VLT2800 Data Sheet
VLT2800 Data Sheet
Data sheet
VLT 2800
Mains voltage
VLT 2800 is available for two mains voltage ranges:
200-240 V and 380-480 V.
Type
2803
2805
2807
2811
2815
[HP]
0.5
0.75
1.0
1.5
2.0
[HP]
0.5
0.75
1.0
1.5
2.0
3.0
5.0
Type
2803
2805
2807
2811
2815
2822
2840
Type
2805
2807
2811
2815
2822
2830
2840
2855
2875
2880
2881
2882
[HP]
0.75
1.0
1.5
2.0
3.0
4.0
5.0
7.5
10.0
15
20
25
FC protocol
Danfoss VLT frequency converters are able to fulfill
RFI filter
many different functions in a monitoring system. The
VLT 2800 is available with or without an integral 1A
frequency converter can be integrated directly in an
RFI-filter. The integral 1A RFI filter complies with
overall surveillance system, which will allow detailed
EMC standards EN 55011-1A.
process data to be transferred via serial communication.
With an integral RFI filter there is compliance with EN
The protocol standard is based on an RS 485 bus
55011-1B with a max. 15-metre screened/armoured
system with a maximum transmission speed of 9600
motor cable on VLT 2803-2815 1 x 220-240 Volt.
baud. The following Drive profiles are supported as
standard:
- FC Drive, which is a profile adapted to Danfoss.
Data sheet
Fieldbusoption
The increasing information requirements in industry
make it necessary to collect or visualize many different process data. Important process data help the
system technician with the daily monitoring of the
system. The large amounts of data involved in major
systems make a higher transmission speed than
9600 baud desirable.
Profibus
Profibus is a fieldbus system, which can be used for
linking automation devices such as sensors and
actuators with the controls by means of a twoconductor cable. Profibus DP is a very fast
communication protocol, made specially for communication between the automation system and various
types of equipment.
Profibus is a registered trade mark.
DeviceNet
DeviceNet fieldbus systems can be used for linking
automation devices such as sensors and actuators
with the controls by means of a fourwire conductor
cable.
DeviceNet is a medium speed communication protocol, made specially for communication between the
automation system and various types of equipment.
Units with DeviceNet protocol cannot be controlled
by FC protocol and Profidrive protocol.
VLT Software Dialog can be used on the Sub D plug.
200 m
100 m
IP 20
16 A
480 V AC
Side-by-side
100 mm
200 x 90 x 152
3.8 kg
Data sheet
Motor coils
By fitting the motor coil module between the VLT
2800 and the motor it is possible to use up to 200
metres of unscreened/unarmoured motor cable or
When a motor is controlled by a frequency converter, at times you will be able to hear the acoustic
noise from the motor. The noise, which is caused by
the design of the motor, is generated every time one
of the inverter contacts in the frequency converter is
activated. The frequency of the acoustic noise therefore corresponds to the frequency converters
connection frequency.
The filter reduces the voltages du/dt, the peak voltage Upeak and ripple current I to the motor, so that
the current and voltage are almost sine-shaped. The
acoustic motor noise is thus reduced to a minimum.
Data sheet
NB!:
The 1B/LC filter is not suitable for 200
V devices due to the high 1 input current.
Data sheet
1,1 kW
RFI
0,37 kW
RFI
Unit
ST
Profibus DP
ST
195N0037
SB
195N0038
R1
ST
195N0039
195N0001
R1
SB
195N0040
195N0041
195N0042
195N0043
SB
195N0002
ST
ST
195N0003
SB
R1
SB
195N0004
R1
ST
ST
195N0005
R1
SB
X
X
X
X
SB
195N0006
ST
195N0007
SB
195N0008
R1
ST
195N0009
R1
SB
Unit
Profibus DP
R1
ST
R1
SB
ST
SB
R1
ST
R1
SB
0,55 kW
RFI
Unit
X
X
X
X
DeviceNet
195N0011
1,5 kW
195N0012
RFI
Ordering no.
DP
195N0049
195N0050
R1
ST
195N0051
R1
SB
195N0052
195N0053
195N0054
195N0055
R1
ST
195N0015
R1
ST
R1
SB
195N0016
R1
SB
X
X
X
X
ST
195N0017
ST
195N0018
SB
195N0019
R1
ST
195N0020
R1
SB
Unit
Profibus DP
195N0013
ST
195N0014
SB
SB
ST
SB
R1
ST
R1
SB
X
X
X
X
Ordering no.
DeviceNet
R1
195N0048
ST
ST
195N0047
SB
ST
SB
195N0046
SB
195N0044
195N0045
R1
X
X
X
X
X
X
X
X
195N0010
Ordering no.
Ordering no.
R1
X
X
X
X
DeviceNet
DeviceNet
DP
-
X
X
X
X
195N0056
195N0057
195N0058
195N0059
195N0060
195N0021
195N0022
2,2 kW
195N0023
RFI
195N0024
ST
195N0061
SB
195N0062
Ordering no.
0,75 kW
R1
ST
195N0063
RFI
Unit
Profibus DP
DeviceNet
Ordering no.
R1
SB
195N0064
ST
195N0025
ST
195N0065
195N0026
SB
195N0066
195N0067
R1
ST
195N0027
R1
ST
R1
SB
195N0028
R1
SB
X
X
X
X
ST
195N0029
ST
195N0030
SB
195N0031
R1
ST
195N0032
R1
SB
SB
SB
R1
ST
R1
SB
X
X
X
X
ST
SB
R1
ST
R1
SB
10
X
X
X
X
X
X
X
X
195N0068
195N0069
195N0070
195N0071
195N0072
195N0033
195N0034
195N0035
195N0036
Profibus DP
DeviceNet
Ordering no.
ST
195N0073
SB
195N0074
R1
ST
195N0075
R1
SB
195N0076
195N0077
195N0078
195N0079
R1
ST
R1
SB
X
X
X
X
ST
ST
SB
SB
R1
ST
R1
SB
X
X
X
X
195N0080
195N0081
195N0082
195N0083
195N0084
Data sheet
NB!:
For VLT 2803-2815 220-with an R1 filter it is
only possible to connect single-phase mains
voltage 1 x 220 - 240 Volt.
11
1,5 kW
RFI
0,55 kW
RFI
Profibus DP
Unit
DeviceNet
Profibus DP
DeviceNet
Ordering no.
ST
195N1037
Ordering no.
SB
195N1038
ST
195N1001
R1
ST
195N1039
SB
195N1002
R1
SB
195N1040
195N1041
195N1042
195N1043
R1
ST
195N1003
ST
R1
SB
195N1004
SB
195N1005
R1
ST
195N1006
R1
SB
X
X
X
X
195N1007
ST
ST
SB
R1
ST
R1
SB
X
X
X
X
ST
SB
R1
ST
R1
SB
X
X
X
X
195N1008
SB
195N1009
R1
ST
195N1010
R1
SB
Unit
Profibus DP
RFI
Profibus DP
Unit
DeviceNet
X
X
X
X
195N1044
195N1045
195N1046
195N1047
195N1048
195N1011
195N1012
2,2 kW
RFI
0,75 kW
Ordering no.
ST
195N1049
Ordering no.
SB
195N1050
ST
195N1013
R1
ST
195N1051
SB
195N1014
R1
SB
195N1052
195N1053
195N1054
195N1055
R1
ST
195N1015
ST
R1
SB
195N1016
SB
195N1017
R1
ST
195N1018
R1
SB
X
X
X
X
195N1019
ST
ST
SB
R1
ST
R1
SB
X
X
X
X
ST
SB
R1
ST
R1
SB
X
X
X
X
195N1020
SB
195N1021
R1
ST
195N1022
R1
SB
Unit
Profibus DP
RFI
195N1024
Profibus DP
DeviceNet
X
X
X
X
195N1056
195N1057
195N1058
195N1059
195N1060
195N1023
3,0 kW
RFI
1,1 kW
Ordering no.
ST
195N1061
Ordering no.
SB
195N1062
ST
195N1025
R1
ST
195N1063
SB
195N1026
R1
SB
195N1064
195N1065
195N1066
195N1067
R1
ST
195N1027
ST
R1
SB
195N1028
SB
195N1029
R1
ST
195N1030
R1
SB
X
X
X
X
195N1031
ST
ST
SB
R1
ST
R1
SB
X
X
X
X
ST
SB
R1
ST
R1
SB
12
X
X
X
X
195N1032
SB
195N1033
R1
ST
195N1034
R1
SB
X
X
X
X
195N1068
195N1069
195N1070
195N1071
195N1072
195N1035
195N1036
RFI
Profibus DP
DeviceNet
11 kW
Ordering no.
RFI
Profibus DP
DeviceNet
Ordering no.
