The document discusses various Controller Area Network (CAN) nodes that expand the monitoring capabilities of Smartpack and Smartpack2 power control systems. The CAN nodes plug directly into the CAN bus and are powered through it, allowing flexible positioning. Models discussed include the Battery Monitor, Load Monitor, I/O Monitors for inputs/outputs, CAN Power for additional power, and AC Mains Monitor. The nodes have compact designs, digital and analog inputs/outputs, and communicate via CAN ID numbers to integrate with the Smartpack controllers.

Uploaded by

Regal Beagle
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
297 views4 pages

Controller CAN Nodes

The document discusses various Controller Area Network (CAN) nodes that expand the monitoring capabilities of Smartpack and Smartpack2 power control systems. The CAN nodes plug directly into the CAN bus and are powered through it, allowing flexible positioning. Models discussed include the Battery Monitor, Load Monitor, I/O Monitors for inputs/outputs, CAN Power for additional power, and AC Mains Monitor. The nodes have compact designs, digital and analog inputs/outputs, and communicate via CAN ID numbers to integrate with the Smartpack controllers.

Uploaded by

Regal Beagle
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Controller CAN Nodes

Extending the control system


Controller CAN Nodes
Various CAN Nodes are available for Smartpack and Smartpack2. The nodes have dedicated inputs and outputs that expand the system monitoring. The units plug-and-play with Smartpack controllers, no local powering of the units is needed.

Control system
Overview The controller CAN nodes cover all aspects of DC power system monitoring: AC Mains Voltage, current, frequency and energy consumption Battery symmetry, current and fuse monitoring Alarm outputs and control inputs Load branch current and fuse Climate control of fan/filter cabinets Generator control/fuel tank level measurements

Product Features and Advantages


Flexibility and reliability Most CAN Nodes have a rugged sealed-plastic design, with post, DIN-rail or Velcro tabs as standard mounting options. Power and communication goes through the CAN bus, and hence only a RJ45 patch cable is required for connecting the node to the control system. This allows great flexibility in positioning of the nodes they can be put close to their measuring connections, reducing wiring. All controller CAN nodes comes with a DIP-switch to allow multiple modules of the same type on the CAN bus. The maximum number of each type is limited to 14. Plug and play After setting the CAN ID of module by the DIP-switch and connecting it to the CAN bus, it will plug and Play with the Smartpack1/2 controller. Meaning, the module will automatically communicate with the controller when connected to the CAN bus. Configuration, setup and calibration are then available via the user display on Smartpack2 and for all controllers through the software tools WebPower and PowerSuite. Global compliance The CAN Nodes are approved for global use meeting CE safety and EMC requirements. Units are also UL Recognized for safety (incl. CSA).

See last page for specifications

www.eltekvalere.com

Models
Battery Monitor Its compact design and easy connection to the control system through the CAN bus, makes it perfect for both co-located and remote battery banks. Battery temperature is measured by the embedded temperature probe no external sensor and wiring required. The unit has 4 voltage measurement inputs used for battery symmetry monitoring based on midpoint or block measurements. Furthermore the battery monitor has inputs for monitoring one battery shunt and battery breaker.

Load Monitor Individual distribution breaker monitoring can be done with the Load Monitor. The unit has the possibility to connect up to 8 current shunts and monitor 8 fuses individually. It can be used for both positive and negative distributions. However it is important for the current measurements that the shunts are connected to the same pole as the system reference of the control system. CAN repeater and CAN Power device can be used in cases where this is not fulfilled.

I/O Monitors The I/O Monitors are used to expand the standard monitor and alarm capabilities of the controller. Each I/O monitor module has 6 configurable inputs for fuse sense and feeding external signals into the control system, and 6 configurable relay outputs for connecting external alarms. The I/O Monitor Type3 is designed for doing tank level measurements. Some of its inputs are prepared to do high resolution current and voltage measurements. In addition, special inputs and outputs are added for climate control in outdoor cabinets in the I/O Monitor (Outdoor) and Type3.

CAN Power All nodes are powered by the distributed power supplied on the CAN bus by the Smartpack and Smartpack2 basic controllers. If the CAN bus needs to be isolated or additional CAN bus power is need, the CAN power module can be added to supplement the available power. The CAN power module is mandatory if any CAN control units are to be connected to a Compack controller.

www.eltekvalere.com

2(4)

242100.CAN.DS3 v4

Models
AC Mains Monitor With inputs for measuring voltage and current on up to 3 phases of the AC mains of a system, the mains availability, quality and consumed energy are easily monitored. The energy log keeps track of consumption per phase and total, and stores it by hour, day and week. The log is available for download through the WebPower interface to the system. The current range are set by selecting the sensor, 0 50 A up to 0 600 A are available. Due to software restraints the energy log supports only up to 200A. There is also a configurable data log that by default stores AC frequency together with current and voltage for each measured phase and a time stamp. The log interval is configurable and the log has space for the last 5000 samples. The 5 configurable digital inputs can be used for monitoring SPDs and other external equipment

Additional Technical Specifications


CAN Power
Input Outputs Functionality 20 - 75Vdc (Screw terminals) +/-15V, 500mA (Dual RJ45 connector) o o Dimensions (WxDxH) Isolates the power distributed on the CAN bus Increase power available for the CAN nodes in the system

AC Mains Monitor
3 mains current sensor ports (for LEM HAL or equivalent) o o o o Sensor reference Signal Sensor supply Sensor supply + Signal NO/NC, Pull Up/Dn, Diode matrix CSCP Protocol Max 300 mA 402093.009 Energy log (non-volatile memory) of each phase and total (max 200A per phase) o Last 52 hours o Last 52 days o Last 52 weeks Data log with up to 5000 samples with timestamp (default: VAC, IAC and frequency) 176 x 97.6 x 42.8 mm (WxDxH) (6.93 x 3.84 x 1.69) 0V 0 4 Vp-p (45 - 65 Hz) -15 V 15 V 0-300 Vrms(45-65 Hz) (0 60 V)

3 mains voltage inputs o 5 configurable digital inputs o o 1 RS 485 Communication port for customer connection Max. CAN Power consumption

155.5 x 70.5 x 31 mm (6.12 x 2.78 x 1.22 )

Note: 500mA is supplied per Smartpack, 1A per Smartpack2 Basic

Controller CAN Nodes CAN ID


CAN ID # range CAN Device Smartpack Smartpack2 Basic Smartpack2 Master Smartnode Battery Monitor Load Monitor I/O Monitors Mains Monitor
www.eltekvalere.com

Start 1 1 11 17 33 49 81 97

End 14 10 14 30 46 62 94 110

Number of nodes 14 10 4 14 14 14 14 14
3(4)

SW Part number Functionality

Dimensions

242100.CAN.DS3 v4

Controller CAN Nodes


Additional Technical Specifications
Battery Monitor
Inputs 4x Symmetry Voltage (0 - 60V) 1x Fuse failure detect NO/NC/Diode Matrix 1x Current sense Voltage: 76mV Current (200A): +/- 1A Symmetry measurement o 2, 6, 12, 24, 30 or 36V Fuse failure o NO, NC or Diode Matrix Current sense o 50mV or 60mV shunt Temperature measurement o Embedded in unit 402086.009 90mA 72 x 54 x 25 mm (2.83 x 2.13 x 0.98 )

I/O Monitors: 1-Outdoor / 2-Type 2 / 3-Type 3


6 configurable inputs: digital, voltage/current measurement o NO/NC, Pull Up/Dn, Diode Matrix Voltage range 0-75V (78mV res) o NO/NC, Voltage range 0-10V (13mV resolution) o Current measurement 4-20mA (27A resolution) No1-6(1,2), No1-2(3) No3-6(3) No5-6(3)

Accuracy based on resolution (calibrated) Functionality

6 configurable relay outputs: normally activated/deactivated o Dry/Form C, Max 1A/60W/75V o Dry/Form C, Max 8A/300W/75V No1-4(1,3), No1-6(2) No5-6(1,3)

Outdoor cabinet specific ports: temp, fan control/monitoring o 2xTemp sensor inputs (-40-100C with 0.14C res.)(1,3) o 2xFan speed inputs (0-5V or pulse sense 1-10 p/r)(1,3) o 2xFan speed control outputs (0-10V, max -10/+20mA) (1,3) Max. CAN Power consumption SW Part number Functionality 402088.009
(1,2,3)

SW Part number Max. CAN Power consumption Dimensions (WxDxH)

Max 3.4W (1,2,3)

Load Monitor
Inputs Accuracy based on resolution (calibrated) Functionality 8x Configurable (Fuse failure) 8x Current sense Current (200A): +/- 1A Fuse failure o NO, NC or Diode Matrix Current sense o 50mV or 60mV shunt 402087.009 120mA 155.5 x 70.5 x 31 mm (6.12 x 2.78 x 1.22 ) Dimensions (WxDxH)

Data logging (non-volatile memory) o 10000 time stamped logs o 4 user selectable data points o Default: 2x Temp. 2x Fan Speed 155.5 x 85.2 x 31 mm (1,3) (6.1 x 3.4 x 1.2 ) 135.9 x 59 x 25.6 mm (2) (5.4 x 2.3 x 1.2 )

SW Part number Max. CAN Power consumption Dimensions (WxDxH)

All CAN Nodes


Max. nodes Mounting Visual Indication 14 units of same type can be added a single CAN bus 3xLED (1xLED CAN Power) o GREEN: Power o YELLOW: Warning o RED: Alarm (Flashing LED: insufficient power) Smartpack2 Master through CAN or FWLoader (Ver 3.25) and IXXAT USB-to-CAN Converter (p/n: 208565) Plastic - V0 rated / Steel (CAN Power) -40 to 70C (-40 to 158F) Storage temp -40 to 85C (-40 to 185F) (Also see CAN Power) Slotted groove for post mounting or DIN rail/Velcro (for Battery Monitor)

SW Upload tools Casing material Operating temp

Applicable Standards
Electrical safety IEC 60950-1 UL 60950-1 CSA C22.2 IEC 61000-6-1 IEC 61000-6-2 IEC 61000-6-3 /A1 IEC 61000-6-4 ETSI EN 300 386 v1.3.3 FCC Part 15B Subpart 109 2002/95/EC (RoHS) & 2002/96/EC (WEEE) ETS 300 019-2-1 Class 1.2 ETS 300 019-2-2 Class 2.3 ETS 300 019-2-3 Class 3.2
Specifications are subject to change without notice 241120.200.DS3 v4

EMC

Part numbers

Part no.

Environment

242100.300 242100.301 242100.303 242100.304 242100.502 242100.306 242100.305

Description

Battery Monitor Load Monitor CAN Power I/O Monitor (Outdoor) I/O Monitor Type 2 I/O Monitor Type 3 AC Mains Monitor

www.eltekvalere.com
Eltek Valere Grterudv. 8, PB 2340 Strms, 3003 Drammen, Norway Phone: +47 32 20 32 00 Fax: +47 32 20 32 10