 MOV(21) #0000 DM 0101
# DM
Although two ADD(30) can be used together to perform eight-digit BCD addition, ADDL(54) is designed specifically for this purpose.
Limitations Description
DM 6144 to DM 6655 cannot be used for R. When the execution condition is OFF, SUB(31) is not executed. When the execution condition is ON, SUB(31) subtracts the contents of Su and CY from Mi, and places the result in R. If the result is negative, CY is set and the 10s complement of the actual result is placed in R. To convert the 10s complement to the true result, subtract the content of R from zero (see example below).
Mi Su CY
Flags ER: Mi and/or Su is not BCD.
CY
Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) CY: EQ: ON when the result is negative, i.e., when Mi is less than Su plus CY. ON when the result is 0.
458
Section 7-21
Be sure to clear the carry flag with CLC(41) before executing SUB(31) if its previous status is not required, and check the status of CY after doing a subtraction with SUB(31). If CY is ON as a result of executing SUB(31) (i.e., if the result is negative), the result is output as the 10s complement of the true answer. To convert the output result to the true value, subtract the value in R from 0. When 00002 is ON, the following ladder program clears CY, subtracts the contents of DM 0100 and CY from the content of 201 and places the result in HR 10. If CY is set by executing SUB(31), the result in HR 10 is subtracted from zero (note that CLC(41) is again required to obtain an accurate result), the result is placed back in HR 10, and HR 1100 is turned ON to indicate a negative result. If CY is not set by executing SUB(31), the result is positive, the second subtraction is not performed, and HR 1100 is not turned ON. HR 1100 is programmed as a self-maintaining bit so that a change in the status of CY will not turn it OFF when the program is rescanned. In this example, differentiated forms of SUB(31) are used so that the subtraction operation is performed only once each time 00002 is turned ON. When another subtraction operation is to be performed, 00002 will need to be turned OFF for at least one cycle (resetting HR 1100) and then turned back ON.
Example
TR 0 00002 CLC(41)
First subtraction
Second subtraction
HR 1100
459
Section 7-21
LD LD OR AND LD OUT
The first and second subtractions for this diagram are shown below using example data for 201 and DM 0100. Note The actual SUB(31) operation involves subtracting Su and CY from 10,000 plus Mi. For positive results the leftmost digit is truncated. For negative results the 10s complement is obtained. The procedure for establishing the correct answer is given below. First Subtraction IR 201 1029 DM 0100 3452 CY 0 HR 10 7577 (1029 + (10000 3452)) CY 1 (negative result) Second Subtraction 0000 HR 10 7577 CY 0 HR 10 2423 (0000 + (10000 7577)) CY 1 (negative result) In the above case, the program would turn ON HR 1100 to indicate that the value held in HR 10 is negative.
Limitations
460
Section 7-21
When the execution condition is OFF, MUL(32) is not executed. When the execution condition is ON, MUL(32) multiplies Md by the content of Mr, and places the result In R and R+1.
Md
X
R +1
Mr
Example
When IR 00000 is ON with the following program, the contents of IR 013 and DM 0005 are multiplied and the result is placed in HR 07 and HR 08. Example data and calculations are shown below the program.
Instruction LD MUL(32)
DM HR
Md: IR 013 3 5 6
X
0 R+1: HR 08 0 0 8
Mr: DM 0005 0 2 5
R: HR 07 9 0
Flags
ER:
Md and/or Mr is not BCD. Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.)
CY: EQ:
Limitations
R and R+1 must be in the same data area. DM 6144 to DM 6655 cannot be used for R.
461
Section 7-21
When the execution condition is OFF, DIV(33) is not executed and the program moves to the next instruction. When the execution condition is ON, Dd is divided by Dr and the result is placed in R and R + 1: the quotient in R and the remainder in R + 1.
Remainder R+1 Quotient R
Dr
Dd
Flags
ER:
Dd or Dr is not in BCD. Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.)
EQ: Example
When IR 00000 is ON with the following program, the content of IR 216 is divided by the content of HR 09 and the result is placed in DM 0017 and DM 0018. Example data and calculations are shown below the program.
Instruction LD DIV(33)
Quotient R: DM 0017 1 5 0
Remainder R + 1: DM 0018 0 0 0 2
HR DM
Dd: HR 09 0 0 3
Dd: IR 216 4 5 2
Limitations
462
Section 7-21
When the execution condition is OFF, ADDL(54) is not executed. When the execution condition is ON, ADDL(54) adds the contents of CY to the 8-digit value in Au and Au+1 to the 8-digit value in Ad and Ad+1, and places the result in R and R+1. CY will be set if the result is greater than 99999999.
Au + 1 Ad + 1
Au Ad CY
+
CY R+1
Flags
ER:
Au and/or Ad is not BCD. Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.)
When 00000 is ON, the following program section adds two 12-digit numbers, the first contained in LR 00 through LR 02 and the second in DM 0010 through DM 0012. The result is placed in HR 10 through HR 13. The rightmost 8 digits of the two numbers are added using ADDL(54), i.e., the contents of LR 00 and LR 01 are added to DM 0010 and DM 0011 and the results is placed in HR 10 and HR 11. The second addition adds the leftmost 4 digits of each number using ADD(30), and includes any carry from the first addition. The last instruction, ADB(50) (see 7-22-1 BINARY ADD ADB(50)) adds two allzero constants to place any carry from the second addition into HR 13.
Operands 00000
463
Section 7-21
Limitations Description
DM 6144 to DM 6655 cannot be used for R. When the execution condition is OFF, SUBL(55) is not executed. When the execution condition is ON, SUBL(55) subtracts CY and the 8-digit contents of Su and Su+1 from the 8-digit value in Mi and Mi+1, and places the result in R and R+1. If the result is negative, CY is set and the 10s complement of the actual result is placed in R. To convert the 10s complement to the true result, subtract the content of R from zero. Since an 8-digit constant cannot be directly entered, use the BSET(71) instruction (see 7-17-4 BLOCK SET BSET(71)) to create an 8-digit constant.
Mi + 1 Su + 1 Mi Su CY
CY R+1
Flags
ER:
Mi, M+1,Su, or Su+1 are not BCD. Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.)
CY: EQ:
ON when the result is negative, i.e., when Mi is less than Su. ON when the result is 0.
464
Section 7-21
The following example works much like that for single-word subtraction. In this example, however, BSET(71) is required to clear the content of DM 0000 and DM 0001 so that a negative result can be subtracted from 0 (inputting an 8-digit constant is not possible).
TR 0 00003 CLC(41)
First subtraction
Second subtraction
HR 0100
Operands 00003 0
Operands
TR
LD LD OR AND LD OUT
DM DM DM TR HR HR
465
Section 7-21
Limitations Description
DM 6144 to DM 6655 cannot be used for R. When the execution condition is OFF, MULL(56) is not executed. When the execution condition is ON, MULL(56) multiplies the eight-digit content of Md and Md+1 by the content of Mr and Mr+1, and places the result in R to R+3.
Md + 1 Md Mr
x
R+3 R+2
Mr + 1
R+1
Flags
ER:
CY: EQ:
Md, Md+1,Mr, or Mr+1 is not BCD. Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) ON when there is a carry in the result. ON when the result is 0.
Limitations Description
DM 6144 to DM 6655 cannot be used for R. When the execution condition is OFF, DIVL(57) is not executed. When the execution condition is ON, DIVL(57) the eight-digit content of Dd and D+1 is divided by the content of Dr and Dr+1 and the result is placed in R to R+3: the quotient in R and R+1, the remainder in R+2 and R+3.
Remainder R+3 R+2 R+1 Quotient R
Dr+1
Dr
Dd+1
Dd
466
Section 7-22
Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) EQ: ON when the result is 0.
Limitations Description
DM 6144 to DM 6655 cannot be used for R. When the execution condition is OFF, ADB(50) is not executed. When the execution condition is ON, ADB(50) adds the contents of Au, Ad, and CY, and places the result in R. CY will be set if the result is greater than FFFF.
Au + Ad + CY
CY
ADB(50) can also be used to add signed binary data. With the CPM1A, CPM2A, CPM2C, and SRM1(-V2), the underflow and overflow flags (SR 25404 and SR 25405) indicate whether the result has exceeded the lower or upper limits of the 16-bit signed binary data range. Flags ER: CY: EQ: OF: UF: Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) ON when the result is greater than FFFF. ON when the result is 0. ON when the result exceeds +32,767 (7FFF). ON when the result is below 32,768 (8000).
467
Section 7-22
The following example shows a four-digit addition with CY used to place either #0000 or #0001 into R+1 to ensure that any carry is preserved.
TR 0 00000 CLC(41)
Operands TR 00000 0
ADB(50) 200 DM 0100 HR 10 25504 MOV(21) #0000 HR 11 25504 MOV(21) #0001 HR 11 = R+1 = R+1 =R
LD AND MOV(21)
# HR
In the case below, A6E2 + 80C5 = 127A7. The result is a 5-digit number, so CY (SR 25504) = 1, and the content of R + 1 becomes #0001.
Au: IR 200 6 E 2
+
0 R+1: HR 11 0 0 1
Ad: DM 0100 0 C 5
R: HR 10 7 A
Note For signed binary calculations, the status of the UF and OF flags indicate whether the result has exceeded the signed binary data range (32,768 (8000) to +32,767 (7FFF)).
Limitations
468
Section 7-22
When the execution condition is OFF, SBB(51) is not executed. When the execution condition is ON, SBB(51) subtracts the contents of Su and CY from Mi and places the result in R. If the result is negative, CY is set and the 2s complement of the actual result is placed in R.
Mi Su CY
CY
SBB(51) can also be used to subtract signed binary data. With the CPM1A, CPM2A, CPM2C, and SRM1(-V2), the underflow and overflow flags (SR 25404 and SR 25405) indicate whether the result has exceeded the lower or upper limits of the 16-bit signed binary data range. Flags ER: CY: EQ: OF: UF: Example Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) ON when the result is negative, i.e., when Mi is less than Su plus CY. ON when the result is 0. ON when the result exceeds +32,767 (7FFF). ON when the result is below 32,768 (8000).
The following example shows a four-digit subtraction. When IR 00001 is ON, the content of LR 00 and CY are subtracted from the content of IR 002 and the result is written to HR 01. CY is turned ON if the result is negative. If normal data is being used, a negative result (signed binary) must be converted to normal data using NEG(). Refer to 7-20-12 2s COMPLEMENT NEG() for details.
Address Instruction LD OUT CLC(41) SBB(51) Operands TR 00001 1
00001 CLC(41)
LR HR
200 00 01
In the case below, the content of LR 00 (#7A03) and CY are subtracted from IR 002 (#F8C5). Since the result is positive, CY is 0. If the result had been negative, CY would have been set to 1. For normal (unsigned) data, the result would have to be converted to its 2s complement.
Mi: IR 002 8 C 5 Su: LR 00 A 0 3 0 0 0
7 0
CY = 0 (from CLC(41))
R: HR 01 E C
Note For signed binary calculations, the status of the UF and OF flags indicate whether the result has exceeded the signed binary data range (32,768 (8000) to +32,767 (7FFF)).
469
Section 7-22
Limitations Description
DM 6144 to DM 6655 cannot be used for R. MLB(52) cannot be used to multiply signed binary data. When the execution condition is OFF, MLB(52) is not executed. When the execution condition is ON, MLB(52) multiplies the content of Md by the contents of Mr, places the rightmost four digits of the result in R, and places the leftmost four digits in R+1.
Md
X
R +1
Mr
Flags
ER: EQ:
Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) ON when the result is 0.
Limitations Description
DM 6144 to DM 6655 cannot be used for R. DVB(53) cannot be used to divide signed binary data. When the execution condition is OFF, DVB(53) is not executed. When the execution condition is ON, DVB(53) divides the content of Dd by the content of Dr and the result is placed in R and R+1: the quotient in R, the remainder in R+1.
Quotient R Remainder R+1
Dr
Dd
470
Section 7-23
Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) EQ: ON when the result is 0.
Limitations
This instruction is available in the CPM2A/CPM2C only. N must be BCD between 0001 to 9999. R1 and R1+N1 must be in the same data area. DM 6144 to DM 6655 cannot be used for C.
Description
When the execution condition is OFF, SRCH() is not executed. When the execution condition is ON, SRCH() searches the range of memory from R1 to R1+N1 for addresses that contain the comparison data in C. If one or more addresses contain the comparison data, the EQ Flag (SR 25506) is turned ON and the lowest address containing the comparison data is identified in C+1. The address is identified differently for the DM area: 1, 2, 3... 1. For an address in the DM area, the word address is written to C+1. For example, if the lowest address containing the comparison data is DM 0114, then #0114 is written in C+1. 2. For an address in another data area, the number of addresses from the beginning of the search is written to C+1. For example, if the lowest address containing the comparison data is IR 114 and the first word in the search range is IR 014, then #0100 is written in C+1. If none of addresses in the range contain the comparison data, the EQ Flag (SR 25506) is turned OFF and C+1 is left unchanged.
Flags
ER:
Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) N is not BCD between 0001 and 9999. R1 and R1+N1 are not in the same data area.
EQ: Example
ON when the comparison data has been matched in the search range.
In the following example, the 10 word range from IR 200 to IR 209 is searched for addresses that contain the same data as DM 0100 (89AB). Since IR 204 con-
471
Section 7-23
tains the same data, the EQ Flag (SR 25506) is turned ON and #0004 is written to DM 0101.
Instruction LD @SRCH() #
DM
DM 0100 IR 200 IR 201 IR 202 IR 203 IR 204 IR 205 IR 206 IR 207 IR 208 IR 209
89AB 1234 5678 ABCD EF13 89AB 8860 90CD 00FF 89AB 810C
Offset: 0004
DM 0101
0004
Note The matching search data in IR 208 is ignored because the search data was found in an earlier word in the range.
Limitations
This instruction is available in the CPM2A/CPM2C only. N must be BCD between 0001 to 9999. R1 and R1+N1 must be in the same data area. DM 6144 to DM 6655 cannot be used for D. When the execution condition is OFF, MAX() is not executed. When the execution condition is ON, MAX() searches the range of memory from R1 to R1+N1 for the address that contains the maximum value and outputs the maximum value to the destination word (D). The address is identified differently for the DM area: 1, 2, 3... 1. For an address in the DM area, the word address is written to C+1. For example, if the address containing the maximum value is DM 0114, then #0114 is written in D+1. 2. For an address in another data area, the number of addresses from the beginning of the search is written to D+1. For example, if the address containing the maximum value is IR 114 and the first word in the search range is IR 014, then #0100 is written in D+1.
Description
472
Section 7-23
If bit 14 of C is ON and more than one address contains the same maximum value, the position of the lowest of the addresses will be output to D+1. The position will be output as the DM address for the DM area, but as an absolute position relative to the first word in the range for all other areas. The number of words within the range (N) is contained in the 3 rightmost digits of C, which must be BCD between 001 and 999. When bit 15 of C is OFF, data within the range is treated as unsigned binary and when it is ON the data is treated as signed binary.
15 14 13 12 11 00
C:
Number of words in range (N: 001 to 999 BCD) Not used set to zero. Output address to D+1? 1 (ON): Yes. 0 (OFF): No.
! Caution
If bit 14 of C is ON, values above #8000 are treated as negative numbers, so the results will differ depending on the specified data type. Be sure that the correct data type is specified. ER: Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) R1 and R1+N1 are not in the same data area. EQ: ON when the maximum value is #0000.
Flags
Example
When IR 00000 is ON, the control data in DM 0000 (4010) will cause a search for the maximum value in the 10 words starting at IR 200. The largest unsigned val-
473
Section 7-23
ue will be stored in DM 0500. The offset from the beginning of the search of the word containing the maximum value will be stored in DM 0501.
Instruction LD MAX()
DM 0000 IR 200 IR 201 IR 202 IR 203 IR 204 10 words IR 205 IR 206 IR 207 IR 208 IR 209 DM 0500 DM 0501
4010 3F2A 51C3 E02A 7C9F 2A20 A827 2A20 E02A C755 94DC E02A 0002 If there are two words containing the maximum value, the one found first will be stored in DM 0501. Maximum value Maximum value
Limitations
This instruction is available in the CPM2A/CPM2C only. N must be BCD between 0001 to 9999. R1 and R1+N1 must be in the same data area. DM 6144 to DM 6655 cannot be used for D. When the execution condition is OFF, MIN() is not executed. When the execution condition is ON, MIN() searches the range of memory from R1 to R1+N1 for the address that contains the minimum value and outputs the minimum value to the destination word (D). The address is identified differently for the DM area: 1, 2, 3... 1. For an address in the DM area, the word address is written to C+1. For example, if the address containing the minimum value is DM 0114, then #0114 is written in D+1.
Description
474
Section 7-23
2. For an address in another data area, the number of addresses from the beginning of the search is written to D+1. For example, if the address containing the minimum value is IR 114 and the first word in the search range is IR 014, then #0100 is written in D+1. If bit 14 of C is ON and more than one address contains the same minimum value, the position of the lowest of the addresses will be output to D+1. The position will be output as the DM address for the DM area, but as an absolute position relative to the first word in the range for all other areas. The number of words within the range (N) is contained in the 3 rightmost digits of C, which must be BCD between 001 and 999. When bit 15 of C is OFF, data within the range is treated as unsigned binary and when it is ON the data is treated as signed binary.
15 14 13 12 11 00
C:
Number of words in range (N: 001 to 999 BCD) Not used set to zero. Output address to D+1? 1 (ON): Yes. 0 (OFF): No.
! Caution
If bit 14 of C is ON, values above #8000 are treated as negative numbers, so the results will differ depending on the specified data type. Be sure that the correct data type is specified. ER: Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) R1 and R1+N1 are not in the same data area. EQ: ON when the minimum value is #0000.
Flags
Example
When IR 00000 is ON, the control data in DM 0300 (4010) will cause a search for the maximum value in the 10 words starting at DM 0000. The smallest unsigned
475
Section 7-23
value will be stored in DM 0500. The address of the word containing the minimum value (0014) will be stored in DM 0501.
Instruction LD MIN()
DM 0300 DM0010 DM0011 DM0012 DM0013 DM0014 10 words DM0015 DM0016 DM0017 DM0018 DM0019 DM 0500 DM 0501
4010 3F2A 51C3 E02A 7C9F 2A20 A827 33BF E02A 2A20 94DC 2A20 0014 If there are two words containing the minimum value, the one found first will be stored in DM 0501. Minimum value Minimum value
Limitations
This instruction is available in the CPM2A/CPM2C only. S must be hexadecimal. N must be BCD from #0001 to #0064. D and D+N+1 must be in the same data area. DM 6144 to DM 6655 cannot be used for S, N, or D to D+N+1. AVG() is used to calculate the average value of S over N cycles. When the execution condition is OFF, AVG() is not executed. Each time that AVG() is executed, the content of S is stored in words D+2 to D+N+1. On the first execution, AVG() writes the content of S to D+2; on the second execution it writes the content of S to D+3, etc. On the Nth execution, AVG() writes the content of S is stored in D+N+1, AVG() calculates the average value of the values stored in D+2 to D+N+1, and writes the average to D.
Description
476
Section 7-23
The following diagram shows the function of words D to D+N+1.
D D+1 D+2 D+3 Average value (after N or more executions) Used by the system. Content of S from the 1st execution of AVG() Content of S from the 2nd execution of AVG()
D+N+1
Precautions
The average value is calculated in binary. Be sure that the content of S is in binary. N must be BCD from #0001 to #0064. If the content of N #0065, AVG() will operate with N=64. The average value will be rounded off to the nearest integer value. (0.5 is rounded up to 1.) Set the contents of D+1 to #0000 to execute AVG() from the first scan. ER: Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) One or more operands have been set incorrectly. D and D+N+1 are not in the same data area.
Flags
Example
In the following example, the content of IR 200 is set to #0000 and then incremented by 1 each cycle. For the first two cycles, AVG() moves the content of IR 200 to DM 1002 and DM 1003. On the third and later cycles AVG() calculates the average value of the contents of DM 1002 to DM 1004 and writes that average value to DM 1000.
00001 @MOV(21) #0000 200
Instruction LD @MOV(21) #
00002
AVG() # DM
CLC(41)
00003 00004
IR 200
477
Section 7-23
Limitations
This instruction is available in the CPM2A/CPM2C only. The 3 rightmost digits of C must be BCD between 001 and 999. DM 6144 to DM 6655 cannot be used for D. If bit 14 of C is OFF (setting for BCD data), all data within the range R1 to R1+N1 must be BCD.
Description
When the execution condition is OFF, SUM() is not executed. When the execution condition is ON, SUM() adds either the contents of words R1 to R1+N1 or the bytes in words R1 to R1+N/21 and outputs that value to the destination words (D and D+1). The data can be summed as binary or BCD and will be output in the same form. Binary data can be either signed or unsigned. The function of bits in C are shown in the following diagram and explained in more detail below.
15 14 13 12 11 00
C:
Number of items in range (N, BCD) Number of words or number of bytes 001 to 999 First byte (when bit 13 is ON) 1 (ON): Rightmost 0 (OFF): Leftmost Data type 1 (ON): Binary 0 (OFF): BCD Not used set to zero. Addition units 1 (ON): Bytes 0 (OFF): Words
The number of items within the range (N) is contained in the 3 rightmost digits of C, which must be BCD between 001 and 999. This number will indicate the number of words or the number of bytes depending the items being summed. Words will be added if bit 13 is OFF and bytes will be added if bit 13 is ON. If bytes are specified, the range can begin with the leftmost or rightmost byte of R1. The leftmost byte of R1 will not be added if bit 12 is ON.
R1 R1+1 R1+2 R1+3 MSB 1 3 5 7 LSB 2 4 6 8
Addition Units
478
Logic Instructions
Section 7-24
The bytes will be added in this order when bit 12 is OFF: 1+2+3+4.... The bytes will be added in this order when bit 12 is ON: 2+3+4....
Data Type
Data within the range is treated as unsigned binary when bit 14 of C is ON and bit 15 is OFF, and it is treated as signed binary when both bits 14 and 15 are ON. Data within the range is treated as BCD when bit 14 of C is OFF, regardless of the status of bit 15.
Flags
ER:
Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) R1 and R1+N1 are not in the same data area. The number of items in C is not BCD between 001 and 999. The data being summed in not BCD when BCD was designated.
EQ: Example
In the following example, the BCD contents of the 8 words from DM 0000 to DM 0007 are added when IR 00001 is ON and the result is written to DM 0010 and DM 0011.
00001 @SUM() #0008 DM 0000 DM 0010
Instruction LD @SUM()
DM 0010 DM 0011
0036 0000
Limitations Description
DM 6144 to DM 6655 cannot be used for Wd. When the execution condition is OFF, COM(29) is not executed. When the execution condition is ON, COM(29) clears all ON bits and sets all OFF bits in Wd.
479
Logic Instructions
Precautions
Section 7-24
The complement of Wd will be calculated every cycle if the undifferentiated form of COM(29) is used. Use the differentiated form (@COM(29)) or combine COM(29) with DIFU(13) or DIFD(14) to calculate the complement just once.
15 Original 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 00 1
Example
15 Complement 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1
00 0
Flags
ER: EQ:
Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) ON when the result is 0.
Limitations Description
DM 6144 to DM 6655 cannot be used for R. When the execution condition is OFF, ANDW(34) is not executed. When the execution condition is ON, ANDW(34) logically ANDs the contents of I1 and I2 bit-by-bit and places the result in R.
15 00 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 00 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1
Example I1
1 15
I2
15
00 0 0 1 0 0 0 1 0 0 0 1 0 0 0 1
Flags
ER: EQ:
Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) ON when the result is 0.
480
Logic Instructions
Section 7-24
Limitations Description
DM 6144 to DM 6655 cannot be used for R. When the execution condition is OFF, ORW(35) is not executed. When the execution condition is ON, ORW(35) logically ORs the contents of I1 and I2 bitby-bit and places the result in R.
15 00 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1
Example I1
15
00 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1
I2
15
00 1 0 1 1 1 0 1 1 1 0 1 1 1 0 1
Flags
ER: EQ:
Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) ON when the result is 0.
Limitations
481
Logic Instructions
Description
Section 7-24
When the execution condition is OFF, XORW(36) is not executed. When the execution condition is ON, XORW(36) exclusively ORs the contents of I1 and I2 bit-by-bit and places the result in R.
15 00 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 00 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1
Example I1
1 15
I2
15
00 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0
Flags
ER: EQ:
Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) ON when the result is 0.
Limitations Description
DM 6144 to DM 6655 cannot be used for R. When the execution condition is OFF, XNRW(37) is not executed. When the execution condition is ON, XNRW(37) exclusively NORs the contents of I1 and I2 bit-by-bit and places the result in R.
15 00 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 00 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1
I1
1 15
I2
15
00 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1
Flags
ER: EQ:
Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) ON when the result is 0.
482
Increment/Decrement Instructions
Section 7-25
DM 6144 to DM 6655 cannot be used for Wd. When the execution condition is OFF, INC(38) is not executed. When the execution condition is ON, INC(38) increments Wd, without affecting Carry (CY). The content of Wd will be incremented every cycle if the undifferentiated form of INC(38) is used. Use the differentiated form (@INC(38)) or combine INC(38) with DIFU(13) or DIFD(14) to increment Wd just once. ER: Wd is not BCD Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) EQ: ON when the incremented result is 0.
Flags
Limitations Description
DM 6144 to DM 6655 cannot be used for Wd. When the execution condition is OFF, DEC(39) is not executed. When the execution condition is ON, DEC(39) decrements Wd, without affecting CY. DEC(39) works the same way as INC(38) except that it decrements the value instead of incrementing it. The content of Wd will be decremented every cycle if the undifferentiated form of DEC(39) is used. Use the differentiated form (@DEC(39)) or combine DEC(39) with DIFU(13) or DIFD(14) to decrement Wd just once. ER: Wd is not BCD. Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) EQ: ON when the decremented result is 0.
Precautions
Flags
483
Subroutine Instructions
Section 7-26
Limitations Description
The subroutine number must be between 000 and 049. A subroutine can be executed by placing SBS(91) in the main program at the point where the subroutine is desired. The subroutine number used in SBS(91) indicates the desired subroutine. When SBS(91) is executed (i.e., when the execution condition for it is ON), the instructions between the SBN(92) with the same subroutine number and the first RET(93) after it are executed before execution returns to the instruction following the SBS(91) that made the call.
Main program
000
SBS(91) may be used as many times as desired in the program, i.e., the same subroutine may be called from different places in the program).
484
Subroutine Instructions
Section 7-26
SBS(91) may also be placed into a subroutine to shift program execution from one subroutine to another, i.e., subroutines may be nested. When the second subroutine has been completed (i.e., RET(93) has been reached), program execution returns to the original subroutine which is then completed before returning to the main program. Nesting is possible to up to sixteen levels. A subroutine cannot call itself (e.g., SBS(91) 000 cannot be programmed within the subroutine defined with SBN(92) 000). The following diagram illustrates two levels of nesting.
SBN(92) 010 SBN(92) 011 SBN(92) 012
SBS(91) 010
SBS(91) 011
SBS(91) 012
RET(93)
RET(93)
RET(93)
The following diagram illustrates program execution flow for various execution conditions for two SBS(91).
A SBS(91) B Main program SBS(91) 001 ON execution condition for subroutine 000 only C 000 OFF execution conditions for subroutines 000 and 001
000
Subroutines
001
A
E
RET(93) END(01)
Flags
ER:
A subroutine does not exist for the specified subroutine number. A subroutine has called itself. An active subroutine has been called.
! Caution
SBS(91) will not be executed and the subroutine will not be called when ER is ON.
485
Subroutine Instructions
Section 7-26
Limitations Description
The subroutine number must be between 000 and 049. Each subroutine number can be used in SBN(92) once only. SBN(92) is used to mark the beginning of a subroutine program; RET(93) is used to mark the end. Each subroutine is identified with a subroutine number, N, that is programmed as a definer for SBN(92). This same subroutine number is used in any SBS(91) that calls the subroutine (refer to 7-26-1 SUBROUTINE ENTER SBS(91)). No subroutine number is required with RET(93). All subroutines must be programmed at the end of the main program. When one or more subroutines have been programmed, the main program will be executed up to the first SBN(92) before returning to address 00000 for the next cycle. Subroutines will not be executed unless called by SBS(91). END(01) must be placed at the end of the last subroutine program, i.e., after the last RET(93). It is not required at any other point in the program. If SBN(92) is mistakenly placed in the main program, it will inhibit program execution past that point, i.e., program execution will return to the beginning when SBN(92) is encountered. If either DIFU(13) or DIFU(14) is placed within a subroutine, the operand bit will not be turned OFF until the next time the subroutine is executed, i.e., the operand bit may stay ON longer than one cycle. There are no flags directly affected by these instructions.
Precautions
Flags
Limitations Description
The subroutine number must be between 000 and 049. If a DM address is used for O1, O1 through O1+3 must be read/write DM. The MACRO instruction allows a single subroutine to replace several subroutines that have identical structure but different operands. There are 4 input words (SR 232 to SR 235) and 4 output words (SR 236 to SR 239), allocated to MCRO(99). These 8 words are used in the subroutine and take their contents from I1 to I1+3 and O1 to O1+3 when the subroutine is executed. When the execution condition is OFF, MCRO(99) is not executed. When the execution condition is ON, MCRO(99) copies the contents of I1 to I1+3 to SR 232 to SR 235, and then calls and executes the subroutine specified in N. When the subroutine is completed, the contents of SR 236 through SR 239 are then transferred back to O1 to O1+3 before MCRO(99) is completed.
486
Section 7-27
In this example, the contents of DM 0010 through DM 0013 are copied to SR 232 through SR 235, and then subroutine 10 is called and executed. When the subroutine is completed, the contents of SR 236 through SR 239 are copied to output words DM 0020 to DM 0023.
Main program MCRO(99) 010 DM 0010 DM 0020 Main program
010
Flags
ER:
A subroutine does not exist for the specified subroutine number. An operand has exceeded a data area boundary. Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) A subroutine has called itself. An active subroutine has been called.
Limitations
This instruction is supported by the CPM1A and CPM2A/CPM2C PCs with transistor outputs only. N and N+1 must be in the same data area. DM 6144 to DM 6655 cannot be used for N.
487
Section 7-27
PULS(65) is used to set the number of pulses for pulse outputs that are started later in the program using SPED(64) or ACC(). The number of pulses set with PULS(65) are output in independent mode. The number of pulses cannot be changed while pulses are being output. In general, PULS(65) should be executed just once each time that the number of pulses needs to be set; use the differentiated variation (@PULS(65)) or an input condition that is ON for just one cycle.
Note Refer to 2-5 Pulse Output Functions for more details. Port Specifier (P) The port specifier indicates the pulse output location. The parameters set by the in C and N will apply to the next SPED(64) or ACC() instruction in which the same port output location is specified.
P Pulse output location(s) 000 Single-phase pulse output 0 without acceleration or deceleration (output 01000) or single-phase pulse output 0 with trapezoidal acceleration and deceleration (outputs 01000 and 01001) 010 Single-phase pulse output 1 without acceleration or deceleration (output 01001) This setting is supported by CPM2A/CPM2C PCs only.
Control Data (C) The control data determines the type of pulses (relative or absolute).
C 000 Relative pulse specification 001 Absolute pulse specification (Valid only when the absolute coordinate system is being used.) This setting is supported by CPM2A/CPM2C PCs only. Pulse type
Number of Output Pulses (N+1 and N) N+1 and N contain the 8-digit BCD number of output pulses setting for independent mode pulse outputs. The number of output pulses can be 16,777,215 to 16,777,215. Bit 15 of N+1 acts as a sign bit; the number is negative if bit 15 is ON, positive if it is OFF. Positive: 0 to +16,777,215 (0000 0000 to 1677 7215) Negative: 16,777,215 to 0 (9677 7215 to 8000 0000) N+1 contains the leftmost 4 digits and N contains the rightmost 4 digits. Number of Movement Pulses The number of movement pulses depends upon the number of output pulses (N+1 and N) and the pulse type (C).
Coordinate system Relative Absolute Movement pulses Number of movement pulses = Number of output pulses Pulse type: Relative (C=000) Number of movement pulses = Number of output pulses Pulse type: Absolute (C=001, CPM2A/CPM2C only) Number of movement pulses = Number of output pulses PV
After PULS(65) has been executed, the calculated number of movement pulses will not be changed even if INI(61) is executed to change the pulse output PV. A specification that causes movement outside of the allowed PV range (16,777,215 to 16,777,215) can be specified without problems. PULS(65) will not be executed and an error will occur (SR 25503 ON) if the calculated number of movement pulses is 0. When the pulse output is operating in independent mode without acceleration or deceleration and the number of movement pulses is negative, the absolute val-
488
Section 7-27
ue of the number of movement pulses will be used. (For example, if the number of movement pulses is 500, a value of 500 will be used.)
Flags
ER:
A data area boundary is exceeded. Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) P is not 000 or 010. C is not 000 or 001. (C cannot be set to 001 when relative coordinates are being used.) The number of output pulses is not between 16,777,215 and 16,777,215. PULS(65) is executed in an interrupt subroutine while a pulse I/O or high-speed counter instruction (INI(61), PRV(62), CTBL(63), SPED(64), PULS(65), ACC(), PWM(), or SYNC()) is being executed in the main program. After PULS(65) is executed, the absolute value of the number of movement pulses is not between 1 and 16,777,215.
Limitations
This instruction is supported by the CPM1A and CPM2A/CPM2C PCs with transistor outputs only. In the CPM1A: F must be BCD, #0000 or #0002 to #0200. In the CPM2A/CPM2C: F must be BCD, #0000 or #0001 to #1000. DM 6144 to DM 6655 cannot be used for F. SPED(64) is used to set the output pulse frequency and start the pulse output from the specified output bit. When the execution condition is OFF, SPED(64) is not executed. When the execution condition is ON, SPED(64) sets the pulse frequency F for the output bit specified by P. M determines the output mode. In general, SPED(64) should be executed just once each time that the frequency needs to be set; use the differentiated variation (@SPED(64)) or an input condition that is ON for just one cycle. Note Refer to 2-5 Pulse Output Functions for more details. Port Specifier (P) The port specifier indicates the output bit where the pulses will be output.
P Pulse output location(s) 000 Single-phase pulse output 0 without acceleration or deceleration (output 01000) 010 Single-phase pulse output 1 without acceleration or deceleration (output 01001) This setting is supported by CPM2A/CPM2C PCs only.
Description
489
Section 7-27
Operation in independent mode and continuous mode is described below. Target Frequency (F) The 4-digit BCD value of F sets the pulse frequency in units of 10 Hz, as shown below. Setting F to 0000 will stop the pulse output from the specified output bit.
PC CPM1A CPM2A/CPM2C Possible values of F 0000 (stops pulse output) or 0002 to 0200 (20 Hz to 2 kHz) 0000 (stops pulse output) or 0001 to 1000 (10 Hz to 10 kHz)
General Operation
The pulse output started by SPED(64) will continue until one of the following occurs: 1, 2, 3... 1. The INI(61) instruction is executed with C=003. 2. In independent mode, the number of output pulses specified by PULS(65) is reached. (Execute PULS(65) before SPED(64).) 3. SPED(64) is executed again with the target frequency, F, set to #0000. 4. The PC is switched to PROGRAM mode. Pulses can be output simultaneously and independently from two output bits. When outputting pulses in independent mode, specify the number of pulses beforehand by executing PULS(65). The number of output pulses must be specified again with PULS(65) each time that the pulse output has been stopped. The frequency cannot be changed with SPED(64) when pulses are already being output from the specified output bit by ACC() or PWM(). An error will occur and SR 25503 will be turned ON if SPED(64) is executed under these circumstances.
In independent mode, just the number of output pulses set by PULS(65) will be output. The number of output pulses must be specified by executing PULS(65) before executing SPED(64). (Pulses wont be output if the number of output pulses has not been specified in advance.) When the calculated number of movement pulses is negative, the absolute value of the number of movement pulses will be used. (For example, if the number of movement pulses is 500, a value of 500 will be used.)
Pulse frequency
Time
490
Section 7-27
In continuous mode, pulses will be output indefinitely until stopped by executing INI(61) with C=003, executing SPED(64) again with F=0000, or switching the PC to PROGRAM mode.
Pulse frequency
Time
Flags
ER:
A data area boundary is exceeded. Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) P is not 000 or 010, M is not 000 or 001, or F is not 0000 to 1000. SPED(64) is executed in an interrupt subroutine while a pulse I/O or high-speed counter instruction (INI(61), PRV(62), CTBL(63), SPED(64), PULS(65), ACC(), PWM(), or SYNC()) is being executed in the main program.
Limitations
This instruction is available in the CPM2A/CPM2C only. P must be 001 or 002 and M must be 000 to 003. C to C+3 must be in the same data area.
Description
ACC() is used to specify the acceleration/deceleration rate and start the pulse output for a pulse output with trapezoidal acceleration and deceleration. In general, ACC() should be executed just once each time that the acceleration/deceleration rate needs to be set; use the differentiated variation (@ACC()) or an input condition that is ON for just one cycle. Note Refer to 2-5 Pulse Output Functions for more details. Port Specifier (P) Always set the port specifier to 000. The 000 setting specifies single-phase pulse output 0 with trapezoidal acceleration and deceleration.
491
Section 7-27
000 Independent mode and up/down pulse output mode 002 Independent mode and pulse + direction output mode 010 011 012 013 CW (continuous mode and up/down pulse output mode) CCW (continuous mode and up/down pulse output mode) CW (continuous mode and pulse + direction output mode) CCW (continuous mode and pulse + direction output mode)
In independent mode, the output direction is set when PULS(65) is executed. Control Words (C, C+1, and C+2) The 3 control words indicate the acceleration rate, target frequency, and deceleration rate. (Each frequency is set in multiples of 10 Hz.)
Word C Function The content of C determines the acceleration rate. During acceleration, the output frequency is increased by the amount set in C every 10 ms. C must be BCD from 0001 to 1000 (10 Hz to 10 kHz). The content of C+1 specifies the target frequency. C+1 must be BCD from 0001 to 1000 (10 Hz to 10 kHz). The content of C+2 determines the deceleration rate. During deceleration, the output frequency is decreased by the amount set in C+2 every 10 ms. C must be BCD from 0001 to 1000 (10 Hz to 10 kHz).
C+1 C+2
General Operation
Two output bits are required for pulse outputs controlled by ACC().
Up/down pulse output mode IR 01000 (CW operation) IR 01001 (CCW operation) Pulse + direction output mode IR 01000 (Pulse output) IR 01001 (Direction specifier)
The pulse output will start when ACC() is executed and the output frequency will be increased every 10 ms by amount specified in control word C. When the target frequency (specified in C+1) is reached, acceleration is stopped and the pulse output continues at a constant frequency. When the pulse output is operating with trapezoidal acceleration and deceleration, the pulse output can be stopped by one of the following methods. 1, 2, 3... 1. Execute the INI(61) instruction with C=003. (Immediate stop) 2. In independent mode, the number of output pulses specified by PULS(65) is reached. (Decelerates to a stop.) 3. ACC() is executed with the target frequency (in C+1) set to 0000. a) When pulses are being output in independent mode, the output will decelerate to a stop at the deceleration rate set when the pulse output was started. b) When pulses are being output in continuous mode, the output will decelerate to a stop at the specified deceleration rate. 4. Switch the PC to PROGRAM mode. (Immediate stop)
492
Section 7-27
In independent mode, just the number of output pulses set by PULS(65) will be output. The number of output pulses must be specified by executing PULS(65) before executing ACC(). (Pulses wont be output if the number of output pulses has not been specified in advance.)
Pulse frequency
Time
The number of output pulses must be specified again with PULS(65) each time that the pulse output has been stopped. In independent mode, the pulse output will begin decelerating at the point determined by the preset number of output pulses and the acceleration/deceleration rates. The pulse output will stop when the preset number of output pulses has been output.
Pulse frequency
If the number of output pulses required for acceleration and deceleration (the time to reach the target frequency the target frequency) exceeds the preset number of pulses, the acceleration and deceleration will be cut short and the pulse output will be triangular rather than trapezoidal.
Pulse frequency
If a high acceleration/deceleration rate and a low number of output pulses are set, there will be effectively no acceleration and deceleration. (The pulse output will operate at a constant speed.) If the (target frequency acceleration/deceleration rate) is not an integer value, the specified acceleration/deceleration rates will be increased or decreased. In the following example, the acceleration and deceleration are 10-ms long, (1) is the acceleration/deceleration rate, and (2) is the target frequency.
Pulse frequency
Time 10 ms 10 ms
493
Section 7-27
In continuous mode, pulses will be output indefinitely until stopped by executing INI(61) with C=003, executing ACC() again with the target frequency (in C+1) set to 0000, or switching the PC to PROGRAM mode.
Pulse frequency
Time
The following conditions apply when ACC() is executed while pulses are already being output with trapezoidal acceleration/deceleration. ACC() will have no effect if it is executed when the pulse output is accelerating or decelerating. When ACC() is executed while pulses are being output in continuous mode, the frequency can be changed to a new target frequency (0001 to 1000: 10 Hz to 10 kHz) with the set acceleration/deceleration rates. If pulses are being output in independent mode, the pulse output can be decelerated to a stop while by executing ACC() with the target frequency (in C+1) set to 0000. The acceleration/deceleration rates and number of output pulses wont be checked or changed. ACC() will have no effect if it is executed when pulses are being output by one of the following instructions. (The pulse output will continue unchanged.) Pulses being output from output 01000 by SPED(64). Pulses being output from output 01001 by SPED(64). Pulses being output from output 01000 by PWM(). Pulses being output from output 01001 by PWM(). Note Be sure to check the status of the pulse output before executing ACC(). Flags ER: A data area boundary is exceeded. Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) P is not 000. M is not 000, 002, or 010 to 013. (The mode specifier is read only when starting the pulse output.) ACC() is executed for a bit from which pulses are already being output by PWM() or SPED(64). ACC() is executed in an interrupt subroutine while a pulse I/O or highspeed counter instruction (INI(61), PRV(62), CTBL(63), SPED(64), PULS(65), ACC(), PWM(), or SYNC()) is being executed in the main program.
494
Section 7-27
P must be 000 or 010, F must be BCD between 0001 and 9999, and D must be BCD between 0001 and 0100. Description PWM() is used to output pulses with the specified duty ratio from the specified output bit. The pulse output continues until PWM() is executed again with a different duty ratio, INI(61) is executed with C=003, or the PC is switched to PROGRAM mode. In general, PWM() should be executed just once to start the pulse output; use the differentiated variation (@PWM()) or an input condition that is ON for just one cycle. Variable duty-ratio pulses can be output simultaneously and independently from two output bits. When variable duty-ratio pulses are being output from an output bit and PWM() is executed for that bit again with a different duty ratio, pulses will continue being output with the new duty ratio. The frequency cannot be changed. PWM() cannot be executed for an output bit if pulses are already being output from that bit by SPED(64) or ACC(). An error will occur and SR 25503 will be turned ON if PWM() is executed under these circumstances. Note Refer to 2-5 Pulse Output Functions for more details. Port Specifier (P) The port specifier indicates the output bit where the pulses will be output.
P Pulse output location(s) 000 Variable duty-ratio pulse output 0 (output 01000) 010 Variable duty-ratio pulse output 1 (output 01001)
Frequency (F) The 4-digit BCD value of F sets the pulse frequency in units of 0.1 Hz. The frequency can be set between 0001 and 9999 (0.1 to 999.9 Hz). Duty Ratio (D) The 4-digit BCD value of D specifies the duty ratio of the pulse output, i.e., the percentage of time that the output is ON. The duty ratio can be set between 0001 and 0100 (1% to 100%). The duty ratio is 75% in the following diagram.
ton t on + D (1% to 100%) T T
Flags
ER:
A data area boundary is exceeded. Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) P is not 000 or 010, F is not BCD between 0001 and 9999, or D is not BCD between 0001 and 0100. (The frequency setting in F is read only when starting the pulse output.) ACC() is executed for a bit from which pulses are already being output by ACC() or SPED(64). PWM() is executed in an interrupt subroutine while a pulse I/O or high-speed counter instruction (INI(61), PRV(62), CTBL(63), SPED(64), PULS(65), ACC(), PWM(), or SYNC()) is being executed in the main program.
495
Section 7-27
Limitations Description
This instruction is available in the CPM2A/CPM2C only. P1 must be 000 and P2 must be 000 or 010. SYNC() takes the frequency of the input pulse received through the highspeed counter inputs, multiplies it by a fixed scaling factor, and outputs pulses from the specified output bit at the resulting frequency. Output frequency = Input frequency Scaling factor/100 In general, SYNC() should be executed just once each time that synchronized pulse output control needs to be set; use the differentiated variation (@SYNC()) or an input condition that is ON for just one cycle. Note Refer to 2-5 Pulse Output Functions for more details. Input Port Specifier (P1) Always set P1 to 000. Output Port Specifier (P2) The value of P2 determines where the scaled pulse frequency is output.
P2 Pulse output location(s) 000 Synchronized pulse output 0 (output 01000) 010 Synchronized pulse output 1 (output 01001)
Scaling Factor (C) The 4-digit BCD value of C sets the scaling factor by which the input frequency is multiplied. The scaling factor can be set between 0001 and 1000 (1 to 1,000%). PC Setup Settings and General Operation The counter input mode for inputs 00000 and 00001 is set in bits 00 to 03 of DM 6642.
DM 6642 bits 00 to 03 0 1 2 4 High-speed counter setting Differential phase mode (5 kHz) Pulse + direction input mode (20 kHz) Up/down input mode (20 kHz) Increment mode (20 kHz)
Input Frequency Range The input frequency range for the synchronized pulse control is set in bits 08 to 15 of DM 6642, as shown in the following table.
DM 6642 bits 08 to 15 02 03 04 Function of inputs 00000 and 00001 Use for synchronized pulse control (10 to 500 Hz) Use for synchronized pulse control (20 Hz to 1 kHz). Use for synchronized pulse control (300 Hz to 20 kHz).
Synchronized pulse control cannot be executed unless inputs 00000 to 00003 are set for synchronized pulse control in bits 08 to 15 (settings 02, 03, and 04). An error will occur and SR 25503 will be turned ON if SYNC() is executed but DM 6642 is not set for synchronized pulse control.
496
Special Instructions
Section 7-28
The high-speed counter function and pulse output functions cannot be used while synchronized pulse control is in operation. An error will occur and SR 25503 will be turned ON if a related pulse output instruction is executed to use one of these functions while synchronized pulse control is being performed. If the input frequency exceeds the maximum in the table above, the maximum input frequency for that range will be used. If the input frequency falls below the minimum, an input frequency of 0 Hz will be used. Output Frequency Range The output frequency range is 10 Hz to 10 kHz. If the calculated output frequency (input frequency scaling factor/100) exceeds 10 kHz, pulses will be output at 10 kHz. If the calculated output frequency falls below 10 Hz, pulses will not be output (0 Hz). Changing the Scaling Factor or Output Port The scaling factor can be changed while synchronized pulse control is in operation by executing SYNC() again with a different scaling factor, but the output port specifier cannot be changed during operation. Stopping the Synchronized Pulse Control Output The synchronized pulse output can be stopped by executing INI(61) with C=005 or switching the PC to PROGRAM mode.
