Duct Sizing Chart-English
Duct Sizing Chart-English
Duct Sizing Chart-English
0003 ft
Duct Design
Fig. 9 Friction Chart for Round Duct (ρ = 0.075 lbm/ft3 and ε = 0.0003 ft)
34.9
34.10 2001 ASHRAE Fundamentals Handbook
Dynamic losses occur along a duct length and cannot be sepa- where pv,c is the velocity pressure at the common section c, and Cc,s
rated from friction losses. For ease of calculation, dynamic and Cc,b are losses for the straight (main) and branch flow paths,
losses are assumed to be concentrated at a section (local) and to respectively, each referenced to the velocity pressure at section c. To
exclude friction. Frictional losses must be considered only for convert junction local loss coefficients referenced to straight and
relatively long fittings. Generally, fitting friction losses are branch velocity pressures, use the following equation:
accounted for by measuring duct lengths from the centerline of
one fitting to that of the next fitting. For fittings closely coupled C c Ii
(less than six hydraulic diameters apart), the flow pattern enter- C i Z ---------------------2- (34)
( Vi ⁄ Vc )
ing subsequent fittings differs from the flow pattern used to
determine loss coefficients. Adequate data for these situations
where
are unavailable.
For all fittings, except junctions, calculate the total pressure loss Ci = local loss coefficient referenced to section being calculated (see
subscripts), dimensionless
∆pj at a section by
Cc,i = straight (Cc,s ) or branch (Cc,b ) local loss coefficient referenced to
dynamic pressure at common section, dimensionless
∆p j Z C o p v Io (30)
Vi = velocity at section to which Ci is being referenced, fpm
Vc = velocity at common section, fpm
where the subscript o is the cross section at which the velocity pres-
sure is referenced. The dynamic loss is based on the actual velocity Subscripts:
in the duct, not the velocity in an equivalent noncircular duct. For the b = branch
cross section to reference a fitting loss coefficient, refer to Step 4 in s = straight (main) section
the section on HVAC Duct Design Procedures. Where necessary c = common section
(unequal area fittings), convert a loss coefficient from section o to The junction of two parallel streams moving at different veloci-
section i using Equation (31), where V is the velocity at the respec- ties is characterized by turbulent mixing of the streams, accompa-
tive sections. nied by pressure losses. In the course of this mixing, an exchange of
Co momentum takes place between the particles moving at different
C i Z ----------------------2 (31) velocities, finally resulting in the equalization of the velocity distri-
( Vi ⁄ Vo ) butions in the common stream. The jet with higher velocity loses a
part of its kinetic energy by transmitting it to the slower moving jet.
For converging and diverging flow junctions, total pressure The loss in total pressure before and after mixing is always large and
losses through the straight (main) section are calculated as positive for the higher velocity jet and increases with an increase in
the amount of energy transmitted to the lower velocity jet. Conse-
∆p j Z C c Is p v Ic (32) quently, the local loss coefficient, defined by Equation (29), will
always be positive. The energy stored in the lower velocity jet
For total pressure losses through the branch section, increases as a result of mixing. The loss in total pressure and the
local loss coefficient can, therefore, also have negative values for the
∆p j Z C c Ib p v Ic (33) lower velocity jet (Idelchik et al. 1994).