Transformer Test Form

The document provides test results and evaluation of a power transformer. It includes 6 electrical tests measuring winding resistance, turn ratio, insulation resistance, polarization index, insulation power factor, and oil dielectric breakdown voltage. Mechanical inspections checked the high voltage bushing, connections, bolt tightness, and grounding. Test results are compared to industry standards. The evaluation report concludes the transformer assessment, noting any issues found and providing recommendations.

Uploaded by

Joriel Ines
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
157 views5 pages

Transformer Test Form

The document provides test results and evaluation of a power transformer. It includes 6 electrical tests measuring winding resistance, turn ratio, insulation resistance, polarization index, insulation power factor, and oil dielectric breakdown voltage. Mechanical inspections checked the high voltage bushing, connections, bolt tightness, and grounding. Test results are compared to industry standards. The evaluation report concludes the transformer assessment, noting any issues found and providing recommendations.

Uploaded by

Joriel Ines
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 5

POWER TRANSFORMER

Date
Project
Location
Client

Technical Specification
Manufacturer Rated Power
Type Rated Voltage
Vector Group Frequency
Cooling System Phase
Date Manufacture % Impedance @ Tap
Total Lifting Wt. 9
Standard
Designation
Serial Number

Test Applied No. 1 Winding Resistance Test


Date of Test Test Instrument
Time Make HUAZHENG
Weather Model HZ-3120A
Ambient Temp. / RH% Serial Number HZ19201090604-02

Primary Winding Test Current: 2.5A / Winding Temperature: Maximum %


Tap No. H1-H2 (milli Ohms) H2-H3 (milli Ohms) H3-H1 (milli Ohms) Deviation

Secondary Winding Test Current: 20A / Winding Temperature:


Tap No. X1-X0 (milli Ohms) X2-X0 (milli Ohms) X3-X0 (milli Ohms)

Remarks:
As per IEEE STD 62-1995 Percent Unbalanced must be within +/- 5.0%
Test Applied No. 2 Turn Ratio Test
Date of Test Test Instrument
Time Make HUAZHENG
Weather Model HZBB-10A
Ambient Temp. / RH% Serial Number HZ19201090604-03
Tap Tap Voltage Rated Measured Value
No. Of H1-H2 % H2-H3 % H3-H1 %
(V) Ratio X1-X2 Error X2-X3 Error X3-X1 Error

Page | 1 of 3
Remarks:
As per IEEE STD 62-1995 Percent error must within +/- 0.5%

Test Applied No. 4 Insulation & Power Factor Test


Date Test Instrument
Time Make HUAZHENG
Weather Model HZ-2000B
Ambient Temp. / RH% Serial Number HZ19201090604-04
Test Point Test Voltage Power Loss Current Power Capacitance
(mW) (mA) Factor (%) (nF)
H.V.to L.V.+Earth (GST)
H.V. + L.V. to Earth (GST)
L.V. to H.V+Earth (GST)
HV to LV (UST)
Remarks: As Per ANSI/NETA MTS-2011 Table 100.3
Recommended Power Factor must not greater than 1.0% for Power Transformer and 2.0% for Distribution Transformer.
Test Applied No. 3 Insulation Resistance Test
Date Test Instrument
Time Make REED INSTRUMENTS
Weather Model R5002
Ambient Temp. / RH% Serial Number 11092958

Test Point Test 15sec. 30sec. 60sec. 600 sec. P.I.


Voltage
Primary Ground
Primary-Secondary
Secondary-Ground
Remarks: As per ANSI/NETA MTS 2011 - Table 100.5; the Minimum Insulation Resistance for 0 to 600V Transformer coil
rating must be 100 MΩ, for 601 to 5000V transformer coil rating must be 1000 MΩ, and for greater than 5000V coil rating
must be 5000 MΩ.

Page | 2 of 4
Test Applied No. 5 Oil Dielectric Breakdown Voltage Test
Date Test
Time Make HUAZHENG
Weather Model HZJQ-1B
Amb. Temp./RH% Serial Number HZ19201090604-01

Test Standard Oil Sample Main Body


IEC 60156 Main Body Conservator

Oil Temperature Top Conservator Bottom OLTC


Test No.
1
2
3
4
5
Average
Remarks: As Per ANSI/IEEE C57.106-2002 Table 100.4.1 (ASTM Method: D877) (IN SERVICE)
Recommendation insulating oil value above 26kV

Page | 3 of 4
Power Transformer
Evaluation Report
Electrical Test:
Winding Resistance Test
Turn Ratio Test
Insulation Resistance Test
Polarization Index Test
Insulation Power Factor Test
Oil Dielectric Breakdown Voltage Test

Mechanical & Visual Inspection:


H.V. Bushing Appearance
H.V. Connection Tightness
Bolt Tightness and Torque
Frame and Body Grounding

As Found:

Remarks/Recommendation:

Conducted by: Noted by: Witnessed by:

JORIEL M. INES, REE ARVIN L. ABOGADIL, PEE


T & C Engineer General Manager
Lower Valley Engineering Lower Valley Engineering

Page | 4 of 4