01 CC
01 CC
NEMA Rated Full Voltage Power Devices Magnetic Nonreversing Starters (CR307, CR407, CR308, CR408)
GE Fastrac Program Information........................................................1-5 (continued)
Application Information and Technical Data (300-Line) ..........1-6 Nonfusible and Fusible Part Number Configuration
Magnetic Nonreversing Starters (CR306, CR386) Size 0-2, NEMA Type 1 (CR308).......................................................1-36
Basic Features (300-Line) and Technical Features Size 0-4, NEMA Type 1, 3R, 12, 4/4X (CR408) ...........................1-39
(CR306, CR386)..........................................................................................1-9 Thermal Magnetic Circuit Breaker Type (CR307, CR407) ......1-44
Non-combination, NEMA Sizes 00-9 with Thermal Overload Thermal Magnetic Part Number Configuration
Relays — Application Information and Selection Instructions Size 0-2, NEMA Type 1 (CR307).......................................................1-45
(CR306, CR386).......................................................................................1-10 Size 0-4, NEMA Type 1, 3R, 12, 4/4X (CR407) ...........................1-48
Non-combination, NEMA Sizes 00-9 Outlines and Dimensions .....................................................................1-61
with Thermal Overload Relays (CR306, CR386) ......................1-11 Mag-Break Magnetic Nonreversing Starters (CR387, CR487)
Non-combination, NEMA Sizes 1-6 with Solid State Overload Application Information and Selection Instructions ...............1-52
Relays — Selection Instructions and Technical Features Mag-Break Circuit Breaker Type (CR387, CR487) .....................1-53
(CR306) .......................................................................................................1-13 Mag-Break Part Number Configuration
Non-combination, NEMA Sizes 1-6 Size 0-2, NEMA Type 1 (CR387).......................................................1-54
with Solid State Overload Relays ..................................................1-14 Size 0-4, NEMA Type 1, 3R, 12, 4/4X (CR487) ...........................1-57
Outlines and Dimensions (CR306, CR386)....................................1-15 Outlines and Dimensions .....................................................................1-61
Magnetic Reversing Starters (CR309) Magnetic Reversing Starters (CR310, CR410, CR311, CR411)
Application Information and Selection Instructions ...............1-19 Application Information and Selection Instructions ...............1-66
Non-combination, NEMA Sizes 00-7 Nonfusible Disconnect Type (CR311, CR411)..............................1-67
with Thermal Overload Relays, Three-Phase ..........................1-20 Fusible Disconnect Type (CR311, CR411) .....................................1-68
Non-combination, NEMA Sizes 00-1 Nonfusible and Fusible Part Number Configuration
with Thermal Overload Relays, Single-Phase..........................1-21 Size 0-4, NEMA Type 1, 3R, 12, 4/4X (CR411) ...........................1-70
Outlines and Dimensions (CR309)....................................................1-22 Thermal Magnetic Circuit Breaker Type (CR310, CR410) ......1-75
Magnetic Two-Speed Starters (CR309) Thermal Magnetic Part Number Configuration
Application Information and Selection Instructions ...............1-26 Size 0-4, NEMA Type 1, 3R, 12, 4/4X (CR410) ...........................1-76
Non-combination, NEMA Sizes 0-5 Outlines and Dimensions .....................................................................1-86
with Thermal Overload Relays, Two-Winding.........................1-27 Mag-Break Magnetic Reversing Starters (CR390, CR490)
Non-combination, NEMA Sizes 0-5 Application Information and Selection Instructions ...............1-80
with Thermal Overload Relays, One-Winding.........................1-28 Mag-Break Circuit Breaker Type (CR390, CR490) .....................1-81
Outlines and Dimensions (CR309)....................................................1-29 Mag-Break Part Number Configuration
Magnetic Nonreversing Starters (CR307, CR407, CR308, CR408) Size 0-4, NEMA Type 1, 3R, 12, 4/4X (CR490) ...........................1-82
Application Information and Selection Instructions ...............1-32 Outlines and Dimensions .....................................................................1-86
Nonfusible Disconnect Type (CR308, CR408)..............................1-33 Magnetic Two-speed Controllers (CR412, CR413, CR492)
Fusible Disconnect Type (CR308, CR408) .....................................1-34 Application Information and Selection Instructions ...............1-88
Nonfusible Disconnect Type (CR413)..............................................1-89
NOTES:
NOTES:
Other Coil Voltages: See page 1-8 Field Installed Modifications: See pages 1-134 to 1-140
Factory Installed Modifications: See pages 1-126 Extra Auxiliary Contacts: See pages 1-134 to 1-136
to 1-133 Heater Selection Tables: See pages 1-155 to 1-161
Single-Phase
List price includes a holding interlock. One heater (per starter) for sizes 00-2 and two heaters (per starter) for size 3 should be ordered
as separate items. See pages 1-155 to 1-161 for selection. List price $9.00 each, GO-10H.
1Motor full load current should not exceed continuous ampere rating of the starter.
2External reset not included on standard listed forms.
Full Load Current Selection Table
For continuous rated motors, with a service factor of 1.15 to 1.25,
select the heater with maximum motor Amperes equal to or
immediately greater than the motor full-load current (provides a
maximum of 125 percent protection). For continuous rated
motors with no service factor, multiply the full-load current of the
motor by 0.90 and use this value to select the heater.
Open Type, NEMA Sizes 3 (19 lbs.) and 4 (20 lbs.) Open Type, NEMA Size 5 (55 lbs.)
CR306 NEMA Type 1 and 12, Size 6 CR306 Open Type, NEMA Size 6
CR386 Open Type, NEMA Size 7, 115 lbs. CR386 Open Type, NEMA Size 8
Application
These reversing starters are used for full-voltage starting and
reversing of squirrel-cage induction motors up to 600 horsepower,
600 Volts maximum.
These starters are used for single-phase or polyphase motors on
applications where plugging and/or reversing operations are
required.
Refer to page 1-9 for features of basic starter.
Jogging Duty
The horsepower ratings shown in the product tables for CR309 Typical CR309 Reversing Starter
reversing starters are not to be used when operation requires
continuous plug-stop or jogging (inching) duty at a rate in excess 6. Product Notes
of five times per minute or 10 times in 10 minutes. Refer to page Motor full-load current should not exceed continuous ampere
1-6 for information. rating of starter. External reset not included on standard listed
forms (NEMA Type 12).
Product Number Selection Instructions Order heaters by complete Product Number from appropriate
1. Specify by complete Product Number and form. heater tables on pages 1-155 to 1-161.
Example: CR309D103 is a Size 2 reversing starter, three-pole in
NEMA Type 1 enclosure with 230-240-Volt, 60-Hertz coil @ Reference Publications
$1086.00, GO-10G. Descriptive bulletin GEA-10928
Instructions
2. Order forms not listed or with special modifications by complete NEMA Size Publication Number
description using a listed Product Number as reference wherever 00, 0, 1 GEH-5190
2 GEH-4775
possible.
3 GEH-4806
Example: Similar to CR309D103 except with three-position 4 GEH-4807
FORWARD-REVERSE-STOP push button in cover. 5 GEH-4839
Total List Price . . . . . . . . . . . . . $1326.00, GO-10G. 6 GEH-5198
Other Coil Voltages: See page 1-8 Field Installed Modifications: See pages 1-134 to 1-140
Factory Installed Modifications: See pages 1-126 to Extra Auxiliary Contacts: See pages 1-134 to 1-136
1-133 Heater Selection Tables: See pages 1-155 to 1-161
Open Type, NEMA Size 00, 0 and 1 Reversing (Horizontal); 7 3/4 lbs. Open Type, NEMA Size 0 and 1 Reversing (Vertical); 7 1/4 lbs.
Open Type, NEMA Size 2 Reversing (Horizontal), 16 1/4 lbs. Open Type, NEMA Size 2 Reversing (Vertical); 16 1/4 lbs.
Open Type, NEMA Size 3 and 4 Reversing (Horizontal); 49 lbs. Open Type, NEMA Size 3 and 4 Reversing (Vertical); 49 lbs.
Open Type, NEMA Size 5 Reversing (Horizontal); 115 lbs. Open Type, NEMA Size 5 Reversing (Vertical), 115 lbs.
Application
Used for full-voltage operation of two-speed squirrel-cage
induction motors at either speed. Consists of two mechanical
and cross electrical interlocked contactors with two three-leg
block type overload relays, one on each contactor. These
bimetallic relays provide overload protection for each speed.
3-3 pole starters are for Two-Speed, Two Winding motors;
5-3 pole starters are for Two-Speed, One-Winding Consequent
Pole motors.
Proper motor-speed selection is obtained by adding pilot devices Typical NEMA Size 1 Two-Speed Controller in Type 1 Enclosure
to correspond to each of the motor speeds. Refer to page 1-9 for
features of basic starter. Reference Publications
Instructions
NEMA Size Publication Number
Product Number Selection Instructions 0, 1 GEH-5190
2 GEH-4775
1. Specify starter by complete Product Number. 3 GEH-4806
Example: CR309C104AKA @ $744.00, GO-10G. 4 GEH-4807
5 GEH-4839
2. Order forms not listed or with special modifications by com- 6 GEH-5198
plete description using a listed Product Number as reference
wherever possible. Example: Similar to CR309E103AKA except CR309 Magnetic Two-Speed Starters – Contents
with FAST-SLOW-STOP push button in cover.
Application Information and Selection Instructions ...............1-26
Total List Price . . . . . . . . . . $2328.00, GO-10G.
Non-combination, NEMA Sizes 0-5
3. Overload Relay Heaters For NEMA Size 3 Starters with Thermal Overload Relays, Two-Winding.........................1-27
For two-speed, variable torque motors with full-load ampere Non-combination, NEMA Sizes 0-5
rating, on low speed, below the minimum heater ampere rat- with Thermal Overload Relays, One-Winding.........................1-28
ing listed in Size 3 table, page 1-157, contact nearest GE Outlines and Dimensions (CR309)....................................................1-29
Energy Representative for suitable overload provision.
4. 50 Hertz Starters
Pricing for 50 Hertz forms (at standard voltages) is the same
as shown in table for 60 Hertz. Listed prices for 460-480 Volt
also apply to 380-415 Volt, 50 Hertz. See page 1-6 for 380-415
Volt horsepower ratings.
5. Product Notes
The two-winding Product Numbers listed are starters suitable
for wye or closed delta connected motor windings. For open
delta connected motor windings, contact your nearest GE
Energy Representative.
Open form, one-winding starters are wired for constant or
variable torque motor application. Reconnection of control
wiring may be required for constant horsepower application.
Motor full-load current should not exceed continuous ampere
rating of starter. Refer to Coil Table, page 1-8, for other avail-
able coils including 50 Hertz.
External reset not included on standard listed forms (NEMA
Type 12). Order heaters by complete Product Number from
appropriate heater tables on pages 1-157 to 1-161.
Other Coil Voltages: See page 1-8 Field Installed Modifications: See pages 1-134 to 1-140
Factory Installed Modifications: See pages 1-126 to Extra Auxiliary Contacts: See pages 1-134 to 1-136
1-133 Heater Selection Tables: See pages 1-155 to 1-161
Other Coil Voltages: See page 1-8 Field Installed Modifications: See pages 1-134 to 1-140
Factory Installed Modifications: See pages 1-126 to Extra Auxiliary Contacts: See pages 1-134 to 1-136
1-133 Heater Selection Tables: See pages 1-155 to 1-161
Application
These combination starters are used for full voltage starting of
single-speed squirrel-cage induction motors up to 400 horse-
power maximum, 600 Volts maximum. Each starter provides
short-circuit protection by means of a fusible disconnect, a
thermal magnetic trip circuit breaker, or circuit interrupter func-
tion with a nonfusible disconnect switch.
Features
—Branch circuit protection—is provided by means of a Type
QMR disconnect switch or molded case circuit breaker.
—Mechanism—always controls interrupting switch.
—Easy inspection, maintenance—performed from starter front.
—Optional factory-installed control transformer.
Refer to page 1-9 for features of basic starter. Typical Combination Starter in General Purpose
Type 1 Enclosure
Product Number Selection Instructions
1. Specify starter by complete Product Number. Example:
CR308CT03HB1AAAAA is a Size 1 starter, combination discon- Reference Publications
nect form with 230-240 Volt, 60-Hertz coil and 60-Ampere Instructions
class H fuse clips in Type 1 general-purpose enclosure @ NEMA Size Publication Number
$606.00, GO-10G1. 0, 1 GEH-5190
2 GEH-4774
2. Order special features or forms not listed by complete 3 GEH-4806
4 GEH-4807
description using a listed Product Number as reference. 5 GEH-4838
Example: Similar to CR308CT03HB1AAAAA except with red 6 GEH-5198
indicating light in cover. Total List Price, $696.00, GO-10G1.
3. 50-Hertz Starters CR307, CR407, CR308, CR408 Magnetic Starters – Contents
Pricing of starters for use on 50 Hertz (at standard voltages) is Application Information and Selection Instructions ...............1-32
the same as shown in tables for 60 Hertz. Order by description, Nonfusible Disconnect Type (CR308, CR408)..............................1-33
using a listed form as reference. Refer to page 1-6 for three- Fusible Disconnect Type (CR308, CR408) .....................................1-34
phase horsepower rating at 380-415 Volts, 50 Hertz. Nonfusible and Fusible Part Number Configuration
4. Control Transformer Size 0-2, NEMA Type 1 (CR308).......................................................1-36
All catalog listed CR307 and CR308 combination starters have Size 0-4, NEMA Type 1, 3R, 12, 4/4X (CR408) ...........................1-39
provision for field mounting a standard control circuit trans- Thermal Magnetic Circuit Breaker Type (CR307, CR407) ......1-44
former. Refer to page 1-139 for transformer kit Product Thermal Magnetic Part Number Configuration
Numbers and pricing. Also, see page 1-128 for information on Size 0-2, NEMA Type 1 (CR307).......................................................1-45
factory-installed standard and extra-capacity transformers. Size 0-4, NEMA Type 1, 3R, 12, 4/4X (CR407) ...........................1-48
Specify transformer rating on order. Outlines and Dimensions .....................................................................1-61
5. Product Notes
Motor full-load current should not exceed continuous ampere
rating of starter.
Order heaters by complete Product Number from appropriate
heater tables on pages 1-155 to 1-161.
Digits: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
C R
Steps: Step 1 Step 2 Step 3 Step 4 Step 5 Step 6 Step 7 Step 8 Step 9
To configure the part number, use the tables below to fill in the digit boxes with the
appropriate code. Add list price from each step to arrive at total list for price for starter.
Disconnect with Class H Fuse Clips - For use with Non-Time Delay/Single Element Class H Fuses
200-208V 230-240V 460-480V 575-600V
Max Fuse Clip List Price Max Fuse Clip List Price Max Fuse Clip List Price Max Fuse Clip List Price
NEMA Size Hp (Amps) Code GO-10G1 Hp (Amps) Code GO-10G1 Hp (Amps) Code GO-10G1 Hp (Amps) Code GO-10G1
0 3 30 HA $18.00 3 30 HA $18.00 5 30 H3 $30.00 5 30 H3 $30.00
7 1/2 60 HB $30.00 7 1/2 60 HB $30.00 7 1/2 30 H3 $30.00 10 30 H3 $30.00
1
10 60 H6 $42.00 60 H6 $42.00
10 100 HC $96.00 15 100 HC $96.00 15 60 H6 $42.00 20 60 H6 $42.00
2
25 100 H11 $108.00 25 100 H11 $108.00
1Oversized enclosure included as standard.
Disconnect with Class R Fuse Clips - For use with Time Delay/Dual Element Class RK1/RK5 Fuses
200-208V 230-240V 460-480V 575-600V
Max Fuse Clip List Price Max Fuse Clip List Price Max Fuse Clip List Price Max Fuse Clip List Price
NEMA Size Hp (Amps) Code GO-10G1 Hp (Amps) Code GO-10G1 Hp (Amps) Code GO-10G1 Hp (Amps) Code GO-10G1
0 3 30 RA $27.00 3 30 RA $27.00 5 30 R3 $39.00 5 30 R3 $39.00
5 30 RA $27.00 5 30 RA $27.00 10 30 R3 $39.00 10 30 R3 $39.00
1
7 1/2 60 RB $39.00 7 1/2 60 RB $39.00
10 60 RB $33.00 15 60 RB $33.00 30 R3 $39.00 15 30 R3 $39.00
2
25 60 R6 $51.00 25 60 R6 $51.00
Disconnect with Class J Fuse Clips - For use with Time Delay/Dual Element Class J Fuses
200-208V 230-240V 460-480V 575-600V
Max Fuse Clip List Price Max Fuse Clip List Price Max Fuse Clip List Price Max Fuse Clip List Price
NEMA Size Hp (Amps) Code GO-10G1 Hp (Amps) Code GO-10G1 Hp (Amps) Code GO-10G1 Hp (Amps) Code GO-10G1
0 3 30 J3 $48.00 3 30 J3 $48.00 5 30 J3 $48.00 5 30 J3 $48.00
5 30 J3 $48.00 5 30 J3 $48.00 10 30 J3 $48.00 10 30 J3 $48.00
1
7 1/2 60 J6 $48.00 7 1/2 60 J6 $48.00
10 60 J6 $72.00 15 60 J6 $72.00 30 J3 $60.00 15 30 J3 $60.00
2
25 60 J6 $72.00 25 60 J6 $72.00
GENERAL NOTE:
On NEMA Size 3 & 4 starters, if selecting factory installed and wired operator devices
(Push Buttons, Selector Switches, and/or Pilot Lights) then control circuit fusing, a
control power transformer, or 120V separate sourced control is required when the
protective device is rated greater than 100 Amps.
Digits: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
C R
Steps: Step 1 Step 2 Step 3 Step 4 Step 5 Step 6 Step 7 Step 8 Step 9
To configure the part number, use the tables below to fill in the digit boxes with the appropriate code.
Add list price from each step to arrive at total list for price for starter.
Step 2 (Digits 8, 9) Select Control Voltage (No CPT and Standard Size CPT)
NEMA Size
Control Standard 0 1 2 3 4
No List Price Fuses, List Price Size List Price List Price List Price List Price List Price
Control Circuit Voltage & CPT CPT GO-10G1 No CPT GO-10G1 CPT GO-10G1 GO-10G1 GO-10G1 GO-10G1 GO-10G1
120V w/ Surge Protector (SP) 01 $54.00 F1 $132.00 -
120V 02 $0.00 F2 $132.00 -
240V 03 $0.00 F3 $132.00 -
480V 04 $0.00 F4 $132.00 -
600V 05 $0.00 F5 $132.00 -
208V 08 $0.00 F8 $132.00 -
24V3 09 $0.00 - -
240V/120V w/CPT - - 93 $294.00 $294.00 $352.00 $468.00 $540.00
480V/120V w/CPT - - 94 $294.00 $294.00 $352.00 $468.00 $540.00
600V/120V w/CPT - - 95 $294.00 $294.00 $352.00 $468.00 $540.00
208V/120V w/CPT - - 98 $294.00 $294.00 $352.00 $468.00 $540.00
240V/120V w/CPT & SP - - 33 $348.00 $348.00 $406.00 $522.00 $594.00
480V/120V w/CPT & SP - - 34 $348.00 $348.00 $406.00 $522.00 $594.00
600V/120V w/CPT & SP - - 35 $348.00 $348.00 $406.00 $522.00 $594.00
208V/120V w/CPT & SP - - 38 $348.00 $348.00 $406.00 $522.00 $594.00
240V/24V w/CPT3 - - S3 $294.00 $294.00 $352.00 - -
480V/24V w/CPT3 - - S4 $294.00 $294.00 $352.00 - -
600V/24V w/CPT3 - - S5 $294.00 $294.00 $352.00 - -
208V/24V w/CPT3 - - S8 $294.00 $294.00 $352.00 - -
Note: CPT includes 2 primary fuses and 1 secondary fuse.
324V coils not available for NEMA size 3 & 4.
Disconnect with Class H Fuse Clips - For use with Non-Time Delay/Single Element Class H Fuses
200-208V 230-240V 460-480V 575-600V
Max Fuse Clip List Price Max Fuse Clip List Price Max Fuse Clip List Price Max Fuse Clip List Price
NEMA Size Hp (Amps) Code GO-10G1 Hp (Amps) Code GO-10G1 Hp (Amps) Code GO-10G1 Hp (Amps) Code GO-10G1
0 3 30 HA $18.00 3 30 HA $18.00 5 30 H3 $30.00 5 30 H3 $30.00
7 1/2 60 HB $30.00 7 1/2 60 HB $30.00 7 1/2 30 H3 $30.00 10 30 H3 $30.00
1
10 60 H6 $42.00 60 H6 $42.00
10 100 HC $96.00 15 100 HC $96.00 15 60 H6 $42.00 20 60 H6 $42.00
2
25 100 H1 $108.00 25 100 H1 $108.00
25 200 HD $192.00 30 200 HD $192.00 30 100 H1 $90.00 30 100 H1 $90.00
31
50 200 H2 $216.00 50 200 H2 $216.00
40 400 HE $216.00 50 400 HE $216.00 60 200 H2 $126.00 60 200 H2 $126.00
42
100 400 H4 $216.00 100 400 H4 $216.00
1Oversized enclosure provided as standard with 200Amp Fusible Disconnect
2Oversized enclosure provided as standard with any NEMA Size 4 Fusible/Nonfusible
Disconnect with Class R Fuse Clips - For use with Time Delay/Dual Element Class RK1/RK5 Fuses
200-208V 230-240V 460-480V 575-600V
Max Fuse Clip List Price Max Fuse Clip List Price Max Fuse Clip List Price Max Fuse Clip List Price
NEMA Size Hp (Amps) Code GO-10G1 Hp (Amps) Code GO-10G1 Hp (Amps) Code GO-10G1 Hp (Amps) Code GO-10G1
0 3 30 RA $27.00 3 30 RA $27.00 5 30 R3 $39.00 5 30 R3 $39.00
5 30 RA $27.00 5 30 RA $27.00 10 30 R3 $39.00 10 30 R3 $39.00
1
7 1/2 60 RB $39.00 7 1/2 60 RB $39.00
10 60 RB $33.00 15 60 RB $33.00 30 R3 $39.00 15 30 R3 $39.00
2
25 60 R6 $51.00 25 60 R6 $51.00
20 100 RC $78.00 25 100 RC $78.00 60 R6 $42.00 30 60 R6 $42.00
31
25 200 RD $210.00 30 200 RD $210.00 50 100 R1 $108.00 50 100 R1 $108.00
40 200 RD $120.00 50 200 RD $120.00 100 R1 $108.00 60 100 R1 $108.00
42
100 200 R2 $144.00 100 200 R2 $144.00
1Oversized enclosure provided as standard with 200Amp Fusible Disconnect
2Oversized enclosure provided as standard with any NEMA Size 4 Fusible/Nonfusible
GENERAL NOTE:
On NEMA Size 3 & 4 starters, if selecting factory installed and wired operator devices
(Push Buttons, Selector Switches, and/or Pilot Lights) then control circuit fusing, a
control power transformer, or 120V separate sourced control is required when the
protective device is rated greater than 100 Amps.
Digits: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
C R
Steps: Step 1 Step 2 Step 3 Step 4 Step 5 Step 6 Step 7 Step 8 Step 9
To configure the part number, use the tables below to fill in the digit boxes with the
appropriate code. Add list price from each step to arrive at total list for price for starter.
GENERAL NOTE:
On NEMA Size 3 & 4 starters if selecting factory installed and wired operator devices
(Push Buttons, Selector Switches, and/or Pilot Lights) then control circuit fusing, a
control power transformer, or 120V separate sourced control is required when the
protective device is rated greater than 100 Amps.
Digits: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
C R
Steps: Step 1 Step 2 Step 3 Step 4 Step 5 Step 6 Step 7 Step 8 Step 9
To configure the part number, use the tables below to fill in the digit boxes with the appropriate code.
Add list price from each step to arrive at total list for price for starter.
Step 1 (Digits 1-7) Select NEMA Size and Enclosure
NEMA Type 1 NEMA Type 3R NEMA Type 12 NEMA Type 4/4X
Standard List Oversized List Standard List Oversized List Standard List Oversized List Standard List Oversized List
NEMA Enclosure Price Enclosure Price Enclosure Price Enclosure Price Enclosure Price Enclosure Price Enclosure Price Enclosure Price
Size CR GO-10G1 CR GO-10G1 CR GO-10G1 CR GO-10G1 CR GO-10G1 CR GO-10G1 CR GO-10G1 CR GO-10G1
0 Use CR307 407B5 $724.00 407B6 $732.00 407BR $868.00 407B2 $732.00 407B7 $868.00 407B4 $1164.00 407BS $1410.00
1 Use CR307 407C5 $754.00 407C6 $762.00 407CR $898.00 407C2 $762.00 407C7 $898.00 407C4 $1194.00 407CS $1440.00
2 Use CR307 407D5 $1084.00 407D6 $1152.00 407DR $1288.00 407D2 $1152.00 407D7 $1288.00 407D4 $1836.00 407DS $2082.00
3 407E1 $1632.00 407E5 $1854.00 407E6 $1896.00 407ER $2118.00 407E2 $1896.00 407E7 $2118.00 407E4 $3180.00 407ES $3738.00
4 407F1 $3582.00 407F5 $3972.00 407F6 $4314.00 407FR $4704.00 407F2 $4314.00 407F7 $4704.00 407F4 $5562.00 407FS $6249.00
Note: All enclosures include external overload reset buttons. NEMA 4 enclosures are stainless steel.
Step 2 (Digits 8, 9) Select Control Voltage (No CPT and Standard Size CPT)
NEMA Size
Control Standard 0 1 2 3 4
No List Price Fuses, List Price Size List Price List Price List Price List Price List Price
Control Circuit Voltage & CPT CPT GO-10G1 No CPT GO-10G1 CPT GO-10G1 GO-10G1 GO-10G1 GO-10G1 GO-10G1
120V w/ Surge Protector (SP) 01 $54.00 F1 $132.00 -
120V 02 $0.00 F2 $132.00 -
240V 03 $0.00 F3 $132.00 -
480V 04 $0.00 F4 $132.00 -
600V 05 $0.00 F5 $132.00 -
208V 08 $0.00 F8 $132.00 -
24V1 09 $0.00 - -
240V/120V w/CPT - - 93 $294.00 $294.00 $352.00 $468.00 $540.00
480V/120V w/CPT - - 94 $294.00 $294.00 $352.00 $468.00 $540.00
600V/120V w/CPT - - 95 $294.00 $294.00 $352.00 $468.00 $540.00
208V/120V w/CPT - - 98 $294.00 $294.00 $352.00 $468.00 $540.00
240V/120V w/CPT & SP - - 33 $348.00 $348.00 $406.00 $522.00 $594.00
480V/120V w/CPT & SP - - 34 $348.00 $348.00 $406.00 $522.00 $594.00
600V/120V w/CPT & SP - - 35 $348.00 $348.00 $406.00 $522.00 $594.00
208V/120V w/CPT & SP - - 38 $348.00 $348.00 $406.00 $522.00 $594.00
240V/24V w/CPT1 - - S3 $294.00 $294.00 $352.00 - -
480V/24V w/CPT1 - - S4 $294.00 $294.00 $352.00 - -
600V/24V w/CPT1 - - S5 $294.00 $294.00 $352.00 - -
208V/24V w/CPT1 - - S8 $294.00 $294.00 $352.00 - -
Step 2 (Digits 8, 9) Select Control Voltage (Extra Capacity CPT + 100VA and 200VA)
NEMA Size NEMA Size
Standard 0 1 2 3 4 Standard 0 1 2 3 4
Size List Price List Price List Price List Price List Price Size List Price2 List Price2 List Price2 List Price List Price
Control Circuit Voltage & CPT CPT + 100VA GO-10G1 GO-10G1 GO-10G1 GO-10G1 GO-10G1 CPT + 200VA GO-10G1 GO-10G1 GO-10G1 GO-10G1 GO-10G1
120V w/ Surge Protector (SP) - -
120V - -
240V - -
480V - -
600V - -
208V - -
24V1 - -
240V/120V w/CPT 13 $420.00 $420.00 $504.00 $600.00 $660.00 23 $523.00 $523.00 $618.00 $714.00 $775.00
480V/120V w/CPT 14 $420.00 $420.00 $504.00 $600.00 $660.00 24 $523.00 $523.00 $618.00 $714.00 $775.00
600V/120V w/CPT 15 $420.00 $420.00 $504.00 $600.00 $660.00 25 $523.00 $523.00 $618.00 $714.00 $775.00
208V/120V w/CPT 18 $420.00 $420.00 $504.00 $600.00 $660.00 28 $523.00 $523.00 $618.00 $714.00 $775.00
240V/120V w/CPT & SP 53 $474.00 $474.00 $558.00 $654.00 $714.00 63 $577.00 $577.00 $672.00 $768.00 $829.00
480V/120V w/CPT & SP 54 $474.00 $474.00 $558.00 $654.00 $714.00 64 $577.00 $577.00 $672.00 $768.00 $829.00
600V/120V w/CPT & SP 55 $474.00 $474.00 $558.00 $654.00 $714.00 65 $577.00 $577.00 $672.00 $768.00 $829.00
208V/120V w/CPT & SP 58 $474.00 $474.00 $558.00 $654.00 $714.00 68 $577.00 $577.00 $672.00 $768.00 $829.00
240V/24V w/CPT1 A3 $420.00 $420.00 $504.00 - - B3 $523.00 $523.00 $618.00 - -
480V/24V w/CPT1 A4 $420.00 $420.00 $504.00 - - B4 $523.00 $523.00 $618.00 - -
600V/24V w/CPT1 A5 $420.00 $420.00 $504.00 - - B5 $523.00 $523.00 $618.00 - -
208V/24V w/CPT1 A8 $420.00 $420.00 $504.00 - - B8 $523.00 $523.00 $618.00 - -
Note: CPT includes 2 primary fuses and 1 secondary fuse.
124V coils not available for NEMA size 3 & 4.
2Requires Oversized Enclosure for NEMA sizes 0-2. Select proper NEMA size and enclosure type from Step 1 (Digits 1-7) Table, and adjust price accordingly.
GENERAL NOTE:
On NEMA Size 3 & 4 starters, if selecting factory installed and wired operator devices
(Push Buttons, Selector Switches, and/or Pilot Lights) then control circuit fusing, a
control power transformer, or 120V separate sourced control is required when the
protective device is rated greater than 100 Amps.
Application
The CR387/487 nonreversing starters are designed for more
accurate fault protection for motor circuits by utilizing Spectra™
Mag-Break motor circuit protectors for sizes 0-4 and Type TJC
for size 5.
Spectra™ Features
—Spectra™ Mag-Break motor circuit protector—provides protec-
Typical CR387 Starter with Mag-Break Protector with
tion against faults. Has adjustable trip.
Current Limiter
—Meets NEC standards—continuous current ratings and
adjustable instantaneous trip ranges meet NEC standards on
motor full-load and locked rotor currents. Reference Publications
—Can eliminate nuisance tripping and provide fault protection— Instructions
NEMA Size Publication Number
by setting the Mag-Break instantaneous trip point just above 0,1 GEH-5190
transient motor inrush current. 2 GEH-4774
—Less than one cycle clearing time—to open and clear a fault. 3 GEH-4806
4 GEH-4807
5 GEH-4839
Product Number Selection Instructions
1. Order by complete Product Number. CR387, CR487, Mag-Break Magnetic Starters– Contents
Example: A size 2 combination starter is required to control a Application Information and Selection Instructions ...............1-52
15-hp, 230-Volt, 60-Hertz nonreversing motor with FLA of 42.0. Mag-Break Circuit Breaker Type (CR387, CR487) .....................1-53
The starter will include a Mag-Break motor circuit protector, Mag-Break Part Number Configuration
230-240 Volt, 60-Hertz coil, and a three-leg block overload. Size 0-2, NEMA Type 1 (CR387).......................................................1-54
Order 1—CR387DT03MJ1AAAAA at $1122.00, GO-10G1, and Size 0-4, NEMA Type 1, 3R, 12, 4/4X (CR487) ...........................1-57
3—CR123C460B heaters. List Price $9.00 each, GO-10H. Outlines and Dimensions .....................................................................1-61
2. Order special features or forms not listed by complete descrip-
tion using a listed Product Number as reference. Example:
Similar to CR387DT03MJ1AAAAA except with OFF-ON selector
switch in cover.
Total List Price . . . . . . . . . . . . . . . . . . . . . . . $1170.00, GO-10G1.
3. 50 Hertz Starters
Pricing for 50 Hertz forms (at standard voltages) is the same as
shown in table for 60 Hertz. Listed prices for 460-480 Volt also
apply to 380-415 Volt, 50 Hertz. See page 1-6 for 380-415 Volt
horsepower ratings.
4. Product Notes
Motor full-load current should not exceed continuous ampere
rating of starter.
Digits: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
C R
Steps: Step 1 Step 2 Step 3 Step 4 Step 5 Step 6 Step 7 Step 8 Step 9
To configure the part number, use the tables below to fill in the digit boxes with the
appropriate code. Add list price from each step to arrive at total list for price for starter.
GENERAL NOTE:
If selecting factory installed and wired operator devices (Push Buttons, Selector
Switches, and/or Pilot Lights) control circuit fusing, a control power transformer, or
24V/120V separate sourced control is required, regardless of protective device rating.
Digits: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
C R
Steps: Step 1 Step 2 Step 3 Step 4 Step 5 Step 6 Step 7 Step 8 Step 9
To configure the part number, use the tables below to fill in the digit boxes with the appropriate code.
Add list price from each step to arrive at total list for price for starter.
Step 2 (Digits 8, 9) Select Control Voltage (No CPT and Standard Size CPT)
NEMA Size
Control Standard 0 1 2 3 4
No List Price Fuses, List Price Size List Price List Price List Price List Price List Price
Control Circuit Voltage & CPT CPT GO-10G1 No CPT GO-10G1 CPT GO-10G1 GO-10G1 GO-10G1 GO-10G1 GO-10G1
120V w/ Surge Protector (SP) 01 $54.00 F1 $132.00 -
120V 02 $0.00 F2 $132.00 -
240V 03 $0.00 F3 $132.00 -
480V 04 $0.00 F4 $132.00 -
600V 05 $0.00 F5 $132.00 -
208V 08 $0.00 F8 $132.00 -
24V1 09 $0.00 - -
240V/120V w/CPT - - 93 $294.00 $294.00 $352.00 $468.00 $540.00
480V/120V w/CPT - - 94 $294.00 $294.00 $352.00 $468.00 $540.00
600V/120V w/CPT - - 95 $294.00 $294.00 $352.00 $468.00 $540.00
208V/120V w/CPT - - 98 $294.00 $294.00 $352.00 $468.00 $540.00
240V/120V w/CPT & SP - - 33 $348.00 $348.00 $406.00 $522.00 $594.00
480V/120V w/CPT & SP - - 34 $348.00 $348.00 $406.00 $522.00 $594.00
600V/120V w/CPT & SP - - 35 $348.00 $348.00 $406.00 $522.00 $594.00
208V/120V w/CPT & SP - - 38 $348.00 $348.00 $406.00 $522.00 $594.00
240V/24V w/CPT1 - - S3 $294.00 $294.00 $352.00 - -
480V/24V w/CPT1 - - S4 $294.00 $294.00 $352.00 - -
600V/24V w/CPT1 - - S5 $294.00 $294.00 $352.00 - -
208V/24V w/CPT1 - - S8 $294.00 $294.00 $352.00 - -
124V coils not available for NEMA size 3 and 4.
GENERAL NOTE:
If selecting factory installed and wired operator devices (Push Buttons, Selector
Switches, and/or Pilot Lights) control circuit fusing, a control power transformer, or
24V/120V separate sourced control is required, regardless of protective device rating.
ON
1.19
(30.2)
1.63
(41.3)
6.75 3 Mounting Holes
5
(171.5) for 16 " Hardware
10.00
(254.0)
CR307, CR387, CR308 (excludes 100A, 600V fuse clips); Type 1, Standard Size Enclosure
19.96
(507.0)
R0.41
(R10.3)
ON
OFF
32.44 33.32
(824.0) (846.3)
CR308 (includes 100A, 600V fuse clips); Type 1, Standard Size Enclosure
NEMA Type 1, CR307, CR308, CR387: Size 5 NEMA Type 1, CR307, CR308: Size 6 Floor-Mounted
OFF
G B
E
H F F
ON
OFF
G B
E
H F F
ON
OFF
G B
E
H F F
Application
Used for full-voltage starting and reversing of squirrel cage induc-
tion motors up to 200 horsepower maximum, 600 Volts maximum.
Provides short-circuit protection, either by means of fuses or a
circuit breaker. Consists of a reversing controller and a fusible or
nonfusible disconnect switch or circuit breaker to provide branch
circuit protection.
Three-leg block overload relay provides overload protection on
starters. Undervoltage protection or release can be provided CR310 NEMA Size 2 Combination Reverser in
by using appropriate accessory controls. Refer to page 1-9 for NEMA Type 1 Enclosure with Circuit Breaker
features of basic starter.
Digits: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
C R
Steps: Step 1 Step 2 Step 3 Step 4 Step 5 Step 6 Step 7 Step 8 Step 9
To configure the part number, use the tables below to fill in the digit boxes with the appropriate code.
Add list price from each step to arrive at total list for price for starter.
Step 2 (Digits 8, 9) Select Control Voltage (No CPT and Standard Size CPT)
NEMA Size
Control Standard 0 1 2 3 4
No List Price Fuses, List Price Size List Price List Price List Price List Price List Price
Control Circuit Voltage & CPT CPT GO-10G1 No CPT GO-10G1 CPT GO-10G1 GO-10G1 GO-10G1 GO-10G1 GO-10G1
120V w/ Surge Protector (SP) 01 $54.00 F1 $132.00 -
120V 02 $0.00 F2 $132.00 -
240V 03 $0.00 F3 $132.00 -
480V 04 $0.00 F4 $132.00 -
600V 05 $0.00 F5 $132.00 -
208V 08 $0.00 F8 $132.00 -
24V1 09 $0.00 - -
240V/120V w/CPT - - 93 $294.00 $294.00 $352.00 $468.00 $540.00
480V/120V w/CPT - - 94 $294.00 $294.00 $352.00 $468.00 $540.00
600V/120V w/CPT - - 95 $294.00 $294.00 $352.00 $468.00 $540.00
208V/120V w/CPT - - 98 $294.00 $294.00 $352.00 $468.00 $540.00
240V/120V w/CPT & SP - - 33 $348.00 $348.00 $406.00 $522.00 $594.00
480V/120V w/CPT & SP - - 34 $348.00 $348.00 $406.00 $522.00 $594.00
600V/120V w/CPT & SP - - 35 $348.00 $348.00 $406.00 $522.00 $594.00
208V/120V w/CPT & SP - - 38 $348.00 $348.00 $406.00 $522.00 $594.00
240V/24V w/CPT1 - - S3 $294.00 $294.00 $352.00 - -
480V/24V w/CPT1 - - S4 $294.00 $294.00 $352.00 - -
600V/24V w/CPT1 - - S5 $294.00 $294.00 $352.00 - -
208V/24V w/CPT1 - - S8 $294.00 $294.00 $352.00 - -
Note: CPT includes 2 primary fuses and 1 secondary fuse.
124V coils not available for NEMA size 3 & 4.
Disconnect with Class H Fuse Clips - For use with Non-Time Delay/Single Element Class H Fuses
200-208V 230-240V 460-480V 575-600V
Max Fuse Clip List Price Max Fuse Clip List Price Max Fuse Clip List Price Max Fuse Clip List Price
NEMA Size Hp (Amps) Code GO-10G1 Hp (Amps) Code GO-10G1 Hp (Amps) Code GO-10G1 Hp (Amps) Code GO-10G1
0 3 30 HA $18.00 3 30 HA $18.00 5 30 H3 $30.00 5 30 H3 $30.00
7 1/2 30 H3 $30.00 10 30 H3 $30.00
1
7 1/2 60 HB $30.00 7 1/2 60 HB $30.00 10 60 H6 $42.00 60 H6 $42.00
15 60 H6 $42.00 20 60 H6 $42.00
2
10 100 HC $96.00 15 100 HC $96.00 25 100 H1 $108.00 25 100 H1 $108.00
30 100 H1 $90.00 30 100 H1 $90.00
3
25 200 HD $192.00 30 200 HD $192.00 50 200 H2 $216.00 50 200 H2 $216.00
60 200 H2 $126.00 60 200 H2 $126.00
4
40 400 HE $216.00 50 400 HE $216.00 100 400 H4 $216.00 100 400 H4 $216.00
Disconnect with Class R Fuse Clips - For use with Time Delay/Dual Element Class RK1/RK5 Fuses
200-208V 230-240V 460-480V 575-600V
Max Fuse Clip List Price Max Fuse Clip List Price Max Fuse Clip List Price Max Fuse Clip List Price
NEMA Size Hp (Amps) Code GO-10G1 Hp (Amps) Code GO-10G1 Hp (Amps) Code GO-10G1 Hp (Amps) Code GO-10G1
0 3 30 RA $27.00 3 30 RA $27.00 5 30 R3 $39.00 5 30 R3 $39.00
5 30 RA $27.00 5 30 RA $27.00 10 30 R3 $39.00 10 30 R3 $39.00
1
7 1/2 60 RB $39.00 7 1/2 60 RB $39.00
30 R3 $39.00 15 30 R3 $39.00
2
10 60 RB $33.00 15 60 RB $33.00 25 60 R6 $51.00 25 60 R6 $51.00
60 R6 $42.00 30 60 R6 $42.00
3 20 100 RC $78.00 25 100 RC $78.00 50 100 R1 $108.00 50 100 R1 $108.00
25 200 RD $210.00 30 200 RD $210.00
100 R1 $108.00 60 100 R1 $108.00
4
40 200 RD $120.00 50 200 RD $120.00 100 200 R2 $144.00 100 200 R2 $144.00
Disconnect with Class J Fuse Clips - For use with Time Delay/Dual Element Class J Fuses
200-208V 230-240V 460-480V 575-600V
Max Fuse Clip List Price Max Fuse Clip List Price Max Fuse Clip List Price Max Fuse Clip List Price
NEMA Size Hp (Amps) Code GO-10G1 Hp (Amps) Code GO-10G1 Hp (Amps) Code GO-10G1 Hp (Amps) Code GO-10G1
0 3 30 J3 $48.00 3 30 J3 $48.00 5 30 J3 $48.00 5 30 J3 $48.00
5 30 J3 $48.00 5 30 J3 $48.00 10 30 J3 $48.00 10 30 J3 $48.00
1
7 1/2 60 J6 $48.00 7 1/2 60 J6 $48.00
30 J3 $60.00 15 30 J3 $60.00
2
10 60 J6 $72.00 15 60 J6 $72.00 25 60 J6 $72.00 25 60 J6 $72.00
60 J6 $96.00 30 60 J6 $96.00
3 20 100 J1 $162.00 25 100 J1 $162.00 50 100 J1 $162.00 50 100 J1 $162.00
25 200 J2 $246.00 30 200 J2 $246.00
100 J1 $210.00 60 100 J1 $210.00
4
40 200 J2 $246.00 50 200 J2 $246.00 100 200 J2 $246.00 100 200 J2 $246.00
GENERAL NOTE:
On NEMA Size 3 & 4 starters, if selecting factory installed and wired operator devices
(Push Buttons, Selector Switches, and/or Pilot Lights) then control circuit fusing, a
control power transformer, or 120V separate sourced control is required when the
protective device is rated greater than 100 Amps.
Digits: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
C R
Steps: Step 1 Step 2 Step 3 Step 4 Step 5 Step 6 Step 7 Step 8 Step 9
To configure the part number, use the tables below to fill in the digit boxes with the appropriate code.
Add list price from each step to arrive at total list for price for starter.
Step 2 (Digits 8, 9) Select Control Voltage (No CPT and Standard Size CPT)
NEMA Size
Control Standard 0 1 2 3 4
No List Price Fuses, List Price Size List Price List Price List Price List Price List Price
Control Circuit Voltage & CPT CPT GO-10G1 No CPT GO-10G1 CPT GO-10G1 GO-10G1 GO-10G1 GO-10G1 GO-10G1
120V w/ Surge Protector (SP) 01 $54.00 F1 $132.00 -
120V 02 $0.00 F2 $132.00 -
240V 03 $0.00 F3 $132.00 -
480V 04 $0.00 F4 $132.00 -
600V 05 $0.00 F5 $132.00 -
208V 08 $0.00 F8 $132.00 -
24V1 09 $0.00 - -
240V/120V w/CPT - - 93 $294.00 $294.00 $352.00 $468.00 $540.00
480V/120V w/CPT - - 94 $294.00 $294.00 $352.00 $468.00 $540.00
600V/120V w/CPT - - 95 $294.00 $294.00 $352.00 $468.00 $540.00
208V/120V w/CPT - - 98 $294.00 $294.00 $352.00 $468.00 $540.00
240V/120V w/CPT & SP - - 33 $348.00 $348.00 $406.00 $522.00 $594.00
480V/120V w/CPT & SP - - 34 $348.00 $348.00 $406.00 $522.00 $594.00
600V/120V w/CPT & SP - - 35 $348.00 $348.00 $406.00 $522.00 $594.00
208V/120V w/CPT & SP - - 38 $348.00 $348.00 $406.00 $522.00 $594.00
240V/24V w/CPT1 - - S3 $294.00 $294.00 $352.00 - -
480V/24V w/CPT1 - - S4 $294.00 $294.00 $352.00 - -
600V/24V w/CPT1 - - S5 $294.00 $294.00 $352.00 - -
208V/24V w/CPT1 - - S8 $294.00 $294.00 $352.00 - -
Note: CPT includes 2 primary fuses and 1 secondary fuse.
124V coils not available for NEMA size 3 & 4.
GENERAL NOTE:
On NEMA Size 3 & 4 starters, if selecting factory installed and wired operator devices
(Push Buttons, Selector Switches, and/or Pilot Lights) then control circuit fusing, a
control power transformer, or 120V separate sourced control is required when the
protective device is rated greater than 100 Amps.
Application
Used for full-voltage starting and reversing of squirrel cage induc-
tion motors up to 200 horsepower maximum, 600 Volts maximum.
Consists of Spectra™ Mag-Break motor circuit protector for branch
circuit protection (Sizes 0-4), reversing controller, and three-leg
block overload relay. Refer to page 1-9 for features of basic starter.
Digits: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
C R
Steps: Step 1 Step 2 Step 3 Step 4 Step 5 Step 6 Step 7 Step 8 Step 9
To configure the part number, use the tables below to fill in the digit boxes with the appropriate code.
Add list price from each step to arrive at total list for price for starter.
Step 2 (Digits 8, 9) Select Control Voltage (No CPT and Standard Size CPT)
NEMA Size
Control Standard 0 1 2 3 4
No List Price Fuses, List Price Size List Price List Price List Price List Price List Price
Control Circuit Voltage & CPT CPT GO-10G1 No CPT GO-10G1 CPT GO-10G1 GO-10G1 GO-10G1 GO-10G1 GO-10G1
120V w/ Surge Protector (SP) 01 $54.00 F1 $132.00 -
120V 02 $0.00 F2 $132.00 -
240V 03 $0.00 F3 $132.00 -
480V 04 $0.00 F4 $132.00 -
600V 05 $0.00 F5 $132.00 -
208V 08 $0.00 F8 $132.00 -
24V1 09 $0.00 - -
240V/120V w/CPT - - 93 $294.00 $294.00 $352.00 $468.00 $540.00
480V/120V w/CPT - - 94 $294.00 $294.00 $352.00 $468.00 $540.00
600V/120V w/CPT - - 95 $294.00 $294.00 $352.00 $468.00 $540.00
208V/120V w/CPT - - 98 $294.00 $294.00 $352.00 $468.00 $540.00
240V/120V w/CPT & SP - - 33 $348.00 $348.00 $406.00 $522.00 $594.00
480V/120V w/CPT & SP - - 34 $348.00 $348.00 $406.00 $522.00 $594.00
600V/120V w/CPT & SP - - 35 $348.00 $348.00 $406.00 $522.00 $594.00
208V/120V w/CPT & SP - - 38 $348.00 $348.00 $406.00 $522.00 $594.00
240V/24V w/CPT1 - - S3 $294.00 $294.00 $352.00 - -
480V/24V w/CPT1 - - S4 $294.00 $294.00 $352.00 - -
600V/24V w/CPT1 - - S5 $294.00 $294.00 $352.00 - -
208V/24V w/CPT1 - - S8 $294.00 $294.00 $352.00 - -
Note: CPT includes 2 primary fuses and 1 secondary fuse.
124V coils not available for NEMA size 3 & 4.
Step 2 (Digits 8, 9) Select Control Voltage (Extra Capacity CPT + 100VA and 200VA)
NEMA Size NEMA Size
Standard 0 1 2 3 4 Standard 0 1 2 3 4
Size List Price List Price List Price List Price List Price Size List Price List Price List Price List Price List Price
Control Circuit Voltage & CPT CPT + 100VA GO-10G1 GO-10G1 GO-10G1 GO-10G1 GO-10G1 CPT + 200VA GO-10G1 GO-10G1 GO-10G1 GO-10G1 GO-10G1
120V w/ Surge Protector (SP) - -
120V - -
240V - -
480V - -
600V - -
208V - -
24V1 - -
240V/120V w/CPT 13 $420.00 $420.00 $504.00 $600.00 $660.00 23 $523.00 $523.00 $618.00 $714.00 $775.00
480V/120V w/CPT 14 $420.00 $420.00 $504.00 $600.00 $660.00 24 $523.00 $523.00 $618.00 $714.00 $775.00
600V/120V w/CPT 15 $420.00 $420.00 $504.00 $600.00 $660.00 25 $523.00 $523.00 $618.00 $714.00 $775.00
208V/120V w/CPT 18 $420.00 $420.00 $504.00 $600.00 $660.00 28 $523.00 $523.00 $618.00 $714.00 $775.00
240V/120V w/CPT & SP 53 $474.00 $474.00 $558.00 $654.00 $714.00 63 $577.00 $577.00 $672.00 $768.00 $829.00
480V/120V w/CPT & SP 54 $474.00 $474.00 $558.00 $654.00 $714.00 64 $577.00 $577.00 $672.00 $768.00 $829.00
600V/120V w/CPT & SP 55 $474.00 $474.00 $558.00 $654.00 $714.00 65 $577.00 $577.00 $672.00 $768.00 $829.00
208V/120V w/CPT & SP 58 $474.00 $474.00 $558.00 $654.00 $714.00 68 $577.00 $577.00 $672.00 $768.00 $829.00
240V/24V w/CPT1 A3 $420.00 $420.00 $504.00 - - B3 $523.00 $523.00 $618.00 - -
480V/24V w/CPT1 A4 $420.00 $420.00 $504.00 - - B4 $523.00 $523.00 $618.00 - -
600V/24V w/CPT1 A5 $420.00 $420.00 $504.00 - - B5 $523.00 $523.00 $618.00 - -
208V/24V w/CPT1 A8 $420.00 $420.00 $504.00 - - B8 $523.00 $523.00 $618.00 - -
Note: CPT includes 2 primary fuses and 1 secondary fuse.
124V coils not available for NEMA size 3 & 4.
GENERAL NOTE:
If selecting factory installed and wired operator devices (Push Buttons, Selector
Switches, and/or Pilot Lights) control circuit fusing, a control power transformer, or
24V/120V separate sourced control is required, regardless of protective device rating.
J F F E D C
ON
OFF
G B
H F F E
Application
Used for variable torque, constant torque, or constant horsepower
full-voltage 2 speed – 1 winding motors up to 100 horsepower
maximum, 600 Volts maximum. Consists of fusible or non-fusible
disconnect or circuit breaker to provide disconnecting means
and/or branch circuit protection, one 5-pole and one 3-pole
contactors, and quantity 2 three-leg block overload relay.
Digits: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
C R
Steps: Step 1 Step 2 Step 3 Step 4 Step 5 Step 6 Step 7 Step 8 Step 9
To configure the part number, use the tables below to fill in the digit boxes with the appropriate code.
Add list price from each step to arrive at total list for price for starter.
Step 2 (Digits 8, 9) Select Control Voltage (No CPT and Standard Size CPT)
NEMA Size
Control Standard 0 1 2 3 4
No List Price Fuses, List Price Size List Price List Price List Price List Price List Price
Control Circuit Voltage & CPT CPT GO-10G1 No CPT GO-10G1 CPT GO-10G1 GO-10G1 GO-10G1 GO-10G1 GO-10G1
120V w/ Surge Protector (SP) 01 $54.00 F1 $132.00 -
120V 02 $0.00 F2 $132.00 -
240V 03 $0.00 F3 $132.00 -
480V 04 $0.00 F4 $132.00 -
600V 05 $0.00 F5 $132.00 -
208V 08 $0.00 F8 $132.00 -
24V1 09 $0.00 - -
240V/120V w/CPT - - 93 $294.00 $294.00 $352.00 $468.00 $540.00
480V/120V w/CPT - - 94 $294.00 $294.00 $352.00 $468.00 $540.00
600V/120V w/CPT - - 95 $294.00 $294.00 $352.00 $468.00 $540.00
208V/120V w/CPT - - 98 $294.00 $294.00 $352.00 $468.00 $540.00
240V/120V w/CPT & SP - - 33 $348.00 $348.00 $406.00 $522.00 $594.00
480V/120V w/CPT & SP - - 34 $348.00 $348.00 $406.00 $522.00 $594.00
600V/120V w/CPT & SP - - 35 $348.00 $348.00 $406.00 $522.00 $594.00
208V/120V w/CPT & SP - - 38 $348.00 $348.00 $406.00 $522.00 $594.00
240V/24V w/CPT1 - - S3 $294.00 $294.00 $352.00 - -
480V/24V w/CPT1 - - S4 $294.00 $294.00 $352.00 - -
600V/24V w/CPT1 - - S5 $294.00 $294.00 $352.00 - -
208V/24V w/CPT1 - - S8 $294.00 $294.00 $352.00 - -
Note: CPT includes 2 primary fuses and 1 secondary fuse.
124V coils not available for NEMA size 3 & 4.
