GENERATOR OUTPUT / NEUTRAL POINT

CUBICLE

GT13E2 Functional Description

&

Operation Manual

en C-1036-0710-12543 fdom 0 Generator output / Neutral Point Cubicle


2010-07-23 GT13E2 Functional Description & Operation Manual
Revision History
Revision Content of Change Document Pages
total : 10

2 C-1036-0710-12543 fdom 0 en Generator Output / Neutral Point Cubicle


2010-07-23 GT13E2 Functional Description & Operation Manual
Contents
Controls & Switchgear

Contents
1 Safety information.......................................................................................... 5
1.1 Definition of symbols ....................................................................... 5
1.2 General safety information .............................................................. 6

2 General Arrangement..................................................................................... 8

3 Function and design of the system .............................................................. 8


3.1 Name of Components of NP Cubicle............................................... 9

4 Principle of Operation.................................................................................. 10

Figures
Fig. 1 : Side View of Generator Output / Neutral Point Cubicle......................... 8
Fig. 2 : Front View of Generator Output / Neutral Point Cubicle looking from
neutral side....................................................................................................... 9

Generator Output / Neutral Point Cubicle C-1036-0710-12543 fdom 0 en 3


GT13E2 Functional Description & Operation Manual 2010-07-23
Additional Documents

Additional Documents

Document No Document Name


C-1036-0510-11989 General arrangement drawing.
C-1036-0510-11989/12 Bill of material
C-1036-0510-11993 Control schematic diagram
C-1036-0510-11991 Standard component drawings of Generator output /
Neutral point cubicle.
C-1036-0710-12543mm Maintenance Manual

4 C-1036-0710-12543 fdom 0 en Generator Output / Neutral Point Cubicle


2010-07-23 GT13E2 Functional Description & Operation Manual
Safety information 1
Controls & Switchgear Definition of symbols 1.1

1 SAFETY INFORMATION
1.1 Definition of symbols
DANGER indicates an imminently hazardous situation which, if not avoided, will
result in death or serious injury. This signal word is to be limited to the most extreme
situations.

DANGER
Type/Source of Hazard
Hazard consequences
à Steps to avoid the hazard.

WARNING indicates a potentially hazardous situation which, if not avoided, could


result in death or serious injury.

WARNING
Type/Source of Hazard
Hazard consequences
à Steps to avoid the hazard.

CAUTION indicates a potentially hazardous situation which, if not avoided, may


result in minor or moderate injury. It may also be used to alert against unsafe
practices.

CAUTION
Type/Source of hazard
Hazard consequences
à Steps to avoid the hazard.

DAMAGE information not relevant for the safety of personnel but pointing out
possible damage to the machine is depicted as shown below.

CAUTION
Information pointing out possible damages to the Machine.

Generator Output / Neutral Point Cubicle C-1036-0710-12543 fdom 0 en 5


GT13E2 Functional Description & Operation Manual 2010-07-23
1 Safety information
1 General safety information

1.2 General safety information


Adhere the following safety notes:

WARNING
High voltage/Electrical shock
Can result in serious injuries or death
à Don’t touch live parts of the electrical installation.
à Adhere also to safety markings on the equipment itself.

WARNING
WARNING
Hot surface of NP Cubicle (especially in the contact with enclosure or
busbar just after the shutdown the system)
Do not touch hot surface, Skin burns by touching hot parts.
à Before beginning to work on the NP Cubicle, make sure surface
temperature is below 40°C.

Intended use
à Do not operate the NP Cubicle beyond the intended use and the
intended operating conditions. Adhere to the performance data within
this O & M documentation set.
à Maintenance of the NP Cubicle must be done in accordance with this
O&M documentation set and according to state of the art technology.
à Rebuilding, alterations and additions must not be done without
agreement of C & S, especially if safety and functionality is concerned.
à Only use original spare parts or spare parts recommended by C & S.
à The NP Cubicle is designed for the intended power plant. Using the NP
Cubicle for another plant or another purpose shall only be done in
accordance with C & S.
In case of non-compliance with the requirements mentioned above C & S shall
not be responsible for insufficient functioning, system malfunction or other
damages. Any non-compliance will also void or abate C & S ‘s responsibility
under the warranty provisions.

