Solenoid Driver KFD2-SL2-Ex1.

LK

Features Assembly

• 1-channel isolated barrier


• 24 V DC supply (Power Rail)
Front view
• Output 45 mA at 11.2 V DC
Removable terminal
• Logic input, non-polarized blue
• Error message output
• Line fault detection (LFD)
1 2 3
4 5 6
LED yellow:
• Up to SIL2 acc. to IEC 61508 Status KFD2-SL2-Ex1.LK
LED green:
Power supply

Function
LED red: OUT CHK PWR

LB/SC
This isolated barrier is used for intrinsic safety applications. I II

It supplies power to solenoids, LEDs, and audible alarms,


LB/SC
located in a hazardous area. Position I: ON
It is controlled via a logic signal. The input has two defined Position II: OFF 7 8 9
10 11 12

states: 1-Signal = 16 V DC ... 30 V DC, 0-


13 14 15

Signal = 0 V DC ... 5 V DC.


At full load, 11.2 V at 45 mA is available for the hazardous area
application. Removable terminals
green
If the field impedance is > 10 kΩ for lead breakage or < 50 Ω
for short circuits a line fault is detected.
During an error condition, the fault indication output de-
energizes.
A fault is signalized by LEDs acc. to NAMUR NE44 and a
separate collective error message output.

Connection
200542_eng.xml

KFD2-SL2-Ex1.LK

1+ 7
Date of issue 2011-10-24

2-
V
3- 8 (+/-)

10
11 ERR
12
Release date 2011-10-24 16:18

14+
15-
24 V DC

ERR 24 V DC
Zone 0, 1, 2 Power Rail Zone 2

Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 1
Technical data KFD2-SL2-Ex1.LK

General specifications
Signal type Digital Output
Supply
Connection Power Rail or terminals 14+, 15-
Rated voltage 19 ... 30 V DC
Power consumption ≤ 1.9 W at 45 mA output current
Input
Connection terminals 7, 8
Input current approx. 3 mA
Signal level 1-signal: 16 ... 30 V DC
0-signal: 0 ... 5 V DC
Output
Output I
Connection terminals 1+, 2- or 3-
Internal resistor Ri 270 Ω
Current Ie ≤ 45 mA
Voltage Ue ≥ 11.2 V
Open loop voltage Us ≥ 23.5 V
Output signal These values are valid for the rated operational voltage 19 ... 30 V DC.
Energized/De-energized delay ≤ 20 ms / ≤ 20 ms
Line fault detection signal at short-circuit RB < 50 Ω, lead breakage RB > 10 kΩ ; test current < 650 µA
Output II fault signal
Connection terminals 10, 11, 12 , non-intrinsically safe
Contact loading 253 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load
Mechanical life 2 x 107 switching cycles
Energized/De-energized delay ≤ 20 ms / ≤ 20 ms
Electrical isolation
Input/power supply functional insulation acc. to EN 50178, rated insulation voltage 50 Veff
Directive conformity
Electromagnetic compatibility
Directive 2004/108/EC EN 61326-1:2006 , EN 61000-6-4:2007
Low voltage
Directive 2006/95/EC EN 50178:1997
Conformity
Electromagnetic compatibility NE 21:2006
Protection degree IEC 60529
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Protection degree IP20
Mass approx. 150 g
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in) , housing type B2
Data for application in connection
with Ex-areas
EC-Type Examination Certificate ZELM 99 ATEX 0015 , for additional certificates see www.pepperl-fuchs.com
Group, category, type of protection ¬ II (1)GD [Ex ia] IIC, [Ex iaD] [circuit(s) in zone 0/1/2]
Output I Ex ia IIC, Ex iaD
Voltage Uo 28 V
200542_eng.xml

Current Io 110 mA
Power Po 770 mW (linear characteristic)
Supply
Maximum safe voltage Um 40 V (Attention! The rated voltage can be lower.)
Date of issue 2011-10-24

Input
Maximum safe voltage Um 60 V (Attention! The rated voltage can be lower.)
Collective error indication
Maximum safe voltage Um 40 V (Attention! The rated voltage can be lower.)
Statement of conformity TÜV 02 ATEX 1820 X
Group, category, type of protection, ¬ II 3G Ex nA nC IIC T4
temperature class
Release date 2011-10-24 16:18

Output II
Contact loading 50 V AC/2 A/cos φ > 0.7; 40 V DC/1 A resistive load
Electrical isolation
Output I/other circuits safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 94/9/EC EN 60079-0:2006, EN 60079-11:2007 , EN 60079-15:2005 , EN 61241-11:2006, EN 61241-0:2006

Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 2
Technical data KFD2-SL2-Ex1.LK

General information
Supplementary information EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of
Conformity and instructions have to be observed where applicable. For information see www.pepperl-
fuchs.com.

Output characteristics

Output circuit diagram Output characteristic

Ri U

Us
Us

Ue

Ie I

Accessories

Power feed module KFD2-EB2


The power feed module is used to supply the devices with 24 V DC via the Power Rail. The fuse-protected power feed module
can supply up to 100 individual devices depending on the power consumption of the devices. A galvanically isolated mechanical
contact uses the Power Rail to transmit collective error messages.

Power Rail UPR-03


The Power Rail UPR-03 is a complete unit consisting of the electrical inset and an aluminium profile rail 35 mm x 15 mm. To make
electrical contact, the devices are simply engaged.

Profile Rail K-DUCT with Power Rail


The profile rail K-DUCT is an aluminum profile rail with Power Rail insert and two integral cable ducts for system and field cables.
Due to this assembly no additional cable guides are necessary.

Power Rail and Profile Rail must not be fed via the device terminals of the individual devices!

Attention
200542_eng.xml
Date of issue 2011-10-24
Release date 2011-10-24 16:18

Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany