PFD Consiltator

This document contains information from a PFD calculator on two configurations - simple and advanced. The simple configuration contains three subsystems - sensor element, logic solver, and final element. It provides the failure rates, common cause factors, test periods, and average PFDs for each subsystem and the total system PFD of 1.30E-02, which meets SIL 1 requirements. The advanced configuration also contains three subsystems and provides more detailed failure rate, test coverage, lifetime and PFD information for each subsystem and the total system PFD of 1.80E-02, again meeting SIL 1 requirements.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
138 views5 pages

PFD Consiltator

This document contains information from a PFD calculator on two configurations - simple and advanced. The simple configuration contains three subsystems - sensor element, logic solver, and final element. It provides the failure rates, common cause factors, test periods, and average PFDs for each subsystem and the total system PFD of 1.30E-02, which meets SIL 1 requirements. The advanced configuration also contains three subsystems and provides more detailed failure rate, test coverage, lifetime and PFD information for each subsystem and the total system PFD of 1.80E-02, again meeting SIL 1 requirements.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 5

Version 2.

PFD CONSILTATOR - Simple

SE - Sensor Element subsystem LS - Logic Solver subsystem FE - Final Element subsystem Total PFD
Configuration 2oo3 Configuration 1oo1 Configuration 1oo2 SE - Sensor Element subsystem 3.15E-03
Dangerous undetected failure rate 1 λDU,1 1.00E-06 /h Dangerous undetected failure rate 1 λDU,1 2.00E-06 /h Dangerous undetected failure rate 1 λDU,1 4.00E-07 /h LS - Logic Solver subsystem 8.76E-03
Dangerous undetected failure rate 2
Dangerous undetected failure rate 3
λDU,2
λDU,3
5.00E-06 /h
4.00E-07 /h
+ Dangerous undetected failure rate 2
Dangerous undetected failure rate 3
λDU,2
λDU,3
1.00E-06 /h
4.00E-07 /h
+ Dangerous undetected failure rate 2
Dangerous undetected failure rate 3
λDU,2
λDU,3
4.00E-07 /h
4.00E-07 /h
= Total PFD
FE - Final Element subsystem
avg
1.10E-03 +
1.30E-02 à SIL 1
Common cause factor β 10 % Common cause factor β 10 % Common cause factor β 15 %
Test period T 4 years Test period T 1 years Test period T 4 years
Average PFD PFDavg 3.15E-03 Average PFD PFDavg 8.76E-03 Average PFD PFDavg 1.10E-03

01/24/2023 PFD CONSILTATOR - PFD calculator (simple) Consiltant - Version 2.0


Version 2.0

PFD CONSILTATOR - Advanced

SE - Sensor Element subsystem LS - Logic Solver subsystem FE - Final Element subsystem Total PFD
Configuration 1oo2 Configuration 1oo1 Configuration 1oo3 SE - Sensor Element subsystem 4.79E-04
Dangerous undetected failure rate 1 λDU,1 2.00E-06 /h Dangerous undetected failure rate 1 λDU,1 2.00E-06 /h Dangerous undetected failure rate 1 λDU,1 4.00E-07 /h LS - Logic Solver subsystem 1.71E-02
Dangerous undetected failure rate 2 λDU,2 1.00E-06 /h Dangerous undetected failure rate 2 λDU,2 1.00E-06 /h Dangerous undetected failure rate 2 λDU,2 4.00E-07 /h FE - Final Element subsystem 4.21E-04 +
Dangerous undetected failure rate 3
Common cause factor
λDU,3
β
4.00E-07 /h
10 %
+ Dangerous undetected failure rate 3
Common cause factor
λDU,3
β
4.00E-07 /h
10 %
+ Dangerous undetected failure rate 3
Common cause factor
λDU,3
β
4.00E-07 /h
10 %
= Total PFDavg 1.80E-02 à SIL 1

Test period T 1 years Test period T 12 months Test period T 4 years


Proof test coverage PTC 100 % Proof test coverage PTC 95 % Proof test coverage PTC 95 %
Lifetime LT 20 years Lifetime LT 20 years Lifetime LT 20 years
Average PFD PFDavg 4.79E-04 Average PFD PFDavg 1.71E-02 Average PFD PFDavg 4.21E-04

01/24/2023 PFD CONSILTATOR - PFD calculator (advanced) Consiltant - Version 2.0


Version 2.0

PFD CONSILTATOR - Help Enter the desired


configuration by using
the dropdown box.
Enter the (different)
failure rates of the
SE - Sensor Element subsystem equipment. LS - Logic Solver subsystem FE - Final Element subsystem Total PFD
Configuration 1oo2 Configuration 1oo1 Configuration 2oo3 SE - Sensor Element subsystem 4.79E-04
Dangerous undetected failure rate 1 λDU,1 2.00E-06 /h Dangerous undetected failure rate 1 λDU,1 2.00E-06 /h Dangerous undetected failure rate 1 λDU,1 4.00E-07 /h LS - Logic Solver subsystem 1.71E-02
Dangerous undetected failure rate 2 λDU,2 1.00E-06 /h Dangerous undetected failure rate 2 λDU,2 1.00E-06 /h Dangerous undetected failure rate 2 λDU,2 1.00E-06 /h FE - Final Element subsystem 2.62E-03 +
Dangerous undetected failure rate 3
Common cause factor
λDU,3
β
4.00E-07 /h
10 %
+ Dangerous undetected failure rate 3
Common cause factor
λDU,3
β
4.00E-07 /h
10 %
+ Dangerous undetected failure rate 3
Common cause factor
λDU,3
β
2.00E-06 /h
10 %
= Total PFDavg 2.02E-02 à SIL 1

Test period T 1 years Test period T 12 months Test period T 4 years


Proof test coverage PTC 100 % Proof test coverage PTC 95 % Proof test coverage PTC 95 %
Lifetime LT 20 years Lifetime LT 20 years Lifetime LT 20 years Blue fields are input
Average PFD PFDavg 4.79E-04 Average PFD PFDavg 1.71E-02 Average
Change PFD
the unit of PFDavg 2.62E-03 fields. Orange fields are
time by using the output fields
dropdown box. (calculation results).

β modifiction factor
When applying the the β-factor for common cause failure (CFF) calculations, it will be automatically modified for
redundant configurations (other than 1oo2).
IEC 61508-6:2010 suggests the modification factor in table D.5.

Note: the simple PFD calculator version does not apply this modification factor.

01/24/2023 PFD CONSILTATOR - Help Consiltant - Version 2.0


PFD CONSILTATOR

Basis of PFD calculations (simple)


The simple version of the PFD CONSILTATOR calculates the average Probability of Failure on Demand according the following formulas:
𝜆 𝐷𝑈 ∙𝑇
1oo1 𝑃𝐹𝐷𝐴𝑉𝐺 ≈ 2

∙𝑇ሻ2
𝜆 𝐷𝑈 ,1 ∙𝜆 𝐷𝑈 ,2 ∙ሺሾ1−𝛽ሿ 𝑚𝑖𝑛
𝛽 ∙𝜆 𝐷𝑈 ∙𝑇
1oo2 𝑃𝐹𝐷𝐴𝑉𝐺 ≈ 3
∙+ 2

∙𝑇ሻ3
𝜆 𝐷𝑈 ,1 ∙𝜆 𝐷𝑈 ,2 ∙𝜆 𝐷𝑈 ,3 ∙ሺሾ1−𝛽 ሿ 𝛽 ∙𝜆 𝑚𝑖𝑛
𝐷𝑈 ∙𝑇
1oo3 𝑃𝐹𝐷𝐴𝑉𝐺 ≈ +
4 2

𝜆 𝐷𝑈 ,1 ∙𝜆 𝐷𝑈 ,2 +𝜆 𝐷𝑈 ,2 ∙𝜆 𝐷𝑈 ,3 +𝜆 𝐷𝑈 ,1 ∙𝜆 𝐷𝑈 ,3 ൯
൫ ∙𝑇ሻ2
ሺሾ1−𝛽 ሿ 𝛽 ∙𝜆 𝑚𝑖𝑛
𝐷𝑈 ∙𝑇
2oo3 𝑃𝐹𝐷𝐴𝑉𝐺 ≈ +
3 2

𝑃𝐹𝐷𝐴𝑉𝐺 Average Probability of Failure on Demand


𝜆𝐷𝑈,𝑛 Dangerous undetected failure rate of item n
𝜆𝑚𝑖𝑛
𝐷𝑈 Smallest of all dangerous undetected failure rates
𝑇 Test period
𝛽 Common cause factor

Basis of PFD calculations (advanced)


The advanced version of the PFD CONSILTATOR calculates the average Probability of Failure on Demand according the methods described in IEC 61508-6 and VDI/VDE 2180 (see references below).

References
IEC-61508-6 - Appendix B
VDI/VDE 2180 part 3 (September 2019)
Gabriel, T., Menck, U., & Hildebrandt, A. (2016). PFD Calculation Considering Imperfect Proof Tests. Chemical Engineering Transactions, 48, 637-642. https://doi.org/10.3303/CET1648107

Common cause factor - Beta


Some guidance on beta-factors can be found at Sintef
Common Cause Failures in Safety Instrumented Systems; Beta-factors and equipment specific checklists based on operational experience

01/24/2023 PFD CONSILTATOR - References Consiltant - Version 2.0


Revision data

Date Version Description Author


7/19/2018 1.0 Initial version Jeroen Mijnarends
10/2/2020 2.0 New calculation method added (advanced), based on Jeroen Mijnarends
VDI-VDE 2180 part 3 (2019).

01/24/2023 PFD CONSILTATOR - Revision Consiltant - Version 2.0