ST
195N1073
ST
195N1109
SB
195N1074
SB
195N1110
R1
ST
195N1075
R3
ST
195N1111
R1
SB
195N1076
R3
SB
195N1112
195N1077
ST
195N1113
195N1078
SB
195N1114
195N1079
R3
ST
195N1115
195N1080
R3
SB
X
X
X
X
195N1081
ST
195N1082
SB
195N1083
R3
ST
195N1084
R3
SB
RFI
Unit
Profibus DP
DeviceNet
ST
195N1121
SB
195N1122
195N1123
195N1124
195N1125
195N1126
195N1127
195N1128
R1
ST
R1
SB
X
X
X
X
ST
ST
SB
SB
R1
ST
R1
SB
X
X
X
X
15 kW
Unit
Profibus DP
DeviceNet
Ordering no.
R3
ST
ST
195N1085
R3
SB
SB
195N1086
ST
R1
ST
195N1087
SB
R1
SB
195N1088
ST
ST
195N1089
R3
SB
SB
195N1090
ST
R1
ST
195N1091
SB
R1
SB
X
X
X
X
R3
195N1092
R3
ST
ST
195N1093
R3
SB
SB
R1
ST
R1
SB
7,5 kW
RFI
Profibus DP
DeviceNet
195N1096
Ordering no.
ST
195N1097
SB
195N1098
R1
ST
195N1099
R1
SB
195N1100
ST
195N1101
SB
195N1102
R1
ST
195N1103
R1
SB
X
X
X
X
ST
SB
R1
ST
R1
SB
195N1118
195N1119
195N1120
X
X
X
X
X
X
X
X
Ordering no.
195N1129
195N1130
195N1131
195N1132
195N1095
X
X
X
X
195N1116
195N1117
195N1094
X
X
X
X
RFI
X
X
X
X
195N1104
195N1105
195N1106
18.5 kW
RFI
Unit
Profibus DP
DeviceNet
ST
195N1133
SB
195N1134
Ordering no.
R3
ST
195N1135
R3
SB
195N1136
ST
195N1137
195N1138
195N1139
SB
R3
ST
R3
SB
X
X
X
X
ST
SB
R3
ST
R3
SB
195N1107
X
X
X
X
195N1140
Data sheet
4,0 kW
195N1141
195N1142
195N1143
195N1144
195N1108
ST:
SB:
R1:
R3:
Standard
Standard
With RFI
With RFI
unit.
unit with integral brake.
filter that complies with EN 55011-1A.
filter that complies with EN 55011-1B
13
Type
2803
2805
2807
2811
2815
2822
2840
2805
2807
2811
2815
2822
2830
2840
(200
(200
(200
(200
(200
(200
(200
(400
(400
(400
(400
(400
(400
(400
V)
V)
V)
V)
V)
V)
V)
V)
V)
V)
V)
V)
V)
V)
P motor
[kW]
0.37
0.55
0.75
1.10
1.50
2.20
3.70
0.55
0.75
1.10
1.50
2.20
3.00
4.00
RMIN
[
]
297
198
135
99
69
43
21
747
558
387
297
198
135
99
Size [
] / [W]
per item
330
/ 100 W
220
/ 100 W
150
/ 100 W
100
/ 100 W
72
/ 200 W
50
/ 200 W
50
/ 200 W
830
/ 100 W
620
/ 100 W
430
/ 100 W
310
/ 200 W
210
/ 200 W
150
/ 200 W
240
/ 200 W
Duty cycle %
30
20
14
8
16
9
11
20
14
8
16
9
5.5
11
Order no.
175Uxxxx
1003
1004
1005
1006
0992
0993
2x09931
1000
1001
1002
0984
0987
0989
2x09861
Type
2803
2805
2807
2811
2815
2822
2840
2805
2807
2811
2815
2822
2830
2840
2855
2875
2880
2881
2882
(200
(200
(200
(200
(200
(200
(200
(400
(400
(400
(400
(400
(400
(400
(400
(400
(400
(400
(400
V)
V)
V)
V)
V)
V)
V)
V)
V)
V)
V)
V)
V)
V)
V)
V)
V)
V)
V)
Pmotor
[kW]
0.37
0.55
0.75
1.10
1.50
2.20
3.70
0.55
0.75
1.10
1.50
2.20
3.00
4.00
5.50
7.50
11.00
15.00
18.50
RMIN
[
]
297
198
135
99
74
50
22
747
558
387
297
198
135
99
80
56
40
30
25
RREC
[
]
330
220
150
110
82
56
25
830
620
430
330
220
150
110
80
56
40
30
25
Ppeak
[kW]
0.44
0.66
0.90
1.10
1.80
2.60
4.50
0.60
0.90
1.32
1.80
2.60
3.60
4.00
5.50
7.50
11.00
15.00
18.50
Pavg.