Disconnect with Class H Fuse Clips - For use with Non-Time Delay/Single Element Class H Fuses
200-208V 230-240V 460-480V 575-600V
Max Fuse Clip List Price Max Fuse Clip List Price Max Fuse Clip List Price Max Fuse Clip List Price
NEMA Size Hp (Amps) Code GO-10G1 Hp (Amps) Code GO-10G1 Hp (Amps) Code GO-10G1 Hp (Amps) Code GO-10G1
0 3 30 HA $96.00 3 30 HA $96.00 5 30 H3 $96.00 5 30 H3 $96.00
7 1/2 30 H3 $96.00 10 30 H3 $96.00
1
7 1/2 60 HB $96.00 7 1/2 60 HB $96.00 10 60 H6 $96.00 60 H6 $96.00
15 60 H6 $48.00 20 60 H6 $48.00
2
10 100 HC $174.00 15 100 HC $174.00 25 100 H1 $174.00 25 100 H1 $174.00
30 100 H1 $72.00 30 100 H1 $72.00
3
25 200 HD $312.00 30 200 HD $312.00 50 200 H2 $312.00 50 200 H2 $312.00
60 200 H2 $216.00 60 200 H2 $216.00
4
40 400 HE $540.00 50 400 HE $540.00 100 400 H4 $216.00 100 400 H4 $216.00
Disconnect with Class R Fuse Clips - For use with Time Delay/Dual Element Class RK1/RK5 Fuses
200-208V 230-240V 460-480V 575-600V
Max Fuse Clip List Price Max Fuse Clip List Price Max Fuse Clip List Price Max Fuse Clip List Price
NEMA Size Hp (Amps) Code GO-10G1 Hp (Amps) Code GO-10G1 Hp (Amps) Code GO-10G1 Hp (Amps) Code GO-10G1
0 3 30 RA $105.00 3 30 RA $105.00 5 30 R3 $105.00 5 30 R3 $105.00
5 30 RA $105.00 5 30 RA $105.00 10 30 R3 $105.00 10 30 R3 $105.00
1
7 1/2 60 RB $105.00 7 1/2 60 RB $105.00
30 R3 $57.00 15 30 R3 $57.00
2
10 60 RB $57.00 15 60 RB $57.00 25 60 R6 $57.00 25 60 R6 $57.00
60 R6 $66.00 30 60 R6 $66.00
3 20 100 RC $90.00 25 100 RC $90.00 50 100 R1 $90.00 50 100 R1 $90.00
25 200 RD $330.00 30 200 RD $330.00
100 R1 $90.00 60 100 R1 $90.00
4
40 200 RD $234.00 50 200 RD $234.00 100 200 R2 $234.00 100 200 R2 $234.00
Disconnect with Class J Fuse Clips - For use with Time Delay/Dual Element Class J Fuses
200-208V 230-240V 460-480V 575-600V
Max Fuse Clip List Price Max Fuse Clip List Price Max Fuse Clip List Price Max Fuse Clip List Price
NEMA Size Hp (Amps) Code GO-10G1 Hp (Amps) Code GO-10G1 Hp (Amps) Code GO-10G1 Hp (Amps) Code GO-10G1
0 3 30 J3 $114.00 3 30 J3 $114.00 5 30 J3 $114.00 5 30 J3 $114.00
5 30 J3 $114.00 5 30 J3 $114.00 10 30 J3 $114.00 10 30 J3 $114.00
1
7 1/2 60 J6 $114.00 7 1/2 60 J6 $114.00
30 J3 $78.00 15 30 J3 $78.00
2
10 60 J6 $78.00 15 60 J6 $78.00 25 60 J6 $78.00 25 60 J6 $78.00
60 J6 $120.00 30 60 J6 $120.00
3 20 100 J1 $144.00 25 100 J1 $144.00 50 100 J1 $144.00 50 100 J1 $144.00
25 200 J2 $384.00 30 200 J2 $384.00
4 100 J1 $192.00 60 100 J1 $192.00
40 200 J2 $336.00 50 200 J2 $336.00 100 200 J2 $336.00 100 200 J2 $336.00
GENERAL NOTE:
On NEMA Size 3 & 4 starters, if selecting factory installed and wired operator devices
(Push Buttons, Selector Switches, and/or Pilot Lights) then control circuit fusing, a
control power transformer, or 120V separate sourced control is required when the
protective device is rated greater than 100 Amps.
Digits: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
C R
Steps: Step 1 Step 2 Step 3 Step 4 Step 5 Step 6 Step 7 Step 8 Step 9
To configure the part number, use the tables below to fill in the digit boxes with the appropriate code.
Add list price from each step to arrive at total list for price for starter.
Step 2 (Digits 8, 9) Select Control Voltage (No CPT and Standard Size CPT)
NEMA Size
Control Standard 0 1 2 3 4
No List Price Fuses, List Price Size List Price List Price List Price List Price List Price
Control Circuit Voltage & CPT CPT GO-10G1 No CPT GO-10G1 CPT GO-10G1 GO-10G1 GO-10G1 GO-10G1 GO-10G1
120V w/ Surge Protector (SP) 01 $54.00 F1 $132.00 -
120V 02 $0.00 F2 $132.00 -
240V 03 $0.00 F3 $132.00 -
480V 04 $0.00 F4 $132.00 -
600V 05 $0.00 F5 $132.00 -
208V 08 $0.00 F8 $132.00 -
24V1 09 $0.00 - -
240V/120V w/CPT - - 93 $294.00 $294.00 $352.00 $468.00 $540.00
480V/120V w/CPT - - 94 $294.00 $294.00 $352.00 $468.00 $540.00
600V/120V w/CPT - - 95 $294.00 $294.00 $352.00 $468.00 $540.00
208V/120V w/CPT - - 98 $294.00 $294.00 $352.00 $468.00 $540.00
240V/120V w/CPT & SP - - 33 $348.00 $348.00 $406.00 $522.00 $594.00
480V/120V w/CPT & SP - - 34 $348.00 $348.00 $406.00 $522.00 $594.00
600V/120V w/CPT & SP - - 35 $348.00 $348.00 $406.00 $522.00 $594.00
208V/120V w/CPT & SP - - 38 $348.00 $348.00 $406.00 $522.00 $594.00
240V/24V w/CPT1 - - S3 $294.00 $294.00 $352.00 - -
480V/24V w/CPT1 - - S4 $294.00 $294.00 $352.00 - -
600V/24V w/CPT1 - - S5 $294.00 $294.00 $352.00 - -
208V/24V w/CPT1 - - S8 $294.00 $294.00 $352.00 - -
Note: CPT includes 2 primary fuses and 1 secondary fuse.
124V coils not available for NEMA size 3 & 4.
GENERAL NOTE:
On NEMA Size 3 & 4 starters, if selecting factory installed and wired operator devices
(Push Buttons, Selector Switches, and/or Pilot Lights) then control circuit fusing, a
control power transformer, or 120V separate sourced control is required when the
protective device is rated greater than 100 Amps.
Digits: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
C R
Steps: Step 1 Step 2 Step 3 Step 4 Step 5 Step 6 Step 7 Step 8 Step 9
To configure the part number, use the tables below to fill in the digit boxes with the appropriate code.
Add list price from each step to arrive at total list for price for starter.
Step 2 (Digits 8, 9) Select Control Voltage (No CPT and Standard Size CPT)
NEMA Size
Control Standard 0 1 2 3 4
No List Price Fuses, List Price Size List Price List Price List Price List Price List Price
Control Circuit Voltage & CPT CPT GO-10G1 No CPT GO-10G1 CPT GO-10G1 GO-10G1 GO-10G1 GO-10G1 GO-10G1
120V w/ Surge Protector (SP) 01 $54.00 F1 $132.00 -
120V 02 $0.00 F2 $132.00 -
240V 03 $0.00 F3 $132.00 -
480V 04 $0.00 F4 $132.00 -
600V 05 $0.00 F5 $132.00 -
208V 08 $0.00 F8 $132.00 -
24V1 09 $0.00 - -
240V/120V w/CPT - - 93 $294.00 $294.00 $352.00 $468.00 $540.00
480V/120V w/CPT - - 94 $294.00 $294.00 $352.00 $468.00 $540.00
600V/120V w/CPT - - 95 $294.00 $294.00 $352.00 $468.00 $540.00
208V/120V w/CPT - - 98 $294.00 $294.00 $352.00 $468.00 $540.00
240V/120V w/CPT & SP - - 33 $348.00 $348.00 $406.00 $522.00 $594.00
480V/120V w/CPT & SP - - 34 $348.00 $348.00 $406.00 $522.00 $594.00
600V/120V w/CPT & SP - - 35 $348.00 $348.00 $406.00 $522.00 $594.00
208V/120V w/CPT & SP - - 38 $348.00 $348.00 $406.00 $522.00 $594.00
240V/24V w/CPT1 - - S3 $294.00 $294.00 $352.00 - -
480V/24V w/CPT1 - - S4 $294.00 $294.00 $352.00 - -
600V/24V w/CPT1 - - S5 $294.00 $294.00 $352.00 - -
208V/24V w/CPT1 - - S8 $294.00 $294.00 $352.00 - -
Note: CPT includes 2 primary fuses and 1 secondary fuse.
124V coils not available for NEMA size 3 & 4.
GENERAL NOTE:
If selecting factory installed and wired operator devices (Push Buttons, Selector
Switches, and/or Pilot Lights) control circuit fusing, a control power transformer, or
24V/120V separate sourced control is required, regardless of protective device rating.
Application
Used for full-voltage 2 speed – 2 winding motors up to 100 horse-
power maximum, 600 Volts maximum. Consists of fusible or non-
fusible disconnect or circuit breaker to provide disconnecting
means and/or branch circuit protection, two 3-pole contactors,
and quantity 2 three-leg block overload relay.
Digits: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
C R
Steps: Step 1 Step 2 Step 3 Step 4 Step 5 Step 6 Step 7 Step 8 Step 9
To configure the part number, use the tables below to fill in the digit boxes with the appropriate code.
Add list price from each step to arrive at total list for price for starter.
Step 2 (Digits 8, 9) Select Control Voltage (No CPT and Standard Size CPT)
NEMA Size
Control Standard 0 1 2 3 4
No List Price Fuses, List Price Size List Price List Price List Price List Price List Price
Control Circuit Voltage & CPT CPT GO-10G1 No CPT GO-10G1 CPT GO-10G1 GO-10G1 GO-10G1 GO-10G1 GO-10G1
120V w/ Surge Protector (SP) 01 $54.00 F1 $132.00 -
120V 02 $0.00 F2 $132.00 -
240V 03 $0.00 F3 $132.00 -
480V 04 $0.00 F4 $132.00 -
600V 05 $0.00 F5 $132.00 -
208V 08 $0.00 F8 $132.00 -
24V1 09 $0.00 - -
240V/120V w/CPT - - 93 $294.00 $294.00 $352.00 $468.00 $540.00
480V/120V w/CPT - - 94 $294.00 $294.00 $352.00 $468.00 $540.00
600V/120V w/CPT - - 95 $294.00 $294.00 $352.00 $468.00 $540.00
208V/120V w/CPT - - 98 $294.00 $294.00 $352.00 $468.00 $540.00
240V/120V w/CPT & SP - - 33 $348.00 $348.00 $406.00 $522.00 $594.00
480V/120V w/CPT & SP - - 34 $348.00 $348.00 $406.00 $522.00 $594.00
600V/120V w/CPT & SP - - 35 $348.00 $348.00 $406.00 $522.00 $594.00
208V/120V w/CPT & SP - - 38 $348.00 $348.00 $406.00 $522.00 $594.00
240V/24V w/CPT1 - - S3 $294.00 $294.00 $352.00 - -
480V/24V w/CPT1 - - S4 $294.00 $294.00 $352.00 - -
600V/24V w/CPT1 - - S5 $294.00 $294.00 $352.00 - -
208V/24V w/CPT1 - - S8 $294.00 $294.00 $352.00 - -
Note: CPT includes 2 primary fuses and 1 secondary fuse.
124V coils not available for NEMA size 3 & 4.
Disconnect with Class H Fuse Clips - For use with Non-Time Delay/Single Element Class H Fuses
200-208V 230-240V 460-480V 575-600V
Max Fuse Clip List Price Max Fuse Clip List Price Max Fuse Clip List Price Max Fuse Clip List Price
NEMA Size Hp (Amps) Code GO-10G1 Hp (Amps) Code GO-10G1 Hp (Amps) Code GO-10G1 Hp (Amps) Code GO-10G1
0 3 30 HA $96.00 3 30 HA $96.00 5 30 H3 $96.00 5 30 H3 $96.00
7 1/2 30 H3 $96.00 10 30 H3 $96.00
1
7 1/2 60 HB $96.00 7 1/2 60 HB $96.00 10 60 H6 $96.00 60 H6 $96.00
15 60 H6 $48.00 20 60 H6 $48.00
2
10 100 HC $174.00 15 100 HC $174.00 25 100 H1 $174.00 25 100 H1 $174.00
30 100 H1 $72.00 30 100 H1 $72.00
3
25 200 HD $312.00 30 200 HD $312.00 50 200 H2 $312.00 50 200 H2 $312.00
60 200 H2 $216.00 60 200 H2 $216.00
4
40 400 HE $540.00 50 400 HE $540.00 100 400 H4 $216.00 100 400 H4 $216.00
Disconnect with Class R Fuse Clips - For use with Time Delay/Dual Element Class RK1/RK5 Fuses
200-208V 230-240V 460-480V 575-600V
Max Fuse Clip List Price Max Fuse Clip List Price Max Fuse Clip List Price Max Fuse Clip List Price
NEMA Size Hp (Amps) Code GO-10G1 Hp (Amps) Code GO-10G1 Hp (Amps) Code GO-10G1 Hp (Amps) Code GO-10G1
0 3 30 RA $105.00 3 30 RA $105.00 5 30 R3 $105.00 5 30 R3 $105.00
5 30 RA $105.00 5 30 RA $105.00 10 30 R3 $105.00 10 30 R3 $105.00
1
7 1/2 60 RB $105.00 7 1/2 60 RB $105.00
30 R3 $57.00 15 30 R3 $57.00
2
10 60 RB $57.00 15 60 RB $57.00 25 60 R6 $57.00 25 60 R6 $57.00
60 R6 $66.00 30 60 R6 $66.00
3 20 100 RC $90.00 25 100 RC $90.00 50 100 R1 $90.00 50 100 R1 $90.00
25 200 RD $330.00 30 200 RD $330.00
100 R1 $90.00 60 100 R1 $90.00
4
40 200 RD $234.00 50 200 RD $234.00 100 200 R2 $234.00 100 200 R2 $234.00
Disconnect with Class J Fuse Clips - For use with Time Delay/Dual Element Class J Fuses
200-208V 230-240V 460-480V 575-600V
Max Fuse Clip List Price Max Fuse Clip List Price Max Fuse Clip List Price Max Fuse Clip List Price
NEMA Size Hp (Amps) Code GO-10G1 Hp (Amps) Code GO-10G1 Hp (Amps) Code GO-10G1 Hp (Amps) Code GO-10G1
0 3 30 J3 $114.00 3 30 J3 $114.00 5 30 J3 $114.00 5 30 J3 $114.00
5 30 J3 $114.00 5 30 J3 $114.00 10 30 J3 $114.00 10 30 J3 $114.00
1
7 1/2 60 J6 $114.00 7 1/2 60 J6 $114.00
30 J3 $78.00 15 30 J3 $78.00
2
10 60 J6 $78.00 15 60 J6 $78.00 25 60 J6 $78.00 25 60 J6 $78.00
60 J6 $120.00 30 60 J6 $120.00
3 20 100 J1 $144.00 25 100 J1 $144.00 50 100 J1 $144.00 50 100 J1 $144.00
25 200 J2 $384.00 30 200 J2 $384.00
100 J1 $192.00 60 100 J1 $192.00
4
40 200 J2 $336.00 50 200 J2 $336.00 100 200 J2 $336.00 100 200 J2 $336.00
GENERAL NOTE:
On NEMA Size 3 & 4 starters, if selecting factory installed and wired operator devices
(Push Buttons, Selector Switches, and/or Pilot Lights) then control circuit fusing, a
control power transformer, or 120V separate sourced control is required when the
protective device is rated greater than 100 Amps.
Digits: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
C R
Steps: Step 1 Step 2 Step 3 Step 4 Step 5 Step 6 Step 7 Step 8 Step 9
To configure the part number, use the tables below to fill in the digit boxes with the appropriate code.
Add list price from each step to arrive at total list for price for starter.
Step 2 (Digits 8, 9) Select Control Voltage (No CPT and Standard Size CPT)
NEMA Size
Control Standard 0 1 2 3 4
No List Price Fuses, List Price Size List Price List Price List Price List Price List Price
Control Circuit Voltage & CPT CPT GO-10G1 No CPT GO-10G1 CPT GO-10G1 GO-10G1 GO-10G1 GO-10G1 GO-10G1
120V w/ Surge Protector (SP) 01 $54.00 F1 $132.00 -
120V 02 $0.00 F2 $132.00 -
240V 03 $0.00 F3 $132.00 -
480V 04 $0.00 F4 $132.00 -
600V 05 $0.00 F5 $132.00 -
208V 08 $0.00 F8 $132.00 -
24V1 09 $0.00 - -
240V/120V w/CPT - - 93 $294.00 $294.00 $352.00 $468.00 $540.00
480V/120V w/CPT - - 94 $294.00 $294.00 $352.00 $468.00 $540.00
600V/120V w/CPT - - 95 $294.00 $294.00 $352.00 $468.00 $540.00
208V/120V w/CPT - - 98 $294.00 $294.00 $352.00 $468.00 $540.00
240V/120V w/CPT & SP - - 33 $348.00 $348.00 $406.00 $522.00 $594.00
480V/120V w/CPT & SP - - 34 $348.00 $348.00 $406.00 $522.00 $594.00
600V/120V w/CPT & SP - - 35 $348.00 $348.00 $406.00 $522.00 $594.00
208V/120V w/CPT & SP - - 38 $348.00 $348.00 $406.00 $522.00 $594.00
240V/24V w/CPT1 - - S3 $294.00 $294.00 $352.00 - -
480V/24V w/CPT1 - - S4 $294.00 $294.00 $352.00 - -
600V/24V w/CPT1 - - S5 $294.00 $294.00 $352.00 - -
208V/24V w/CPT1 - - S8 $294.00 $294.00 $352.00 - -
Note: CPT includes 2 primary fuses and 1 secondary fuse.
124V coils not available for NEMA size 3 & 4.
GENERAL NOTE:
On NEMA Size 3 & 4 starters, if selecting factory installed and wired operator devices
(Push Buttons, Selector Switches, and/or Pilot Lights) then control circuit fusing, a
control power transformer, or 120V separate sourced control is required when the
protective device is rated greater than 100 Amps.
Digits: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
C R
Steps: Step 1 Step 2 Step 3 Step 4 Step 5 Step 6 Step 7 Step 8 Step 9
To configure the part number, use the tables below to fill in the digit boxes with the appropriate code.
Add list price from each step to arrive at total list for price for starter.
Step 2 (Digits 8, 9) Select Control Voltage (No CPT and Standard Size CPT)
NEMA Size
Control Standard 0 1 2 3 4
No List Price Fuses, List Price Size List Price List Price List Price List Price List Price
Control Circuit Voltage & CPT CPT GO-10G1 No CPT GO-10G1 CPT GO-10G1 GO-10G1 GO-10G1 GO-10G1 GO-10G1
120V w/ Surge Protector (SP) 01 $54.00 F1 $132.00 -
120V 02 $0.00 F2 $132.00 -
240V 03 $0.00 F3 $132.00 -
480V 04 $0.00 F4 $132.00 -
600V 05 $0.00 F5 $132.00 -
208V 08 $0.00 F8 $132.00 -
24V1 09 $0.00 - -
240V/120V w/CPT - - 93 $294.00 $294.00 $352.00 $468.00 $540.00
480V/120V w/CPT - - 94 $294.00 $294.00 $352.00 $468.00 $540.00
600V/120V w/CPT - - 95 $294.00 $294.00 $352.00 $468.00 $540.00
208V/120V w/CPT - - 98 $294.00 $294.00 $352.00 $468.00 $540.00
240V/120V w/CPT & SP - - 33 $348.00 $348.00 $406.00 $522.00 $594.00
480V/120V w/CPT & SP - - 34 $348.00 $348.00 $406.00 $522.00 $594.00
600V/120V w/CPT & SP - - 35 $348.00 $348.00 $406.00 $522.00 $594.00
208V/120V w/CPT & SP - - 38 $348.00 $348.00 $406.00 $522.00 $594.00
240V/24V w/CPT1 - - S3 $294.00 $294.00 $352.00 - -
480V/24V w/CPT1 - - S4 $294.00 $294.00 $352.00 - -
600V/24V w/CPT1 - - S5 $294.00 $294.00 $352.00 - -
208V/24V w/CPT1 - - S8 $294.00 $294.00 $352.00 - -
Note: CPT includes 2 primary fuses and 1 secondary fuse.
124V coils not available for NEMA size 3 & 4.
GENERAL NOTE:
If selecting factory installed and wired operator devices (Push Buttons, Selector
Switches, and/or Pilot Lights) control circuit fusing, a control power transformer, or
24V/120V separate sourced control is required, regardless of protective device rating.
J F F E D C
ON
OFF
G B
H F F E
J F F E D C
ON
OFF
G B
H F F E
1d START Push Button and H-O-A Selector Any 2 $264.00 $264.00 $264.00 $264.00 $264.00 $264.00 $264.00
Switch (HEAVY-DUTY, CR104P)
Single Push Button, Unwired (Specify 1 2 $40.00 $40.00 $40.00 $40.00 $40.00 $40.00 $40.00
Marking) (HEAVY-DUTY, CR104P)
1e
Single Push Button, Unwired (Specify Any 2 $90.00 $90.00 $90.00 $90.00 $90.00 $90.00 $90.00
Marking) (HEAVY-DUTY, CR104P)
Single Illuminated Push Button, Unwired
Pilot 1f (Specify Marking) Any 2 $180.00 $180.00 $180.00 $180.00 $180.00 $180.00 $180.00
Devices (HEAVY-DUTY, CR104P)
Mounted
in Cover 2 Selector Switches
or Flange
of HAND-OFF-AUTO 1,3 1 $48.00 $48.00 $48.00 $48.00 $48.00 $48.00 $48.00 $132.00
CR306 2a HAND-OFF-AUTO 1,3
CR307 Any 2 $132.00 $132.00 $132.00 $132.00 $132.00 $132.00 $132.00
(HEAVY-DUTY, CR104P)
CR308
CR387 OFF-ON 1 1 $48.00 $48.00 $48.00 $48.00 $48.00 $48.00 $48.00 $132.00
CR407 2b
Any 2 $132.00 $132.00 $132.00 $132.00 $132.00 $132.00 $132.00
CR408 OFF-ON (HEAVY-DUTY, CR104P)
CR487
Single Selector Switch Maintained
(Specify Marking)
2c Two- or Three-Position (Specify 2
Position) 4 (HEAVY-DUTY, CR104P) Any $132.00 $132.00 $132.00 $132.00 $132.00 $132.00 $132.00
Four-Position4 (HEAVY-DUTY, CR104P) Any 2 $150.00 $150.00 $150.00 $150.00 $150.00 $150.00 $150.00
Key Operated Maintained (Specify
Marking and Key-Removal Position)
2d
Two- or Three-Position4 2
(HEAVY-DUTY, CR104P) Any $168.00 $168.00 $168.00 $168.00 $168.00 $168.00 $168.00
Note: For indicating light modifications on CR309-311 & CR390, see p. 1-126. 2 Factory-installed field modification kit for sizes 00-4 and size 5 without CPT.
1 One indicating light: Wired in parallel with operating coil. 3 Not available in NEMA Size 00. Use Size 0 starter and modification.
Two indicating lights: Red is wired in parallel with operating coil, 4 Maximum of three additional auxiliary contacts available on size 0-1.
green is wired through an auxiliary contact. 5 Specify CR104P operator and contact block by product number.
20 Disconnect Switch
2
20a One Normally Open or One Normally Closed (Specify) 1, 3R, 4/4X, 12 $66.00 $66.00 $66.00 $66.00 $66.00 $66.00 $66.00
Auxiliary
Contacts 2
20b Single Pole Double Throw 1, 3R, 4/4X, 12 $132.00 $132.00 $132.00 $132.00 $132.00 $132.00 $132.00
on
Operator 21 Circuit Breaker
Handle 2
21a One Normally Open or One Normally Closed (Specify) 1, 3R, 4/4X, 12 $66.00 $66.00 $66.00 $66.00 $66.00 $66.00 $66.00
2
21b Single Pole Double Throw 1, 3R, 4/4X, 12 $132.00 $132.00 $132.00 $132.00 $132.00 $132.00 $132.00
1 NEMA Type 1 enclosures require oiltight pilot devices when this 2 Not available in NEMA Size 00. Use Size 0 starter and modification.
modification is used with NEMA Starter sizes 0, 1, and 2. 3 Requires 100 VA extra capacity control transformer.
Only oiltight pilot devices will fit the oversized enclosure required.
The list price addition for the oversized enclosure is already
included in the published list price.
Overload Relay 22a 1 NC Contact, Manual Reset (Standard) Any N/C N/C N/C N/C N/C N/C N/C N/C
Mounted On
CR306, CR307, 22b 1 NO and 1 NC Isolated Contact Any $24.00 $24.00 $24.00 $24.00 $24.00 $24.00 $24.00 $24.00
CR308, CR309,
CR310, CR311, 22c Ambient Compensated (1 NC Contact) Any $27.00 $27.00 $27.00 $27.00 $27.00 $27.00 $27.00 $27.00
CR387, CR390,
23 Automatic Reset Any $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00 $50.00
CR407, CR408,
CR410, CR411, 24 Omit the Overload (Deduct) Any $-30.00 $-30.00 $-30.00 $-54.00 $-90.00 $-144.00 $-504.00 $-504.00
CR487, CR490
25 Solid-State Overload1 Any — — $27.00 $27.00 $27.00 $27.00 $27.00 $27.00
Metering 1, 3R, 12 2 $348.00 $348.00 $348.00 $348.00 $348.00 $348.00 $348.00
Mounted In
CR306, CR307,
CR308, CR309, 27 Elapsed Time Meter
CR310, CR311, 4/4X 2 $588.00 $588.00 $588.00 $588.00 $588.00 $588.00 $588.00
CR387, CR390,
CR407, CR408,
CR410, CR411,
CR487, CR490
Class H (Standard) Any 2 N/C N/C N/C N/C N/C N/C N/C
Fuse Clips
Mounted In 2 —
28 Class J Any $18.00 $18.00 $30.00 $72.00 $120.00 $168.00
CR308, CR311,
CR408, CR411 Class R Any 2 $9.00 $9.00 $9.00 $18.00 $18.00 $42.00 —
Enclosure
CR306, CR307, Space Heater 3
CR308, CR309, 50 Watts—NEMA Size 0-4
CR310, CR311, 30 Any 2 $120.00 $120.00 $120.00 $120.00 $120.00 $120.00 $420.00
Contactor/Starter
CR387, CR390, 100 Watts—NEMA Size 5
CR407, CR408, Contactor/Starter
CR410, CR411,
CR487, CR490
31 Operating Coil Surge Any $54.00 $54.00 $54.00 $54.00 $54.00 $54.00 $54.00 $54.00
Misc. Suppressor (120 V/60 Hz)
Mounted On 32 Insulated Neutral Lug Any 2 $132.00 $132.00 $132.00 $132.00 $132.00 $132.00 $132.00
CR306, CR307,
33 Ground Lug Any 2 $48.00 $48.00 $48.00 $48.00 $48.00 $48.00 $48.00
CR308, CR309,
CR310, CR311,
CR387, CR390, Terminal Block, (Catalog Number CR151B) 2
CR407, CR408, 34 Any $24.00 $24.00 $24.00 $24.00 $24.00 $24.00 $24.00
30A, Unwired (per point) (Specify Points)
CR410, CR411,
CR487, CR490 Power Factor Correction Capacitor
35 Any 2 $24.00 $24.00 $24.00 $24.00 $24.00 $24.00 $24.00
Terminals
1 Solid-state overload is ambient insensitive and has 1 NO and 1 NC
isolated contacts as standard.
2 Not available in NEMA Size 00. Use Size 0 starter and modification.
3 If connected to control circuit transformer, 115-Volt heater requires
an extra capacity transformer for Size 0-1 and Size 5.
1 — — — — $1224.00 $1524.00 —
1 — — — — — $2172.00 $2472.00
42 Fusible 400A 250-600V 3R, 12 — — — — — $2568.00 $2712.00
4/4X — — — — — $3108.00 $3456.00
1 1 $846.00 $846.00 $1002.00 $1122.00 $2052.00 $3990.00
CR309 Two-
Speed with 1
Circuit Breaker 43 Circuit Breaker 3R, 12 $846.00 $846.00 $1080.00 $1206.00 $2772.00 $4566.00
CR310, CR410 4/4X 1 $1206.00 $1206.00 $1488.00 $2058.00 $2988.00 $4974.00
1 Not available in NEMA Size 00. Use Size 0 starter and modification.
Contact Location
4 Contacts Max.
Final Suffix Letter of
Product No. on Starter W X Y T Z U
A or None
B
C
D
E
F
G
H
J
K
L
M
N
P
NEMA Sizes 0 and 1 Single-Speed, Nonreversing,
R
2- and 3-Pole Starters
Contact Location
5 Contacts Max.
Final Suffix Letter of
Product No. on Starter W X Y Z T U
A or None
B
C
D
E
F
G
H
J
K
L
M
N
P
R
S NEMA Sizes 2, 3 and 4, Single-Speed
T Nonreversing Starters
U
W
X
Y
Contact Location
5 Contacts Max.
Contact Location
Final Suffix Letter of 5 Contacts Max.
Product No. on Starter W X Y T Z
A or None
B
C
D
E
F
G
H
J
K
L
M
N
P
R
S
T Typical connection diagram
U NEMA Sizes 7-9
W
X
Y
Application
Auxiliary contacts can add to the versatility of magnetic starters
by providing additional control circuits to do a variety of jobs
without adding to the width of the starter.
Kits make it easy to add contacts to control accessory equipment
such as indicating lights; to control sequencing of other motor
starters; and in conjunction with a standard reversing starter and
plugging switch, to plug-stop motors. Auxiliary contacts can be
added to all across-the-line magnetic starters, combination
magnetic starters, reversing and multi-speed starters.
Each auxiliary contact is rated 10 Amperes ac, resistive load,
NEMA “A600,” and is suitable for either right or left side mounting.
An insulating shield is also provided between each auxiliary
contact unit and the starter. Auxiliary contacts are furnished in
the basic block design or as an adder block.
Each contact is marked NO or NC on the block and is not
convertible.
Basic Block and Adder Block
Logic reed contacts suitable for low energy level circuits are also
available. These are designed for applications on low-voltage
control circuits (24 Volts and below), such as inputs to computers
and programmable starters.
Product Number Selection Instructions Field-Installed Modifications for Magnetic Starters – Contents
1. Order by quantity and complete product number. Auxiliary Contact Kits (CR305X, CR385X) ...................................1-134
Example: Three CR305X300A at $36.00 each, GO-10G. Modification Kits ....................................................................................1-137
Fuse-Clip Kits (CR308X).......................................................................1-141
Reference Publications
Instructions
NEMA Size Publication Number
0, 1 GEH-4758
2 GEH-4759
3, 4 GEH-4760
5, 6 GEH-4761
7-9 GEH-5109
0, 1 Logic Reed GEH-5178
2 Logic Reed GEH-5185
3, 4 Logic Reed GEH-5186
5, 6 Logic Reed GEH-5187
Standard Block
Continuous Inrush Continuous Inrush
AC Volts Current Amperes Current Amperes DC Volts Current Amperes Current Amperes
115 6.0 60 125 1.1 —
230 3.0 30 250 0.5 —
460 1.5 15 — — —
575 1.2 12 — — —
1First adder block must be mounted to a basic block. A second adder block can be added to the first adder block on size 2 through size 9 starters.
Four extra auxiliary contacts (not blocks) is the maximum that can be added to either a NEMA size 0 or 1 starter while five is the maximum extra auxiliary contacts that can
be added to NEMA Size 2 through 6 devices.
2CR305X logic reed switch auxiliary contacts may be ordered as a factory-installed modification. Order by description. For factory-installed modification,
add $75.00, GO-10G, per circuit to price of starter.
Fifth-Pole Kits
To be installed on NEMA Size 0, 1, and 2 magnetic four-pole contactors and starters.
Permits the addition of a fifth pole with the same rating as the main poles.
List Price
NEMA Size Mounting Position Product Number GO-10G
0, 1 Right CR305X111B $66.00
2 (add to 4-pole form) Left CR305X211B $120.00
START-STOP Push Button kits
Fifth-Pole Kit
Reference Publications
Instructions, Indicating Light Kits for Type 1 Enclosure
NEMA Size Publication Number
00, 0, 1 GEH-4767
2 GEH-4768
3, 4 GEH-4770
Instructions, Push Button and Selector Switch Kits for Type 1 Enclosure
NEMA Size Publication Number
00, 0, 1 GEH-4763
2 GEH-4764
3, 4 GEH-4765
5 GEH-4766
Control Amplifier
The GE CR305X control amplifier is suitable for applications with low level 24 Volt dc
outputs. It allows the low level signals from a programmable control, microprocessor, Typical Size 2 Starter with CR305X Control
or photoelectric cell to operate GE’s 300-Line starters while their control coils operate Amplifier Mounted on Right
at the line voltage. The control amplifier is UL listed and CSA Certified, and forms are
available for NEMA Sizes 00 through 5.
List Price
Operation Type NEMA Size Product Number GO-10G
Nonreversing 00, 0, & 1 CR305X112A $54.00
Nonreversing 2 CR305X212A $54.00
Nonreversing 3&4 CR305X312A $54.00
Reversing 00, 0, 1, 2, 3, & 4 CR305X112P3 $54.00
Reference Publications
Instructions:
Space heater kits GEH-4772
Control transformer kits GEH-4842
Application
To accommodate an occasional requirement for a starter in an
enclosure, not stocked complete, it may be convenient and
economical to stock enclosure kits for use with open starters; or
even for conversion of a starter stocked in a different enclosure.
UL listing can be maintained by use of these listed enclosures
with listed starters, accessories, and modification kits.
Standard instructions, wiring-diagram labels and overload heater
selection labels are included in each kit. Each enclosure includes
an external reset for the starter overload relay, and provisions or
plugged holes for optional addition of appropriate pilot devices.
For example, push button(s), selector switch, and/or pilot light can
be added, once the proper plug(s) is (are) removed. The external
reset can be removed and replaced by use of a suitable hole plug kit.
Reference Publications
Instructions
Base Product No. Size 1 Size 2 Size 3 Size 4 Size 5
CR306X, 309X GEH-4879 GEH-4880 GEH-4881 GEH-4882 GEH-4883
CR307X, 308X, CR387X GEH-4884 GEH-4885 GEH-4886 GEH-4887 GEH-4888
CR310X, 311X CR390X GEH-4890 GEH-4891 GEH-4892 GEH-4893 —
Nonreversing
Enclosure NEMA For Use Provision for Outline Product List Price
Type Size With CR306 Control Transformer Width Height Depth Number Number GO-10G1
NEMA Type 1 00, 0, 1 A, B, C No 6.00 10.00 4.63 55-178430P001 CR306X190B $42.00
NEMA Type 1 2 D No 7.38 13.25 6.13 55-178434P001 CR306X290B $86.00
NEMA Type 1 3 E No 8.75 20.25 7.31 55-200200 CR306X390B $120.00
NEMA Type 1 4 F No 8.75 25.00 7.31 55-200202 CR306X490B $252.00
NEMA Type 1 5 G No CR306X590B $462.00
NEMA Type 1 00, 0, 1 A, B, C Yes 10.00 10.00 4.63 55-178440P001 CR306X190C $60.00
NEMA Type 1 2 D Yes 12.00 13.25 6.13 55-178441P001 CR306X290C $96.00
NEMA Type 1 3 E Yes 18.00 21.62 8.62 55-200208 CR306X390C $168.00
NEMA Type 1 4 F Yes CR306X490C $312.00
NEMA Type 1 5 G Yes CR306X590C $642.00
NEMA Type 3R 00, 0, 1 A, B, C No 6.88 14.50 4.75 55-192653 CR306X190K $96.00
NEMA Type 3R 2 D No 7.84 16.50 6.50 55-192656 CR306X290K $204.00
NEMA Type 3R 3 E Yes or No 17.19 23.50 7.25 55-210105 CR306X390K1 $288.00
NEMA Type 3R 4 F Yes or No 17.19 27.50 7.25 55-210106 CR306X490K1 $780.00
NEMA Type 3R 5 G Yes or No CR306X590K1 $1794.00
NEMA Type 3R 00, 0, 1 A, B, C Yes 10.38 14.50 4.75 55-205749 CR306X190M $96.00
NEMA Type 3R 2 D Yes 12.50 16.50 6.50 55-205749 CR306X290M $204.00
NEMA Type 12 00, 0, 1 A, B, C No 6.25 14.25 4.75 55-184777 CR306X190G $96.00
NEMA Type 12 2 D No 7.63 16.25 6.25 55-184781 CR306X290G $204.00
NEMA Type 12 3 E No 10.00 27.25 7.25 55-200203 CR306X390G $288.00
NEMA Type 12 4 F No CR306X490G $780.00
NEMA Type 12 5 G No CR306X590G $1794.00
NEMA Type 12 00, 0, 1 A, B, C Yes 10.25 14.25 4.75 55-188449 CR306X190L $96.00
NEMA Type 12 2 D Yes 12.25 16.25 6.25 55-184780 CR306X290L $204.00
NEMA Type 12 3 E Yes CR306X390L $288.00
NEMA Type 12 4 F Yes CR306X490L $780.00
NEMA Type 12 5 G Yes CR306X590L $1794.00
NEMA Type 4/4X 00, 0, 1 A, B, C Yes CR306X190T $246.00
NEMA Type 4/4X 2 D Yes CR306X290T $510.00
NEMA Type 4/4X 3 E Yes CR306X390S $750.00
NEMA Type 4/4X 4 F Yes CR306X490S $1314.00
NEMA Type 4/4X 5 G Yes CR306X590S $1800.00
• NEMA Type 1: Includes provisions for 1 pilot device and 1 red neon light;
• NEMA Type 3R and 12 includes 2 plugged holes for heavy duty pilot device(s);
• NEMA Type 4/4X includes 3 plugged holes for heavy duty pilot devices.
Reversing
Enclosure NEMA For Use Provision for Outline Product List Price
Type Size With CR306 Control Transformer Width Height Depth Number Number GO-10G
NEMA Type 1 00, 0, 1 A, B, C Yes or No CR309X190C1 $54.00
NEMA Type 1 2 D Yes or No CR309X290C1 $114.00
NEMA Type 1 3 E No CR309X390B $186.00
NEMA Type 1 4 F No CR309X490B $330.00
NEMA Type 1 3 E Yes CR309X390C $234.00
NEMA Type 1 4 F Yes CR309X490C $390.00
NEMA Type 3R 00, 0, 1 A, B, C Yes or No 14.38 14.50 4.75 55-192655 CR309X190J $162.00
NEMA Type 3R 2 D Yes or No CR309X290J $294.00
NEMA Type 3R 3 E Yes or No CR309X390J $582.00
NEMA Type 3R 4 F Yes or No CR309X490J $942.00
NEMA Type 12 00, 0, 1 A, B, C Yes or No CR309X190L $162.00
NEMA Type 12 2 D Yes or No CR309X290L $294.00
NEMA Type 12 3 E Yes or No CR309X390L $582.00
NEMA Type 12 4 F Yes or No CR309X490L $942.00
NEMA Type 4/4X 00, 0, 1 A, B, C Yes or No CR309X190S2 $450.00
NEMA Type 4/4X 2 D Yes or No CR309X290S2 $750.00
NEMA Type 4/4X 3 E Yes or No CR309X390S2 $1122.00
NEMA Type 4/4X 4 F Yes or No CR309X490S2 $1974.00
• NEMA Types 1, 3R and 12 include 3 plugged holes for heavy duty pilot device(s);
• NEMA Type 4/4X includes 5 plugged holes for heavy duty pilot device(s).
1For use with or without control transformer.
2Type 4/4X stainless steel reversers also include baseplate.
Application
The panel-mount block overload relay provides overload
protection for motors having full-load currents up to 135
Amperes. The relays are furnished complete for use on control
panels. When an overload condition occurs in any of the three
A
legs in which heaters are inserted, it will cause the relay to trip,
opening a normally closed contact, and, as an option, closing a
normally open contact.
Standard and ambient compensated forms with various contact B
arrangements are available. A normally open circuit may be F
connected to a signal light, an alarm bell, or input circuit of a
programmable controller, e.g., to provide indication of an over-
load relay trip. C
D
Features E
—Flexibility of operation; trip rating can be easily changed by
replacing the front-accessible heaters.
—Dual Bimetal Current Monitoring; additional bimetal strip Typical 300-line Overload Relay with Heater
“anticipates” the rate of temperature rise in the motor winding; Shown in Center Pole Only
effectively reduces trip time in locked rotor conditions. It pre-
vents dangerous temperature overshoot in the motor windings.
A Manual weld check for contacts
B Overload trip adjustment ±10%
Product Number Selection Instructions C Safe reset operates on upstroke only
1. Order required relay by complete product number as shown in D Visual trip indication
pricing table. E Optional normally open isolated,
Example: An open block-type relay with one normally closed high-fidelity contacts
contact is to be mounted in a control panel. Three-leg overload F GE exclusive dual bimetal overload
protection is needed and the full-load current of the motor
protection
being controlled is 40.5 amperes. Order: CR324D310A at
$78.00, GO-10H and three CR123C400B heaters. List Price
$9.00 each, GO-10H. Heaters are selected from tables on
page 1-159.
Reference Publications
Time Current Curves GES-7202
Instructions GEH-4821
Contact Ratings
Continuous
Rating Make Recommended Maximum Interrupting Capacity, Amperes
Amperes Amperes DC Circuits AC Circuits
AC or DC 125 V 250 V 115 V 230 V 460 V 575 V
10 30 0.35 0.17 3 1.5 0.75 0.6
Application
Single-pole overload relays are used to provide overload protec-
tion for dc and single-phase ac motors having full load currents
of 270 Amperes or less; also, three relays for 3-phase motors
requiring quick-trip protection.
Optional NO-NC contact (SPDT) can be connected to alarm circuit
to signal when relay trips.
Features
—Positive Overload Protection; relay utilizes a bimetallic strip CR124E028 Overload Relay
and heater which closely simulates thermal characteristics
of motor.
—Manual or Automatic Reset; on normally-closed contact
forms–simple spring clip shift from one to the other.
—Trip Current Adjustment; knob can be set from 85 to 115% of
nominal heater trip rating.
—Front Mounting; is provided by use of mounting brackets for 1,
2, or 3 relays.
—Optional Back Mounting; requires no brackets.
—Front-Replaceable Heaters; provide change of trip current
rating in approximately 10% steps.
Reference Publications
Instructions GEH-4729 (CR124C, D)
GEH-2543 (CR124E, F)
Heater Selection Guide GET-2681
Instructions GEH-4734 (CR124X)
Accessories
CR324 CR124
900 28.5 24.8 12.4 9.9 900 435 378 189 151
3600 — 446 223 178
3600 27.4 23.8 11.9 9.5
200 1800 — 468 234 187
1800 31.3 27.2 13.6 10.9
10 —
1200 32.7 28.4 14.2 11.4 1200 482 241 193
3600 — 574 287 230
900 33.1 28.8 14.4 11.5
250 1800 — 590 295 236
3600 42.6 37.0 18.5 14.8
1800 46.7 40.6 20.3 16.2 1200 — 594 297 238
15 —
1200 45.1 39.2 19.6 15.7 3600 676 338 270
300
900 47.6 41.4 20.7 16.6 1800 — 686 343 274
3600 62.3 54.2 27.1 21.7 3600 — 774 387 310
350
1800 59.3 51.6 25.8 20.6 1800 — 792 396 317
20
1200 56.6 48.2 24.6 19.7 400 3600 — 890 445 356
900 63.9 55.6 27.8 22.2 Note: The listed data is based on approximate full-load current
1 For expected values on 208-Volt, 50-Hertz, three-phase motors, contact ratings of standard, open, 1.15 service factor, continuous rated GE
nearest GE Energy Representative. motors. Full-load current ratings of similar motors of other
2 Open, Type K, General-Purpose, NEMA SF, Solid-Base, manufacturers may vary considerably. Therefore, whenever
possible use actual full-load current rating given on motor nameplate.
Rolled-Steel-Shell, GE Induction Motors. Contact motor manufacturer for full-load currents of single-phase and
DC motors.
Heater Table
Base Product Number Quantity Heaters Column
Starter/Overload Relay Description NEMA Type Enclosure Required (Pages 1-156 to 1-157)
Single-Phase, 2-Pole, Size 00-2 Open 1 A
Single-Phase, 2-Pole, Size 00-2 1, 3R, 4/4X, 12 1 B
CR306
Single-Phase, 2-Pole, Size 3 Open 2 A
Single-Phase, 2-Pole, Size 6 1, 3R, 4/4X, 12 2 B
3-Phase, 3-Pole, 3-Leg Protection
standard, size 00-5 Open 3 C
CR306 ambient compensated, size 00, 0, 1, 2 & 5 Open 3 C
ambient compensated, size 3 Open 3 D
ambient compensated, size 8 Open 3 E
3-Phase, 3-Pole, 3-Leg Protection
standard, size 00-5 1, 3R, 4/4X, 12 3 D
CR306, CR307, ambient compensated, size 00, 0, 1, 2 & 5 1, 3R, 4/4X, 12 3 C
CR308, CR387,
CR407, CR408, CR487 ambient compensated, size 3 1, 3R, 4/4X, 12 3 D
ambient compensated, size 8 1, 3R, 4/4X, 12 3 E
3-Phase, 3 3-Pole, 3-Leg Protection
standard, size 00-5 Open 3-Reverser 6-Two-Speed C
CR309 ambient compensated, size 00, 0, 1, 2 & 5 Open 3-Reverser 6-Two-Speed C
ambient compensated, size 3 Open 3-Reverser 6-Two-Speed D
ambient compensated, size 8 Open 3-Reverser 6-Two-Speed E
3-Phase, 3 3-Pole, 3-Leg Protection
standard, size 00-5 1, 3R, 4/4X, 12 3-Reverser 6-Two-Speed D
CR309, CR410, ambient compensated, size 00, 0, 1, 2 & 5 1, 3R, 4/4X, 12 3-Reverser 6-Two-Speed C
CR411, CR490
ambient compensated, size 3 1, 3R, 4/4X, 12 3-Reverser 6-Two-Speed D
ambient compensated, size 8 1, 3R, 4/4X, 12 3-Reverser 6-Two-Speed E
CR324 Panel-Mounted See tables, page 1-159
All NEMA Sizes 6-9 3-Phase, 3-Leg Protection, Standard See tables, page 1-158
CR124 Single-Element, Panel-Mounted See tables, page 1-160
Product
NEMA Size 4
Maximum Motor Full-Load Amperes
C D E Heater Product Number
32.2 32.0 32.0 CR123F357B
34.0 34.2 34.2 CR123F395B
36.8 36.7 36.7 CR123F430B
44.6 43.9 43.9 CR123F487B
48.4 46.6 46.6 CR123F567B
53.9 52.6 52.6 CR123F614B
57.4 55.6 55.6 CR123F658B
60.0 58.7 58.7 CR123F719B
69.5 67.1 67.1 CR123F772B
71.7 70.6 70.6 CR123F848B
79.9 76.3 76.3 CR123F914B
92.3 88.7 88.7 CR123F104C
97.0 93.4 93.4 CR123F114C
108.0 102.0 105.0 CR123F118C
118.0 110.0 114.0 CR123F133C
131.0 122.0 128.0 CR123F149C
135.0 131.0 131.0 CR123F161C
— 135.0 135.0 CR123F174C
Product
Overload Relays
For CR324 Standard and Ambient Compensated Block
Overloads—Panel-Mounted
Product Number List Price Each, GO-10H
Overload Relays All CR123C and 123F heaters are packaged three to a carton.
Items of these heaters, being ordered for either customer’s stock
Product r List Price Each, GO-10H or any other purpose, are to be specified in multiples of three
CR123K (All) $9.00 (such as 3, 6, 9, 12, 15, etc.). Minimum order quantity is three.
CR123L (All) $9.00
Technical Features
—2:1 Adjustable full load amps with tactile feedback dial
—Selectable 10/20/30 protection class
—Ambient insensitive within the stated operating temperature
range of –20° to +70°C
—Built-in thermal memory to prevent hot motor restarts
—Protection against complete phase current loss
—Manual reset (standard) and remote reset (optional) 24 VDC
or 120 VAC
—Accuracy: ± 2%
—Repeatability: ± 2%
—Self-powered @ 50% of minimum current range
—Size: 1-6 (0.40A-540A, 600 V, 50/60 Hz)
—Unbalance trip signal for PLC operation
—Manual trip
—Visual trip indication
—Standard isolated 1 NO and 1 NC aux. contact (A600, Q600) CR324X Overload Relay (Panel-Mount)
—Built-in line/load straps
—Fits with existing 300-Line Starters
—Power factor correction terminals (sizes 1-4)
—DIN rail mountable sizes 1 & 2
Panel Mount
Size A* B C D
1 4.11 3.77 3.60 3.70
2 4.11 3.77 3.60 3.70
3 5.60 5.26 5.06 6.25
4 5.60 5.26 5.06 6.25
*If used
Panel Mount
Size A B C D* E F* G H*
1 7.00 3.63 3.94 3.92 3.70 4.76 6.50 .84
2 9.12 4.57 5.50 4.91 3.70 5.44 8.50 .84
3 11.62 5.32 6.50 5.66 6.24 7.50 10.62 .88
4 11.62 5.32 6.50 5.66 6.24 7.50 10.62 .88
*If used
Reference Publications
UL File E103664 CAS File LR30821
Publication DEP-058
Order Motor Starter publications from Section 16
Instructions – NEMA Size 1, 2 GEH-6430
Instructions – NEMA Size 3, 4 GEH-6431
Instructions – NEMA Size 5, 6 GEH-6432
Application
Designed for starting and stopping single-phase motors up to 10 HP. These manual
starters have provision for overload protection and their low cost provides economical
starter selection for applications where no undervoltage protection is required. This
line of starters may be used on such equipment as grinders, conveyors, fans, mixers,
and blowers.
Features
—Terminal design; box terminals provide easy access for wiring.
Open Starter
—Molded plastic switch housing; protects starter mechanism.
—Small size; open starter fits GEM™ or handy box.
right and ordered as a separate item at $6.00 each, GO-10H. CR123H (all) $6.00
One heater is required per starter (two for 2-speed forms and for The table below gives a proper size heater to trip the switch on
combination starter CR101H13). approximately 125 percent motor current.
Toggle-Operated Nonreversing Open1 Listed values are for motors with 1.15-1.25 service factor. For motors
List Price with 1.0 service factor continuously, multiply full-load current of
No. of Poles Product Number GO-10G3
motor by 0.9 and use this value to select heater. Contact nearest
1 CR101Y2 $33.00
2 CR101H2 $39.00 GE Energy Representative for recommendation on heaters to be used
1For flush or outlet box mounting. with definite-purpose motors. If motor full-load Amperes falls
2Units are individually boxed and “Poly-Packed” 10 per carton as standard.
between two ratings, select heater for the highest of those two.
Toggle-Operated Nonreversing Enclosed NEMA Type 13 For 1.35 service factor motors, multiply full-load current of motor
List Price by 1.15 and use this value to select heater(s).
No. of Poles Indicating Light Product Number GO-10G3
Maximum Motor
1 No CR101Y12 $39.00 Full-Load Amperes Heater Product Number
2 No CR101H12 $45.00 .48 CR123H055A
1 Yes CR101Y11 4 $57.00 .53 CR123H061A
2 Yes CR101H11 4 $63.00 .58 CR123H067A
2Units are individually boxed and “Poly-Packed” 10 per carton as standard. .65 CR123H074A
3Surface mounting. .71 CR123H082A
4Includes a 115/230-Volt neon lamp(s). Not available at 277 Volts. .78 CR123H090A
.86 CR123H099A
Lever-Operated Nonreversing Enclosed NEMA Type 3/4/12 .95 CR123H108A
1.04 CR123H120A
List Price
1.14 CR123H132A
No. of Poles Hubs Product Number GO-10G3
1.25 CR123H144A
1 3/4-inch Hub on One End CR101Y400H $138.00 1.37 CR123H158A
2 3/4-inch Hub on One End CR101H400H $144.00 1.49 CR123H172A
1 3/4-inch Hub on Both Ends CR101Y400J $150.00 1.63 CR123H188A
2 3/4-inch Hub on Both Ends CR101H400J $156.00 1.78 CR123H205A
1.95 CR123H224A
Multi-speed Enclosed NEMA Type 1 Surface Mount 2.13 CR123H245A
List Price 2.32 CR123H267A
No. of Poles Indicating Light Product Number GO-10G3 2.53 CR123H291A
2.76 CR123H317A
1 None CR101Y600B $172.00 3.01 CR123H346A
1 Two CR101Y610B4 $255.00 3.27 CR123H377A
2 None CR101H600B $187.00 3.56 CR123H410A
2 Two CR101H610B4 $270.00 3.88 CR123H446A
4Includes a 115/230-Volt neon lamp(s). Not available at 277 Volts. 4.22 CR123H486A
4.60 CR123H529A
Multi-speed Enclosed NEMA Type 1 Gray Flush-Plate 5.00 CR123H575A
List Price 5.43 CR123H625A
No. of Poles Indicating Light Product Number GO-10G3 5.90 CR123H680A
6.41 CR123H739A
1 None CR101Y600A $165.00
6.98 CR123H802A
1 Two CR101Y610A4 $247.00
7.60 CR123H873A
2 None CR101H600A $180.00
8.25 CR123H950A
2 Two CR101H610A4 $262.00 8.95 CR123H103B
4Includes a 115/230-Volt neon lamp(s). Not available at 277 Volts.
9.75 CR123H112B
10.6 CR123H122B
Multi-speed Enclosed NEMA Type 1 Stainless-Steel Flush-Plate 11.4 CR123H132B
List Price 12.5 CR123H144B
No. of Poles Indicating Light Product Number GO-10G3 13.6 CR123H157B
14.8 CR123H171B
1 None CR101Y608A $172.00
16.0 CR123H186B
1 Two CR101Y618A4 $255.00
2 None CR101H608A $187.00
2 Two CR101H618A4 $270.00 Maximum Horsepower Ratings-AC or DC
4Includes a 115/230-Volt neon lamp(s). Not available at 277 Volts.
Continuous Carry-16 Amperes
Combination Device Enclosed NEMA Type 1 Product No. of Horsepower Horsepower Horsepower Horsepower Horsepower Horsepower
Number Poles @ 32 V AC @ 115 V AC @ 230 V AC @ 277 V AC @ 115 V DC @ 230 V DC
List Price
No. of Poles Description Product Number GO-10G3 CR101Y 1 1/4 1 1 — 1 1/4
CR101H 2 1/4 1 1 3/4 1 1
2 CR101H + Base Unit HOA CR101H12 $102.00
2 2 (CR101H) CR101H13 $108.00
CR101 Manual Starter in Type 1 Enclosure, 2 lbs. CR101H12 or CR101X13 Combination Starter, 4 lbs.
CR101 Two-Speed Manual Starter in Type 1 Enclosure, 3 lbs. CR101 Manual Starter in Type 4 Enclosure, 4 lbs.
CR101X12 or CR101X13 Combination Flush Plate, 1 lb. CR101 Manual Starter, Open Type, 1 lb.
Schematic Diagrams
Horsepower Ratings
Maximum Horsepower Ratings
Coil Motor Voltage and Frequency
60 Hertz 50 Hertz
Phase NEMA Size 115 V 200-208 V 230-240 V 277 V 460-600 V 380 V
M-0 1 — 2 2 — —
Single M-1 2 — 3 2 — —
M-1P 3 — 5 2 — —
M- 0 — 3 3 — 5 5
Three
M- 1 — 7-1/2 7-1/2 — 10 10
Reference Publications
Instructions GEH-4737
1 Select NEMA Size and Number of Poles 4 Select Type of Operator and Enclosure Type
List Price List Price
NEMA Size Number of Poles Product No. Digits Adder, GO-10G3 Type of Operator Enclosure Class Product No. Digit Adder, GO-10G3
Single-Phase DC (in series) R1 $120.00 Open P1 $0.00
M-0 Single-Phase (AC) R2 $99.00 Type 1 P2 $12.00
3-Pole Three-Phase R3 $120.00 Push Button Type 3/12/13 — —
Single-Phase DC (in series) S1 $150.00 Type 4/4X — —
M-1 Single-Phase (AC) S2 $129.00 Flush Mounted P5 $146.00
3-Pole Three-Phase S3 $150.00 Open T1 $0.00
Single-Phase DC (in series) — — Type 1 T2 $12.00
M-1P Single-Phase AC in Parallel T2 $195.00 Toggle Lever Type 3/12/13 T3 $54.00
3-Pole Three-Phase — — Type 4/4X T4 $246.00
Flush Mounted T5 $146.00
No hubs installed on Types 1, 3, 12, and 13 enclosures. 3/4-inch hubs
2 Select Protection standard on Type 4X enclosures.
Single-Phase Three-Phase
Product No. List Price Product No. List Price 5 Select Indicating Light Option
Protection Digit Adder, GO-10G3 Digit Adder, GO-10G3
Product No. Digit
Standard Overload A $0.00 A $0.00
List Price Type 3/12/13 List Price
Omit Overload B Deduct $9.00 B Deduct $24.00 Type 1 Adder, and 4/4X Adder,
Enclosure GO-10G3 Enclosures GO-10G3
Order heaters as a separate item from Heater Selection Tables, page 1-174.
No Indicating Light 00 $0.00 00 $0.00
120 V/60 Hz 100 V/50 Hz 02 $48.00 02 $162.00
240 V/60 Hz 220 V/50 Hz 03 $48.00 03 $162.00
480 V/60 Hz 440 V/50 Hz 04 $48.00 04 $162.00
3 Select Auxiliary Contacts
600 V/60 Hz 05 $48.00 05 $162.00
Size 0 Size 1 Size 1-P
List Price List Price List Price
Auxiliary Product No. Adder, Product No. Adder, Product No. Adder,
Contacts Digit GO-10G3 Digit GO-10G3 Digit GO-10G3 6 Select Indicating Light Color
None A $0.00 A $0.00 A $0.00
Indicating Light Color Product No. Digit
1 NO B $60.00 B $72.00 B $72.00
No Indicating Light Ø
2 NO C $120.00 C $144.00 — —
Red Light R
Cannot have 2 auxiliary contacts with size 1-P device.
Green Light G
Enclosure Kits
Product List Price,
Description Number GO-10G3
➋ ➌
Type 1 Enclosure for Toggle- CR1062X9 $12.00
C R 1 0 6 2 Operated 2- to 4-Pole Starters
Type 1 Enclosure for Push Button- CR1062X10 $12.00
Operated 2- to 4-Pole Starters
Example: CR1062S3ABT302R is a Size M-1 three-phase starter Type 3/12/13 Enclosure (no hubs) CR1062X28 $54.00
with overload protection, 1NO auxiliary contact and toggle opera- Toggle Devices Only
tion in a NEMA Type 3/12/13 enclosure with a red 120V indicating Type 4X Enclosure (with hubs) CR1062X23 $246.00
Toggle Devices Only
light at $150.00 + 72.00 + 54.00 + 162.00 = $438.00 each.
Type 1 Flush-Mounted Enclosure for CR1062X30 $146.00
Toggle-Operated Starters
Type 1 Flush-Mounted Enclosure for CR1062X31 $146.00
Push Button-Operated Starters
Open
List Price
NEMA Size Motor Type Operator Type Product Number GO-10G3
M-0 Single Phase Push Button CR1062R2AAP1000 $99.00
M-1 Single Phase Push Button CR1062S2AAP1000 $129.00
M-1P Single Phase Push Button CR1062T2AAP1000 $195.00
M-0 Three Phase Push Button CR1062R3AAP1000 $120.00
M-1 Three Phase Push Button CR1062S3AAP1000 $150.00
M-0 Single Phase Toggle CR1062R2AAT1000 $99.00
M-1 Single Phase Toggle CR1062S2AAT1000 $129.00
M-1P Single Phase Toggle CR1062T2AAT1000 $195.00
M-0 Three Phase Toggle CR1062R3AAT1000 $120.00
M-1 Three Phase Toggle CR1062S3AAT1000 $150.00
Type 4-4X
Open Type Toggle and Push Button Operated, NEMA NEMA Type 3/12/13/4/4X Enclosure, NEMA
Sizes M-0 and M-1; 2-, 3- and 4-Pole; Sizes M-0, M-1 and M-1P; 2-, 3- and 4-Pole;
Approximate shipping weight 2 1/2 lbs. Approximate shipping weight 6 lbs.
Reference Publications
Heater Selection Guide GET-2681
Application
Specifically designed for outdoor installation, these pumping
panels provide full voltage control of squirrel-cage pump motors.
They offer protection from motor burnouts due to overloading,
protection against untimely restarts after power failure, and pro-
tection of the motor circuit against damage from short circuits.
Enclosure provides additional space for customer to mount
desired modifications and accessories. Custom panel designs
available upon request. Contact nearest GE Energy representative
or authorized distributor for additional information.
The following tables contain common product numbers. Use the selection guide starting on page 1-181 to select other configurations.
Without Overload
NEMA Size No overload list price deduction
1 $30.00
2 $54.00
3 $90.00
4 $144.00
5 $504.00
Example: CR341K013BAA1AA becomes CR341K043BAA1AA at $711.
The following tables contain common product numbers. Use the selection guide starting on page 1-181 to select other configurations.
*Coil Table
(To Complete Product Number)
The following tables contain common product numbers. Use the selection guide starting on page 1-181 to select other configurations.
Class H Fuse Clips
Maximum Maximum Fuse Clip Maximum Overload NEMA Type 3R Narrow NEMA Type 3R Wide
NEMA Horsepower Horsepower Rating Fuse Rating Range Product Number List Price Product Number List Price
Size (3 phase) @ 230-240V1 (3 phase) @ 440-480V1 (Amps) (Amps) (Amps) CR GO-10GP CR GO-10GP
1 - - 30 3 0.4-0.85 341K0X*BAA1AAC $780.00 341C0X*BAA1AAC $807.00
1 - 0.75 30 6 0.8-1.7 341K0X*BAA1AAD $780.00 341C0X*BAA1AAD $807.00
1 0.75 2 30 10 1.6-3.4 341K0X*BAA1AAE $780.00 341C0X*BAA1AAE $807.00
1 2 3 30 25 3.2-6.8 341K0X*BAA1AAF $780.00 341C0X*BAA1AAF $807.00
1 3 7.5 30 30 6.5-13.5 341K0X*BAA1AAG $780.00 341C0X*BAA1AAG $807.00
1 7.5 10 30 30 13-27 341K0X*BAA1AAH $780.00 341C0X*BAA1AAH $807.00
2 3 7.5 30 30 6.5-13.5 341L0X*BAA1AAG $1056.00 341D0X*BAA1AAG $1082.00
2 7.5 20 60 60 13-27 341L0X*CAA1AAH $1056.00 341D0X*CAA1AAH $1082.00
2 15 25 60 60 25-50 341L0X*CAA1AAJ $1056.00 341D0X*CAA1AAJ $1082.00
3 10 25 60 50 17-35 - - 341E0X*CAC1AAK3 $1881.00
3 25 50 60 60 35-70 - - 341E0X*CAC1AAL3 $1881.00
3 30 - 60 60 65-90 - - 341E0X*CAC1AAM3 $1881.00
4 10 25 200 200 17-35 - - 341F0X*EAC1AAK3 $3327.00
4 25 50 200 200 35-70 - - 341F0X*EAC1AAL3 $3327.00
4 50 100 200 200 65-135 - - 341F0X*EAC1AAM3 $3327.00
5 50 100 200 200 65-135 - - 341G0X*EAC1AAP3 $7048.00
5 100 200 400 400 130-270 - - 341G0X*FAC1AAQv $7048.00
6 100 200 600 600 130-270 - - 341H0X*GAD1AAS3 $18330.00
6 200 400 1200 1200 260-540 - - 341H0X*LAD1AAT3 $18330.00
* Insert number from coil table below in place of asterisk in product number for voltage/frequency desired.
*Coil Table
(To Complete Product Number)
Digits: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
C R
Steps: Step 1 Step 2 Step 3 Step 4 Step 5 Step 6 Step 7 Step 8 Step 9 Step 10 Step 11
To configure the part number, use the tables below to fill in the digit boxes with the appropriate code.
Add list price from each step to arrive at total list for price for starter.
Step 1 (Digits 1-6) Select Pump Panel Type, NEMA Size & Enclosure (NEMA Sizes 1 & 2)
NEMA Size 1 NEMA Size 2
Narrow List Wide List Narrow List Wide List
Enclosure Price Enclosure Price Enclosure Price Enclosure Price
Voltage CR GO-10GP CR GO-10GP CR GO-10GP CR GO-10GP
Pumping Panel - Fusible Disconnect 230-240 341K $741.00 341C $768.00 341L $1011.00 341D $1038.00
Pumping Panel - Fusible Disconnect 460-480 341K $753.00 341C $780.00 341L $1029.00 341D $1056.00
Step 1 (Digits 1-6) Select Pump Panel Type, NEMA Size & Enclosure (NEMA Sizes 3 - 5)
NEMA Size 3 NEMA Size 4 NEMA Size 5
Narrow List Wide List Narrow List Wide List Narrow List Wide List
Enclosure Price Enclosure Price Enclosure Price Enclosure Price Enclosure Price Enclosure Price
Voltage CR GO-10GP CR GO-10GP CR GO-10GP CR GO-10GP CR GO-10GP CR GO-10GP
Pumping Panel - Fusible Disconnect 230-240 N/A - 341E $1818.00 N/A - 341F $3276.00 N/A - 341G $6876.00
Pumping Panel - Fusible Disconnect 460-480 N/A - 341E $1854.00 N/A - 341F $3300.00 N/A - 341G $7020.00
Note for sizes 3, 4 & 5: Control Circuit Fusing (CCF) included in pricing. In Step 7 (Digit 12), page 1-182, select appropriate code including CCF.
The following tables contain common product numbers. Use the selection guide starting on page 1-187 to select other configurations.
Mag-Break Type
Coil Maximum NEMA Type 3R Narrow NEMA Type 3R Wide
Voltage NEMA Horsepower CB Rating Product Number List Price Product Number List Price
(60Hz)1 Size (3 phase) (Amps) CR GO-10GP CR GO-10GP
230-240 1 3 15 340K213CAC1AA $957.00 340C213CAC1AA $984.00
230-240 1 7 1/2 30 340K213DAC1AA $957.00 340C213DAC1AA $984.00
230-240 2 15 50 340L213EAC1AA $1197.00 340D213EAC1AA $1224.00
230-240 3 30 100 - - 340E213FAC1AA $1746.00
230-240 4 50 150 - - 340F213GAC1AA $3828.00
230-240 5 100 400 - - 340G213HAC1AA $8538.00
460-480 1 7 1/2 15 340K214CAC1AA $957.00 340C214CAC1AA $984.00
460-480 1 10 30 340K214DAC1AA $957.00 340C214DAC1AA2 $984.00
460-480 2 25 50 340L214EAC1AA $1197.00 340D214EAC1AA2 $1224.00
460-480 3 50 100 - - 340E214FAC1AA2 $1746.00
460-480 4 100 150 - - 340F214GAC1AA2 $3828.00
460-480 5 200 400 - - 340G214HAC1AA $8538.00
460-480 6 400 600 - - 340H214KAD1AA $18357.00
460-480 7 600 1200 - - 340J214NAD1AA $24681.00
For pump panel without overload (sizes 0-5 only), change 8th digit in product number from "1" to "4" and subtract price according to table below.
Without Overload
NEMA Size No overload list price deduction
1 $30.00
2 $54.00
3 $90.00
4 $144.00
5 $504.00
Example: CR340K013AAA1AA becomes CR340K043AAA1AA at $735.00.
150 Hertz forms are available. Contact nearest GE Energy Representative for proper
selection and pricing.
2Available with CL-type current limiter and UL listed 100kA/C short-circuit rating,
contact a GE Energy Representative for availability and pricing. The 7th digit in the
product number changes to "3".
General Note:
Control Circuit Fusing included in pricing for Mag-Break Type.
The following tables contain common product numbers. Use the selection guide starting on page 1-187 to select other configurations.
Mag-Break Type with Thermal Overload Relay, Thermal Class 10 with Differential Protection
Maximum Maximum Maximum Overload NEMA Type 3R Narrow NEMA Type 3R Wide
NEMA Horsepower Horsepower CB Rating Range Product Number List Price Product Number List Price
Size (3 phase) @ 230-240V1 (3 phase) @ 440-480V1 (Amps) (Amps) CR GO-10GP CR GO-10GP
1 - 1 7 1.3-1.9 340K29*BAC1AAG $1089.00 340C29*BAC1AAG $1116.00
1 1/2 1 1/2 7 1.8-2.7 340K29*BAC1AAH $1089.00 340C29*BAC1AAH $1116.00
1 1 2 15 2.5-4.1 340K29*CAC1AAJ $1089.00 340C29*CAC1AAJ $1116.00
1 1 1/2 3 15 4.0-6.3 340K29*CAC1AAK $1089.00 340C29*CAC1AAK $1116.00
1 2 5 15 5.5-8.5 340K29*CAC1AAL $1089.00 340C29*CAC1AAL $1116.00
1 3 7 1/2 30 8.0-12.0 340K29*DAC1AAM $1089.00 340C29*DAC1AAM $1116.00
1 5 10 30 10.0-16.0 340K29*DAC1AAP $1089.00 340C29*DAC1AAP $1116.00
1 - - 30 14.5-18.0 340K29*DAC1AAR $1089.00 340C29*DAC1AAR $1116.00
1 - - 30 17.5-22.0 340K29*DAC1AAS $1089.00 340C29*DAC1AAS $1116.00
1 7 1/2 - 30 21.0-26.0 340K29*DAC1AAT $1089.00 340C29*DAC1AAT $1116.00
2 - 15 30 17.5-22.0 340L29*DAC1AAG $1329.00 340D29*DAC1AAG $1356.00
2 - - 50 21-26 340L29*EAC1AAH $1329.00 340D29*EAC1AAH $1356.00
2 10 20 50 25-32 340L29*EAC1AAJ $1329.00 340D29*EAC1AAJ $1356.00
2 - 25 50 30-43 340L29*EAC1AAK $1329.00 340D29*EAC1AAK $1356.00
2 15 - 50 42-55 340L29*EAC1AAL $1329.00 340D29*EAC1AAL $1356.00
3 - 30 50 30-43 - - 340E29*EAC1AAG $1878.00
3 20 40 100 42-55 - - 340E29*FAC1AAH $1878.00
3 - - 100 54-65 - - 340E29*FAC1AAJ $1878.00
3 30 50 100 63-90 - - 340E29*FAC1AAK $1878.00
4 - 60 100 63-90 - - 340F29*FAC1AAG $3828.00
4 40 100 150 90-120 - - 340F29*GAC1AAH $3828.00
4 50 - 150 110-140 - - 340F29*GAC1AAJ $3828.00
5 75 150 400 120-190 - - 340G29*HAC1AAG $8538.00
5 - 200 400 175-280 - - 340G29*HAC1AAH $8538.00
5 100 - 400 200-310 - - 340G29*HAC1AAJ $8538.00
* Insert number from coil table below in place of asterisk in product number for voltage/frequency desired
*Coil Table
(To Complete Product Number)
General Note:
Control Circuit Fusing included in pricing for Mag-Break Type.
The following tables contain common product numbers. Use the selection guide starting on page 1-187 to select other configurations.
Mag-Break Type with Thermal Overload Relay, Solid State Class 10-20-30 Electronic Overload
Maximum Maximum CB Trip Overload NEMA Type 3R Narrow NEMA Type 3R Wide
NEMA Horsepower Horsepower Rating Range Product Number List Price Product Number List Price
Size (3 phase) @ 230-240V1 (3 phase) @ 440-480V1 (Amps) (Amps) CR GO-10GP CR GO-10GP
1 - - 3 0.4-0.85 340K2X*AAC1AAC $1084.00 340C2X*AAC1AAC $1011.00
1 - 0.75 3 0.8-1.7 340K2X*AAC1AAD $1084.00 340C2X*AAC1AAD $1011.00
1 0.75 2 7 1.6-3.4 340K2X*BAC1AAE $1216.00 340C2X*BAC1AAE $1143.00
1 2 3 7 3.2-6.8 340K2X*BAC1AAF $1216.00 340C2X*BAC1AAF $1143.00
1 3 7.5 7 6.5-13.5 340K2X*BAC1AAG $1216.00 340C2X*BAC1AAG $1143.00
1 7.5 10 30 13-27 340K2X*DAC1AAH $1216.00 340C2X*DAC1AAH $1143.00
2 3 7.5 30 6.5-13.5 340L2X*DAC1AAG $1356.00 340D2X*DAC1AAG $1383.00
2 7.5 20 50 13-27 340L2X*EAC1AAH $1356.00 340D2X*EAC1AAH $1383.00
2 15 25 50 25-50 340L2X*EAC1AAJ $1356.00 340D2X*EAC1AAJ $1383.00
3 10 25 50 17-35 - - 340E2X*EAC1AAK $1895.00
3 25 50 100 35-70 - - 340E2X*FAC1AAL $1895.00
3 30 - 100 65-90 - - 340E2X*FAC1AAM $1895.00
4 10 25 100 17-35 - - 340F2X*FAC1AAK $3755.00
4 25 50 100 35-70 - - 340F2X*FAC1AAL $3755.00
4 50 100 150 65-135 - - 340F2X*GAC1AAM $3755.00
5 50 100 150 65-135 - - 340G2X*GAC1AAP $8565.00
5 100 200 400 130-270 - - 340G2X*HAC1AAQ $8565.00
6 100 200 400 130-270 - - 340H2X*FAD1AAS $18385.00
6 200 400 600 260-540 - - 340H2X*GAD1AAT $18385.00
* Insert number from coil table below in place of asterisk in product number for voltage/frequency desired.
*Coil Table
(To Complete Product Number)
General Note:
Control Circuit Fusing included in pricing.
Digits: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
C R
Steps: Step 1 Step 2 Step 3 Step 4 Step 5 Step 6 Step 7 Step 8 Step 9 Step 10 Step 11
To configure the part number, use the tables below to fill in the digit boxes with the appropriate code.
Add list price from each step to arrive at total list for price for starter.
Step 1 (Digits 1-6) Select Pump Panel Type, NEMA Size & Enclosure (NEMA Sizes 1 & 2)
NEMA Size 1 NEMA Size 2
Narrow List Wide List Narrow List Wide List
Enclosure Price Enclosure Price Enclosure Price Enclosure Price
CR GO-10GP CR GO-10GP CR GO-10GP CR GO-10GP
Pumping Panel - Circuit Breaker Type 340K $957.00 340C $984.00 340L $1197.00 340D $1224.00
Step 1 (Digits 1-6) Select Pump Panel Type, NEMA Size & Enclosure (NEMA Sizes 3 - 5)
NEMA Size 3 NEMA Size 4 NEMA Size 5
Narrow List Wide List Narrow List Wide List Narrow List Wide List
Enclosure Price Enclosure Price Enclosure Price Enclosure Price Enclosure Price Enclosure Price
CR GO-10GP CR GO-10GP CR GO-10GP CR GO-10GP CR GO-10GP CR GO-10GP
Pumping Panel - Circuit Breaker Type N/A - 340E $1746.00 N/A - 340F $3828.00 N/A - 340G $8538.00
Note for sizes 4 & 5: Control Circuit Fusing (CCF) included in pricing. In Step 7 (Digit 12), page 1-188, select appropriate code including CCF.
11.72
(297.7)
8.26
3.63 (209.8) 3.63
(92.2) (92.2)
3.56 6.34
0.50 Ø0.44 (qty. 4) (90.5) (161.0)
(12.7) (Ø11.1)
Ø1.12 (qty. 2)
(Ø28.6)
ON
OFF
33.74
32.24 29.13 (857.0)
(818.9) (739.9)
28.12
(714.2)
Ø0.41 (qty. 4)
(Ø10.3)
0.75 0.50
(19.0) 16.07
(12.7) (408.1)
3.63 3.63
(92.2) (92.2)
8.26
(209.8)
CR340, CR341 NEMA Sizes 1 and 2 Narrow-Type Enclosures; 32 lbs. (Size 1), 47 lbs. (Size 2)
CR340, CR341 NEMA Sizes 1 and 2 Wide-Type Enclosures; 85 lbs. (Size 1), 90 lbs. (Size 2)
CR340, CR341 NEMA Sizes 6 and 7 Wide-Type Enclosures; 1,200 lbs. (Size 6), 1,300 lbs. (Size 7)
Application
GE’s magnetic contactor is designed for use on today’s modern
equipment. Especially suitable for handling the switching of
resistance heating and capacitor circuit loads, their compact size
also fits the needs of the panel building industry. In addition, they
may be used for controlling ac motors where overload protection
is provided separately. Typical CR305 Open-Type Magnetic Contactor
Features
—Easy disassembly for maintenance and inspection of contacts. 5. Holding Contacts
—Auxiliary contacts with vertical contact surfaces enclosed to Each CR305 contactor is furnished with a normally open auxil-
prevent accumulation of dust and dirt. iary contact for use as a holding interlock in three-wire control
—Attractive, modern squared-off design enclosure. circuits. This auxiliary contact has the same rating as a main
—Magnet faces specially treated to resist rust. pole (contact) for Sizes 00, 0, and 1. If this contact is not
—Provision for ring terminals may be specified as a special feature, required on these sizes, specify contactor with one less pole.
if required. No price addition applies for this optional feature.
6. 50 Hertz Contactors
Pricing of contactors for use on 50 Hertz is the same as in table
Product Number Selection Instructions
for 60 Hertz. See three-phase horsepower ratings for 380-415
1. Specify contactor by product number. Volts, 50 Hertz on page 1-6.
Example: CR305B103 at $186.00, GO-10G is a Size 0, 18-Ampere,
7. Product Notes
three-pole contactor (extra pole to be used as an auxiliary), with
Motor full-load current should not exceed continuous ampere
230-240 Volt 60 Hertz coil. Contactor is in Type 1 enclosure.
rating of contactor.
2. Order forms not listed or with special features by complete
description.
Example: Similar to CR305B103 at $186.00 except with a red Reference Publications
Instructions
indicating light in cover at $90.00. Total List Price: $276.00,
NEMA Size Publication Number
GO-10G. 00, 0, 1 GEH-5190
2 GEH-4774
3. The final letter of the product number denotes extra auxiliary 3 GEH-4806
contacts (sometimes referred to as auxiliary interlocks). Order 4 GEH-4807
the desired extra auxiliary contacts by replacing the final letter 5 GEH-4839
6 GEH-5198
from first column of auxiliary interlock table (see page 1-132). 7-9 GEH-5108
Example: CR305C102AAB at $282.00, GO-10G, is Size 1 contac-
tor with one extra auxiliary contact, normally open. Magnetic Nonreversing Contactors (CR305, CR385) – Contents
4. Contactors are available with coils of other ratings (at same Application Information and Selection Instructions
price) than those shown on pages 1-196 to 1-198. Refer to coil (CR305, CR385) ....................................................................................1-195
suffix table on page 1-8 for information. To order contactor NEMA Sizes 00-9, One- and Two-Pole (CR305, CR385) .......1-196
forms with these other coil ratings, insert suffix from table in NEMA Sizes 00-9, Three-Pole (CR305, CR385) .........................1-197
place of fifth and sixth numbers of contactor product number NEMA Sizes 00-9, Four-Pole (CR305, CR385)............................1-198
shown on pages 1-196 to 1-198. Factory Installed Modifications (CR305, CR385).....................1-199
Example: A CR305C123 NEMA Size 1, three-pole contactor in Outlines and Dimensions (CR305, CR385) .................................1-210
Type 1 enclosure, except with 24 Volt, 60 Hertz coil, becomes a
CR305C124 product number.
For NEMA Size 7-9 contactors with other control circuit voltages,
contact your nearest GE Energy Representative.
1Motor full-load current should not exceed continuous ampere rating of contactor.
CR385, Single-Phase, 2-Pole Magnetic Contactors NEMA sizes 7-9
Open Type
Product List
NEMA Continuous Control Number Price
Size Ampere Rating1 Circuit Voltage Horsepower CR385 GO-10G
7 900A 115-120 — S002AA1A $10722.00
7 900A 230-240 — S003AA1A $10722.00
7 900A 460-480 — S004AA1A $10722.00
7 900A 575-600 — S005AA1A $10722.00
8 1350A 115-120 — T002AA1A $17208.00
8 1350A 230-240 — T003AA1A $17208.00
8 1350A 460-480 — T004AA1A $17208.00
8 1350A 575-600 — T005AA1A $17208.00
9 2500A 115-120 — U002AA1A $22800.00
9 2500A 230-240 — U003AA1A $22800.00
9 2500A 460-480 — U004AA1A $22800.00
9 2500A 575-600 — U005AA1A $22800.00
1Motor full-load current should not exceed continuous ampere rating of contactor.
CR385, Three-Phase, 3-Pole Magnetic Contactors NEMA sizes 7-9
Open Type
Product List
NEMA Continuous Control Circuit Number Price
Size Ampere Rating1 Motor Voltage Horsepower Voltage CR385 GO-10G
7 900A N/A — 115 J002AA1A $12228.00
7 900A 220-240 300 230 J003AA1A $12228.00
7 900A 440-480 600 460 J004AA1A $12228.00
7 900A 550-600 600 575 J005AA1A $12228.00
8 1350A N/A — 115 K002AA1A $18876.00
8 1350A 220-240 450 230 K003AA1A $18876.00
8 1350A 440-480 900 460 K004AA1A $18876.00
8 1350A 550-600 900 575 K005AA1A $18876.00
9 2500A N/A — 115 L002AA1A $25410.00
9 2500A 220-240 800 230 L003AA1A $25410.00
9 2500A 440-480 1600 460 L004AA1A $25410.00
9 2500A 550-600 1600 575 L005AA1A $25410.00
Product Number Selection Instructions: See page 1-195 Other Coil Voltages: See page 1-8
Factory Installed Modifications: See pages 1-199 to 1-203
Field Installed Modifications: See pages 1-204 to 1-209
1d START Push Button and H-O-A Selector Any 2 $264.00 $264.00 $264.00 $264.00 $264.00 $264.00 $264.00
Switch (HEAVY-DUTY, CR104P)
Single Push Button, Unwired (Specify 1 2 $40.00 $40.00 $40.00 $40.00 $40.00 $40.00 $40.00
Marking) (HEAVY-DUTY, CR104P)
1e
Single Push Button, Unwired (Specify Any 2 $90.00 $90.00 $90.00 $90.00 $90.00 $90.00 $90.00
Marking) (HEAVY-DUTY, CR104P)
Single Illuminated Push Button, Unwired
Pilot 1f (Specify Marking) Any 2 $180.00 $180.00 $180.00 $180.00 $180.00 $180.00 $180.00
Devices
(HEAVY-DUTY, CR104P)
Mounted
in Cover 2 Selector Switches
or Flange
of HAND-OFF-AUTO1,3 1 $48.00 $48.00 $48.00 $48.00 $48.00 $48.00 $48.00 $132.00
CR305 2a HAND-OFF-AUTO1,3
Any 2 $132.00 $132.00 $132.00 $132.00 $132.00 $132.00 $132.00
(HEAVY-DUTY, CR104P)
OFF-ON1 1 $48.00 $48.00 $48.00 $48.00 $48.00 $48.00 $48.00 $132.00
2b
Any 2 $132.00 $132.00 $132.00 $132.00 $132.00 $132.00 $132.00
OFF-ON (HEAVY-DUTY, CR104P)
Single Selector Switch Maintained
(Specify Marking)
2c Two- or Three-Position (Specify 2
Any $132.00 $132.00 $132.00 $132.00 $132.00 $132.00 $132.00
Position) 4 (HEAVY-DUTY, CR104P)
4 2
Four-Position (HEAVY-DUTY, CR104P) Any $150.00 $150.00 $150.00 $150.00 $150.00 $150.00 $150.00
Key Operated Maintained (Specify
Marking and Key-Removal Position)
2d
Two- or Three-Position4 2
Any $168.00 $168.00 $168.00 $168.00 $168.00 $168.00 $168.00
(HEAVY-DUTY, CR104P)
3 Any 2 $9.00 $9.00 $9.00 $9.00 $9.00 $9.00 $9.00
Nonstandard Markings (Specify)
1 Factory-installed modification kit for sizes 00-5.
2 Not available in NEMA Size 00. Use Size 0 starter and modification.
3 This modification not available with items 1a, 1b or 1c because STOP
push button would not work in AUTO position; instead order modification 1d.
4 Specify CR104 operator and contact block by product number
Reference Publications
Instructions
NEMA Size Publication Number
00, 0, 1 GEH-5190
2 GEH-4774
3 GEH-4806
4 GEH-4807
5 GEH-4839
6 GEH-5198
NEMA Size
Type of 00 0 1 2 3 4 5 6
Installation/ Item Enclosure
Contactors No. Modifications Type List Price Addition, GO-10G
Separate Control Circuit (Specify Voltage and
8 Frequency, Reference Items 13a and 13b for Any N/C N/C N/C N/C N/C N/C N/C N/C
Standard Voltages)
1 $132.00
9 Fused Control Circuit—Two Fuses Any $132.00 $132.00 $132.00 $132.00 $132.00 $132.00
11 Control Transformer—100 VA Additional Any 1 $288.00 $288.00 $372.00 $468.00 $528.00 $588.00 $588.00
Capacity, 60 Hertz
12
13 Operating Coil
4 Standard Voltages at 60 Hertz: Any N/C N/C N/C N/C N/C N/C N/C N/C
13a
24, 115-120, 200-208, 230-240, 460-480, 575-600
13b Standard Voltages at 50 Hertz: Any N/C N/C N/C N/C N/C N/C N/C N/C
110, 220, 380-415, 440, 550
DC—Standard Voltages: Any 3 3 $102.00 $114.00 $198.0 0 $264.00 $720.00 $720.00
13d
24, 115-125
1 Not available in NEMA Size 00. Use size 0 contactor modification.
2 The National Electrical Code, Article 450-3(B), requires primary fuses in most typical installations. Refer to the NEC, Article 450 prior to ordering control
transformer without primary fuses to insure compliance. Control circuit fuse kits from page 1-162 may be used to provide primary fusing. Fuses must be
sized to meet the requirements of the NEC according to the table below.
3 Not available in NEMA Sizes 00 or 0. Use Size 1 contactor modification.
4 24V coil not available on size 5 and 6.
Recommended Fuse
Primary Voltage
CPT VA 208/240 480 600
50 1 0.5 0.5
100 2 1 0.75
150 3 1.5 1
250 5 2 2
300 6 3 2
1 NEMA Type 1 enclosures require oiltight pilot devices when this 2 Not available in NEMA Size 00. Use Size 0 contactor modification.
modification is used with NEMA Contactor sizes 0, 1, and 2. 3 Requires 100 VA extra capacity control transformer.
Only oiltight pilot devices will fit the oversized enclosure required.
The list price addition for the oversized enclosure is already
included in the published list price.
NEMA Size
Type of 00 0 1 2 3 4 5 6
Installation/ Item Enclosure
Contactors No. Modifications Type List Price Addition, GO-10G
Space Heater 2
Enclosure 50 Watts—NEMA Size 0-4
30 Any 1 $120.00 $120.00 $120.00 $120.00 $120.00 $120.00 $420.00
CR305 Contactor/Starter
100 Watts—NEMA Size 5
Contactor
31 Operating Coil Surge Any $54.00 $54.00 $54.00 $54.00 $54.00 $54.00 $54.00 $54.00
Suppressor (120 V/60 Hz)
Misc. 32 Insulated Neutral Lug Any 1 $132.00 $132.00 $132.00 $132.00 $132.00 $132.00 $132.00
Mounted On
33 Any 1 $48.00 $48.00 $48.00 $48.00 $48.00 $48.00 $48.00
CR305 Ground Lug
34 Terminal Block, (Product Number CR151B) Any 1 $24.00 $24.00 $24.00 $24.00 $24.00 $24.00 $24.00
30A, Unwired (per point) (Specify Points)
35 Power Factor Correction Capacitor Any 1 $24.00 $24.00 $24.00 $24.00 $24.00 $24.00 $24.00
Terminals
1 Not available in NEMA Size 00. Use Size 0 contactor modification.
2 If connected to control circuit transformer, 115-Volt heater requires
an extra capacity transformer for Size 0-1 and Size 5.
Heater Selection Tables: See pages 1-155 to 1-161 Product Number Selection Instructions: See page 1-199
Contact Location
5 Contacts Max.
Contact Location
4 Contacts Max.
Final Suffix Letter of
Product No. on Contactor W X Y T Z U
A or None
B
C
D
E
F
G
H
J
K
L
M
NEMA Sizes 0 and 1,
N
Single-Speed, Nonreversing 2- and 3-Pole Contactors
P
R
Contact Location
5 Contacts Max.
Contact Location
Final Suffix Letter of 5 Contacts Max.
Product No. on Contactor W X Y T Z
A or None
B
C
D
E
F
G
H
J
K
L
M
N
P
R
S
Typical connection diagram,
T
NEMA Sizes 7-9
U
W
X
Y
Application
Auxiliary contacts can add to the versatility of magnetic contac-
tors by providing additional control circuits to do a variety of jobs
without adding to the width of the contactor.
Kits make it easy to add contacts to control accessory equipment
such as indicating lights. Auxiliary contacts can be added to all
across-the-line magnetic contactors. Each auxiliary contact is
rated 10 Amperes ac, resistive load, NEMA “A600,” and is suitable
for either right or left side mounting. An insulating shield is also
provided between each auxiliary contact unit and the contactor.
Auxiliary contacts are furnished in the basic block design or as an
adder block.
Each contact is marked NO or NC on the block and is not con-
vertible. Logic reed contacts suitable for low energy level circuits
are also available. These are designed for applications on low-
voltage control circuits (24 Volts and below), such as inputs to Basic Block and Adder Block
computers and programmable starters.
Reference Publications
Instructions
NEMA Size Publication Number
0, 1 GEH-4758
2 GEH-4759
3, 4 GEH-4760
5, 6 GEH-4761
7-9 GEH-5109
0, 1 Logic Reed GEH-5178
2 Logic Reed GEH-5185
3, 4 Logic Reed GEH-5186
5, 6 Logic Reed GEH-5187
Standard Block
Continuous Inrush Continuous Inrush
AC Volts Current Amperes Current Amperes DC Volts Current Amperes Current Amperes
115 6.0 60 125 1.1 —
230 3.0 30 250 0.5 —
460 1.5 15 — — —
575 1.2 12 — — —
1First adder block must be mounted to a basic block. A second adder block can be added to the first adder block on size 2 through size 9 starters.
Four extra auxiliary contacts (not blocks) is the maximum that can be added to either a NEMA size 0 or 1 starter while five is the maximum extra auxiliary contacts that can
be added to NEMA Size 2 through 6 devices.
2CR305X logic reed switch auxiliary contacts may be ordered as a factory-installed modification. Order by description. For factory-installed modification,
add $75.00, GO-10G, per circuit to price of starter.
Fifth-Pole Kits
To be installed on NEMA Size 0, 1, and 2 magnetic four-pole contactors. Permits the
addition of a fifth pole with the same rating as the main poles.
NEMA Mounting Product List Price
Size Position Number GO-10G
0, 1 Right CR305X111B $66.00
2 (add to 4-pole form) Left CR305X211B $120.00
Control Amplifier
The GE CR305X control amplifier is suitable for applications with low level 24 Volt dc
outputs. It allows the low level signals from a programmable control, microprocessor,
or photoelectric cell to operate GE’s 300-Line contactors while their control coils operate
at the line voltage. The control amplifier is UL listed and CSA Certified, and forms are
available for NEMA Sizes 00 through 5.
Operation NEMA Product List Price
Type Size Number GO-10G
Nonreversing 00, 0, & 1 CR305X112A $54.00
Nonreversing 2 CR305X212A $54.00
Nonreversing 3&4 CR305X312A $54.00
Nonreversing 00, 0, 1, 2, 3, & 4 CR305X112P1 $54.00
1A quantity of two panel mount CR305X112P is required for use with reversing contactors and starters.
Instructions, Push Button and Selector Switch Kits for Type 1 Enclosure
NEMA Size Publication Number
00, 0, 1 GEH-4763
2 GEH-4764
3, 4 GEH-4765
5 GEH-4766
Reference Publications
Instructions:
Space heater kits GEH-4772
Control transformer kits GEH-4842
Open Type, NEMA Sizes 00-1, (auxiliary interlocks Open Type, NEMA Size 2, 7 lbs.
not provided on size 00); 2 3/4 lbs.
Open Type, NEMA Sizes 3 and 4; 17 1/2 lbs. Open Type, NEMA Size 5, 50 lbs.
CR305, NEMA Size 6, Type 1 and Type 12 CR385, Open Type, NEMA Size 7, 82 lbs.
CR305, Open Type, NEMA Size 6; 50 lbs. CR385, Open Type, NEMA Size 9, 310 lbs.
NOTES: