INTRODUCTION
The Company
The Product
The G-Volution Series is the latest Precision Air Conditioning units from Citec
International that are engineered to run seamlessly in critical environments by
delivering constant, efficient and intelligent cooling circulation consistently and
reliably for 24 hours per day, 7 days per week.
The G-Volution Series is designed for areas with limited space as well as large data
centers. The units are designed with wide range of options to meet the requirement of
precision cooling needs in various applications and environment. Typical applications
include:
o Data Centers
o Computer Rooms
o Telecommunication Rooms
o Co-location Centers
o ISP
o Hospital Operating Rooms
o Laboratories
The G-Volution Chilled Water type Precision Air Conditioning units cover capacity
range from 25kW to 200kW, and distributed over 2 different model ranges, i.e. EC
and ECL. Each model range has its own unique features for different design
objectives and optimized for specific application.
The G-Volution EC Range units are available in both downflow and upflow
configuration while ECL range units are only available in downflow configuration.
The G-Volution CW units only require front service access, thus can be easily
installed side by side or tucked into a corner.
~1~
EC Range
ECL Range
The Citec ECL Range is design to further maximize the coil surface area by letting
the fan operated under the raise floor. The design allows the units to have largest coil
surface area possible and at the same time, optimizes the air flow and increase the fan
efficiency, thus achieving highest efficiency with minimum foot print. The ECL
Range is best suited for data centers with high raise floor.
~2~
FEATURES AND BENEFITS
The solid and rigid double skin insulated access panels on the G-Volution Series
ensure excellent sound isolation and greatly reduce the breakout noise of the unit. The
special FERMAPOR gasket on the door panels effectively eliminates air leakage from
the units. This gasket is applied to the door panels using a special machine to ensure
strong bonding between the gasket and the panels, thus increase the reliability of the
whole panel assembly.
Modulating ball valve with equal percentage characteristic is used to ensure excellent
control of water flow through the cooling coil. The flow characterised disc inside the
valve has greatly enhance the control stability especially under low load condition.
The standard valve is rated PN25 and has high closed-off pressure rating, therefore
suitable for wide range of operating condition.
The G-Volution Series offer 3 types of fan configuration. DIDW centrifugal fan
driven by AC motor is fitted as standard while high efficiency Electronically
Commutated (EC) Fan is offered as option. Apart from increasing the efficiency of
the units, EC Fan also enable various control strategies for data center cooling such as
underfloor pressure control and variable air flow control. For downflow system, if the
raise floor has sufficient height (>400mm), then the efficiency of the unit can be
further improved as much as 15% by locating the EC fan under the raise floor. For
Citec G-Volution Series Underfloor EC Fan option, the fans are located inside the unit
during transportation. After the unit is in position, the fans will be lowered down to
underfloor. This has greatly simplified the installation process and also future service
and maintenance.
Inlet water temperature and outlet water temperature can be fitted to the units to
monitor the supply and return water condition. The unit would provide early warning
if the incoming water is out of the desired operating condition, thus enable early
rectification actions and prevent potential downtime.
Cooling Coil
Hydrophilic fin provides additional protection to the coil and at the same time, ensure
fast removal of condensate on the coil. Thus, improves the heat transfer and
~3~
performance of the coil. Hydrophilic fin also reduce the air friction loss across the coil,
thus reduce the fan power requirement.
Heaters
Depends on models, single stage or multiple stages of PTC heating elements are
balanced over 3 phases and comes with safe dynamic self-regulating function. It
automatic controls the thermal power through air flow to eliminate the possibility of
overheating when air flow is low. It operates at a nearly constant temperature and fast
heat up promise an accurate control of temperature. Uniform heating without power
variation extend the life span of the elements. Proportional heating capacity is
available as an option via power regulators. All heaters are protected by thermal cut-
out switches. The heater may be interlocked with humidifier to reduce power
requirement when operating under power restricted area.
High and low voltage cables are segregated and each component is protected by
individual MCB. AC3 components such as fan motors are protected by manual motor
starters. All cabling are colour coded and numbered for easy reference.
Genius 5+ Controller
The latest Citec Genius 5+ ontroller provides intelligent and advance control for
precision cooling application. The G-Volution Series fitted with Genius 5+ controller,
offered highest flexibility and capability in mission critical cooling control, remote
monitoring and system integration. The Genius 5+ controller supports wide range of
cooling control strategies for mission critical facilities including auto-sequencing,
supply air control and containment system. Energy saving features such as EC fan
control and intelligent humidity control are built-in to the standard control program.
Optional touch screen display provides informative and user-friendly interface for
easy navigation. The display can show graphical information via animated icons and
also capable of plotting trend graphs for temperature and humidity. The display can
support multiple languages such as English, Malay, Chinese, Thai and Japanese.
Humidity Control
The G-Volution Series offered 2 humidity control mode, i.e. the conventional RH
Control Mode and the ASHRAE TC9.9 compliance Dew Point Control Mode.
~4~
RH Control Mode (Relative Humidity Control)
In RH Control Mode, room humidity is control in term of Relative Humidity (RH). As
RH is not directly reflexes the actual moisture content in the air, keeping constant RH
might involve adding and removing of moisture just because the change of
%
40
20 %
30
°C
e- ASHRAE 2004 Recommendation
5
10%
~5~
NOMENCLATURE
E C D 25 A
E - G-Volution Series
D - Downflow
U ± Upflow
L ± Large Capacity
~6~
AIR FLOW ARRANGEMENT
~7~
Type D (EC Only):
Downflow unit, discharge into raise
floor. Top return.
Type E:
Downflow unit, with bottom discharge
plenum. Top return.
Type F:
Downflow unit, with underfloor EC
Fans. Top return.
~8~
DIMENSION & WEIGHT
EC Range
~9~
ECL Range
~ 10 ~
GUIDE SPECIFICATION
The frame shall be constructed of 2mm steel for strength and durability. The exterior
panels shall be powder coated with a textured finish and shall be insulated with a
minimum 1 inch (25.4mm) thick PE foam insulation with minimum 40kg/m3 density
lined with aluminium foil rated to class O rating. All front panels shall have double
skinned construction with FERMAPOR gasket for better sound proofing and thermal
insulation. All front panels shall be locked with compression latches to prevent
unauthorized access. All front panels shall be provided with removable hinge to allow
easy access for installation and maintenance.
Air Filtration
The air filters shall be located within the cabinet of the unit and shall be serviceable
from the front of the unit. The filters shall be rated not less than 30% efficiency
(based on ASHRAE 52.1) or MERV 8 (based on ASHRAE 52.2) and shall be >
50mm depth. A differential pressure switch shall be fitted to indicate the filters need
changing through a service alarm from the controller.
Electric Reheat
Electrical heaters shall be provided in one or two stages depend on models. The PTC
heating elements shall be made of PTC thermistor and aluminium fin housing with
safe dynamic self-regulating function. The heating elements shall include a high
temperature safety cut-out. Heater may be interlocked with humidifier (if present) to
prevent simultaneous operation for sites with limited power supply.
The chilled water circuit shall include a 2-way modulating valve and actuator with
manual override facility. Cooling capacity shall be controlled by modulating the
volume of chilled water into the cooling coil via the modulating valve. The valve shall
be equal percentage characterised ball valve in order to have better control stability.
The controller shall position the valve opening in response to return air or supply air
condition.
Fans
The fan shall be of double width double inlet forward curved centrifugal type, and
shall be factory-balanced as a completed assembly. The shaft shall be heavy duty steel
with self-aligning ball bearings with a minimum life span of 100,000 hours. Belt shall
be sized for 200% of the fan motor horsepower. Each fan shall be driven individually
by a fan motor. The fan motor shall be mounted on an adjustable frame on the fan.
The fan motor shall be of TEFC type, IEC compliant, with class F insulation.
~ 11 ~
All fans and motors shall be accessible from the front of the unit. The fans shall be of
draw through type, located after the cooling coil to ensure even air distribution and
maximum coil performance. A differential pressure switch shall be provided to detect
air flow failure.
The EC fan should be capable of ramping slowly to the desired speed & shall not have
any high inrush current. The fan shall be accessible from the front of the unit and be
of draw through type located after the cooling coil to ensure even air distribution and
maximum coil performance. A differential pressure switch shall be provided to detect
air flow failure.
Underfloor EC Fan (Standard for ECL Range. Option for EC range, Downflow
Models Only)
The EC fan shall be capable of variable speed control without use of VFD and can be
set by the user to operate within a certain range of fan speed and shall also be capable
of being set to automatically adjust its fan speed according to the air temperature of
the room to provide energy saving during periods of low load.
The EC fan should be capable of ramping slowly to the desired speed & shall not have
any high inrush current. The fan shall be accessible from the front of the unit and be
of draw through type located after the cooling coil to ensure even air distribution and
maximum coil performance. A differential pressure switch shall be provided to detect
air flow failure.
~ 12 ~
Cooling Coil
The cooling coils shall be with draw through air design for uniform air distribution
and superior heat transfer. The cooling medium (chilled water or glycol) shall run
counter flow to the air for optimum heat transfer. The coil shall be constructed of
plain copper tubes and corrugated aluminium fins. The coil shall have hydrophilic
coating for better water removal and improved heat transfer. The cooling coil shall
have a maximum of 6 rows and 12 fins per inch and face velocity shall not exceed
2.4m/s. Condensate tray for the cooling coil shall be made of stainless steel.
a) The control system shall be able to maintain the temperature and humidity to a
tolerance of ±1.0°C and ±5 %RH.
b) The control system shall have a fascia with 132 x 64 pixel resolution LCD display
located on the front panel of the unit for display and programming functions. The
display shall show current modes of operation, current return air temperature and
relative humidity.
c) System configuration and setting shall be stored in non-volatile memory and
safeguard in the event of power failure.
d) The system shall have at least three levels of programmable password access to
prevent any unauthorized changes of the system configurations.
e) The system shall have programmable selections: manual or automatic restart
option. A programmable start-up delay shall be provided for the automatic restart
option which allows multiple units to restart progressively when power resumes
after a power failure.
f) The accumulated run time of the following components shall be logged.
1. Fan
2. Heater
3. Humidifier
g) Components shall be scheduled to activate sequentially to minimize inrush current.
h) The control system shall have but not limited to the following alarms.
1. High / low temperature
2. High / low humidity
3. Filter clogged
4. Loss of air flow
5. Water in high temperature
6. Heater overheat
7. Humidifier fault (if humidifier present)
8. Humidifier cylinder change (if humidifier present)
~ 13 ~
9. Drip tray full (if water detection option present)
10. Water on floor (if water detection option present)
i) When an alarm condition exists, the common alarm output shall be energized until
acknowledged. Active alarm record shall remain until the alarm condition is
cleared.
j) A historical event log shall record up to 100 alarm events. The text description
and occurrence time of the all alarms shall be logged and shall be displayed in
order of occurrence for ease of troubleshooting.
k) The units shall have built-in master and slave inter-networking capability and
auto-sequencing which allow a combination of all units to form a local area
network. The control of a slave unit shall not be limited to any particular master
unit. In case of a master unit failure, the remaining units in the same network shall
automatically take over the control and one of then shall act as master unit.
l) The controller shall be compatible with most remote monitoring and control
devices. Controller shall have built-in RS485 port ready for Modbus connection.
Options shall be available for BMS interface via BACnet, LonWorks and SNMP.
~ 14 ~
OPTIONS ʹ GUIDE SPECIFICATION
Humidifier
Serviceable Humidifier
Humidification shall be via an electrode boiler type humidifier complete with feed
and drain valves and overflow indicator. The humidifier cylinder shall be serviceable
with cleanable electrodes. The humidifier control shall include proportional steam
output and an auto flush cycle, which is user adjustable from the front display. Power
supply shall be disconnected from the electrodes when humidifier is in drain mode to
prevent earth leakage.
Water level sensors shall be located at the condensate tray to detect undue water
levels at the drain pan. A water sensing tape shall also be provided (supplied loose
with sufficient length to cover entire length of the respective unit) to detect presence
of water on the floor. When water is detected, an alarm shall be triggered and user
may set to stop or continue unit operation.
The chilled water circuit shall include a 3-way modulating valve and actuator with
manual override facility. Cooling capacity shall be controlled by modulating the
volume of chilled water into the cooling coil via the modulating valve. The valve shall
be equal percentage characterised ball valve in order to have better control stability.
The controller shall position the valve opening in response to return air or supply air
condition.
A water temperature sensor shall be placed at the chilled water inlet piping to detect
incoming chilled water temperature. An alarm signal shall be raised if the chilled
water temperature is above a user defined setpoint. The temperature reading shall be
shown on the unit display and can be logged for graph trending.
A water temperature sensor shall be placed at the chilled water outlet piping to
monitor the leaving chilled water temperature. The temperature reading shall be
shown on the unit display and can be logged for graph trending.
~ 15 ~
Dual Belt for Belt Driven Fan (For EC Range Only)
The fan shall be of double width double inlet forward curved centrifugal type, and
shall be factory-balanced as a completed assembly. The shaft shall be heavy duty steel
with self-aligning ball bearings with a minimum life span of 100,000 hours. The fan
shall be driven with 2 belts and each belt shall be sized for 200% of the fan motor
horsepower for redundancy. Each fan shall be driven individually by a fan motor. The
fan motor shall be mounted on an adjustable frame on the fan. The fan motor shall be
of TEFC type, IEC compliant, with class F insulation, of IP55 rating and EFF 2
efficiency.
All fans and motors shall be accessible from the front of the unit. The fans shall be of
draw through type, located after the cooling coil to ensure even air distribution and
maximum coil performance. A differential pressure switch shall be provided to detect
air flow failure.
Horizontal discharge section shall consist of a double deflection grille fitted into a
rigid sheet metal box. The complete assembly shall be bolted to the top of the unit on
site. The grille shall have two sets of blades, which allow for both vertical and
horizontal directional adjustment of air flow. The standard height for this section shall
be 500mm.
The ceiling discharge section shall consist of rigid riveted sheet metal assembly
comprising of unit matched front, rear and end panels lined with 25mm thick
insulation. The extension shall be bolted to the top of the unit on site. The section
height shall be suitable for the distance between the top of the unit and the underside
of the suspended ceiling. The overall height of the section shall be this dimension plus
50mm.
Ceiling return duct shall comprise of unit matched panels lined with 25mm thick
insulation bolted to the top of the unit on site. The height of the duct shall be suitable
for the distance between the top of the unit and the underside of the suspended ceiling.
The overall height of the duct shall be this dimension plus 50mm.
The air filters shall be located within the cabinet of the unit and shall be serviceable
from the front of the unit. The filters shall be rated not less than 80% efficiency
(based on ASHRAE 52.1) and shall be of >50mm depth. A differential pressure
switch shall be fitted to indicate the filters need changing through a service alarm
from the controller. Air filter shall be of disposable type & with cardboard frame.
~ 16 ~
Differential Pressure Transmitter for Underfloor Pressure Control
A 24VDC relay shall be provided to receive an external signal from the fire control
panel or detection system. When the external signal is received, the unit shall stop
operation.
Wooden Crate
A plywood and timber enclosure shall be provided to protect the unit from damage
during transportation to site.
ATS shall be provided to handle the transfer of incoming power source for dual power
system. The ATS shall be factory installed and wired and integrated the switching
signal to the controller.
a) The control system shall be able to maintain the temperature and humidity to a
tolerance of ±1.0°C and ±5 %RH.
b) The control system shall have a fascia with 480 x 272 pixel resolution TFT touch
screen graphical display located on the front panel of the unit for display and
programming functions. The display shall show current modes of operation,
current return air temperature and relative humidity, target set point temperature &
relative humidity.
c) System configuration and setting shall be stored in non-volatile memory and
safeguard in the event of power failure.
d) The system shall have at least three levels of programmable password access
to prevent any unauthorized changes of the system configurations.
e) The display shall have multi language support with option to select between
English, Malay, Chinese, Japanese and Thai languages.
f) The system shall have a temperature and humidity graph which shows data up
to 4 weeks duration. The data of the graph shall be logged in one minute
intervals. An option to show the temperature graph of the chilled water system
(inlet and outlet if applicable) shall be available.
~ 17 ~
g) The system shall have programmable selections: manual or automatic restart
option. A programmable start-up delay shall be provided for the automatic
restart option which allows multiple units to restart progressively when power
resumes after a power failure.
h) The accumulated run time of the following components shall be logged.
a. Fan
b. Heater
c. Humidifier
i) Components shall be scheduled to activate sequentially to minimize inrush
current.
j) The control system shall have but not limited to the following alarms.
a. High / low temperature
b. High / low humidity
c. Filter clogged
d. Loss of air flow
e. Water in high temperature
f. Heater overheat
g. Humidifier fault (if humidifier present)
h. Humidifier cylinder change (if humidifier present)
i. Drip tray full (if water detection option present)
j. Water on floor (if water detection option present)
k) When an alarm condition exists, the common alarm output shall be energized
until acknowledged. Active alarm record shall remain until the alarm
condition is cleared.
l) A historical event log which maintains the latest events of up to 4 weeks shall
be provided. The text description and occurrence time of the all alarms shall
be logged and shall be displayed in order of occurrence for ease of
troubleshooting.
m) The units shall have built-in master and slave inter-networking capability and
auto-sequencing which allow a combination of all units to form a local area
network. The control of a slave unit shall not be limited to any particular
master unit. In case of a master unit failure, the remaining units in the same
network shall automatically take over the control and one of then shall act as
master unit.
n) The controller shall be compatible with most remote monitoring and control
devices. Controller shall have built-in RS485 port ready for Modbus
connection. Options shall be available for other BMS interface via BACnet,
LonWorks and SNMP.
~ 18 ~
REMOTE MONITORING AND SUPERVISORY SYSTEM
Several remote monitoring, control and supervisory systems are available as add-ons
to the controller to enable user to access data and make settings changes to the units
without having to be physically present in front of the unit.
WebGate
pCOWeb
Allows communication between controller with BACnet Ethernet, BACnet over IP,
SNMP protocol (v1 & v2c), HTTP protocol, FTP and DHCP protocol. The device
functions as a web server with a fixed IP which can be accessed via a LAN or through
the Internet.
pCOnet
G-Visor
Notes:
1. For more detailed information on these options, please refer to the Genius Controller Engineering Data.
2. Please note that certain combinations of options are not available with other options while other combinations
might require further upgrades or additional accessories to be added. To check whether a certain combination
of options is available, please consult factory. For availability of other special options & accessories not listed
above, please also check with factory.
~ 19 ~
TECHNICAL DATA
EC Range - Downflow
Notes:
1. Cooling capacity is based on 24ºC, 45%RH, Chilled Water in/out based on 7/12ºC, 50Hz, 50Pa ESP.
2. Sound level is measured at 1m in free ¿eld conditions.
3. For underfloor EC fan option, raise floor height must be >400mm.
4. *For downflow version, only EC fan is available.
~ 20 ~
Unit Model 95 110 125 135 150
Gross Total Capacity kW 100.27 113.93 123.42 131.51 155.54
Gross Sensible Capacity kW 87.09 99.01 106.18 115.05 133.88
S.H.R. 0.87 0.87 0.86 0.88 0.86
General Data
Nominal Air Flow m³/s 6.00 7.00 7.00 7.60 8.60
No. of Fan(s) 2 3 3 3 4
Sound Level dBA 68 68 68 68 68
Chilled Water Coil
Nominal Water Flow l/s 4.79 5.44 5.90 6.28 7.43
Water Pressure Drop kPa 107.6 145.4 90.6 60.6 87.2
Electric Re-heater
Nominal Heater Capacity kW 12 12 12 12 12
No. of Heater Step(s) 2 2 2 2 2
Electrode Humidifier
Nominal Humidifier Capacity kg/hr 8 8 8 8 8
Air Filter
Type G4, MERV8, Disposable
301x700x100(4) 301x700x100(6) 301x700x100(6) 301x700x100(3)
WxHxD (Qty) mm 301x700x100(8)
350x700x100(2) 350x700x100(1) 350x700x100(1) 350x700x100(5)
Notes:
1. Cooling capacity is based on 24ºC, 45%RH, Chilled Water in/out based on 7/12ºC, 50Hz, 50Pa ESP.
2. Sound level is measured at 1m in free ¿eld conditions.
3. For underfloor EC fan option, raise floor height must be >400mm.
4. *For downflow version, only EC fan is available.
~ 21 ~
EC Range - Upflow
Notes:
1. Cooling capacity is based on 24ºC, 45%RH, Chilled Water in/out based on 7/12ºC, 50Hz, 50Pa ESP.
2. Sound level is for downflow models measured at 1m in free ¿eld conditions.
3. *For upflow version, only EC fan is available (except model 25 & 50).
~ 22 ~
Unit Model 95 110 125 135 150
Gross Total Capacity kW 95.93 108.2 117.73 127.41 151.06
Gross Sensible Capacity kW 83.55 94.22 101.33 111.52 130.11
S.H.R. 0.87 0.87 0.86 0.88 0.86
General Data
Nominal Air Flow m³/s 5.80 6.70 6.70 7.40 8.40
No. of Fan(s) 2 3 3 3 4
Sound Level dBA 68 68 68 68 68
Chilled Water Coil
Nominal Water Flow l/s 4.58 5.17 5.63 6.09 7.22
Water Pressure Drop kPa 101.2 135.0 89.5 59.8 86.5
Electric Re-heater
Nominal Heater Capacity kW 12 12 12 12 12
No. of Heater Step(s) 2 2 2 2 2
Electrode Humidifier
Nominal Humidifier Capacity kg/hr 8 8 8 8 8
Air Filter
Type G4, MERV8, Disposable
633X850X100(1) 633X850X100(1)
633X850X100(1) 633X850X100(1) 633X850X100(1)
WxHxD (Qty) mm 384X582X100(4) 540X582X100(4)
540X582X100(4) 633X582X100(4) 633X582X100(4)
633X582X100(2) 633X582X100(2)
Unit Piping Connection
Water In/Out mm 54 67 67 67 67
Drain mm 22 22 22 22 22
Humidifier Feed 3/4" G(M) 3/4" G(M) 3/4" G(M) 3/4" G(M) 3/4" G(M)
Humidifier Drain mm 32 32 32 32 32
Unit Dimension
Width mm 2065 2300 2300 2550 2815
Depth mm 891 891 891 891 891
Height mm 1985 1985 1985 1985 1985
Min. Service Allowance mm 725 725 725 725 725
Notes:
1. Cooling capacity is based on 24ºC, 45%RH, Chilled Water in/out based on 7/12ºC, 50Hz, 50Pa ESP.
2. Sound level is for downflow models measured at 1m in free ¿eld conditions.
3. *For upflow version, only EC fan is available (except model 25 & 50).
~ 23 ~
ECL Range
Notes:
1. Cooling capacity is based on 24ºC, 45%RH, Chilled Water in/out based on 7/12ºC, 50Hz, 50Pa ESP.
2. Sound level is for downflow models measured at 1m in free ¿eld conditions.
3. Raise floor height must be >500mm.
4. Only downflow version with EC fan is available.
~ 24 ~
ELECTRICAL DETAIL
EC Range
Notes:
1. Operating current and power stated for unit running in cooling mode under nominal conditions.
2. Unit rated load power and current is calculated based on worst possible combination of components operating at the same time. Unit
assumed to have nominDOKHDWHUDQGKXPLGL¿HU
3. Electrical data is based on 400V/3ph/50Hz power supply.
~ 25 ~
ECL Range
Notes:
1. Operating current and power stated for unit running in cooling mode under nominal conditions.
2. Unit rated load power and current is calculated based on worst possible combination of components operating at the same time. Unit
DVVXPHGWRKDYHQRPLQDOKHDWHUDQGKXPLGL¿HU
3. Electrical data is based on 400V/3ph/50Hz power supply.
'XHWRRXUSROLF\RIFRQWLQXHVGHYHORSPHQWDQGLPSURYHPHQWWKHVSHFL¿FDWLRQVDQGGDWDKHUHLQDUHVXEMHFWWRFKDQJHZLWKRXWSrior
notice. We must therefore reserve the right to supply equipment that may differ from that described and illustrated herein. All
information, including illustrations, contained in this brochure, is believed to be accurate and reliable. Users, however, should
independently evaluate the suitability of each product for their own application. CITEC makes no warranties as to the accuracy or
completeness of the information, and disclaims any liability regarding its use.
~ 26 ~
~ 27 ~
Version 3.0/2016/GVEC