[kW]
0.18
0.26
0.36
0.44
0.72
1.06
1.80
0.25
0.36
0.53
0.72
1.06
1.44
1.60
2.20
3.00
5.00
9.30
12.70
Order no.
175U0xxx
900
901
902
975
903
904
925
976
910
911
912
913
914
979
977
978
997
998
999
Data sheet
Order form
15
16
Data sheet
17
18
Data sheet
19
20
Data sheet
21
No.
01-03
12
18-33
20, 55
42
461
50
53
60
671
68,
691
701
Function
Relay outputs 01-03 can be used for
indicating status and alarms/warnings.
24 V DC voltage supply.
Digital inputs.
Common frame for input
and output terminals.
Analog output for displaying frequency,
reference, current or torque.
Digital output for displaying status,
warnings or alarms, as well as
frequency output.
+10 V DC supply
voltage for potentiometer or thermistor.
Analogue voltage input 0 - 10 V DC.
Analogue current input 0/4 - 20 mA.
+ 5 V DC supply voltage
to Profibus.
RS 485, Serial communication.
Frame for terminals 67, 68 and 69.
Normally this terminal is not to be used.
22
All digital inputs are galvanically isolated from the supply voltage (PEL V) and other high-voltage terminals. See
section entitled Galvanic Isolation.
23
Data sheet
24
25
Data sheet
26
2803
2805
2807
2811
2815
2822
2840
I INV. [A]
2.2
3.2
4.2
6.0
6.8
9.6
16
(3 x 200-240V)
Output power (230 V)
Typical shaft output
3.5
0.9
0.37
5.1
1.3
0.55
6.7
1.7
0.75
9.6
2.4
1.1
10.8
2.7
1.5
15.3
3.8
2.2
25.6
6.4
3.7
PM,N [HP]
[mm 2 /AWG] 1 )
0.5
4/10
0.75
4/10
1.0
4/10
1.5
4/10
2.0
4/10
3.0
4/10
5.0
4/10
5.9
9.4
8.3
13.3
10.6
16.7
14.5
23.2
15.2
24.3
2.9
4.6
4/10
4.0
6.4
4/10
5.1
8.2
4/10
7.0
11.2
4/10
7.6
12.2
4/10
8.8
14.1
4/10
14.7
23.5
4/10
[A]
[%]
[W]
20/20
95
24
20/20
95
35
20/20
95
48
20/20
95
69
20/20
95
94
20/20
95
125
25/25
95
231
[kg]
type
2.0
IP 20
2.0
IP 20
2.0
IP 20
2.0
IP 20
2.0
IP 20
3,7
IP 20
6.0
IP 20
Input current
(1 x 220-240 V)
Input current
(3 x 200-240 V)
Max. cable cross
section, power
Max. pre-fuses
Efficiency3 )
Power loss at 100%
load
Weight
Enclosure4
Type
IL,MAX
IL,N [A]
(60s) [A]
IL,N [A]
IL,MAX (60s) [A]
[mm2 /AWG] 1 )
[A]/UL
2 )
Data sheet
1. American Wire Gauge. Max. cable cross section is the largest cable cross section that can be
attached to the terminals. Always observe national
and local regulations.
2. Type gG pre-fuses must be used. If you want to
maintain UL/cUL you must use pre-fuses of the
type Bussmann KTN-R 200 V, KTS-R 500 V or
Ferraz Shawmut, type ATMR (max. 30A). The
fuses must be placed for protection in a circuit that
is capable of supplying a maximum of 100,000
amps RMS (symmetrical), 500 V maximum.
3. Measured using a 25 m screened/armoured motor cable with a rated load and rated frequency.
4. IP20 is standard for VLT 2805-2875, whereas
NEMA 1 is an option.