Flags
ER:
A data area boundary is exceeded. Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) P1 is not 000, P2 is not 000 or 010, or C is not BCD between 0001 and 1000. SYNC() is executed when bits 08 to 15 of DM 6642 are not set for synchronized pulse control. SYNC() is executed in an interrupt subroutine while a pulse I/O or high-speed counter instruction (INI(61), PRV(62), CTBL(63), SPED(64), PULS(65), ACC(), PWM(), or SYNC()) is being executed in the main program.
Limitations Description
DM 6649 to DM 6655 cannot be used for FM. When executed with an ON execution condition, MSG(46) reads eight words of extended ASCII code from FM to FM+7 and displays the message on the Programming Console. The displayed message can be up to 16 characters long, i.e., each ASCII character code requires eight bits (two digits). Refer to Appendix G for the ASCII codes. Japanese katakana characters are included in this code. If not all eight words are required for the message, it can be stopped at any point by inputting OD. When OD is encountered in a message, no more words will be read and the words that normally would be used for the message can be used for other purposes.
497
Special Instructions
Message Buffering and Priority
Section 7-28
Up to three messages can be buffered in memory. Once stored in the buffer, they are displayed on a first in, first out basis. Since it is possible that more than three MSG(46)s may be executed within a single cycle, there is a priority scheme, based on the area where the messages are stored, for the selection of those messages to be buffered. The priority of the data areas is as follows for message display: LR > IR > HR > AR > TC > DM In handling messages from the same area, those with the lowest address values have higher priority. In handling indirectly addressed messages (i.e. *DM), those with the lowest final DM addresses have higher priority.
Clearing Messages
To clear a message, execute FAL(06) 00 or clear it via a Programming Console or the Support Software. If the message data changes while the message is being displayed, the display will also change. ER: Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.)
Flags Example
The following example shows the display that would be produced for the instruction and data given when 00000 was ON. If 00001 goes ON, a message will be cleared.
Address
MSG(46) DM 0010
00000
Instruction LD MSG(46)
00001 FAL(06) 00
LD FAL(06)
ASCII equivalent A B C E G I K M O D F H J L N P
MSG ABCDEFGHIJKLMNOP
Note This instruction is not supported by SRM1(-V2) PCs. Limitations St must be less than or equal to E.
498
Special Instructions
Description
Section 7-28
To refresh I/O words, specify the first (St) and last (E) I/O words to be refreshed. When the execution condition for IORF(97) is ON, all words between St and E will be refreshed. This will be in addition to the normal I/O refresh performed during the CPU Units cycle. (If St>E, IORF(97) will be treated as NOP(00).) Normally, I/O refreshing is performed just once each cycle at the end of program execution, but IORF(97) can be used to refresh I/O words immediately during program execution.
! Caution
Although IORF(97) can be used in interrupt subroutines, you must be careful of the interval between IORF(97) executions. If IORF(97) is executed to frequently, a fatal system error may occur (FALS 9F), stopping operation. The interval between executions of IORF(97) should be at least 1.3 ms + total execution time of the interrupt subroutine.
Flags
ER:
St or E is not within the allowed range (IR 000 to IR 019). St is greater than E. (If St>E, IORF(97) will be treated as NOP(00).)
Flags
Note BCNT(67) is an expansion instruction in the CPM2A/CPM2C and SRM1(-V2). The function code 67 is the factory setting and can be changed for if desired. Limitations N cannot be 0. DM 6144 to DM 6655 cannot be used for R. Description When the execution condition is OFF, BCNT(67) is not executed. When the execution condition is ON, BCNT(67) counts the total number of bits that are ON in all words between SB and SB+(N1) and places the result in R. ER: N is not BCD, or N is 0; SB and SB+(N1) are not in the same area. A DM address is used for SB, but SB through SB+(N1) are not all in read/write DM. Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) EQ: ON when the result is 0.
Flags
499
Special Instructions
Section 7-28
Limitations
This instruction is available in the CPM2A/CPM2C/SRM1(-V2) only. The 3 rightmost digits of C must be BCD between 001 and 999. DM 6144 to DM 6655 cannot be used for D. FCS() can be used to check for errors when transferring data through communications ports. When the execution condition is OFF, FCS() is not executed. When the execution condition is ON, FCS() calculates the frame checksum of the specified range by exclusively ORing either the contents of words R1 to R1+N1 or the bytes in words R1 to R1+N1. The frame checksum value (hexadecimal) is then converted to ASCII and output to the destination words (D and D+1). The function of bits in C are shown in the following diagram and explained in more detail below.
15 14 13 12 11 00
Description
C:
Number of items in range (N, BCD) 001 to 999 words or bytes First byte (when bit 13 is ON) 1 (ON): Rightmost 0 (OFF): Leftmost Not used. Set to zero. Calculation units 1 (ON): Bytes 0 (OFF): Words
The number of items within the range (N) is contained in the 3 rightmost digits of C, which must be BCD between 001 and 999. The frame checksum of words will be calculated if bit 13 is OFF and the frame checksum of bytes will be calculated if bit 13 is ON. If bytes are specified, the range can begin with the leftmost or rightmost byte of R1. The leftmost byte of R1 will not be included if bit 12 is ON.
R1 R1+1 R1+2 R1+3 MSB 1 3 5 7 LSB 2 4 6 8
When bit 12 is OFF the bytes will be ORed in this order: 1, 2, 3, 4, .... When bit 12 is ON the bytes will be ORed in this order: 2, 3, 4, 5, .... Conversion to ASCII The byte frame checksum calculation yields a 2-digit hexadecimal value which is converted to its 4-digit ASCII equivalent. The word frame checksum calculation
500
Section 7-29
yields a 4-digit hexadecimal value which is converted to its 8-digit ASCII equivalent, as shown below. Byte frame checksum value 4A Word frame checksum value F10B
D Flags ER:
3 4 4 1
4 6 3 1
D+1
3 0 4 2
Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) The number of items is not 001 to 999 BCD.
Example
When IR 00000 is ON in the following example, the frame checksum (0008) is calculated for the 8 words from DM 0000 to DM 0007 and the ASCII equivalent (30 30 30 38) is written to DM 0010 and DM 0011.
00000 @FCS() #0008 DM 0000 DM 0010
Instruction LD @FCS()
501
Section 7-29
When the execution condition is OFF, INT(89) is not executed. When the execution condition is ON, INT(89) is used to control interrupts and performs one of the seven functions shown in the following table depending on the value of C1.
C1 000 001 002 003 004* 100 200 Clear interrupt inputs Read current mask status of interrupt inputs Restart decrementing counter and unmask interrupt Restart incrementing counter and unmask interrupt Mask all interrupts Unmask all interrupts INT(89) function Mask/unmask interrupt inputs
Note *This setting can be used in CPM2A/CPM2C PCs only. Mask/Unmask Interrupt Inputs (C1=000) This function is used to mask and unmask interrupt inputs 00003 to 00006. Masked inputs are recorded, but ignored. When an input is masked, the interrupt program for it will be run as soon as the bit is unmasked (unless it is cleared beforehand by executing INT(89) with C1=001). Set the corresponding bit in C2 to 0 or 1 to unmask or mask an interrupt input. Bits 00 to 03 correspond to 00003 to 00006. Bits 04 to 15 should be set to 0.
Word C2 bits: 3 2 1 0 Interrupt input 00003 (0: unmask, 1: mask) Interrupt input 00004 (0: unmask, 1: mask) Interrupt input 00005 (0: unmask, 1: mask) Interrupt input 00006 (0: unmask, 1: mask)
All of the interrupt inputs are masked at the start of PC operation, so the inputs must be unmasked in order to be used. Clear Interrupt Inputs (C1=001) This function is used to clear interrupt inputs 00003 to 00006. Since interrupt inputs are recorded, masked interrupts will be serviced as soon as the mask is removed unless they are cleared first. Set the corresponding bit in C2 to 1 to clear an I/O interrupt input. Bits 00 to 03 correspond to 00003 to 00006. Bits 04 to 15 should be set to 0.
Word C2 bits: 3 2 1 0 Interrupt input 00003 (0: Do not clear, 1: clear) Interrupt input 00004 (0: Do not clear, 1: clear) Interrupt input 00005 (0: Do not clear, 1: clear) Interrupt input 00006 (0: Do not clear, 1: clear)
This function reads the current mask status for interrupt inputs 00003 to 00006 and writes that information to word C2. The corresponding bit will be ON if the input is masked. (Bits 00 to 03 correspond to 00003 to 00006.)
Word C2 bits: 3 2 1 0 Interrupt input 00003 (0: not masked, 1: masked) Interrupt input 00004 (0: not masked, 1: masked) Interrupt input 00005 (0: not masked, 1: masked) Interrupt input 00006 (0: not masked, 1: masked)
These functions are used to restart interrupt inputs (counter mode) by refreshing the counter SV (in SR 240 to SR 243) and unmasking the interrupt input (00003 to 00006).
502
Section 7-29
Set C1=3 to restart decrementing counters or C1=4 (CPM2A/CPM2C PCs only) to restart incrementing counters. Set the corresponding bit in C2 to 0 to refresh the inputs counter SV and unmask the interrupt. (Bits 00 to 03 correspond to 00003 to 00006.)
Word C2 bits: 3 2 1 0 Interrupt input 00003 counter Interrupt input 00004 counter Interrupt input 00005 counter Interrupt input 00006 counter
Use the differentiated variation (@INT(89)) or an input condition that is ON for just one cycle when executing INT(89) with C1=003 or C1=004. The counter PV will be reset to the SV if INT(89) is executed while the counter is operating, so the interrupt will never be generated if INT(89) is executed every cycle. When INT(89) is executed with C1=003 or C1=004 and the SV word contains a non-zero SV (0001 to FFFF), the corresponding counter will begin operating (decrementing or incrementing) and the corresponding interrupt will be enabled in counter mode. When the count reaches the SV, an interrupt will be generated and the PV will be returned to the SV, so interrupts will be generated repeatedly until the counter is stopped. Writing 0000 to a counters SV word (SR 240 to SR 243) and executing INT(89) to refresh the SV will stop the counter and disable the corresponding interrupt. To restart the counter, write the non-zero SV to its SV word and execute INT(89). (The SV words are reset to 0000 at the start of operation, so the counters SV must be written to its SV word from the ladder program.) When an interrupt has already been enabled (unmasked), the SV cannot be refreshed just by writing a new value to the SV word. Refresh the SV by executing INT(89) with C1=003 (C1=004 for an incrementing counter). A counter mode interrupt can be masked by executing INT(89) with C1=000 and the corresponding bit in C2 set to 1, but an input will operate in interrupt input mode, not counter mode, when its corresponding bit in C2 is set to 0. Masking or Unmasking All Interrupts (C1=100 or C1=200) All interrupts, including input interrupts, interval timer interrupts, and high-speed counter interrupts, can be masked or unmasked as a group by executing INT(89) with C1=100 or C1=200. The masked inputs are recorded, but ignored. The global mask is in addition to any masks on the individual types of interrupts. Furthermore, clearing the masks for all interrupts does not clear the masks on the individual types of interrupts, but restores them to the masked conditions that existed before INT(89) was executed to mask them as a group. Do not use INT(89) to mask interrupts unless it is necessary to temporarily mask all interrupts. Always use INT(89) instructions in pairs to do so, using the first INT(89) instruction to mask all interrupts and the second one to unmask all interrupts. INT(89) cannot be used to mask and unmask all interrupts from within interrupt routines. Masking Interrupts (C1=100) Use the INT(89) instruction with C1=100 to mask all interrupts.
(@)INT(89) 100 000 000
If an interrupt is generated while interrupts are masked, interrupt processing will not be executed but the interrupt will be recorded for the input, interval timer, and high-speed counter interrupts. The interrupts will then be serviced as soon as interrupts are unmasked.
503
Section 7-29
Unmasking Interrupts (C1=200) Use the INT(89) instruction with C1=200 to unmask interrupts as follows:
(@)INT(89) 200 000 000
Flags
ER:
A data area boundary is exceeded. Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) C1 is not 000 to 004,100, or 200. C2 is not 0000 to 000F. INT(89) is executed with C1=100 or C1=200 while an interrupt program was being executed. INT(89) is executed with C1=100 when all inputs were already masked. C1=200 when inputs were not all unmasked.
Note STIM(69) is an expansion instruction in the CPM2A/CPM2C and SRM1(-V2). The function code 69 is the default setting and can be changed if desired. Limitations C1 must be 000, 003, 006. or 010. If C1 is 000 or 003, C3 represents a BCD subroutine number up to 0049. If C1 is 006, constants cannot be used for C2 or C3. If C1 is 010, both C2 and C3 must be set to 000. STIM(69) is used to control the interval timers by performing four basic functions: starting the timer for a one-shot interrupt, starting the timer for scheduled interrupts, reading the timers PV, and stopping the timer. Set the value of C1 to specify which of these functions will be performed, as shown in the following table. Refer to Section 2 Special Features for more detailed descriptions of using interval timer interrupts. STIM(69) is also described in more detail after the table.
C1 value 000 003 006 010 Function Starts the one-shot interrupt timer. Starts the scheduled interrupt timer. Reads the timer PV. Stops the timer.
Description
Set C1=000 to activate the one-shot interrupt timer. Set C1=003 to start the scheduled interrupt timer.
504
Communications Instructions
Section 7-30
C2, which specifies the timers SV, can be a constant or the first of two words containing the SV. The settings are slightly different depending on the method used. C2 = Constant If C2 is a constant, it specifies the SV of the decrementing counter in BCD. The setting range is 0000 to 9999 (0 to 9.999 ms). (The timing units are fixed at 1 ms.) C3 specifies subroutine number: 0000 to 0049. C2 = Word Address If C2 is a word address, the content of C2 contains the SV of the decrementing counter (BCD, 0000 to 9999). The content of C2+1 specifies the timing units (BCD, 0005 to 0320) in units of 0.1 ms. The decrementing time interval can thus be 0.5 to 32 ms. The timer SV is: (the content of C2) (the content of C2+1) 0.1 ms. C3 specifies subroutine number: 0000 to 0049. Reading the Timer PV (C1=006) Set C1=006 to read the timer PV. C2 specifies the first of two destination words that will receive the timers PV. C2 receives the number of times the decrementing counter has been decremented (hexadecimal, 0000 to 9999) and C2+1 receives the timing units (BCD in 0.1 ms units). C3 specifies the destination word that receives the time which has elapsed since the last time the timer was decremented (BCD in 0.1 ms units). Note The time that has elapsed since the timer was started is computed as follows: ((Content of C2) (Content of C2+1)) + ((Content of C3)) 0.1 ms Stopping the Timer (C=010) Flags Set C1=010 to stop the timer. C2 and C3 have no function and should both be set to 000. ER: C1 is not 000, 003, 006, or 010. A specified subroutine number is not between 0000 and 0049. Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) A data area boundary has been exceeded.
Limitations
This instruction is available in the CPM2A/CPM2C and SRM1(-V2) only. D and D+(N2)1 must be in the same data area. DM 6144 to DM 6655 cannot be used for D or N.
505
Communications Instructions
Section 7-30
N must be BCD from #0000 to #0256. (#0000 to #0061 in Host Link mode) Description When the execution condition is OFF, RXD(47) is not executed. When the execution condition is ON, RXD(47) reads N bytes of data received at the port specified in the control word, and then writes that data in words D to D+(N2)1. Up to 256 bytes of data can be read at one time. If fewer than N bytes are received, the amount received will be read. Note Refer to 4-1Communications Functions for details on using the RXD(47) instruction, setting communications protocol in the PC Setup, etc. ! Caution The PC will be incapable of receiving more data once 256 bytes have been received if received data is not read using RXD(47). Read data as soon as possible after the Reception Completed Flag is turned ON (AR 0806 for the RS-232C port, AR 0814 for the peripheral port.) The value of the control word determines the port from which data will be read and the order in which data will be written to memory.
Digit number: 3 2 1 0
Control Word
Byte order 0: Most significant bytes first, same word 1: Least significant bytes first, same word Not used. (Set to 00.) Port 0: RS-232C port. 1: Peripheral port.
The order in which data is written to memory depends on the value of digit 0 of C. Eight bytes of data 12345678... will be written in the following manner:
Digit 0 = 0 MSB D 1 D+1 3 D+2 5 D+3 7 LSB 2 4 6 8 Digit 0 = 1 MSB D 2 D+1 4 D+2 6 D+3 8 LSB 1 3 5 7
LSB 3 5 7
Flags
ER:
The settings in C are not correct. N is greater than 256. The PC Setup is not set for no-protocol mode. RXD(47) is already being executed.
AR 08: AR 0806 will be turned ON when data has been received normally at the RS-232C port. Reset when RXD(47) is executed.
506
Communications Instructions
Section 7-30
AR 0814 will be turned ON when data has been received normally at the peripheral port. Reset when RXD(47) is executed.
AR 09: Contains the number of bytes received at the RS-232C port. Reset to 0000 when RXD(47) is executed. AR 10: Contains the number of bytes received at the peripheral port. Reset to 0000 when RXD(47) is executed. Note Communications flags and counters can be cleared either by specifying 0000 for N or using the Port Reset Bits (SR 25208 for peripheral port and SR 25209 for RS-232C port.)
Limitations
This instruction is available in the CPM2A/CPM2C and SRM1(-V2) only. S and S+(N2)1 must be in the same data area. DM 6144 to DM 6655 cannot be used for S or N. N must be BCD from #0000 to #0256. (#0000 to #0061 in Host Link mode)
Description
When the execution condition is OFF, TXD(48) is not executed. When the execution condition is ON, TXD(48) reads N bytes of data from words S to S+(N2)1, converts it to ASCII, and outputs the data from the specified port. TXD(48) operates differently in Host Link mode and RS-232C mode, so these modes are described separately. Note 1. Flag AR 0805 will be ON when the PC is capable of transmitting data through the RS-232C port and AR 0813 will be ON when the PC is capable of transmitting data through the peripheral port. 2. Refer to 4-1 Communications Functions for details on using the TXD(48) instruction, setting communications protocol in the PC Setup, etc.
N must be BCD from #0000 to #0061 (i.e., up to 122 bytes of ASCII). The value of the control word determines the port from which data will be output, as shown below.
Digit number: 3 2 1 0
Not used. (Set to 000.) Port 0: Specifies RS-232C port. 1: Specifies peripheral port.
507
Communications Instructions
Section 7-30
The specified number of bytes will be read from S through S+(N/2)1, converted to ASCII, and transmitted through the specified port. The bytes of source data shown below will be transmitted in this order: 12345678...
S S+1 S+2 S+3 MSB 1 3 5 7 LSB 2 4 6 8
The following diagram shows the format for Host Link command (TXD) sent from the CPM2A/CPM2C. The CPM2A/CPM2C automatically attaches the prefixes and suffixes, such as the node number, header, and FCS. @ E X .........
CR
Node number
Header code
FCS
Terminator
RS-232C Mode
N must be BCD from #0000 to #00256. The value of the control word determines the port from which data will be output and the order in which data will be written to memory. The value of the control word determines the port from which data will be read and the order in which data will be written to memory.
Digit number: 3 2 1 0 Byte order 0: Most significant bytes first 1: Least significant bytes first
Control Word
Not used. (Set to 00.) Port 0: Specifies RS-232C port. 1: Specifies peripheral port.
The specified number of bytes will be read from S through S+(N2)1 and transmitted through the specified port.
S S+1 S+2 S+3 MSB 1 3 5 7 LSB 2 4 6 8
When digit 0 of C is 0, the bytes of source data shown above will be transmitted in this order: 12345678... When digit 0 of C is 1, the bytes of source data shown above will be transmitted in this order: 21436587... Note When start and end codes are specified the total data length should be 256 bytes max., including the start and end codes. Flags ER: The settings in C are not correct. N is greater than 256 for no-protocol mode or greater than 61 for Host Link mode.
508
Communications Instructions
Section 7-30
The PC Setup is not set for the correct communications mode. Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) TXD(48) is already being executed.
AR 08: AR 0805 will be turned ON when it is possible to transmit through the RS-232C port. AR 0813 will be turned ON when it is possible to transmit through the peripheral port.
Limitations
This instruction is available in the CPM2A/CPM2C and SRM1(-V2) only. N must be 000. S and S+4 must be in the same data area. (S can be set to #0000 to change the RS-232C settings to their defaults.) STUP() cant be executed within an interrupt subroutine.
Description
When the execution condition is OFF, STUP() is not executed. When the execution condition is ON, STUP() changes the PC Setup settings for the built-in RS-232C port. The settings are changed in the PC Setup, but they are not written to flash memory until the PC is switched to PROGRAM mode (from RUN or MONITOR mode) or the PC is turned OFF and then ON again. In CPM2A/CPM2C and SRM1(-V2) PCs, N must be 000 because STUP() can change the RS-232C Setup for the built-in RS-232C port (DM 6645 to DM 6649) only. If S is a word address, the contents of S through S+4 are copied to DM 6645 to DM 6649. If S is input as the constant #0000, the settings for the built-in RS-232C port are returned to their default values.
S Word address Constant (#0000) Function The contents of S through S+4 are copied to DM 6645 through DM 6649. The settings in DM 6645 through DM 6649 are returned to their default values.
Note
1. The Changing RS-232C Setup Flag (SR 25312) will be ON while STUP() is being executed; it is turned OFF when STUP() is completed. 2. In the CPM2A/CPM2C, an error will occur and STUP() will not be executed if the Communications Switch on the front of the CPU Unit is ON. When this switch is ON, RS-232C communications are governed by the default settings.
509
Communications Instructions
Application Example
Section 7-30
This example shows a program that transfers the contents of DM 0100 through DM 0104 to the PC Setup area for the built-in RS-232C port (DM 6645 through DM 6649).
00000 @STUP() 000 DM 0100 000
Instruction LD @STUP()
DM
The settings are transferred as shown below. The Changing RS-232C Setup Flag (SR 25312) will be turned OFF when the transfer has been completed. The following table shows the function of the transferred setup data.
Source word DM 0100 Destination word DM 6645 Content 1001 Function Enables the communications settings in DM 0101 and sets the communications mode to no-protocol. Sets the following communications settings: 9,600 bps, 1 start bit, 8-bit data, 1 stop bit, no parity No transmission delay (0 ms) Enables the end code CR, LF. (No function when DM 6648 is set to 2000.)
DM 0101
DM 6646
0803
Flags
ER:
Indirectly addressed DM word is non-existent. (Content of *DM word is not BCD, or the DM area boundary has been exceeded.) The port specifier (N) isnt 000. In the CPM2A/CPM2C, the Communications Switch on the front of the CPU Unit is ON. Another STUP() instruction is already being executed or event processing is being performed. The specified source words exceed the data area. The instruction was executed from an interrupt program. The PC Setup is write-protected.
510
8-2
8-3
511
Section
8-1
8-1
Power application
Initialization processes
Initialization
Check hardware and Program Memory. No Check OK? Overseeing processes Yes Set error flags and activate indicators. ALARM (flashing) Preset cycle time monitoring time.
Yes Check cycle time setting. Minimum cycle time set? Yes Wait until minimum cycle time expires. No Cycle time
Note Initialization processes include clearing the IR, SR, and AR areas, presetting system timers, and checking I/O Units.
512
Section
8-1
Program execution
Total time for executing instructions. (Varies according to content of users program.) Almost instantaneous, except for standby processing. 10-point CPU : 0.06 ms 20-point CPU: 0.06 ms 30-point CPU: 0.3 ms Expansion I/O Unit: 0.3 ms 0.26 ms min., 5% or less of cycle time up to 66 ms (see note)
Standby until set time, when minimum cycle time is set in DM 6619 of PC Setup. Calculation of cycle time. Input information is read to input bits. Output information (results of executing program) is written to output bits. Devices connected to peripheral port serviced.
I/O refresh
Note The percentage of the cycle allocated to peripheral port servicing can be changed in the PC Setup (DM 6617).
The effects of the cycle time on CPM1/CPM1A operations are as shown below. When a long cycle time is affecting operation, either reduce the cycle time or improve responsiveness with interrupt programs.
Operation conditions
Cycle time 10 ms or longer 20 ms or longer 100 ms or longer 120 ms or longer 200 ms or longer
TIMH(15) may be inaccurate when TC 004 through TC 127 are used (operation will be normal for TC 000 through TC 003). Programming using the 0.02-second Clock Bit (SR 25401) may be inaccurate. TIM may be inaccurate. Programming using the 0.1-second Clock Bit (SR 25500) may be inaccurate. A CYCLE TIME OVER error is generated (SR 25309 will turn ON). See note 1. The FALS 9F monitoring time SV is exceeded. A system error (FALS 9F) is generated, and operation stops. See note 2. Programming using the 0.2-second Clock Bit (SR 25501) may be inaccurate.
Note
1. The PC Setup (DM 6655) can be used to disable detection of CYCLE TIME OVER error. 2. The cycle monitoring time can be changed in the PC Setup (DM 6618).
In this example, the cycle time is calculated for a CPM1/CPM1A CPU Unit with 20 I/O points (12 input points and 8 output points). The I/O is configured as follows: Inputs: 1 word (00000 to 00011) Outputs: 1 word (01000 to 01007) The rest of the operating conditions are assumed to be as follows: Users program:500 instructions (consists of only LD and OUT) Cycle time: Variable (no minimum set)
513
Section
8-1
The average processing time for a single instruction in the users program is assumed to be 2.86 s. The cycle times are as shown in the following table.
Process 1. Overseeing 2. Program execution 3. Cycle time calculation 4. I/O refresh 5. Peripheral port servicing Cycle time Calculation method Fixed 2.86 500 (s) Negligible 0.01 1 + 0.005 1 (s) Minimum time (1) + (2) + (3) + (4) + (5) Time with Programming Device 0.6 ms 1.43 ms 0 ms 0.06 ms 0.26 ms 2.35 ms Time without Programming Device 0.6 ms 1.43 ms 0 ms 0.06 ms 0 ms 2.09 ms
Note
1. The cycle time can be read from the PC via a Programming Device. 2. The maximum and current cycle time are stored in AR 14 and AR 15. 3. The cycle time can vary with actual operating conditions and will not necessarily agree precisely with the calculated value.
The following conditions are taken as examples for calculating the I/O response times. Input ON delay: Overseeing time: Instruction execution time: Output ON delay: Peripheral port: 8 ms (input time constant: default setting) 1 ms (includes I/O refresh for CPM1A) 14 ms 10 ms Not used.
Minimum I/O Response Time The CPM1/CPM1A responds most quickly when it receives an input signal just prior to I/O refreshing, as shown in the illustration below.
Input point Input bit I/O refreshing Program execution and other processes (15 ms) I/O refreshing Output ON delay (10 ms) Output point Min. I/O response time = 8+15+10 = 33 ms
514
Section
8-1
Maximum I/O Response Time The CPM1/CPM1A takes longest to respond when it receives the input signal just after the input refresh phase of the cycle, as shown in the illustration below. In that case, a delay of approximately one cycle will occur.
I/O refreshing
I/O refreshing
The following conditions are taken as examples for calculating the I/O response times. In CPM1/CPM1A PCs, LR area words LR 00 to LR 15 are used in 1:1 data links and the transmission time is fixed at 12 ms. Input ON delay: Master cycle time: Slave cycle time: Output ON delay: Peripheral port: 8 ms (input time constant: default setting) 10 ms 15 ms 10 ms Not used.
Minimum I/O Response Time The CPM1/CPM1A responds most quickly under the following circumstances: 1, 2, 3... 1. The CPM1/CPM1A receives an input signal just prior to the input refresh phase of the cycle. 2. The Masters communications servicing occurs just as the Master-to-Slave transmission begins.
515
Section
8-1
3. The Slaves communications servicing occurs just after the transmission is completed.
Input point Input bit I/O refresh Overseeing, communications, etc.
Master
CPU processing
Transmission time (12 ms) CPU processing Slave Output point Min. I/O response time = 8+10+12+15+10 = 55 ms Program execution Output ON Slaves cycle time (15 ms) delay (10 ms)
Calculation formula = Input ON response time + Masters cycle time + Slaves cycle time + Output ON response time Maximum I/O Response Time The CPM1/CPM1A takes the longest to respond under the following circumstances: 1, 2, 3... 1. The CPM1/CPM1A receives an input signal just after the input refresh phase of the cycle. 2. The Masters communications servicing just misses the Master-to-Slave transmission. 3. The transmission is completed just after the Slaves communications servicing ends. I/O Maximum Response Time Input ON response time + Masters cycle time x 2 + Transmission time x 3 + Output ON response time
Input point
Input ON response time
Program execution
Master #1
Master to Slave Transmission time Slave to Master Transmission time
Program execution
Program execution
Program execution
Program execution
Slave #1
Slave #2
Slave #3
516
Section
8-1
Item Interrupt ON delay Wait for completion of interrupt-mask processing Change to interrupt processing Return
30 s 30 s
Mask Processing Interrupts are masked during processing of the operations described below. Until the processing is completed, any interrupts will remain masked for the indicated times. Generation and clearing of non-fatal errors: When a non-fatal error is generated and the error contents are registered at the CPM1, or when an error is being cleared, interrupts will be masked for a maximum of 100 s until the processing has been completed. Online editing: Interrupts will be masked for a maximum of 600 ms (i.e.: editing DM 6144 to DM 6655) when online editing is executed during operation. In addition, the system processing may have to wait for a maximum of 170 s during this processing. Example Calculation This example shows the interrupt response time (i.e., the time from when the interrupt input turns ON until the start of the interrupt processing routine) when input interrupts are used under the conditions shown below. Minimum Response Time Interrupt ON delay: 100 s Interrupt mask standby time: 0 s 30 s + Change-to-interrupt processing: Minimum response time: 130 s Maximum Response Time (Except for the Online Editing of DM 6144 to DM6655) Interrupt ON delay: 100 s Interrupt mask standby time: 170 s 30 s + Change-to-interrupt processing: Maximum response time: 300 s
517
Section
8-1
In addition to the response time shown above, the time required for executing the interrupt processing routine itself and a return time of 30 s must also be accounted for when returning to the process that was interrupted.
Special Instructions
Code 00 01 02 03 04 05 06 07 08 09 10 Mnemonic NOP END IL ILC JMP JME FAL FALS STEP SNXT SFT ON execution time (s) 0.36 10.8 4.6 3.6 4.3 4.7 38.5 5.0 14.9 14.2 21.9 34.1 93.6 6.2 Conditions (Top: min.; bottom: max.) Any y 2.6 3.6 2.4 4.7 5.5 5.4 11.1 7.6 Reset 19.7 26.5 60.1 Reset 6.1 Reset 16.8 Shift 10.1 Shift 10.0 OFF execution time (s)
11 12
KEEP CNTR
With 1-word shift register With 10-word shift register With 100-word shift register Any
13 14
DIFU DIFD
JMP 2.6 2.6 2.6 JMP 3.1 JMP 12.2 JMP 12.2 JMP 2.3
518
Section
8-1
OFF execution time (s) Reset 25.7 41.2 5.6 IL 28.4 43.6 JMP 15.8 15.8
17
ASFT
5.6
20
CMP
5.6
21
MOV
5.6
22
MVN
5.6
23 24 25 26 27 28 29 30
31
SUB
5.6
32
MUL
5.6
33
DIV
5.6
34
ANDW
5.6
519
Section
8-1
36
XORW
5.6
37
XNRW
5.6
38 39 40 41 46 50
51
SBB
5.6
52
MLB
5.6
53
DVB
5.6
54 55 56 57 60 61
62
PRV
520
Section
8-1
65 67 68
69
STIM
70
XFER
71
BSET
73 74
XCHG SLD
75
SRD
76 77
MLPX DMPX
521
Section
8-1
81
COLL
83
MOVD
84
SFTR
85
TCMP
86 89
ASC INT
91 92 93
522
Section
8-2
99
MCRO
5.6
8-2
Total time for executing instructions. (Varies according to content of users program.) Negligible except for the delay itself when required. CPM2C CPU Unit: 20-point CPM2A CPU Unit: 30-point CPM2A CPU Unit: 40-point CPM2A CPU Unit: 60-point CPM2A CPU Unit: Expansion I/O Unit: 0.06 ms 0.06 ms 0.3 ms 0.3 ms 0.54 ms 0.3 ms
Communications processing when a Programming Device or Communications Adapter is connected to the RS-232C port. Devices connected to peripheral port serviced.
0.55 ms min., 5% or less of cycle time up to 131 ms (The percentage of cycle time allocated to RS-232C servicing can be set in DM 6616.) 0.55 ms min., 5% or less of cycle time up to 131 ms (The percentage of cycle time allocated to peripheral port servicing can be set in DM 6617.)
The effects of the cycle time on CPM2A/CPM2C operations are as shown below. When a long cycle time is affecting operation, either reduce the cycle time or improve responsiveness with interrupt programs.
Operation conditions
Cycle time 1 ms or longer 10 ms or longer 20 ms or longer 100 ms or longer 120 ms or longer 200 ms or longer
TMHH() may be inaccurate when TC 000 through TC 003 or TC 008 through TC 255 are used (operation will be normal for TC 004 through TC 007). TIMH(15) may be inaccurate when TC 004 through TC 255 are used (operation will be normal for TC 000 through TC 003). Programming using the 0.02-second Clock Bit (SR 25401) may be inaccurate. TIM may be inaccurate. Programming using the 0.1-second Clock Bit (SR 25500) may be inaccurate. A CYCLE TIME OVER error is generated (SR 25309 will turn ON). The FALS 9F monitoring time SV is exceeded. A system error (FALS 9F) is generated, and operation stops. Programming using the 0.2-second Clock Bit (SR 25501) may be inaccurate.
523
Section
8-2
In this example, the cycle time is calculated for a CPM2A/CPM2C CPU Unit with 30 I/O points (18 input points and 12 output points). The I/O is configured as follows: 18 inputs: 2 words (00000 to 00011, 00100 to 00105) 12 outputs: 2 words (01000 to 01007, 01100 to 01103) The rest of the operating conditions are assumed to be as follows: Users program:500 instructions (consists of only LD and OUT) Cycle time: Variable (no minimum set) The average processing time for a single instruction in the users program is assumed to be 1.26 s. The cycle times are as shown in the following table.
Process 1. Overseeing 2. Program execution 3. Cycle time calculation 4. I/O refreshing 5. Peripheral port servicing Cycle time
Calculation method Fixed 1.26 500 (s) Negligible Fixed Minimum time (1) + (2) + (3) + (4) + (5)
Time with Programming Device 0.3 ms 0.6 ms 0 ms 0.3 ms (CPM2C: 0.06 ms) 0.55 ms 1.75 ms (CPM2C: 1.51 ms)
Time without Programming Device 0.3 ms 0.6 ms 0 ms 0.3 ms (CPM2C: 0.06 ms) 0 ms 1.2 ms (CPM2C: 0.96 ms)
Note
1. The cycle time can be read from the PC via a Programming Device. 2. The maximum and current cycle time are stored in AR 14 and AR 15. 3. The cycle time can vary with actual operating conditions and will not necessarily agree precisely with the calculated value.
Output Input
The following conditions are taken as examples for calculating the I/O response times. Input ON delay: Overseeing time: Instruction execution time: Output ON delay: Communications ports: 10 ms (input time constant: default setting) 1 ms (includes I/O refreshing) 14 ms 15 ms Not used.
524
Section
8-2
Minimum I/O Response Time The CPM2A/CPM2C responds most quickly when it receives an input signal just prior to I/O refreshing, as shown in the illustration below.
Input point Input bit I/O refreshing Program execution and other processes (15 ms) I/O refreshing Output ON delay (10 ms) Output point Min. I/O response time = 10+15+15 = 40 ms
Maximum I/O Response Time The CPM2A/CPM2C takes longest to respond when it receives the input signal just after the input refresh phase of the cycle, as shown in the illustration below. In that case, a delay of approximately one cycle will occur.
Input point Input bit I/O refreshing Program execution and other processes (15 ms) I/O refreshing Program execution and other processes (15 ms) I/O refreshing Output ON delay (10 ms) Output point Max. I/O response time = 10+15 2+15 = 55 ms
The following conditions are taken as examples for calculating the I/O response times. In CPM2A/CPM2C PCs, LR area words LR 00 to LR 15 are used in 1:1 data links and the transmission time is fixed at 21 ms. Input ON delay: Master cycle time: Slave cycle time: Output ON delay: 10 ms (input time constant: default setting) 10 ms 15 ms 15 ms
Minimum I/O Response Time The CPM2A/CPM2C responds most quickly under the following circumstances:
525
Section
8-2
1. The CPM2A/CPM2C receives an input signal just prior to the input refresh phase of the cycle. 2. The Masters communications servicing occurs just as the Master-to-Slave transmission begins. 3. The Slaves communications servicing occurs just after the transmission is completed.
I/O refresh Input ON delay (10 ms) Overseeing, communications servicing, etc.
Master
CPU processing
Transmission time (21 ms) CPU processing Slave Output point Min. I/O response time = 10+10+12+15+15 = 62 ms Program execution Output ON Slaves cycle time (15 ms) delay (10 ms)
Maximum I/O Response Time The CPM2A/CPM2C takes the longest to respond under the following circumstances: 1, 2, 3... 1. The CPM2A/CPM2C receives an input signal just after the input refresh phase of the cycle. 2. The Masters communications servicing just misses the Master-to-Slave transmission. 3. The transmission is completed just after the Slaves communications servicing ends. I/O Maximum Response Time Input ON response time + Masters cycle time 2 + Transmission time 3 + Slaves cycle time 2 + Output ON response time
Input point
Input ON response time
Program execution
Master #1
Master to Slave Transmission time Slave to Master Transmission time
Program execution
Program execution
Program execution
Program execution
Slave #1
Slave #2
Slave #3
526
Section
8-2
This is the delay time from the time the interrupt input bit turns ON until the time that the interrupt is executed. This delay does not affect other interrupts. Wait for completion of When a process that disables (masks) the interrupt is being executed, this is interrupt-mask processing the time required for that process to be completed. Change to interrupt This is the time it takes to change processing to the interrupt process. processing Return This is the time it takes, from execution of RET(93), to return to the processing that was interrupted.
Mask Processing Interrupts are masked during processing of the operations described below. Until the processing is completed, any interrupts will remain masked for the indicated times. Generation and clearing of non-fatal errors: Interrupts will be masked for up to 100 s when a non-fatal error has been generated and the error contents are being registered in the PC, or when an error is being cleared. Online editing: Operation will stop and interrupts will be masked for up to 600 ms (for DM 6144 to DM 6655) when online editing is executed or the settings are changed with STUP() during operation. The program or PC Setup can be overwritten during that delay. In addition to the online editing delay, interrupts may be masked for up to 170 s for system processing. Example Calculation This example shows the interrupt response time (i.e., the time from when the interrupt input turns ON until the start of the interrupt processing routine) when input interrupts are used under the conditions shown below. Minimum Response Time Interrupt ON delay: 100 s Interrupt mask standby time: 0 s 30 s + Change-to-interrupt processing: Minimum response time: 130 s Maximum Response Time (Except for the Online Editing of DM 6144 to DM 6655) Interrupt ON delay: 100 s Interrupt mask standby time: 170 s 30 s + Change-to-interrupt processing: Maximum response time: 300 s
527
Section
8-2
In addition to the response time shown above, the time required for executing the interrupt processing routine itself and a return time of 30 s must also be accounted for when returning to the process that was interrupted.
0.26 1.88 2.58 4.76 4.50 Constant for SV :DM for SV Constant for SV :DM for SV 7.8 15.6 6.8 14.5 7.6 15.4 2.9 2.9 2.9 2.9 3.1 3.1
Special Instructions
Code 00 01 02 03 04 05 06 07 08 09 10 Mnemonic NOP END IL ILC JMP JME FAL FALS STEP SNXT SFT ON execution time (s) 0.15 6.2 1.1 1.6 0.95 2.1 20.5 2.9 7.3 5.1 10.4 15.3 39.6 3.2 Conditions (Top: min.; bottom: max.) Any y 2.1 1.6 1.8 2.1 2.5 2.5 6.0 3.6 Reset 9.2 11.9 26.2 Reset 3.1 Reset 7.9 Shift 5.1 Shift 5.4 OFF execution time (s)
11 12
KEEP CNTR
With 1-word shift register With 10-word shift register With 53-word shift register Any
13 14
DIFU DIFD
JMP 0.98 1.0 1.0 JMP 1.3 JMP 5.6 JMP 0.96 JMP 0.97
528
Section
8-2
OFF execution time (s) Reset 13.0 14.4 20.8 22.2 2.6 IL 12.6 14.0 20.5 22.0 JMP 6.1 7.5 6.1 7.5
17
ASFT
2.6
20
CMP
2.6
21
MOV
2.6
22
MVN
2.6
23 24 25 26 27 28 29 30
31
SUB
2.6
32
MUL
2.6
33
DIV
2.6
34
ANDW
2.6
529
Section
8-2
36
XORW
2.6
37
XNRW
2.6
38 39 40 41 46 47 48
50
ADB
51
SBB
2.6
52
MLB
2.6
53
DVB
2.6
54 55 56 57 58 59 60
530
Section
8-2
531
Section
8-2
Registering a target value comparison table and 2.6 starting comparison in incrementing/decrementing pulse input mode via word Registering a target value comparison table and starting comparison in incrementing/decrementing pulse input mode via :DM Registering a target value comparison table and starting comparison in incrementing mode via word Registering a target value comparison table and starting comparison in incrementing mode via :DM Registering a range comparison table and starting comparison in incrementing/decrementing pule input mode via word Registering a range comparison table and starting comparison in incrementing/decrementing pule input mode via :DM Registering a range comparison table and starting comparison in incrementing mode via word Registering a range comparison table and starting comparison in incrementing mode via :DM Only registering a target value comparison table in incrementing/decrementing pulse input mode via word Only registering a target value comparison table in incrementing/decrementing pulse input mode via :DM Only registering a target value comparison table in incrementing mode via word Only registering a target value comparison table in incrementing mode via :DM Only registering a range comparison table in incrementing/decrementing pule input mode via word Only registering a range comparison table in incrementing/decrementing pule input mode via :DM Only registering a range comparison table in incrementing mode via word Only registering a range comparison table in incrementing mode via :DM Specifying a constant in independent mode Specifying :DM in independent mode Specifying a constant in continuous pulse output mode Specifying :DM in continuous pulse output mode Specifying a word when changing output frequency Specifying :DM when changing output frequency 2.6
807.5
185.8
781.9
410.0
418.9
810.3
359.1
532
Section
8-2
67 68
BCNT BCMP
69
STIM
70
XFER
71
BSET
73 74
XCHG SLD
75
SRD
76 77 78 80
533
Section
8-2
83
MOVD
2.6
84
SFTR
2.6
85
TCMP
2.6
86 89
ASC INT
2.6 2.6
91 92 93 97
99
MCRO
Refreshing IR 000 Refreshing one input word Refreshing one output word With word-set I/O operands With :DM-set I/O operands
2.6
534
Section
8-2
---
FCS
2.6
535
Section
8-2
---
PID
---
PWM
---------
---
STUP
2.6
---
SYNC
---
TIML
2.6
536
Section
8-3
8-3
Initialization
Overseeing processes
Program execution
Output refreshing
Note
1. The cycle time can be read using Programming Devices. 2. Cycle time maximum and current cycle time are stored in AR 14 and AR 15. 3. Change to processing will cause cycle times to change therefore the calculated values and actual values (for cycle time) will no always match.
537
Section
8-3
Input information is read to input bits. User program is executed. Refer to 8-3-6 SRM1(-V2) Instruction Execution Times. Standby until set time, when minimum cycle time is set in DM 6619 of PC Setup. Calculation of cycle time. Output information (results of executing program) is written to output bits. CompoBus/S communications are started. Devices connected to RS-232C port serviced.
Output refreshing
5% or less of cycle time, but always between 0.55 and 131 ms (Set in DM 6616.) 5% or less of cycle time, but always between 0.55 and 131 ms (Set in DM 6617.)
In SRM1(-V2) PCs, CompoBus/S communications are started after the output refresh is completed. As a result, when the overseeing time plus the RS-232C port servicing time plus the peripheral port servicing time is shorter than the CompoBus/S communications response time, processing is placed on stand-by until CompoBus/S communications are completed. The minimum cycle time therefore is the the CompoBus/S communications response time plus the program execution time plus the input refresh time plus the output refresh time. The CompoBus/S communications response time depends on the maximum number of nodes and communications mode settings, as follows:
Max. number of nodes Communications mode 32 High-speed mode Long-distance mode 16 High-speed mode Long-distance mode CompoBus/S response time 0.8 ms 6.0 ms 0.5 ms 4.0 ms
Note The maximum number of nodes and communications mode are set in the PC Setup (DM 6603).
538
Section
8-3
The effects of the cycle time on SRM1(-V2) operations are as shown below. When a long cycle time is affecting operation, either reduce the cycle time or improve responsiveness with interrupt programs.
Operation conditions
Cycle time 10 ms or longer 20 ms or longer 100 ms or longer 120 ms or longer 200 ms or longer
TIMH(15) may be inaccurate when TC 004 through TC 127 are used (operation will be normal for TC 000 through TC 003). Programming using the 0.02-second Clock Bit (SR 25401) may be inaccurate. TIM may be inaccurate. Programming using the 0.1-second Clock Bit (SR 25500) may be inaccurate. A CYCLE TIME OVER error is generated (SR 25309 will turn ON). See note 1. The FALS 9F monitoring time SV is exceeded. A system error (FALS 9F) is generated, and operation stops. See note 2. Programming using the 0.2-second Clock Bit (SR 25501) may be inaccurate.
Note
1. The PC Setup (DM 6655) can be used to disable detection of CYCLE TIME OVER error. 2. The cycle monitoring time can be changed in the PC Setup (DM 6618).
The following is an example of a cycle time calculation. The operating conditions are assumed to be as follows: Users program:500 instructions (consists of only LD and OUT) Cycle time: Variable (no minimum set)
RS-232C port: Not used. Max. nodes: Peripheral: 32 nodes and high-speed communications mode (CompoBus/S communication response time = 0.8 ms) 0.7 ms
The average processing time for a single instruction in the users program is assumed to be 1.16 s. The cycle times are as shown in the following table.
Process 1. Overseeing 2. CompoBus/S end wait 3. Input refresh 4. Program execution 5. Cycle time calculation 6. Output refresh 7. RS-232C port servicing 8. Peripheral port servicing Cycle time Calculation method Fixed See previous page. Fixed 1.16 500 (s) Negligible 0.01 1 + 0.005 1 (s) Not required 5% of cycle time (1) + (2) + (3) + ...+ (8) Peripheral port used 0.18 ms 0.00 ms 0.02 ms 0.8 ms 0.00 ms 0.05 ms 0.00 ms 0.7 ms 1.75 ms Peripheral port not used 0.18 ms 0.62 ms 0.02 ms 0.8 ms 0.00 ms 0.05 ms 0.00 ms 0.00 ms 1.67 ms
Note
1. The cycle time can be read from the PC via a Programming Device. 2. The maximum and current cycle time are stored in AR 14 and AR 15. 3. The cycle time can vary with actual operating conditions and will not necessarily agree precisely with the calculated value. 4. When the peripheral port is used, there is no CompoBus/S end wait time as it is always 0 or less. 5. CompoBus/S end wait time = 0.8 0.18 0 0 = 0.62 (CompoBus/S communication response time Overseeing RS-232C port servicing time peripheral port servicing time.
539
Section
8-3
Input on Slave
Output on Slave
Maximum I/O Response Time Maximum I/O response time = Input ON delay + Output ON delay + CompoBus/S communications cycle time + SRM1(-V2) cycle time x 2
Input on Slave
Output on Slave
540
Section
8-3
Transmission time (39 ms) Program execution Output ON Slaves cycle time (15 ms) delay (10 ms) Output point Min. I/O response time = 8+10+39+15+10 = 82 ms
Maximum I/O Response Time The SRM1(-V2) takes the longest to respond under the following circumstances: 1, 2, 3... 1. The SRM1(-V2) receives an input signal just after the I/O refresh phase of the cycle. 2. The Masters communications servicing just misses the Master-to-Slave transmission.
541
Section
8-3
3. The transmission is completed just after the Slaves communications servicing ends.
Input point Input bit Program execution Masters cycle time (10 ms) Master to Slave Slave to Master Master to Slave Program execution I/O refresh Input ON delay (8 ms) Overseeing, communications, etc.
Item Wait for completion of interrupt-mask processing Change to interrupt processing Return
15 s 15 s
Mask Processing Interrupts are masked during processing of the operations described below. Until the processing is completed, any interrupts will remain masked for the indicated times. Generation and clearing of non-fatal errors: When a non-fatal error is generated and the error contents are registered at the SRM1(-V2), or when an error is being cleared, interrupts will be masked for a maximum of 100 s until the processing has been completed.
542
Section
8-3
Interrupts will be masked for a maximum of 600 ms (i.e.: editing DM 6144 to DM 6655) when online editing is executed during operation. In addition, the system processing may have to wait for a maximum of 170 s during this processing.
Any Any
-----
11 12
KEEP CNTR
With 1-word shift register With 10-word shift register With 100-word shift register Any
JMP 1.4 1.4 1.4 JMP 1.7 JMP 6.5 JMP 1.3
543
Section
8-3
OFF execution time (s) Shift 5.8 Reset 14.1 15.6 22.8 23.9 2.9 IL 5.7 IL 13.9 15.4 22.1 23.6 JMP 1.3 JMP 7.0 8.5 7.0 8.5
17
ASFT*
20
CMP
21
MOV
22
MVN
23 24 25 26 27 28 29 30
31
SUB
32
MUL
33
DIV
544
Section
8-3
35
ORW
36
XORW
37
XNRW
38 39 40 41 46 47 48
50
ADB
51
SBB
52
MLB
53
DVB
54 55 56 57 60
545
Section
8-3
69
STIM*
3.0
70
XFER
3.0
71
BSET
3.0
73 74
XCHG SLD
3.1 3.0
75
SRD
3.0
76 77 78 80
546
Section
8-3
83
MOVD
2.9
84
SFTR
3.0
85
TCMP
3.0
86 91 92 93 99
Note Those instructions marked with an asterisk are expansion instructions. Expansion Instructions without Default Function Codes
Code ------Mnemonic FCS HEX NEG ON execution time (s) 23.4 643.7 43.6 73.5 46.0 48.0 65.5 420.0 452.0 63.0 84.5 51.2 58.2 Conditions (Top: min.; bottom: max.) Adding one word and outputting to word Adding 999 words and outputting to :DM DM DM :DM :DM Converting constant to word Converting word to word Converting :DM to :DM Initializing word to word Initializing :DM to :DM Sampling word to word Sampling :DM to :DM Transferring constant to word Transferring word to word 3.0 3.0 3.0 OFF execution time (s) 3.0
---
PID
3.0
---
STUP
547
Section
8-3
548
SECTION 9 Troubleshooting
This section describes how to diagnose and correct the hardware and software errors that can occur during PC operation. 9-1 9-2 9-3 9-4 9-5 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Programming Console Operation Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Programming Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . User-defined Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Operating Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-5-1 Non-fatal Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-5-2 Fatal Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-5-3 Other Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Error Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Host Link Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Troubleshooting Flowcharts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 550 550 551 552 553 553 554 554 555 557 557
549
Section
9-2
9-1
Introduction
PC errors can be divided broadly into the following four categories: 1, 2, 3... 1. Program Input Errors These errors occur when inputting a program or attempting an operation used to prepare the PC for operation. 2. Programming Errors These errors will occur when the program is checked using the Program Check operation. 3. User-defined Errors There are three instructions that the user can use to define his own errors or messages. The instructions will be executed when a particular condition (defined by the user) has occurred during operation. 4. Operating Errors These errors occur after program execution has been started. a) Non-fatal Operating Errors PC operation and program execution will continue after one or more of these errors have occurred. b) Fatal Operating Errors PC operation and program execution will stop and all outputs from the PC will be turned OFF when any of these errors have occurred. The PCs indicators will indicate when a PC error has occurred and an error message or code will be displayed on the Programming Console or host computer if one is connected. The error code is also contained in SR 25300 to SR 25307. For the most recent errors, both the type of error and time of occurrence will be recorded in the PCs error log area. Details are provided starting on page 555. There are flags and other information provided in the SR and AR areas that can be used in troubleshooting. Refer to Section 3 Memory Areas for lists of these. Note In addition to the errors described above, communications errors can occur when the PC is part of a Host Link System. Refer to page 557 for details.
9-2
550
Programming Errors
Section
9-3
9-3
Programming Errors
These errors in program syntax will be detected when the program is checked using the Program Check operation. Three levels of program checking are available. The desired level must be designated to indicate the type of errors that are to be detected. The following table provides the error types, displays, and explanations of all syntax errors. Check level 0 checks for type A, B, and C errors; check level 1, for type A and B errors; and check level 2, for type A errors only.
Level A Errors
Meaning and appropriate response The program has been damaged, creating a non-existent function code. Re-enter the program. The number of logic blocks and logic block instructions does not agree, i.e., either LD or LD NOT has been used to start a logic block whose execution condition has not been used by another instruction, or a logic block instruction has been used that does not have the required number of logic blocks. Check your program. A constant entered for the instruction is not within defined values. Change the constant so that it lies within the proper range. There is no END(01) in the program. Write END(01) at the final address in the program. An instruction is in the wrong place in the program. Check instruction requirements and correct the program. A JME(05) instruction is missing for a JMP(04) instruction. Correct the jump number or insert the proper JME(05) instruction. The same jump number or subroutine number has been used twice. Correct the program so that the same number is only used once for each. The SBS(91) instruction has been programmed for a subroutine number that does not exist. Correct the subroutine number or program the required subroutine. STEP(08) with a section number and STEP(08) without a section number have been used incorrectly. Check STEP(08) programming requirements and correct the program. Meaning and appropriate response IL(02) and ILC(03) are not used in pairs. Correct the program so that each IL(02) has a unique ILC(03). Although this error message will appear if more than one IL(02) is used with the same ILC(03), the program will be executed as written. Make sure your program is written as desired before proceeding. JMP(04) and JME(05) are not used in pairs. Make sure your program is written as desired before proceeding. If the displayed address is that of SBN(92), two different subroutines have been defined with the same subroutine number. Change one of the subroutine numbers or delete one of the subroutines. If the displayed address is that of RET(93), RET(93) has not been used properly. Check requirements for RET(93) and correct the program.
Level B Errors
551
User-defined Errors
Level C Errors
Message COIL DUPL
Section
Meaning and appropriate response
9-4
The same bit is being controlled (i.e., turned ON and/or OFF) by more than one instruction (e.g., OUT, OUT NOT, DIFU(13), DIFD(14), KEEP(11), SFT(10)). Although this is allowed for certain instructions, check instruction requirements to confirm that the program is correct or rewrite the program so that each bit is controlled by only one instruction. JME(05) has been used with no JMP(04) with the same jump number. Add a JMP(04) with the same number or delete the JME(05) that is not being used. A subroutine exists that is not called by SBS(91). Program a subroutine call in the proper place, or delete the subroutine if it is not required.
! Caution
Expansion instructions (those assigned to function codes 17, 18, 19, 47, 48, 60 to 69, 87, 88, and 89) are not subject to program checks. Program checks also do not cover DM 1024 to DM 6143 for PCs that do not support this part of the DM area. Data will not be written even if these areas are specified and data read from these areas will always be 0000.
9-4
User-defined Errors
There are four instructions that the user can use to define his own errors or messages. These instructions are used to send messages to the Programming Console connected to the PC, cause a non-fatal or a fatal error.
MESSAGE MSG(46)
MSG(46) is used to display a message on the Programming Console. The message, which can be up to 16 characters long, is displayed when the instructions execution condition is ON. Refer to page 497 for details. FAL(06) is an instruction that causes a non-fatal error. Refer to page 385 for details. The following will occur when an FAL(06) instruction is executed: 1. The ERR/ALM indicator on the CPU Unit will flash. PC operation will continue. 2. The instructions 2-digit BCD FAL number (01 to 99) will be written to SR 25300 to SR 25307. 3. The FAL number will be recorded in the PCs error log area. The time of occurrence will also be recorded in CPM2A PCs and CPM2C PCs that are equipped with an internal clock. The FAL numbers can be set arbitrarily to indicate particular conditions. The same number cannot be used as both an FAL number and an FALS number. To clear an FAL error, correct the cause of the error, execute FAL 00, and then clear the error using the Programming Console. FALS(07) is an instruction that causes a fatal error. Refer to page 385 for details. The following will occur when an FALS(07) instruction is executed: 1. Program execution will be stopped and outputs will be turned OFF. 2. The ERR/ALM indicator on the CPU Unit will be lit. 3. The instructions 2-digit BCD FALS number (01 to 99) will be written to SR 25300 to SR 25307. 4. The FALS number will be recorded in the PCs error log area. The time of occurrence will also be recorded in CPM2A PCs and CPM2C PCs that are equipped with an internal clock. The FALS numbers can be set arbitrarily to indicate particular conditions. The same number cannot be used as both an FAL number and an FALS number. To clear an FALS error, switch the PC to PROGRAM Mode, correct the cause of the error, and then clear the error using the Programming Console.
552
Operating Errors
Section
9-5
9-5
Operating Errors
There are two kinds of operating errors, non-fatal and fatal. PC operation will continue after a non-fatal error occurs, but operation will be stopped if a fatal error occurs. ! Caution Investigate all errors, whether fatal or not. Remove the cause of the error as soon as possible and restart the PC. Refer to the CPM1 Operation Manual, CPM2A Operation Manual, or CPM2C Operation Manual for hardware information and Programming Console operations related to errors. Refer to the SSS Operation Manual for SSS operations related to errors.
9B
F8
Note ** is 01 to 99 or 9B.
553
Operating Errors
Section
9-5
NO END INST I/O BUS ERR (See note 1.) I/O UNIT OVER (See note 1.) SYS FAIL FALS** (See note 2.)
F0 C0
An error has occurred during data transfer between the CPU Unit and an Expansion Unit or Expansion I/O Unit. Check the Units connecting cable. E1 Too many Expansion Units or Expansion I/O Units have been connected. Check the PC configuration. 01 to 99 A FALS(07) instruction has been executed in the program. Check the FALS number to determine the conditions that caused execution, correct the cause, and clear the error. 9F The cycle time has exceeded the FALS 9F Cycle Time Monitoring Time (DM 6618). Check the cycle time and adjust the Cycle Time Monitoring Time if necessary.
Note
None
554
Error Log
Section
9-6
9-6
Error Log
The error log function registers the error code of any fatal or non-fatal error that occurs in the PC. The date and time at which the error occurred are registered along with the error code. Refer to page 553 for error codes.
to
Error Log Storage Methods The error log storage method is set in the PC Setup (DM 6655). Set any of the following methods. 1, 2, 3... 1. You can store the most recent 10 error log records and discard older records. This is achieved by shifting the records as shown below so that the oldest record (record 0) is lost whenever a new record is generated.
Lost Error log record 1 Error log record 2 All records shifted Error log record 6 Error log record 7 New record added
2. You can store only the first 10 error log records, and ignore any subsequent errors beyond those 10. 3. You can disable the log so that no records are stored. The default setting is the first method. Refer to Error Log Settings on page 21 for details on the PC Setup for the error log. Clearing the Error Log To clear the entire error log, turn ON SR 25214 from a Programming Device. (After the error log has been cleared, SR 25214 will turn OFF again automatically.) CPM2A/CPM2C Error Log Area
DM 2000 DM 2021 DM 2022 DM 2023 Error log pointer Error log record 1 (3 words used.)
In CPM2A/CPM2C PCs, the error log is stored in DM 2000 through DM 2021. Up to 7 error records can be stored.
Indicates the number of records stored in the log (0 to 7). A 0 indicates no records. Each error log record is configured as follows: 15 8 7 Leading word Leading word + 1 Leading word + 2 Error classification Min Day Error code Sec Hour
to
555
Error Log
Section
9-6
Note An error record with an error code of 00 will be stored in the error log for power interruptions. Error Log Storage Methods The error log storage method is set in the PC Setup (DM 6655). Set any of the following methods. 1, 2, 3... 1. You can store the most recent 7 error log records and discard older records. This is achieved by shifting the records as shown below so that the oldest record (record 0) is lost whenever a new record is generated.
Lost Error log record 1 Error log record 2 All records shifted Error log record 6 Error log record 7 New record added
2. You can store only the first 7 error log records, and ignore any subsequent errors beyond those 7. 3. You can disable the log so that no records are stored. The default setting is the first method. Refer to Error Log Settings on page 21 for details on the PC Setup for the error log. Clearing the Error Log To clear the entire error log, turn ON SR 25214 from a Programming Device. (After the error log has been cleared, SR 25214 will turn OFF again automatically.) SRM1 Error Log Area
DM2000 DM2001 DM2002 DM2003 Error log pointer Error log record 1
to
Error Log Storage Methods The error log storage method is set in the PC Setup (DM 6655). Set any of the following methods. 1, 2, 3... 1. You can store the most recent 7 error log records and discard older records. This is achieved by shifting the records as shown below so that the oldest record (record 0) is lost whenever a new record is generated.
Lost Error log record 1 Error log record 2 All records shifted Error log record 6 Error log record 7 New record added
2. You can store only the first 7 error log records, and ignore any subsequent errors beyond those 7.
556
Troubleshooting Flowcharts
Section
9-8
3. You can disable the log so that no records are stored. The default setting is the first method. Refer to Error Log Settings on page 21 for details on the PC Setup for the error log. Clearing the Error Log To clear the entire error log, turn ON SR 25214 from a Programming Device. (After the error log has been cleared, SR 25214 will turn OFF again automatically.)
9-7
9-8
Troubleshooting Flowcharts
The troubleshooting flowcharts are available in the Operation Manuals. Refer to 5-6 Troubleshooting Flowcharts in the CPM1 Operation Manual. Refer to 5-6 Troubleshooting Flowcharts in the CPM1A Operation Manual. Refer to 5-5 Troubleshooting Flowcharts in the CPM2A Operation Manual. Refer to 5-5 Troubleshooting Flowcharts in the CPM2C Operation Manual. Refer to 5-6 Troubleshooting Flowcharts in the SRM1 Operation Manual.
CPM1 Flowcharts CPM1A Flowcharts CPM2A Flowcharts CPM2C Flowcharts SRM1 Flowcharts
557
Appendix A
Programming Instructions
A PC instruction is input either by pressing the corresponding Programming Console key(s) (e.g., LD, AND, OR, NOT) or by using function codes. To input an instruction with its function code, press FUN, the function code, and then WRITE. Refer to the pages listed programming and instruction details.
Code Mnemonic AND AND LD AND NOT CNT LD LD NOT OR OR LD OR NOT OUT OUT NOT AND AND LOAD AND NOT COUNTER LOAD LOAD NOT OR OR LOAD OR NOT OUTPUT OUTPUT NOT Name Function Logically ANDs status of designated bit with execution condition. Logically ANDs results of preceding blocks. Logically ANDs inverse of designated bit with execution condition. A decrementing counter. Used to start instruction line with the status of the designated bit or to define a logic block for use with AND LD and OR LD. Used to start instruction line with inverse of designated bit. Logically ORs status of designated bit with execution condition. Logically ORs results of preceding blocks. Logically ORs inverse of designated bit with execution condition. Turns ON operand bit for ON execution condition; turns OFF operand bit for OFF execution condition. Turns operand bit OFF for ON execution condition; turns operand bit ON for OFF execution condition (i.e., inverts operation). Turns the operand bit OFF when the execution condition is ON, and does not affect the status of the operand bit when the execution condition is OFF. Turns the operand bit ON when the execution condition is ON, and does not affect the status of the operand bit when the execution condition is OFF. ON-delay (decrementing) timer operation. Nothing is executed and program moves to next instruction. Required at the end of the program. If interlock condition is OFF, all outputs are turned OFF and all timer PVs reset between this IL(02) and the next ILC(03). Other instructions are treated as NOP; counter PVs are maintained. If j p condition is OFF, all instructions between JMP(04) jump , ( ) and th corresponding JME(05) are i d the di ignored. d Generates a non-fatal error and outputs the designated FAL number to the Programming Console. Generates a fatal error and outputs the designated FALS number to the Programming Console. When used with a control bit, defines the start of a new step and resets the previous step. When used without N, defines the end of step execution. Used with a control bit to indicate the end of the step, reset the step, and start the next step. Creates a bit shift register. Defines a bit as a latch controlled by set and reset inputs. Increases or decreases PV by one whenever the increment input or decrement input signals, respectively, go from OFF to ON. Turns ON the designated bit for one cycle on the rising edge of the input signal. Page 376 377 376 394 376 376 376 377 376 377 377
RSET
RESET
378
SET
SET
378
00 01 02 03 04 05 06 07 08
TIMER NO OPERATION END INTERLOCK INTERLOCK CLEAR JUMP JUMP END FAILURE ALARM AND RESET SEVERE FAILURE ALARM STEP DEFINE
389 381 381 381 381 383 383 385 385 385
09 10 11 12
13
DIFU
380
559
Programming Instructions
Code 14 15 16 17 to 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 Mnemonic DIFD TIMH (@)WSFT Name DIFFERENTIATE DOWN HIGH-SPEED TIMER WORD SHIFT Function Turns ON the bit for one cycle on the trailing edge. A high-speed, ON-delay (decrementing) timer.
Appendix A
Page 380 390 405 160 Compares the contents of two words and outputs result to GR, EQ, and LE Flags. Copies source data (word or constant) to destination word. Inverts source data (word or constant) and then copies it to destination word. Converts four-digit, BCD data in source word into 16-bit binary data, and outputs converted data to result word. Converts binary data in source word into BCD, and outputs converted data to result word. Shifts each bit in single word of data one bit to left, with CY. Shifts each bit in single word of data one bit to right, with CY. Rotates bits in single word of data one bit to left, with CY. Rotates bits in single word of data one bit to right, with CY. Inverts bit status of one word of data. Adds two four-digit BCD values and content of CY, and outputs result to specified result word. Subtracts a four-digit BCD value and CY from another fourdigit BCD value and outputs result to the result word. Multiplies two four-digit BCD values and outputs result to specified result words. Divides four-digit BCD dividend by four-digit BCD divisor and outputs result to specified result words. Logically ANDs two 16-bit input words and sets corresponding bit in result word if corresponding bits in input words are both ON. Logically ORs two 16-bit input words and sets corresponding bit in result word if one or both of corresponding bits in input data are ON. Exclusively ORs two 16-bit input words and sets bit in result word when corresponding bits in input words differ in status. Exclusively NORs two 16-bit input words and sets bit in result word when corresponding bits in input words are same in status. Increments four-digit BCD word by one. Decrements four-digit BCD word by one. Sets carry flag (i.e., turns CY ON). Clears carry flag (i.e., turns CY OFF). Displays a 16-character message on the Programming Console display. Adds two four-digit hexadecimal values and content of CY, and outputs result to specified result word. Subtracts a four-digit hexadecimal value and CY from another four-digit hexadecimal value and outputs result to the result word. Multiplies two four-digit hexadecimal values and outputs result to specified result words. Divides four-digit hexadecimal dividend by four-digit hexadecimal divisor and outputs result to specified result words. 432 411 412 439 440 405 406 406 407 479 457 458 460 461 480
Shifts data between starting and ending words in word units, writing zeros into starting word.
For expansion instructions. CMP (@)MOV (@)MVN (@)BIN (@)BCD (@)ASL (@)ASR (@)ROL (@)ROR (@)COM (@)ADD (@)SUB (@)MUL (@)DIV (@)ANDW COMPARE MOVE MOVE NOT BCD TO BINARY BINARY TO BCD ARITHMETIC SHIFT LEFT ARITHMETIC SHIFT RIGHT ROTATE LEFT ROTATE RIGHT COMPLEMENT BCD ADD BCD SUBTRACT BCD MULTIPLY BCD DIVIDE LOGICAL AND
35
(@)ORW
LOGICAL OR
481
36 37
(@)XORW (@)XNRW
481 482
38 39 40 41 46 47 & 48 50 51
52 53
(@)MLB (@)DVB
470 470
560
Programming Instructions
Code 54 55 56 57 58 Mnemonic (@)ADDL (@)SUBL (@)MULL (@)DIVL (@)BINL Name DOUBLE BCD ADD DOUBLE BCD SUBTRACT DOUBLE BCD MULTIPLY DOUBLE BCD DIVIDE DOUBLE BCD TO DOUBLE BINARY DOUBLE BINARY TO DOUBLE BCD Function
Appendix A
Page 463 464 466 466 440
Adds two eight-digit values (2 words each) and content of CY, and outputs result to specified result words. Subtracts an eight-digit BCD value and CY from another eight-digit BCD value and outputs result to the result words. Multiplies two eight-digit BCD values and outputs result to specified result words. Divides eight-digit BCD dividend by eight-digit BCD divisor and outputs result to specified result words. Converts BCD value in two consecutive source words into binary and outputs converted data to two consecutive result words. (CPM2A only) Converts binary value in two consecutive source words into BCD and outputs converted data to two consecutive result words. (CPM2A only) Moves content of several consecutive source words to consecutive destination words. Copies content of one word or constant to several consecutive words. Exchanges contents of two different words. Left shifts data between starting and ending words by one digit (four bits). Right shifts data between starting and ending words by one digit (four bits). Converts up to four hexadecimal digits in source word into decimal values from 0 to 15 and turns ON, in result word(s), bit(s) whose position corresponds to converted value. Determines position of highest ON bit in source word(s) and turns ON corresponding bit(s) in result word. Converts hexadecimal values from source word to data for seven-segment display. Moves one word of source data to destination word whose address is given by destination base word plus offset. Extracts data from source word and writes it to destination word. Transfers designated bit of source word or constant to designated bit of destination word. Moves hexadecimal content of specified four-bit source digit(s) to specified destination digit(s) for up to four digits. Shifts data in specified word or series of words to either left or right. Compares four-digit hexadecimal value with values in table consisting of 16 words. Converts hexadecimal values from the source word to eightbit ASCII code starting at leftmost or rightmost half of starting destination word. Calls and executes subroutine N. Marks start of subroutine N. Marks the end of a subroutine and returns control to main program. Refreshes all I/O words between the start and end words. Cannot be used with the SRM1(-V2). Calls and executes a subroutine replacing I/O words.
59
(@)BCDL
441
60 to 69 70 71 73 74 75 76
For expansion instructions. (@)XFER (@)BSET (@)XCHG (@)SLD (@)SRD (@)MLPX BLOCK TRANSFER BLOCK SET DATA EXCHANGE ONE DIGIT SHIFT LEFT ONE DIGIT SHIFT RIGHT 4-TO-16 DECODER
77 78 80 81 82 83 84 85 86
16-TO-4 ENCODER 7-SEGMENT DECODER SINGLE WORD DISTRIBUTE DATA COLLECT MOVE BIT MOVE DIGIT REVERSIBLE SHIFT REGISTER TABLE COMPARE ASCII CONVERT
87 to 89 91 92 93 97 99
For expansion instructions. (@)SBS SBN RET (@)IORF (@)MCRO SUBROUTINE ENTRY SUBROUTINE DEFINE RETURN I/O REFRESH MACRO
561
Programming Instructions
Appendix A
Expansion Instructions
The following table shows the instructions that can be treated as expansion instructions in the CPM2A, CPM2C, and SRM1(-V2) PCs. The default function codes are given for instructions that have codes assigned by default.
Code Mnemonic 17 (@)ASFT Name ASYNCHRONOUS SHIFT REGISTER RECEIVE TRANSMIT DOUBLE COMPARE MODE CONTROL Function Creates a shift register that exchanges the contents of adjacent words when one of the words is zero and the other is not. Receives data via a communications port. Sends data via a communications port. Compares two eight-digit hexadecimal values. Starts and stops counter operation, compares and changes counter PVs, and stops pulse output. Reads counter PVs and status data for the highspeed counter. Compares counter PVs and generates a direct table or starts operation. Outputs pulses at the specified frequency (10 Hz to 50 KHz in 10 Hz units). The output frequency can be changed while pulses are being output. Outputs the specified number of pulses at the specified frequency. The pulse output cannot be stopped until the specified number of pulses have been output. Performs a scaling conversion on the calculated value. Use the Programming Console or SSS to access this instruction for the SRM1(-V2). 67 68 69 89 --(@)BCNT (@)BCMP (@)STIM (@)INT (@)ACC BIT COUNTER BLOCK COMPARE INTERVAL TIMER INTERRUPT CONTROL ACCELERATION CONTROL AVERAGE VALUE Counts the total number of bits that are ON in the specified block of words. Judges whether the value of a word is within 16 ranges (defined by lower and upper limits). Controls interval timers used to perform scheduled interrupts. Performs interrupt control, such as masking and unmasking the interrupt bits for I/O interrupts. Together with PULS(), ACC() controls the acceleration and/or deceleration of pulses output from port 1 or 2. Adds the specified number of hexadecimal words and computes the mean value. Rounds off to 4 digits past the decimal point. CPU Units All Page 410
47 48 60 61
62 63 64
65
(@)PULS
SET PULSES
CPM2A/ CPM2C
487
66
(@)SCL
SCALING
All (But, Version 2 only for SRM1) All All All CPM2A/ CPM2C CPM2A/ CPM2C CPM2A/ CPM2C All All CPM2A/ CPM2C CPM2A/ CPM2C CPM2A/ CPM2C All (But, Version 2 only for SRM1)
421
---
AVG
476
-------------
FCS CALCULATE
Checks for errors in data transmitted by a Host Link command. ASCII-TO-HEXADECIMAL Converts ASCII data to hexadecimal data. SECONDS TO HOURS FIND MAXIMUM FIND MINIMUM 2S COMPLEMENT Converts second data to hour and minute data. Finds the maximum value in specified data area and outputs that value to another word. Finds the minimum value in specified data area and outputs that value to another word. Converts the four-digit hexadecimal content of the source word to its 2s complement and outputs the result to R. Use the Programming Console or SSS to access this instruction for the SRM1(-V2).
562
Programming Instructions
Code Mnemonic --PID Name PID CONTROL Function Performs PID control based on the specified parameters. Use the Programming Console or SSS to access this instruction for the SRM1(-V2). ----------(@)PWM (@)SCL2 (@)SCL3 (@)SEC (@)SRCH PULSE WITH VARIABLE DUTY RATIO SIGNED BINARY TO BCD SCALING BCD TO SIGNED BINARY SCALING HOURS TO SECONDS DATA SEARCH Outputs pulses with the specified duty ratio (0% to 99%) from port 1 or 2. Linearly converts a 4-digit signed hexadecimal value to a 4-digit BCD value. Linearly converts a 4-digit BCD value to a 4-digit signed hexadecimal value. Converts hour and minute data to second data. Searches the specified range of memory for the specified data. Outputs the word address(es) of words in the range that contain the data. Changes the communications parameters in the PC Setup for a specified port. Computes the sum of the contents of the words in the specified range of memory. Multiplies an input pulse frequency by a fixed scaling factor and outputs pulses from the specified output bit at the resulting frequency.
Appendix A
CPU Units All (But, Version 2 only for SRM1) CPM2A/ CPM2C CPM2A/ CPM2C CPM2A/ CPM2C CPM2A/ CPM2C CPM2A/ CPM2C All CPM2A/ CPM2C CPM2A/ CPM2C CPM2A/ CPM2C CPM2A/ CPM2C All (But, Version 2 only for SRM1) CPM2A/ CPM2C 438 494 423 424 453 471 Page 426
-------
CHANGE RS-232C SETUP SUM CALCULATE SYNCHRONIZED PULSE CONTROL LONG TIMER
-------
A decrementing ON-delay timer with SV of up to 99,990 s VERY HIGH-SPEED A high-speed, decrementing ON-delay timer that TIMER times in 1-ms units AREA RANGE COMPARE Compares a word to a range defined by lower and upper limits and outputs the result to the GR, EQ, and LE flags. Use the Programming Console or SSS to access this instruction for the SRM1(-V2). Compares an 8-digit value to a range defined by lower and upper limits and outputs the result to the GR, EQ, and LE flags.
---
ZCPL
563
Appendix B
Error and Arithmetic Flag Operation
The following table shows the instructions that affect the ER, CY, GT, LT and EQ flags. In general, ER indicates that operand data is not within requirements. CY indicates arithmetic or data shift results. GT indicates that a compared value is larger than some standard, LT that it is smaller, and EQ, that it is the same. EQ also indicates a result of zero for arithmetic operations. Refer to Section 7 Instruction Set for details. Vertical arrows in the table indicate the flags that are turned ON and OFF according to the result of the instruction. Although ladder diagram instructions,TIM, and CNT are executed when ER is ON, other instructions with a vertical arrow under the ER column are not executed if ER is ON. All of the other flags in the following table will also not operate when ER is ON. Instructions not shown do not affect any of the flags in the table. Although only the non-differentiated form of each instruction is shown, differentiated instructions affect flags in exactly the same way. The ER, CY, GT, LT and EQ Flags are turned OFF when END(01) is executed, so their status cannot be monitored with a Programming Device. The status of the ER, CY, GT, LT and EQ Flags is affected by instruction execution and will change each time an instruction that affects them is executed. Differentiated instructions are executed only once when their execution condition changes (ON to OFF or OFF to ON) and are not executed again until the next specified change in their execution condition. The status of the ER, CY, GT, LT and EQ Flags is thus affected by a differentiated instruction only when the execution condition changes and is not affected during scans when the instruction is not executed, i.e., when the specified change does not occur in the execution condition. When a differentiated instruction is not executed, the status of the ER, CY, GT, LT and EQ Flags will not change and will maintain the status produced by the last instruction that was executed.
Instructions TIM CNT END(01) STEP(08) SNXT(09) CNTR(12) TIMH(15) WSFT(16) CMP(20) MOV(21) MVN(22) BIN(23) BCD(24) ASL(25) ASR(26) ROL(27) ROR(28) COM(29) ADD(30) SUB(31) Unaffected Unaffected OFF OFF Unaffected OFF Unaffected OFF Unaffected OFF Unaffected OFF Unaffected OFF Unaffected 25503 (ER) 25504 (CY) Unaffected 25505 (GR) Unaffected 25506 (EQ) Unaffected 25507 (LE) Unaffected 25402 (N) Unaffected Page 389 394 381 385 385 395 390 405 432 411 412 439 440 405 406 406 407 479 Unaffected 457 458
Unaffected
OFF Unaffected
Unaffected
Unaffected
Unaffected
565
Appendix B
25402 (N) Unaffected Page 460 461 480 481 481 482 483 483 Unaffected 457 457 497 467 468 470 470 463 464 466 466 440 441 413 414 Unaffected 415 408 408 442 444 446 415 417 419 420 409 433 449 484 486 Unaffected Unaffected
Unaffected
Unaffected
Unaffected Unaffected
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected Unaffected
566
Appendix B
Unaffected
Unaffected
Unaffected
Unaffected
Unaffected Unaffected
Unaffected
Unaffected
Unaffected Unaffected
Unaffected
Note *Depending on the results, NEG() may also affect the status of the underflow flag (SR 25405).
567
Appendix C
Memory Areas CPM1/CPM1A Memory Areas
Memory Area Structure
The following memory areas can be used with the CPM1/CPM1A.
Data area IR area1 Input area Output area Work area SR area TR area HR area2 AR area2 LR area1 Timer/Counter area2 DM area Read/write2 Words IR 000 to IR 009 (10 words) IR 010 to IR 019 (10 words) IR 200 to IR 231 (32 words) SR 232 to SR 255 (24 words) --Bits IR 00000 to IR 00915 (160 bits) IR 01000 to IR 01915 (160 bits) IR 20000 to IR 23115 (512 bits) SR 23200 to SR 25515 (384 bits) TR 0 to TR 7 (8 bits) HR 00 to HR 19 HR 0000 to HR 1915 (20 words) (320 bits) AR 00 to AR 15 AR 0000 to AR 1515 (16 words) (256 bits) LR 00 to LR 15 LR 0000 to LR 1515 (16 words) (256 bits) TC 000 to TC 127 (timer/counter numbers)3 DM 0000 to DM 0999 --DM 1022 to DM 1023 (1,002 words) DM 1000 to DM 1021 --(22 words) Function These bits can be allocated to the external I/O terminals. /O e as
Work bits can be freely used within the program. These bits serve specific functions such as flags and control bits. These bits are used to temporarily store ON/OFF status at program branches. These bits store data and retain their ON/ OFF status when power is turned off. These bits serve specific functions such as flags and control bits. Used for a 1:1 data link with another PC. The same numbers are used for both timers and counters. DM area data can be accessed in word units only. Word values are retained when the power is turned off. Used to store the error code of errors that occur. These words can be used as ordinary read/write DM when the error log function isnt being used. Cannot be overwritten from program. Used to store various parameters that control PC operation.
Error log2
Read-only4 PC Setup4
Note 1. IR and LR bits that are not used for their allocated functions can be used as work bits. 2. The contents of the HR area, AR area, Counter area, and read/write DM area are backed up by a capacitor. The backup time varies with the ambient temperature, but at 25_C, the capacitor will back up memory for 20 days. If the power supply is off longer than the backup time, memory contents will be cleared and AR1314 will turn ON. (This flag turns ON when data can no longer be retained by the built-in capacitor.) Refer to 2-1-2 Characteristics in the CPM1 Operation Manual for a graph showing the backup time vs. temperature. 3. When accessing a PV, TC numbers are used as word data; when accessing Completion Flags, they are used as bit data. 4. Data in DM 6144 to DM 6655 cannot be overwritten from the program, but they can be changed from a Programming Device.
SR Area
These bits mainly serve as flags related to CPM1/CPM1A operation or contain present and set values for various functions. The functions of the SR area are explained in the following table. Note Read-only words and bits can be read as status in controller PC operation, but they cannot be written from the ladder program. Bits and words that are Not used are also read-only.
569
Memory Areas
Word(s) SR 232 to SR 235 SR 236 to SR 239 SR 240 Bit(s) 00 to 15 Function Macro Function Input Area Contains the input operands for MCRO(99). (Can be used as work bits when MCRO(99) is not used.) Macro Function Output Area Contains the output operands for MCRO(99). (Can be used as work bits when MCRO(99) is not used.) Input Interrupt 0 Counter Mode SV SV when input interrupt 0 is used in counter mode (4 digits hexadecimal). (Can be used as work bits when input interrupt 0 is not used in counter mode.) Input Interrupt 1 Counter Mode SV SV when input interrupt 1 is used in counter mode (4 digits hexadecimal). (Can be used as work bits when input interrupt 1 is not used in counter mode.) Input Interrupt 2 Counter Mode SV SV when input interrupt 2 is used in counter mode (4 digits hexadecimal). (Can be used as work bits when input interrupt 2 is not used in counter mode.) Input Interrupt 3 Counter Mode SV SV when input interrupt 3 is used in counter mode (4 digits hexadecimal). (Can be used as work bits when input interrupt 3 is not used in counter mode.) Input Interrupt 0 Counter Mode PV Minus One Counter PV1 when input interrupt 0 is used in counter mode (4 digits hexadecimal). Input Interrupt 1 Counter Mode PV Minus One Counter PV1 when input interrupt 1 is used in counter mode (4 digits hexadecimal). Input Interrupt 2 Counter Mode PV Minus One Counter PV1 when input interrupt 2 is used in counter mode (4 digits hexadecimal). Input Interrupt 3 Counter Mode PV Minus One Counter PV1 when input interrupt 3 is used in counter mode (4 digits hexadecimal). High-speed Counter PV Area (Can be used as work bits when the high-speed counter is not used.) Analog Setting 0 Used to store the 4-digit BCD set value (0000 to 0200) from analog control 0. Analog Setting 1 Used to store the 4-digit BCD set value (0000 to 0200) from analog control 1.
Appendix C
Read/ write Read/ write Page 157
00 to 15
00 to 15
81
SR 241
00 to 15
SR 242
00 to 15
SR 243
00 to 15
SR 244
00 to 15
Readonly
82
SR 245
00 to 15
SR 246
00 to 15
SR 247
00 to 15
00 to 15 00 to 15 00 to 15
87 150
570
Memory Areas
Word(s) SR 252 Bit(s) 00 01 to 07 08 High-speed Counter Reset Bit Not used. Peripheral Port Reset Bit Turn ON to reset peripheral port. (Not valid when Programming Device is connected.) Automatically turns OFF when reset is complete. Function
Appendix C
Read/ write Read/ write Read/ write Page 88
272
09 10
11
Not used. Read/ PC Setup Reset Bit write Turn ON to initialize PC Setup (DM 6600 through DM 6655). Automatically turns OFF again when reset is complete. Only effective if the PC is in PROGRAM mode. Forced Status Hold Bit (See note.) OFF: The forced status of bits that are forced set/reset is cleared when switching between PROGRAM mode and MONITOR mode. ON: The status of bits that are forced set/reset are maintained when switching between PROGRAM mode and MONITOR mode. The status of this bit can be maintained when PC power turns off by using the PC Setup. I/O Hold Bit (See note.) OFF: IR and LR bits are reset when starting or stopping operation. ON: IR and LR bit status is maintained when starting or stopping operation. The status of this bit can be maintained when PC power turns off by using the PC Setup. Not used. Error Log Reset Bit Turn ON to clear error log. Automatically turns OFF again when operation is complete. Not used. FAL Error Code The error code (a 2-digit number) is stored here when an error occurs. The FAL number is stored here when FAL(06) or FALS(07) is executed. This word is reset (to 00) by executing a FAL 00 instruction or by clearing the error from a Programming Device. Not used. Cycle Time Overrun Flag Turns ON when a cycle time overrun occurs (i.e., when the cycle time exceeds 100 ms). Not used. Always ON Flag Always OFF Flag First Cycle Flag Turns ON for 1 cycle at the start of operation. 1-minute clock pulse (30 seconds ON; 30 seconds OFF) 0.02-second clock pulse (0.01 second ON; 0.01 second OFF) Negative (N) Flag Not used. Differential Monitor Complete Flag Turns ON when differential monitoring is complete. STEP(08) Execution Flag Turns ON for 1 cycle only at the start of process based on STEP(08). Not used. Read/ write
17
12
17
13 14
555
SR 253
15 00 to 07
Readonly
385
08 09
Readonly
---
10 to 12 13 14 15 SR 254 00 01 02 03 to 05 06 07 08 to 15
Readonly l
-------------
Reado y only
159 385
571
Memory Areas
Word(s) SR 255 Bit(s) 00 01 02 03 04 05 06 Function 0.1-second clock pulse (0.05 second ON; 0.05 second OFF) 0.2-second clock pulse (0.1 second ON; 0.1 second OFF) 1.0-second clock pulse (0.5 second ON; 0.5 second OFF) Instruction Execution Error (ER) Flag Turns ON when an error occurs during execution of an instruction. Carry (CY) Flag Turns ON when there is a carry in the results of an instruction execution. Greater Than (GR) Flag Turns ON when the result of a comparison operation is greater. Equals (EQ) Flag Turns ON when the result of a comparison operation is equal, or when the result of an instruction execution is 0. Less Than (LE) Flag Turns ON when the result of a comparison operation is less. Not used.
Appendix C
Read/ write Readl only Page ---------------
07 08 to 15
---
Note DM 6601 in the PC Setup can be set to maintain the previous status of the I/O Hold Bit (SR 25212) and the I/O Hold Bit (SR 25212) when power is turned OFF. If power is left OFF for longer than the backup time, however, status may be cleared. For details regarding the backup time, refer to the CPM1A or CPM1 Operation Manual. Refer to 1-1-2 CPM1/CPM1A PC Setup Settings for details on the PC Setup.
AR Area
These bits mainly serve as flags related to CPM1/CPM1A operation. These bits retain their status even after the CPM1/CPM1A power supply has been turned off or when operation begins or stops.
Word(s) AR 00, AR 01 AR 02 Bit(s) 00 to 15 00 01 02 03 to 07 08 to 11 12 to 15 AR 03 to AR 07 AR 08 00 to 15 00 to 07 08 to 11 Not used. Expansion Unit Error Flag for 1st Unit Expansion Unit Error Flag for 2nd Unit (Not used by CPM1 CPU Units without -V1 suffix.) Expansion Unit Error Flag for 3rd Unit (Not used by CPM1 CPU Units without -V1 suffix.) Not used. Number of I/O Units Connected Not used. Not used. Not used. Programming Device Error Code 0: Normal completion 1: Parity error 2: Frame error 3: Overrun error Programming Device Error Flag Not used. Not used. Power-off Counter (4 digits BCD) This is the count of the number of times that the power has been turned off. To clear the count, write 0000 from a Programming Device. --These flags turn ON g when there is an error in h h i i the corresponding Unit. --Function Page
---
273
12 13 to 15 AR 09 AR 10 00 to 15 00 to 15
572
Memory Areas
Word(s) AR 11 Bit(s) 00 to 07 Function High-speed Counter Range Comparison Flags 00 ON: Counter PV is within comparison range 1 01 ON: Counter PV is within comparison range 2 02 ON: Counter PV is within comparison range 3 03 ON: Counter PV is within comparison range 4 04 ON: Counter PV is within comparison range 5 05 ON: Counter PV is within comparison range 6 06 ON: Counter PV is within comparison range 7 07 ON: Counter PV is within comparison range 8 Not used. Pulse Output Status ON: Stopped. OFF: Pulses being output. Not used.
Appendix C
Page 90
08 to 14 15
---
AR 12 AR 13
00 to 15 00
553 Power-up PC Setup Error Flag Turns ON when there is an error in DM 6600 to DM 6614 (the part of the PC Setup area that is read at power-up). Start-up PC Setup Error Flag Turns ON when there is an error in DM 6615 to DM 6644 (the part of the PC Setup area that is read at the beginning of operation). RUN PC Setup Error Flag Turns ON when there is an error in DM 6645 to DM 6655 (the part of the PC Setup area that is always read). Not used. Long Cycle Time Flag Turns ON if the actual cycle time is longer than the cycle time set in DM 6619. Not used. Memory Area Specification Error Flag Turns ON when a non-existent data area address is specified in the program. Flash Memory Error Flag Turns ON when there is an error in flash memory. Read-only DM Error Flag (See note 3.) Turns ON when a checksum error occurs in the read-only DM (DM 6144 to DM 6599) and that area is initialized. PC Setup Error Flag Turns ON when a checksum error occurs in the PC Setup area. Program Error Flag Turns ON when a checksum error occurs in the program memory (UM) area, or when an improper instruction is executed. Not used. Data Save Error Flag Turns ON when power is turned on if data could not be saved with the built-in capacitor. Data is saved in the following areas with the built-in capacitor: DM area (Read/write-capable: DM 0000 to 0999 and DM 1022 to 1023) HR area (HR 00 to 19) Counter area (CNT 000 to 127) SR area, word 252, bits 11, 12 (when PC Setup in DM 6601 is set to maintain status) AR area, word 10 (power-off counter) Operation mode (when PC Setup in DM 6600 is set to continue mode last used before power failure) If data could not be saved in the above areas: The DM, error log, HR, counter, SR (word 252, bits 11 and 12), and AR (word 10) areas will be cleared and the operating mode will go into PROGRAM mode if DM 0000 is set to continue mode last used before power failure or if DM6604 is set to generate an error. ---
01
02
03, 04 05 06, 07 08 09 10
----554
11 12
---
13 14
---
15
(For details regarding the holding time, refer to the CPM1A Operation Manual.) Not used.
573
Memory Areas
Word(s) AR 14 Bit(s) 00 to 15 Function
Appendix C
Page 537
Maximum Cycle Time (4 digits BCD) (See note 1.) The longest cycle time since the beginning of operation is stored. It is cleared at the beginning, and not at the end, of operation. The units can be any of the following, depending on the setting of in DM 6618. Default: 0.1 ms; 10 ms setting: 0.1 ms; 100 ms setting: 1 ms; 1 s setting: 10 ms Current Cycle Time (4 digits BCD) (See note 1.) The most recent cycle time during operation is stored. The Current Cycle Time is not cleared when operation stops. The units can be any of the following, depending on the setting of in DM 6618. Default: 0.1 ms; 10 ms setting: 0.1 ms; 100 ms setting: 1 ms; 1 s setting: 10 ms
AR 15
00 to 15
Note 1. The units will be as follows, depending on the unit setting for the cycle monitor time (DM 6618): Initial status: 0.1-ms unit When 10-ms unit is set: 0.1-ms unit When 100-ms unit is set: 1-ms unit When 1-s unit is set: 10-ms unit 2. Areas that cannot be used are cleared when the power is turned on. 3. The contents of AR 10 is backed up by the built-in capacitor. If power is left OFF for longer than the backup time, however, the contents may be cleared. For details regarding the backup time, refer to the CPM1A or CPM1 Operation Manual.
Work bits can be freely used within the program. These bits serve specific functions such as flags and control bits. These bits are used to temporarily store ON/OFF status at program branches. These bits store data and retain their ON/ OFF status when power is turned off. These bits serve specific functions such as flags and control bits. Used for a 1:1 data link with another PC. The same numbers are used for both timers and counters. DM area data can be accessed in word units only. Word values are retained when the power is turned off. Used to store the error code of errors that occur. These words can be used as ordinary read/write DM when the error log function isnt being used. Cannot be overwritten from program. Used to store various parameters that control PC operation.
SR 22800 to SR 25515 (448 bits) TR 0 to TR 7 (8 bits) HR 00 to HR 19 HR 0000 to HR 1915 (20 words) (320 bits) AR 00 to AR 23 AR 0000 to AR 2315 (24 words) (384 bits) LR 00 to LR 15 LR 0000 to LR 1515 (16 words) (256 bits) TC 000 to TC 255 (timer/counter numbers)3 DM 0000 to DM 1999 --DM 2022 to DM 2047 (2,026 words) DM 2000 to DM 2021 --(22 words)
Error log2
Read-only4 PC Setup4
574
Memory Areas
Appendix C
Note 1. IR and LR words that are not used for their allocated functions can be used as work words. 2. The contents of the HR area, AR area, Counter area, and read/write DM area are backed up by the CPU Units battery. If the battery is removed or fails, the data in these areas will be lost and reset to default values. (In CPM2C CPU Units without a battery, these areas are backed up by a capacitor. At 25_C, the capacitor will back up memory for 10 days.) 3. When a TC number is used as a word operand, it accesses the timer or counters PV; when used as a bit operand, it accesses the Completion Flag. 4. Data in DM 6144 to DM 6655 cannot be overwritten from the program, but they can be changed from a Programming Device. The program and data in DM 6144 to DM 6655 are backed up in flash memory.
SR Area
These bits mainly serve as flags related to CPM2A/CPM2C operation or contain present and set values for various functions. The functions of the SR area are explained in the following table. Note Read-only words and bits can be read as status in controller PC operation, but they cannot be written from the ladder program. Bits and words that are Not used are also read-only.
Word(s) SR 228, SR 229 Bit(s) 00 to 15 Read/ write ReadPulse Output PV 0 Contains the pulse output PV (16,777,215 to 16,777,215). SR 22915 acts as only the sign bit; a negative number is indicated when SR 22915 is ON. (The same PV data can be read immediately with PRV(62).) Only Pulse Output PV 0 is used for ACC(). Pulse Output PV 1 Contains the pulse output PV (16,777,215 to 16,777,215). SR 23115 acts as the sign bit; a negative number is indicated when SR 23115 is ON. (The same PV data can be read immediately with PRV(62).) Macro Function Input Area Contains the input operands for MCRO(99). (Can be used as work bits when MCRO(99) is not used.) Macro Function Output Area Contains the output operands for MCRO(99). (Can be used as work bits when MCRO(99) is not used.) Interrupt Input 00003 Counter Mode SV SV when interrupt input 00003 is used in counter mode (4 digits hexadecimal). (Can be used as work bits when interrupt input 00003 is not used in counter mode.) Interrupt Input 00004 Counter Mode SV SV when interrupt input 00004 is used in counter mode (4 digits hexadecimal). (Can be used as work bits when interrupt input 00004 is not used in counter mode.) Interrupt Input 00005 Counter Mode SV SV when interrupt input 00005 is used in counter mode (4 digits hexadecimal). (Can be used as work bits when interrupt input 00005 is not used in counter mode.) Interrupt Input 00006 Counter Mode SV SV when interrupt input 00006 is used in counter mode (4 digits hexadecimal). (Can be used as work bits when interrupt input 00006 is not used in counter mode.) (Input 00006 does not exist in CPM2C CPU Units with 10 I/O points.) 73 Function Page 106
SR 230, SR 231
00 to 15
00 to 15
Read/ write
157
00 to 15
00 to 15
SR 241
00 to 15
SR 242
00 to 15
SR 243
00 to 15
575
Memory Areas
Word(s) SR 244 Bit(s) 00 to 15 Function Interrupt Input 00003 Counter Mode PV Counter PV when interrupt input 00003 is used in counter mode (4 digits hexadecimal). Interrupt Input 00004 Counter Mode PV Counter PV when interrupt input 00004 is used in counter mode (4 digits hexadecimal). Interrupt Input 00005 Counter Mode PV Counter PV when interrupt input 00005 is used in counter mode (4 digits hexadecimal). Interrupt Input 00006 Counter Mode PV Counter PV when interrupt input 00006 is used in counter mode (4 digits hexadecimal). (Input 00006 does not exist in CPM2C CPU Units with 10 I/O points.) SR 248, SR 249 SR 250 SR 251 SR 252 00 to 15 00 to 15 00 to 15 00 01 to 03 04 05 06, 07 08 High-speed Counter PV Area (Can be used as work bits when the high-speed counter is not used.) Analog Setting 0 (CPM2A PCs only) Used to store the 4-digit BCD set value (0000 to 0200) from analog control 0. Analog Setting 1 (CPM2A PCs only) Used to store the 4-digit BCD set value (0000 to 0200) from analog control 1. High-speed Counter Reset Bit Not used. Pulse Output 0 PV Reset Bit Turn ON to clear the PV of pulse output 0. Pulse Output 1 PV Reset Bit Turn ON to clear the PV of pulse output 1. Not used. Peripheral Port Reset Bit Turn ON to reset the peripheral port. Automatically turns OFF when reset is complete. RS-232C Port Reset Bit Turn ON to reset the RS-232C port. Automatically turns OFF when reset is complete. PC Setup Reset Bit Turn ON to initialize PC Setup (DM 6600 through DM 6655). Automatically turns OFF again when reset is complete. Only effective if the PC is in PROGRAM mode. Forced Status Hold Bit (See note.) OFF: The forced status of bits that are forced set/reset is cleared when switching between PROGRAM mode and MONITOR mode. ON: The status of bits that are forced set/reset are maintained when switching between PROGRAM mode and MONITOR mode. The PC Setup can be set to maintain the status of this bit when the PC is turned off. I/O Hold Bit (See note.) OFF: IR and LR bits are reset when starting or stopping operation. ON: IR and LR bit status is maintained when starting or stopping operation. The PC Setup can be set to maintain the status of this bit when the PC is turned off. Not used. Error Log Reset Bit Turn ON to clear error log. Automatically turns OFF again when operation is complete. Not used.
Appendix C
Read/ write Readonly Page 75
SR 245
00 to 15
SR 246
00 to 15
SR 247
00 to 15
60 150
51
97
Read/ write
---
09
---
10
11
17
12
17
13 14
Read/ write
555
15
576
Memory Areas
Word(s) SR 253 Bit(s) 00 to 07 Function FAL Error Code The error code (a 2-digit number) is stored here when an error occurs. The FAL number is stored here when FAL(06) or FALS(07) is executed. This word is reset (to 00) by executing a FAL 00 instruction or by clearing the error from a Programming Device. Battery Error Flag Turns ON when the CPU Unit backup batterys voltage is too low. Cycle Time Overrun Flag Turns ON when a cycle time overrun occurs (i.e., when the cycle time exceeds 100 ms). Not used. Changing RS-232C Setup Flag Turns ON when the RS-232C ports settings are being changed. Always ON Flag Always OFF Flag First Cycle Flag Turns ON for 1 cycle at the start of operation. 1-minute clock pulse (30 seconds ON; 30 seconds OFF) 0.02-second clock pulse (0.01 second ON; 0.01 second OFF) Negative (N) Flag Not used. Overflow (OF) Flag Turns ON when an overflow occurs in a signed binary calculation. Underflow (UF) Flag Turns ON when an underflow occurs in a signed binary calculation. Differential Monitor Complete Flag Turns ON when differential monitoring is completed. STEP(08) Execution Flag Turns ON for 1 cycle only at the start of process based on STEP(08). Not used. 0.1-second clock pulse (0.05 second ON; 0.05 second OFF) 0.2-second clock pulse (0.1 second ON; 0.1 second OFF) 1.0-second clock pulse (0.5 second ON; 0.5 second OFF) Instruction Execution Error (ER) Flag Turns ON when an error occurs during execution of an instruction. Carry (CY) Flag Turns ON when there is a carry in the results of an instruction execution. Greater Than (GR) Flag Turns ON when the result of a comparison operation is greater. Equals (EQ) Flag Turns ON when the result of a comparison operation is equal, or when the result of an instruction execution is 0. Less Than (LE) Flag Turns ON when the result of a comparison operation is less. Not used.
Appendix C
Read/ write Readonly Page 385
08 09
-----
10,11 12 13 14 15 SR 254 00 01 02 03 04 05 06 07 08 to 15 00 01 02 03 04 05 06
---------------
Reado y only
----159 385
SR 255
Readl only
---------------
07 08 to 15
---
Note DM 6601 in the PC Setup can be set to maintain the previous status of the Forced Status Hold Bit (SR 25211) and the I/O Hold Bit (SR 25212) when power is turned OFF. Refer to 1-1-3 CPM2A/CPM2C PC Setup Settings for details on the PC Setup.
577
Memory Areas
Appendix C
AR Area
These bits mainly serve as flags related to CPM2A/CPM2C operation. These bits retain their status even after the CPM2A/CPM2C power supply has been turned off or when operation begins or stops.
Word(s) AR 00, AR 01 AR 02 Bit(s) 00 to 15 00 01 02 03 04 05 to 07 08 to 11 12 to 15 AR 03 to AR 06 AR 07 00 to 15 00 to 11 12 Not used. These flags turn ON g Expansion Unit Error Flag for 1st Unit h h i i when there is an error in Expansion Unit Error Flag for 2nd Unit the corresponding Unit Unit. Expansion Unit Error Flag for 3rd Unit Expansion Unit Error Flag for 4th Unit (Not used by CPM2A.) Expansion Unit Error Flag for 5th Unit (Not used by CPM2A.) Not used. Number of Expansion Units and Expansion I/O Units Connected Not used. Not used. Not used. Valid only for CPM2C CPU Units with lot numbers of 0190O or later. (Cannot be used for CPM2C CPU Units with lot numbers of 3180O or earlier and cannot be used with CPM2A CPU Units.) Refer to 1-3 Changes in SW2 for information on lot numbers. ON: SW2 on the front of the CPU Unit is ON. OFF: SW2 on the front of the CPU Unit is OFF. Not used. RS-232C Port Error Code 0: Normal completion 1: Parity error 2: Frame error 3: Overrun error RS-232C Communications Error Flag Turns ON when an RS-232C port communications error occurs. RS-232C Transmit Ready Flag Turns ON when the PC is ready to transmit data. (No-protocol and Host Link only) RS-232C Reception Completed Flag Turns ON when the PC has completed reading data. (No-protocol only) RS-232C Reception Overflow Flag Turns ON when an overflow has occurred. (No-protocol only) Peripheral Port Error Code 0: Normal completion 1: Parity error 2: Frame error 3: Overrun error Peripheral Port Communications Error Flag Turns ON when a peripheral port communications error occurs. Peripheral Port Transmit Ready Flag Turns ON when the PC is ready to transmit data. (No-protocol and Host Link only) Peripheral Port Reception Completed Flag Turns ON when the PC has completed reading data. (No-protocol only) Peripheral Port Reception Overflow Flag Turns ON when an overflow has occurred. (No-protocol only) RS-232C Port Reception Counter (4 digits BCD) Valid only when no-protocol communications are used. Peripheral Port Reception Counter (4 digits BCD) Valid only when no-protocol communications are used. 258 258 250, 258 ----Function Page
---
13 to 15 AR 08 00 to 03
04 05 06 07 08 to 11
12 13 14 15 AR 09 AR 10 00 to 15 00 to 15
578
Memory Areas
Word(s) AR 11 (Note 1) Bit(s) 00 to 07 Function High-speed Counter Range Comparison Flags 00 ON: Counter PV is within comparison range 1 01 ON: Counter PV is within comparison range 2 02 ON: Counter PV is within comparison range 3 03 ON: Counter PV is within comparison range 4 04 ON: Counter PV is within comparison range 5 05 ON: Counter PV is within comparison range 6 06 ON: Counter PV is within comparison range 7 07 ON: Counter PV is within comparison range 8 High-speed Counter Comparison Operation ON: Operating OFF: Stopped High-speed Counter PV Overflow/Underflow Flag ON: An overflow or underflow occurred. OFF: Normal operation Not used. Pulse Output 0 Output Status ON: Pulse output 0 is accelerating or decelerating. OFF: Pulse output 0 is operating at a constant rate. Pulse Output 0 Overflow/Underflow Flag ON: An overflow or underflow occurred. OFF: Normal operation Pulse Output 0 Pulse Quantity Set Flag ON: Pulse quantity has been set. OFF: Pulse quantity has not been set. Pulse Output 0 Pulse Output Completed Flag ON: Completed OFF: Not completed Pulse Output 0 Output Status ON: Pulses being output. OFF: Stopped. Not used. Pulse Output 1 Overflow/Underflow Flag ON: An overflow or underflow occurred. OFF: Normal operation Pulse Output 1 Pulse Quantity Set Flag ON: Pulse quantity has been set. OFF: Pulse quantity has not been set. Pulse Output 1 Pulse Output Completed Flag ON: Completed OFF: Not completed Pulse Output 1 Output Status ON: Pulses being output. OFF: Stopped.
Appendix C
Page 61
08
09
10 11
104
12
13
14
15
AR 12 (Note 1)
00 to 11 12
104
13
14
15
579
Memory Areas
Word(s) AR 13 Bit(s) 00 Function
Appendix C
Page 553
Power-up PC Setup Error Flag Turns ON when there is an error in DM 6600 to DM 6614 (the part of the PC Setup area that is read at power-up). Start-up PC Setup Error Flag Turns ON when there is an error in DM 6615 to DM 6644 (the part of the PC Setup area that is read at the beginning of operation). RUN PC Setup Error Flag Turns ON when there is an error in DM 6645 to DM 6655 (the part of the PC Setup area that is always read). Not used. Cycle Time Too Long Flag Turns ON if the actual cycle time is longer than the cycle time set in DM 6619. Not used. Memory Area Specification Error Flag Turns ON when a non-existent data area address is specified in the program. Flash Memory Error Flag Turns ON when there is an error in flash memory. Read-only DM Error Flag Turns ON when a checksum error occurs in the read-only DM (DM 6144 to DM 6599) and that area is initialized. PC Setup Error Flag Turns ON when a checksum error occurs in the PC Setup area. Program Error Flag Turns ON when a checksum error occurs in the program memory (UM) area, or when an improper instruction is executed.
01
02
03, 04 05 06, 07 08 09 10
---
----554
11 12
---
13
Expansion Instruction Area Error Flag Turns ON when a checksum error occurs in the expansion instruction assignments area. The expansion instruction assignments will be cleared to their default settings. Data Save Error Flag Turns ON if data could not be retained with the backup battery. The following words are normally backed up by the battery: DM read/write words (DM 0000 to DM 1999 and DM 2022 to DM 2047), Error Log (DM 2000 to DM 2021), HR area, counter area, SR 25511, SR 25512 (if DM 6601 is set to hold I/O memory at startup), AR 23, operating mode (if DM 6600 is set to use the previous operating mode), and clock words (AR 17 to AR 21, for CPU Units with clocks). If the above words cannot be retained, all data will be cleared except that AR 2114 will be turned ON. The CPU Unit will start in PROGRAM mode if DM 6600 is set to use the previous operating mode. (If DM 6604 is set to generate an error, the PC will start in PROGRAM mode regardless.) ---
14
15 AR 14 00 to 15
Not used. Maximum Cycle Time (4 digits BCD, see note 3) The longest cycle time since the beginning of operation is stored. It is not cleared when operation stops, but it is cleared when operation starts again. Current Cycle Time (4 digits BCD, see note 3) The most recent cycle time during operation is stored. The Current Cycle Time is not cleared when operation stops. Not used. Minute (00 to 59, BCD) Hour (00 to 59, BCD) Second (00 to 59, BCD) Minute (00 to 59, BCD) Hour (00 to 23, BCD) Day of the Month (01 to 31, BCD) Month (01 to 12, BCD) Year (00 to 99, BCD) 163 523
AR 15
00 to 15
00 to 15 00 to 07 08 to 15 00 to 07 08 to 15 00 to 07 08 to 15 00 to 07 08 to 15
580
Memory Areas
Word(s) AR 21 (Note 2) 08 to 12 13 Bit(s) 00 to 07 Day of the 00: Sunday 04: Thursday Week3 Function (00 to 06, BCD) 01: Monday 02: Tuesday 05: Friday 06: Saturday 03: Wednesday
Appendix C
Page 163
Not used. 30-second Compensation Bit Turn this bit ON to round off to the nearest minute. When the seconds are 00 to 29, the seconds are cleared to 00 and the rest of the time setting is left unchanged. When the seconds are 30 to 59, the seconds are cleared to 00 and the time is incremented by one minute. Clock Stop Bit Turn this bit ON to stop the clock. The time/date can be overwritten while this bit is ON. Clock Set Bit To change the time/date, turn ON AR 2114, write the new time/date (being sure to leave AR 2114 ON), and then turn this bit ON to enable a new time/date setting. The clock will restart and both AR 2114 and AR 2115 will be turned OFF automatically. Not used. Power-off Counter (4 digits BCD) This is the count of the number of times that the power has been turned off. To clear the count, write 0000 from a Programming Device.
163
14 15
AR 22 AR 23
00 to 15 00 to 15
---
Note 1. The same data can be read immediately with PRV(62). 2. The time and date can be set while AR 2114 is ON. The new setting becomes effective when AR 2115 is turned ON. (AR 2114 and AR 2115 are turned OFF automatically when the new setting goes into effect.) These words will contain 0000 in CPM2C CPU Units that are not equipped with the clock function. 3. The units for the maximum and current cycle times are determined by the setting in bits 08 to 15 of DM 6618. A setting of 00 specifies 0.1-ms units, 01 specifies 0.1-ms units, 02 specifies 1-ms units, and 03 specifies 10-ms units.
Output area
Work area
SR area
(When the CompoBus/S is used in 128-bit mode, IR 004 to IR 007 and IR 014 to IR 017 can also be used as work bits.) IR 00800 to IR 00915 Work bits can be freely used within the proIR 01800 to IR 01915 gram. IR 232 to IR 239 however, are used IR 20000 to IR 23915 as the MACRO input area when MCRO(99) (704 bits) is being used. SR 24000 to SR 25507 These bits serve as storage space for flags (248 bits) and function set values/present values for SRM1 operation. Refer to SR Area. TR 0 to TR 7 (8 bits) When a complicated ladder diagram cannot be recorded as a mnemonic these bits are used to temporarily store ON/OFF status at program branches. These temporary bits cannot be used within the same block but if the blocks are different several may be used. The ON/OFF status of these bits cannot be monitored using the monitoring function of a Programming Device. These bits store data and retain their ON/ OFF status when power is turned off, or operation starts or stops. They are used in the same way as work bits.
TR area
HR area2
HR 00 to HR 19 (20 words)
581
Memory Areas
Data area AR area2 Words AR 00 to AR 15 (16 words) Bits AR 0000 to AR 1515 (256 bits) Function
Appendix C
These bits serve specific functions such as flags and control bits. AR 04 to 07 are used as slaves. Refer to AR Area. Used for a 1:1 data link with another SRM1, CQM1 or C200HS PC. Timers and counter use the TIM, TIMH(15), CNT and CNTR(12) instructions. The same numbers are used for both timers and counters. Timer/counter numbers should be specified as bits when dealing with timer/counter present values. The counter data will be stored even when the SRM1 power is turned off or operation is stopped or started. When timer/counter are treated as up-flags the number should be specified as relay data. DM area data can be accessed in word units only. Word values are retained when the power is turned off, or operation started or stopped. Read/write areas can be read and written freely within the program. Used to store the time of occurrence and error code of errors that occur. Refer to 7-5 Coding Right-hand Instructions. Cannot be overwritten from program. Used to store various parameters that control PC operation.
LR 00 to LR 15 LR 0000 to LR 1515 (16 words) (256 bits) TC 000 to TC 127 (timer/counter numbers)3
DM area Read/write2
Error log4
DM 2000 to DM 2021 --(22 words) DM 6144 to DM 6599 --(456 words) DM 6600 to DM 6655 --(56 words)
Read-only4 PC Setup4
Note 1. IR and LR bits that are not used for their allocated functions can be used as work bits. 2. The contents of the HR area, LR area, Counter area, and read/write DM area are backed up by a capacitor. At 25_C, the capacitor will back up memory for 20 days. Refer to 2-1-2 Characteristics in the SRM1 Master Control Unit Operation Manual for a graph showing the backup time vs. temperature. 3. When accessing a PV, TC numbers are used as word data; when accessing Completion Flags, they are used as bit data. 4. Data in DM 6144 to DM 6655 cannot be overwritten from the program, but they can be changed from a Programming Device.
SR Area
These bits mainly serve as flags related to SRM1 operation or contain present and set values for various functions. The functions of the SR area are explained in the following table. Note Read-only words and bits can be read as status in controller PC operation, but they cannot be written from the ladder program. Bits and words that are Not used are also read-only.
Word(s) SR 240 to SR 247 SR 248, SR 249 SR 250, SR 251 Bit(s) 00 to 15 Not used. Function Read/ write Page
00 to 15 00 to 15
582
Memory Areas
Word(s) SR 252 Bit(s) 00 01 to 07 08 Function Not used. (system use) Not used. Peripheral Port Reset Bit Turn ON to reset peripheral port. (Not valid when Programming Device is connected.) Automatically turns OFF when reset is complete. RS-232C Port Reset Bit Automatically turns OFF when reset is complete. PC Setup Reset Bit Turn ON to initialize PC Setup (DM 6600 through DM 6655). Automatically turns OFF again when reset is complete. Only effective if the PC is in PROGRAM mode. Forced Status Hold Bit OFF: The forced status of bits that are forced set/reset is cleared when switching between PROGRAM mode and MONITOR mode. ON: The status of bits that are forced set/reset are maintained when switching between PROGRAM mode and MONITOR mode. I/O Hold Bit OFF: IR and LR bits are reset when starting or stopping operation. ON: IR and LR bit status is maintained when starting or stopping operation. Not used. Error Log Reset Bit Turn ON to clear error log. Automatically turns OFF again when operation is complete. Not used. FAL Error Code The error code (a 2-digit number) is stored here when an error occurs. The FAL number is stored here when FAL(06) or FALS(07) is executed. This word is reset (to 00) by executing a FAL 00 instruction or by clearing the error from a Programming Device. Not used. Cycle Time Overrun Flag Turns ON when a cycle time overrun occurs. Not used. RS-232C Port Set Bit Turn ON to set RS-232C port. Turn OFF when reset is complete. Always ON Flag Always OFF Flag First Cycle Flag Turns ON for 1 cycle at the start of operation. 1-minute clock pulse (30 seconds ON; 30 seconds OFF) 0.02-second clock pulse (0.01 second ON; 0.01 second OFF) Negative (N) Flag Not used. Overflow Flag Underflow Flag Differential Monitor Complete Flag Turns ON when differential monitoring is complete. STEP(08) Execution Flag Turns ON for 1 cycle only at the start of process based on STEP(08). Not used.
Appendix C
Read/ write Page
Read/ write
272
09 10
11
17
12
17
13 14
Read/ write
555
SR 253
15 00 to 07
Readonly
385
08 09 10 to 11 12
---
13 14 15 SR 254 00 01 02 03 04 05 06 07 08 to 15
-------------
Readonly l
----159 385
583
Memory Areas
Word(s) SR 255 Bit(s) 00 01 02 03 04 05 06 Function 0.1-second clock pulse (0.05 second ON; 0.05 second OFF) 0.2-second clock pulse (0.1 second ON; 0.1 second OFF) 1.0-second clock pulse (0.5 second ON; 0.5 second OFF) Instruction Execution Error (ER) Flag Turns ON when an error occurs during execution of an instruction. Carry (CY) Flag Turns ON when there is a carry in the results of an instruction execution. Greater Than (GR) Flag Turns ON when the result of a comparison operation is greater. Equals (EQ) Flag Turns ON when the result of a comparison operation is equal, or when the result of an instruction execution is 0. Less Than (LE) Flag Turns ON when the result of a comparison operation is less. Not used.
Appendix C
Read/ write Readl only Page ---------------
07 08 to 15
---
AR Area
These bits mainly serve as flags related to SRM1 operation. These bits retain their status even after the SRM1 power supply has been turned off or when operation begins or stops.
Word(s) AR 00, AR 01 AR 02 Bit(s) 00 to 15 00 to 07 08 to 11 12 to 15 00 to 15 00 to 15 00 to 03 Not used. Not used. Not used. (system use) Not used. Not used. Slave Status Flag RS-232C Error Code (1-digit number) 0: Normal completion 1: Parity error 2: Framing error 3: Overrun error RS-232C Communications Error RS-232C Transmission Enabled Flag Valid only when Host Link, no-protocol communications are used. RS-232C Reception Completed Flag Valid only when no-protocol communications are used. RS-232C Reception Overflow Flag Valid only when no-protocol communications are used. Programming Device Error Code 0: Normal completion 1: Parity error 2: Frame error 3: Overrun error Programming Device Error Flag Programming Device Transmission Enabled Flag Valid only when Host Link, no-protocol communications are used. Programming Device Reception Completed Flag Valid only when no-protocol communications are used. Programming Device Reception Overflow Flag Valid only when no-protocol communications are used. ----Function Page
AR 03 AR 04 to AR 07 AR 08
04 05 06 07 08 to 11
--------273
12 13 14 15
-------
584
Memory Areas
Word(s) AR 09 Bit(s) 00 to 15 Function
Appendix C
Page -----
When the no-protocol communications mode is being used: RS-232C Reception Counter (4 digits BCD) When the 1:N NT Link communications mode is being used (V2 only): Communicating with PT Flags (Bits 00 to 07 are flags for PTs 0 to 7.) Registering Priority with PT Flags (Bits 08 to 15 are flags for PTs 0 to 7.) Programming Device Reception Counter (4 digits BCD) Valid only when no-protocol communications are used. 4 digits BCD Power supply cut frequency. Not used.
AR 10 AR 11 AR 12 AR 13
00 to 15 00 to 15 00 to 15 00
-----
553 Power-up PC Setup Error Flag Turns ON when there is an error in DM 6600 to DM 6614 (the part of the PC Setup area that is read at power-up). Start-up PC Setup Error Flag Turns ON when there is an error in DM 6615 to DM 6644 (the part of the PC Setup area that is read at the beginning of operation). RUN PC Setup Error Flag Turns ON when there is an error in DM 6645 to DM 6655 (the part of the PC Setup area that is always read). Not used. Long Cycle Time Flag Turns ON if the actual cycle time is longer than the cycle time set in DM 6619. Turns ON when the program memory (UM) area is full. Turns ON when instructions other than those in the support software area used. Memory Area Specification Error Flag Turns ON when a non-existent data area address is specified in the program. Flash Memory Error Flag Turns ON when there is an error in flash memory. Read-only DM Error Flag Turns ON when a checksum error occurs in the read-only DM (DM 6144 to DM 6599) and that area is initialized. PC Setup Error Flag Turns ON when a checksum error occurs in the PC Setup area. Program Error Flag Turns ON when a checksum error occurs in the program memory (UM) area, or when an improper instruction is executed. Not used. (Cleared when power is turned on.) Data Save Error Flag Turns ON when power is turned on if data could not be saved in the following areas: DM area (read/write-capable), HR area, CNT area, SR 252, bits 11, 12 (when PC Setup in DM 6601 is set to maintain status), error log, operation mode (when PC Setup in DM 6600 is set to continue mode last used before power failure). (For details regarding the holding time, refer to the SRM1 Operation Manual.) If data could not be saved in the above areas: The DM (read/write-capable), error log, HR, and CNT areas, and SR 252, bits 11 and 12 will be cleared. The operation mode will go into PROGRAM mode. SRM1 CompoBus/S Communications Error Flag --Maximum Cycle Time (4 digits BCD) The longest cycle time since the beginning of operation is stored. It is cleared at the beginning, and not at the end, of operation. The units can be any of the following, depending on the setting of in DM 6618. Default: 0.1 ms; 10 ms setting: 0.1 ms; 100 ms setting: 1 ms; 1 s setting: 10 ms Current Cycle Time (4 digits BCD) The most recent cycle time during operation is stored. The Current Cycle Time is not cleared when operation stops. The units can be any of the following, depending on the setting of in DM 6618. Default: 0.1 ms; 10 ms setting: 0.1 ms; 100 ms setting: 1 ms; 1 s setting: 10 ms 523 ----------554
01
02
03, 04 05 06 07 08 09 10
11 12
---
13 AR 13 14
15 AR 14 00 to 15
AR 15
00 to 15
585
Appendix D
I/O Assignment Sheet
Name of system PC model IR_____ 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 IR_____ 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 Unit No.: Model: Unit No.: Model: Sheet No. IR_____ 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 IR_____ 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 Unit No.: Model: Unit No.: Model: Produced by y Verified by y Authorized by y
587
Appendix E
Program Coding Sheet
Name of system PC Address 0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 3 3 3 3 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 Chart No. Instruction Function code Operands Produced by y Verified by y Authorized by y
589
Appendix E
590
Appendix E
591
Appendix F
List of FAL Numbers
Name of system PC model FAL No. 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 FAL contents Chart No. Corrective measure FAL No. 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 FAL contents Corrective measure Produced by y Verified by y Authorized by y
593
Appendix F
Corrective measure
594
Appendix G
Extended ASCII
The following codes are used to output characters to the Programming Console or Data Access Console using MSG(46). Refer to pages 497 for details.
Right g digit di i 0 1 2 3 4 5 6 7 8 9 A B C D E F . / ! " # $ % & ' ( ) * + , Left digit 0, 1, 8, 9 2 3 0 1 2 3 4 5 6 7 8 9 : ; < = > ? 4 @ A B C D E F G H I J K L M N O 5 P Q R S T U V W X Y Z [ \ ] ^ _ 6 ` a b c d e f g h i j k l m n o 7 p q r s t u v w x y z { | } ~ . / ! " # $ % & ' ( ) * + , 1 2 3 4 5 6 7 8 9 : ; < = > ? A B C @ A B C D E F G H I J K L M N O D P Q R S T U V W X Y Z [ \ ] ^ _ E ` a b c d e f g h i j k l m n o ~ F p q r s t u v w x y z { | }
595
Index Numbers
1:1 PC Link CPM1/CPM1A, 229 CPM2A/CPM2C, 263 SRM1, 279 1:1 PC Link communications, I/O response timing CPM1/CPM1A, 515 CPM2A/CPM2C, 525 SRM1, 541 CPM1/CPM1A, 227 CPM2A/CPM2C, 231 SRM1, 268 NT Link, CPM1/CPM1A, 228 types, 226 wiring, 226 communications functions, 225 Communications Switch, setting CPM2A, 253, 262, 266 CPM2C, 254, 262, 267 CompoBus/S I/O Link Unit, 147, 214 using, 214
AB
analog controls, 150 analog I/O functions, 147, 166, 177 Analog I/O Units, 147 for CPM1A/CPM2A, 166 for CPM2C, 177 Analog Input Units averaging function, 183 input range, 180 open-circuit detection function, 183 analog inputs, 169, 184 Analog Output Units, output range, 182 analog outputs, 170, 185 analog settings, 150 arithmetic flags, 159, 365 ASCII converting data, 449, 451 table of codes, 595 averaging function, 183 binary data, signed binary, 159 bits, controlling, 377
CompoBus/S I/O Master functions, 148 CompoBus/S I/O Slave functions, 147, 214 constants, operands, 365 counter mode interrupts, CPM2A/CPM2C, 68 counters conditions when reset, 394, 396 creating extended timers, 395 reversible counters, 395 cycle monitor time, PC Setup settings, 18 cycle time CPM1/CPM1A calculating, 513 effects on operations, 513 processes, 513 CPM2A/CPM2C calculating, 523 effects on operations, 523 processes, 523 SRM1 calculating, 538 effects on operations, 539 processes, 538 cycle time (minimum), PC Setup settings, 19
D C
check levels, program checks, 551 checksum, calculating frame checksum, 500 clock, 163 communications 1:1 NT Link CPM2A/CPM2C, 260 SRM1, 277 1:1 PC Link CPM1/CPM1A, 229 CPM2A/CPM2C, 263 SRM1, 279 1:N NT Link, SRM1, 278 errors, 554 host link data computation standards, 146 decrementing, 483 incrementing, 483 decrementing. See data definers, definition, 364 Differential Monitor, function, 159 differential monitoring, 159 differentiated instructions, 366 function codes, 364 display, for Temperature Sensor Units, 208 duty ratio fixed duty ratio pulse outputs, 101 variable duty ratio pulse outputs, 111
597
Index
E
error codes, programming, 385 error log, PC Setup settings, 21 error log area, 552 error messages, programming, 497 errors communications, 554 degree of error in pulse outputs, 146 fatal, 554 general, 550 non-fatal, 553 other, 554 PC Setup, 2 programming, 551 Programming Console operations, 550 programming messages, 497 resetting, 385 types, 550 user-defined errors, 552 execution condition, definition, 336 expansion instructions, 371, 372, 562 function codes, 160 Expansion Units, using, 165
CPM2A/CPM2C, 231 SRM1, 268 host link commands ::, 304 EX, 304 FK, 298 IC, 305 KC, 299 KR, 297 KS, 296 MF, 295 MM, 300 MS, 293 QQ, 302 R#, 289 R$, 290 RC, 282 RD, 283 RG, 283 RH, 282 RJ, 284 RL, 282 RP, 301 RR, 281 SC, 294 TS, 300 W#, 291 W$, 292 WC, 286 WD, 288 WG, 287 WH, 286 WJ, 288 WL, 285 WP, 301 WR, 285 XZ, 304
F
FAL area, 385 FAL numbers, table, 593 FAL(06), 552 FALS(07), 552 flag arithmetic, programming example, 433, 437 CY clearing, 457 setting, 457 flags, error and arithmetic, 565 Frame Check Sequence. See frames, FCS frame checksum, calculating with FCS(), 500 frames, FCS, 239 function codes, 364 expansion instructions, 160, 161, 162, 371, 372
IJ
I/O points, refreshing, 498 I/O response time 1:1 PC Link communications CPM1/CPM1A, 515 CPM2A/CPM2C, 525 SRM1, 541 CPM1/CPM1A. See timing CPM2A/CPM2C. See timing SRM1. See timing incrementing, 483 indicators, CompoBus/S LED indicators, 215, 220 indirect addressing, 365 INI(61), 133 initialization processes, CPM1/CPM1A, 512 input interrupts CPM1/CPM1A, 79 CPM2A/CPM2C, 30 input interrupts (counter mode), CPM2A/CPM2C, 68 input mode
H
high-speed counter interrupts CPM1/CPM1A, 86 CPM2A/CPM2C, 46 high-speed counters, CPM2A/CPM2C, 45 hold bit status, PC Setup settings, 17 host link CPM1/CPM1A, 227
598
Index
CPM2A/CPM2C, 49 selecting, 137 input time constants, PC Setup settings, 19 inputs, quick-response inputs, 153 instruction set, 559 ACC(), 491 ADB(50), 467 ADD(30), 457 ADDL(54), 462 AND, 338, 376 combining with OR, 339 AND LD, 341, 377 combining with OR LD, 344 use in logic blocks, 343 AND NOT, 338, 376 ANDW(34), 480 ASC(86), 449 ASFT(17), 410 ASL(25), 405 ASR(26), 406 AVG(), 476 BCD(24), 440 BCDL(59), 441 BCMP(68), 434 BCNT(67), 499 BIN(23), 439 BINL(58), 440 BSET(71), 414 CLC(41), 457 CMP(20), 432 CMPL(60), 436 CNT, 394 CNTR(12), 395 COLL(81), 417 COM(29), 479 CTBL(63), 396 DEC(39), 483 DIFD(14), 355, 380389 using in interlocks, 382 using in jumps, 384 DIFU(13), 355, 380389 using in interlocks, 382 using in jumps, 384 DIST(80), 415 DIV(33), 461 DIVL(57), 466 DMPX(77), 444 DVB(53), 470 END(01), 341, 381 FAL(06), 385 FALS(07), 385 FCS(), 500 HEX(), 451 HTS(65), 453 IL(02), 351, 381383 ILC(03), 351, 381383 INC(38), 483 INI(61), 133, 399 INT(89), 83, 501 IORF(97), 498 JME(05), 383 JMP(04), 383 JMP(04) and JME(05), 353 KEEP(11), 379 in controlling bit status, 355 ladder instructions, 337 LD, 338, 376 LD NOT, 338, 376 MAX(), 472 MCRO(99), 157, 486 MIN(), 474 MLB(52), 470 MLPX(76), 442 MOV(21), 411 MOVB(82), 419 MOVD(83), 420 MSG(46), 497 MUL(32), 460 MULL(56), 466 MVN(22), 412 NEG(), 455 NOP(00), 381 NOT, 335 operands, 334 OR, 339, 376 combining with AND, 339 OR LD, 342, 377 combining with AND LD, 344 use in logic blocks, 343 OR NOT, 339, 376 ORW(35), 481 OUT, 340, 377 OUT NOT, 340, 377 PID(), 426 PRV(62), 401 PULS(65), 132, 487 PWM(), 494 RESET, 354 RET(93), 486 ROL(27), 406 ROR(28), 407 RSET, 378379 RXD(47), 252, 276, 505 SBB(51), 468 SBN(92), 26, 77, 486 SBS(91), 484 SCL(66), 421 SCL2(), 423 SCL3(), 424 SDEC(78), 446 SET, 354, 378379 SFT(10), 404 SFTR(84), 409 SLD(74), 408 SNXT(09), 385 SPED(64), 132, 489 SRCH(), 471 SRD(75), 408 STC(40), 457 STEP(08), 385 STH(), 454 STIM(69), 504 STUP(), 509 SUB(31), 458 SUBL(55), 464 SUM(), 478 SYNC(), 496 TCMP(85), 433
599
Index
terminology, 334 TIM, 389 TIMH(15), 390 using in jumps, 384 TIML(), 392 TMHH(), 391 using in jumps, 384 TXD(48), 252, 276, 507 WSFT(16), 405 XCHG(73), 415 XFER(70), 413 XNRW(37), 482 XORW(36), 481 ZCP(), 437 ZCPL(), 438 instructions execution times CPM1/CPM1A, 518 CPM2A/CPM2C, 528 SRM1, 543 expansion, 160 instruction set lists, 370 mnemonics list, ladder, 373 right-hand instructions, coding multiple, 349 subroutines, 484 INT(89), 83 interlocks, 381383 using self-maintaining bits, 356 interrupt functions CPM1/CPM1A, 77 CPM2A/CPM2C, 26 SRM1(-V2), 94 interrupt processing calculating response time CPM1/CPM1A, 517 CPM2A/CPM2C, 527 masking CPM1/CPM1A, 517 CPM2A/CPM2C, 527 SRM1, 542 timing CPM1/CPM1A, 517 CPM2A/CPM2C, 527 SRM1, 542 interrupts control, 501 CPM1/CPM1A counter mode, 82 high-speed counter, 86 overflows and underflows, 88 input interrupt mode, 80 input interrupts, 79 interval timers, 84 scheduled interrupt mode, 84 masking, 83 setting modes, 80 types, 77 unmasking, 84 CPM2A/CPM2C high-speed counter, 46 input interrupts, 30 interval timers, 37 scheduled interrupt mode, 39 masking, 34 order of priority, 27 selecting interrupts to be used, 51 setting modes, 33 types, 26 unmasking, 34, 35 high-speed counter, programming, 57, 90 masking, masking, 35 SRM1 interval timers, 94 scheduled interrupt mode, 95 types, 94 unmasking, 504 interval timer interrupts CPM1/CPM1A, 84 CPM2A/CPM2C, 37 SRM1, 94 JOG operation, CPM2A/CPM2C, 109 jogging, 128 jump numbers, 383 jumps, 383384
L
ladder diagram branching, 349 IL(02) and ILC(03), 351 using TR bits, 350 combining logic blocks, 345 controlling bit status using DIFU(13) and DIFD(14), 355, 380389 using KEEP(11), 379380 using OUT and OUT NOT, 340 using SET and RESET, 354 using SET and RSET, 378379 converting to mnemonic code, 336354 display via GPC, FIT, LSS, or SSS, 335 instructions combining, AND LD and OR LD, 344 controlling bit status using KEEP(11), 355 using OUT and OUT NOT, 377 format, 364 notation, 364 structure, 335 using logic blocks, 341 ladder diagram instructions, 376377 logic block instructions, converting to mnemonic code, 341348 logic blocks. See ladder diagram
600
Index
M
macro function, subroutines. See programming masking CPM1/CPM1A interrupt processes, 517 CPM2A/CPM2C interrupt processes, 527 SRM1 interrupt processes, 542 MCRO(99), 157 memory areas AR area bits CPM2A/CPM2C, 578 SRM1, 584 flags and control bits CPM1/CPM1A, 569 CPM2A/CPM2C, 575 SRM1, 582 structure CPM1/CPM1A, 308, 569 CPM2A/CPM2C, 309, 574 SRM1, 310, 581 messages, programming, 497 mnemonic code, converting, 336354 MSG(46), 552
P
PC Link, CPM2A/CPM2C, 263 PC Setup. See settings PC Setup settings CPM1/CPM1A, 3 CPM2A/CPM2C, 7 SRM1(-V2), 13 peripheral port, servicing time, 18 peripheral port servicing time, PC Setup settings, 18 positioning, 126 precautions, general, xvii program coding sheet, 589 Program Memory, structure, 336 program write protection, PC Setup settings, 17 programming errors, 551 for temperature monitoring, 202 high-speed counter CPM1/CPM1A, 90 CPM2A/CPM2C, 57 instructions, 559 interrupts, 57, 90 jumps, 353 macro function, subroutines, 157 precautions, 358 preparing data in data areas, 414 program coding sheet, 589 special features, 160 writing, 334 programs checking, check levels, 551 executing, 360 PULS(65), 132 pulse output errors/delays, 146 fixed duty ratio, 101 synchronized to input frequency, 134, 496 variable duty ratio, 111 pulse output functions CPM1A, 131 CPM2A/CPM2C, 97 PV CNTR(12), 395 timers and counters, 389
N
nesting, subroutines, 485 no-protocol communications CPM2A/CPM2C, 251 program example, 257, 277 SRM1, 272 transmission data configuration, 252, 276 transmission flags, 252, 276 normally open/closed condition, definition, 335 NOT, definition, 335 NT Link CPM1/CPM1A, 228 CPM2A/CPM2C, 260 SRM1, 277, 278
O
open-circuit detection function, 183 operand bit, 336 operands, 364 allowable designations, 364 requirements, 364 operations CPM1/CPM1A internal processing, flowchart, 512 effects on CPM1/CPM1A cycle time, 513 effects on CPM2A/CPM2C cycle time, 523 effects on SRM1 cycle time, 539 SRM1 internal processing, flowchart, 537 output bit
R
range code, 173, 191 range comparison interrupts, CPM2A/CPM2C, 52 right-hand instructions, coding. See instructions
601
Index
RS-232C communications receiving CPM2A/CPM2C, 259 SRM1, 272 transmitting CPM2A/CPM2C, 258 SRM1, 272 control bits, SRM1, 273 RS-232C port, servicing time (CPM2A/CPM2C/SRM1), 18 RS-232C port servicing time, PC Setup settings, 18 RXD(47), 252, 276 synchronized pulse output, 496
TW
target value comparison table, CPM2A/CPM2C, 57 TC numbers, 388 temperature sensor input functions, 147 Temperature Sensor Units, 147, 193 time reading the time, 163 setting the time, 163 timers, conditions when reset, 389, 390 TIML(), 393 TMHH(), 392 timing basic instructions CPM1/CPM1A, 518 CPM2A/CPM2C, 528 SRM1, 543 CPM1/CPM1A cycle time, 513 CPM2A/CPM2C cycle time, 523 I/O response time CPM1/CPM1A, 514 CPM2A/CPM2C, 524 SRM1, 540 instruction execution CPM1/CPM1A. See instruction CPM2A/CPM2C. See instruction SRM1. See instruction interrupt processing CPM1/CPM1A, 517 CPM2A/CPM2C, 527 SRM1, 542 special instructions CPM1/CPM1A, 518 CPM2A/CPM2C, 528, 535 SRM1, 543, 547 SRM1 cycle time, 538 TR bits, use in branching, 350 two-decimal place display, 208 TXD(48), 252, 276 write protecting the program, PC Setup settings, 17
S
SBN(92), 26, 77 serial communications, CPM2A/CPM2C, 251 settings basic operations hold bit status, 17 startup mode, 16 changing, 2 communications, 226 host link CPM1/CPM1A, 227 CPM2A/CPM2C, 231 SRM1, 268 defaults, 2 I/O operations, 16 port servicing scan time, 18, 19 seven-segment displays, converting data, 446 signed binary data, 158, 159 SPED(64), 132 startup mode, PC Setup settings, 16 subroutine number, 486 subroutines, interrupt subroutines, 26 SV CNTR(12), 395 timers and counters, 389 synchronized pulse control, 134 errors/delays, 146
602
Revision History
A manual revision code appears as a suffix to the catalog number on the front cover of the manual.
The following table outlines the changes made to the manual during each revision. Page numbers refer to the previous version.
Revision code
1 2
Date
May 1999 January 2000 Original production
Revised content
Information on new Expansion Units and the relevant PCs was added throughout the manual. Additional changes were made on the following pages: Page xi: Updated to new contents of manual. Page xv: Change made to first caution. Page xvi: Change made to first installation precaution. Page xvii: Ground precaution changed to warning and moved to safety precaution section. Other precautions expanded or reworded. Page xv: Caution on online editing reworded. Page xvi: First installation precaution expanded. Pages 9, 11, 185, 186, 194, 195, 200: Host Link unit number added to port settings. Pages 11, 186, 195: Communications mode description changed. Page 17: Setting to protect memory changed. Page 24: Position of notes changed. Pages 54, 55, 56, 57, 58, 71, 79, 92, 99, 106, 107, 112, 113, 115, 116, 117, 119, 133, 153, 154, 160, 174, 175, 198, 201, 213, 348, 414, 425, 428, 429: Changes to graphics. Pages 96, 111: Change to Pulse Output Flag description. Page 120: Pulse output number changed in program. Page 134: Section added on data calculations. Pages 137 to 139: Analog control sections combined. Pages 148, 149: Corrections made for function codes. Page 159: Table removed. Pages 187, 207: Change to first line of program. Pages 190, 300, 475: Note added. Pages 238, 367, 444: Changes made to tables. Pages 283-285: Updated to new contents and order of section. Pages 293, 294: Changes made to existing table. Table added. Pages 311-314: Information added to Precautions. Page 313: Changes made to graphics and Limitations. Section moved to the end of section on TMHH. Page 314: Changes made to graphics and Limitations. Pages 387, 388: Example added. Page 413: Section onSRCH moved before section on MAX. Page 443: Information on I/O refreshing added. Page 490: Volume removed from information on SR 250 and SR 251. Pages 490, 491, 495-497, 501-503: Read/write column added to table. Page 497: Changes made to information on AR 02. Page 498: Changes made to information on AR 1111. Page 499: Changes made to information on AR 1314.
603
Revision History
Revision code
03
Date
February 2001
Revised content
Revisions and additions were made accompanying specifications changes and new products. The CPM1A-MAD11 Analog I/O Unit was added as section 3-1-2 and the CPM1A-DRT21 DeviceNet I/O Link Unit was added as section 3-4. Interrupt programming precautions were added to sections 2-1 and 2-3. Specific changes are as follows: Pages xi, 1, 23, 148, 163, 177, 197, 203, 331, 341, 383, 495, 500, and 546: CPM2C-S added. Pages 7 and 21: Information added on DIP switch changes. Page 138: Note added. Page 161: Information added on startup operation. Page 162: Programming example modified. Pages 295 to 298 and 300: Models added. Page 545: Description of AR 1314 altered. Page 550: Description of AR 0712 added.
04
July 2003
The following revisions and changes were made. Page xi: Support Software information updated. Page xv: Caution added. Page 27: Section added. Page 164: Bottom illustration changed. Pages 170, 411, and 413: Notes added. Page 183: Range for range code 011 corrected, note following table changed, and top illustration corrected. Page 202: DM area address corrected for SBB and BCD instructions at bottom of ladder program code. Page 216: Communications current consumption added to top table. Page 219: Callouts in top illustration corrected. Pages 229, 231, 257, and 261: -V1 version added to illustration. Pages 240 and 248: -V1 added to version in note. Page 251: Recommended cables added. Page 313: Model number added at top of page. Pages 385 to 388, 390, and 391: Timer/counter notation changed in introductions. Pages 387 and 389: TML() corrected to the Programming Console. Page 388: Programming example corrected. Page 549: Information added to description of F7 in table.
05
February 2004
The following revisions and changes were made. Page xi: CX-Programmer information updated in table. Page 131: Catalog number of manual added. Pages 214 and 219: CS1 changed to CS. Page 233: Note changed. Page 397: Note added.
06
February 2008
Page xii: Added information on warranty and liability. Page 7: Changed description of a setting of 00 for bits 08 to 15 of CM 6600. Page 71: Replaced top two graphics. Page 186: Changed number of Analog I/O Units to 3 and added note. Page 187: Changed analog input numbers in table column headings. Page 214: Changed bottom callout in top diagram and added table.
604