IV.1.41.01 Engineered Discharge Nozzles
IV.1.41.01 Engineered Discharge Nozzles
IV.1.41.01 Engineered Discharge Nozzles
DATA SHEET
ENGINEERED DISCHARGE NOZZLES FOR Approvals
SYSTEMS USING 3M™ NOVEC™ 1230 Underwriters Laboratories (UL)
FIRE PROTECTION FLUID Underwriters Laboratories of Canada (ULC)
Factory Mutual (FM)
For exact certification listings, please reference the respective
agency web site.
Ordering
Part Number Description
80‐124‐50‐XXXX 1/2” (15 mm) 360° nozzle
80‐124‐75‐XXXX 3/4” (20 mm) 360° nozzle
360° Nozzle 180° Nozzle
80‐124‐100‐XXXX 1” (25 mm) 360° nozzle
Description 80‐124‐125‐XXXX 1 1/4” (32 mm) 360° nozzle
80‐124‐150‐XXXX 1 1/2” (40 mm) 360° nozzle
The discharge nozzles are made of brass and are
available in a 180° and 360° discharge patterns. The 80‐124‐200‐XXXX 2” (50 mm) 360° nozzle
nozzles are designed to control the agent flow and to 80‐122‐50‐XXXX 1/2” (15 mm) 180° nozzle
distribute the agent throughout the protected
80‐122‐75‐XXXX 3/4” (20 mm) 180° nozzle
enclosure in a uniform, predetermined pattern and
concentration. 80‐122‐100‐XXXX 1” (25 mm) 180° nozzle
Six sizes of discharge nozzles are available, 1/2” (15 80‐122‐125‐XXXX 1 1/4” (32 mm) 180° nozzle
mm) through 2” (50 mm). The size refers to the size 80‐122‐150‐XXXX 1 1/2” (40 mm) 180° nozzle
of schedule 40 or 80 pipe that the nozzle can be
80‐122‐200‐XXXX 2” (50 mm) 180° nozzle
connected to. Each nozzle has NPT female threads for
Note: ‐XXXX in part number is the orifice code designation.
connection to the pipe network.
When ordering nozzles, orifice size must be specified.
The nozzle orifice area is determined by performing a
hydraulic calculation using the Fike Engineered Flow
Calculation program. Nozzle(s) should not be ordered
until the clean agent system pipe network is installed
and an “As Built” hydraulic calculation is performed.
Nozzle orifice drilling must be done at Fike factory, or
at a UL listed nozzle drill station.
This document is only intended to be a guideline and is not applicable to all situations.
Information is subject to Fike’s full disclaimer at http://www.fike.com/disclaimer.
Form No. IV.1.41.01 ● 06/19 ISO 9001:2015 Certified Page 1 of 1