  DATA SHEET 

ENGINEERED DISCHARGE NOZZLES FOR  Approvals 
SYSTEMS USING 3M™ NOVEC™ 1230  Underwriters Laboratories (UL) 
FIRE PROTECTION FLUID   Underwriters Laboratories of Canada (ULC) 
Factory Mutual (FM) 
For  exact  certification  listings,  please  reference  the  respective 
agency web site. 

Ordering 
Part Number  Description 
80‐124‐50‐XXXX  1/2” (15 mm) 360° nozzle 
 
80‐124‐75‐XXXX  3/4” (20 mm) 360° nozzle 
360° Nozzle 180° Nozzle
80‐124‐100‐XXXX  1” (25 mm) 360° nozzle 
Description  80‐124‐125‐XXXX  1 1/4” (32 mm) 360° nozzle 
80‐124‐150‐XXXX  1 1/2” (40 mm) 360° nozzle 
The  discharge  nozzles  are  made  of  brass  and  are 
available in a 180° and 360° discharge patterns. The  80‐124‐200‐XXXX  2” (50 mm) 360° nozzle 
nozzles are designed to control the agent flow and to  80‐122‐50‐XXXX  1/2” (15 mm) 180° nozzle 
distribute  the  agent  throughout  the  protected 
80‐122‐75‐XXXX  3/4” (20 mm) 180° nozzle 
enclosure  in  a  uniform,  predetermined  pattern  and 
concentration.  80‐122‐100‐XXXX  1” (25 mm) 180° nozzle 
Six sizes of discharge nozzles are available, 1/2” (15  80‐122‐125‐XXXX  1 1/4” (32 mm) 180° nozzle 
mm) through 2” (50 mm). The size refers to the size  80‐122‐150‐XXXX  1 1/2” (40 mm) 180° nozzle 
of  schedule  40  or  80  pipe  that  the  nozzle  can  be 
80‐122‐200‐XXXX  2” (50 mm) 180° nozzle 
connected to. Each nozzle has NPT female threads for 
Note: ‐XXXX in part number is the orifice code designation. 
connection to the pipe network.  
 
When ordering nozzles, orifice size must be specified. 
The nozzle orifice area is determined by performing a 
hydraulic calculation using the Fike Engineered Flow 
Calculation program. Nozzle(s) should not be ordered 
until the clean agent system pipe network is installed 
and an “As Built” hydraulic calculation is performed. 
Nozzle orifice drilling must be done at Fike factory, or 
at a UL listed nozzle drill station. 

This document is only intended to be a guideline and is not applicable to all situations. 
Information is subject to Fike’s full disclaimer at http://www.fike.com/disclaimer. 
Form No. IV.1.41.01 ● 06/19  ISO 9001:2015 Certified  Page 1 of 1
 