Get 8432
Get 8432
that to be followed?
Yes, all the T60 features can accommodate autotransformer protection and some
windings configuration rules are applicable to ensure proper operation of the Percent
Differential Protection element.
AUTOTRANSFORMER
PERCENT
DIFFERENTIAL
PROTECTION
i2 CT2 LV
HV
CT1
i1
i3
CT3
(3 phases)
T60
Example;
672 MVA autotransformer, ratio of 500kV/230kV, with CT ratios as shown in the
diagram above: CT1=1000:5, CT2=2000:5, CT3=2500:5
When the rules mention above are followed, the T60 scales the secondary currents from
the different CT internally, thus resulting in zero differential current under normal
conditions. The secondary compensated differential-, and restraint-currents currents are:
v v v
Id = i1sec + i 2 sec + i3sec = 0 and Ir = max( abs (i1sec , i 2 sec , i3sec ))
The autotransformer configuration per URPC: