Engineering Data EC - ECL v3.0

The document provides information on the G-Volution Series precision air conditioning units from Citec International. [1] It describes the company and introduces the product as designed for critical environments requiring constant, efficient cooling. [2] Key features include double skin access panels for sound isolation, modulating ball valves for water flow control, three fan configurations including electronically commutated fans, and temperature sensors for monitoring supply and return water. [3] The document discusses the Genius 5+ controller which provides intelligent control capabilities as well as remote monitoring and system integration functions.

Uploaded by

Kim Wong
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
134 views

Engineering Data EC - ECL v3.0

The document provides information on the G-Volution Series precision air conditioning units from Citec International. [1] It describes the company and introduces the product as designed for critical environments requiring constant, efficient cooling. [2] Key features include double skin access panels for sound isolation, modulating ball valves for water flow control, three fan configurations including electronically commutated fans, and temperature sensors for monitoring supply and return water. [3] The document discusses the Genius 5+ controller which provides intelligent control capabilities as well as remote monitoring and system integration functions.

Uploaded by

Kim Wong
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 29

ENGINEERING

DATA
CONTENT

Introduction 1
Features & Benefits 3
Nomenclature 6
Air Flow Arrangement 7
Dimension & Weight 9
Guide Specification 11
Options ± Guide Specification 15
Remote Monitoring & Supervisory System 19
Technical Data 20
Electrical Details 25
INTRODUCTION

The Company

Citec International is one of the global leaders in designing and manufacturing


Precision Air Conditioning system. Citec International places great emphasis on
achieving the highest standards and incorporates stringent quality controls throughout
its operations. Every CITEC product is designed and built within a Quality
Management System ISO9001 and Environmental Management System ISO14001,
using our unrivalled experience in Precision Air Conditioning, with extensive testing
of components and complete systems. Every aspect is engineered to ensure maximum
reliability, economy of operation and long working life, together with ease of
installation and maintenance.

The Product

The G-Volution Series is the latest Precision Air Conditioning units from Citec
International that are engineered to run seamlessly in critical environments by
delivering constant, efficient and intelligent cooling circulation consistently and
reliably for 24 hours per day, 7 days per week.

The G-Volution Series is designed for areas with limited space as well as large data
centers. The units are designed with wide range of options to meet the requirement of
precision cooling needs in various applications and environment. Typical applications
include:

o Data Centers
o Computer Rooms
o Telecommunication Rooms
o Co-location Centers
o ISP
o Hospital Operating Rooms
o Laboratories

The G-Volution Chilled Water (CW) Units

The G-Volution Chilled Water type Precision Air Conditioning units cover capacity
range from 25kW to 200kW, and distributed over 2 different model ranges, i.e. EC
and ECL. Each model range has its own unique features for different design
objectives and optimized for specific application.

The G-Volution EC Range units are available in both downflow and upflow
configuration while ECL range units are only available in downflow configuration.
The G-Volution CW units only require front service access, thus can be easily
installed side by side or tucked into a corner.

~1~
EC Range

Citec EC Range is designed to fit in large coil with


maximum heat exchange surface. The components
are in an arrangement that allows 3 different fan
configurations, i.e. belt driven centrifugal fan, EC
fans and underfloor EC fans. The EC Range units
have low coil face velocity thus reducing air friction
loss and therefore ensure the units operate at highest
efficiency.

ECL Range

The Citec ECL Range is design to further maximize the coil surface area by letting
the fan operated under the raise floor. The design allows the units to have largest coil
surface area possible and at the same time, optimizes the air flow and increase the fan
efficiency, thus achieving highest efficiency with minimum foot print. The ECL
Range is best suited for data centers with high raise floor.

~2~
FEATURES AND BENEFITS

Double Skin Access Panel with Gasket Lining

The solid and rigid double skin insulated access panels on the G-Volution Series
ensure excellent sound isolation and greatly reduce the breakout noise of the unit. The
special FERMAPOR gasket on the door panels effectively eliminates air leakage from
the units. This gasket is applied to the door panels using a special machine to ensure
strong bonding between the gasket and the panels, thus increase the reliability of the
whole panel assembly.

Modulating Ball Valve

Modulating ball valve with equal percentage characteristic is used to ensure excellent
control of water flow through the cooling coil. The flow characterised disc inside the
valve has greatly enhance the control stability especially under low load condition.
The standard valve is rated PN25 and has high closed-off pressure rating, therefore
suitable for wide range of operating condition.

3 Types of Fan Configuration (EC Range Only)

The G-Volution Series offer 3 types of fan configuration. DIDW centrifugal fan
driven by AC motor is fitted as standard while high efficiency Electronically
Commutated (EC) Fan is offered as option. Apart from increasing the efficiency of
the units, EC Fan also enable various control strategies for data center cooling such as
underfloor pressure control and variable air flow control. For downflow system, if the
raise floor has sufficient height (>400mm), then the efficiency of the unit can be
further improved as much as 15% by locating the EC fan under the raise floor. For
Citec G-Volution Series Underfloor EC Fan option, the fans are located inside the unit
during transportation. After the unit is in position, the fans will be lowered down to
underfloor. This has greatly simplified the installation process and also future service
and maintenance.

Water Temperature Sensors (Optional)

Inlet water temperature and outlet water temperature can be fitted to the units to
monitor the supply and return water condition. The unit would provide early warning
if the incoming water is out of the desired operating condition, thus enable early
rectification actions and prevent potential downtime.

Cooling Coil

Depends on models, A-frame or V-frame coil arrangement allows larger coil to be


fitted in to the unit. Large coil face area allows more cooling capacity at lower face
velocity. Therefore, the unit can achieve better efficiency while at the same time
minimizing the air side pressure loss.

Hydrophilic fin provides additional protection to the coil and at the same time, ensure
fast removal of condensate on the coil. Thus, improves the heat transfer and
~3~
performance of the coil. Hydrophilic fin also reduce the air friction loss across the coil,
thus reduce the fan power requirement.

Heaters

Depends on models, single stage or multiple stages of PTC heating elements are
balanced over 3 phases and comes with safe dynamic self-regulating function. It
automatic controls the thermal power through air flow to eliminate the possibility of
overheating when air flow is low. It operates at a nearly constant temperature and fast
heat up promise an accurate control of temperature. Uniform heating without power
variation extend the life span of the elements. Proportional heating capacity is
available as an option via power regulators. All heaters are protected by thermal cut-
out switches. The heater may be interlocked with humidifier to reduce power
requirement when operating under power restricted area.

Electrical and Control Panel

High and low voltage cables are segregated and each component is protected by
individual MCB. AC3 components such as fan motors are protected by manual motor
starters. All cabling are colour coded and numbered for easy reference.

Genius 5+ Controller

The latest Citec Genius 5+ ontroller provides intelligent and advance control for
precision cooling application. The G-Volution Series fitted with Genius 5+ controller,
offered highest flexibility and capability in mission critical cooling control, remote
monitoring and system integration. The Genius 5+ controller supports wide range of
cooling control strategies for mission critical facilities including auto-sequencing,
supply air control and containment system. Energy saving features such as EC fan
control and intelligent humidity control are built-in to the standard control program.

The Genius 5+ controller supports various communication protocols for remote


monitoring. The built-in RS485 communication port is ready for connecting to
Modbus system without needs of additional accessories. Other communication
protocols such as TCP/IP, BACnet and LonWorks are supported with additional
interface cards.

Touch Screen Display

Optional touch screen display provides informative and user-friendly interface for
easy navigation. The display can show graphical information via animated icons and
also capable of plotting trend graphs for temperature and humidity. The display can
support multiple languages such as English, Malay, Chinese, Thai and Japanese.

Humidity Control

The G-Volution Series offered 2 humidity control mode, i.e. the conventional RH
Control Mode and the ASHRAE TC9.9 compliance Dew Point Control Mode.

~4~
RH Control Mode (Relative Humidity Control)
In RH Control Mode, room humidity is control in term of Relative Humidity (RH). As
RH is not directly reflexes the actual moisture content in the air, keeping constant RH
might involve adding and removing of moisture just because the change of

%
40
20 %
30
°C
e- ASHRAE 2004 Recommendation

Humidity Ratio - kg/kg


tur
p era
T em 15
ulb 20%
tB
We
10

5
10%

ASHRAE 2008 Recommendation

Dry Bulb Temperature - °C

temperature instead of the variation in moisture content. These unintended processes


are causing unnecessary power consumption in data center cooling. However, this
humidity control mode shall be chosen for application where RH gives more impact
than the actual moisture content.

Dew Point Control Mode (Absolute Humidity Control)


Since year 2008, ASHRAE TC9.9 has specified recommended humidity in term of
dew point. It specified that the humidity level in data center environment should be
between 5.5°C and 15°C. To comply to the latest ASHRAE recommendation and also
to prevent the unnecessary humidifying and de-humidifying process. Dew Point
Control Mode is preferred over the conventional RH Control Mode.

~5~
NOMENCLATURE

E C D 25 A

E - G-Volution Series

C ± Chilled Water System

D - Downflow
U ± Upflow
L ± Large Capacity

Model - Nominal Capacity


in kW

A ± Belt Driven Fans


E ± EC Fans
U ± Underfloor EC Fans

~6~
AIR FLOW ARRANGEMENT

Type A (EC Only):


Upflow unit, top discharge into ceiling
or duct with front return.

Type B (EC Only):


Upflow unit, with horizontal discharge
plenum. Front return.

Type C (EC Only):


Upflow unit, top discharge into ceiling
or duct. Bottom return.

~7~
Type D (EC Only):
Downflow unit, discharge into raise
floor. Top return.

Type E:
Downflow unit, with bottom discharge
plenum. Top return.

Type F:
Downflow unit, with underfloor EC
Fans. Top return.

~8~
DIMENSION & WEIGHT

EC Range

Model 25 30 50 60 70 80 95 110 125 135 150


Gross Weight (kg) 255 285 345 455 535 570 785 850 890 935 980

~9~
ECL Range

Model 70 80 125 140 180 200

Gross Weight (kg): 375 395 615 645 855 900

~ 10 ~
GUIDE SPECIFICATION

Cabinet and Frame Construction

The frame shall be constructed of 2mm steel for strength and durability. The exterior
panels shall be powder coated with a textured finish and shall be insulated with a
minimum 1 inch (25.4mm) thick PE foam insulation with minimum 40kg/m3 density
lined with aluminium foil rated to class O rating. All front panels shall have double
skinned construction with FERMAPOR gasket for better sound proofing and thermal
insulation. All front panels shall be locked with compression latches to prevent
unauthorized access. All front panels shall be provided with removable hinge to allow
easy access for installation and maintenance.

Air Filtration

The air filters shall be located within the cabinet of the unit and shall be serviceable
from the front of the unit. The filters shall be rated not less than 30% efficiency
(based on ASHRAE 52.1) or MERV 8 (based on ASHRAE 52.2) and shall be >
50mm depth. A differential pressure switch shall be fitted to indicate the filters need
changing through a service alarm from the controller.

Electric Reheat

Electrical heaters shall be provided in one or two stages depend on models. The PTC
heating elements shall be made of PTC thermistor and aluminium fin housing with
safe dynamic self-regulating function. The heating elements shall include a high
temperature safety cut-out. Heater may be interlocked with humidifier (if present) to
prevent simultaneous operation for sites with limited power supply.

2-Way Chilled Water Control Valve

The chilled water circuit shall include a 2-way modulating valve and actuator with
manual override facility. Cooling capacity shall be controlled by modulating the
volume of chilled water into the cooling coil via the modulating valve. The valve shall
be equal percentage characterised ball valve in order to have better control stability.
The controller shall position the valve opening in response to return air or supply air
condition.

Fans

Centrifugal Belt-Driven Fan (For EC Range only)

The fan shall be of double width double inlet forward curved centrifugal type, and
shall be factory-balanced as a completed assembly. The shaft shall be heavy duty steel
with self-aligning ball bearings with a minimum life span of 100,000 hours. Belt shall
be sized for 200% of the fan motor horsepower. Each fan shall be driven individually
by a fan motor. The fan motor shall be mounted on an adjustable frame on the fan.
The fan motor shall be of TEFC type, IEC compliant, with class F insulation.

~ 11 ~
All fans and motors shall be accessible from the front of the unit. The fans shall be of
draw through type, located after the cooling coil to ensure even air distribution and
maximum coil performance. A differential pressure switch shall be provided to detect
air flow failure.

Electronically Commutated (EC) Fan

Fans shall be of backward curved plug fan type which is direct-driven by an


Electronically Commutated (EC) motor. The EC fan shall be capable of variable
speed control without use of VFD and can be set by the user to operate within a
certain range of fan speed and shall also be capable of being set to automatically
adjust its fan speed according to the air temperature of the room to provide energy
saving during periods of low load.

Alternatively, it should also be possible to automatically regulate the fan speed to


maintain a certain level of positive pressure in the room. User should be able to
override and manually set the fan speed if required.

The EC fan should be capable of ramping slowly to the desired speed & shall not have
any high inrush current. The fan shall be accessible from the front of the unit and be
of draw through type located after the cooling coil to ensure even air distribution and
maximum coil performance. A differential pressure switch shall be provided to detect
air flow failure.

Underfloor EC Fan (Standard for ECL Range. Option for EC range, Downflow
Models Only)

Fans shall be of backward curved plug fan type which is direct-driven by an


Electronically Commutated (EC) motor. Fans shall be pre-wired and placed within the
unit for delivery, ready to be lowered into position at site. Fan mounting assembly
shall be enclosed and provided with a perforated plate to prevent any accidental direct
contact with the fan when it is in operation.

The EC fan shall be capable of variable speed control without use of VFD and can be
set by the user to operate within a certain range of fan speed and shall also be capable
of being set to automatically adjust its fan speed according to the air temperature of
the room to provide energy saving during periods of low load.

Alternatively, it should also be possible to automatically regulate the fan speed to


maintain a certain level of positive pressure in the room. User should be able to
override and manually set the fan speed if required.

The EC fan should be capable of ramping slowly to the desired speed & shall not have
any high inrush current. The fan shall be accessible from the front of the unit and be
of draw through type located after the cooling coil to ensure even air distribution and
maximum coil performance. A differential pressure switch shall be provided to detect
air flow failure.

~ 12 ~
Cooling Coil

The cooling coils shall be with draw through air design for uniform air distribution
and superior heat transfer. The cooling medium (chilled water or glycol) shall run
counter flow to the air for optimum heat transfer. The coil shall be constructed of
plain copper tubes and corrugated aluminium fins. The coil shall have hydrophilic
coating for better water removal and improved heat transfer. The cooling coil shall
have a maximum of 6 rows and 12 fins per inch and face velocity shall not exceed
2.4m/s. Condensate tray for the cooling coil shall be made of stainless steel.

Electrical and Control Cabinet

High voltage compartment shall contain contactors, miniature circuit breakers,


transformer and terminal isolator while the low voltage section shall include the
controller and all other additional add-on control interface and terminal blocks. Each
component shall be protected by an individual MCB while fan motors shall be
protected by motor starters. Low voltage circuit shall be protected by fuse. All high
and low voltage cables shall be segregated and placed in cable trunking. All cabling
shall be colour coded and numbered for easy referencing.

Microprocessor Control System with LCD Display

a) The control system shall be able to maintain the temperature and humidity to a
tolerance of ±1.0°C and ±5 %RH.
b) The control system shall have a fascia with 132 x 64 pixel resolution LCD display
located on the front panel of the unit for display and programming functions. The
display shall show current modes of operation, current return air temperature and
relative humidity.
c) System configuration and setting shall be stored in non-volatile memory and
safeguard in the event of power failure.
d) The system shall have at least three levels of programmable password access to
prevent any unauthorized changes of the system configurations.
e) The system shall have programmable selections: manual or automatic restart
option. A programmable start-up delay shall be provided for the automatic restart
option which allows multiple units to restart progressively when power resumes
after a power failure.
f) The accumulated run time of the following components shall be logged.
1. Fan
2. Heater
3. Humidifier
g) Components shall be scheduled to activate sequentially to minimize inrush current.
h) The control system shall have but not limited to the following alarms.
1. High / low temperature
2. High / low humidity
3. Filter clogged
4. Loss of air flow
5. Water in high temperature
6. Heater overheat
7. Humidifier fault (if humidifier present)
8. Humidifier cylinder change (if humidifier present)

~ 13 ~
9. Drip tray full (if water detection option present)
10. Water on floor (if water detection option present)
i) When an alarm condition exists, the common alarm output shall be energized until
acknowledged. Active alarm record shall remain until the alarm condition is
cleared.
j) A historical event log shall record up to 100 alarm events. The text description
and occurrence time of the all alarms shall be logged and shall be displayed in
order of occurrence for ease of troubleshooting.
k) The units shall have built-in master and slave inter-networking capability and
auto-sequencing which allow a combination of all units to form a local area
network. The control of a slave unit shall not be limited to any particular master
unit. In case of a master unit failure, the remaining units in the same network shall
automatically take over the control and one of then shall act as master unit.
l) The controller shall be compatible with most remote monitoring and control
devices. Controller shall have built-in RS485 port ready for Modbus connection.
Options shall be available for BMS interface via BACnet, LonWorks and SNMP.

~ 14 ~
OPTIONS ʹ GUIDE SPECIFICATION

Humidifier

Humidification shall be via an electrode boiler type humidifier with disposable


cylinder complete with feed and drain valves and overflow indicator. The humidifier
control shall include proportional steam output and an auto flush cycle, which is user
adjustable from the front display. Power supply shall be disconnected from the
electrodes when humidifier is in drain mode to prevent earth leakage.

Serviceable Humidifier

Humidification shall be via an electrode boiler type humidifier complete with feed
and drain valves and overflow indicator. The humidifier cylinder shall be serviceable
with cleanable electrodes. The humidifier control shall include proportional steam
output and an auto flush cycle, which is user adjustable from the front display. Power
supply shall be disconnected from the electrodes when humidifier is in drain mode to
prevent earth leakage.

Water Detection Kits

Water level sensors shall be located at the condensate tray to detect undue water
levels at the drain pan. A water sensing tape shall also be provided (supplied loose
with sufficient length to cover entire length of the respective unit) to detect presence
of water on the floor. When water is detected, an alarm shall be triggered and user
may set to stop or continue unit operation.

3-Way Chilled Water Control Valve

The chilled water circuit shall include a 3-way modulating valve and actuator with
manual override facility. Cooling capacity shall be controlled by modulating the
volume of chilled water into the cooling coil via the modulating valve. The valve shall
be equal percentage characterised ball valve in order to have better control stability.
The controller shall position the valve opening in response to return air or supply air
condition.

Inlet Water Temperature Sensor

A water temperature sensor shall be placed at the chilled water inlet piping to detect
incoming chilled water temperature. An alarm signal shall be raised if the chilled
water temperature is above a user defined setpoint. The temperature reading shall be
shown on the unit display and can be logged for graph trending.

Outlet Water Temperature Sensor

A water temperature sensor shall be placed at the chilled water outlet piping to
monitor the leaving chilled water temperature. The temperature reading shall be
shown on the unit display and can be logged for graph trending.
~ 15 ~
Dual Belt for Belt Driven Fan (For EC Range Only)

The fan shall be of double width double inlet forward curved centrifugal type, and
shall be factory-balanced as a completed assembly. The shaft shall be heavy duty steel
with self-aligning ball bearings with a minimum life span of 100,000 hours. The fan
shall be driven with 2 belts and each belt shall be sized for 200% of the fan motor
horsepower for redundancy. Each fan shall be driven individually by a fan motor. The
fan motor shall be mounted on an adjustable frame on the fan. The fan motor shall be
of TEFC type, IEC compliant, with class F insulation, of IP55 rating and EFF 2
efficiency.

All fans and motors shall be accessible from the front of the unit. The fans shall be of
draw through type, located after the cooling coil to ensure even air distribution and
maximum coil performance. A differential pressure switch shall be provided to detect
air flow failure.

Horizontal Discharge Section (Upflow Unit Only)

Horizontal discharge section shall consist of a double deflection grille fitted into a
rigid sheet metal box. The complete assembly shall be bolted to the top of the unit on
site. The grille shall have two sets of blades, which allow for both vertical and
horizontal directional adjustment of air flow. The standard height for this section shall
be 500mm.

Ceiling Discharge Section (Upflow Unit Only)

The ceiling discharge section shall consist of rigid riveted sheet metal assembly
comprising of unit matched front, rear and end panels lined with 25mm thick
insulation. The extension shall be bolted to the top of the unit on site. The section
height shall be suitable for the distance between the top of the unit and the underside
of the suspended ceiling. The overall height of the section shall be this dimension plus
50mm.

Ceiling Return Duct (Downflow Unit Only)

Ceiling return duct shall comprise of unit matched panels lined with 25mm thick
insulation bolted to the top of the unit on site. The height of the duct shall be suitable
for the distance between the top of the unit and the underside of the suspended ceiling.
The overall height of the duct shall be this dimension plus 50mm.

High Efficiency Filter

The air filters shall be located within the cabinet of the unit and shall be serviceable
from the front of the unit. The filters shall be rated not less than 80% efficiency
(based on ASHRAE 52.1) and shall be of >50mm depth. A differential pressure
switch shall be fitted to indicate the filters need changing through a service alarm
from the controller. Air filter shall be of disposable type & with cardboard frame.

~ 16 ~
Differential Pressure Transmitter for Underfloor Pressure Control

Differential Pressure Transmitter shall be used to detect pressure difference between


the room and the underfloor in order to maintain a constant differential pressure when
using EC fan. The EC fan shall regulate its speed in order to maintain the pre-set
differential pressure. This differential pressure setting shall be set via the controller
display interface.

Fire Alarm Relay

A 24VDC relay shall be provided to receive an external signal from the fire control
panel or detection system. When the external signal is received, the unit shall stop
operation.

Supply Temperature and Humidity Sensor

An additional Temperature and Humidity Sensor shall be provided to measure the


supply air condition of the unit. User shall be able to set to either control the unit via
supply air condition or return air condition.

Wooden Crate

A plywood and timber enclosure shall be provided to protect the unit from damage
during transportation to site.

Automatic Transfer Switch (ATS)

ATS shall be provided to handle the transfer of incoming power source for dual power
system. The ATS shall be factory installed and wired and integrated the switching
signal to the controller.

Microprocessor Control System with Touch Screen Display

a) The control system shall be able to maintain the temperature and humidity to a
tolerance of ±1.0°C and ±5 %RH.
b) The control system shall have a fascia with 480 x 272 pixel resolution TFT touch
screen graphical display located on the front panel of the unit for display and
programming functions. The display shall show current modes of operation,
current return air temperature and relative humidity, target set point temperature &
relative humidity.
c) System configuration and setting shall be stored in non-volatile memory and
safeguard in the event of power failure.
d) The system shall have at least three levels of programmable password access
to prevent any unauthorized changes of the system configurations.
e) The display shall have multi language support with option to select between
English, Malay, Chinese, Japanese and Thai languages.
f) The system shall have a temperature and humidity graph which shows data up
to 4 weeks duration. The data of the graph shall be logged in one minute
intervals. An option to show the temperature graph of the chilled water system
(inlet and outlet if applicable) shall be available.

~ 17 ~
g) The system shall have programmable selections: manual or automatic restart
option. A programmable start-up delay shall be provided for the automatic
restart option which allows multiple units to restart progressively when power
resumes after a power failure.
h) The accumulated run time of the following components shall be logged.
a. Fan
b. Heater
c. Humidifier
i) Components shall be scheduled to activate sequentially to minimize inrush
current.
j) The control system shall have but not limited to the following alarms.
a. High / low temperature
b. High / low humidity
c. Filter clogged
d. Loss of air flow
e. Water in high temperature
f. Heater overheat
g. Humidifier fault (if humidifier present)
h. Humidifier cylinder change (if humidifier present)
i. Drip tray full (if water detection option present)
j. Water on floor (if water detection option present)
k) When an alarm condition exists, the common alarm output shall be energized
until acknowledged. Active alarm record shall remain until the alarm
condition is cleared.
l) A historical event log which maintains the latest events of up to 4 weeks shall
be provided. The text description and occurrence time of the all alarms shall
be logged and shall be displayed in order of occurrence for ease of
troubleshooting.
m) The units shall have built-in master and slave inter-networking capability and
auto-sequencing which allow a combination of all units to form a local area
network. The control of a slave unit shall not be limited to any particular
master unit. In case of a master unit failure, the remaining units in the same
network shall automatically take over the control and one of then shall act as
master unit.
n) The controller shall be compatible with most remote monitoring and control
devices. Controller shall have built-in RS485 port ready for Modbus
connection. Options shall be available for other BMS interface via BACnet,
LonWorks and SNMP.

~ 18 ~
REMOTE MONITORING AND SUPERVISORY SYSTEM

Several remote monitoring, control and supervisory systems are available as add-ons
to the controller to enable user to access data and make settings changes to the units
without having to be physically present in front of the unit.

WebGate

To connect controller to a local network based on standard Ethernet & TCP/IP


protocol. The device functions as a web server with a fixed IP which can be accessed
via a LAN or through the Internet.

pCOWeb

Allows communication between controller with BACnet Ethernet, BACnet over IP,
SNMP protocol (v1 & v2c), HTTP protocol, FTP and DHCP protocol. The device
functions as a web server with a fixed IP which can be accessed via a LAN or through
the Internet.

pCOnet

Allows communication with BACnet MS/TP protocol.

LonWorks Interface Card

Allows controller to interface directly with a LonWorks network.

G-Visor

Manage CRAC operation to optimise cooling efficiency.

Notes:
1. For more detailed information on these options, please refer to the Genius Controller Engineering Data.
2. Please note that certain combinations of options are not available with other options while other combinations
might require further upgrades or additional accessories to be added. To check whether a certain combination
of options is available, please consult factory. For availability of other special options & accessories not listed
above, please also check with factory.

~ 19 ~
TECHNICAL DATA

EC Range - Downflow

Unit Model 25 30* 50 60 70 80


Gross Total Capacity kW 24.07 30.27 51.01 64.31 74.71 83.63
Gross Sensible Capacity kW 22.31 27.58 46.08 57.00 66.77 73.76
S.H.R. 0.93 0.91 0.90 0.89 0.89 0.88
General Data
Nominal Air Flow m³/s 1.84 2.24 3.70 4.40 5.20 5.20
No. of Fan(s) 1 1 2 2 2 2
Sound Level dBA 61 62 64 67 67 67
Chilled Water Coil
Nominal Water Flow l/s 1.15 1.45 2.44 3.07 3.57 4.00
Water Pressure Drop kPa 34.6 56.6 67.7 107.9 69.2 70.9
Electric Re-heater
Nominal Heater Capacity kW 6 6 12 12 12 12
No. of Heater Step(s) 1 1 2 2 2 2
Electrode Humidifier
Nominal Humidifier Capacity kg/hr 5 5 5 5 5 5
Air Filter
Type G4, MERV8, Disposable
301x700x100(2) 301x700x100(2)
WxHxD (Qty) mm 632x700x100(1) 350x700x100(2) 565x700x100(2) 350x700x100(4)
350x700x100(3) 350x700x100(3)

Unit Piping Connection


Water In/Out mm 35 35 42 54 54 54
Drain mm 22 22 22 22 22 22
Humidifier Feed 3/4" G(M) 3/4" G(M) 3/4" G(M) 3/4" G(M) 3/4" G(M) 3/4" G(M)
Humidifier Drain mm 32 32 32 32 32 32
Unit Dimension
Width mm 800 885 1315 1550 1800 1800
Depth mm 891 891 891 891 891 891
Height mm 1985 1985 1985 1985 1985 1985
Min. Service Allowance mm 725 725 725 725 725 725

Notes:
1. Cooling capacity is based on 24ºC, 45%RH, Chilled Water in/out based on 7/12ºC, 50Hz, 50Pa ESP.
2. Sound level is measured at 1m in free ¿eld conditions.
3. For underfloor EC fan option, raise floor height must be >400mm.
4. *For downflow version, only EC fan is available.

~ 20 ~
Unit Model 95 110 125 135 150
Gross Total Capacity kW 100.27 113.93 123.42 131.51 155.54
Gross Sensible Capacity kW 87.09 99.01 106.18 115.05 133.88
S.H.R. 0.87 0.87 0.86 0.88 0.86
General Data
Nominal Air Flow m³/s 6.00 7.00 7.00 7.60 8.60
No. of Fan(s) 2 3 3 3 4
Sound Level dBA 68 68 68 68 68
Chilled Water Coil
Nominal Water Flow l/s 4.79 5.44 5.90 6.28 7.43
Water Pressure Drop kPa 107.6 145.4 90.6 60.6 87.2
Electric Re-heater
Nominal Heater Capacity kW 12 12 12 12 12
No. of Heater Step(s) 2 2 2 2 2
Electrode Humidifier
Nominal Humidifier Capacity kg/hr 8 8 8 8 8
Air Filter
Type G4, MERV8, Disposable
301x700x100(4) 301x700x100(6) 301x700x100(6) 301x700x100(3)
WxHxD (Qty) mm 301x700x100(8)
350x700x100(2) 350x700x100(1) 350x700x100(1) 350x700x100(5)

Unit Piping Connection


Water In/Out mm 54 67 67 67 67
Drain mm 22 22 22 22 22
Humidifier Feed 3/4" G(M) 3/4" G(M) 3/4" G(M) 3/4" G(M) 3/4" G(M)
Humidifier Drain mm 32 32 32 32 32
Unit Dimension
Width mm 2065 2300 2300 2550 2815
Depth mm 891 891 891 891 891
Height mm 1985 1985 1985 1985 1985
Min. Service Allowance mm 725 725 725 725 725

Notes:
1. Cooling capacity is based on 24ºC, 45%RH, Chilled Water in/out based on 7/12ºC, 50Hz, 50Pa ESP.
2. Sound level is measured at 1m in free ¿eld conditions.
3. For underfloor EC fan option, raise floor height must be >400mm.
4. *For downflow version, only EC fan is available.

~ 21 ~
EC Range - Upflow

Unit Model 25* 30 50* 60 70 80


Gross Total Capacity kW 24.07 30.27 51.01 61.16 71.20 79.58
Gross Sensible Capacity kW 22.31 27.58 46.08 54.22 63.76 70.39
S.H.R. 0.93 0.91 0.90 0.89 0.90 0.88
General Data
Nominal Air Flow m³/s 1.84 2.24 3.70 4.20 5.00 5.00
No. of Fan(s) 1 1 2 2 2 2
Sound Level dBA 61 62 64 67 67 67
Chilled Water Coil
Nominal Water Flow l/s 1.15 1.45 2.44 2.92 3.40 3.80
Water Pressure Drop kPa 34.6 56.6 67.7 104.0 65.8 65.9
Electric Re-heater
Nominal Heater Capacity kW 6 6 12 12 12 12
No. of Heater Step(s) 1 1 2 2 2 2
Electrode Humidifier
Nominal Humidifier Capacity kg/hr 5 5 5 5 5 5
Air Filter
Type G4, MERV8, Disposable
633X850X100(1) 633X850X100(1) 633X850X100(1)
WxHxD (Qty) mm 637x572x100(1) 722x572x100(1) 547x572x100(2)
633X582X100(2) 384X582X100(4) 384X582X100(4)

Unit Piping Connection


Water In/Out mm 35 35 42 54 54 54
Drain mm 22 22 22 22 22 22
Humidifier Feed 3/4" G(M) 3/4" G(M) 3/4" G(M) 3/4" G(M) 3/4" G(M) 3/4" G(M)
Humidifier Drain mm 32 32 32 32 32 32
Unit Dimension
Width mm 800 885 1315 1550 1800 1800
Depth mm 891 891 891 891 891 891
Height mm 1985 1985 1985 1985 1985 1985
Min. Service Allowance mm 725 725 725 725 725 725

Notes:
1. Cooling capacity is based on 24ºC, 45%RH, Chilled Water in/out based on 7/12ºC, 50Hz, 50Pa ESP.
2. Sound level is for downflow models measured at 1m in free ¿eld conditions.
3. *For upflow version, only EC fan is available (except model 25 & 50).

~ 22 ~
Unit Model 95 110 125 135 150
Gross Total Capacity kW 95.93 108.2 117.73 127.41 151.06
Gross Sensible Capacity kW 83.55 94.22 101.33 111.52 130.11
S.H.R. 0.87 0.87 0.86 0.88 0.86
General Data
Nominal Air Flow m³/s 5.80 6.70 6.70 7.40 8.40
No. of Fan(s) 2 3 3 3 4
Sound Level dBA 68 68 68 68 68
Chilled Water Coil
Nominal Water Flow l/s 4.58 5.17 5.63 6.09 7.22
Water Pressure Drop kPa 101.2 135.0 89.5 59.8 86.5
Electric Re-heater
Nominal Heater Capacity kW 12 12 12 12 12
No. of Heater Step(s) 2 2 2 2 2
Electrode Humidifier
Nominal Humidifier Capacity kg/hr 8 8 8 8 8
Air Filter
Type G4, MERV8, Disposable
633X850X100(1) 633X850X100(1)
633X850X100(1) 633X850X100(1) 633X850X100(1)
WxHxD (Qty) mm 384X582X100(4) 540X582X100(4)
540X582X100(4) 633X582X100(4) 633X582X100(4)
633X582X100(2) 633X582X100(2)
Unit Piping Connection
Water In/Out mm 54 67 67 67 67
Drain mm 22 22 22 22 22
Humidifier Feed 3/4" G(M) 3/4" G(M) 3/4" G(M) 3/4" G(M) 3/4" G(M)
Humidifier Drain mm 32 32 32 32 32
Unit Dimension
Width mm 2065 2300 2300 2550 2815
Depth mm 891 891 891 891 891
Height mm 1985 1985 1985 1985 1985
Min. Service Allowance mm 725 725 725 725 725

Notes:
1. Cooling capacity is based on 24ºC, 45%RH, Chilled Water in/out based on 7/12ºC, 50Hz, 50Pa ESP.
2. Sound level is for downflow models measured at 1m in free ¿eld conditions.
3. *For upflow version, only EC fan is available (except model 25 & 50).

~ 23 ~
ECL Range

Unit Model 70 80 125 140 180 200


Gross Total Capacity kW 69.20 76.74 127.79 141.71 180.09 200.13
Gross Sensible Capacity kW 61.05 66.61 112.58 122.97 159.52 174.46
S.H.R. 0.88 0.87 0.88 0.87 0.89 0.87
General Data
Nominal Air Flow m³/s 4.4 4.4 8.2 8.2 11.7 11.7
No. of Fan(s) 1 1 2 2 3 3
Sound Level dBA 67 67 68 68 70 70
Chilled Water Coil
Nominal Water Flow l/s 3.31 3.67 6.11 6.77 8.60 9.56
Water Pressure Drop kPa 105.3 68.3 86.3 86.3 111.5 122.3
Electric Re-heater
Nominal Heater Capacity kW 12 12 12 12 12 12
No. of Heater Step(s) 2 2 2 2 2 2
Electrode Humidifier
Nominal Humidifier Capacity kg/hr 5 5 8 8 8 8
Air Filter
Type G4, MERV8, Disposable
512X348X50(6) 872X348X50(6) 829X348X50(9)
WxHxD (Qty) mm 514X523X50(4) 874X523X50(4) 832X523X50(6)
Unit Piping Connection
Water In/Out mm 54 54 67 67 67 67
Drain mm 22 22 22 22 22 22
Humidifier Feed 3/4" G(M) 3/4" G(M) 3/4" G(M) 3/4" G(M) 3/4" G(M) 3/4" G(M)
Humidifier Drain mm 32 32 32 32 32 32
Unit Dimension
Width mm 1315 1315 2065 2065 2815 2815
Depth mm 991 991 991 991 991 991
Height mm 1985 1985 1985 1985 1985 1985
Min. Service Allowance mm 725 725 725 725 725 725

Notes:
1. Cooling capacity is based on 24ºC, 45%RH, Chilled Water in/out based on 7/12ºC, 50Hz, 50Pa ESP.
2. Sound level is for downflow models measured at 1m in free ¿eld conditions.
3. Raise floor height must be >500mm.
4. Only downflow version with EC fan is available.

~ 24 ~
ELECTRICAL DETAIL

EC Range

Unit Model 25 30 50 60 70 80 95 110 125 135 150


Belt Driven Fan Version
Operating Current A 5.6 6.3 11.8 12.4 12.9 13.0 14.5 18.3 18.7 19.3 24.8
Operating Power kW 2.6 3.0 5.7 6.0 6.3 6.3 7.1 8.9 9.1 9.4 12.7
With Humidifier:
Rated Load Amps A 23.5 23.5 39.2 39.2 39.2 39.2 46.9 50.0 50.0 50.0 56.2
Max. Inrush Amps A 46.2 46.2 91.4 91.4 91.4 91.4 116.5 137.2 137.2 137.2 182.5
Rated Load kW kW 15.1 15.1 25.2 25.2 25.2 25.2 30.0 31.6 31.6 31.6 35.8
Without Humidifier:
Rated Load Amps A 16.5 16.5 32.2 32.2 32.2 32.2 35.6 38.7 38.7 38.7 44.9
Max. Inrush Amps A 46.2 46.2 91.4 91.4 91.4 91.4 116.5 137.2 137.2 137.2 182.5
Rated Load kW kW 10.2 10.2 20.3 20.3 20.3 20.3 22.2 23.8 23.8 23.8 28.0
EC Fan Version
Operating Current A 3.8 4.2 6.7 6.7 7.5 7.5 8.3 9.6 9.6 10.8 12.5
Operating Power kW 2.0 2.2 3.7 3.7 4.2 4.2 4.5 5.5 5.5 6.2 7.2
With Humidifier:
Rated Load Amps A 21.3 21.8 34.6 34.6 35.7 35.7 40.5 42.8 42.8 44.4 46.7
Max. Starting Amps A 7.3 8.2 13.8 13.8 15.6 15.6 15.6 20.3 20.3 23.0 26.7
Rated Load kW kW 14.1 14.5 23.1 23.1 23.9 23.9 27.1 28.5 28.5 29.6 30.9
Without Humidifier:
Rated Load Amps A 14.2 14.8 27.6 27.6 28.7 28.7 29.2 31.5 31.5 33.1 35.4
Max. Starting Amps A 7.3 8.2 13.8 13.8 15.6 15.6 15.6 20.3 20.3 23.0 26.7
Rated Load kW kW 9.2 9.6 18.3 18.3 19.0 19.0 19.3 20.7 20.7 21.8 23.1

Notes:
1. Operating current and power stated for unit running in cooling mode under nominal conditions.
2. Unit rated load power and current is calculated based on worst possible combination of components operating at the same time. Unit
assumed to have nominDOKHDWHUDQGKXPLGL¿HU
3. Electrical data is based on 400V/3ph/50Hz power supply.

~ 25 ~
ECL Range

Unit Model 70 80 125 140 180 200

Operating Current A 5.3 5.9 9.9 11.0 14.3 16.0


Operating Power kW 3.0 3.4 5.8 6.5 8.6 9.7
With Humidifier:
Rated Load Amps A 32.5 32.5 42.4 42.4 48.0 48.0
Max. Starting Amps A 9.3 9.3 17.7 17.7 26.1 26.1
Rated Load kW kW 21.8 21.8 28.2 28.2 31.7 31.7
Without Humidifier:
Rated Load Amps A 25.5 25.5 31.1 31.1 36.7 36.7
Max. Starting Amps A 9.3 9.3 17.7 17.7 26.1 26.1
Rated Load kW kW 16.9 16.9 20.4 20.4 23.9 23.9

Notes:
1. Operating current and power stated for unit running in cooling mode under nominal conditions.
2. Unit rated load power and current is calculated based on worst possible combination of components operating at the same time. Unit
DVVXPHGWRKDYHQRPLQDOKHDWHUDQGKXPLGL¿HU
3. Electrical data is based on 400V/3ph/50Hz power supply.

'XHWRRXUSROLF\RIFRQWLQXHVGHYHORSPHQWDQGLPSURYHPHQWWKHVSHFL¿FDWLRQVDQGGDWDKHUHLQDUHVXEMHFWWRFKDQJHZLWKRXWSrior
notice. We must therefore reserve the right to supply equipment that may differ from that described and illustrated herein. All
information, including illustrations, contained in this brochure, is believed to be accurate and reliable. Users, however, should
independently evaluate the suitability of each product for their own application. CITEC makes no warranties as to the accuracy or
completeness of the information, and disclaims any liability regarding its use.

~ 26 ~