6 C-1036-0710-12543 fdom 0 en Generator Output / Neutral Point Cubicle


2010-07-23 GT13E2 Functional Description & Operation Manual
Safety information 1
Controls & Switchgear General safety information 1.2

Operating and maintenance personnel


Only qualified and authorized personnel may operate the
NP Cubicle equipment or do any maintenance work on it.
The personnel must have read the O&M documentation
set. The safety information in this documentation set is of
special importance.
The personnel must be familiar with and follow the national
relevant stipulations and accident prevention regulations.
The personnel must immediately notify the responsible
safety inspector of any irregularities or safety risks.

Generator Output / Neutral Point Cubicle C-1036-0710-12543 fdom 0 en 7


GT13E2 Functional Description & Operation Manual 2010-07-23
2 General Arrangement
3 General safety information

2 GENERAL ARRANGEMENT
The Generator output / Neutral point cubicle (NPC) comprises of three phase
terminals and three neutral terminals with the star formation. It is also provided with
Current Transformer, Neutral grounding Resistor, Neutral Voltage Transformer,
Marshalling Box (Terminal box), Pamos® Sensor, flexibles, Seal off bushing and
insulator etc.

3 FUNCTION AND DESIGN OF THE SYSTEM


NPC is intended to house phase & neutral busbars that serve as interconnection
between the generator terminals and the isolated phase busduct. It also houses the
generator star point formation and necessary protection equipments like Current
Transformer, Neutral grounding Resistor, Neutral Voltage Transformer, Marshalling
Box (Terminal box), and Pamos® Sensor for Generator protection.
NPC is suitable to withstand short circuit force of 100kA(rms) for one second and
255kA (peak), This also suitable to impulse withstand voltage for 125kV(peak).

Fig. 1 : Side View of Generator Output / Neutral Point Cubicle

8 C-1036-0710-12543 fdom 0 en Generator Output / Neutral Point Cubicle


2010-07-23 GT13E2 Functional Description & Operation Manual
0
Controls & Switchgear Name of Components of NP Cubicle 3.1

A1
E2

B4

S1

B8

Fig. 2 : Front View of Generator Output / Neutral Point Cubicle looking from neutral side

3.1 Name of Components of NP Cubicle


Pos. Description

A1 Pamos®

B1 Seal-Off Bushing

B2 Support Insulator

B3 Current Transforemr

B4 Braided Flexible (7200 Sq.Mm / PH.)

B5 Neutral Voltage Transformer

B6 Neutral Grounding Resistor

B7 Rubber Bellow

B8 Vibration Damper

Generator Output / Neutral Point Cubicle C-1036-0710-12543 fdom 0 en 9


GT13E2 Functional Description & Operation Manual 2010-07-23
0
4 Name of Components of NP Cubicle

B9 Earthing Braided Flexible

B10 LV Bushing

B11 Support Insulator for Y Phase Only

E1 NPC Enclosure

E2 Conductor Or Busbar

E3 Adaptor Box

E4 Marshalling Box (Terminal Box)

E5 Barrier

E6 EPDM Gasket

E7 Earth Link

E10 Canopy

S1 Terminal Support Structure

4 PRINCIPLE OF OPERATION
Generator output / Neutral Point Cubicle (NPC)is intended to house phase & neutral
busbars that serve as interconnection between the generator terminals and the
isolated phase busduct.
NPC is being a static electrical equipment, after commissioning this equipment and
connection between generator and Isolated phase busduct no operation required for
this equipment. Once generator will generate the power the power will go through
the NPC to Isolated phase busduct, transformer etc.

====xxx===