27
Type
2805
2807
2811
2815
2822
2830
dards
Output current
I INV. [A]
1.7
2.1
3.0
3.7
5.2
7.0
(3 x 380-480V)
2.7
3.3
4.8
5.9
8.3
11.2
SINV. [KVA]
1.1
1.7
2.0
2.6
3.6
4.8
PM,N [kW]
0.55
0.75
1.1
1.5
2.2
3.0
PM,N [HP]
0.75
1.0
1.5
2.0
3.0
4.0
4/10
4/10
4/10
4/10
4/10
4/10
[mm2 /AWG]
1 )
tion, motor
Input current
IL,N [A]
1.6
1.9
2.6
3.2
4.7
6.1
(3 x 380-480 V)
IL,MAX(60s)[A]
2.6
3.0
4.2
5.1
7.5
9.8
[mm2 /AWG]
4/10
4/10
4/10
4/10
4/10
4/10
20/20
1 )
tion, power
Max. pre-fuses
[A]/UL
2 )
[A]
20/20
20/20
20/20
20/20
20/20
[%]
96
96
96
96
96
96
[W]
28
38
55
75
110
150
Efficiency3
load
Weight
[kg]
Enclosure4
type
Type
2.1
IP 20
2840
2.1
2.1
2.1
IP 20
IP 20
IP 20
2855
2875
2880
3.7
IP 20
2881
3.7
IP 20
2882
dards
Output current
IINV. [A]
9.1
12
16
24
32.0
37.5
(3 x 380-480V)
14.5
19.2
25.6
38.4
51.2
60.0
26.0
SINV. [KVA]
6.3
8.3
11.1
16.6
22.2
PM,N [kW]
4.0
5.5
7.5
11.0
15.0
18.5
PM,N [HP]
5.0
7.5
10.0
15.0
20.0
25.0
4/10
4/10
4/10
16/6
16/6
16/6
37.5
[mm2 /AWG]
1 )
tion, motor
Input current
8.1
10.6
14.9
24.0
32.0
(3 x 380-480 V)
IL,MAX(60s)[A]
IL,N [A]
13.0
17.0
23.8
38.4
51.2
60
[mm2 /AWG]
4/10
4/10
4/10
16/6
16/6
16/6
20/20
25/25
25/25
50/50
50/50
50/50
1 )
tion, power
Max. pre-fuses
[A]/UL
2 )
[A]
Efficiency3 )
[%]
96
96
96
97
97
97
[W]
200
275
372
412
562
693
load
Weight
Enclosure4
[kg]
3.7
6.0
6.0
18.5
18.5
18.5
type
IP20
IP20
IP20
IP20/
IP20/
IP20/
NEMA 1
NEMA 1
NEMA 1
1. American Wire Gauge. Max. cable cross section is the largest cable cross section that can be
attached to the terminals. Always observe national
and local regulations.
2. Type gG pre-fuses must be used. If you want to
maintain UL/cUL you must use pre-fuses of the
type Bussmann KTN-R 200 V, KTS-R 500 V or
Ferraz Shawmut, type ATMR (max. 30A). The
fuses must be placed for protection in a circuit that
is capable of supplying a maximum of 100,000
amps RMS (symmetrical), 500 V maximum.
28
3. Measured using a 25 m screened/armoured motor cable with a rated load and rated frequency.
4. IP20 is standard for VLT 2805-2875, whereas
NEMA 1 is an option.
Type
Motor coil
RFI 1B filter
RFI 1B/LC filter 4 A
RFI 1B/LC filter 9.1 A
NEMA 1 terminal cover
NEMA 1 terminal cover
NEMA 1 terminal cover
LCP2 control unit
Cable for LCP2 control unit
DeviceNet cable
LCP2 remote-mounting kit
LOP (Local Operation Pad)
VLT Software Dialog
Description
The motor coil module can be used for VLT 2803-2875
The RFI 1B filter module can be used for VLT 2803-2875
The RFI 1B/LC filter 4 A can be used for VLT 2803-2805
200-240 V and VLT 2805-2815 380-400 V
RFI 1B/LC filter 9.1 A can be used for VLT 2807-2815
200-240 V and VLT 2822-2840 380-400 V
VLT 2803-2815 200-240 V, VLT 2805-2815 380-480 V
VLT 2822 200-240 V, VLT 2822-2840 380-480 V
VLT 2840 200-240 V, VLT 2855-2875 380-480 V
LCP2 for programming the frequency converter
Cable from LCP2 to frequency converter
Cable for DeviceNet connection
Kit for remote-mounting of LCP2 (incl. 3 m cable,
excl. LCP2)
LOP can be used for setting the reference
and start/stop via the control terminals.
CD-ROM version*
Ordering no.
195N3110
195N3103
195N3100
195N3101
195N1900
195N1901
195N1902
175N0131
175Z0929
195N3113
175Z0850
175N0128
175Z0953
Data sheet
29
30